STIEBEL ELTRON HSBC 200, HSBC 200 S Operation And Installation

Page 1
BEDIENUNG UND INSTALLATION OPERATION AND INSTALLATION UTILISATION ET INSTALLATION BEDIENING EN INSTALLATIE USO E INSTALLAZIONE
 Integral-Speicher| Integral cylinder| Ballon intégral| Combiboiler| Caldaia integrale
Page 2
30 | HSBC www.stiebel-eltron.com
CONTENTS | SPECIAL INFORMATION
SPECIAL INFORMATION
- The appliance may be used by children over 8years of age and persons with reduced phys­ical, sensory or mental capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the ap­pliance or perform user maintenance unless they are supervised.
- The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power sup­ply by an isolator that disconnects all poles with at least 3mm contact separation.
- Observe all applicable national and regional reg­ulations and instructions.
- Observe minimum distances (see chapter "Instal­lation/ Preparations/ Installation site").
- Only a qualified contractor should carry out in­stallation, commissioning, maintenance and re­pair of the appliance.
DHW cylinder
- Drain the appliance as described in chapter "In­stallation/ Maintenance/ Draining the DHW cylinder".
- Observe the maximum permissible pressure (see chapter "Installation/ Specification/ Data table").
- The appliance is pressurised. During the heat-up process, expansion water will drip from the safety valve.
- Regularly activate the safety valve to prevent it from becoming blocked, e.g. by limescale deposits.
- The safety valve drainage aperture must remain open to atmosphere.
SPECIAL INFORMATION OPERATION
1. General information ��������������������������������������� 31
1.1 Relevant documents�������������������������������������������� 31
1.2 Safety instructions ����������������������������������������������31
1.3 Other symbols in this documentation ���������������������� 31
1.4 Information on the appliance �������������������������������� 31
1.5 Units of measurement ����������������������������������������� 31
2. Safety �������������������������������������������������������� 32
2.1 Intended use ����������������������������������������������������� 32
2.2 General safety instructions �����������������������������������32
2.3 Test symbols ����������������������������������������������������� 32
3. Appliance compatibility ����������������������������������� 32
4. Appliance description ������������������������������������� 32
5. Settings ����������������������������������������������������� 33
6. Cleaning, care and maintenance ������������������������� 33
7. Troubleshooting �������������������������������������������� 33
INSTALLATION
8. Safety �������������������������������������������������������� 34
8.1 General safety instructions �����������������������������������34
8.2 Instructions, standards and regulations ������������������� 34
9. Appliance description ������������������������������������� 34
9.1 Standard delivery ����������������������������������������������� 34
9.2 Accessories ������������������������������������������������������� 34
10. Preparations ������������������������������������������������ 34
10.1 Installation site �������������������������������������������������� 34
10.2 Transport and handling ���������������������������������������35
11. Installation �������������������������������������������������� 37
11.1 Positioning the appliance �������������������������������������37
11.2 Heating water connection and safety valve ���������������37
11.3 DHW connection and safety assembly ���������������������� 39
11.4 Filling the system ����������������������������������������������� 40
11.5 Venting the appliance ������������������������������������������ 41
12. Power supply ����������������������������������������������� 41
12.1 Electric emergency/booster heater and control voltage 42
12.2 Low voltage, BUS cable ���������������������������������������� 43
12.3 Sensor installation ����������������������������������������������44
12.4 Remote control �������������������������������������������������� 45
13. Commissioning ��������������������������������������������� 45
13.1 Checks before commissioning the heat pump manager 45
13.2 Commissioning the heat pump manager ������������������ 46
13.3 Appliance handover �������������������������������������������� 46
14. Appliance shutdown ��������������������������������������� 46
15. Maintenance ������������������������������������������������ 46
16. Specification ������������������������������������������������ 48
16.1 Dimensions and connections ��������������������������������� 48
16.2 Wiring diagram for HSBC 200 �������������������������������� 50
16.3 Wiring diagram for HSBC 200 S ������������������������������ 52
16.4 Data table �������������������������������������������������������� 55
16.5 Details on energy consumption ������������������������������ 56
GUARANTEE | ENVIRONMENT AND RECYCLING
Page 3
OPERATION
General information
www.stiebel-eltron.com HSBC | 31
ENGLISH
OPERATION
1. General information
The chapters "Special information" and "Operation" are intended for both users and qualified contractors.
The chapter "Installation" is intended for qualified contractors.
Note
Read these instructions carefully before using the appli­ance and retain them for future reference. Pass on the instructions to a new user if required.
1.1 Relevant documents
Operating and installation instructions for the WPM3
heat pump manager
Operating and installation instructions for the connected
heat pump
Operating and installation instructions for all other sys-
tem components
1.2 Safety instructions
1.2.1 Structure of safety instructions
!
KEYWORD Type of risk Here, possible consequences are listed that may result from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
Injury
Electrocution
Burns (burns, scalding)
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
injury or death.
WARNING Failure to observe this information may result in serious
injury or death.
CAUTION Failure to observe this information may result in non-seri-
ous or minor injury.
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
Material losses (appliance damage, consequential losses and environmen­tal pollution)
Appliance disposal
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
 These symbols show you the software menu level (in
this example level3).
1.4 Information on the appliance
Connections
Symbol Meaning
Inlet/ intake
Red arrow: Hot Blue arrow: Cold Green arrow: Neutral
Drain/ outlet
Red arrow: Hot Blue arrow: Cold Green arrow: Neutral
Domestic hot water
DHW circulation
Heat pump
Central heating
1.5 Units of measurement
Note
All measurements are given in mm unless stated oth­erwise.
!
!
Page 4
OPERATION
Safety
32 | HSBC www.stiebel-eltron.com
2. Safety
2.1 Intended use
This appliance is intended to be used for heating and cooling interiors (area cooling 18°C/ 23°C) and for DHW heating.
The appliance is intended for domestic use. It can be used safely by untrained persons. The appliance can also be used in non-do­mestic environments, e.g. in small businesses, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappro­priate. Observation of these instructions and of the instructions for any accessories used is also part of the correct use of this appliance.
2.2 General safety instructions
WARNING Burns There is a risk of scalding at outlet temperatures in ex­cess of 43 °C.
!
WARNING Injury The appliance may be used by children over 8years of age and persons with reduced physical, sensory or men­tal capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the ap­pliance or perform user maintenance unless they are supervised.
!
WARNING Injury For safety reasons, only operate the appliance with the front casing closed.
Note
The DHW cylinder is under mains pressure. During the heat-up process, expansion water will drip from the safe­ty valve.
If water continues to drip when heating is complet-
ed, please inform your qualified contractor.
2.3 Test symbols
See type plate on the appliance.
3. Appliance compatibility
The appliance can be operated in conjunction with the following air | water heat pumps:
- WPL 13 E, WPL 13 (S) basic
- WPL 10 AC (S)
- WPL 15-25AC (S), WPL 15-25 A (S)
- WPL 08-28 (S) Trend
4. Appliance description
The buffer cylinder and DHW cylinder with indirect coil are ar­ranged one above the other and can be separated for easier han­dling.
The appliance has a plastic jacket with foam insulation and is equipped with a removable front casing. The appliance is connect­ed hydraulically and electrically to the heat pump. All hydraulic connections are made at the top.
In addition to the DHW cylinder and the buffer cylinder, further system components are integrated:
- Heat pump manager
- Cylinder primary pump
- Highly efficient circulation pump for a heating circuit without mixer
- Multifunction assembly with safety valve and 3-way diverter valve
- Emergency/booster heater for mono energetic operation
DHW cylinder
The steel cylinder is coated on the inside with special direct enam­el and is equipped with a signal anode. The anode with consump­tion indicator protects the cylinder interior from corrosion.
The heating water heated by the heat pump is pumped through an indirect coil inside the DHW cylinder. The heat channelled through the indirect coil is thus transferred to the domestic hot water. The integral heat pump manager regulates the DHW heating to the required temperature.
Buffer cylinder
The steel cylinder provides hydraulic separation between the flow rates of heat pump and heating circuit. The heating water heated by the heat pump is transferred into the buffer cylinder by the cylinder charging pump. When a demand is issued, the integral heating circuit pump delivers the heating water to the heating circuit.
Heat pump manager (WPM)
The system is controlled by means of the integral heat pump man­ager.
The heat pump manager is suitable for the control of a direct heating circuit and a heating circuit with mixer.
You can set the times and temperatures for heating operation and heating DHW. Remote controls for controlling the direct heating circuit and the heating circuit with mixer are available as acces­sories.
For detailed information, see the enclosed operating and instal­lation instructions for the WPM3 heat pump manager.
Multifunction assembly (MFG)
The multifunction assembly switches between heating circuit and DHW heating.
Page 5
OPERATION
Settings
www.stiebel-eltron.com HSBC | 33
ENGLISH
5. Settings
!
Material losses
The system's active frost protection is not guaranteed if the power supply is interrupted.
Never interrupt the power supply even outside the
heating season.
Note
The heat pump manager has an automatic summer/win­ter changeover so you can leave the system switched on in summer.
The system is controlled by means of the integral heat pump manager. Please observe the heat pump manager operating and installation instructions.
OKMENU
D0000064711
6. Cleaning, care and maintenance
Have the electrical safety of the appliance and the function
of the safety assembly regularly checked by a qualified contractor.
Never use abrasive or corrosive cleaning agents. A damp
cloth is sufficient for cleaning the appliance.
Signal anode with consumption indicator
!
Material losses
If the consumption indicator changes colour from white to red, have the signal anode checked by a qualified con­tractor and if necessary replaced.
1 2
D0000055608
1 White = Anode OK 2 Red = Requires checking by qualified contractor
Scaling
Almost every type of water will deposit limescale at high tem­peratures. This settles inside the appliance and affects both the performance and service life. A qualified contractor who knows the local water quality will tell you when the next service is due.
Check the taps regularly. Limescale deposits at the tap out-
lets can be removed using commercially available descaling agents.
Regularly activate the safety valve to prevent it from becom-
ing blocked, e.g. by limescale deposits.
7. Troubleshooting
Problem Cause Remedy
The water does not heat up. The heating does not work.
There is no power.
Check the fuses/MCBs in your distribution board.
If you cannot remedy the fault, contact your qualified contractor. To facilitate and speed up your request, provide the number from the type plate (000000-0000-000000).
No.:
000000-0000-000000
Made in Germany
D0000056320
Page 6
INSTALLATION
Safety
34 | HSBC www.stiebel-eltron.com
INSTALLATION
8. Safety
Only a qualified contractor should carry out installation, commis­sioning, maintenance and repair of the appliance.
8.1 General safety instructions
We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the appliance are used.
8.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations and instructions.
9. Appliance description
9.1 Standard delivery
The following are delivered with the appliance:
- Operating and installation instructions for the WPM3 heat pump manager
- Outside temperature sensor AFS 2
- 4 adjustable feet
- Drain hose
9.2 Accessories
Required accessories
Safety assemblies and pressure reducing valves are available to suit the prevailing supply pressure. These type-tested safety assemblies protect the appliance against impermissible excess pressure.
Required for area cooling:
- Temperature sensor TF 6
- FEK remote control
Additional accessories
- Pump assembly for a heating circuit with mixer HSBC-HKM
- Remote control for heating operation
- High limit safety cut-out STB-FB
- Pressure hoses
- Water softening fitting HZEA
10. Preparations
10.1 Installation site
!
Material losses
Never install the appliance in wet rooms.
Install the appliance near the draw-off point in a dry room free from the risk of frost. To reduce line losses, keep the distance short between the appliance and the heat pump.
Ensure the floor has sufficient load-bearing capacity and evenness (for weight, see chapter "Specification/ Data table").
The room must not be subject to a risk of explosions arising from dust, gases or vapours.
If you are installing the appliance in a boiler room together with other heating equipment, ensure that the operation of other heat­ing equipment will not be impaired.
Minimum clearances
≥500 ≥100
≥100 ≥400
≥800
D0000055505
The minimum side clearances can be swapped between left and right.
Page 7
INSTALLATION
Preparations
www.stiebel-eltron.com HSBC | 35
ENGLISH
10.2 Transport and handling
!
Material losses
Store and transport the appliance at temperatures be­tween -20°C to +60°C.
Handling
Undo the 4screws from the non-returnable pallet.
D0000055519
Tilt the appliance and wind the 4adjustable feet into the
appliance.
Lift the appliance off the pallet. For a better hold during
transport, use the recessed grips on the underside and rear of the appliance.
If narrow doors or hallways hinder handling, you can separate the upper and lower sections of the appliance as described in the following chapters.
10.2.1 Removing/ fitting the front casing
Removing the front casing
D0000055619
Remove the screw at the top in the middle of the appliance.Unhook the front casing towards the top.
D0000055620
Detach the plug of the electronic assembly for operation and
the earth connection from the front fascia.
Fitting the front casing
Fit the front casing in reverse order.
10.2.2 Separating/ joining the appliance sections
Separating the appliance sections
D0000055689
1
Disconnect the push-fit connectors of the 4hydraulic connec-
tions. To do this, pull the spring clips fully out with a screw­driver. Pull the hydraulic connectors off downwards.
D0000055874
Pull out the sensor at the buffer cylinder.
Page 8
INSTALLATION
Preparations
36 | HSBC www.stiebel-eltron.com
D0000055685
Release the 4screws on the tabs at the front of the appliance.
D0000057295
Pull the upper section of the appliance towards the front.
D0000057294
1
1 Recessed grip
Tip the upper section of the appliance backwards. For a
better hold during transport, use the recessed grips on the underside and rear of the appliance.
D0000057298
Place the upper section of the appliance on a base to prevent
damage.
Joining appliance sections
Rejoin the appliance sections in reverse order. The positioning aids and the dotted line marking provide assis-
tance when positioning and inserting the upper appliance section into the guide groove on the lower section:
D0000055687
1 2
4
3
5
1 Recessed grip 2 Guide pin 3 Dotted line (perforation in the panel) 4 Guide groove 5 Positioning aid
Page 9
INSTALLATION
Installation
www.stiebel-eltron.com HSBC | 37
ENGLISH
1
D0000057300
1 Dotted line (perforation in the panel)
Place the upper appliance section onto the lower appliance
section along the dotted line.
D0000055688
Slide the upper appliance section to the back until it is flush
with the lower appliance section. If the appliance sections are joined correctly, the final position is determined by the guide groove and guide pin.
Secure the tabs on the appliance front.Insert the sensor at the buffer cylinder.Connect the push-fit connectors of the 4hydraulic connec-
tions. Ensure that the spring clips click into place.
11. Installation
11.1 Positioning the appliance
When positioning the appliance, observe minimum clearanc-
es (see chapter "Preparations/ Installation site").
Use the adjustable feet to compensate for any unevenness in
the floor.
11.2 Heating water connection and safety valve
11.2.1 Safety instructions
!
Material losses
The heating system to which the appliance is connected must be installed by a qualified contractor in accord­ance with the water installation drawings in the technical guides.
!
Material losses
When fitting additional shut-off valves, install a further safety valve in an accessible location on the heat gen­erator itself or in the flow line in close proximity to the heat generator. There must be no shut-off valve between the heat gen­erator and the safety valve.
Oxygen diffusion
!
Material losses
Avoid open vented heating systems and underfloor heat­ing systems with plastic pipes which are permeable to oxygen.
In underfloor heating systems with plastic pipes that are per­meable to oxygen and in open vented heating systems, oxygen diffusion may lead to corrosion on the steel components of the heating system (e.g.on the indirect coil of the DHW cylinder, on buffer cylinders, steel radiators or steel pipes).
!
Material losses
The products of corrosion (e.g.rusty sludge) can set­tle in the heating system components, which may re­sult in a lower output or fault shutdowns due to reduced cross-sections.
Page 10
INSTALLATION
Installation
38 | HSBC www.stiebel-eltron.com
Supply lines
The maximum permissible line length between the appli-
ance and the heat pump will vary, depending on the version of the heating system (pressure drop). As a standard value, assume a maximum line length of 10m and a pipe diameter of 22-28mm.
Protect the flow and return lines against frost with sufficient
thermal insulation.
Also protect all supply lines/cables against humidity, damage
and UV radiation by means of a conduit.
Pressure hoses against structure-borne sound transmission: The appliance and the heat pump are connected to each other
hydraulically via pipes carrying heating water. To reduce the trans-
mission of structure-borne sound on the water side, connect the appliance to the heat pump with pressure hoses (not required for WPL 15-25 A).
Pressure differential: If the available external pressure difference is exceeded, the pres-
sure drop in the heating system could result in a reduced heating output.
When sizing the pipes, ensure that the available external
pressure differential is not exceeded (see chapter "Specifica­tion/ Data table").
When calculating the pressure drop, take account of the flow
and return lines and the pressure drop of the heat pump. The pressure drop must be covered by the available pressure differential.
11.2.2 Fitting the pump assembly (accessory) if required
To extend the appliance with a heating circuit with mixer, you can install pump assembly HSBC-HKM (available as accessory).
- Insulated connection pipes
- Pre-fitted contact thermostat
- Heating circuit pump
- 3-way mixer with servomotor
- 2 plastic fixing aids
- Supplement, HSBC-HKM installation and electrical connection
- Operating and installation instructions for the heating circuit pump
D0000056342
1
2
4
3
1 Dummy plug 2 Union nut (mixed heating return connection) 3 Plastic fixing aid 4 Tee (mixed heating flow connection)
Replace the dummy plugs with the enclosed plastic fixing
aids at the mixed heating flow and return connections.
Remove the union nut at the mixed heating return
connection.
Remove the tee at the mixed heating flow connection of the
buffer cylinder.
Fit the pump assembly connection pipes.
Observe the parameter settings in menu "SETTINGS/ HEATING/ HEATING CIRCUIT 2" in the enclosed operating and installation instructions for the heat pump manager.
Page 11
INSTALLATION
Installation
www.stiebel-eltron.com HSBC | 39
ENGLISH
11.2.3 Connection
Installation example:
1
2
D0000055506
1 Pipes carrying heating water 2 Pressure hose (available as accessory)
Thoroughly flush the pipes before connecting the heat pump.
Foreign bodies (e.g. welding pearls, rust, sand, sealant, etc.) can impair the operational reliability of the heat pump.
Install the heating water pipes (see chapter "Specification/
Dimensions and connections").
Safety valve
1
3
2
D0000055520
1 Drain hose 2 Fasteners (not part of the standard delivery) 3 Drain (not part of the standard delivery)
Size the drain hose so that water can drain off unimpeded
when the safety valve is fully opened.
Ensure that the safety valve drain hose is open to the outside.Lay the safety valve drain hose with a constant fall to the
drain.
Secure the drain hose to prevent any hose movement while
water is discharged.
11.3 DHW connection and safety assembly
11.3.1 Safety instructions
!
Material losses
The maximum permissible pressure must not be exceed­ed (see chapter "Specification/ Data table").
!
Material losses
Operate the appliance only with pressure-tested taps.
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved materials.
!
Material losses
A safety valve is required.
DHW line, DHW circulation line
Stainless steel, copper and plastic are approved materials.
11.3.2 Installing the DHW circulation line, if applicable
A DHW circulation line with external DHW circulation pump can be fitted to the DHW circulation connection (see chapter "Specification / Dimensions and connections").
Remove the sealing cap from the DHW circulation connection
(see chapter "Specification / Dimensions and connections").
Connect the DHW circulation line.
D0000060804
Open the shut-off valve for the DHW circulation.
Page 12
INSTALLATION
Installation
40 | HSBC www.stiebel-eltron.com
11.3.3 DHW connection and safety assembly
Flush the pipes thoroughly.Install the DHW outlet line and the cold water inlet line (see
chapter "Specification/ Dimensions and connections").
Install a type-tested safety valve in the cold water inlet line.
Please note that, depending on the supply pressure, you may also need a pressure reducing valve.
Size the drain pipe so that water can drain off unimpeded
when the safety valve is fully opened.
The safety valve drainage aperture must remain open to
atmosphere.
Install the safety valve drain pipe with a constant fall to the
drain.
11.4 Filling the system
Heating circuit water quality
Carry out a fill water analysis before filling the system. This anal­ysis may, for example, be requested by the relevant water supply utility.
To avoid damage as a result of scaling, it may be necessary to soften or desalinate the fill water. The fill water limits specified in chapter "Specification/ Data table" must always be observed.
Recheck these limits 8-12weeks after commissioning and
during the annual system service.
Note
With a conductivity >1000μS/cm, desalination treatment is recommended in order to avoid corrosion.
Note
If you treat the fill water with inhibitors or additives, the same limits apply as for desalination.
Note
Suitable appliances for water softening, as well as for filling and flushing heating systems, can be obtained via trade suppliers.
!
Material losses
Never switch on the power before filling the system.
11.4.1 Filling the heating system
In the delivered condition, the 3-way diverter valve of the mul­tifunction assembly is in its centre position, so that the heating circuit and the heat exchanger for DHW heating are filled evenly. When power is switched on, the 3-way diverter valve automatically switches to heating mode.
To fill or drain the system later, you must first place the 3-way diverter valve into its centre position.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
DIAGNOSIS
RELAY TEST SYSTEM  DRAIN HYD
D0000055788
Fill the heating system via the drain valve.Vent the pipework.
11.4.2 DHW cylinder filling
Fill the DHW cylinder via the cold water connection.Open all downstream draw-off valves until the appliance is
full and the pipework is free of air.
Adjust the flow rate. For this, observe the maximum permis-
sible flow rate with a fully opened tap (see chapter "Specifi­cation/ Data table"). If necessary reduce the flow rate at the butterfly valve of the safety assembly.
Carry out a tightness check.Check the safety valve.
Page 13
INSTALLATION
Power supply
www.stiebel-eltron.com HSBC | 41
ENGLISH
11.5 Venting the appliance
To ventilate, temporarily open the quick-action air vent valve
in the multifunction assembly.
D0000055606
21
1 PCB 2 Quick-action air vent valve
!
Material losses
The air vent in the knurled cap of the quick-action air vent valve must not point towards the multifunction as­sembly PCB.
Turn the air vent in the direction shown in the fol-
lowing diagram.
D0000055605
!
Material losses
Close the quick-action air vent valve again after venting.
12. Power supply
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations. Before any work on the appliance, disconnect all poles from the power supply.
WARNING Electrocution Only use a permanent connection to the power supply. Ensure the appliance can be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation. This requirement can be met with contactors, circuit breakers, fuses/MCBs, etc.
!
Material losses
Provide separate fuses for the two power circuits of the appliance and the control unit.
!
Material losses
Provide separate fuses/MCBs for the two power circuits, i.e. for the compressor and the electricemergency/boost­er heater circuits.
!
Material losses
Observe the type plate. The specified voltage must match the mains voltage.
Note
You must have permission to connect the appliance from the relevant power supply utility.
The terminal box of the appliance is located behind the front casing (see chapter "Preparations/ Transport and handling/ Removing/ fitting the front casing").
D0000055594
Route all power cables and sensor leads into the appliance
through the cable entry.
Connect the power cables and sensor leads as detailed
below.
Page 14
INSTALLATION
Power supply
42 | HSBC www.stiebel-eltron.com
Install cables with the following cross-sections in accordance with the respective fuse rating:
MCB/fuse rating
Assignment Cable cross-section
B 16 A
Electric emergency/ booster heater (DHC) Three-phase
2.5mm²
1.5mm² with only two live wires, rout­ing according to applicable regulations
B 16 A
Electric emergency/ booster heater (DHC) 1 phase
2.5mm²
1.5mm² when routing a multi-core cable on a wall or in an electrical con­duit on a wall
B 16 A Control 1.5 mm²
12.1 Electric emergency/booster heater and control voltage
Appliance function
Effect of the electric emergency/booster heater
Mono energetic operation
If the heat pump undershoots the dual mode point, the electric emergency/booster heater safeguards both the heating operation and the delivery of high DHW temper­atures.
Emergency mode Should the heat pump suffer a fault that prevents its con-
tinued operation, the heating output will be covered by the electric emergency/booster heater.
HSBC 200: Electrical connection three-phase
D0000055646
X3 Electric emergency/booster heater (DHC)
Connected load Terminal assignment
2.9 kW PE N L1
5.9 kW PE N L2 L1
8.8 kW PE N L3 L2 L1
Connect the electrical emergency/booster heater with the
desired rating as detailed in the table.
HSBC 200 S: Electrical connection single phase
D0000056876
X3 Electric emergency/booster heater (DHC)
Connected load
Cable cross-sec­tion
Terminal assignment
2.9 kW 2.5mm² PE N L
5.9 kW
2.5mm² PE N L
2.5mm² PE N L
Connect the cables for the electrical emergency/booster
heater with the desired rating as in the table.
Control voltage
!
Material losses
Only connect energy efficient circulation pumps ap-
proved by us to the pump connections.
X4 Terminals, external control
EVU Enable signal 2WE Heat source 2 (floating contact) 2WE Heat source 2 (floating contact) Kue/Solar Output, cooling/ solar circuit pump
Zirk/
2WE WW
DHW circulation pump (floating contact, function availa­ble as optional extension)/ heat source 2 for DHW (floating contact)
Page 15
INSTALLATION
Power supply
www.stiebel-eltron.com HSBC | 43
ENGLISH
12.2 Low voltage, BUS cable
D0000055645
X2.1 Terminals, external low voltage
T(Puf) Temperature sensor, buffer cylinder (function part of
the standard delivery)
T(WW) Temperature sensor, DHW (function part of the stand-
ard delivery)
T(Kue/WW) For cooling: flow sensor/
For solar connection: lower DHW sensor
T(2WE) Temperature sensor heat source 2
X2.2 Terminals, external low voltage
T(KOLL) Collector sensor
T(A) Outside temperature sensor (function part of the
standard delivery)
T(MK) Mixer circuit temperature sensor (function available as
optional extension)
Fernb. FE 7 remote control (function available as optional
extension)
X5 CAN BUS terminal
+ (only in conjunction with FEK)
Ground L Low H High
Connecting BUS cables
!
Material losses
Bus cables, power cables and sensor leads must be in­stalled separately.
Install a J-Y (St) 2 x 2 x 0.8mm² cable as bus to the heat
pump.
A3
A2
A1
1 2 3 4
H L
T
+
1 2 3 4
X5
D0000056307
A1 WPM 3 heat pump manager A2 Programming unit A3 Heat pump
Page 16
INSTALLATION
Power supply
44 | HSBC www.stiebel-eltron.com
12.3 Sensor installation
12.3.1 Outside temperature sensor AFS 2
The outside temperature sensors have a significant influence on the function of your heating system. Therefore ensure that the outside temperature sensors are correctly positioned and well insulated.
26�03�21 �0052
- Install the outside temperature sensor on a north or north-eastern wall.
- Ensure that the outside temperature sensor is freely exposed to the elements but not placed in direct sunlight.
- Never mount the outside temperature sensor above win­dows, doors or air ducts.
- Observe the following minimum clearances: 2.5m above the ground and 1m to the side of windows and doors
Installation
Remove the cover.Secure the base with the screw supplied.Connect the cable. Connect the outside temperature sensor to
T(A) of terminalX2.2 of the appliance.
Replace the cover. The cover must audibly click into place.
12.3.2 Fitting the temperature sensor (accessory) for area cooling
Area cooling requires the fitting of a temperature sensor, available as an accessory.
Remove the front casing (see chapter "Preparations/ Trans-
port and handling/ Removing/ fitting the front casing").
D0000062830
Insert the temperature sensor into the sensor well "Sensor
heat pump cooling, optional".
Connect the temperature sensor to T(Kue/WW) of termi-
nalX2.1 of the appliance.
Page 17
INSTALLATION
Commissioning
www.stiebel-eltron.com HSBC | 45
ENGLISH
12.4 Remote control
12.4.1 FE 7 remote control
3
1
1 2 3
26�21�01�0008
With the FE 7 remote control you can adjust the set room tempera­ture for heating circuit1 or heating circuit2 by ± 5°C in automatic mode only. You can also select the operating mode. Connect the remote control to Fernb.1, Fernb.3 and Fernb.- at terminal X2.2 of the appliance.
12.4.2 FEK remote control
1
2 3 4
5
6
H
L
+
26�03�01�0094
With the FEK remote control you can select the operating mode and change the set room temperature for heating circuit 1 or heating circuit 2 by ± 5°C. Connect the remote control to H, L and + of terminal X5 of the appliance.
13. Commissioning
Our customer support can assist with commissioning, which is a chargeable service.
If the appliance is intended for commercial use, observe the rules of the relevant Health & Safety at Work Act during commissioning. For further details, check with your local authorising body (in Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump manager
!
Material losses
Observe the maximum system temperature in underfloor heating systems.
Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
Check whether the outside temperature sensor is correctly
placed and connected.
Check whether the power supply is connected correctly.Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
High limit safety cut-out
Note
At temperatures below –15°C the high limit safety cut-out may respond. The appliance may be subjected to these temperatures during storage or transport.
Check whether the high limit safety cut-out has tripped.
1
D0000055607
1 High limit safety cut-out reset button
Page 18
INSTALLATION
Appliance shutdown
46 | HSBC www.stiebel-eltron.com
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in accordance with the operating and installation instructions for the heat pump manager.
Note
For DHW mode, ensure that the PARALLEL OPERATION option is set in the heat pump manager. With this setting the primary pump is also active in DHW mode.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SETTINGS
Value
DHW  STANDARD SETTING  DHW MODE PARALLEL OPERA-
TION
Note
On appliances with a single phase connection, set the heat pump manager as follows for calculating the amount of heat.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SETTINGS
Value
HEATING  ELECTRIC REHEATING  NUMBER OF STAGES 2
Area cooling setting
!
Material losses
Condensation caused by the temperature falling below the dew point can lead to material losses. HSBC is there­fore exclusively approved for area cooling.
Adjusting the heat pump manager settings for area cooling:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SETTINGS
Value
COOLING  COOLING ON  STANDARD SETTING  COOLING CAPACITY system specific  ACTIVE COOLING  AREA COOLING ON  SET FLOW TEMPERATURE system specific  FLOW TEMP HYSTERESIS system specific  SET ROOM TEMPERATURE system specific
13.3 Appliance handover
Explain the appliance function to users and familiarise them
with its operation.
Make users aware of potential dangers.Hand over these instructions.
14. Appliance shutdown
!
Material losses
Observe the temperature application limits and the min­imum circulation volume on the heat consumer side (see chapter "Specification/ Data table").
!
Material losses
Drain the system when there is a risk of frost and the heat pump is completely switched off (see chapter "Mainte­nance/ Draining the DHW cylinder").
If you take the system out of use, set the heat pump manager
to standby so that the safety functions that protect the appli­ance (e.g. frost protection) remain active.
15. Maintenance
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations.
WARNING Electrocution Before any work on the appliance, disconnect all poles of the appliance from the power supply.
Draining the buffer cylinder
D0000055788
Drain the buffer cylinder via the drain valve.
Page 19
INSTALLATION
Maintenance
www.stiebel-eltron.com HSBC | 47
ENGLISH
Draining the DHW cylinder
CAUTION Burns Hot water may escape during draining.
Close the shut-off valve in the cold water inlet line.Open the hot water taps on all draw-off points.
D0000055604
Drain the buffer cylinder via the drain valve.
Draining the DHW cylinder
!
Material losses
Never use descaling pumps or descaling agents to clean the cylinder.
Clean the appliance through the inspection flange.
For the torque of the flange screws, see chapter "Specification/ Dimensions and connections".
Replacing the signal anode
Replace the signal anode if it becomes depleted.
Page 20
INSTALLATION
Specication
48 | HSBC www.stiebel-eltron.com
16. Specification
16.1 Dimensions and connections
16.1.1 HSBC 200 | HSBC 200 S
1844
10-20
1908
871
94
680
340
170
255
340
425
510
595
85
577
639
1158
1328
c10
d01
c01
e02
d02
c06e01
b01
c12
233
D0000055503
HSBC 200 HSBC 200 S
b01 Cable entry c01 Cold water inlet Diameter mm 22 22 c06 DHW outlet Diameter mm 22 22 c10 DHW circulation Diameter mm 12 12 c12 Safety valve drain d01 Heat pump flow Diameter mm 28 28 d02 Heat pump return Diameter mm 28 28 e01 Heating flow Diameter mm 22 22 e02 Heating return Diameter mm 22 22
Page 21
INSTALLATION
Specication
www.stiebel-eltron.com HSBC | 49
ENGLISH
Other dimensions and connections
h09
i18
h16
i01
h53
D0000060246
HSBC
200
HSBC
200 S
h09 Sensor heat pump
cooling, optional
Diameter mm 9.5 9.5
h16 Sensor DHW Diameter mm 9.5 9.5 h53 Sensor heating Diameter mm 9.5 9.5 i01 Flange
Diameter mm 140 140 Pitch circle diameter mm 120 120
Screws M 10 M 10 Torque Nm 55 55 i18 Protective anode Female thread G 1 1/4 G 1 1/4
16.1.2 HSBC-HKM accessories
10-20
1908
622
85
170
e31
e30
D0000056347
HSBC-HKM
e30 Heating flow, mixed Diameter mm 22 e31 Heating return, mixed Diameter mm 22
Page 22
INSTALLATION
Specication
50 | HSBC www.stiebel-eltron.com
16.2 Wiring diagram for HSBC 200
XD02
DHC (MFG)
L3 L2
L1
AA07
(MFG)
AA08
(Netzteil)
AA01
(WPM3)
X11
X12
X13
X14
X15
X20
X21
X22
Yonos Para 7,5
Steuerspannung
MA14
M 1~
X71
X72
X70
X29
2 (N)
ws (PWM)
br (GND)
1 (L)
N
5 4
2 1
3
1 2
1 2
1 2 3
2 1
1 2 3 4
1 2 3 4 5 6 7 8 9
10
10
9 8 7 6 5 4 3 2 1
4 3 2
1
KF20
KF21
321 3 2 1
X30 X31 X31 X31
“+”
H
H
L
L
“+”
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
L H
1
2
313
XD03
XE03
L’
2.WE
2.WE
N
XD20
XD05
1
2
3
4 5 6 7 8
9
1
1
3
4
L
Yonos Para 7,5
MA10
M 1~
N
XD01
2 N
2
3
4
12 22 32
11 3121
BT55
<T
AA07
KF20
KF21
KF22
1
3
3
1
3
1
EB01
MFG
X59
1
2N 3
2
5
N
1
4 5 6
3
2
L
L
N
Zirk. / 2. WE WW
KUE / Solar
EVU
N
XD11
“+”
MISCHER
MKP
1
9
4
5
8
3
6
7
2
N
L
Z
L
A
L
XE03
Steuerspannung
H
4 123
L
“+”
BT06
BT20
10
N
L
HKP
L
N
L
BUS
Netz
L1
1
HK-STB
1
2
10
11
Page 23
INSTALLATION
Specication
www.stiebel-eltron.com HSBC | 51
ENGLISH
AA07
(MFG)
X11
X12
X13
X14
X15
KleinspannungXD04.1
MA15 BP10 BF01
M 1~
M 1~
X71
X72
X70
X69
X68
X67
PWM
GND
X66 X65 X63 X62 X61 X60
1 2
1 2
1 2 3
1 2 3 4
1 2 3 4 5 6 7 8 9
10
4 3 2
1
1
2
3 4
5
6
KF20
KF21
KF22
321 3 2 1
2 1
6 5
4 3
3
3
2
2
1
1
1
4
4
4
4
3
2
1
2 1
5 4
3 2 1
5 4
2 1
2 1 2 1
2 1
3 2 1
“+”
p
OUT
+5V
GND
Hz
T2
T1
+5V
OUT
GND
H
H
L
L
“+”
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
L H
1
2
313
PT 1000
X27
AA06
4
3
2
1
1 = H 2 = L 3 = 4 = +12V
XD05
1
2
3
4 5 6 7 8 9
1
2
3
4 5 6 7 8 9
“+”
“+”
“+”
“+”“+”“+”
“+”
“-”“-” “-”“-”“-” “-”
“-”
“-” 1
3
T (Puer)
T (WW )
T (KUE)
T (2.WE)
T (KOLL)
T (A)
T (MK)
Fernb.
XD04.2
H
4 123
L
“+”
X64
T (WW )
BT06
BT20
BUS
BT02
BT01
D0000055681
Page 24
INSTALLATION
Specication
52 | HSBC www.stiebel-eltron.com
16.3 Wiring diagram for HSBC 200 S
XD02
DHC (MFG)
L N
L
AA07
(MFG)
AA08
(Netzteil)
AA01
(WPM3)
X11
X12
X13
X14
X15
X20
X21
X22
Yonos Para 7,5
Steuerspannung
MA14
M 1~
X71
X72
X70
X29
2 (N)
ws (PWM)
br (GND)
1 (L)
N
5 4
2 1
3
1 2
1 2
1 2 3
2 1
1 2 3 4
1 2 3 4 5 6 7 8 9
10
10
9 8 7 6 5 4 3 2 1
4 3 2
1
KF20
KF21
321 3 2 1
X30 X31 X31 X31
“+”
H
H
L
L
“+”
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
L H
1
2
313
XD03
XE03
L’
2.WE
2.WE
N
XD20
XD05
1
2
3
4 5 6 7 8
9
1
1
3
4
L
Yonos Para 7,5
MA10
M
1~
N
XD01
2
N
2
3
4
12 22 32
11 3121
BT55
<T
AA07
KF20
KF21
KF22
1
3
3
1
3
1
EB01
MFG
X59
1
2N 3
2
5
N
1
4 5 6
3
2
L
L
N
Zirk. / 2. WE WW
KUE / Solar
EVU
N
XD11
“+”
MISCHER
MKP
1
9
4
5
8
3
6
7
2
N
L
Z
L
A
L
XE03
Steuerspannung
H
4 123
L
“+”
BT06
BT20
10
N
L
HKP
L
N
L
BUS
Netz
10
11
1
STB-HK
2
L1
1
Page 25
INSTALLATION
Specication
www.stiebel-eltron.com HSBC | 53
ENGLISH
AA07
(MFG)
X11
X12
X13
X14
X15
KleinspannungXD04.1
MA15 BP10 BF01
M
1~
M
1~
X71
X72
X70
X69
X68
X67
PWM
GND
X66 X65 X63 X62 X61 X60
1 2
1 2
1 2 3
1 2 3 4
1 2 3 4 5 6 7 8 9
10
4 3 2
1
1
2
3 4
5
6
KF20
KF21
KF22
321 3 2 1
2 1
6 5
4 3
3
3
2
2
1
1
1
4
4
4
4
3
2
1
2 1
5 4
3 2 1
5 4
2 1
2 1 2 1
2 1
3 2 1
X30 X31 X31 X31
“+”
p
OUT
+5V
GND
Hz
T2
T1
+5V
OUT
GND
H
H
L
L
“+”
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
“+”
L H
1 2 3
1 43
L H
1
2
313
PT 1000
X27
AA06
4
3
2
1
1 = H 2 = L 3 = 4 = +12V
XD05
1
2
3
4 5 6 7 8 9
1
2
3
4 5 6 7 8 9
“+”
“+”
“+”
“+”“+”“+”
“+”
“-”“-” “-”“-”“-” “-”
“-”
“-” 1
3
T (Puer)
T (WW )
T (KUE)
T (2.WE)
T (KOLL)
T (A)
T (MK)
Fernb.
XD04.2
H
4 123
L
“+”
X64
T (WW )
BT06
BT20
BUS
BT02
BT01
D0000056875
Page 26
INSTALLATION
Specication
54 | HSBC www.stiebel-eltron.com
AA01 Heat pump manager WPM 3 AA06 Programming unit AA07 PCB, booster heater MFG AA08 Power supply unit, booster heater MFG BF01 Flow rate and temperature, heating circuit BP10 Pressure sensor, heating circuit BT01 Temperature sensor, heat pump flow BT02 Temperature sensor, heat pump return BT06 Temperature sensor, heat pump buffer cylinder (not for HSBB classic or TSBB eco) BT20 Temperature sensor, DHW cylinder BT55 High limit safety cut-out MFG (manual reset) EB01 Booster heater MFG (not for HSBB 200 S classic BE or HSBC 200 S BE) KF20 Relay, booster heater MFG KF21 Relay, booster heater MFG KF22 Relay, booster heater MFG MA10 Motor, heating circuit pump (not for HSBB classic or TSBB eco) MA14 Motor, buffer charging pump (PWM/1-10V) MA15 Motor, diverter valve, heating/DHW XD01 Power terminals XD02 Terminal, MFG power supply XD03 Control terminal XD04.1 Terminal, external low voltage XD04.2 Terminal, external low voltage XD05 Terminal, bus XD11 Control terminal XD20 Terminal, power supply connection, internal XE03 Earth terminal, control unit AA01-X 11 Connector, WPM temperature sensor AA01-X 12 Connector, WPM, heat source output temperature AA01-X 13 Connector, WPM mixer circuit temperature AA01-X 14 Connector, WPM remote control AA01-X 15 Connector, WPM bus AA01-X 20 Connector, WPM pumps and power supply utility AA01-X 21 Connector, WPM mixer control AA01-X 22 Connector, WPM control unit A A0 6-X 27 Terminal, programming unit A A0 8-X 29 Power supply, power supply unit A A0 8-X 30 CAN bus connection, power supply unit A A08 -X31 CAN bus connection, power supply unit AA07-X5 9 Terminal, MFG AA07-X6 0 Connector, temperature sensor, heat pump flow AA07-X61 Connector, temperature sensor, heat pump return AA07-X62 Not assigned – connector, temperature sensor, heat pump return AA07-X63 Not assigned – connector, temperature sensor, DHW cylinder, internal AA07-X6 4 Connector, temperature and flow rate, heating circuit AA07-X65 Not assigned AA07-X6 6 Rast 2.5 connector (heating system pressure) AA07-X67 Not assigned AA07-X6 8 Connector, switching, motor, diverter valve central heating / DHW AA07-X69 Not assigned AA07-X70 Connector, switching, pump, heating circuit PWM/1-10V AA07-X71 Not assigned AA07-X7 2 Connector, CAN bus
Page 27
INSTALLATION
Specication
www.stiebel-eltron.com HSBC | 55
ENGLISH
16.4 Data table
HSBC 200 HSBC 200 S
233510 234801 Hydraulic data Nominal capacity, DHW cylinder l 168 168 Nominal capacity, buffer cylinder l 100 100 Surface area, indirect coil 3.3 3.3 Capacity, indirect coil l 21 21 External available pressure differential, circulation pump / heat pump at 1.0 m³/h hPa 656 656 External available pressure differential, circulation pump / heat pump at 1.5 m³/h hPa 527 527 External available pressure differential, circulation pump / heat pump at 2.0 m³/h hPa 210 210 External available pressure differential, circulation pump / heating circuit 1 at 1.0 m³/h hPa 725 725 External available pressure differential, circulation pump / heating circuit 1 at 1.5 m³/h hPa 663 663 External available pressure differential, circulation pump / heating circuit 1 at hPa 444 444 External available pressure differential, circulation pump / heating circuit 2 (optional) at 1.0 m³/h hPa 665 665 External available pressure differential, circulation pump / heating circuit 2 (optional) at 1.5 m³/h hPa 518 518 External available pressure differential, circulation pump / heating circuit 2 (optional) at 2.0 m³/h hPa 189 189 Application limits Max. permissible pressure, DHW cylinder MPa 1.0 1.0 Test pressure, DHW cylinder MPa 1.5 1.5 Max. flow rate l/min 25 25 Max. permissible pressure, buffer cylinder MPa 0.3 0.3 Test pressure, buffer cylinder MPa 0.45 0.45 Max. permissible temperature °C 95 95 Water quality requirements Water hardness °dH ≤3 ≤3 pH value (with aluminium compounds) 8.0-8.5 8.0-8.5 pH value (without aluminium compounds) 8.0-10.0 8.0-10.0 Conductivity (softening) μS/cm <1000 <1000 Conductivity (desalination) μS/cm 20-100 20-100 Chloride mg/l <30 <30 Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 Power consumption Power consumption, emergency/booster heater kW 8.8 5.9 Max. power consumption, charging pump W 72 72 Max. power consumption, circulation pump on the heating side W 72 72 Energy data Standby energy consumption/24 h at 65°C kWh 1.6 1.6 Energy efficiency class C C Electrical data Rated voltage, control unit V 230 230 Control unit phases 1/N/PE 1/N/PE Control unit fuse/MCB A 1 x B 16 1 x B 16 Rated voltage, emergency/booster heater V 400 230 Emergency/booster heater phases 3/N/PE 2/N/PE MCB/fuse protection, emergency/booster heater A 3 x B 16 2 x B 16 Frequency Hz 50 50 Versions IP rating IP20 IP20 Dimensions Height mm 1896 1896 Width mm 680 680 Depth mm 871 871 Height when tilted mm 2035 2035 Weights Weight, full kg 471 471 Weight, empty kg 203 203
Page 28
INSTALLATION
Specication
56 | HSBC www.stiebel-eltron.com
Guarantee
The guarantee conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only grant­ed if the subsidiary has issued its own terms of guarantee. No other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products. This will not aect warranties issued by any importers.
Environment and recycling
We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations.
16.5 Details on energy consumption
The product data complies with EU regulations relating to the Directive on the ecodesign of energy related products (ErP).
HSBC 200 HSBC 200 S
233510 234801 Manufacturer STIEBEL ELTRON STIEBEL ELTRON Energy efficiency class C C Standby losses W 65 65 Cylinder capacity l 189 189
Page 29
Deutschland
STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Straße 33 | 37603 Holzminden Tel. 05531 702-0 | Fax 05531 702-480 info@stiebel-eltron.de www.stiebel-eltron.de
Verkauf Tel. 05531 702-110 | Fax 05531 702-95108 | info-center@stiebel-eltron.de Kundendienst Tel. 05531 702-111 | Fax 05531 702-95890 | kundendienst@stiebel-eltron.de Ersatzteilverkauf Tel. 05531 702-120 | Fax 05531 702-95335 | ersatzteile@stiebel-eltron.de
Irrtum und technische Änderungen vorbehalten! | Subject to errors and technical changes! | Sous réserve d‘erreurs et de modifications techniques! | Onder voorbehoud van ver
g
issingen en technische wijzigingen! |
Salvo error o modificación técnica! | Excepto erro ou alteração técnica | Zastrzeżone zmian
y
techniczne i ewentualne błędy | Omyly a technické změny jsou vyhrazeny! | A muszaki változtatások és tévedések jogát fenntartjuk! |
Отсутствие ошибок не гарантируется. Возможны технические изменения.
| Chyby a
technické zmeny sú vyhradené! Stand 9147
Australia
STIEBEL ELTRON Australia Pty. Ltd. 6 Prohasky Street | Port Melbourne VIC 3207 Tel. 03 9645-1833 | Fax 03 9645-4366 info@stiebel.com.au www.stiebel.com.au
Austria
STIEBEL ELTRON Ges.m.b.H. Gewerbegebiet Neubau-Nord Margaritenstraße 4 A | 4063 Hörsching Tel. 07221 74600-0 | Fax 07221 74600-42 info@stiebel-eltron.at www.stiebel-eltron.at
Belgium
STIEBEL ELTRON bvba/sprl 't Hofveld 6 - D1 | 1702 Groot-Bijgaarden Tel. 02 42322-22 | Fax 02 42322-12 info@stiebel-eltron.be www.stiebel-eltron.be
China
STIEBEL ELTRON (Guangzhou) Electric Appliance Co., Ltd. Rm 102, F1, Yingbin-Yihao Mansion, No. 1 Yingbin Road Panyu District | 511431 Guangzhou Tel. 020 39162209 | Fax 020 39162203 info@stiebeleltron.cn www.stiebeleltron.cn
Czech Republic
STIEBEL ELTRON spol. s r.o. K Hájům 946 | 155 00 Praha 5 - Stodůlky Tel. 251116-111 | Fax 235512-122 info@stiebel-eltron.cz www.stiebel-eltron.cz
Finland
STIEBEL ELTRON OY Kapinakuja 1 | 04600 Mäntsälä Tel. 020 720-9988 info@stiebel-eltron.fi www.stiebel-eltron.fi
France
STIEBEL ELTRON SAS 7-9, rue des Selliers B.P 85107 | 57073 Metz-Cédex 3 Tel. 0387 7438-88 | Fax 0387 7468-26 info@stiebel-eltron.fr www.stiebel-eltron.fr
Hungary
STIEBEL ELTRON Kft. Gyár u. 2 | 2040 Budaörs Tel. 01 250-6055 | Fax 01 368-8097 info@stiebel-eltron.hu www.stiebel-eltron.hu
Japan
NIHON STIEBEL Co. Ltd. Kowa Kawasaki Nishiguchi Building 8F 66-2 Horikawa-Cho Saiwai-Ku | 212-0013 Kawasaki Tel. 044 540-3200 | Fax 044 540-3210 info@nihonstiebel.co.jp www.nihonstiebel.co.jp
Netherlands
STIEBEL ELTRON Nederland B.V. Daviottenweg 36 | 5222 BH 's-Hertogenbosch Tel. 073 623-0000 | Fax 073 623-1141 info@stiebel-eltron.nl www.stiebel-eltron.nl
Poland
STIEBEL ELTRON Polska Sp. z O.O. ul. Działkowa 2 | 02-234 Warszawa Tel. 022 60920-30 | Fax 022 60920-29 biuro@stiebel-eltron.pl www.stiebel-eltron.pl
Russia
STIEBEL ELTRON LLC RUSSIA Urzhumskaya street 4, building 2 | 129343 Moscow Tel. 0495 7753889 | Fax 0495 7753887 info@stiebel-eltron.ru www.stiebel-eltron.ru
Slovakia
TATRAMAT - ohrievače vody s.r.o. Hlavná 1 | 058 01 Poprad Tel. 052 7127-125 | Fax 052 7127-148 info@stiebel-eltron.sk www.stiebel-eltron.sk
Switzerland
STIEBEL ELTRON AG Industrie West Gass 8 | 5242 Lupfig Tel. 056 4640-500 | Fax 056 4640-501 info@stiebel-eltron.ch www.stiebel-eltron.ch
Thailand
STIEBEL ELTRON Asia Ltd. 469 Moo 2 Tambol Klong-Jik Amphur Bangpa-In | 13160 Ayutthaya Tel. 035 220088 | Fax 035 221188 info@stiebeleltronasia.com www.stiebeleltronasia.com
United Kingdom and Ireland
STIEBEL ELTRON UK Ltd. Unit 12 Stadium Court Stadium Road | CH62 3RP Bromborough Tel. 0151 346-2300 | Fax 0151 334-2913 info@stiebel-eltron.co.uk www.stiebel-eltron.co.uk
United States of America
STIEBEL ELTRON, Inc. 17 West Street | 01088 West Hatfield MA Tel. 0413 247-3380 | Fax 0413 247-3369 info@stiebel-eltron-usa.com www.stiebel-eltron-usa.com
A 319204-39883-9238
4<AMHCMO=bjcaeg>
Loading...