Sterling RTAA-70, RTAA-90, RTAA-80, RTAA-IOM-4A, RTAA-IOM-4 User Manual

...

Specifications and Main Features

  • Rotary Liquid Chillers of the Model RTAA Series R®
  • The unit is available in a capacity range of 70 to 125 tons.
  • The unit employs Dual helically rotary compressor types with two independent refrigerant circuits.
  • Refrigerant used is HCFC-22.
  • Standard unit uses ambient air in a temp range of 15°F to 125°F, whereas low ambient models can use temp of up to -10°F.
  • Water Tank Capacity (in gallons):
  • RTAA-70: 39.8 gallons (150.6 liters)
  • RTAA-80: 37.8 gallons (143.1 liters)
  • RTAA-90: 34.4 gallons (130.2 liters)
  • RTAA-100: 32.1 gallons (121.5 liters)
  • RTAA-110: 53.4 gallons (202.1 liters)
  • RTAA-125: 45.8 gallons (173.4 liters)
  • Min. Chilled Water Flow (GPM):
  • RTAA-70: 84 GPM
  • RTAA-80: 96 GPM
  • RTAA-90: 198 GPM
  • RTAA-100: 123 GPM
  • RTAA-110: 132 GPM
  • RTAA-125: 140 GPM
  • Max. Chilled Water Flow (GPM):
  • RTAA-70: 252 GPM
  • RTAA-80: 288 GPM
  • RTAA-90: 324 GPM
  • RTAA-100: 360 GPM
  • RTAA-110: 396 GPM
  • RTAA-125: 450 GPM
  • Number of Coils: 4
  • Height of the Coil: 42 inches
  • The length of the coil is as follows:
  • RTAA-70: 13 feet
  • RTAA-80: 13 feet
  • RTAA-90: 14 feet
  • RTAA-100: 14 feet
  • RTAA-110: 17 feet
  • RTAA-125: 17 feet
  • Depending on the model, it has 4 to 5 Fans which are 30 inches in diameter
  • Electrical Data:
  • The unit operates on 200/230/460/575 volts
  • Most Applicable Full Load Amp: each models respective data table.
  • Logic Control: Employs Adaptive Control™ featuring a Clear Language Display Engine.
  • There are model basis settings for compressor overload dip switches.
  • There is an option to use a remote display unit that can be connected to the unit to display its operations from a distance.
  • Type of Package Unit: Oil and Refrigerant Charged, wired in the factory, leak tested and dehydrated.

Frequently Asked Questions

Q1: Nominal capacity limits for RTAA series can be in what metric ton range?

A1: Between 70-125 tons.

Q2: Which refrigerant does the RTAA series cold water product use?

A2: It incorporates HCFC-22 as a refrigerant.

Q3: What is the normal ambient temperature range for standard units in operation?

A3: For standard units post 15F ambient temperature it becomes feasible to operate them.

Q4: Is there a configuration available to supervise RTAA unit from a different location?

A4: Yes, a remote display can be operated to monitor unit's operation from a different location.

Q5: What is the procedure for charging the equipment to ensure there's no leakage?

A5: Equipment is charged with refrigerant and oil in factory before sending for shipment.

Q6: RTAA Units nMaintainance kya door hoing protectors

A6: Kool cleaning, oil checking and refrigerant charge monitoring is little bit regular maintenance.

Q7: What Power Supply is required to the RTAA series.

A7: RTAA series Power supply is needed for 3-phase supply with 200 VBox, 230, 460 and 575 volts.

User Manual

Sterling RTAA-70, RTAA-90, RTAA-80, RTAA-IOM-4A, RTAA-IOM-4 User Manual