Stiebel Eltron HSBB 180 Plus User guide

Page 1
OPERATION AND INSTALLAT ION
Integral cylinder
» HSBB 180 Plus (GB) » HSBB 180 S Plus (GB)
Page 2
CONTENTS | SPECIAL INFORMATION
SPECIAL INFORMATION OPERATION
1. General information �����������������������������������������3
1.1 Relevant documents_____________________________________________ 3
1.2 Safety instructions _______________________________________________ 3
1.3 Other symbols in this documentation _______________________ 3
1.4 Information on the appliance _________________________________ 3
1.5 Units of measurement __________________________________________ 3
2. Safety ���������������������������������������������������������� 4
2.1 Intended use ______________________________________________________ 4
2.2 General safety instructions ____________________________________ 4
2.3 Test symbols ______________________________________________________ 4
3. Appliance compatibility �������������������������������������4
4. Appliance description ���������������������������������������4
5. Settings �������������������������������������������������������5
6. Cleaning, care and maintenance ���������������������������5
7. Troubleshooting ����������������������������������������������5
INSTALLATION
8. Safety ���������������������������������������������������������� 6
8.1 General safety instructions ____________________________________ 6
8.2 Instructions, standards and regulations ____________________ 6
9. Appliance description ���������������������������������������6
9.1 Standard delivery ________________________________________________ 6
9.2 Accessories ________________________________________________________ 6
10. Preparation ���������������������������������������������������6
10.1 Installation site ___________________________________________________ 6
10.2 Transport and handling ________________________________________ 7
11. Installation ����������������������������������������������������7
11.1 Positioning the appliance ______________________________________ 7
11.2 Removing/fitting the front casing ____________________________ 8
11.3 Heating water connection and safety valve ________________ 8
11.4 DHW connection and safety assembly _______________________ 9
11.5 Filling the system _______________________________________________ 10
11.6 Venting the appliance __________________________________________ 11
12. Electrical connection ��������������������������������������� 11
12.1 Electric emergency/booster heater and control voltage 12
12.2 Sensor installation ______________________________________________ 14
12.3 Remote control __________________________________________________ 14
13. Commissioning ��������������������������������������������� 14
13.1 Checks before commissioning the heat pump manager 14
13.2 Commissioning the heat pump manager __________________ 14
13.3 Appliance handover ____________________________________________ 15
14. Shutting down the system �������������������������������� 15
15. Maintenance ������������������������������������������������ 15
16. Specification ������������������������������������������������ 16
16.1 Dimensions and connections _________________________________ 16
16.2 Hydraulic diagram ______________________________________________ 17
16.3 Wiring diagram _________________________________________________ 18
16.4 Energy consumption data _____________________________________ 22
16.5 Data table ________________________________________________________ 22
GUARANTEE ENVIRONMENT AND RECYCLING

SPECIAL INFORMATION

- The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power sup­ply by an isolator that disconnects all poles with at least 3mm contact separation.
- Observe all applicable national and regional reg­ulations and instructions.
- Observe minimum distances (see chapter “Instal­lation/ Preparations/ Installation site”).
- Only a qualified contractor should carry out in­stallation, commissioning, maintenance and re­pair of the appliance.
DHW cylinder
- Drain the appliance as described in chapter “Installation/ Maintenance/ Draining the DHW cylinder”.
- Observe the maximum permissible pressure (see chapter “Installation/ Specification/ Data table”).
- The DHW cylinder is under supply pressure. If no diaphragm expansion vessel is installed, expan­sion water will drip from the safety valve during heat-up.
- Regularly activate the safety valve to prevent it from becoming blocked, e.g. by limescale deposits.
- The safety valve drain aperture must remain open to atmosphere.
2 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 3
OPERATION

General information

OPERATION

1. General information
The chapters “Special information” and “Operation” are intended for appliance users and qualified contractors.
The chapter “Installation” is intended for qualified contractors.
Note
Read these instructions carefully before using the appli­ance and retain them for future reference. Pass on these instructions to a new user if required.

1.1 Relevant documents

Operating and installation instructions for the WPM heat
pump manager
Operating and installation instructions for the connected
heat pump
Operating and installation instructions for all other sys-
tem components

1.2 Safety instructions

1.3 Other symbols in this documentation

Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
!
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
 These symbols show you the software menu level (in
this example level3).
Material losses (appliance damage, consequential losses and environmen­tal pollution)
Appliance disposal

1.4 Information on the appliance

Connections
Symbol Meaning
Inlet/ intake
1.2.1 Structure of safety instructions
KEYWORD Type of risk
!
Here, possible consequences are listed that may result from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
!
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
WARNING Failure to observe this information may result in serious
CAUTION Failure to observe this information may result in non-seri-
Injury
Electrocution
Burns (burns, scalding)
injury or death.
injury or death.
ous or minor injury.
Drain/ outlet
Domestic hot water
DHW circulation
Heat pump
Heating

1.5 Units of measurement

Note
All measurements are given in mm unless stated oth­erwise.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 3
Page 4
OPERATION

Safety

2. Safety

2.1 Intended use

The appliance is used for heating and seasonal cooling of rooms and for DHW heating. For sub dew point cooling, CDT 180 conden­sate pump and condensate pan accessories must be used. With the CDT 180 accessories, cooling rooms is only permissible with monitoring of the dew point. Sub dew point cooling is only ever permissible on a seasonal basis with a subsequent heating period.
The appliance is intended for domestic use. It can be used safely by untrained persons. The appliance can also be used in non-do­mestic environments, e.g.in small businesses, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappro­priate. Observation of these instructions and of the instructions for any accessories used is also part of the correct use of this appliance.

2.2 General safety instructions

WARNING Burns There is a risk of scalding at outlet temperatures in ex­cess of 43°C.
WARNING Injury
!
The appliance may be used by children over 8 years of age and persons with reduced physical, sensory or men­tal capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Cleaning and user maintenance must not be carried out by children without supervision.
WARNING Injury
!
For safety reasons, only operate the appliance with the front casing closed.
Note
The DHW cylinder is under supply pressure. If no dia­phragm expansion vessel is installed, expansion water will drip from the safety valve during heat-up.
If water continues to drip when heating is complet-
ed, please inform your qualified contractor.

3. Appliance compatibility

The appliance can be operated in conjunction with the following air source heat pumps:
- WPL-A 05/07 HK 230 Premium
- WPL 07-17 ACS classic
- HPA-O 05.1/07.1 CS Premium
- HPA-O 3-8 CS Plus

4. Appliance description

The appliance comprises a hydraulic module and an integral DHW cylinder and is equipped with a removable front casing. The appli­ance is connected hydraulically and electrically to the heat pump.
In addition to the DHW cylinder, the following system components are integrated:
- Heat pump manager
- Cylinder charging pump/ heating circuit pump
- Multifunction assembly with safety valve, 3-way diverter valve and emergency/booster heater for monoenergetic operation
DHW cylinder
The steel cylinder is equipped with special directly applied enamel coating on the inside and a sacrificial anode. The sacrificial anode protects the cylinder interior from corrosion.
The heating water heated by the heat pump is pumped through an indirect coil inside the DHW cylinder. The heat channelled through the indirect coil is thus transferred to the domestic hot water. The integral heat pump manager regulates the DHW heating to the required temperature.
Heat pump manager (WPM)
The system is controlled by means of the integral heat pump man­ager.
The heat pump manager is suitable for the control of a direct heating circuit and a heating circuit with mixer.
You can set the times and temperatures for heating operation and heating DHW. Remote controls for controlling the heating circuit are available as accessories.
For detailed information, see the enclosed operating and instal­lation instructions for the WPMheat pump manager.

2.3 Test symbols

See type plate on the appliance.
4 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Multifunction assembly (MFG)
3-way diverter valve: The multifunction assembly switches be­tween heating circuit and DHW heating.
Safety valve: When the pressure is high, the safety valve opens to relieve the pressure in the system.
Air vent valve: Components are vented through air vent valves, e.g. pipes or indirect coil.
Page 5
OPERATION

Settings

Emergency/booster heater: in standard mode, the emergency/ booster heater can support the heat pump in monoenergetic mode below the dual mode point. Depending on the setting and connected heat pump, the emergency/booster heater can also be used to back up DHW heating or in pasteurisation mode. In the event of a heat pump malfunction, the emergency/booster heater can temporarily ensure DHW heating and the heating of rooms.
5. Settings
Material losses
!
The system‘s active frost protection is not guaranteed if the power supply is interrupted.
Never interrupt the power supply even outside the
heating season.
Note
The heat pump manager has an automatic summer/win­ter changeover so you can leave the system switched on in summer.
The system is controlled by means of the integral heat pump manager. Please observe the heat pump manager operating and installation instructions.

6. Cleaning, care and maintenance

Have the electrical safety of the appliance and the function
of the safety assembly regularly checked by a qualified contractor.
Have the sacrificial anode checked by a qualified contractor
after the first two years of use. The qualified contractor will then determine the intervals at which the sacrificial anode should be checked.
Never use abrasive or corrosive cleaning agents. A damp
cloth is sufficient for cleaning the unit.

7. Troubleshooting

Problem Cause Remedy
The water does not heat up. The heating does not work.
Observe the information about troubleshooting in other applicable documents (see chapter “Other applicable documents”).
If you cannot remedy the fault, contact your qualified contractor. To facilitate and speed up your enquiry, please provide the serial number from the type plate (000000-0000-000000).
There is no power.
Check the fuses/ MCBs in your fuse box/ distribu­tion board.
No.:000000-0000-000000
OKMENU
Made in Germany
D0000064711
D0000102715
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 5
Page 6
INSTALLATION
400

Safety

INSTALLATION

8. Safety
Only a qualified contractor should carry out installation, commis­sioning, maintenance and repair of the appliance.

8.1 General safety instructions

We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the unit are used.

8.2 Instructions, standards and regulations

Note
Observe all applicable national and regional regulations and instructions.

9. Appliance description

9.1 Standard delivery

The following are delivered with the appliance:
- Operating and installation instructions for the WPM heat pump manager
- Outside temperature sensor AFPT
- 3adjustable feet
- Drain hose
- DHW circulation line and flat gasket union nut
- Expansion vessel (incl. fastening material)
- Installation kit (pressure reducing valve, check valves, expan­sion relief valve, tundish)
10. Preparation
10.1 Installation site
Material losses
!
Never install the appliance in wet rooms.
Install the appliance near the draw-off point in a dry room free from the risk of frost. To reduce line losses, keep the distance short between the appliance and the heat pump.
Ensure the floor has sufficient load bearing capacity and evenness (for weight, see chapter “Specification/ Data table”).
The room must not be subject to a risk of explosions arising from dust, gases or vapours.
If you are installing the appliance in a boiler room together with other heating equipment, ensure that the operation of the other heating equipment will not be impaired.
Minimum clearances
≥200
≥100≥100

9.2 Accessories

Required accessories
Safety assemblies and pressure reducing valves are available to suit the prevailing supply pressure. These type-tested safety assemblies protect the appliance against impermissible excess pressure.
Required for area cooling:
- Pt1000 temperature sensor
- FET remote control
Additional accessories
- Remote control for heating operation
- High limit safety cut-out STB-FB
- Water softening fitting HZEA
- Segmented anode
- CDT 180 condensate pump and condensate pan (required for continuous cooling without dew point monitoring)
6 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Minimum ceiling clearance: Without DHW circulation 200 mm, with DHW circulation 400 mm.
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
≥800
D0000103271
Page 7
INSTALLATION

Installation

10.2 Transport and handling
Material losses
!
Store and transport the appliance at temperatures be­tween -20°C and +60°C.
Note
Two people are required when installing the adjustable feet and transporting the appliance.
Undo the 3screws on the non-returnable pallet.
Material losses
!
Never roll the appliance over the edge of the pallet.
Slide a pipe over one carrying strap.Fold over the end of the carrying straps with the two holes
and insert an adjustable foot with washers into the carrying strap, as shown in the figure.
Tilt the appliance.Screw the adjustable foot with the carrying strap into one
of the threaded holes (shown in the figure) in the appliance base.
Fit the second carrying strap likewise.Screw an adjustable foot without a carrying strap into the
threaded hole in the appliance base.
1 Carrying straps
D0000102526
!
1
Material losses
Always carry the appliance by the carrying straps. Never transport the appliance using a hoist. During transportation, never subject the pipe connectors to any strain. Protect the appliance against heavy impact during trans­port.
1
1
D0000103273
Installing supplied carrying straps and adjustable feet
5
1 Carrying strap 2 Washer 3 Adjustable foot 4 Pipe 5 Threaded hole
Lift the appliance off the pallet by the carrying straps.After transportation, tuck the lower carrying straps under the
appliance. You can also cut off the upper and lower carrying straps.
1
11. Installation
11.1 Positioning the appliance
2
3
4
When positioning the appliance, observe minimum clearanc-
es (see chapter “Preparations/ Installation site”).
Use the adjustable feet to compensate for any unevenness in
the floor.
D0000102527
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 7
Page 8
INSTALLATION
Installation
11.2 Removing/fitting the front casing
Removing the front casing
1
1 Front panel
Remove the screws on the left and right of the front panel.Carefully pull the front panel forwards to remove it from
the appliance and store it securely so that it cannot tip over, without putting strain on the cable connections.
AA01-X1.18
Material losses
!
When fitting additional shut-off valves, install a further safety valve in an accessible location on the heat gen­erator itself or in the flow line in close proximity to the heat generator. There must not be a shut-off valve between the heat gen­erator and the safety valve.
Note
The use of non-return valves in the charging circuits be­tween the heat generator and the buffer or DHW cylin­der can impair the function of the integral multifunction assembly (MFG) and lead to faults in the heating system.
Only use our standard hydraulic solutions for the
installation of the appliances.
D0000103275
Oxygen diffusion
Material losses
!
Avoid open vented heating systems and underfloor heating systems with plastic pipes that are permeable to oxygen.
In underfloor heating systems with plastic pipes that are per­meable to oxygen and in open vented heating systems, oxygen diffusion may lead to corrosion on the steel components of the heating system (e.g. on the indirect coil of the DHW cylinder, on buffer cylinders, steel radiators or steel pipes).
XE06
To be able to store the front panel at a distance from the ap-
pliance, loosen the cable tie, unplug the connector from the electronic assembly for operation (AA01-X1.18) and the earth (XE06) at the heat pump manager and store the front panel securely so that it cannot tip over.
Fitting the front casing
Fit the front casing in reverse order. Take care to position the connection lines correctly and not to pinch any cables.
11.3 Heating water connection and safety valve
11.3.1 Safety instructions
Material losses
!
The heating system to which the appliance is connected must be installed by a qualified contractor in accord­ance with the water installation drawings in the technical guides.
Material losses
!
The products of corrosion (e.g. rusty sludge) can set­tle in the heating system components, which may re-
D0000102755
Supply lines
Pressure differential
If the available external pressure difference is exceeded, the pres­sure drop in the heating system could result in a reduced heating output.
sult in a lower output or fault shutdowns due to reduced cross-sections.
The maximum permissible line length between the appli-
ance and the heat pump will vary, depending on the version of the heating system (pressure drop). As a standard value, assume a maximum line length of 10m and a pipe diameter of 22mm.
Protect the flow and return lines against frost with sufficient
thermal insulation.
Also protect all supply lines against humidity, damage and
UV radiation by means of a conduit.
Connect the hydraulic connections with flat gaskets.
When sizing the pipes, ensure that the available external
pressure differential is not exceeded (see chapter “Specifica­tion/ Data table”).
When calculating the pressure drop, take account of the flow
and return lines and the pressure drop of the heat pump. The pressure drop must be covered by the available pressure differential.
8 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 9
INSTALLATION
Installation
11.3.2 Heating water connection
Installation example:
1
1 Pipes carrying heating water
Thoroughly flush the pipes before connecting the heat pump.
Foreign bodies (e.g. welding pearls, rust, sand, sealant, etc.) can impair the operational reliability of the heat pump.
Install the heating water pipes (see chapter “Specification/
Dimensions and connections”).
11.4 DHW connection and safety assembly
11.4.1 Safety instructions
Material losses
!
The maximum permissible pressure must not be exceed­ed (see chapter “Specification/ Data table”).
Material losses
!
Operate the appliance only with pressure-tested taps.
Note
The use of non-return valves in the charging circuits be­tween the heat generator and the buffer or DHW cylin­der can impair the function of the integral multifunction assembly (MFG) and lead to faults in the heating system.
Only use our standard hydraulic solutions for the
installation of the appliances.
D0000103276
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved materials.
Material losses
!
A safety valve is required.
Safety valve drain hose
1
1 Safety valve drain hose
Unroll the safety valve drain hose connected to the multi-
function assembly.
On one of the lower prepared openings on the left or right,
remove just enough insulating material as necessary for the drain hose, in order to minimise the exchange of air.
Route the drain hose through the prepared opening from the
appliance.
Route the drain hose with a constant fall to a drain.Ensure that the drain hose is open to the outside.Secure the drain hose above the drain to prevent any hose
movement in the event of water being discharged.
Material losses
!
Route the drain hose to a drain to enable water to drain freely when the safety valve is open.
DHW line, DHW circulation line
Stainless steel, copper and plastic are approved materials.
11.4.2 Fitting the DHW circulation line (optional)
A DHW circulation line with external DHW circulation pump can be fitted to the DHW circulation connection (see chapter “Specifi­cation/ Dimensions and connections”).
D0000103253
1 2
3 4
5
1 Union nut 2 Insulating sleeve 3 DHW circulation line 4 Gasket 5 “DHW circulation” connection
Remove the sealing cap from the DHW circulation connection
(see chapter “Specification/ Dimensions and connections”).
Connect the DHW circulation line with the gasket, the insulat-
ing bushing and the flat gasket union nut.
D0000103254
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 9
Page 10
INSTALLATION
Installation
11.4.3 DHW connection and safety assembly
Flush the pipes thoroughly.Install the DHW outlet line and the cold water inlet line (see
chapter “Specification/ Dimensions and connections”). Con­nect the hydraulic connections.
Install a type-tested safety valve in the cold water supply
line. Please note that, depending on the supply pressure, you may also need a pressure reducing valve.
Size the drain pipe so that water can drain off unimpeded
when the safety valve is fully opened.
The safety valve drain aperture must remain open to
atmosphere.
Install the safety valve drain pipe with a constant fall to the
drain.
11.5 Filling the system
Heating circuit water quality
Carry out a fill water analysis before filling the system. This analy­sis may, for example, be requested from the relevant water supply utility.
To avoid damage as a result of scaling, it may be necessary to soften or desalinate the fill water. The fill water limits specified in chapter “Specification/ Data table” must always be observed.
Recheck these limits 8-12weeks after commissioning and
during the annual system service.
When power is switched on, the 3-way diverter valve automatically switches to heating mode.
To fill or drain the system later, you must first place the 3-way diverter valve into its centre position.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
DIAGNOSIS
RELAY TEST SYSTEM  DRAIN HYD
D0000102722
Fill the heating system via the left-hand drain & fill valve.Vent the pipework.
11.5.3 DHW cylinder filling
Material losses
!
Never switch on the power before filling the system.
Note
With a conductivity >1000μS/cm, desalination treatment is recommended in order to avoid corrosion.
Note
If you treat the fill water with inhibitors or additives, the same limits apply as for desalination.
Note
Suitable appliances for water softening, as well as for filling and flushing heating systems, can be obtained via trade suppliers.
11.5.1 Flushing out the hot water system
Before turning on the water supply, open all taps. Allow
the system to fill and flush out all flux and debris from the installation.
11.5.2 Filling the heating system
Note
Fill the heating system exclusively via the left-hand drain & fill valve.
Material losses
!
Some fluxes used to solder pipes and fittings need to be flushed out with hot water.
Heat the cylinder to its normal operating tempera-
ture and flush all pipe work with hot water to ensure all flux and debris is removed from the system.
Fill the DHW cylinder via the cold water connection in com-
pliance with the UK Water Supply (Water Fittings) Regula­tions 1999, Section 8 G24.
Open all downstream draw-off valves until the appliance is
full and the pipework is free of air.
Adjust the flow rate. For this, observe the maximum permis-
sible flow rate with a fully opened tap (see chapter “Specifi­cation/ Data table”). If necessary reduce the flow rate at the butterfly valve of the safety assembly.
Carry out a tightness check.Check the safety valve.
In the delivered condition, the 3-way diverter valve of the mul­tifunction assembly is in its centre position, so that the heating circuit and the heat exchanger for DHW heating are filled evenly.
10 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 11
INSTALLATION

Electrical connection

11.6 Venting the appliance
1
2
1
1 Air vent valve 2 PCB
Vent the pipework and indirect coil by pulling up the red cap
on the air vent valves.
Close the air vent valves after the venting process.
D0000103256
Material losses
!
Close the air vent valves again after venting.
12. Electrical connection
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations.
Before any work on the appliance, disconnect all
poles from the power supply.
WARNING Electrocution The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power supply by an isolator that dis­connects all poles with at least 3mm contact separation. This requirement can be met by using contactors, circuit breakers, fuses/MCBs, etc.
Material losses
!
Provide separate fuses for the two power circuits of the appliance and the control unit.
Material losses
!
Provide separate fuses/MCBs for the two power circuits, i.e. for the compressor and the electricemergency/boost­er heater circuits.
Material losses
!
Observe the type plate. The specified voltage must match the mains power supply.
Note
You must have permission to connect the appliance from the relevant power supply utility.
1
1 Cable entry plug
Cut the 4 cable entry plugs only as much as required for the
cable diameter in order to minimise the exchange of air.
Route all power supply cables and sensor leads into the ap-
pliance through the cable entry from the left or right. From the left, route the cables behind the terminal box to the right-hand side. Lay the lines on the right-hand side through the empty conduits and cable entry plugs.
Connect the power cables and sensor leads as detailed
below.
Install cables with the following cross-sections in accordance with the respective fuse protection:
Fuse protec­tion
B 16A
B 16A
B 16A Control unit 1.5mm²
Assignment Cable cross-section
Electric emergency/ booster heater (DHC) Three-phase
Electric emergency/ booster heater (DHC) Single phase
2.5mm²
1.5mm² with only two live wires, rout­ing according to applicable regulations
2.5mm²
1.5mm² when routing a multi-core cable on a wall or in an electrical con­duit on a wall
D0000103257
The terminal box of the appliance is located behind the front casing (see chapter “Installation/ Removing/ fitting the front casing”).
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 11
Page 12
INSTALLATION
Electrical connection
12.1 Electric emergency/booster heater and control voltage
Appliance function
Mono energetic operation
Emergency mode Should the heat pump suffer a fault that prevents its con-
HSBB180: Electrical connection three-phase
XD02 Electric emergency/booster heater (DHC)
Connected load Terminal assignment
2.9 kW PE N L1
5.9 kW PE N L2 L1
8.8 kW PE N L3 L2 L1
Effect of the electric emergency/booster heater
If the dual mode point is undershot, the electric emergen­cy/booster heater safeguards both the heating operation and the provision of high DHW temperatures.
tinued operation, the heating output will be covered by the electric emergency/booster heater.
L1
317964-41782
L2
L3
N
XD02 Electric emergency/booster heater (DHC)
Connected load
2.9 kW 2.5mm² PE N L
5.9 kW
2.5mm² PE N L
Cable cross-sec­tion
2.5mm² PE N L
Terminal assignment
Connect the electrical emergency/booster heater cables to
deliver the required rating as detailed in the table.
Control voltage
Material losses
!
Only connect energy efficient circulation pumps ap-
proved by us to the pump connections.
XD01.2 Heat pump enable signal
EVU Enable signal, bus cable to the WPM screened with
strain relief in terminal.
Heat pump manager terminal assignment
WARNING Electrocution Only components that operate with safety extra low voltage (SELV) and that ensure secure separation from
D0000102543
the mains voltage supply may be connected to the low voltage terminals of the appliance. Connecting other components can make parts of the ap­pliance and connected components live.
Only use components which have been approved by
us.
Connect the electrical emergency/booster heater with the
desired rating as detailed in the table.
HSBB180S: Electrical connection single phase
L1
317964-41782 317965-38886
L2
L3
N
N L N L
D0000071841
D0000102544
12 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 13
INSTALLATION
Electrical connection
Safety ex tra low voltage
X1.1 CAN A
X1.2 CAN B
X1.3 Signal
X1.4 Signal
X1.5 Signal
X1.6 Signal
X1.7 Signal
X1.8 Signal
X1.9 Signal
X1.10 Signal
X1.11 Signal
X1.12 Signal
X1.13 Signal
X1.14 Constant 12V
X1.15 Constant 12V
X1.16 Signal
X1.17 Signal
X1.18 CAN B
X1.19 CAN A
Mains power supply
X2.1
X2.2 L‘ (power supply
X2.3 L
X2.4 L
X2.5 L
X2.6 L
+
­L H
+
­L H
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth
Earth Signal
Input GND
Input GND
Earth
Earth +
­L H
+
­L H
L L N PE
utility input) L* (pumps L)
N PE
N PE
N PE
N PE
+
­L H
+
­L H
1 2Outside sensor
1 2Buffer sensor (heating circuit sensor 1)
1 2Flow sensor
1 2Heating circuit sensor 2
1 2Heating circuit sensor 3
1 2DHW cylinder sensor
1 2Source sensor
1 22nd heat generator (2.WE)
1 2Cooling flow
1 2DHW circulation sensor
1 2 3
+ IN
+ IN
1 2PWM output 1
1 2PWM output 2
+
­L H
+
­L H
L L N
L‘
L* (pumps L) L
N
L N
L N
L N
CAN (connection for heat pump and WPE heat pump extension)
CAN (connection for FET remote control and ISG Internet Service Gateway)
FE7 remote control/ telephone remote switch/ heating curve optimisation/ SGReady
Analogue input 0-10V
Analogue input 0-10V
CAN (FES)
CAN (connection for heat pump and WPE heat pump extension)
Power supply
L‘ (power supply utility input)
L* (pumps L) Heating circuit pump 1
PE
Heating circuit pump 2
PE
Heating circuit pump 3
PE
Buffer charging pump 1
PE
Mains power supply
X2.7 L
X2.8 L
X2.9 L
X2.10 L
X2.11 L
X2.12 L
X2.13 L
X2.14
X2.15
N PE
N PE
N PE
N PE
N PE
N PE
N PE
Mixer OPEN N PE Mixer CLOSE
Mixer OPEN N PE Mixer CLOSE
L N
L N
L N
L N
L N
L N
L N
5 N
6 5
N
6
PE
PE
PE
PE
PE
PE
PE
PE
PE
Buffer charging pump 2
DHW charging pump
Source pump/ defrost
Fault output
DHW circulation pump/ 2nd heat source DHW
2ndheat source heating
Cooling
Not assigned
Not assigned
Note
For every appliance fault, output X2.10 issues a 230V signal. In the case of temporary faults, the output switches the signal through for a specific time. In the case of faults that result in a permanent appliance shutdown, the output switches through permanently.
Accessories, STB-FB high limit safety cut-out for underfloor heating systems (optional)
XD01.1
L1
N
2
1
3
2
4
Netz
L
1
EVU
XD01.2
L’
2
Remove the jumper at XD01.1 between L1 and 2. Connect the STB-FB high limit safety cut-out to XD01.1 be-
tween L1 and 2.
D0000084472
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 13
Page 14
INSTALLATION

Commissioning

12.2 Sensor installation
12.2.1 Outside temperature sensor AFPT
The outside temperature sensors have a significant influence on the function of your heating system. Therefore ensure that the outside temperature sensors are correctly positioned and well insulated.
- Install the outside temperature sensor on a north or north-eastern wall.
- Ensure that the outside temperature sensor is freely exposed to the elements but not placed in direct sunlight.
- Never mount the outside temperature sensor above win­dows, doors or air ducts.
- Observe the following minimum clearances: 2.5m above the ground and 1m to the side of windows and doors
Installation
Remove the cover.Secure the base with the screw supplied.Connect the cable.Connect the outside temperature sensor to AA01-X1.3.Replace the cover. The cover must audibly click into place.
12.3 Remote control
Please observe the commissioning instructions for the heat
pump manager.
The FET remote control is required to record humidity in the case of cooling via an area heating system.
13. Commissioning
Our customer support can assist with commissioning, which is a chargeable service.
If the appliance is intended for commercial use, observe the rules of the relevant Health & Safety at Work Act during commissioning. For further details, check with your local authorising body (in Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump manager
Material losses
!
Observe the maximum system temperature in underfloor heating systems.
Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
Check whether the outside temperature sensor is correctly
placed and connected.
Check whether the power supply is connected correctly.Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
High limit safety cut-out
Note
At temperatures below –15°C the high limit safety cut-out may respond. The appliance may be subjected to these temperatures during storage or transport.
1
1 High limit safety cut-out reset button
Check whether the high limit safety cut-out has tripped.If the high limit safety cut-out has triggered, reset it with the
reset button.
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in ac­cordance with the heat pump manager operating and installation instructions.
Note
For DHW mode, ensure that the PARALLEL OPERATION option is set in the heat pump manager. With this setting, the cylinder charging pump/ heating circuit pump is also activated in DHW mode.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SET TINGS
DHW  STANDARD SETTING  DHW MODE PARALLEL OPERATION
Note
On appliances with a single phase connection, set the heat pump manager as follows for calculating the amount of heat.
To set the heat pump manager:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SET TINGS
H EATI NG  ELECTRIC BOOSTER HEATER  NUMBER OF STAGES 2
Value
Value
D0000103267
14 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 15
INSTALLATION

Shutting down the system

Cooling settings
Material losses
!
Condensation caused by the temperature falling below the dew point can lead to material losses. The appliance is therefore approved exclusively for area cooling. For dew point independent cooling, additional accesso­ries (CDT 180) are required to ensure that any condensate is reliably drained away.
Observe the instructions for the heat pump manager.
Adjusting the heat pump manager settings for area cooling:
With the MENU key, call up the main menu.Select the menu or value and confirm with OK:
SET TINGS
COOLING  COOLING ON  STANDARD SETTING  COOLING CAPACITY system specific  ACTIVE COOLING  AREA COOLING ON  SET FLOW TEMPERATURE system specific  FLOW TEMP HYSTERESIS system specific  SET ROOM TEMPERATURE system specific
Value
15. Maintenance
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations.
WARNING Electrocution
Before any work on the appliance, disconnect all
poles of the appliance from the power supply.
Draining the DHW cylinder
CAUTION Burns Hot water may escape during draining.
Close the shut-off valve in the cold water supply line.Open the hot water taps on all draw-off points.
13.3 Appliance handover
Explain the appliance function to users and familiarise them
with how it works.
Make users aware of potential dangers.Hand over these instructions.
14. Shutting down the system
Material losses
!
Observe the temperature application limits and the min­imum circulation volume of the heat pump.
Material losses
!
Drain the system when there is a risk of frost and the heat pump is completely switched off (see chapter “Mainte­nance/ Draining the DHW cylinder”).
If you take the system out of use, set the heat pump manager
to standby so that the safety functions that protect the appli­ance (e.g. frost protection) remain active.
D0000103378
Drain the DHW cylinder via the right-hand drain & fill valve.
Testing the sacrificial anode
Arrange for the sacrificial anode to be tested at least every
two years and replace immediately if it becomes depleted. For this, observe the maximum transition resistance between the sacrificial anode and the cylinder of 0.3Ω. If it is not possible to insert the sacrificial anode from above, install a segmented anode.
The intervals at which subsequent testing should be carried out depends on the wear of the sacrificial anode.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 15
Page 16
INSTALLATION
Specication
16. Specification
16.1 Dimensions and connections
601
300
915
685
c13
1201
c10
590
c06
1279
1418
c12
10-20
c01
9595
b01
1261
130 130 130
d02 e01
d01 e02
HSBB 180 Plus (GB) HSBB 180 S Plus (GB)
b01 Entry electrical cables c01 Cold water inlet Male thread G 1 G 1 c06 DHW outlet Diameter mm 22 22 c10 DHW circulation Male thread G 1/2 G 1/2 c12 Safet y valve drain Diameter mm 22 22 c13 T&P valve d01 Heat pump flow Diameter mm 22 22 d02 Heat pump return Diameter mm 22 22 e01 Heating flow Diameter mm 22 22 e02 Heating return Diameter mm 22 22
16 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
D0000103277
Page 17
INSTALLATION
Specication
Other dimensions and connections
i18
h16
d47 d47
HSBB 180
h16 Sensor DHW Diameter mm 9.5 9.5 i18 Sacrificial anode Torque Nm 120 120 d47 Drain & fill valve
Female thread G 1 1/4 G 1 1/4
Plus (GB)
HSBB 180
S Plus (GB)
16.2 Hydraulic diagram
15
181716
11 14
13
D0000103278
1 Discharge below fixed grate 2 Cold water supply 3 Shut-off valve 4 Line strainer 5 Pressure reducing valve 6 Balanced pressure; cold water outlet 7 Check valve 8 Safety assembly 9 Tundish 10 Metal discharge pipe (D2) from tundish, with continuous fall 11 Equipotential bond 12 Drain valve 13 Cylinder 14 DHW outlet 15 T&P valve 16 Metal discharge pipe (D1) from T&P valve to tundish 17 Expansion vessel 18 Expansion relief valve
< 600
12 11
9
> 300
10
4
568
7
3 2 1
D0000040507
Material losses
!
The tundish should be installed away from electrical de­vices.
Note
If secondary return circuits are used then an additional expansion vessel may be required.
Data table
Minimum size of discharge pipe D1 mm 15 Minimum size of discharge pipe D2 from tundish mm 22 28 35 Maximum permissible pressure drop, expressed as
a length of straight pipe (i.e. no elbows or bends) Pressure drop of each elbow or bend m 0.8 1.0 1.4
Connection dimensions
Safety assembly connection mm 22 Expansion valve end connection mm 15 Expansion vessel connection, male, BSP G 1 A Tundish inlet connection mm 22 Tundish outlet connection G 1
m 9 18 27
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 17
Page 18
INSTALLATION
Specication
16.3 Wiring diagram
HSBB 180 Plus
AB01 (CDT 180)
L1 2 K1 K2N
2 3 4 5 61
BK
FC07
BK
L
M 1~
MA13
BU
WH
N
XD13
GNYE
GNYEVTVT
L
BNBUGNYE
L
N
ws (PWM)
M
br (GND)
1~
XD01.1
L1
GNYE
1
2
2
BK
N
3
BU
4
L
1
L’
2
MA14
XD01.2
L
MA10
XE01
L L
X2.1
N PE
L‘ L*
X2.2X2.3X2.4X2.5X2.6X2.7
L N PE
L N PE
L N PE
BNBUGNYE
L
N
M 1~
L N PE
L N PE
L N
X2.8X2.9X2.10X2.11X2.12X2.13
PE
L N PE
L N PE
L N PE
L N PE
L N PE
N PE
X2.14
N PE
X2.15
AA01 (WPM)
AA01 Extra low voltage (WPM4 heat pump manager) AA06 Programming unit AA07 PCB, booster heater MFG EB01 Booster heater MFG BF01 Flow rate and temperature, heating circuit BP10 Heating circuit pressure sensor BT01 Temperature sensor, heat pump flow BT02 Temperature sensor, heat pump return BT06 Temperature sensor HP buffer cylinder (not assigned) BT08 Temperature sensor HP cooling (not assigned) BT20 Temperature sensor, DHW cylinder BT55 High limit safety cut-out MFG (manual reset) FC07 Condensate pump fuse MA10 Motor, pump, heating circuit (not assigned) MA13 Condensate pump motor
MA14 Motor, buffer charging pump (PWM/1-10V) MA15 Motor, diverter valve, heating/DHW KF20 Relay, booster heater MFG KF21 Relay, booster heater MFG KF22 Relay, booster heater MFG XD01.1 Terminal, power supply XD01.2 Terminal, power-OFF contact XD02 Terminal, MFG power supply XD13 Terminal, condensate pump XE01 Power supply earth terminal XE02 Earth terminal MFG/DHC XE05 Earth stud, front panel XE06 Earth, front panel AA 01-X1.1 Connector, CAN A (heat pump connection) AA 01-X1. 2 Connector, CAN B (FET/ISG connection)
18 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 19
INSTALLATION
XE05
XE06
Specication
CAN A
CAN B
CAN B
CAN A
+
-
L
X1.1
H
+
­L H
1 2
X1.3X1.4X1.5X1.6X1.7X1.8X1.9X1.10X1.11
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2 3
+
IN
+
IN
1 2
1 2
X1.17 X1.16 X1.15 X1.14 X1.13 X1.12 X1.2
+
-
L
X1.18
H
+
­L
X1.19
H
WH
4321
BN GN YE
+ L
H
T
321
KF20KF21KF22
EB01
X71 X72X70X69X68
321
PWM
GND
2 1
6
6
5
1~
1~
M
M
5
3 4
3 4
2
2
1
1
(MFG)
AA07
MA15
X67X66
1
4
OUT
2
3
p
BT06
+5V
1
4
GND
BP10
BT20
T2 T1
+5V
Hz
GND OUT
BT08
T
T
BF01
BT02
BT01
4 3 2 1
WH YE
BN GN
AA06
X27
PT 1000
4
4
1 = H 2 = L 3 = 4 = +12V
2
3
2
3
4321 4321
12 22 32
BT55
<T
11 3121
X65X63X62X61X60
1 2 3 4 51 2 3 4 5
X64
3
1
3
KF22
KF21
1
2 1
2 1
2 1
2 1
3
KF20
1
AA07
X59
2N 3
1
MFG
1
1
GNBNYEWH
N
1
2
XD02
XE02
L3 L2
3
L1
5
4
D0000089904
AA 01-X1. 3 Connector, outside temperature sensor AA 01-X1.4 Connector, buffer temperature sensor BT06 (not assigned) AA 01-X1.5 Connector, flow temperature sensor AA 01-X1.6 Connector, heating circuit temperature sensor 2 AA 01-X1.7 Connector, heating circuit temperature sensor 3 AA 01-X1. 8 Connector, DHW cylinder sensor BT20 AA 01-X1.9 Connector, source sensor AA01-X1.10 Connector, 2nd heat generator AA 01-X1. 11 Connector, flow, cooling (not assigned) AA 01-X1.12 Connector, DHW circulation sensor AA 01-X1.13 Connector, remote control FE7 AA 01-X1.14 Connector, analogue input 0-10V AA 01-X2.14 Connector, mixer, heating circuit 2 (X2.14.1 Mixer OPEN/X2.14.2
Mixer CLOSE)
AA01-X2.15 Connector, mixer, heating circuit 3
(X2.15.1 Mixer OPEN/X2.15.2 Mixer CLOSE)
AA 07-X60 Connector, temperature sensor, heat pump flow BT01 AA 07-X61 Connector, temperature sensor, heat pump return BT02 AA 07-X62 Not assigned – connector, temperature sensor, heat pump return AA 07-X63 Not assigned – connector, temperature sensor, DHW cylinder,
internal AA 07-X64 Connector, temperature and flow rate, heating circuit, BF01 AA 07-X65 Not assigned AA 07-X66 Rast 2.5 connector (heating system pressure) BP01 AA 07-X67 Not assigned AA 07-X68 Connector, switching, motor, diverter valve central heating /
DHW AA 07-X69 Not assigned AA 07-X70 Connector, switching, pump, heating circuit PWM/1-10V AA 07-X71 Not assigned AA 07-X72 Connector, CAN bus EB01-X59 Terminal, MFG
AA 06-X27 Terminal, programming unit
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 19
Page 20
INSTALLATION
Specication
HSBB180S Plus
AB01 (CDT 180)
L1 2 K1 K2N
2 3 4 5 61
BK
FC07
BK
L
M 1~
MA13
BU
WH
N
XD13
GNYE
GNYEVTVT
L
BNBUGNYE
L
N
ws (PWM)
M
br (GND)
1~
XD01.1
L1
GNYE
1
2
2
BK
N
3
BU
4
L
1
L’
2
MA14
XD01.2
L
MA10
XE01
L L
X2.1
N PE
L‘ L*
X2.2X2.3X2.4X2.5X2.6X2.7
L N PE
L N PE
L N PE
BNBUGNYE
L
N
M 1~
L N PE
L N PE
L N
X2.8X2.9X2.10X2.11X2.12X2.13
PE
L N PE
L N PE
L N PE
L N PE
L N PE
N PE
X2.14
N PE
X2.15
AA01 (WPM)
AA01 Extra low voltage (WPM4 heat pump manager) AA06 Programming unit AA07 PCB, booster heater MFG EB01 Booster heater MFG BF01 Flow rate and temperature, heating circuit BP10 Heating circuit pressure sensor BT01 Temperature sensor, heat pump flow BT02 Temperature sensor, heat pump return BT06 Temperature sensor HP buffer cylinder (not assigned) BT08 Temperature sensor HP cooling (not assigned) BT20 Temperature sensor, DHW cylinder BT55 High limit safety cut-out MFG (manual reset) FC07 Condensate pump fuse MA10 Motor, pump, heating circuit (not assigned) MA13 Condensate pump motor
MA14 Motor, buffer charging pump (PWM/1-10V) MA15 Motor, diverter valve, heating/DHW KF20 Relay, booster heater MFG KF21 Relay, booster heater MFG KF22 Relay, booster heater MFG XD01.1 Terminal, power supply XD01.2 Terminal, power-OFF contact XD02 Terminal, MFG power supply XD13 Terminal, condensate pump XE01 Power supply earth terminal XE02 Earth terminal MFG/DHC XE05 Earth stud, front panel XE06 Earth, front panel AA 01-X1.1 Connector, CAN A (heat pump connection) AA 01-X1. 2 Connector, CAN B (FET/ISG connection)
20 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 21
INSTALLATION
XE05 XE06
Specication
CAN A
CAN B
CAN B
CAN A
+
-
L
X1.1
H
+
­L H
1 2
X1.3X1.4X1.5X1.6X1.7X1.8X1.9X1.10X1.11
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2 3
+ IN
+ IN
1 2
1 2
X1.17 X1.16 X1.15 X1.14 X1.13 X1.12 X1.2
+
-
L
X1.18
H
+
­L
X1.19
H
WH
4321
BN GN YE
+ L
H
T
321
KF20KF21KF22
EB01
X71 X72X70X69X68
321
PWM
GND
2 1
6
6
5
1~
1~
M
M
5
3 4
3 4
2
2
1
1
AA07 (MFG)
MA15
X67X66
1
4
OUT
2
3
p
BT06
+5V
1
4
GND
BP10
BT20
T2 T1
+5V
Hz
GND OUT
BT08
T
T
BF01
BT02
BT01
4 3 2 1
WH YE
BN GN
AA06
X27
PT 1000
4
4
1 = H 2 = L 3 = 4 = +12V
2
3
2
3
4321 4321
12 22 32
BT55
<T
11 3121
X65X63X62X61X60
1 2 3 4 51 2 3 4 5
X64
3
1
3
KF20
KF21
1
2 1
2 1
2 1
2 1
3
KF22
1
AA07
X59
LN N
L
MFG
1
1
GNBNYEWH
N
1
2
L N
3
L
5
4
XD02
XE02
D0000096750
AA 01-X1. 3 Connector, outside temperature sensor AA 01-X1.4 Connector, buffer temperature sensor BT06 (not assigned) AA 01-X1.5 Connector, flow temperature sensor AA 01-X1.6 Connector, heating circuit temperature sensor 2 AA 01-X1.7 Connector, heating circuit temperature sensor 3 AA 01-X1. 8 Connector, DHW cylinder sensor BT20 AA 01-X1.9 Connector, source sensor AA01-X1.10 Connector, 2nd heat generator AA 01-X1. 11 Connector, flow, cooling (not assigned) AA 01-X1.12 Connector, DHW circulation sensor AA 01-X1.13 Connector, remote control FE7 AA 01-X1.14 Connector, analogue input 0-10V AA 01-X2.14 Connector, mixer, heating circuit 2 (X2.14.1 Mixer OPEN/X2.14.2
Mixer CLOSE)
AA01-X2.15 Connector, mixer, heating circuit 3
(X2.15.1 Mixer OPEN/X2.15.2 Mixer CLOSE)
AA 07-X60 Connector, temperature sensor, heat pump flow BT01 AA 07-X61 Connector, temperature sensor, heat pump return BT02 AA 07-X62 Not assigned – connector, temperature sensor, heat pump return AA 07-X63 Not assigned – connector, temperature sensor, DHW cylinder,
internal AA 07-X64 Connector, temperature and flow rate, heating circuit, BF01 AA 07-X65 Not assigned AA 07-X66 Rast 2.5 connector (heating system pressure) BP01 AA 07-X67 Not assigned AA 07-X68 Connector, switching, motor, diverter valve central heating /
DHW AA 07-X69 Not assigned AA 07-X70 Connector, switching, pump, heating circuit PWM/1-10V AA 07-X71 Not assigned AA 07-X72 Connector, CAN bus EB01-X59 Terminal, MFG
AA 06-X27 Terminal, programming unit
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 21
Page 22
INSTALLATION
Specication
16.4 Energy consumption data
Product datasheet: DHW cylinder to Regulation (EU) No 812/2013 (S.I. 2019 No. 539 / Programme 2)
HSBB 180 Plus (GB) HSBB 180 S Plus (GB)
202926 203084 Manufacturer STIEBEL ELTRON STIEBEL ELTRON Supplier‘s model identifier HSBB 180 Plus (GB) HSBB 180 S Plus (GB) Energy efficiency class B B Standby losses S W 53.9 53.9 Cylinder capacity V l 195 195
16.5 Data table
HSBB 180 Plus (GB) HSBB 180 S Plus (GB)
202926 203084 Hydraulic data Nominal capacity, DHW cylinder l 178 178 Surface area, heat exchanger 1.59 1.59 Capacity, heat exchanger l 10 10 External available pressure differential at 1.0 m³/h hPa 690 690 External available pressure differential at 1.5 m³/h hPa 461 461 External available pressure differential at 2 m³/h hPa 219 219 Application limits Max. permissible pressure, DHW cylinder MPa 1 1 Test pressure, DHW cylinder MPa 1.5 1.5 Max. flow rate l/min 25 25 Max. permissible temperature °C 95 95 Max. permissible temperature, primary side °C 75 75 Heating water quality requirements Water hardness °dH ≤3 ≤3 pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 Conductivity (softening) μS/cm <1000 <1000 Conductivity (desalination) μS/cm 20-100 20-1 00 Chloride mg/l <30 <30 Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 Power consumption Power consumption, emergency/booster heater kW 8.8 5.9 Max. power consumption, circulation pump, heating side W 60 60 Energy data Standby energy consumption/ 24 h at 65 °C kWh 1.29 1.29 Energy efficiency class B B Electrical data Rated voltage, control unit V 230 230 Phases, control unit 1/N/PE 1/N/PE Control unit fuse protection A 1 x B 16 1 x B 16 Rated voltage, emergency/booster heater V 400 230 Phases, emergency/booster heater 3/N/PE 2/N/PE Emergency/booster heater fuse protection A 3 x B 16 2 x B 16 Frequency Hz 50 50 Versions IP rating IP20 IP20 Suitable for Heat pump Heat pump Dimensions Height mm 1280 1280 Width mm 605 605 Depth mm 917 917 Height when tilted mm 1500 1500 Weights Weight, full kg 280 280 Weight, empty kg 100 100
22 | HSBB 180 Plus (GB)|HSBB 180 S Plus (GB) www.stiebel-eltron.com
Page 23
INSTALLATION | GUARANTEE | ENVIRONMENT AND RECYCLING
Specication
Further details
HSBB 180 Plus (GB) HSBB 180 S Plus (GB)
202926 203084 Maximum height for installation m 2000 2000

Guarantee

The guarantee conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only grant­ed if the subsidiary has issued its own terms of guarantee. No other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products. This will not aect warranties issued by any importers.

Environment and recycling

We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations.
www.stiebel-eltron.com HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)| 23
Page 24
Deutschland
STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Straße 33 | 37603 Holzminden Tel. 05531 702-0 | Fax 05531 702-480 info@stiebel-eltron.de www.stiebel-eltron.de
Verkauf Tel. 05531 702-110 | Fax 05531 702-95108 | info-center@stiebel-eltron.de Kundendienst Tel. 05531 702-111 | Fax 05531 702-95890 | kundendienst@stiebel-eltron.de Ersatzteilverkauf Tel. 05531 702-120 | Fax 05531 702-95335 | ersatzteile@stiebel-eltron.de
Australia
STIEBEL ELTRON Australia Pty. Ltd. 294 Salmon Street | Port Melbourne VIC 3207 Tel. 03 9645-1833 | Fax 03 9644-5091 info@stiebel-eltron.com.au www.stiebel-eltron.com.au
Austria
STIEBEL ELTRON Ges.m.b.H. Gewerbegebiet Neubau-Nord Margaritenstraße 4 A | 4063 Hörsching Tel. 07221 74600-0 | Fax 07221 74600-42 info@stiebel-eltron.at www.stiebel-eltron.at
Belgium
STIEBEL ELTRON bvba/sprl 't Hofveld 6 - D1 | 1702 Groot-Bijgaarden Tel. 02 42322-22 | Fax 02 42322-12 info@stiebel-eltron.be www.stiebel-eltron.be
China
STIEBEL ELTRON (Tianjin) Electric Appliance Co., Ltd. Plant C3, XEDA International Industry City Xiqing Economic Development Area 300385 Tianjin Tel. 022 8396 2077 | Fax 022 8396 2075 info@stiebeleltron.cn www.stiebeleltron.cn
Czech Republic
STIEBEL ELTRON spol. s r.o. Dopraváků 749/3 | 184 00 Praha 8 Tel. 251116-111 | Fax 235512-122 info@stiebel-eltron.cz www.stiebel-eltron.cz
Finland
STIEBEL ELTRON OY Kapinakuja 1 | 04600 Mäntsälä Tel. 020 720-9988 info@stiebel-eltron.fi www.stiebel-eltron.fi
France
STIEBEL ELTRON SAS 7-9, rue des Selliers B.P 85107 | 57073 Metz-Cédex 3 Tel. 0387 7438-88 | Fax 0387 7468-26 info@stiebel-eltron.fr www.stiebel-eltron.fr
Hungary
STIEBEL ELTRON Kft. Gyár u. 2 | 2040 Budaörs Tel. 01 250-6055 | Fax 01 368-8097 info@stiebel-eltron.hu www.stiebel-eltron.hu
Japan
NIHON STIEBEL Co. Ltd. Kowa Kawasaki Nishiguchi Building 8F 66-2 Horikawa-Cho Saiwai-Ku | 212-0013 Kawasaki Tel. 044 540-3200 | Fax 044 540-3210 info@nihonstiebel.co.jp www.nihonstiebel.co.jp
Netherlands
STIEBEL ELTRON Nederland B.V. Daviottenweg 36 | 5222 BH 's-Hertogenbosch Tel. 073 623-0000 | Fax 073 623-1141 info@stiebel-eltron.nl www.stiebel-eltron.nl
New Zealand
Stiebel Eltron NZ Limited 61 Barrys Point Road | Auckland 0622 Tel. +64 9486 2221 info@stiebel-eltron.co.nz www.stiebel-eltron.co.nz
Poland
STIEBEL ELTRON Polska Sp. z O.O. ul. Działkowa 2 | 02-234 Warszawa Tel. 022 60920-30 | Fax 022 60920-29 biuro@stiebel-eltron.pl www.stiebel-eltron.pl
Russia
STIEBEL ELTRON LLC RUSSIA Urzhumskaya street 4, building 2 | 129343 Moscow Tel. +7 495 125 0 125 info@stiebel-eltron.ru www.stiebel-eltron.ru
Slovakia
STIEBEL ELTRON Slovakia, s.r.o. Hlavná 1 | 058 01 Poprad Tel. 052 7127-125 | Fax 052 7127-148 info@stiebel-eltron.sk www.stiebel-eltron.sk
Switzerland
STIEBEL ELTRON AG Industrie West Gass 8 | 5242 Lupfig Tel. 056 4640-500 | Fax 056 4640-501 info@stiebel-eltron.ch www.stiebel-eltron.ch
Thailand
STIEBEL ELTRON Asia Ltd. 469 Moo 2 Tambol Klong-Jik Amphur Bangpa-In | 13160 Ayutthaya Tel. 035 220088 | Fax 035 221188 info@stiebeleltronasia.com www.stiebeleltronasia.com
United Kingdom and Ireland
STIEBEL ELTRON UK Ltd. Unit 12 Stadium Court Stadium Road | CH62 3RP Bromborough Tel. 0151 346-2300 | Fax 0151 334-2913 info@stiebel-eltron.co.uk www.stiebel-eltron.co.uk
United States of America
STIEBEL ELTRON, Inc. 17 West Street | 01088 West Hatfield MA Tel. 0413 247-3380 | Fax 0413 247-3369 info@stiebel-eltron-usa.com www.stiebel-eltron-usa.com
4<AMHCMO=fafijb>
Irrtum und te chnische Änder ungen vorbehalten! | Subject to errors and technical changes! | Sous réser ve d‘erreur s et de modifica tions techniques! | Onder voorbehoud van vergissingen en technische wijzigingen! | Salvo error o modificación técnica! | Excepto erro ou alteração técnica | Zastr zeżone zmiany technic zne i ewentualne błędy | Omyl y a technické změny jsou vyhrazeny! | A muszaki változt atások és tévedések jogát fenntartjuk ! | Отсутс твие оши бок не гарантируетс я. Возмож ны техниче ские изме нения. | Chyb y a technické zmeny sú vy hradené! Stand 9646
A 350589-43153-9655
B 350561-43150-9648
Loading...