Sterling RF-60, RF-75, RF-90, RF-30, RF-45 User Manual

Page 1
(S) DSLPRFM-1
J30-06933 Rev. A
INSTALLATION INSTRUCTIONS AND PARTS LIST
TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS
– FOR RESIDENTIAL INSTALLATIONS –
ATTENTION:
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE REFERENCE.
READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE
Model No.
Serial No.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do
not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call your fire department.
Improper installation, adjustment, alteration, service, or maintenance can
cause property damage, injury, or death. Read the installation, operating, and maintenance instruction thoroughly before installing or servicing this equipment.
10/05
APPROVED FOR USE IN CALIFORNIA
Install, operate, and maintain unit in accordance with the manufacturer's
instructions to avoid exposure to fuel substances, or substances from incomplete combustion, which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.
INSTALLER'S RESPONSIBILITY
Installer Please Note: This equipment has been test fired and inspected. It has been
shipped free from defects from our factory. However, shipment and installation problems such as loose wires, leaks, or loose fasteners may occur. It is the installer's
responsibility to inspect and correct any problem that may be found.
RECEIVING INSTRUCTIONS
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 564-5540 FAX: (413) 562-5311
www.sterlinghvac.com
MODELS: RF-30, 45, 60, 75, 90
Please utilize this toll free number to contact your local representative 800-490-2290.
HVAC PRODUCTS
Page 2
TABLE OF CONTENTS
SPECIFICATIONS
Basic Description .................................................... 2
Performance & Specification Data .......................... 4
GENERAL SAFETY INFORMATION
Installation Codes ................................................ 2, 3
Special Precautions ............................................ 2, 3
INSTALLATION
Locating Units ..................................................... 5, 6
Combustion Air .................................................... 5, 6
Proper Clearances .............................................. 5, 6
Suspension of Units ............................................ 5, 6
Gas Supply Piping ............................................... 7, 8
ELECTRICAL CONNECTIONS ............................. 9, 10
NOTICE: It is the equipment owners responsibility to provide any scaffolding or other apparatus required to perform emergency service or annual/periodic maintenance to this equipment.
VENTING ................... 11, 12, 13, 14, 15, 16, 17, 18, 19
OPERATION
Explanation of Controls and Operation ................. 20
Main Burner Orifice Schedule ............................... 21
Adjustments .......................................................... 21
High Altitude Operation ...................................21, 22
MAINTENANCE
Servicing & Cleaning ............................................. 22
TROUBLESHOOTING GUIDE.................23, 24, 25, 26
IDENTIFICATION OF PARTS..............................27, 28
WARRANTY...............................................................29
INSPECTION SHEET ................................................ 30
DESCRIPTION
The Residential Tubular Gas Fired Unit Heater is a factory assembled, power vented, low static pressure type propeller fan unit heater designed to be suspended within the space to be heated. THESE HEATERS ARE NOT TO BE CONNECTED TO DUCTWORK. These Tubular Unit Heaters are design certified under ANSI Z83.8 for Industrial/Commercial use and CSA . 10.96
U.S. (2nd ed.) “Unit Heaters for Residential Installation”. The designs are certified by ETL as providing a minimum of 80% thermal efficiency, and approved for use in California. Do not alter these units in any way. If you have any questions after reading this manual, contact the manufacturer.
Figure 1 - Tubular 30 thru 90 Propeller Unit Heaters
See Identification of Parts throughout this manual.
The following terms are used throughout this manual, in addition to the ETL requirements to bring attention to the presence of potential hazards, or to important information concerning the product:
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury, or substantial property damage.
Indicates an imminently hazard­ous situation which, if not avoided, could result in death, serious injury, or substantial property damage.
situation which, if not avoided, may result in minor injury or property damage.
NOTICE: Used to notify of special instructions on installation, operation, or maintenance which are important to equipment but not related to personal injury.
Indicates an imminently hazardous
2
Page 3
GENERAL SAFETY INFORMATION
Failure to comply with the general safety information may result in extensive property damage, severe personal injury, or death.
This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.
Installation must be made in accordance with local codes, or in absence of local codes, with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No. 54) National Fuel Gas Code. All of the ANSI
and NFPA Standards referred to in these installation instructions are those that were applicable at the time the design of this appliance was certified.The ANSI Standards are available from CSA Information Services 1-800-463-6727. The NFPA Standards are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
If installed in Canada, the installation must conform with local building codes, or in the absence of local building codes, with CGA-B149.1 "Installation Codes for Natural Gas Burning Appliances and Equipment" or CGA-B149.2 "Installation Codes for Propane Gas Burning Appliances and Equipment." These unit heaters have been designed and certified to comply with CGA 2.6.
Make certain that the power source conforms to the electrical requirements of the heater.
Do not depend upon a thermostat or other switch as sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric shock.
Special attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a ground conductor between the service panel and the heater. To ensure a proper ground, the grounding means must be tested by a qualified electrician.
Do not insert fingers or foreign objects into heater or its air moving device. Do not block or tamper with the heater in any manner while in operation, or just after it has been turned off, as some parts maybe hot enough to cause injury.
This heater is intended for general heating applications ONLY. It must NOT be used in potentially dangerous locations such as flammable, explosive, chemical-laden, or wet atmospheres.
Do not alter the unit heater in any way or damage to the unit and/or severe personal injury or death may occur!
Disconnect all power and gas supplies before installing or servicing the heater. If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power. Failure to do so could result in fatal electric shock, or severe personal injury.
Ensure that all power sources conform to the requirements of the unit heater, or damage to the unit will result!
Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wiring should be done and checked by a qualified electrician, using copper wire only. All gas connections should be made and leak­tested by a suitably qualified individual, per instructions in this manual. Also follow procedures listed on "Gas Equipment Start-Up Sheet" located in this manual.
Use only the fuel for which the heater is designed (see rating plate). Using LP gas in a heater that requires natural gas, or vice versa, will create risk of gas leaks, carbon monoxide poisoning, and explosion.
Do not attempt to convert the heater for use with a fuel other than the one intended. Such conversion is dangerous, as it will create the risks previously listed.
Do not attach ductwork to this product or use it as a makeup air heater. Such usage voids the warranty and will create unsafe operation.
In cases in which property damage may result from malfunction of the heater, a back-up system or temperature sensitive alarm should be used.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
The open end of piping systems being purged shall not discharge into areas where there are sources of ignition or into confined spaces UNLESS precautions are taken as follows: (1) by ventilation of the space, (2) control of the purging rate, (3) elimination of all hazardous conditions. All precautions must be taken to perform this operation in a safe manner!
Unless otherwise specified, the following conversions may be used for calculating SI unit measurements: 1 foot = 0.305 m 1 inch = 25.4 mm 1 gallon = 3.785 L 1 pound = 0.453 kg 1 psig = 6.894 kPa 1 cubic foot = 0.028m
1000 BTU/cu. ft. = 37.5 MJ/m 1000 BTU per hour = 0.293 kW 1 inch water column = 0.249 kPa liter/second = CFM x 0.472 meters/second = FPM ÷ 196.8
3
3
3
Page 4
Table 1 - Performance and Dimensional Data - Tubular 30 thru 90 Propeller Unit Heater
Unit Size 30 45 60 75 90 PERFORMANCE DATA†
Input - BTU/Hr. 30,000 45,000 60,000 75,000 90,000 (kW) (8.8) (13.2) (17.6) (22.0) (26.4) Output - BTU/Hr. 24,300 36,450 48,600 60,750 72,900 (kW) (7.1) (10.7) (14.2) (17.8) (21.4) Thermal Efficiency (%) 81 81 81 81 81 Free Air Delivery - CFM 500 750 1,000 1,250 1,500 (cu. m/s) (0.236) (0.355) (0.473) (0.591) (0.710) Air Temperature Rise - Deg. F 45 45 45 45 45 (Deg. C) (25) (25) (25) (25) (25) Full Load Amps at 120V 3.0 3.0 3.7 3.7 4.8
MOTOR DATA: Motor HP 1/20 1/20 1/20 1/20 1/20
DIMENSIONAL DATA - inches (mm)
“A” Jacket Height 12 12 17-3/4 17-3/4 17-3/4
“B” Overall Height 13 13 18-3/4 18-3/4 18-3/4
“C” Overall Depth 25-1/2 25-1/2 26-3/4 26-3/4 26-3/4
“Center Line” Height of Flue* 7-1/4 7-1/4 10-1/2 10-1/2 10-1/2
“Center Line” Electric Connection 10-1/4 10-1/4 16 16 16
“F” Discharge Opening Height 10-1/2 10-1/2 16-1/4 16-1/4 16-1/4
“G” Fan Diameter-in 10 10 16 16 16 Unit Weight - lbs. 62 68 87 93 95 (kgs) (28) (31) (39) (42) (43) Shipping Weight - lbs. 72 78 102 108 110 (kgs) (33) (35) (46) (49) (50)
* For all installations, the flue collar is included with the unit and should be field installed per the instructions included with the unit.
† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea
level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54), (also refer to Table 6).
For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certification.
Motor (kW) (0.04) (0.04) (0.04) (0.04) (0.04) Motor Type SP SP SP SP SP R.P.M. 1650 1650 1050 1050 1050 Motor Amps @ 115V 1.9 1.9 2.6 2.6 2.6
(305) (305) (451) (451) (451)
(330) (330) (476) (476) (476)
(648) (648) (679) (679) (679)
(184) (184) (267) (267) (267)
(260) (260) (406) (406) (406)
(267) (267) (413) (413) (413)
DIMENSIONS .XXX STANDARD UNITS DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 2 - Dimensional Drawing – Tubular 30 thru 90 Propeller Unit Heater
4
Page 5
INSTALLATION
Do not install unit heaters in corrosive or flammable atmospheres! Premature failure of, or severe damage to the unit will result!
Avoid locations where extreme drafts can affect burner operation. Unit heaters must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!
Since the unit is equipped with an automatic gas ignition system, the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray, rain or dripping water.
NOTICE: Location of unit heaters is related directly to the selection of sizes. Basic rules are as follows:
MOUNTING HEIGHT: If the unit heater is installed in a
garage, it must be installed with a minimum clearance above the floor of 18 inches (457mm).
AIR DISTRIBUTION: Direct air towards areas of maximum heat loss. When multiple heaters are involved, circulation of air around the perimeter is recommended where heated air flows along exposed walls. Satisfactory results can also be obtained where multiple heaters are located toward the center of the area with heated air directed toward the outside walls. Be careful to avoid all obstacles and obstructions which could impede the warm air distribution patterns.
AIR FOR COMBUSTION: The unit heater shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting, and the maintenance of ambient air at safe limits under normal conditions of use. The unit heater shall be located in such a manner as not to interfere with proper circulation of air within the confined space. When buildings are so tight that normal infiltration does not meet air requirements, outside air shall be introduced per Sections 1.3.4.2 and 1.3.4.3 of ANSI Z223.1 for combustion requirements. A permanent opening or openings having a total free area of not less than one square inch per 5,000 BTU/Hr (1.5 kW) of total input rating of all appliances within the space shall be provided.
NOTICE: Unit Heater sizing should be based on heat loss calculations where the unit heater output equals or exceeds heat loss.
CLEARANCES: Each Gas Unit Heater shall be located
with respect to building construction and other equipment so as to permit access to the Unit Heater. Clearance between vertical walls and the vertical sides of the Unit Heater shall be no less than 1 inch (25.4mm). However, to ensure access to the control box and fan, a minimum of 18" (457mm) is required for the fan, and control box side. A minimum clearance of 1 inch (25.4mm) must be maintained between the top of the Unit Heater and the ceiling. The bottom of the Unit Heater must be no less than 1 inch (25.4mm) from any combustible. The distance between the flue collector and any combustible must be no less than 1 inch (25.4mm). Also see AIR FOR COMBUSTION and VENTING sections.
Unit heaters should not be installed to maintain low temperatures and/or freeze protection of buildings. A minimum of 50°F (10°C) thermostat setting must be maintained. If unit heaters are operated to maintain
lower than 50°F (10°C), hot flue gases are cooled inside the heat exchanger to a point where water vapor (a flue gas by-product) condenses onto the heat exchanger walls. The result is a mildly corrosive acid that prematurely corrodes the aluminized heat exchanger and can actually drip water down from the unit heater onto floor surface. Additional unit heaters should be installed if a minimum 50°F (10°C) thermostat setting cannot be maintained.
NOTICE: Increasing the clearance distances may be necessary if there is a possibility of distortion or discoloration of adjacent materials.
MOUNTING: The Unit Heater may be mounted with the
vent outlet, gas and electrical connections to the right or left of the air moving fan. The Unit Heater is shipped with the connections to the right of the fan when looking in the direction of the air flow. If connections to the right are required, remove hanger brackets from face of unit and attach as pictured in Figure 3. If connections to the left are required, invert the heater (180°), mount the hanging brackets as above, and remove, invert, and replace the control access panel and the air discharge louvers.
5
Page 6
INSTALLATION (continued)
The Unit Heater may be mounted by fastening the hanging brackets directly to ceiling joists or by suspending from four rods. See Figures 3, 4 and 5.
Make certain that the lifting methods used to lift the heater and the method of suspen­sion used in the field installation of the heater are capable of uniformly supporting the weight of the heater at all times. Failure to heed this warning may result in property damage or personal injury!
Make sure that the structure to which the unit heater is to be mounted is capable of safely supporting its weight. Under no circumstances must the gas lines, the venting system or the electrical conduit be used to support the heater; or should any other objects (i.e. ladder, person) lean against the heater gas lines, venting system or the electrical conduit for support. Failure to heed these warnings may result in property damage, personal injury, or death.
Figure 3 - Hanger Bracket Installation Instructions
Figure 4 - Heater Mounting (Steel Construction)
Unit Heaters must be hung level from side to side and from front to back, see Figures 3, 4 and 5. Failure to do so will result in poor performance and/or premature failure of the unit.
Ensure that all hardware used in the suspension of each unit heater is more than adequate for the job. Failure to do so may result in extensive prop­erty damage, severe personal injury, or death!
Refer to Figures 3, 4 and 5 for suspension of units.
Figure 5 - Heater Mounting (Wood Construction)
6
Page 7
GAS PIPING
To avoid damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fire hazard.
Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak tests. These valves may not be completely shut off, exposing the gas valve to excessive pressure and damage.
PIPE SIZING
To provide adequate gas pressure to the gas unit heater, size the gas piping as follows:
1. Find the cu. ft./hr. by using the following formula:
Cu. ft./hr. =
Input
BTU
2. Refer to Table 2. Match “Length of Pipe in Feet” with appropriate “Gas Input - Cu. Ft./Hr.” figure. This figure can then be matched to the pipe size at the top of the column. Example: It is determined that a 67 foot (20.4m) run of gas pipe is required to connect a 75 MBTU gas unit heater to a 1,000 BTU/cu ft. (0.29kW) natural gas supply.
75,000 BTU/Hr
= 75 Cu. ft./hr.
1,000 BTU/cu. ft.
Using Table 2, a 3/4 inch pipe is needed.
NOTE: See General Safety Information section for English/Metric unit conversion factors.
NOTICE: If more than one unit heater is to be served by the same piping arrangement, the total cu. ft./hr. input and length of pipe must be considered.
NOTICE: If the gas unit heater is to be fired with LP gas, consult your local LP gas dealer for pipe size information.
NOTICE: HEATER INSTALLATION FOR USE WITH PROPANE (BOTTLED) GAS MUST BE MADE BY A QUALIFIED L.P. GAS DEALER OR INSTALLER. HE WILL ENSURE THAT PROPER JOINT COMPOUNDS ARE USED FOR MAKING PIPE CONNECTIONS; THAT AIR IS PURGED FROM LINES; THAT A THOROUGH TEST IS MADE FOR LEAKS BEFORE OPERATING THE HEATER; AND THAT IT IS PROPERLY CONNECTED TO THE PROPANE GAS SUPPLY SYSTEM.
Before any connection is made to the existing line supplying other gas appliances, contact the local gas company to make sure that the existing line is of adequate size to handle the combined load.
Table 2 - Gas Pipe Size
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less,
Nominal
Iron Internal Length of Pipe, Feet (meters)
Pipe Size Dia.
in. in. (3.0) (6.1) (9.1) (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)
1/2 0.622 175 120 97 82 73 66 61 57 53 50 44 40 37 35
3/4 0.824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135
1 1/4 1.380 1400 950 770 660 580 530 490 460 430 400 360 325 300 280
1 1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
2 2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020 950 850 800
2 1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280
3 3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280
4 4.026 23000 15800 12800 10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600
1. Determine the required Cu. Ft./Hr. by dividing the input by 1000. For SI/Metric measurements: Convert BTU/Hr. to kilowatts. Multiply the
units inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE GAS: Multiply the Cu. Ft./Hr. value by 0.633; then, use the table. 4. Refer to the metric conversion factors listed in the General Safety section for SI Unit measurement conversions.
10 20 30 40 50 60 70 80 90 100 125 150 175 200
(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)
(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)
(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)
(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)
(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)
(112) (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)
(178) (123) (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)
(311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6)
(651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)
and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)
(Based on a 0.60 Specific Gravity Gas)
7
Page 8
PIPE INSTALLATION
1. Install the gas piping in accordance with applicable local codes.
2. Check gas supply pressure. Each unit heater must be connected to a gas supply capable of supplying its full rated capacity as specified in Table 3. A field LP tank regulator must be used to limit the supply pressure to a maximum of 14 in. W.C. (3.5 kPa). All piping should be sized in accordance with the latest edition of ANSI Standard Z223.1 National Fuel Gas Code; in Canada, according to CGA-B149. See Tables 1 & 2 for correct gas piping size, and also refer to Tables 3, 5 and 6. If gas pressure is excessive on natural gas applications, install a pressure regulating valve in the line upstream from the main shutoff valve.
3. Adequately support the piping to prevent strain on the gas manifold and controls.
4. To prevent the mixing of moisture with gas, run the take-off piping from the top, or side, of the main.
5. Standard Unit Heaters are supplied with a combination valve which includes: a. Manual "A" valve b. Manual "B" valve c. Solenoid valve d. Pressure regulator Pipe directly into the combination valve (see Figure
6).
6. Gas valve has a pressure test post requiring a 3/32" hex head wrench to read gas supply and manifold pressures. Open 1/4 turn counterclockwise to read, turn clockwise to close and reseat. A 5/16" ID hose fits the pressure post.
7. Provide a drip leg in the gas piping near the gas unit heater. A ground joint union and a manual gas shutoff valve should be installed ahead of the unit heater controls to permit servicing. The manual shutoff valve must be located external to the jacket. (See Figure 6)
8. Make certain that all connections have been adequately doped and tightened.
Do not over tighten the inlet gas piping into the valve. This may cause stresses that will crack the valve!
NOTICE: Use pipe joint sealant resistant to the action of liquefied petroleum gases regardless of gas conducted.
Check all pipe joints for leakage using a soap solution or other approved method. Never use an open flame or severe personal injury or death may occur!
Figure 6 - Pipe Installation, Standard Controls
Never use an open flame to detect gas leaks. Explosive conditions may exist which may result in personal injury or death!
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system in excess of 1/2 psig (3.5 kPa).
Table 3 - Gas Piping Requirements
SINGLE STAGE GAS PIPING REQUIREMENTS*
GasType Natural Gas Propane (LP) Gas
Manifold 3.5 in. W.C. 10.0 in. W.C. Pressure (0.9 kPa) (2.5 kPa)
14.0 in. W.C. Max. 14.0 in. W.C. Max.
Supply Inlet (3.5 kPa) (3.5 kPa) Pressure
*
For single stage application only at normal altitudes.
5.0 in. W.C. Min. 11.0 in W.C. Min. (1.2 kPa) (2.7 kPa)
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
8
Page 9
ELECTRICAL CONNECTIONS
THERMOSTAT WIRING AND LOCATION:
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
Standard units are shipped for use on 115 volt, 60 hertz, single phase electric power. The motor name-plate and electrical rating of the transformer should be checked before energizing the unit heater electrical system. All external wiring must conform to the latest edition of ANSI/NFPA No. 70, National Electrical Code, and applicable local codes; in Canada, to the Canadian Electrical Code, Part 1, CSA Standard C22.1.
Do not use any tools (i.e. screwdriver, pliers, etc.) across terminals to check for power. Use a voltmeter.
It is recommended that the electrical power supply to each unit heater be provided by a separate, fused, and permanently live electrical circuit. A disconnect switch of suitable electrical rating should be located as close to the gas valve and controls as possible. Each unit heater must be electrically grounded in accordance with the latest edition of the National Electrical Code, ANSI/NFPA No. 70, or CSA Standard C22.1. Refer to Figures 7, 8 and 9.
NOTICE: The thermostat must be mounted on a vertical, vibration-free surface, free from air currents, and in accordance with the furnished instructions.
Mount the thermostat approximately 5 feet (1.5m) above the floor, in an area where it will be exposed to a free circulation of average temperature air. Always refer to the thermostat instructions, as well as our unit wiring diagram, and wire accordingly. Avoid mounting the thermostat in the following locations:
1. Cold Areas- Outside walls or areas where drafts may affect the operation of the control.
2. Hot Areas- Areas where the sun's rays, radiation, or warm air currents may affect the operation of the control.
3. Dead Areas- Areas where the air cannot circulate freely, such as behind doors or in corners.
THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:
The initial heat anticipator setpoint should equal the thermostat's current amperage draw when the unit is firing. This setpoint should be measured for the best results. Use the recommended ranges for a guide. If further information is needed, consult your thermostat manufacturer's instructions.
Recommended heat anticipator setting:
Unit Size: 30 thru 200 250 thru 400
For Tubular Units: 0.35 Amps 0.65 Amps
Figure 7 - Low-voltage Thermostat Wiring Single Stage
Figure 8 - T834H-1009 or T834H-1017 Thermostat Wiring
Honeywell
T834H-1009
or
T834H-1017
Thermostat
WR
G
Warning: Remove Jumper
between G and R
inside control panel
RGW1W2
NOTICE: The start-up fan delay should not exceed 30 seconds from a cold start.
IMPORTANT: For all wiring connections, refer to the wiring diagram shipped with your unit (either affixed to the side jacket or enclosed in the installation instructions envelope). Should any original wire supplied with the heater have to be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C.
D6922
9
Page 10
ELECTRICAL CONNECTIONS (continued)
Figure 9 - Tubular Propeller Units Equipped with a Rollout Switch
Tubular 30 thru 90 Unit Sizes with Natural and Propane (LP) Gas
NOTICE: See Figures 7, 8 and 9 for connecting the thermostat to the unit heater. If using a standard low voltage thermostat with a sub-base switch for fan control, remove the jumper between G and R. Connect the G terminal of the thermostat to the G terminal of the unit heater.
10
Page 11
VENTING*
All unit heaters must be vented! All Venting installations shall be in accordance with the latest edition of Part 7,
Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of local building codes. Refer to notes* below for Canadian installations. Refer to Figures 12-19.
CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts, or any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, inappropriate tiredness, or flu-like symptoms).
When an existing heater is removed or replaced in venting system, the venting system may not be properly sized to vent the attached appliances. An improperly sized vent system can cause formulation of condensate or leakage or spillage of flue gases.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system;
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace damper.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously.
5. After it has been determined that each appliance connected to the venting system properly vents when tested as outline above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous condition of use.
6. If improper venting is observed during any of the above tests, the venting system must be corrected immediately so that the system conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the venting system, the venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the National Fuel Gas Code, ANSI Z223.1.
The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
Venting into an unlined masonry chimney is prohibited.
ADDITIONAL REQUIREMENTS FOR CANADIAN INSTALLATIONS
*The following instructions apply to Canadian installations in addition to installation and operating instructions.
1. Installation must conform with local building codes, or in the absence of local codes, with current CGA-B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CGA-B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.
2. Any reference to U.S. standards or codes in these instructions are to be ignored and the applicable Canadian standards or codes applied.
11
Page 12
VENTING
ANSI now organizes vented appliances into four categories.
Category
I
Includes non-condensing appliances with negative vent
Venting Categories
Non
Condensing Condensing Negative Vent III Pressure
Positive Vent III IV Pressure
pressure, like the traditional atmospheric unit heater.
Category
II
Groups condensing appliances with negative vent pressure.
VERTICALLY VENTED UNIT HEATERS
(CATEGORY I)
Observe the following precautions when venting the unit: The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
Venting into an unlined masonry chimney is prohibited.
1. Use flue pipe of the same size as the flue connections on the gas unit heater, 4 inch (102mm). All heaters must be vented with UL Listed Type B vent, or single wall pipe.
2. Provide as long a vertical run of flue pipe at the gas unit heater as possible. A minimum of 5 feet (1.5m) of vertical flue is required. The top of the vent pipe should extend at least 2 feet (0.61m) above the highest point on the roof. Install a weather cap over the vent opening.
3. Slope horizontal runs upward from the gas unit heater at least 1/4-inch per foot (21mm/m) minimum. Horizontal runs should not exceed 33% of the vertical height of the vent pipe, or chimney, above the flue pipe connection, up to a maximum length of 10 feet (3m). Horizontal portions of the venting system shall be supported at maximum intervals of 4 feet (1.22m). (See Figure 12)
Category
III
Appliances are non-condensing and operate with a positive vent pressure.
Category
IV
Covers condensing appliances with positive vent pressure.
NOTICE: Category II and IV do not apply to equipment specified within this manual.
4. Use as few elbows as possible.
5. Tape flue pipe joints with high temp, RTV or foil face tape.
6. Avoid running vent pipe through unheated spaces.
7. When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minimum of 1/2 inch (12.7mm) thick foil faced fiberglass, 1-1/2# density insulation.
8. Do not damper the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of flue gas into the occupied space.
9. Avoid installing units in areas under negative pressure due to large exhaust fans or air conditioning. When required, a flue vent fan should be installed in accordance with the instructions included with the fan.
10. Vent connectors serving Category I and Category II heaters shall not be connected into any portion of mechanical draft systems operating under positive pressure.
11. Also refer to Figures 17 and 19 for additional requirements.
Figure 12
12
Page 13
HORIZONTALLY VENTED UNIT HEATERS
(CATEGORY I - U.S. RESIDENTIAL ONLY)
All venting of residential tubular unit heaters must comply with CSA International Requirement 10.96 U.S. for Unit Heaters for Residential Use (2nd Edition).
Category I horizontal venting arrangements are designed to be used with either single wall vent pipe or double wall (Type B) vent pipe. These arrangements must terminate external to the building using either single wall or double wall (Type B) vent. See Table 4 and Figures 13 and 14 for special installation requirements regarding these venting conditions.
An Amerivent Americap, Fields Starkap, or Metalbestos vent cap must be supplied by the customer for each power vented unit.
Termination Clearance Requirements
Structure
Door, window or any gravity vent inlet
Forced air inlet within 10 ft.
Adjoining building or parapet
Adjacent public walkways
Vent Systems
Minimum Clearances for
Termination Locations
4 feet below
4 feet horizontally
1 foot above
3 feet above
6 feet
7 feet above grade
Maintain 1 inch (25.4mm) between the vent pipe and combustible materials.
The vent terminal must be installed with a minimum horizontal clearance of 4 feet (1.2m) from electric meters, gas meters, regulators, and relief equipment.
The horizontal portion of the vent pipe must not exceed 8 feet (2.44m) for the 30 unit size or 10 feet (3.05m) for the 45 to 90 unit sizes. The minimum length for the horizontal portion of the vent pipe is 4 feet (1.22m). The vent system must be constructed as shown in Table 4 and Figure 13. The vent pipe and vertical extension must be supported as shown in Figure 14.
Seal all vent pipe joints and seams to prevent leakage. Use General Electric RTV-108, Dow-Corning RTV-732, or equivalent silicone sealant with a temperature rating of 500°F, or 3M #425 aluminum foil tape (or equivalent). The vent system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage. Install a tee with a condensate drain at the low point of the pipe (See Figure 13). As an alternate, a 3/8 inch diameter hole may be drilled at the low point of the pipe for condensate drainage.
The venting system for these appliances shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontal from, or 1 foot (0.3m) above any door, window, or gravity vent air inlet into the building.
The vent terminal must be at least 12 inches (305mm) from the exterior of the wall that it passes through to prevent degradation of the building material by flue gases.
The vent terminal must be at least 3 feet (1m) above grade, or in snow areas, at least 3 feet (1m) above the snow line to prevent blockage by snow.
Through the wall vent for these appliances shall NOT terminate over public walkways, or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
Horizontal portions of the venting systems shall be supported at maximum intervals of 4 feet (1.2m) to prevent sagging.
Insulate single wall vent pipe exposed to cold air or running through unheated areas.
Local codes may supersede any of the above provisions.
Each unit must have an individual vent pipe and vent terminal! Each unit MUST NOT be connected to
other vent systems or to a chimney.
13
Page 14
Table 4 - Category I Horizontal Venting Requirements
Vent Maximum Number Maximum Horizontal Minimum Extension Unit Diameter Elbows Vent Length Vertical Rise Distance Size (in) * (Ft.) (In.) from Wall
30 4 1 4 12 36
4181836 4241236 4281836
45 4 1 10 18 36
60 5 2 10 12 36
75 5 2 10 24 36
90 5 1 10 24 24
*
One elbow is required to make the vertical extension, See Figure 13.
4251836 5 2 10 12 36
5 2 10 36 24
Figure 13 - Category I Horizontal Venting Requirements
D-06838A
14
Page 15
Figure 14 - Vent Support
D- 06839A
15
Page 16
HORIZONTALLY VENTED UNIT HEATERS
(CATEGORY III)
All venting of residential tubular unit heaters must comply with the latest edition of CSA .10.96 (2nd ed.) requirement.
Category III horizontal venting arrangements are designed to use single wall vent pipe. These arrange­ments must terminate external to the building using either single wall or double wall (Type B) vent. See Figures 15, 16, and 18 for installa­tion requirements regarding these venting conditions. If double wall venting is used, components that are UL Listed and approved for Category III positive pressure venting systems must be used with one exception: a single 5 foot (1.52 M) section of 4 inch (102mm) Type B vent pipe with a draft hood connector may be used between the appliance vent connection and the vent terminal. Use Metalbestos Type B Gas Vent with a Metalbestos 4RV-DH Draft Hood Connector or Amerivent Type B Gas Vent with an Amerivent 4EDC Draft Hood Connector. See Figure 15A. If using a single section of Type B vent pipe, seal the annular space between the inner and outer sections of the draft hood connector with high temperature silicone sealant. See Figure 15B. Attach the draft hood connector to the appliance vent connection with screws and seal the joint with silicone sealant. Install a Type B vent thimble in the wall. Insert the vent pipe through the thimble and attach it to the adapter on the appliance. Seal the joint with silicone sealant or two wraps of aluminum foil tape. Install a vent cap on the outlet of the pipe and secure it with screws.
An Amerivent Americap, Fields Starcap, or Metalbestos vent cap must be supplied by the customer for each power vented unit. The vent pipe diameter MUST be 4 inches (102mm).
Vent Systems
Termination Clearance Requirements
Minimum
Structure
Door, window or any gravity air inlet
Forced air inlet within 10 ft.
Adjoining building or parapet
Adjacent public walkways
Clearances for
Termination
Locations
4 feet below
4 feet horizontally
1 foot above
3 feet above
6 feet
7 feet above grade
The venting system for these appliances shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontal from, or 1 foot (0.3m) above any door, window, or gravity vent air inlet into the building.
The vent terminal must be at least 12 inches (305mm) from the exterior of the wall that it passes through to prevent degradation of the building material by flue gases.
The vent terminal must be at least 1 foot (305mm) above grade, or in snow areas, at least 3 feet (1m) above the snow line to prevent blockage by snow.
Through the wall vent for these appliances shall NOT terminate over public walkways, or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
The vent pipe equivalent length must not exceed 30 feet (9.14m) for the 30 and 45 unit sizes, and 40 feet (12.2m) for the 60, 75 and 90 unit sizes. Equivalent length is the total length of straight sections PLUS 5 feet (1.52m) for each 90 elbow and
2.5 feet (0.76m) for each 45 elbow.
Maintain 1 inch (25.4mm) between the vent pipe and combustible materials.
The vent terminal must be installed with a minimum horizontal clearance of 4 feet (1.2m) from electric meters, gas meters, regulators, and relief equipment.
Seal all vent pipe joints and seams to prevent leakage. Use General Electric RTV-108, Dow-Corning RTV-732, or equivalent silicone sealant with temperature rating of 500°F; or 3M #425 aluminum foil tape (or equivalent). The vent air system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage.
Horizontal portions of the venting systems shall be supported at maximum intervals of 4 feet (1.2m) to prevent sagging (in Canada, support at 3 feet (1m) minimum intervals).
Insulate single wall vent pipe exposed to cold air or running through unheated areas. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minmum of 1/2 inch thick foil faced fiberglass, 1-1/2# density insulation.
Each unit must have an individual vent pipe and vent terminal! Each
unit MUST NOT be connected to other vent systems or to a chimney.
16
Page 17
Figure 15 - Category III Horizontal Venting Requirements Using Single Wall Vent Pipe
Figure 15A - Category III Horizontal Venting Requirements Using Type B Double Wall Vent Pipe
Figure 15B - Type B Draft Hood Connector
17
Page 18
Figure 16
VENTING (continued)
Figure 17
18
Page 19
Figure 18
VENTING (continued)
Figure 19
19
Page 20
OPERATION
POWER VENTED PROPELLER UNITS
DIRECT SPARK IGNITION
EXPLANATION OF CONTROLS (See Figure 20):
1. Each Unit Heater comes equipped with a power vent system that consists of a power venter motor and blower, pressure switch, and sealed flue collector in place of the conventional draft diverter.
2. The power venter motor is energized by the room thermostat through the integrated control board when a demand for heat is sensed. The pressure switch measures the flow through the vent system and energizes the direct spark ignition system beginning the pre-purge timing when the flow is correct.
The pressure switch MUST NOT be bypassed. The unit MUST NOT be fired unless the power venter is operating. An unsafe condition could result.
3. The direct ignition system consists of an ignition control module and a gas valve. When the pre-purge period ends, the spark ignition system is energized, and the gas valve opens to supply gas to the burners. When the thermostat is satisfied, the vent system is de-energized and the valve closes to stop the flow of gas to the unit.
4. The limit switch interrupts the flow of electric current to the control board, interrupting the flow of gas to the gas valve if the unit heater becomes overheated.
5. The flame roll-out switch interrupts the flow of electric current to the control board, interrupting the flow of gas to the unit heater in the event of sustained flame roll-out from the burner area. If this switch trips,
DETERMINE AND CORRECT THE CAUSE of the flame roll-out.
6. Once the thermostat is satisfied, or the limit switch interrupts the flow of electric current to the control board, the unit will begin a post-purge period. When the post-purge period ends, the power venter motor is de-energized.
7. The fan operation is delayed 30 seconds once the thermostat is closed, and continues operation for 30 seconds after the thermostat opens.The start-up fan delay
must not exceed 30 seconds from a cold start.
8. The wall thermostat, supplied optionally, is a temperature sensitive switch that operates the vent system and ignition system to control the temperature of the space being heated. The thermo­stat must be mounted on a vertical, vibration-free surface free from air currents and in accordance with the furnished instructions (also refer to Electrical Section).
START-UP (Also refer to lighting instruction plate equipped on the unit)
1. Open the manual gas valve in the gas supply line to the unit heater with union connection loose, purge air from the gas line. Tighten the union and check for leaks.
Never use an open flame to detect gas leaks. Explosive conditions may exist wich could result in personal injury or death.
2. Open the manual valve on the unit heater.
3. Turn ON the electrical power.
4. The unit should be under the control of the thermostat. Turn the thermostat to the highest point and determine that the power venter motor starts and the burners ignite. Turn the thermostat to the lowest point and determine that the power venter motor shuts off and the burners are extinguished.
5. Turn the thermostat to the desired position.
6. See Gas Input Rate and Adjustments sections.
SHUT DOWN
1. Turn the valve selector lever to the “OFF” position.
2. Turn off the electricity.
3. To relight, follow “start-up” instructions.
See Figure 20 for parts/identification.
Figure 20
20
Page 21
PRIMARY AIR SHUTTER ADJUSTMENT
Primary air adjustment is made at the factory. No field adjustments are necessary.
GAS INPUT RATE
Check the gas input rate as follows (Refer to General Safety Information section for metric conversions).
Never overfire the unit heater, as this may cause unsatisfactory operation, or shorten the life of the heater.
1. Turn off all gas appliances that use gas through the
same meter as the unit heater.
2. Turn the gas on to the unit heater.
3. Clock the time in seconds required to burn 1 cubic
foot of gas by checking the gas meter.
4. Insert the time required to burn one cubic foot of
gas into the following formula and compute the input rate.
3600 (Sec. per Hr.) X BTU/Cu. Ft.
= Input Rate
Time (Sec.)
For example: Assume the BTU content of one cubic foot of gas is 1000, and that it takes 48 seconds to burn one cubic foot of gas.
3600 x 1000 = 75,000
48
NOTICE: If the computation exceeds, or is less than 95% of the gas BTU/hr. input rating (see Table 1), adjust the gas pressure.
Adjust the gas pressure as follows:
1. NATURAL GAS: Best results are obtained when
the unit heater is operating at its full rated input with the manifold pressure of 3.5 inches W.C. (0.9 kPa). Adjustment of the pressure regulator is not normally necessary since it is preset at the factory. However, field adjustment may be made as follows: a. Attach manometer at the pressure tap plug below
the control outlet.
b. Remove the regulator adjustment screw cap,
located on the combination gas valve.
c. With a small screwdriver, rotate the adjustment
screw counterclockwise to decrease pressure, or clockwise to increase pressure.
d. Replace regulator adjustment screw cap.
2. PROPANE GAS: An exact manifold pressure of
10.0 inches W.C. (2.5 kPa) must be maintained for proper operation of the unit heater. If the unit is equipped with a pressure regulator on the combination gas valve, follow steps "a" through "d" above. If the unit is not so equipped, the propane gas supply system pressure must be regulated to attain this manifold operating pressure.
3. The adjusted manifold pressure should not vary more than 10% from pressure specified in Tables 5 & 6.
Table 5 - Main Burner Orifice Schedule*
PROPANETYPE OF GAS NATURAL
3
*
IN
1000
BTU
30
45
60
75
90
HEATING VALUE
MANIFOLD
PRESSURE
FT 3/HR
ORIFICE DRILL
3
FT
/HR
ORIFICE DRILL
3
FT
/HR
ORIFICE DRILL
3
FT
/HR
ORIFICE DRILL
3
FT
/HR
ORIFICE DRILL
INPUT
*This schedule is for units operating at normal altitudes of 2000 ft. (610m) or less.
When installed in Canada, any references to deration at altitudes in excess of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft. (610 to 1372m), the unit heaters must be orificed to 90% of the normal altitude rating, and be so marked in accordance with ETL certification.
1075 BTU/Ft
(40.1 MJ/m3)
3.5" W.C. (0.87kPA)
28 49 42 49 56 49 70 49 84 47
2500 BTU/Ft
(93.1 MJ/m3)
(2.49 kPA)
10" W.C.
12 57 18 57 24 57 30 57 36 55
3
NO. OF
BURNER
ORIFICES
2
3
4
5
5
TUBULAR UNIT HEATER HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing standard burner orifices and a normal manifold pressure setting as per the specifications shown on your unit rating plate (refer to Tables 3, 5 and 6).
All unit deration must be done through field adjustments by a qualified technician (refer to Table 6). Once the proper adjustments are made in the field, attach label #J17-06459 to the unit, and record adjusted manifold pressure, altitude of the unit installation and the technician’s name and date on the label using a permanent marker.
21
Page 22
PROPANE (LP) GASNATURAL GAS
*Heating
Altitude
(Feet)
2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000
*Notes:
1. Consult local utility for actual heating value.
2. Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.
Value
BTU/Cu. ft.
948 931 914 897 881 865 849 833 818
Manifold
Pressure
(In. W.C.)
3.2
3.2
3.2
3.1
3.1
3.1
3.0
3.0
2.9
*Heating
Value
BTU/Cu. ft.
2,278 2,237 2,196 2,156 2,116 2,077 2,039 2,000 1,964
Manifold Pressure
(In. W.C.)
10.0
10.0
10.0
10.0
10.0
9.9
9.7
9.6
9.5
MAINTENANCE
Table 6
Altitude
(Feet)
6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000
NATURAL GAS
*Heating
Value
BTU/Cu. ft.
802 787 771 756 741 726 711 696
Manifold Pressure
(In. W.C.)
2.9
2.8
2.8
2.8
2.7
2.6
2.6
2.5
PROPANE (LP) GAS
*Heating
Value
BTU/Cu. ft.
1,927 1,891 1,853 1,817 1,781 1,745 1,709 1,673
Manifold
Pressure
(In. W.C.)
9.3
9.2
9.0
8.9
8.7
8.5
8.3
8.1
PERIODIC SERVICE
NOTICE: The heater and vent system should be checked once a year by a qualified technician.
All Maintenance/Service information should be recorded accordingly on the Inspection Sheet provided in this manual.
Open all disconnect switches and disconnect all electrical and gas supplies and secure in that position before servicing unit. Failure to do so may result in personal injury or death from electrical shock.
Gas tightness of the safety shut­off valves must be checked on at least an annual basis.
To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the appliance combination control. Remove the 1/8 inch pipe plug on the inlet side of the combination control and connect a manometer to that tapping. Turn the manual valve on to apply pressure to the combination control. Note the pressure reading on the manometer, then turn the valve off. A loss of pressure indicates a leak. If a leak is detected, use a soap solution to check all threaded connections. If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.
Should maintenance be required, perform the following inspection and service routine:
1. Inspect the area near the unit to be sure that there is no combustible material located within the minimum clearance requirements listed in this manual.
Under no circumstances should combustible material be located within the clearances specified in this manual. Failure to provide proper clearance could result in personal injury or equipment damage from fire.
3. Remove service panel.
4. To clean or replace the burners, remove the four screws holding the manifold to the burner box and pull the manifold back slightly to disengage the orifices from the burners. Remove each burner by holding it against the tab on the burner bracket, then rotate the inlet end of the burner toward the fan side of the unit and slide the burner off the tabs. See Figure 20.
5. With the burners removed, wire brush the inside surfaces of the heat exchanger.
6. Remove any dirt, dust, or other foreign matter from the burners using a wire brush and/or compressed air. Ensure that all parts are unobstructed.
7. Reassemble the unit heater by replacing all parts in reverse order.
8. Complete the appropriate unit startup procedure as given in the “Operation” section of this manual. (See lighting instruction on the unit nameplate).
9. Check the burner adjustment.
10. Check all gas control valves and pipe connections for leaks.
11 Check the operation of the automatic gas valve by
lowering the setting of the thermostat, stopping the operation of the gas unit heater.The gas valve should close tightly, completely extinguishing the flame on the burners.
12. Inspect and service motor/fan assembly. To maintain efficient air flow, inspect and clean the fan blades and guard to prevent buildup of foreign matter.
13. Check lubrication instructions on motor. If oiling is required, add 3 or 4 drops of electric motor oil as follows: a. Light Duty - After 3 years or 25,000 hours of
operation.
b. Average Duty - Annually after 3 years or 8,000
hours of operation.
c. Heavy Duty - Annually after 1 year or at least
1500 hours of operation.
Never over oil the motor or premature
failure may occur!
2. Turn off the manual gas valve and electrical power to the unit heater.
14. Check and test the operational functions of all safety devices supplied with your unit.
22
Page 23
SYMPTOMS
A. Flame pops back.
Table 7 - Tubular Propeller Troubleshooting Guide
POSSIBLE CAUSE(S) CORRECTIVE ACTION
1.
1. Burner orifice too small.
Check with local gas supplier for proper orifice size and replace. Refer to “Operation”.
B. Noisy Flame.
C. Yellow tip flame (some yellow
tipping on LP gas is permissible).
D. Floating flame.
E. Gas odor.
F. Delayed ignition.
G. Failure to ignite.
1.
Irregular orifice causing whistle or resonance.
2. Excessive gas input.
1. Clogged main burners.
2. Misaligned orifices.
3. Insufficient combustion air.
4. Possibly over fired.
1. Blocked venting.
2. Insufficient combustion air.
3. Blocked heat exchanger.
4. Air leak into combustion chamber or draft hood.
1. Shut off gas supply immediately!
2. Leaking gas test port on valve.
3. Blocked heat exchanger.
4. Blocked draft hood.
5. Negative pressure in the building.
1. Improper ground.
2. Bad or broken spark cable.
3. Faulty control.
4. Pressure regulator set too low.
5. Main burner orifices dirty.
6. Improper venting.
1. Gas supply is off.
2. No power supply to unit.
3. Thermostat not calling.
4. Defective high limit.
5. Defective drafter prove switch.
6. Loose wiring.
7. Improper ground.
8. Improper thermostat or transformer wiring.
1. Replace orifice.
2. Test and reset manifold pressure.
1. Clean main burner ports.
2. Replace manifold assembly.
3. Insufficient combustion air.
4. Check gas input and manifold pressures.
1. Clean Flue. Refer to “Installation”.
2. Clean combustion air inlet openings.
3. Clean heat exchanger. Refer to “Installation”.
4. Determine cause and repair accordingly.
1. Inspect all gas piping and repair.
2. Check to ensure gas test ports are seated.
3. Clean heat exchanger/flue.
4. Clean flue collector.
5. See “Installation”.
1. Check grounding wires and spark bracket connections.
2. Inspect spark cable connections and cuts.
3. Check to ensure spark is energized after pre purge period.
4. Test and reset manifold pressure refer to “Operations”.
5. Clean or replace orifices.
6. Refer to “Installation”.
1. Open all manual valves “check for leaks”.
2. Turn on power supply, check fuses and replace if bad.
3. Turn up thermostat, Check for 24v on terminals R and W1 on terminal strip.
4. Check switch for continuity if open with no heat present, replace.
5. Check switch operation to ensure switch closes after draftor purge period. If it does not make/check tubing connections/ blockage.
6. Check all wiring per diagram.
7. Check all ground wires and connections.
8. Check both, for wiring according to diagram; check for 24V at gas valve terminals during trial for ignition period if present and valve does not open. Replace valve.
H. Condensation.
1. Improper venting.
2. Unit under fired.
3. Building too cold.
1. Refer to “Installation, Venting”.
2. Check gas supply pressures to unit. Refer to “Installation”.
3. Refer to “Installation”.
23
Page 24
SYMPTOMS
I. Burners will not shut off.
Table 7 - Tubular Propeller Troubleshooting Guide (continued)
POSSIBLE CAUSE(S) CORRECTIVE ACTION
1. Thermostat located incorrectly.
2. Improper thermostat wiring.
3. Shorted circuit.
4. Defective sticking gas valve.
5. Excessive gas supply pressure.
1. Relocate thermostat away from outside wall or drafts.
2. Check thermostat circuit for open and close on terminal strip on heater “R” and “W”.
3. Check thermostat circuit for shorts “staples piercing wires”.
4. Check for 24v on gas valve terminals when thermostat is not calling.
5. Refer to “Installation”.
J. Rapid burner cycling.
K. Noisy power ventor.
L. Fan will not run.
M. Fan motor turns on and off
while burner is operating.
N. Fan will not stop.
O. Not enough heat.
1. Loose electrical connections at thermostat or gas valve.
2. Excessive thermostat heat anticipator setting.
3. Unit cycling on high limit.
4. Poor thermostat location.
1. Power ventor wheel loose.
2. Power ventor wheel is dirty.
3.
Power ventor wheel is rubbing on the housing.
1. Loose electrical connections.
2. Defective motor or overload.
3. Defective control board.
1. Motor overload protection is tripping.
2. Loose wiring or connection.
3. Control board is defective.
1. Control Board is in flame failure mode.
2. Fan improperly wired.
3. Defective board.
1. Incorrect gas input.
2. Heater undersized.
3. Thermostat malfunction.
4. Heater cycling on limit.
5. Incorrect orifice sizes.
1. Tighten all electrical connections.
2. Adjust heat anticipator setting for longer cycles. Refer to “Electrical Connections”.
3. Check for proper air supply across heat exchanger and proper gas supply.
4. Relocate thermostat .
1. Replace or tighten.
2. Clean power ventor wheel.
3. Realign power ventor wheel.
1. Check and tighten wires on fan circuit.
2. Test for 115v on terminal ACB Heat and “L2” if voltage is present replace motor.
3. Test for 115v on terminal ACB Heat and “L2” on the control board, if voltage is not present 45 seconds after trial for ignition replace board.
1.
Check motor amps against motor name plate, check voltage, replace if found defective.
2. Check for 115v between motor leads.
3. Check terminal ACB Heat for voltage if voltage not constant, replace board.
1. Turn 115v power off to the unit, wait 10 seconds and reapply voltage to the unit.
2. Check wiring of fan circuit to wiring diagram.
3. If unit is not calling for heat and board is not in a flash code mode, replace board.
1. Refer to “Operation”.
2. Is the heater output sized correctly for heat loss of the space. Has the space been enlarged.
3. Check thermostat circuit, 24v on terminals “R” and “W” on terminal strip.
4. Check air movement across heat exchanger. Check voltage and amps at the fan motor. Check gas input to ensure unit is not over fired. Check heat exchanger to ensure unit is not dirty.
5. Check orifice size, replace if undersized.
P. Too much heat.
1. Unit is over fired.
2. Thermostat malfunction.
3. Heater runs continuously.
1. Refer to “Operation”. Check orifice size. If too big replace.
2. Check thermostat for operation, to ensure circuit open and closes.
3. Check wiring per diagram; check operation at the gas valve, look for a short in thermostat circuit.
24
Page 25
SYMPTOMS
Q. Cold air is delivered during
heater operation.
Table 7 - Tubular Propeller Troubleshooting Guide
POSSIBLE CAUSE(S) CORRECTIVE ACTION
1. Incorrect manifold pressure or input.
2. Air throughput too high.
1. Refer to “Operation”.
2. Refer to “Operation”.
R. High limit tripping.
S. Power ventor will not run.
T. Power ventor turns on and off
during operation.
U. Power ventor will not stop.
1. Unit is over fired.
2. Air flow is low.
3. Defective switch.
4. Defective control board.
1. Loose wiring or connections.
2. Motor overload is tripped or bad motor.
3. Bad control board.
1. Power ventor improperly wired.
2. Motor overload cycling or defective motor.
3. Defective control board.
1. Power ventor improperly wired.
2. Main burner did not light on call for heat.
3. Defective control board.
1. Burner orifices may be too large, verify and replace.
2. Check for proper voltage, ensure fan blade is correct.
3. Check operation of switch, did the switch open when unit is running or is the switch open during start-up.
4. Check for 24v on line side of the high limit. Constant voltage should be recorded if not control board is suspect. Check flash code.
1.
Check all wring in the power vent circuit to ensure good connection, including “Neutral”.
2.
Check for 115v between motor leads and check amp draw of motor. Replace if needed.
3. Check for continuous 115v on terminal “CBM Blower” and neutral during call for heat. If not present and all checks are normal, replace.
1. Check power ventor circuit per wiring diagram.
2.
Check motor voltage and amp draw to motor name plate, replace if motor found defective.
3. Check for continuous 115v on terminal “CMB Blower” during call for heat, replace board if found defective.
1. Check power ventor circuit per wiring diagram.
2. Heater is in lockout mode check flash code table for problem.
3. No flash codes present along with no call for heat, replace control board.
25
Page 26
Table 8 - Troubleshooting with LED Indicator Assistance
No Cycling or appliance power or thermostat call for heat since appliance failure has occured.
Line voltage power can cause product damage, severe injury or death. Only a trained experienced service technician should perform this trouble­shooting.
1. Check the system thermo­stat to make sure it is call­ing for heat. (Do not cycle the thermostat on and off at this time.)
2. Remove the appliance burner compartment door. Do not interrupt power to the control board by opening any electrically interlocked panels.
3. Observe the LED indicator on the control board (a green LED labeled “OK” indicates system faults); check and repair system as noted in the chart to the right.
LED STATUS
Slow Flash
Fast Flash
Steady Off
Steady On
2 Flashes
3 Flashes
4 Flashes
5 Flashes
INDICATES CHECK/REPAIR
Control OK, no call for heat.
Control OK, call for heat present.
Internal control fault, or no power.
Control internal failure or bad ground.
In lockout from failed ignitions or flame losses.
Pressure Switch open with inducer on or closed with inducer off.
Limit or rollout switch is open.
Flame sensed while gas valve is off.
Not Applicable
Not Applicable
1. Line voltage on terminals 120 and C on transformer.
2. Low voltage (24V) on terminals 24 and C on transformer.
3. 5 Amp fuse on circuit board.
1. Common side of transformer grounded to chassis.
2. Loose spark ignitor.
1. Gas supply off or gas supply pressure too low.
2. Flame sense rod contaminated or loose wire.
3. Gas valve switch is off or wires are not connected.
4. Broken or cracked porcelain on flame probe or spark ignitor.
1. Obstructions or restrictions in appliance air intake or flue outlet are preventing proper combustion airflow.
2. Moisture or debris in tubing that connects pressure switch and draft inducer.
3. Airflow switch jumpered or miswired.
1. Open manual reset rollout switch.
2. Gas pressure too high, over fire condition.
3. Incorrect airflow due to blockage or motor not operating.
1. Flame probe miswired or shortened.
*NOTICE: Air flow proving switch and power venter hose barbs must be free of any dust or debris at all times. Periodically check these openings and/or if any problems occur.
6 Flashes
On-board microprocessors disagree.
1. Thermostat is interfering with control board.
26
Page 27
IDENTIFICATION OF PARTS
RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES
Item
No. ItemDescription
Vestible Panel/Tube Ass’y
1
(Heat Exchanger)
2 Manifold Bracket Sub-Ass’y
3 Manifold
4 Inshot Burner
*Standard Orifice
5
Natural Gas or Propane (LP) Gas
6 Spark Ignitor
7 Flame Sensor
Gas Valve, Single Stage
8
Natural or Propane (LP) Gas
9 Manual Rollout Safety Switch
10 Transformer, 50 VA, 115/24
11 Air Pressure Switch
12 Terminal Block Plate
High Limit Switch
13
w/Mounting Bracket
14 Fan Motor
15 OSHA Fan Guard
16 Standard Fan
Fan/Guard/Motor Mount
17
Hardware Kit
18 **Flue Collector
19 Power Venter (Drafter) Ass’y
20 Flue Collar Ass’y
21 Vinyl Tubing (Pressure Switch)
22 Power Venter Mounting Plate
23 Louver
24 Louver Spring
25 Control Board
26 Service Panel
27 Top Jacket Panel w/Insulation
27 Bottom Jacket Panel w/Insulation
29 Front Jacket
30 Rear Jacket
31 Front Hanger
31 Rear Hanger
32 Tube Support Bracket
33 Green Ground Screw
*** The orifices shown are for units
operating at normal altitudes of 0 to 2000 ft. (610m).
*** When replacing a flue collector, make
sure that the flue collector box is sealed completely to the vestibule panel using RTV Sealant.
27
Page 28
IDENTIFICATION OF PARTS
RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES
Figure 21 - Propeller Parts Figure 22 - Component Parts
Fan Blade
Fan Guard
Motor
Hardware
Hardware
NOTE: No rubber grommets are equipped with the 30 and 45 unit sizes.
Figure 23 - Internal Furnace Components
D4791
Pressure Switch
D4430
D6963
Gas Valve
Figure 24 - Power Ventor Assembly
28
D4810
Page 29
HOW TO ORDER REPLACEMENT PARTS
Please send the following information to your local representative: if further assistance is needed, contact the manufacturer's customer service department.
•Model Number
•Serial Number (if any)
•Part Description and Number as shown in Replacement parts Catalog
LIMITED WARRANTY
Residential Power Vented Tubular Propeller Unit Heaters
1. The "Manufacturer" warrants to the original owner at original installation site that the above model Gas-Fired Heater ("the Product") will be free from defects in material or workmanship for (1) year from the date of shipment from the factory, or one and one-half (1-1/2) years from the date of manufacture, whichever occurs first. The Manufacturer further warrants that the complete heat exchanger, flue collector and burners be free from defects in material or workmanship for a period of ten (10) years from the date of manufacture. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.
2. This limited warranty does not apply: a. if the product has been subjected to misuse or neglect, has been accidentally or intentionally damaged,
has not been installed, maintained, or operated in accordance with furnished written instructions, or has
been altered or modified in any way by any unauthorized person. b. to any expenses, including labor or material, incurred during removal or reinstallation of the Product c. to any damage due to corrosion by chemicals, including halogenated hydrocarbons, precipitated in the air d. to any workmanship of the installer of the Product
3. This limited warranty is conditional upon: a. advising the installing contractor, who in turn notify the distributor or manufacturer b. shipment to the Manufacturer of that part of the Product thought to be defective. Goods can only be
returned with prior written approval of the Manufacturer. All returns must be freight prepaid.
c. determination in the reasonable opinion of the Manufacturer that there exists a defect in material or
workmanship
4. Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
5. THIS LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES, EITHER EXPRESS OR IMPLIED, AND
ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH
MAY VARY BY JURISDICTION.
In the interest of product improvement, we reserve the right to make changes without notice.
29
Page 30
GAS EQUIPMENT
START-UP
Customer ____________________________________ Job Name & Number _________________________
PRE-INSPECTION INFORMATION
With power and gas off.
Type of Equip: Unit Heater
Serial Number _________________________ Model Number __________________________
Name Plate Voltage: _____________ Name Plate Amperage: _____________
Type of Gas: Natural LP Tank Capacity _______ lbs. Rating: ______ BTU @ ____ °F _______ kg ______ kw @ ____ °C
Are all panels, doors, vent caps in place? Has the unit suffered any external damage? Damage ______________________________ Does the gas piping and electric wiring appear to be installed in a professional manner? Has the gas and electric been inspected by the local authority having jurisdiction? Is the gas supply properly sized for the equipment? Were the installation instructions followed when the equipment was installed? Have all field installed controls been installed? Do you understand all the controls on this equipment?
(DO NOT START this equipment unless you fully understand the controls.)
If not, contact your wholesaler or rep.
GENERAL
With power and gas off.
Make certain all packing has been removed.Tighten all electrical terminals and connections.Check all fans & blowers for free movement.Check all controls for proper settings.
BLOWER
With power on and gas off.
Check voltage L1 _____ L2 _____ L3 _____Check rotation of main blower.Check motor amps L1 _____ L2 _____ L3 _____Blower RPM _____________Check air filters.
(Record quantity & size.)
GAS HEATING
With power and gas on.
Inlet gas pressure. ____ in. W.C. or ____ kPaBurner ignition.Manifold gas pressure. ____ in. W.C. or ____ kPaCycle on HIGH LIMIT.Cycle and check all other controls not listed.Cycle by thermostat or operating control.
Remarks: _____________________________________________
__________________________________________________ __________________________________________________
30
Page 31
Page 32
Loading...