Sterling RSG, RSG 25, RSG 45, RSG 35 Series Manual

Page 1
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
RSG SERIES TUBE HEATERS
RSG 25 RSG 35 RSG 45
(Check One)
NATURAL GAS PROPANE GAS
(Check One)
RSGS-2
EQUIPMENT USED:
ACCESSORIES:
Chain Mounting Kit:
Thermostat:
Gas Pressure Regulator:
Gas Shut-Off Valve:
Combustion Air Cap:
Other:
Other:
3/17
PROJECT:
UNIT TAG:
260 North Elm St., Westeld, MA 01085
(413) 564-5540 Fax: (413) 562-5311
www.sterlinghvac.com
Page 2
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
1) GENERAL INFORMATION
This heater complies with ANZI Z83.20 (current standard) and CSA 2-34.
This heater is a self-contained infrared radiant tube heater for use in locations where ammable gases or vapors are not generally present (as dened by OSHA acceptable limits) and is intended for space heating of garages, vestibules and entry ways, workshops, enclosed patios, golf practice ranges and most industrial and commercial applications.
DO NOT install this heater in residential bedrooms or bathrooms, mobile homes or recreational vehicles.
For indoor installation only. Not for use in residential dwellings.
INSTALLATION REQUIREMENTS
The installation must conform to local building codes or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA54 or the Natural Gas and Propane Installation Code CSA B149.1. Heaters shall be installed by a licensed contractor or licensed installer. Clearances to combustibles as outlined in this manual should always be observed. In areas used for
storage of combustible materials where they may be
stacked below the heater, NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to maintain the required
clearances from the heater to combustibles.”
Every heater shall be located with respect to building construction and other equipment so as to permit access to the heater. Each installer shall use quality installation practices when locating the heater and must give consideration to clearances to combustible materials, vehicles parked below, lights, overhead doors, storage areas with stacked materials, sprinkler heads, gas and electrical lines and any other possible obstructions or hazards. Consideration also must be
given to service accessibility.
The heater, when installed in aircraft hangars and public garages, must be installed in accordance with ANSI/NFPA 409-latest edition (Standard for Aircraft Hangars), ANSI/NFPA 88a-latest edition (Standard for Parking Structures), and ANSI/NFPA 88b-latest edition (Standard for Repair Garages) with the following
clearances:
At least 10 feet above the upper surfaces of wings or
engine enclosures of the highest aircraft that may be
housed in the hangar and at least 8 feet above the oor in shops, ofces, and other sections of hangars
communicating with aircraft storage or service areas.
At least 8 feet above the oor in public garages.
Minimum clearances marked on the heater must be maintained from vehicles parked below the heater.
FOR CANADA ONLY
a. Installation of this appliance is to be in accordance
with latest edition of CSA B149.1 (Natural Gas and Propane Installation Code).
b. For installation in public garages or aircraft
hangars, the minimum clearances from the bottom
of the infrared heater to the upper surface of the
highest aircraft or vehicle shall be 50 percent
greater than the certied minimum clearance, but the clearance shall not be less than 8 feet.
Although these heaters may be used in many
applications other than space heating (e.g., process heating), Sterling will not recognize the warranty for any use other than space heating.
This heater is for Indoor Installation and Covered Patio Installation only and can be used in either Vented or Unvented mode. The term Unvented actually means Indirect Vented. While the products of combustion are expelled into the building, national codes require ventilation in the building to dilute these products of combustion. This ventilation may be provided by
gravity or mechanical means.
This heater is not an explosion proof heater.
Where the possibility of exposure to volatile and low ash point materials exists, it could result in property damage or death. This heater must not be installed in a spray booth where the heater can operate during the spraying process. Consult your local re marshal or
insurance company.
High Altitude:
Appliances are supplied as standard for altitudes of 0 to 2,000 feet (0-610 m). High-altitude ratings are obtained by a change in the orice size. When ordered for high altitude installations, burners are supplied by the factory ready for high altitude installation. Check the nameplate for altitude before proceeding with the installation. In Canada the adjustment for altitude is made in accordance with Standard CGA 2.17, Gas­Fired Appliances for Use at High Altitudes.
2
Page 3
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
2) MINIMUM CLEARANCES TO COMBUSTIBLES
Minimum clearances to combustibles shall be
measured from the outer surfaces as shown in the following diagram. For reduced clearances below the heater, use the Deector Kit (Part No. 43504010), described in Section 5, and maintain the minimum
when stored under the heater, will be subjected to radiant heat and could be seriously damaged. Observe the Minimum Clearances to Combustibles listed in the manual and on the heater at all times.
Certain materials or objects,
clearances specied in the notes below. Follow the instructions packaged with the kit for installation.
MINIMUM CLEARANCES TO COMBUSTIBLES
Mounted Horizontally Angle Mounted at 45°
Model No. Sides Ceiling
RSG 25 8" 4" 41" * 8" 30" 4"
RSG 35, 45 12" 4" 57" ** 8" 40" 4"
1
The clearance is 12" when installed in an UNVENTED conguration in industrial and commercial installations.
2
IN CANADA, clearances below the heater are: RSG 25 - 36" (27" with deector); RSG 35/45 - 48" (36" with deector)
* The clearance is 33" with deector.
** The clearance is 42" with deector / 30" side clearance with deector.
NOTE:
1. The clearances specied above must be maintained to combustibles and other materials that may be damaged by temperatures 90°F above ambient temperature. Clearances to combustibles are posted on the control box. In areas used for storage of
combustible materials where they may be stacked below the heater, NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles.” Sterling recommends posting these signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.
2. The stated clearance to combustibles represents a surface temperature of 90°F (32°C) above room temperature. Building
materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower
temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
1
Below
2
Ends 45° Front 45° Rear
3
Page 4
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
3) SPECIFICATIONS
Flue
Heat Total @
Model Btu/hr Exchanger Heater Part Natural Gas Propane Gas @ 45°
No. Input Length Length I.D. Number Horizontal Angle
RSG 25 25,000 7/8" #42741120 #42 (0.094) 1.45mm (0.057) 8' 8'
RSG 35 35,000 16' 9'-3" 1" #42741041 #35 (0.110) 1.75mm (0.069) 8' 8'
RSG 45 45,000 1-1/8" #42741031 1/8" (0.125) 5/64” (0.078) 8' 8'
Restrictor Plate
Orice Size
Minimum
Mounting Height*
* MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and uniform energy distribution for complete building heating applications. Consult your Sterling representative for the particulars of your installation requirements.
Type Gas-Pipe Tube Flue Fresh Air Electrical Current
Gas Connection Diameter: Connection Connection Supply Rating
Natural or 1/2" MPT
Propane (Male) 60Hz, 1 Phase
Firing Rating Ignition System (Direct Spark)
Spark Module: 2 Amp 250V (for 24V Circuit) 30 second pre-purge period
3" 4" Round 4" Round
120 Volt,
2.6 Amp
4
Page 5
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
4) DIMENSIONS
5
Page 6
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
5) ACCESSORY PACKAGES
A. Exhaust Hood Package, Part #42924000
Contains:
Exhaust Hood Assembly, #42925540…...................… QTY–1
#8-18 x 1/2 Self-Drilling Screws, #02189030…........… QTY–2
B. Deector Kit, Part #43504010 The Deector Kit is available for use to reduce the
clearances to combustibles below the heater. Refer to the “Minimum Clearances to Combustibles Table”
in Section 2 when using this Deector Kit. Heater must be mounted ONLY in the horizontal position when using this kit.
6
Page 7
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
6) GAS CONNECTIONS AND REGULATIONS
US ONLY: A gas connector certied for use on a tubular type infrared heater per the standard for Connectors for Gas Appliances, ANSI Z21.24/CSA
6.10 is supplied for installation in US only. The gas
connector is 36" long and 1/2" nominal ID, and must be installed as shown above, in one plane, and without sharp bends, kinks or twists.
CANADA ONLY: A Type I hose connector should be used that is certied as being in compliance with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas (CAN/CGA 8.1) and is of length of 36+/- 6 in (90+/- 15 cm). The gas connector must be installed as shown above, in one plane, and without sharp bends, kinks or twists.
7
Page 8
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
7) GAS PRESSURE TABLE
GAS TYPE MANIFOLD PRESSURE Minimum* Maximum
Natural Gas 3.5" W.C. 5" W.C. 14" W.C.
Propane Gas 10.0" W.C. 11" W.C. 14" W.C.
*Minimum permissible gas supply pressure for purpose of input adjustment.
SUPPLY PRESSURE
This appliance is equipped with a step-opening, combination gas valve. The maximum supply pressure to the appliance is 14" W.C. or 1/2 P.S.I. If the line pressure is more than the maximum supply pressure, then a second stage regulator which corresponds to the supply pressure must be used.
8
Page 9
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
8) ELECTRICAL CONNECTIONS
INTERNAL CONNECTION WIRING DIAGRAM — Direct Spark Ignition
9
Page 10
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
9) THERMOSTAT CONNECTION WIRING DIAGRAMS
A. LINE VOLTAGE (120V) THERMOSTAT CONNECTIONS – SINGLE HEATER PER THERMOSTAT
B. LINE VOLTAGE (120V) THERMOSTAT CONNECTIONS – MULTIPLE HEATERS PER THERMOSTAT
10
Page 11
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
C. LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS – SINGLE HEATER PER THERMOSTAT
Order 24V Relay Kit (Part No. 43274020) for Low Voltage (24V) thermostat connection.
NOTES: a. If any of the original wire as supplied with the appliance must be replaced, it must be replaced with
wiring material having a temperature rating of at least 105°C. (18 Ga. CSA 600V Type TEW)
b. When connecting the supply circuit to the heater, wiring material having a minimum size of 14 AWG
and a temperature rating of at least 90°C shall be used.
c. A replaceable 2-amp fuse (1-1/4" long) is located inside the control box.
D. LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS – MULTIPLE HEATERS PER THERMOSTAT
11
Page 12
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
10) VENTING
A. BASIC FLUE VENTING — Venting must comply
with the latest edition of the National Fuel Gas Code (ANSI Z223.1-latest edition) or the authority having jurisdiction. Other venting references are in the equipment volume of the ASHRAE Handbook.
Heat Exchanger
Model
RSG 25 15 100 75 50
RSG 35 15 100 75 50
RSG 45 15 100 75 50
SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)
Note: For residential applications, the heater must not be connected to a separate chimney, but must
be installed using the venting system specied
below.
1. When venting the heater to outside of building
through a roof, use single-wall metal pipe. This
is to be constructed of galvanized sheet metal or other approved noncombustible corrosion-resistant material as allowed by state or local codes.
2. A vent passing through a combustible roof shall
extend through an approved clearance roof thimble. Double-wall, Type B vent must be used for the
portion of the vent system which passes through
the combustible roof. An approved vent cap must be attached to end of the ue.
3. The maximum equivalent length of vent pipe should
be carefully observed. A safety switch in the heater is designed to shut the heater off before excessive ue restriction causes bad combustion. Refer to the Vent Sizing Table for maximum vent lengths and vent pipe diameter.
• Minimum Equivalent Length = 5 ft. of pipe
• Maximum Equivalent Length = 75 ft. of pipe
Length ft
Vertical Venting Sidewall Venting
Maximum Vent Length ft.
(4" Diameter)
Use the following correction factors to obtain the
equivalent length:
• Subtract 15 ft. if the run is horizontal.
• Subtract 10 ft. for an approved vent cap.
• Subtract 10 ft. for each elbow beyond 15 ft.
from the heater.
• Subtract 15 ft. for each elbow within 15 ft. of the heater.
4. Joints between sections of piping shall be fastened
by sheet metal screws or other approved means and should be sealed to prevent leakage of ue gas into building. For Residential Installations: The seams along the length of the piping and the joints between sections of piping should be sealed to prevent a potential leakage of ue gas into building. Use 100% RTV Silicone Rubber Adhesive sealant suitable for 500°F. For Commercial and Industrial Installations: Use aluminum or Teon tape suitable for 550°F (3M Company tapes 433 or
363) or RTV silicone sealant.
5. Avoid locating elbows in the rst 5' of vent pipe
whenever possible. Limit to (2) 90° elbows.
When vent pipe is in a horizontal run, it must
have 1/4 inch per foot rise.
6. All portions of the vent pipe shall be supported to
prevent from sagging (6' spacing is recommended).
Maximum Fresh Air
Intake Length ft
(4" Diameter)
12
Page 13
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
7. When the vent pipe passes through areas where the ambient temperature is likely to induce condensation of the ue gases, the vent pipe should be insulated and a condensation drain should be provided.
8. Minimum clearance for single-wall ue pipe to
combustible material shall be 6 inches. This may
be reduced when the combustible material is protected as specied in the National Fuel Gas Code or the authority having jurisdiction.
9. Single-wall metal pipe shall not originate in any
unoccupied attic or concealed space and shall not pass through any attic, inside wall or concealed space, or through any oor. For the installation of a single-wall metal pipe through an exterior combustible wall, refer to latest edition of the National Fuel Gas Code or the authority having jurisdiction.
10. A venting system shall terminate at least 3 ft. above any forced air inlet located within 10 ft.
13
Page 14
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
This heater, when horizontally vented, must be installed with the approved venting system. When venting the heater horizontally through a combustible outside sidewall, the same requirements listed previously for venting Vertical Through The Roof apply except
as follows:
1. For horizontal venting, the vent lengths may be as follows:
• Minimum Equivalent Length = 5 ft. of pipe
• Maximum Equivalent Length = 75 ft. of pipe
Use the following correction factors to obtain the
equivalent length:
• Subtract 15 ft. if the run is horizontal.
• Subtract 10 ft. for an approved vent cap.
• Subtract 10 ft. for each elbow beyond 15 ft.
from the heater.
• Subtract 15 ft. for each elbow within 15 ft.
of the heater.
NOTE: To minimize problems associated with condensation in long horizontal runs, vent pipe can be insulated.
2. The horizontal venting system approved with this
heater consists of the following components: one
4" Vent Cap (Part #30297040, one 4" x 36" ‘B’ Vent Section (Part #30496360), and one 4" Wall Thimble (Part #30500040). Please specify the appropriate
number of 24-inch sections of single-wall vent
pipe and elbows when ordering: Vent Pipe (Part #30497240), 90° Elbows (Part #30498040), and 45° Elbows (Part #30499040).
3. Avoid locating elbows in the rst 5 feet of vent pipe whenever possible. Limit the quantity of 90° elbows to two (2). When vent pipe is in a horizontal run, it must be pitched downward 1/4 inch per foot towards the vent terminal. The heater must be installed level.
4. A minimum clearance of 18 inches must be maintained between the outside wall and vent cap (18" clearance will provide stability under high wind conditions).
5. The horizontal venting system shall not terminate:
• Less than 4 ft. (1.2m) below, 4 ft. (1.2m)
horizontally from or 1 ft. (30cm) above any door, operable window or gravity air inlet into any building. The bottom of the vent terminal shall be located at least 7 ft. (2.1m) above grade or above snow accumulation level as determined by local codes.
• Less than 3 ft. (0.9m) from a combustion air inlet.
• Less than 3 ft. (0.9m) from any other building
opening or any gas service regulator.
• Less than 7 ft. (2.1m) above public walkways.
• Directly over areas where condensate or vapor
could create a nuisance or hazard or be harmful
to the operation of gas utility meters, regulators,
relief valves, or other equipment. Building materials should be protected from ue gases and condensate.
• Less than 12 inches (0.30m) when directly below
a combustible overhang.
6. In regions of the country where prevailing winds
are consistently higher than 40 mph, it may be necessary to terminate the vent system above the roof level.
14
Page 15
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
MULTIPLE HEATER VENTING (CONNECTIONS INTO A COMMON VENT OR MANIFOLD)
Requirements for venting of multiple heaters are the same as described for “SINGLE HEATER VENTING” except as follows:
1. The common vent size and total vent height is normally determined by the number of heaters per
common vent, length of horizontal connector runs,
and connector rise. Connector lengths should be as short as possible and have a minimum 1/4 inch per foot rise. Without regard to connector rise and total vent height due to many possible venting congurations, the following should be observed:
a) Common vent pipe & vent connector diameter
should be no less than that shown in the
following Vent Sizing Table.
b) The connector length should be no more than
75% of the vertical portion of vent above the
connector.
c) Where possible, use a Y-connector to the
common vent.
2. Material for connectors should be constructed of galvanized sheet metal or other approved
noncombustible corrosion resistant material as
allowed by state or local codes. All common vent pipe should be insulated ue pipe or double-wall, Type B vent.
3. Avoid unnecessary bends. Limit to two (2) 90° elbows.
4. The entire length of vent connector shall be
readily accessible for inspection, cleaning and
replacement.
5. Groups of heaters with a common vent must be
controlled by a common thermostat.
Multiple Heater Vertical Venting Arrangement
15
Page 16
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
Multiple Heater Venting (Connections into a Manifold)
VENT SIZING TABLE — Multiple Heater Venting
Number of Heaters
1 2 3 4 5
RSG 25 4" 4" 4" 5" 5"
RSG 35 4" 4" 5" 5" 6"
RSG 45 4" 4" 5" 5" 6"
Common Vent Diameter (If a size is not available use the next larger size.)
The above illustrations and Table of Vent Sizes for Common Venting of Multiple Heaters are in accordance with the National Fuel Gas Code ANSI Z223.1-latest edition, NFPA 54-latest edition,
Equipment Volume of 1988ASHRAE handbook, current CAN/CGA-B149.1/2-M86 Installation Code, and AGA publication no. 10M5.85 2.5-2
on Fundamentals of Gas Appliance Venting and Ventilation-revised but are not a part of the CSA
certication.
B. INDIRECT VENTING (UNVENTED HEATERS) — COMMERCIAL AND INDUSTRIAL INSTALLATIONS ONLY — This heater requires ventilation in the building
to dilute the products of combustion and provide fresh air for efcient combustion. Where unvented heaters are used, gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input of installed heaters. Exhaust vents must be located at the highest point above and in the vicinity of the heaters, and the inlet vents must be located below the level of the heaters. An exhaust hood (Part #42924000) must be placed on the outlet collar of the draft inducer or on the existing 4" starting collar when used unvented and must be mounted only in an upright position and directed towards the reector body as shown.
16
Page 17
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
11) AIR FOR COMBUSTION
If indoor combustion air is to be supplied for a tightly enclosed area, one square inch of free area opening shall be provided below the heater for each 1,000 Btu/hr per hour of heater input. When outside air is used, the opening below the heater shall be one square inch of free area for each 4,000 Btu/hr of heater input.
In contaminated atmospheres or high humidity areas, optional outside air for combustion is recommended. Adequate clearances around the perforated fresh air plate must be maintained at all times. In larger open areas of buildings, inltration normally is adequate to provide air for combustion.
12) DIRECT OUTSIDE AIR FOR COMBUSTION
Outside combustion air should be supplied directly to the heater when the building is subject to negative pressure, or when contaminants or high humidity are present in the building air. These contaminants include
paints, solvents, corrosive vapors or any other foreign
particles that may cause damage to the heater or result
in poor combustion.
Outside combustion air can be brought directly to the heater by a 4" diameter duct less than 50 ft. long or equivalent (see table in Section 10 based on selected model and heat exchanger lengths). This is attached to the 4" diameter starting collar. The starting collar is tted to the top of the control box cabinet after rst removing and discarding the perforated cover. An approved vent cap must be placed directly on the end of the outside combustion air inlet pipe. The combustion air inlet should be not less than 3 ft. (0.9m), either vertically or horizontally, from the ue vent termination. The air intake terminal
must be located not less than 1 ft. (30cm) above grade. It is good installation practice to supply
combustion air from the same pressure zone as the vent outlet. Avoid bringing combustion air to the heater from an attic space. There is no guarantee
that adequate combustion air will be supplied.
In colder climates, where necessary, insulate the outside combustion air duct. Avoid locating the outside combustion air duct directly above the control box. Provide a capped cleanout T as necessary. In high humidity applications, the control box should be sealed
with silicone sealer.
In multiple heater applications, the combustion air
intake may be ducted individually or common ducted in the same conguration as shown for venting in Section
10. For combustion air intake duct sizing, please refer to
the Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.
17
Page 18
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
18
Page 19
STERLING “RSG” SERIES INFRARED RADIANT TUBE HEATER
13) SEQUENCE OF OPERATION
The chart below shows the sequence of operation for the normal operating cycle.
If the ame is not sensed during sequence T3 then the burner will automatically begin ignition sequence T2. If the ame is not re-established the heater will go to lockout.
19
Page 20
Warranty
INFRARED HEATER
Sterling (“the Manufacturer”) warrants to the original owner at the original installation site that the Sterling Model Infrared Heater will be free from defects in material and workmanship for one (1) year from the date of shipment from the factory. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the product which is shown to be defective.
Extended warranty:
In addition to the warranty stated above the following models will have:
RSG – Tubes shall be free from defects in material and workmanship for ve (5) years from the date of
shipment from the factory. Burner Head shall be free from defects in material and workmanship for ten (10) years from the date of shipment from the factory.
This limited warranty does not apply:
a) If the Product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has not
been installed, maintained or operated in accordance with the furnished written instructions, or has been altered
or modied in any way by an unauthorized person. b) To any expenses, including labor or material, incurred during removal or reinstallation of the Product. c) To any damage due to corrosion by chemicals, including halogenated hydrocarbons, precipitated in the air. d) To any workmanship of the installer of the Product.
This limited warranty is conditional upon:
a) Advising the installing contractor, who will in turn notify the distributor or manufacturer. b) Shipment to the Manufacturer of that part of the Product thought to be defective. Goods can only be returned
with prior written approval of the Manufacturer. All returns must be freight prepaid. c) Determination in the reasonable opinion of the Manufacturer that there exists a defect in material or workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO DE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH JURISDICTION.
260 North Elm St., Westeld, MA 01085
(413) 564-5540 Fax: (413) 562-5311
www.sterlinghvac.com
Loading...