16.4 Energy consumption data _____________________________________ 22
16.5 Data table ________________________________________________________ 22
GUARANTEE
ENVIRONMENT AND RECYCLING
SPECIAL INFORMATION
- The appliance may be used by children over
8years of age and persons with reduced physical, sensory or mental capabilities or a lack of
experience and expertise, provided that they are
supervised or they have been instructed on how
to use the appliance safely and have understood
the potential risks. Children must never play with
the appliance. Cleaning and user maintenance
must not be carried out by children without
supervision.
- The connection to the power supply must be in
the form of a permanent connection. Ensure the
appliance can be separated from the power supply by an isolator that disconnects all poles with
at least 3mm contact separation.
- Observe all applicable national and regional regulations and instructions.
- Observe minimum distances (see chapter “Installation/ Preparations/ Installation site”).
- Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance.
DHW cylinder
- Drain the appliance as described in chapter
“Installation/ Maintenance/ Draining the DHW
cylinder”.
- Observe the maximum permissible pressure (see
chapter “Installation/ Specification/ Data table”).
- The DHW cylinder is under supply pressure. If no
diaphragm expansion vessel is installed, expansion water will drip from the safety valve during
heat-up.
- Regularly activate the safety valve to prevent
it from becoming blocked, e.g. by limescale
deposits.
- The safety valve drain aperture must remain open
to atmosphere.
2 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 3
OPERATION
General information
OPERATION
1. General information
The chapters “Special information” and “Operation” are intended
for appliance users and qualified contractors.
The chapter “Installation” is intended for qualified contractors.
Note
Read these instructions carefully before using the appliance and retain them for future reference.
Pass on these instructions to a new user if required.
1.1 Relevant documents
Operating and installation instructions for the WPM heat
pump manager
Operating and installation instructions for the connected
heat pump
Operating and installation instructions for all other sys-
tem components
1.2 Safety instructions
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
SymbolMeaning
!
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
These symbols show you the software menu level (in
this example level3).
Material losses
(appliance damage, consequential losses and environmental pollution)
Appliance disposal
1.4 Information on the appliance
Connections
SymbolMeaning
Inlet/ intake
1.2.1 Structure of safety instructions
KEYWORD Type of risk
!
Here, possible consequences are listed that may result
from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
SymbolType of risk
!
1.2.3 Keywords
KEYWORDMeaning
DANGER Failure to observe this information will result in serious
WARNING Failure to observe this information may result in serious
CAUTION Failure to observe this information may result in non-seri-
Injury
Electrocution
Burns
(burns, scalding)
injury or death.
injury or death.
ous or minor injury.
Drain/ outlet
Domestic hot water
DHW circulation
Heat pump
Heating
1.5 Units of measurement
Note
All measurements are given in mm unless stated otherwise.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 3
Page 4
OPERATION
Safety
2. Safety
2.1 Intended use
The appliance is used for heating and seasonal cooling of rooms
and for DHW heating. For sub dew point cooling, CDT 180 condensate pump and condensate pan accessories must be used. With
the CDT 180 accessories, cooling rooms is only permissible with
monitoring of the dew point. Sub dew point cooling is only ever
permissible on a seasonal basis with a subsequent heating period.
The appliance is intended for domestic use. It can be used safely
by untrained persons. The appliance can also be used in non-domestic environments, e.g.in small businesses, as long as it is
used in the same way.
Any other use beyond that described shall be deemed inappropriate. Observation of these instructions and of the instructions
for any accessories used is also part of the correct use of this
appliance.
2.2 General safety instructions
WARNING Burns
There is a risk of scalding at outlet temperatures in excess of 43°C.
WARNING Injury
!
The appliance may be used by children over 8 years of
age and persons with reduced physical, sensory or mental capabilities or a lack of experience and expertise,
provided that they are supervised or they have been
instructed on how to use the appliance safely and have
understood the potential risks. Children must never play
with the appliance. Cleaning and user maintenance must
not be carried out by children without supervision.
WARNING Injury
!
For safety reasons, only operate the appliance with the
front casing closed.
Note
The DHW cylinder is under supply pressure. If no diaphragm expansion vessel is installed, expansion water
will drip from the safety valve during heat-up.
If water continues to drip when heating is complet-
ed, please inform your qualified contractor.
3. Appliance compatibility
The appliance can be operated in conjunction with the following
air source heat pumps:
- WPL-A 05/07 HK 230 Premium
- WPL 07-17 ACS classic
- HPA-O 05.1/07.1 CS Premium
- HPA-O 3-8 CS Plus
4. Appliance description
The appliance comprises a hydraulic module and an integral DHW
cylinder and is equipped with a removable front casing. The appliance is connected hydraulically and electrically to the heat pump.
In addition to the DHW cylinder, the following system components
are integrated:
- Heat pump manager
- Cylinder charging pump/ heating circuit pump
- Multifunction assembly with safety valve, 3-way diverter
valve and emergency/booster heater for monoenergetic
operation
DHW cylinder
The steel cylinder is equipped with special directly applied enamel
coating on the inside and a sacrificial anode. The sacrificial anode
protects the cylinder interior from corrosion.
The heating water heated by the heat pump is pumped through an
indirect coil inside the DHW cylinder. The heat channelled through
the indirect coil is thus transferred to the domestic hot water. The
integral heat pump manager regulates the DHW heating to the
required temperature.
Heat pump manager (WPM)
The system is controlled by means of the integral heat pump manager.
The heat pump manager is suitable for the control of a direct
heating circuit and a heating circuit with mixer.
You can set the times and temperatures for heating operation and
heating DHW. Remote controls for controlling the heating circuit
are available as accessories.
For detailed information, see the enclosed operating and installation instructions for the WPMheat pump manager.
2.3 Test symbols
See type plate on the appliance.
4 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Multifunction assembly (MFG)
3-way diverter valve: The multifunction assembly switches between heating circuit and DHW heating.
Safety valve: When the pressure is high, the safety valve opens to
relieve the pressure in the system.
Air vent valve: Components are vented through air vent valves,
e.g. pipes or indirect coil.
Page 5
OPERATION
Settings
Emergency/booster heater: in standard mode, the emergency/
booster heater can support the heat pump in monoenergetic
mode below the dual mode point. Depending on the setting and
connected heat pump, the emergency/booster heater can also be
used to back up DHW heating or in pasteurisation mode. In the
event of a heat pump malfunction, the emergency/booster heater
can temporarily ensure DHW heating and the heating of rooms.
5. Settings
Material losses
!
The system‘s active frost protection is not guaranteed if
the power supply is interrupted.
Never interrupt the power supply even outside the
heating season.
Note
The heat pump manager has an automatic summer/winter changeover so you can leave the system switched on
in summer.
The system is controlled by means of the integral heat pump
manager. Please observe the heat pump manager operating and
installation instructions.
6. Cleaning, care and maintenance
Have the electrical safety of the appliance and the function
of the safety assembly regularly checked by a qualified
contractor.
Have the sacrificial anode checked by a qualified contractor
after the first two years of use. The qualified contractor will
then determine the intervals at which the sacrificial anode
should be checked.
Never use abrasive or corrosive cleaning agents. A damp
cloth is sufficient for cleaning the unit.
7. Troubleshooting
ProblemCauseRemedy
The water does not heat
up. The heating does not
work.
Observe the information about troubleshooting in other applicable
documents (see chapter “Other applicable documents”).
If you cannot remedy the fault, contact your qualified contractor.
To facilitate and speed up your enquiry, please provide the serial
number from the type plate (000000-0000-000000).
There is no power.
Check the fuses/ MCBs in
your fuse box/ distribution board.
No.:000000-0000-000000
OKMENU
Made in Germany
D0000064711
D0000102715
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 5
Page 6
INSTALLATION
≥400
Safety
INSTALLATION
8. Safety
Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance.
8.1 General safety instructions
We guarantee trouble-free function and operational reliability
only if original accessories and spare parts intended for the unit
are used.
8.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
9. Appliance description
9.1 Standard delivery
The following are delivered with the appliance:
- Operating and installation instructions for the WPM heat
pump manager
Install the appliance near the draw-off point in a dry room free
from the risk of frost. To reduce line losses, keep the distance short
between the appliance and the heat pump.
Ensure the floor has sufficient load bearing capacity and evenness
(for weight, see chapter “Specification/ Data table”).
The room must not be subject to a risk of explosions arising from
dust, gases or vapours.
If you are installing the appliance in a boiler room together with
other heating equipment, ensure that the operation of the other
heating equipment will not be impaired.
Minimum clearances
≥200
≥100≥100
9.2 Accessories
Required accessories
Safety assemblies and pressure reducing valves are available
to suit the prevailing supply pressure. These type-tested safety
assemblies protect the appliance against impermissible excess
pressure.
Required for area cooling:
- Pt1000 temperature sensor
- FET remote control
Additional accessories
- Remote control for heating operation
- High limit safety cut-out STB-FB
- Water softening fitting HZEA
- Segmented anode
- CDT 180 condensate pump and condensate pan (required for
continuous cooling without dew point monitoring)
6 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Minimum ceiling clearance: Without DHW circulation 200 mm,
with DHW circulation 400 mm.
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
≥800
D0000103271
Page 7
INSTALLATION
Installation
10.2 Transport and handling
Material losses
!
Store and transport the appliance at temperatures between -20°C and +60°C.
Note
Two people are required when installing the adjustable
feet and transporting the appliance.
Undo the 3screws on the non-returnable pallet.
Material losses
!
Never roll the appliance over the edge of the pallet.
Slide a pipe over one carrying strap.
Fold over the end of the carrying straps with the two holes
and insert an adjustable foot with washers into the carrying
strap, as shown in the figure.
Tilt the appliance.
Screw the adjustable foot with the carrying strap into one
of the threaded holes (shown in the figure) in the appliance
base.
Fit the second carrying strap likewise.
Screw an adjustable foot without a carrying strap into the
threaded hole in the appliance base.
1 Carrying straps
D0000102526
!
1
Material losses
Always carry the appliance by the carrying straps.
Never transport the appliance using a hoist.
During transportation, never subject the pipe connectors
to any strain.
Protect the appliance against heavy impact during transport.
1
1
D0000103273
Installing supplied carrying straps and adjustable feet
Lift the appliance off the pallet by the carrying straps.
After transportation, tuck the lower carrying straps under the
appliance. You can also cut off the upper and lower carrying
straps.
1
11. Installation
11.1 Positioning the appliance
2
3
4
When positioning the appliance, observe minimum clearanc-
es (see chapter “Preparations/ Installation site”).
Use the adjustable feet to compensate for any unevenness in
the floor.
D0000102527
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 7
Page 8
INSTALLATION
Installation
11.2 Removing/fitting the front casing
Removing the front casing
1
1 Front panel
Remove the screws on the left and right of the front panel.
Carefully pull the front panel forwards to remove it from
the appliance and store it securely so that it cannot tip over,
without putting strain on the cable connections.
AA01-X1.18
Material losses
!
When fitting additional shut-off valves, install a further
safety valve in an accessible location on the heat generator itself or in the flow line in close proximity to the
heat generator.
There must not be a shut-off valve between the heat generator and the safety valve.
Note
The use of non-return valves in the charging circuits between the heat generator and the buffer or DHW cylinder can impair the function of the integral multifunction
assembly (MFG) and lead to faults in the heating system.
Only use our standard hydraulic solutions for the
installation of the appliances.
D0000103275
Oxygen diffusion
Material losses
!
Avoid open vented heating systems and underfloor
heating systems with plastic pipes that are permeable
to oxygen.
In underfloor heating systems with plastic pipes that are permeable to oxygen and in open vented heating systems, oxygen
diffusion may lead to corrosion on the steel components of the
heating system (e.g. on the indirect coil of the DHW cylinder, on
buffer cylinders, steel radiators or steel pipes).
XE06
To be able to store the front panel at a distance from the ap-
pliance, loosen the cable tie, unplug the connector from the
electronic assembly for operation (AA01-X1.18) and the earth
(XE06) at the heat pump manager and store the front panel
securely so that it cannot tip over.
Fitting the front casing
Fit the front casing in reverse order. Take care to position the
connection lines correctly and not to pinch any cables.
11.3 Heating water connection and safety valve
11.3.1 Safety instructions
Material losses
!
The heating system to which the appliance is connected
must be installed by a qualified contractor in accordance with the water installation drawings in the technical
guides.
Material losses
!
The products of corrosion (e.g. rusty sludge) can settle in the heating system components, which may re-
D0000102755
Supply lines
Pressure differential
If the available external pressure difference is exceeded, the pressure drop in the heating system could result in a reduced heating
output.
sult in a lower output or fault shutdowns due to reduced
cross-sections.
The maximum permissible line length between the appli-
ance and the heat pump will vary, depending on the version
of the heating system (pressure drop). As a standard value,
assume a maximum line length of 10m and a pipe diameter
of 22mm.
Protect the flow and return lines against frost with sufficient
thermal insulation.
Also protect all supply lines against humidity, damage and
UV radiation by means of a conduit.
Connect the hydraulic connections with flat gaskets.
When sizing the pipes, ensure that the available external
pressure differential is not exceeded (see chapter “Specification/ Data table”).
When calculating the pressure drop, take account of the flow
and return lines and the pressure drop of the heat pump.
The pressure drop must be covered by the available pressure
differential.
8 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 9
INSTALLATION
Installation
11.3.2 Heating water connection
Installation example:
1
1 Pipes carrying heating water
Thoroughly flush the pipes before connecting the heat pump.
Foreign bodies (e.g. welding pearls, rust, sand, sealant, etc.)
can impair the operational reliability of the heat pump.
Install the heating water pipes (see chapter “Specification/
Dimensions and connections”).
11.4 DHW connection and safety assembly
11.4.1 Safety instructions
Material losses
!
The maximum permissible pressure must not be exceeded (see chapter “Specification/ Data table”).
Material losses
!
Operate the appliance only with pressure-tested taps.
Note
The use of non-return valves in the charging circuits between the heat generator and the buffer or DHW cylinder can impair the function of the integral multifunction
assembly (MFG) and lead to faults in the heating system.
Only use our standard hydraulic solutions for the
installation of the appliances.
D0000103276
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved
materials.
Material losses
!
A safety valve is required.
Safety valve drain hose
1
1 Safety valve drain hose
Unroll the safety valve drain hose connected to the multi-
function assembly.
On one of the lower prepared openings on the left or right,
remove just enough insulating material as necessary for the
drain hose, in order to minimise the exchange of air.
Route the drain hose through the prepared opening from the
appliance.
Route the drain hose with a constant fall to a drain.
Ensure that the drain hose is open to the outside.
Secure the drain hose above the drain to prevent any hose
movement in the event of water being discharged.
Material losses
!
Route the drain hose to a drain to enable water to drain
freely when the safety valve is open.
DHW line, DHW circulation line
Stainless steel, copper and plastic are approved materials.
11.4.2 Fitting the DHW circulation line (optional)
A DHW circulation line with external DHW circulation pump can
be fitted to the DHW circulation connection (see chapter “Specification/ Dimensions and connections”).
D0000103253
1
2
3
4
5
1 Union nut
2 Insulating sleeve
3 DHW circulation line
4 Gasket
5 “DHW circulation” connection
Remove the sealing cap from the DHW circulation connection
(see chapter “Specification/ Dimensions and connections”).
Connect the DHW circulation line with the gasket, the insulat-
ing bushing and the flat gasket union nut.
D0000103254
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 9
Page 10
INSTALLATION
Installation
11.4.3 DHW connection and safety assembly
Flush the pipes thoroughly.
Install the DHW outlet line and the cold water inlet line (see
chapter “Specification/ Dimensions and connections”). Connect the hydraulic connections.
Install a type-tested safety valve in the cold water supply
line. Please note that, depending on the supply pressure, you
may also need a pressure reducing valve.
Size the drain pipe so that water can drain off unimpeded
when the safety valve is fully opened.
The safety valve drain aperture must remain open to
atmosphere.
Install the safety valve drain pipe with a constant fall to the
drain.
11.5 Filling the system
Heating circuit water quality
Carry out a fill water analysis before filling the system. This analysis may, for example, be requested from the relevant water supply
utility.
To avoid damage as a result of scaling, it may be necessary to
soften or desalinate the fill water. The fill water limits specified
in chapter “Specification/ Data table” must always be observed.
Recheck these limits 8-12weeks after commissioning and
during the annual system service.
When power is switched on, the 3-way diverter valve automatically
switches to heating mode.
To fill or drain the system later, you must first place the 3-way
diverter valve into its centre position.
To set the heat pump manager:
With the MENU key, call up the main menu.
Select the menu or value and confirm with OK:
DIAGNOSIS
RELAY TEST SYSTEM
DRAIN HYD
D0000102722
Fill the heating system via the left-hand drain & fill valve.
Vent the pipework.
11.5.3 DHW cylinder filling
Material losses
!
Never switch on the power before filling the system.
Note
With a conductivity >1000μS/cm, desalination treatment
is recommended in order to avoid corrosion.
Note
If you treat the fill water with inhibitors or additives, the
same limits apply as for desalination.
Note
Suitable appliances for water softening, as well as for
filling and flushing heating systems, can be obtained via
trade suppliers.
11.5.1 Flushing out the hot water system
Before turning on the water supply, open all taps. Allow
the system to fill and flush out all flux and debris from the
installation.
11.5.2 Filling the heating system
Note
Fill the heating system exclusively via the left-hand drain
& fill valve.
Material losses
!
Some fluxes used to solder pipes and fittings need to be
flushed out with hot water.
Heat the cylinder to its normal operating tempera-
ture and flush all pipe work with hot water to ensure
all flux and debris is removed from the system.
Fill the DHW cylinder via the cold water connection in com-
pliance with the UK Water Supply (Water Fittings) Regulations 1999, Section 8 G24.
Open all downstream draw-off valves until the appliance is
full and the pipework is free of air.
Adjust the flow rate. For this, observe the maximum permis-
sible flow rate with a fully opened tap (see chapter “Specification/ Data table”). If necessary reduce the flow rate at the
butterfly valve of the safety assembly.
Carry out a tightness check.
Check the safety valve.
In the delivered condition, the 3-way diverter valve of the multifunction assembly is in its centre position, so that the heating
circuit and the heat exchanger for DHW heating are filled evenly.
10 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 11
INSTALLATION
Electrical connection
11.6 Venting the appliance
1
2
1
1 Air vent valve
2 PCB
Vent the pipework and indirect coil by pulling up the red cap
on the air vent valves.
Close the air vent valves after the venting process.
D0000103256
Material losses
!
Close the air vent valves again after venting.
12. Electrical connection
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with relevant regulations.
Before any work on the appliance, disconnect all
poles from the power supply.
WARNING Electrocution
The connection to the power supply must be in the form
of a permanent connection. Ensure the appliance can be
separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation.
This requirement can be met by using contactors, circuit
breakers, fuses/MCBs, etc.
Material losses
!
Provide separate fuses for the two power circuits of the
appliance and the control unit.
Material losses
!
Provide separate fuses/MCBs for the two power circuits,
i.e. for the compressor and the electricemergency/booster heater circuits.
Material losses
!
Observe the type plate. The specified voltage must match
the mains power supply.
Note
You must have permission to connect the appliance from
the relevant power supply utility.
1
1 Cable entry plug
Cut the 4 cable entry plugs only as much as required for the
cable diameter in order to minimise the exchange of air.
Route all power supply cables and sensor leads into the ap-
pliance through the cable entry from the left or right. From
the left, route the cables behind the terminal box to the
right-hand side. Lay the lines on the right-hand side through
the empty conduits and cable entry plugs.
Connect the power cables and sensor leads as detailed
below.
Install cables with the following cross-sections in accordance with
the respective fuse protection:
Fuse protection
B 16A
B 16A
B 16AControl unit1.5mm²
Assignment Cable cross-section
Electric emergency/
booster heater
(DHC)
Three-phase
Electric emergency/
booster heater
(DHC)
Single phase
2.5mm²
1.5mm² with only two live wires, routing according to applicable regulations
2.5mm²
1.5mm² when routing a multi-core
cable on a wall or in an electrical conduit on a wall
D0000103257
The terminal box of the appliance is located behind the front casing
(see chapter “Installation/ Removing/ fitting the front casing”).
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 11
Page 12
INSTALLATION
Electrical connection
12.1 Electric emergency/booster heater and control
voltage
Appliance
function
Mono energetic
operation
Emergency mode Should the heat pump suffer a fault that prevents its con-
HSBB180: Electrical connection three-phase
XD02Electric emergency/booster heater (DHC)
Connected loadTerminal assignment
2.9 kWPENL1
5.9 kWPEN L2L1
8.8 kWPENL3L2L1
Effect of the electric emergency/booster
heater
If the dual mode point is undershot, the electric emergency/booster heater safeguards both the heating operation
and the provision of high DHW temperatures.
tinued operation, the heating output will be covered by
the electric emergency/booster heater.
L1
317964-41782
L2
L3
N
XD02Electric emergency/booster heater (DHC)
Connected
load
2.9 kW2.5mm²PENL
5.9 kW
2.5mm²PENL
Cable
cross-section
2.5mm²PENL
Terminal assignment
Connect the electrical emergency/booster heater cables to
deliver the required rating as detailed in the table.
Control voltage
Material losses
!
Only connect energy efficient circulation pumps ap-
proved by us to the pump connections.
XD01.2Heat pump enable signal
EVU Enable signal, bus cable to the WPM screened with
strain relief in terminal.
Heat pump manager terminal assignment
WARNING Electrocution
Only components that operate with safety extra low
voltage (SELV) and that ensure secure separation from
D0000102543
the mains voltage supply may be connected to the low
voltage terminals of the appliance.
Connecting other components can make parts of the appliance and connected components live.
Only use components which have been approved by
us.
Connect the electrical emergency/booster heater with the
desired rating as detailed in the table.
HSBB180S: Electrical connection single phase
L1
317964-41782
317965-38886
L2
L3
N
N L N L
D0000071841
D0000102544
12 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 13
INSTALLATION
Electrical connection
Safety ex tra low voltage
X1.1
CAN A
X1.2
CAN B
X1.3 Signal
X1.4 Signal
X1.5 Signal
X1.6 Signal
X1.7 Signal
X1.8 Signal
X1.9 Signal
X1.10 Signal
X1.11 Signal
X1.12 Signal
X1.13 Signal
X1.14 Constant 12V
X1.15 Constant 12V
X1.16 Signal
X1.17 Signal
X1.18
CAN B
X1.19
CAN A
Mains power supply
X2.1
X2.2 L‘ (power supply
X2.3 L
X2.4 L
X2.5 L
X2.6 L
+
L
H
+
L
H
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Signal
Input
GND
Input
GND
Earth
Earth
+
L
H
+
L
H
L
L
N
PE
utility input)
L* (pumps L)
N
PE
N
PE
N
PE
N
PE
+
L
H
+
L
H
1 2Outside sensor
1 2Buffer sensor (heating circuit sensor 1)
1 2Flow sensor
1 2Heating circuit sensor 2
1 2Heating circuit sensor 3
1 2DHW cylinder sensor
1 2Source sensor
1 22nd heat generator (2.WE)
1 2Cooling flow
1 2DHW circulation sensor
1
2
3
+
IN
+
IN
1 2PWM output 1
1 2PWM output 2
+
L
H
+
L
H
L
L
N
L‘
L* (pumps L)
L
N
L
N
L
N
L
N
CAN (connection for heat pump and WPE heat
pump extension)
CAN (connection for FET remote control and
ISG Internet Service Gateway)
CAN (connection for heat pump and WPE heat
pump extension)
Power supply
L‘ (power supply utility input)
L* (pumps L)
Heating circuit pump 1
PE
Heating circuit pump 2
PE
Heating circuit pump 3
PE
Buffer charging pump 1
PE
Mains power supply
X2.7 L
X2.8 L
X2.9 L
X2.10 L
X2.11 L
X2.12 L
X2.13 L
X2.14
X2.15
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
Mixer OPEN
N
PE
Mixer CLOSE
Mixer OPEN
N
PE
Mixer CLOSE
L
N
L
N
L
N
L
N
L
N
L
N
L
N
5
N
6
5
N
6
PE
PE
PE
PE
PE
PE
PE
PE
PE
Buffer charging pump 2
DHW charging pump
Source pump/ defrost
Fault output
DHW circulation pump/ 2nd heat
source DHW
2ndheat source heating
Cooling
Not assigned
Not assigned
Note
For every appliance fault, output X2.10 issues a 230V
signal.
In the case of temporary faults, the output switches the
signal through for a specific time.
In the case of faults that result in a permanent appliance
shutdown, the output switches through permanently.
Accessories, STB-FB high limit safety cut-out for underfloor
heating systems (optional)
XD01.1
L1
N
2
1
3
2
4
Netz
L
1
EVU
XD01.2
L’
2
Remove the jumper at XD01.1 between L1 and 2.
Connect the STB-FB high limit safety cut-out to XD01.1 be-
tween L1 and 2.
D0000084472
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 13
Page 14
INSTALLATION
Commissioning
12.2 Sensor installation
12.2.1 Outside temperature sensor AFPT
The outside temperature sensors have a significant influence on
the function of your heating system. Therefore ensure that the
outside temperature sensors are correctly positioned and well
insulated.
- Install the outside temperature sensor on a north or
north-eastern wall.
- Ensure that the outside temperature sensor is freely exposed
to the elements but not placed in direct sunlight.
- Never mount the outside temperature sensor above windows, doors or air ducts.
- Observe the following minimum clearances: 2.5m above the
ground and 1m to the side of windows and doors
Installation
Remove the cover.
Secure the base with the screw supplied.
Connect the cable.
Connect the outside temperature sensor to AA01-X1.3.
Replace the cover. The cover must audibly click into place.
12.3 Remote control
Please observe the commissioning instructions for the heat
pump manager.
The FET remote control is required to record humidity in the case
of cooling via an area heating system.
13. Commissioning
Our customer support can assist with commissioning, which is a
chargeable service.
If the appliance is intended for commercial use, observe the rules
of the relevant Health & Safety at Work Act during commissioning.
For further details, check with your local authorising body (in
Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump
manager
Material losses
!
Observe the maximum system temperature in underfloor
heating systems.
Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
Check whether the outside temperature sensor is correctly
placed and connected.
Check whether the power supply is connected correctly.
Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
High limit safety cut-out
Note
At temperatures below –15°C the high limit safety cut-out
may respond. The appliance may be subjected to these
temperatures during storage or transport.
1
1 High limit safety cut-out reset button
Check whether the high limit safety cut-out has tripped.
If the high limit safety cut-out has triggered, reset it with the
reset button.
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in accordance with the heat pump manager operating and installation
instructions.
Note
For DHW mode, ensure that the PARALLEL OPERATION
option is set in the heat pump manager. With this setting,
the cylinder charging pump/ heating circuit pump is also
activated in DHW mode.
To set the heat pump manager:
With the MENU key, call up the main menu.
Select the menu or value and confirm with OK:
On appliances with a single phase connection, set the
heat pump manager as follows for calculating the amount
of heat.
To set the heat pump manager:
With the MENU key, call up the main menu.
Select the menu or value and confirm with OK:
SET TINGS
H EATI NG
ELECTRIC BOOSTER HEATER
NUMBER OF STAGES2
Value
Value
D0000103267
14 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 15
INSTALLATION
Shutting down the system
Cooling settings
Material losses
!
Condensation caused by the temperature falling below
the dew point can lead to material losses. The appliance
is therefore approved exclusively for area cooling.
For dew point independent cooling, additional accessories (CDT 180) are required to ensure that any condensate
is reliably drained away.
Observe the instructions for the heat pump manager.
Adjusting the heat pump manager settings for area cooling:
With the MENU key, call up the main menu.
Select the menu or value and confirm with OK:
SET TINGS
COOLING
COOLINGON
STANDARD SETTING
COOLING CAPACITYsystem specific
ACTIVE COOLING
AREA COOLINGON
SET FLOW TEMPERATUREsystem specific
FLOW TEMP HYSTERESISsystem specific
SET ROOM TEMPERATUREsystem specific
Value
15. Maintenance
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with relevant regulations.
WARNING Electrocution
Before any work on the appliance, disconnect all
poles of the appliance from the power supply.
Draining the DHW cylinder
CAUTION Burns
Hot water may escape during draining.
Close the shut-off valve in the cold water supply line.
Open the hot water taps on all draw-off points.
13.3 Appliance handover
Explain the appliance function to users and familiarise them
with how it works.
Make users aware of potential dangers.
Hand over these instructions.
14. Shutting down the system
Material losses
!
Observe the temperature application limits and the minimum circulation volume of the heat pump.
Material losses
!
Drain the system when there is a risk of frost and the heat
pump is completely switched off (see chapter “Maintenance/ Draining the DHW cylinder”).
If you take the system out of use, set the heat pump manager
to standby so that the safety functions that protect the appliance (e.g. frost protection) remain active.
D0000103378
Drain the DHW cylinder via the right-hand drain & fill valve.
Testing the sacrificial anode
Arrange for the sacrificial anode to be tested at least every
two years and replace immediately if it becomes depleted.
For this, observe the maximum transition resistance between
the sacrificial anode and the cylinder of 0.3Ω. If it is not
possible to insert the sacrificial anode from above, install a
segmented anode.
The intervals at which subsequent testing should be carried out
depends on the wear of the sacrificial anode.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 15
MA14Motor, buffer charging pump (PWM/1-10V)
MA15Motor, diverter valve, heating/DHW
KF20Relay, booster heater MFG
KF21Relay, booster heater MFG
KF22Relay, booster heater MFG
XD01.1Terminal, power supply
XD01.2Terminal, power-OFF contact
XD02Terminal, MFG power supply
XD13Terminal, condensate pump
XE01Power supply earth terminal
XE02Earth terminal MFG/DHC
XE05Earth stud, front panel
XE06Earth, front panel
AA 01-X1.1Connector, CAN A (heat pump connection)
AA 01-X1. 2Connector, CAN B (FET/ISG connection)
18 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 19
INSTALLATION
XE05
XE06
Specication
CAN A
CAN B
CAN B
CAN A
+
-
L
X1.1
H
+
L
H
1
2
X1.3X1.4X1.5X1.6X1.7X1.8X1.9X1.10X1.11
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
+
IN
+
IN
1
2
1
2
X1.17 X1.16 X1.15 X1.14 X1.13 X1.12X1.2
+
-
L
X1.18
H
+
L
X1.19
H
WH
4321
BN
GN
YE
+
L
H
T
321
KF20KF21KF22
EB01
X71 X72X70X69X68
321
PWM
GND
2
1
6
6
5
1~
1~
M
M
5
3 4
3 4
2
2
1
1
(MFG)
AA07
MA15
X67X66
1
4
OUT
2
3
p
BT06
+5V
1
4
GND
BP10
BT20
T2
T1
+5V
Hz
GND
OUT
BT08
T
T
BF01
BT02
BT01
4
3
2
1
WH
YE
BN
GN
AA06
X27
PT 1000
4
4
1 = H
2 = L
3 =
4 = +12V
2
3
2
3
43214321
12 22 32
BT55
<T
113121
X65X63X62X61X60
1 2 3 4 51 2 3 4 5
X64
3
1
3
KF22
KF21
1
2
1
2
1
2
1
2
1
3
KF20
1
AA07
X59
2N 3
1
MFG
1
1
GNBNYEWH
N
1
2
XD02
XE02
L3 L2
3
L1
5
4
D0000089904
AA 01-X1. 3Connector, outside temperature sensor
AA 01-X1.4Connector, buffer temperature sensor BT06 (not assigned)
AA 01-X1.5Connector, flow temperature sensor
AA 01-X1.6Connector, heating circuit temperature sensor 2
AA 01-X1.7Connector, heating circuit temperature sensor 3
AA 01-X1. 8Connector, DHW cylinder sensor BT20
AA 01-X1.9Connector, source sensor
AA01-X1.10 Connector, 2nd heat generator
AA 01-X1. 11 Connector, flow, cooling (not assigned)
AA 01-X1.12 Connector, DHW circulation sensor
AA 01-X1.13 Connector, remote control FE7
AA 01-X1.14 Connector, analogue input 0-10V
AA 01-X2.14 Connector, mixer, heating circuit 2 (X2.14.1 Mixer OPEN/X2.14.2
Mixer CLOSE)
AA01-X2.15 Connector, mixer, heating circuit 3
(X2.15.1 Mixer OPEN/X2.15.2 Mixer CLOSE)
AA 07-X60Connector, temperature sensor, heat pump flow BT01
AA 07-X61Connector, temperature sensor, heat pump return BT02
AA 07-X62Not assigned – connector, temperature sensor, heat pump return
AA 07-X63Not assigned – connector, temperature sensor, DHW cylinder,
internal
AA 07-X64Connector, temperature and flow rate, heating circuit, BF01
AA 07-X65Not assigned
AA 07-X66Rast 2.5 connector (heating system pressure) BP01
AA 07-X67Not assigned
AA 07-X68Connector, switching, motor, diverter valve central heating /
DHW
AA 07-X69Not assigned
AA 07-X70Connector, switching, pump, heating circuit PWM/1-10V
AA 07-X71Not assigned
AA 07-X72Connector, CAN bus
EB01-X59Terminal, MFG
AA 06-X27Terminal, programming unit
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 19
MA14Motor, buffer charging pump (PWM/1-10V)
MA15Motor, diverter valve, heating/DHW
KF20Relay, booster heater MFG
KF21Relay, booster heater MFG
KF22Relay, booster heater MFG
XD01.1Terminal, power supply
XD01.2Terminal, power-OFF contact
XD02Terminal, MFG power supply
XD13Terminal, condensate pump
XE01Power supply earth terminal
XE02Earth terminal MFG/DHC
XE05Earth stud, front panel
XE06Earth, front panel
AA 01-X1.1Connector, CAN A (heat pump connection)
AA 01-X1. 2Connector, CAN B (FET/ISG connection)
20 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 21
INSTALLATION
XE05XE06
Specication
CAN A
CAN B
CAN B
CAN A
+
-
L
X1.1
H
+
L
H
1
2
X1.3X1.4X1.5X1.6X1.7X1.8X1.9X1.10X1.11
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
+
IN
+
IN
1
2
1
2
X1.17 X1.16 X1.15 X1.14 X1.13 X1.12X1.2
+
-
L
X1.18
H
+
L
X1.19
H
WH
4321
BN
GN
YE
+
L
H
T
321
KF20KF21KF22
EB01
X71 X72X70X69X68
321
PWM
GND
2
1
6
6
5
1~
1~
M
M
5
3 4
3 4
2
2
1
1
AA07 (MFG)
MA15
X67X66
1
4
OUT
2
3
p
BT06
+5V
1
4
GND
BP10
BT20
T2
T1
+5V
Hz
GND
OUT
BT08
T
T
BF01
BT02
BT01
4
3
2
1
WH
YE
BN
GN
AA06
X27
PT 1000
4
4
1 = H
2 = L
3 =
4 = +12V
2
3
2
3
43214321
12 22 32
BT55
<T
113121
X65X63X62X61X60
1 2 3 4 51 2 3 4 5
X64
3
1
3
KF20
KF21
1
2
1
2
1
2
1
2
1
3
KF22
1
AA07
X59
LN N
L
MFG
1
1
GNBNYEWH
N
1
2
L N
3
L
5
4
XD02
XE02
D0000096750
AA 01-X1. 3Connector, outside temperature sensor
AA 01-X1.4Connector, buffer temperature sensor BT06 (not assigned)
AA 01-X1.5Connector, flow temperature sensor
AA 01-X1.6Connector, heating circuit temperature sensor 2
AA 01-X1.7Connector, heating circuit temperature sensor 3
AA 01-X1. 8Connector, DHW cylinder sensor BT20
AA 01-X1.9Connector, source sensor
AA01-X1.10 Connector, 2nd heat generator
AA 01-X1. 11 Connector, flow, cooling (not assigned)
AA 01-X1.12 Connector, DHW circulation sensor
AA 01-X1.13 Connector, remote control FE7
AA 01-X1.14 Connector, analogue input 0-10V
AA 01-X2.14 Connector, mixer, heating circuit 2 (X2.14.1 Mixer OPEN/X2.14.2
Mixer CLOSE)
AA01-X2.15 Connector, mixer, heating circuit 3
(X2.15.1 Mixer OPEN/X2.15.2 Mixer CLOSE)
AA 07-X60Connector, temperature sensor, heat pump flow BT01
AA 07-X61Connector, temperature sensor, heat pump return BT02
AA 07-X62Not assigned – connector, temperature sensor, heat pump return
AA 07-X63Not assigned – connector, temperature sensor, DHW cylinder,
internal
AA 07-X64Connector, temperature and flow rate, heating circuit, BF01
AA 07-X65Not assigned
AA 07-X66Rast 2.5 connector (heating system pressure) BP01
AA 07-X67Not assigned
AA 07-X68Connector, switching, motor, diverter valve central heating /
DHW
AA 07-X69Not assigned
AA 07-X70Connector, switching, pump, heating circuit PWM/1-10V
AA 07-X71Not assigned
AA 07-X72Connector, CAN bus
EB01-X59Terminal, MFG
AA 06-X27Terminal, programming unit
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 21
Page 22
INSTALLATION
Specication
16.4 Energy consumption data
Product datasheet: DHW cylinder to Regulation (EU) No 812/2013 (S.I. 2019 No. 539 / Programme 2)
HSBB 180 Plus (GB)HSBB 180 S Plus (GB)
202926203084
ManufacturerSTIEBEL ELTRONSTIEBEL ELTRON
Supplier‘s model identifierHSBB 180 Plus (GB)HSBB 180 S Plus (GB)
Energy efficiency classBB
Standby losses SW53.953.9
Cylinder capacity Vl195195
16.5 Data table
HSBB 180 Plus (GB)HSBB 180 S Plus (GB)
202926203084
Hydraulic data
Nominal capacity, DHW cylinderl178178
Surface area, heat exchanger m²1.591.59
Capacity, heat exchangerl1010
External available pressure differential at 1.0 m³/hhPa690690
External available pressure differential at 1.5 m³/hhPa461461
External available pressure differential at 2 m³/hhPa219219
Application limits
Max. permissible pressure, DHW cylinderMPa11
Test pressure, DHW cylinderMPa1.51.5
Max. flow ratel/min2525
Max. permissible temperature°C9595
Max. permissible temperature, primary side°C7575
Heating water quality requirements
Water hardness°dH≤3≤3
pH value (with aluminium fittings)8.0-8.58.0-8.5
pH value (without aluminium fittings)8.0-10.08.0-10.0
Conductivity (softening)μS/cm<1000<1000
Conductivity (desalination)μS/cm20-10020-1 00
Chloridemg/l<30<30
Oxygen 8-12 weeks after filling (softening)mg/l<0.02<0.02
Oxygen 8-12 weeks after filling (desalination)mg/l<0.1<0.1
Power consumption
Power consumption, emergency/booster heaterkW8.85.9
Max. power consumption, circulation pump, heating sideW6060
Energy data
Standby energy consumption/ 24 h at 65 °CkWh1.291.29
Energy efficiency classBB
Electrical data
Rated voltage, control unitV230230
Phases, control unit1/N/PE1/N/PE
Control unit fuse protectionA1 x B 161 x B 16
Rated voltage, emergency/booster heaterV400230
Phases, emergency/booster heater3/N/PE2/N/PE
Emergency/booster heater fuse protectionA3 x B 162 x B 16
FrequencyHz5050
Versions
IP ratingIP20IP20
Suitable forHeat pumpHeat pump
Dimensions
Heightmm12801280
Widthmm605605
Depthmm917917
Height when tiltedmm15001500
Weights
Weight, fullkg280280
Weight, emptykg100100
22 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 23
INSTALLATION | GUARANTEE | ENVIRONMENT AND RECYCLING
Specication
Further details
HSBB 180 Plus (GB)HSBB 180 S Plus (GB)
202926203084
Maximum height for installationm20002000
Guarantee
The guarantee conditions of our German companies do not
apply to appliances acquired outside of Germany. In countries
where our subsidiaries sell our products a guarantee can only
be issued by those subsidiaries. Such guarantee is only granted if the subsidiary has issued its own terms of guarantee. No
other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in
countries where we have no subsidiary to sell our products.
This will not aect warranties issued by any importers.
Environment and recycling
We would ask you to help protect the environment. After use,
dispose of the various materials in accordance with national
regulations.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 23
STIEBEL ELTRON (Tianjin) Electric Appliance
Co., Ltd.
Plant C3, XEDA International Industry City
Xiqing Economic Development Area
300385 Tianjin
Tel. 022 8396 2077 | Fax 022 8396 2075
info@stiebeleltron.cn
www.stiebeleltron.cn
Czech Republic
STIEBEL ELTRON spol. s r.o.
Dopraváků 749/3 | 184 00 Praha 8
Tel. 251116-111 | Fax 235512-122
info@stiebel-eltron.cz
www.stiebel-eltron.cz
STIEBEL ELTRON, Inc.
17 West Street | 01088 West Hatfield MA
Tel. 0413 247-3380 | Fax 0413 247-3369
info@stiebel-eltron-usa.com
www.stiebel-eltron-usa.com
4<AMHCMO=fafijb>
Irrtum und te chnische Änder ungen vorbehalten! | Subject to errors and technical changes! | Sous réser ve
d‘erreur s et de modifica tions techniques! | Onder voorbehoud van vergissingen en technische wijzigingen! |
Salvo error o modificación técnica! | Excepto erro ou alteração técnica | Zastr zeżone zmiany technic zne i
ewentualne błędy | Omyl y a technické změny jsou vyhrazeny! | A muszaki változt atások és tévedések jogát
fenntartjuk ! | Отсутс твие оши бок не гарантируетс я. Возмож ны техниче ские изме нения. | Chyb y a
technické zmeny sú vy hradené! Stand 9646
A 350589-43153-9655
B 350561-43150-9648
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.