State GS6 40 YBDS User Manual

RESIDENTIAL
SELECT
DIRECT VENT
Residential Gas Water Heaters
Direct Vent Design - FVIR compliant, one-pipe, dual channel closed-combustion
system draws all make-up air from outside the home, eliminating problems caused by insufficient indoor ventilation. Horizontal air intake and venting on all models up to 80 inches from outside wall, with no electrical power needed.
Intelligent Control Logic - The internal microprocessor provides enhanced
operating parameters and tighter differentials for precise sensing and faster heating response to optimize performance.
Self-Powered Electronic Gas Valve - Uses a thermopile to generate the
power needed to operate the electroic gas control without requiring an external power source.
Diagnostics - The electronic gas control incorporates an LED status indicator that
monitors system operation & service diagnostics.
Diffuser Dip Tube - Reduces lime and sediment buildup, maximizes hot water
output. Made of State PEXAN™, a cross-link PEX polymer that can withstand long-term exposure to water temperatures up to 4000F.
Green Choice™ Eco-Friendly Gas Burner - Patented design reduces NOx
emissions and complies with Southern California and Texas requirements.
Durable Brass Tamper-Resistant Drain Valve.
Glasslined Tank
Push Button Piezo Ignitor
- For long-lasting protection against rust and corrosion.
- Simplifies lighting pilots with one hand spark ignition.
Anode Rod - For added protection against rust and corrosion.
Factory-Installed Temperature & Pressure (T&P) Relief Valve.
Thick, CFC-Free Foam Insulation.
6-Year Limited Tank and Parts Warranty.
All models meet federal minimum energy standards
Low Lead Content
Series 200/201
For more information on Select ® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800-365-0024 Toll-free USA www.statewaterheaters.com
SRGSS04812 May 2012R
RESIDENTIAL
SELECT
DIRECT VENT
Residential Gas Water Heaters
200
200
200
200
FIRST HOUR
RATING
73
87
88
131
ENERGY FACTOR
0.60
0.59
0.58
0.57
GALLON
CAP
40
50
50
75
BTU
INPUT
38,000
42,000
50,000
55,000
RECOVERY
90 DEGREE
RISE
37
45
55
60
68
76
76
***
A
54-3/4
63-3/4
64-3/4
65-3/4
76
MODEL
NUMBER
GS6 40 YBDS
GS6 50 YBDS
GS6 50 YRDS
GS6 75 YRDS
Recoveries are rounded to nearest gallon Water Connections - 3/4” on all models
**
Dual-channel system has 3” vent pipe inside 6” air intake pipe for the 40 & 50-gallon. The 75-gallon models uses a 4” x 7” Co-Axial pipe.
***
A dimension is to center line of flue (recommended vent height) When ordering propane, change “Y” to “H” in model number (GS6 40 HBDS) Propane units are Series 201 All models have 2” foam cavity 75-gallon water connections are 12” on center. All models are certified from sea level to 7,700 ft. elevations.
SERIES
COLUMN
Important! Vent Installation and Termination Requirements
• Maximum horizontal vent distance is 80” to outside of exterior wall.
• Minimum horizontal vent distance is 17” to outside of exterior wall.
• Vent pipes may be trimmed (cut) for short vent installations.
• For vent installation less than 30” the vent restrictor is required. Place restrictor over the flue outlet on heater before installing the outlet vent pipe to the heater.
• Recommended installation height for the heater and vent pipe should be 68” for 40-gallon models and 76” for the 50 and 75-gallon models (vent height).
• Offset Vent Arrangement
1. When replacing an existing direct vent model, the new vent pipe may drop
from the minimum vent height as much as 7 1/4” to exit through the existing vent opening in the exterior wall.
2. Vent may have one horizontal 90 degree turn before exiting through
exterior wall (Do not combine both offset vent arrangements in one installation) (See examples in the installation manual)
• High Rise Vent Arrangement
3. When vent termination is more than 80” above the base of the heater.
The horizontal vent run must be a minimum of 22” from the center of the heater to the outside exterior wall surface. (See example in the installation manual)
• Vent termination clearance hole through the exterior wall should be approximately 7” diameter.
• Snow accumulation and drifting should be considered when locating the termination.
• An optional wire grill vent cap protector is available through the parts department. Request part number 9006627.
• See the installation manual for complete installation and venting requirements.
A
B
DIMENSIONS
C B
22-1/4
22-1/4
22-1/4
26-1/4 16-1/4
6“ DIA. ON 40 & 50-GALLON MODELS
C
D
16
16
16-1/4
MIN VENT
17
MAX VENT
80
7” DIA. ON 75-GALLON MODELS
F
E
12-1/4
12-1/4
12-1/2
12-1/2
25-1/4 for
40 & 50-gallon
29-1/2 for 75-gallon
F
45-1/4
54
55-1/2
55-1/2
TOP
VENT PIPE
Co-Axial
Co-Axial
Co-Axial
Co-Axial
SHIPPING
**
WEIGHT
& T
P
42°
47°
INTERCHANGEABLE
EXTERIOR
WALL
167
185
187
310
D
R
N I A
75-GALLON VENT
TERMINATION CAP
IS NOT
WITH THE VENT
CAP ON THE
40 & 50-GALLON
MODELS.
For complete information on limited warranties, consult written warranty, or contact the State Customer Care Center, 1-800-365-0024.
For more information on Select ® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800-365-0024 Toll-free USA www.statewaterheaters.com
SRGSS04812 May 2012R
D
FRONT