STA-RITE SR, SRC200 User Manual

Page 1
Heater Insulation Kit
Sta-Rite Pool/Spa Group
293 Wright Street, Delavan, WI 53115
North America: 800-752-0183, FAX 800-582-2217 International: 262-728-5551, FAX: 262-728-4461, TELEX: ITT 4970245
www.sta-ritepool.com
Union City, TN • Delavan, WI • Mississauga, Ont. • Murrieta, CA
© 2003, Sta-Rite Industries, Inc. Printed in U.S.A. S430 (Rev. 2/14/03)
Page 2
Tools/Parts Required
Flat Screwdriver, Phillips Screwdriver 1/4” and 3/8” Socket Sets with Extenders
Sockets needed:1/4”, 5/16, 11/32, 7/16, 1/2, 9/16, 7/8
Rubber Mallet To rque Wrench calibrated in Inch-Lbs. High Temperature RTV (600° F. Cont.; 700° F. Intermittent) Flame Holder/Adapter Plate Gaskets
(2 - Part No. 42001-0065)
14” & 12” Pipe Wrenchs (1 Each) or 2 Channel-Lock Pliers
Optional: Lifting Gear capable of handling 150 Lbs.
Safety Precautions:
Risk of electrical shock, fire or explosion.
Disconnect all power to the heater and close the external manual gas valve at start of this procedure. Check for gas leaks with a soapy water solution after reassembly.
Risk of carbon monoxide poisoning from
indoor units if exhaust vent joints are not sealed. Check
all vent joints for leakage after reassembly.
Heavy parts; can cause personal injury. When lifting, use all proper precautions for the weights involved.
Uncured RTV sealants can cause eye irrita­tion. Follow manufacturer’s instructions when using RTV
sealants.
Location
The Insulation is located inside the Combustion Chamber.
Function
The insulation increases the thermal efficiency of the heater and prevents overheating of parts outside the com­bustion chamber.
Servicing Procedure (See Figure 1):
Heavy parts; can cause personal injury. When lifting, use all proper precautions for the weights involved.
1. Turn off the filter pump and all electrical power to the
heater. Close the external Manual Gas Valve.
2. If the heater is below the water level of the pool, close
the isolation valves to avoid draining the pool.
3. Remove the drain plug under the manifold and drain
the heater.
4. While the heater is draining, remove the upper left and
upper right jacket halves.
5. Remove the switch covers on both sides of the mani-
fold and unplug the wires from the Automatic Gas Shutoff, the High Limit Thermostat, and the Thermistor (See Figure 2, Key No. 1). If necessary, disconnect the Water Pressure Switch and remove it.
6. Disconnect exhaust vent from indoor units.
7. Disconnect the gas pipe at the external union between
the heater and the external manual gas valve.
8. Disconnect the incoming electrical wires at the junction
box and cut the wire tie holding the Wiring Harness to the Lower Enclosure (See Figure 2, Key No. 2).
9. Disconnect the inlet and outlet unions and move the
heater enough to allow removal of the manifold adapter and the inlet/outlet manifold as a unit (See Figure 2, Key No. 3).
1/2" Insulation
OFF
ON
OFF
ON
Figure 1: Isolate and Drain Heater; Disconnect Power
2
Blanket
1" Insulation
Flameholder Insulation Cap
Condensate Evaporator
1" Insulation
1/2" Insulation Blanket
3120 1197
Power
Combination Gas Control Valve OFF
Turn Clockwise and press down to turn off gas.
Manual/Gas Valve OFF
O N
FF O
VENT
PRESS
TAB
PILOT
O N
F F O
T
N E V
S S
PRE
B
TA
T O
PIL
Remove Water Pressure Switch to help Manifold Drain
Drain Inlet/Outlet Manifold
Inlet
Open
2704 1196
Drain Cock(s) and Plugs OPEN
Close Isolation Valves
Outlet
Page 3
3
10. Unscrew the bolts that attach the manifold adapter to the tube sheet and remove the manifold adapter and the inlet/outlet manifold as a unit.
11. Carefully disconnect all three metering tubes from the Combustion Air Blower Assembly (1 to the Combination Gas Control Valve, 2 to the Air Flow Switch).
12. Remove the bolt from the Gas Piping Clamp.
13. Unplug all wires to the Control Box. Unscrew three nuts and remove the Control Box, the Heat Shield, and the Membrane Pad and Cover as a unit (See Figure 2, Key No. 4).
14. Unscrew the four nuts holding the Blower Adapter Plate to the top of the Combustion Chamber and remove the Combustion Air Blower, the Igniter, the Combination Gas Valve and associated piping and the Blower Adapter Plate as a unit (See Figure 2, Key No.
5). Remove the Flameholder and Flameholder Cone (if used). NOTICE: BE CAREFUL not to break or crack the igniter – it is fragile!
15. Unscrew the nuts holding the Combustion Chamber top to the Combustion Chamber body.
16. Unscrew 4 hold-down nuts from the hangers support­ing the Combustion Chamber.
17. Wrap a shop rag around each hanger, one at a time (be careful; it’s sharp) and hammer down on the Lower Enclosure while lifting the hanger by the shop rag. This will lift the hanger up off of the hold-down bolt.
18. Lift the Combustion Chamber out of the Lower Enclosure.
Heavy parts; can cause personal injury. When lifting, use all proper precautions for the weights involved.
19. Cut the RTV all the way around the top of the
Combustion Chamber with a screwdriver.
20. With a mallet and screwdriver, go around the Combustion Chamber cover tapping up until the RTV separates and releases the Combustion Chamber cover. Be careful not to damage the Combustion Chamber.
21. Remove the Combustion Chamber cover.
California’s Proposition 65 lists Refractory Ceramic Fibers heated to 1800° F or higher as a possible human carcinogen. See the warning box
on Page 6 for further information. Call 1-800-752-0183 for a Material Data Safety Sheet (MSDS).
22. Remove the top insulation, the Heat Exchanger Coil, the Condensate Evaporator, the Bottom Insulation, and the metal spacer from the Combustion Chamber. Do not remove the RTV that seals the manifold mounting plate to the combustion chamber.
23. Clean up the Combustion Chamber, the Combustion Chamber cover, and the Spacer. Be sure to completely remove all RTV from the Combustion Chamber and Combustion Chamber top.
24. Reinstall the clean spacer in the Combustion Chamber. Install one 1/2” white Insulation Blanket on top of the spacer and one piece of 1” “M” insulation on top of the Blanket. Make sure that the insulation is centered in the Combustion Chamber.
NOTICE: Model SR/SRC200 heaters built before 1/1/98 require two 1/2” Insulation Blankets.
Figure 2: Removal of major sub-assemblies
1/2" Top Blanket
1" Top Insulation
1/2" Bottom Blanket
1" Bottom "M" Insulation
Flameholder Insulation Cap (Tape to bottom of Flameholder)
Spacer
Condensate Evaporator
Flameholder
3122 1197
Figure 3: Correct order for installation of insulation.
5
4
2
3
1
Page 4
4
25. Install the new Condensate Evaporator on top of the insulation.
26. Clean the tubesheet and O-Ring sealing surfaces (see Figure 4).
27. Reinstall the Heat Exchanger Coil on the Insulation. Pull the Heat Exchanger Coil and the Bottom Insulation forward together to align with the mounting plate (see Figure 5).
28. Install the manifold and manifold bolts. See Figure 6 for long and short bolt positions.
Figure 5: Align bottom insulation and Heat Exchanger Coil as shown.
C
Figure 4: Clean the Tube Sheet and O-Ring sealing sur­faces thoroughly as described above.
Figure 6: Install bolts as shown.
• Install O-rings on tube ends; install manifold.
SR/SRC200 and SR/SRC400: Tighten all long bolts
HAND TIGHT; then tighten the bolts next to the short bolts a little more with a wrench.
• Insert and start the two short bolts until they engage three or four threads, then tighten all bolts according to the normal torque pattern shown on Page 5.
SR/SRC333: These models use long bolts only. Tighten all bolts HAND TIGHT; then tighten according to the normal torque pattern shown on Page 5.
*Hand-tighten all long bolts; then tighten indicated bolts enough to allow short bolts to engage.
Clean the tube sheet and O-ring
1. sealing surface with a nylon brush, then brighten the tube sheet surface with 320 grit emery cloth.
NOTE: When cleaning, be careful not to push the tube sheet into the combustion chamber. If you do, thread a couple of bolts into it and pull it back in place.
Brush off all dust and debris
2.
with a brush and wipe it down with a cloth.
Apply silicone grease (supplied)
3. to O-Rings.
4067 0901
A. Center Insulation in lower enclosure. Add Evaporator Plate.
Evaporator Plate
Insulation
B. Center Heating Coil on Insulation.
Heating Coil
Models SR200/SRC200
Short Bolt Placement
2-3/4"
*
2-1/2"
*
2-3/4"
Models SR400/SRC400
Short Bolt Placement
2-3/4"
2-1/2"
2-3/4"
*
*
Do not disturb RTV in these areas
C. Slide Coil, Insulation, and Evaporator Plate into Manifold Mounting Plate.
Lower Enclosure
D. No Gaps between insulation and Tube Sheet
Here and Here
Tube Sheet
4076 1001
2-3/4"
*
2-1/2"
2-3/4"
*
2-1/2"
Page 5
5
29. Tighten the bolts to the torque spec as shown in Figure 7.
30. Turn on the water and check for leaks between the Manifold Adapter and the Tube Sheet.
31. Install one piece of 1” top Insulation on top of the Heat Exchanger and one 1/2” Insulation Blanket over the top Insulation. Make sure that the insulation is centered on the coil so that an equal number of heater coil fins shows around the insulation.
32. Apply fresh High Temperature RTV (600°F Continuous, 700° F. Intermittent rating) all the way around the inside top of the Combustion Chamber and the outside of the Combustion Chamber cover (see Figure 8).
33. Reinstall the Combustion Chamber top and fasten with nuts on studs from Combustion Chamber body.
34. Reinstall the Combustion Chamber in the Lower Enclosure and fasten with hold-down nuts.
35. Reinstall the Flameholder and Flameholder Cone (if used), and then the Combustion Air Blower, the Igniter, the Combination Gas Valve and associated piping and the Blower Adapter Plate as a unit; use new gaskets. Be sure to reinstall the Insulation Cap on the bottom of the Flameholder. Tighten Adapter Plate nuts to 70-80 in.-lbs. torque. See Figure 9.
1. Make sure that all bolts are engaged and hand tight.
2. Torque the bolts in sequence as shown. Some noise (popping, etc.) is normal as you tighten.
3. Go around the manifold and retighten the bolts as needed to 75-115 in-lbs. (8.4-12.9 N-m) (you may have to do this several times).
Figure 7: Torque Specs.
Apply RTV here and here.
Apply RTV bead all the way around both Combustion Chamber and Cover.
3140 0198
Figure 8: RTV Application For Reassembly
Flameholder/Adapter Plate Gasket
Flameholder/Combustion Chamber Gasket
3123 1197
1
2
3
At reassembly, connect tubing as shown:
1. From Air Inlet Port to Combination Gas Valve;
2. From Air Inlet Port to Air Flow Switch;
3. From bottom of Blower to Air Flow Switch.
3123 1197
Figure 9: Make sure new gaskets are in place when reassembling combustion chamber.
Tor que Pattern - All Models
98
54
12
3 6
710
75-115 in.-lbs./8.4-12.9 N-m
Page 6
36. Reinstall Control Box and Heat Shield assembly; fasten with three nuts.
37. Reconnect the water pressure switch (if necessary).
38. Reconnect the metering tubes from the Air Flow Switch and the Combination Gas Control Valve to the Combustion Air Blower Assembly (see Figure 9).
39. Reconnect exhaust vent pipe and seal with RTV or epoxy according to vent manufacturer’s instructions.
Risk of carbon monoxide poisoning. Make
sure that entire exhaust vent is sealed after reinstallation.
40. Reconnect all wiring. See Figure 10 for Junction-box connections, and see Page 7 for complete wiring schematic.
41. Before starting the heater, test for gas leaks from piping and around Combustion Chamber cover with a soapy water solution.
42. Check for water leaks at unions and at manifold flange (where it joins the tube sheet).
43. Reinstall jacketing and test heater by running it through one complete cycle. Test for exhaust leaks from exhaust vent pipe while cycling heater.
44. Heater is ready for service.
6
Wire into bottom of Junction-box in Flexible Conduit
Wiring Harness to Control Box
Black to Black
White to White
Green (Ground)
to
Green (Ground)
Bonding Wire
View From Above (Interior)
Figure 10: Junction Box Wiring Connections
For detailed installation, operation, maintenace and safety information about the Sta-Rite pool heater, call customer service at 1-800-752-0183 and request a Sta-Rite Pool/Spa Heater Training and Service manual, publication S5066.
Prolonged exposure to the ceramic fiber insulation in the combustion chamber may cause cancer. May also cause temporary eye, skin, or respiratory tract irritation.
Avoid breathing fiber particulates and dust.
Wear a NIOSH/MSHA approved respirator, loose, long sleeved clothing, eye protection, and gloves when working with or around insulation. Wash work clothes separately. Rinse washing machine after use.
For first aid:
Eyes: Flush with water. Skin: Wash with soap and water. If swallowed: Do not induce vomiting. Get medical attention if gastrointestinal symptoms develop. If inhaled: Get to fresh, clean air. If any of the irritations above persist, seek medical attention immediately.
For additional product information or for a Material Safety Data Sheet (MSDS), call
1-800-752-0183
Page 7
7
JMP3
9
1
J6
JMP3
1
JMP3
1
External Control Interface Circuit Disabled, Heater Membrane Pad Enabled
External Control Interface Circuit Enabled, "Pool On" and "Spa On" Keys Disabled. "OFF" Key on Membrane Pad Remains Functional.
CONNECTION DIAGRAM
AGS Switch
Stack Flue Sensor
Gas Valve
Air Flow Switch
Extra Switch 1
Hi-Limit Switch
Pressure Switch
VAL
TH
IND
GND
24VAC
24VAC
FS
THERMISTOR
OPERATING CONTROL
1
PS
HLS
ES1
AFS
AGS
SFS
GAS
CONTROL CENTER
SPA CONTROL
VERSION 1 PAD
MEMBRANE PAD
CONNECTION
Spa Line
Common Line
Pool Line
IGNITION CONTROL
MODULE
DIAGNOSTIC INDICATOR
F1 F2
24
VAC
FC1 FC2
S1/
120
L1
L1
L2
BM
FL
F1
L2S2TH IND
VAL GND
GND
GND
GND
BLOWER
120VAC
120VAC (HOT)
120VAC
IGNITER
MOT
TRANS
TRANS
GROUND (GND)
NEUTRAL (NEU)
JUNCTION BOX
F
I R E M A N S
S W I T C H
Replace jumper with leads to Fireman's Switch (field installed)
24VAC
SEC
PRIM
120VAC
Y/W
Y/W
Y/R
Y/O
Y/BL
BK
GY GY
BK
BK
W
W
BK
W
W
WW
G
G
Y
Y
YY
BK
BK
Y/W
W
W
R
R
BL
BL
O
O
O
O
PR
PR
Y/R
Y/BL
Y/O
Y/W
Y
Y
Y
Y
Y
YY Y Y
BR
BR
3661 0200
External Control Interface
If cable from Membrane Pad is a 6-Conductor Cable, connect it to pins 4 - 9 on Operating Control Board as shown.
Y
9
1
J6
NOTICE: If, while there is 120VAC connected to the heater, you touch either 120VAC terminal with any 24VAC wire that is connected to the control board (including the Fireman's Switch jumper), you will immediately destroy the control board and void the warranty.
Page 8
8
REPAIR PARTS LIST
Key Part Part No. Description Qty. No.
1 Flameholder Insulation Cap 1 42001-0075 2 1/2” Blanket 1 42001-0071 3 1” Top Insulation 1 42001-0070 4 Condensate Evaporator 1 42001-0065 51“M” Insulation 1 42001-0072 6 1/2” Blanket* 1 42001-0073
1
2
3
4
6
5
3125 1197
* Model SR/SRC200 heaters built before 1/1/98 use 2 of
Part No. 42001-0073.
Loading...