Sta-Rite PM1250 Installation Manual

Installation and Operation
U.S. Reg. 2,765,423
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
Instructions for
TM
PowerMax
Pool Heater
Model PM
®
If the information in this manual is not
WARNING
followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
P/N 472642 Rev A - 05/22/06
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Page 2
Pentair Water Commercial Pool and Spa
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction ....................................................... 3
1.2 Model Identification ........................................... 3
1.3 Warranty ........................................................... 4
1.4 Dimensions ....................................................... 4
1.5 Locating the Appliance ..................................... 4
1.6 Locating Heater with Respect to Pool
System Loop ..................................................... 6
1.7 Locating Appliance for Correct Horizontal Vent/
Ducted Air Distance From Outside Wall ........... 6
SECTION 2. Venting and Combustion Air
2.1 Combustion Air ................................................. 6
2.1.1 Combustion Air From Room ............................. 6
2.1.2 Intake Combustion Air ...................................... 7
2.2 Venting ............................................................. 7
2.2.1 Vent Categories ................................................ 7
2.2.2 Category I Vent ................................................. 8
2.2.3 Common Venting Systems ............................... 8
2.2.4 Category III Vent ............................................... 8
2.3 Locating Vent & Combustion Air Terminals ...... 9
2.3.1 Side Wall Vent Terminal ................................... 9
2.3.2 Side Wall Combustion Air Terminal ................ 10
2.3.3 Vertical Vent Terminal .................................... 10
2.3.4 Vertical Combustion Air Terminal ................... 10
2.4 Vent Terminals for Outdoor Units ................... 10
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping ................................... 10
SECTION 6. Operating Instructions
6.1 Sequence of Operation ................................... 14
6.2 Filling the Heater System ................................ 15
6.3 Operating the Burner and Set Up ................... 15
6.3.1 Set Up for 0 to 2500 Feet Altitude................... 15
6.3.2 High Altitude Adjustment and Set Up.............. 16
6.4 Shutting Down the PowerMax ........................ 16
6.5 Spring and Fall Operation
Stand-by Service ............................................ 16
6.6 Winter Operation ............................................ 16
6.7 To Restart the PowerMax ............................... 17
6.8 Therapeutic Pools (Spas) ............................... 17
SECTION 7. Maintenance
7.1 System Maintenance ...................................... 17
7.2 Appliance Maintenance and
Component Description .................................. 18
7.2.1 Burners ........................................................... 18
7.2.2 Filter................................................................ 18
7.2.3 Gas Valves ..................................................... 18
7.2.4 Pool Loop High Limit Control .......................... 18
7.2.5 Automatic Reset High Limit Control ................ 18
7.2.6 Temperature Control ...................................... 18
7.2.7 Ignition Controls .............................................. 18
7.2.8 Ignitors ............................................................ 19
7.2.9 Ignition Sensors .............................................. 19
7.2.10 Transformer .................................................. 19
7.2.11 Blowers ........................................................ 19
7.2.12 Flow Switch .................................................. 19
7.2.13 Heat Exchanger Coil .................................... 19
SECTION 4A. Water Connections
4.2 Automatic Chlorinators ................................... 11
4.3 Sensor Locations ............................................ 12
SECTION 5. Electrical Connections
5.1 Main Power ..................................................... 13
5.2 Temperature (Operating) Control ................... 13
5.3 Programming the Temperature Control .......... 13
5.3.1 Temperature Control Overview....................... 13
5.3.2 Programming Control Parameters .................. 13
5.3.3 Setpoint - LSP................................................. 14
5.3.4 Differential - dLS ............................................. 14
5.3.5 Pump Operation ............................................. 14
5.3.6 Heater Purge (Pump Delay) - PD ................... 14
5.4 Limit Controls .................................................. 14
SECTION 8. Trouble Shooting
8.1 Resolving Lockouts ........................................ 20
8.2 Delayed Ignition – Possible Causes ............... 20
8.3 Short Cycling .................................................. 20
8.4 High Gas Consumption .................................. 20
8.5 Troubleshooting the Pool Heater
Temperature Control ...................................... 21
8.6 Troubleshooting PowerMax Controls .............. 21
SECTION 9. Replacement Parts
9.1 General Information ........................................ 22
9.2 Parts List ......................................................... 22
Pentair Technical Support ....................... 35
PowerMax Pool Heater
Page 3
SECTION 1. General Information
In the Commonwealth of Massachusetts, this appliance must be installed by a licensed plumber or gas fitter.
WARNING
The PowerMax pool heater must be installed in accordance with the procedures detailed in this manual, or the warranty may be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CAN/CGA-B149.1, Natural Gas Installation Code or CAN/CGA-B149.2, Propane Gas Installation Code, and/or local codes. Where required by the authority having jurisdiction, the installation of PowerMax appliances must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modifications to the boiler, its gas controls, or wiring may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of PowerMax copper tube pool heaters. Read it carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult Pentair Technical Support (sse page 2), or your local sales representative, with any issues or questions regarding this equipment. Experience has shown that most operating issues are caused by improper installation.
The PowerMax appliance is protected against over pressurization. A pressure relief valve is fitted to all appliances. It is installed on the outlet header, at the water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance with the 1). American National Standard Z223.1/ NFPA54-Latest Edition “National Fuel Gas Code” or
2). CAN/CGA 1-B149 “Installation Codes for Gas Burning Appliances and Equipment” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1). The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2). CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be electrically grounded in accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following information describes the model number structure.
Model Character Designation
1-2 Model Series Designation
P M = PowerMax
3 Usage
P = Pool Heater
4-7 Size
0 5 0 0 = 500,000 BTU/h input 0 7 5 0 = 750,000 BTU/h input 1 0 0 0 = 999,000 BTU/h input 1 2 5 0 = 1,250,000 BTU/h input 1 5 0 0 = 1,500,000 BTU/h input 1 7 5 0 = 1,750,000 BTU/h input 2 0 0 0 = 1,999,000 BTU/h input
8 Fuel
N = Natural Gas P = Liquid Propane
9 Altitude
A = 0-10,000 feet
10 Location
C = Indoor and Outdoor
11 Firing Mode
C = On-off
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
P M P A C C 2 N
SERIES
PM
USAGE
P
SIZE
0500
0750
1000
1250
1500
1750
2000
FUEL
N
P
ALTITUDE
A
LOCATION
C
FIRING
MODE
C (ON/OFF)
REVISION
2
HEAT
EXCHANGER
B
C
K
N
P
S
OPTIONS
CODE
X
J
L
PUMP
OPTIONS
N
Page 4
13 Revision
2 = Second version
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. PM) K = Bronze / copper P = Glass-lined cast iron / cu-nickel / brz trim S = Bronze / cu-nickel
15 Option Code
X = Standard unit J = CSD-1, FM, IRI, IL L = MN and LDS (Indoor units only)
16 Pump Options
N = Pump mounted, normal pump
1.3 Warranty
PowerMax appliances are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Pentair Water Commercial Pool and Spa.
All warranty claims must be made to an authorized Pentair Water Commercial Pool and Spa epresentative or directly to the factory. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
Pentair Water Commercial Pool and Spa
1.4 Dimensions
(See Figure 1.)
1.5 Locating the Appliance
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certified by CSA­International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves. The location for the appliance should be chosen with regard to the vent pipe lengths and external plumbing. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the PowerMax must be located as close as practical to a chimney or outside wall. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade.
Horizontal Air Collar
Heater Vent Collar Vent Pipe & Pipe Max. Pipe Max. No. Side Wall Side Wall
Size Size Diameter* Diameter Length of Elbows Vent Combustion
Terminal Air Terminal
in.
cm
500 6
750 8 1000 10 1250 12 1500 12 1750 14 36 8 2000 14
*Horizontal venting requires stainless vent pipe. See Table 5.
15 20 25 30 30
36
in.
cm
6
15
6
15
8
20
8
20
8
20 20
12
30
Table 1. Horizontal Vent / Combustion Air Parameters.
in
6 6 8 8 8 8
12
cm
15 15 20 20 20 20 30
ft.
m
50
15
50
15
50
15
50 15 3 CA001403 20260703 50
15
50 15 3 CA001405 20260703 50
15
3 CA001401 20260701 3 CA001401 20260701 3 CA001402 20260703
3 CA001403 20260703
3 CA001404 20260706
Part Number Part Number
PowerMax Pool Heater
Page 5
Shipping Weight Size lbs. 500 480 750 560 1000 670 1250 730 1500 815
Dimensions shown in
inches
cm
Size A B C D E F G H W* V* Pipe
500 33½
750 45½
1000 57½
1250 68
1500 78½
1750 89
2000 99½
*Air and vent connections may be on top or back of the PowerMax, and are field convertible. Dimensions in inches cm.
Figure 1. Dimensional Data.
85
116
146
172
199
226
253
15¾
21¾
28¾
34
39¾
44½
49¾
40
55
73
86
101
113
126
101/8
101/8
101/8
101/8
15
15
15
26
26
26
26
29¾
29¾
29¾
30¾
30¾
30¾
30¾
76
76
76
78
78
78
78
32¾
32¾
32¾
29½
29½
29½
29½
83
83
83
75
75
75
75
20
20
20
22
22
22
22
7
22
22
18
22
22
22
22
46
58
70
80
91
101
112
117
147
178
203
231
256
284
1750 880
Air Vent Horiz.
Conn. Conn. Vent
6
15
6
6
15
8
8
20
10
8
20
12
8
20
12
8
20
14
12
30
14
15
20
25
30
30
36
36
218 254 304 331 370 400
6
6
8
8
8
8
12
kg
15
15
20
20
20
20
30
Page 6
Pentair Water Commercial Pool and Spa
The dimensions and requirements that are shown in Table 2 should be met when choosing the locations for the appliance:
Required Recommended
Appliance Clearance From Service Access
Surface Combustible Material Clearance
inches
Left Side 1
Right Side 1
Top 1
Back 1
Front 1
Vertical
(Category 1) 6*
Vent
Horizontal per UL1738 venting
(Category 3) system supplier’s
Vent instructions
*1" (2.5cm) when b-vent is used. **When vent and/or combustion air connects to the back, recommended clearance is 36" (91cm).
Table 2. Clearances.
cm
2.5
2.5
2.5
2.5
2.5
15.2*
inches
24
24
12 30
**12**
36
cm
61
61
30**
91
1.6 Locating Heater with Respect to Pool
System Loop
For the best results, the PowerMax should be located within 15 feet (4.6m) of the pool system loop. The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer piping runs, then larger diameter piping shall be used. Consult the factory for assistance.
1.7 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
From Outside Wall
The forced draft combustion air blower/blowers in the appliance has/have sufficient power to pull air and vent properly when the following guidelines for horizontal air and vent are followed (see Table 1).
NOTE: On models 750-2000, the vent collar size is larger than the size of the vent pipe that can be used. Side wall vent terminals for these sizes are shipped with replacement vent collars, to accommodate horizontal vent sizes. Vent collar size and horizontal pipe diameters can be found in Table 1. The larger vent collar size is to accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the PowerMax combustion air intake terminal must be installed a minimum of 12" (30cm) below the exhaust vent terminal and separated by a minimum of 36 inches (91cm) horizontally.
The air intake terminal must be installed high enough to avoid blockage from snow, leaves and other debris. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
SECTION 2. Venting and Combustion Air
2.1 Combustion Air
PowerMax pool heaters must have provisions for combustion and ventilation air in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149, Installation Codes, or applicable provisions of the local building codes.
A PowerMax appliance may receive combustion air from the space in which it is installed, or it can be ducted directly to the unit from the outside. Ventilation air must be provided in either case. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
2.1.1 Combustion Air From Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Method 1: Two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (5.5 square cm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (11 square cm/kW) of total input rating of all equipment in the enclosure. Table 3 shows data for this sizing method, for each PowerMax model.
Method 2: One permanent opening, commencing within 12 inches (30 cm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (7 square cm/kW) of the
PowerMax Pool Heater
Page 7
total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
Boiler Each Opening*
Model Square inches Square cm
500 125 807
750 188 1213
1000 250 1613
1250 313 2020
1500 375 2420
1750 438 2826 2000 500 3226
*Net Free Area in Square Inches / Square cm Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area could be double the figures indicated.
This chart is for use when communicating directly with the outdoors. For special conditions and alternate methods, refer to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to combustion air.
Table 3. Combustion Air Openings.
2.1.2 Intake Combustion Air
Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result. The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal (see Table 2). When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2).
Use single-wall galvanized pipe, per table 4, for the combustion air intake (see Table 1 for appropriate size). Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Three elbows have been calculated into the 50-foot (15.2m) linear run. Subtract 10 allowable linear feet (3.0m) for every additional elbow used (see Table 1). When fewer than 3 elbows are used, the maximum linear pipe length allowed is still 50 feet (15.2m).
Term Description
Pipe
Joint
Sealing
Table 4. Required Combustion Air Piping Material.
Single-wall galvanized steel pipe, 24 gauge minimum (either insulated or non-insulated)
Permanent duct tape or aluminum tape
The connection for the intake air pipe is on the filter box. The PowerMax appliances may have venting and combustion air ducting attached to the top or the back. They are shipped with the connections at the top. For attaching either or both pipes to the back, the mounting flanges are reversible by removing the mounting screws and orienting the flanges in the desired position. Replace the screws after positioning flanges. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air shall also be supplied for ventilation, including all air required for comfort and proper working conditions for personnel. The PowerMax loses less than 1 percent of its input rating to the room, but other heat sources may be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired PowerMax venting, it may be considered a Category I or a Category III appliance. In general, a vertical vent system will be a Category I system. However, in rare instances, a heater's vertical vent system may be considered Category III. In the U.S., the National Fuel Gas Code (American National Standard Z223.1-Latest Edition), or in Canada the CSA B149.1 (latest edition), defines
Figure 2. Combustion Air and Vent Through Roof.
Page 8
Pentair Water Commercial Pool and Spa
a Category I vent system, and includes rules and tables to size these vent systems. If the heater’s vertical vent system does not satisfy the criteria for Category I venting, it must be vented as a Category III system.
All PowerMax vent systems which discharge horizontally (without the use of a power venter) are considered Category III vent systems.
2.2.2 Category I Vent
When vented as a category I appliance, the vent system must conform to the National Fuel Gas Code (American National Standard Z223.1-Latest Edition) in the U.S., or in Canada, to CSA B149.1 (latest edition). The vent system must be sized and installed for a Category I Fan-Assisted Appliance.
If chimney height is greater than 25 feet, or if multiple units are vented into the same vertical vent, a barometric damper must be installed on each appliance, such that the flue draft does not exceed (negative) 0.1" w.c.
If using a power venter for any type of Category I venting, the draft should be set between (negative)
0.01 and 0.10" w.c.
2.2.3 Common Venting Systems
PowerMax units are Category I fan-assisted when vented vertically and adhering to all applicable codes. PowerMax units are not allowed to be vented into a common horizontal vent system, unless a properly-sized vent fan is used, and the common vent system is properly designed by the vent fan manufacturer or a qualified engineer. When common venting PowerMax fan-assisted heaters with other appliances through one shared vertical duct called a “common vent”, special care must be taken by the installer to ensure safe operation. In the event that the common vent is blocked, it is possible, especially for fan-assisted devices, to vent backwards through non­operating appliances sharing the vent, allowing combustion products to infiltrate occupied spaces. If
the appliances are allowed to operate in this condition, serious injury or death may occur.
WARNING
Operation of appliances with a blocked common vent may lead to serious injury or death. Safety devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
applicable local codes, it is required that installers provide some means to prevent operation with a blocked common vent. It is suggested that a blocked vent safety system be employed such that if the switch from one appliance trips due to excessive stack spill or backpressure indicating a blocked vent condition, that all appliances attached to the vent be locked out and prevented from operating. (Note that the PowerMax pool heater is equipped with a blocked vent safety (pressure) switch, as shipped.) As an additional precaution, it is recommended that a Carbon Monoxide (CO) alarm be installed in all enclosed spaces containing combustion appliances. If assistance is required in determining how a blocked vent safety system should be connected to a this product, please call (800)831-7133.
Refer to the installation and operating instructions on all appliances to be common vented for instructions, warnings, restrictions and safety requirements. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
2.2.4 Category III Vent
When the PowerMax is vented with horizontal discharge, it must be installed per this installation manual and the venting system manufacturer’s installation instructions. The vent system must be sealed stainless steel, per table 5.
Route the vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Horizontal runs must slope downwards not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal. Reference Table 2 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.
Term Description
Pipe Must comply with UL Standard 1738
such as Type 29-4C Stainless Steel
(either insulated or non-insulated).
Joint Follow vent manufacturer’s instructions
Sealing
Table 5. Required Horizontal Venting Material.
It is for this reason that, in addition to following proper vent sizing, construction and safety requirements from the National Fuel Gas Code, ANSI Z223.1 or in Canada, from CSA B149.1 as well as all
2.3 Locating Vent & Combustion Air
PowerMax Pool Heater
Page 9
*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet.
Figure 3. Combustion Air and Vent Through Side Wall.
Terminals
2.3.1 Side Wall Vent Terminal
The side wall vent hood (listed in Table 1) must be used when the heater is vented through a side wall. It provides a means of installing vent piping through the building wall, and must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada the installation must be in accordance with CAN/CGA B149.1 or .2 and local applicable codes (see Figure 3). Consider the following when installing the terminal:
1. Through-the-wall vent terminals must terminate
at least 7-feet above a public walkway.
2. Locate the vent terminal so that vent gases
cannot be drawn into air conditioning system
inlets. The National Fuel Gas Code requires that
it be at least 3 feet (0.9m) above any such inlet
that is within a horizontal distance of 10 feet (3m).
3. Locate the vent terminal so that vent gases
cannot enter the building through doors,
windows, gravity inlets or other openings. The
National Fuel Gas Code requires that it be
located at least 4 feet (1.2m) below, 4 feet (1.2m)
horizontally from, or 1 foot (0.3m) above such
openings. Whenever possible, locations under
windows or near doors should be avoided.
4. Locate the vent terminal so that it cannot be
blocked by snow. The National Fuel Gas Code
requires that it be at least 12 inches (30 cm)
above grade, but the installer may determine it should be higher, depending upon local conditions.
5. Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects. Vent products may damage such surfaces or objects.
6. Locate the terminal at least 6 feet (1.8m) horizontally from any gas or electric metering, regulating, or relief equipment.
7. If the PowerMax uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.
8. Note that side wall vent terminals for models 750-2000 are shipped with reducers for the vent collars, to accommodate horizontal vent sizes, shown in Table 1.
WARNING
The outdoor vent terminal gets hot. Unit must be installed in such a way as to reduce the risk of burns from contact with the vent terminal.
2.3.2 Side Wall Combustion Air Terminal
Page 10
Pentair Water Commercial Pool and Spa
Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result. The side wall combustion air terminal (listed in Table 1) must be used when the unit takes its combustion air through a duct from a side wall. Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches
(30 cm) above grade, but the installer may
determine it should be higher, depending upon
local conditions.
4. If the PowerMax is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
2.4 Vent Terminals for Outdoor Units
For outdoor applications, the vent and combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from falling into the PowerMax.
Part numbers for the terminals to cover the vent and combustion air openings are shown in Table 6. Vent opening must be on top of the unit, and the combustion air opening must be on the back of the unit. The terminals are connected directly to the unit. No vent piping is used.
Model (Size) Terminal Combustion
Air Terminal
500 20254701 D2007900
750 20254703 D2007900
1000 20254705 D2008000
1250 D2007700 D2008000
1500 D2007700 D2008000
1750 D2007800 D2008000
2000 D2007800 D2008200
Table 6. Vent Terminals for Outdoor Units
Alternately, the installer may use a short piece of galvanized single wall or B-vent and an approved rain cap for the vent termination. A minimum 12" of vent height is acceptable. In addition, a properly sized single wall galvanized 90° ell can be used for the intake air terminal, with the open end of the ell facing down to prevent rain infiltration. The combustion air inlet opening must still be high enough to prevent blockage by snow (see Section 2.3.2).
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable hangers or floor stands, not by the appliance.
The heater’s gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.
Review the following instructions before proceeding with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. This
appliance is normally equipped to operate at
elevations up to 2000 feet (610m). PowerMax
appliances may be adjusted to operate properly at
higher elevations; however, input will be reduced
if the heating value of the gas supply is below
sea level values.
2. The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas
pressure is 5" W.C. (1.2kPa).
3. Refer to Table 7, size supply.
Outdoor Vent Outdoor
PowerMax Pool Heater
Page 11
Distance from Gas Meter or Last Stage Regulator
Model and
Gas Type 0-100' 500 natural 1-1/2" 500 propane 1" 750 natural 2" 750 propane 1-1/2" 1000 natural 2" 1000 propane 1-1/2" 1250 natural 2-1/2" 1250 propane 2" 1500 natural 2-1/2" 1500 propane 2" 1750 natural 2-1/2" 1750 propane 2" 2000 natural 3" 2000 propane 2-1/2"
Notes:
1. These figures are based on 1/2" (0.12kPa) water column
pressure drop.
2. Check supply pressure and local code requirements before
proceeding with work.
3. Pipe fittings must be considered when determining gas pipe
sizing.
0-31m
3.8cm
2.5cm
5.1cm
3.8cm
5.1cm
3.8cm
6.4cm
5.1cm
6.4cm
5.1cm
6.4cm
5.1cm
7.6cm
6.4cm
Table 7. Gas Piping Size.
100-200'
2" 1-1/2" 2" 1-1/2" 2-1/2" 2" 2-1/2" 2" 3" 2-1/2" 3" 2-1/2" 3" 2-1/2"
31-61m
5.1cm
3.8cm
5.1cm
3.8cm
6.4cm
5.1cm
6.4cm
5.1cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
200-300'
2" 1-1/2" 2-1/2" 2" 3" 2-1/2" 3" 2-1/2" 3" 2-1/2" 3" 2-1/2" 3-1/2" 3"
61-91m
5.1cm
3.8cm
6.4cm
5.1cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
8.9cm
7.6cm
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
SECTION 4. Water Connections
Hot water piping should be supported by suitable hangers or floor stands. Do not support piping with this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a drain or in a manner to prevent injury in the event of pressure relief. Install shutoff valves where required by code.
PowerMax pool heaters are equipped with mounted pumps, which serve the heater plus 30 feet of full-sized piping with a normal number of fittings. If the pool’s loop is more than 15 feet away from the heater, please contact the factory.
A mixing system is shipped with the heater, to be mounted in the field. The system consists of a three­way valve, temperature control and piping. The temperature sensor for the control is in the heater inlet. When the control detects water temperature that is below 120°F (49°C), it will direct the three-way valve to actuate, which sends water from the outlet of the heater back to the inlet. The outlet water that is diverted to the inlet mixes with the return water from the pool, and keeps the inlet temperature at or above 120°F (49°C) (see Figure 4). This keeps cold return water from causing condensing on the outside of the PowerMax heat exchanger.
See Figure 5 for proper connection of the PowerMax heater to the pool loop.
Do not use open flame to check for leaks.
Caution
NOTE: The PowerMax appliance and all other gas
appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line. The PowerMax may not fire if the gas pressure lower than 5" w.c.
Figure 4. Mixing System.
4.2 Automatic Chlorinators
A concentration of chlorine in the heater can be very destructive; therefore the following rules about the installation and operation of such devices must be followed:
Loading...
+ 25 hidden pages