3
LOCATION OF UNIT
Locate the pump as near the liquid source as possible,
using a short, direct suction pipe. Keep the static suction lift (vertical distance between the center line of the
pump and the liquid level) to a minimum. Mount the
pump on a solid, level foundation, which provides a
rigid and vibration-free support. It should be located
where the unit is readily accessible for service and
maintenance. The pump should be protected against
flooding and excessive moisture. Do not allow pump or
any system component to freeze.
PIPING
Both suction and discharge piping should be independently supported at a point near the pump to avoid
strains being placed on the pump. Start all piping at
pump to avoid strains left by a gap at last connection.
SUCTION PIPING
The suction pipe must be kept free of leaks. The suction pipe must have a gradual slope upward to the
pump. Avoid any fittings which may cause an air trap.
On units that have a suction fitting, a check valve is a
built-in feature and no foot valve is required.
DISCHARGE PIPING
A gate valve and union should be installed in the discharge line. For removal of the pump for service, close
the gate valve, and disconnect at union.
Never run pump dry. Running pump
without water may cause pump to overheat, damaging
seal and possibly causing burns to persons handling
pump. Fill pump with water before starting.
Never run pump against closed discharge. To do so can boil water inside pump, caus-
ing hazardous pressure in unit, risk of explosion and
possibly scalding persons handling pump.
PRIMING THE PUMP
A tee installed in the discharge opening of the pump,
and provided with a priming plug at the top position, will
enable you to fill the pump with liquid. Once filled and
the priming plug replaced, the pump will prime. The
pump should prime itself time after time, as long as the
built-in check valve functions.
TABLE I - RECOMMENDED FUSING AND WIRING DATA - 60 CYCLE MOTORS
DIAMETER IN FEET FROM MOTOR TO METER
BRANCH 0’ 101’ 201’ 301’ 401’
FUSE* TO TO TO TO TO
MOTOR MAX. LOAD RATING 100’ 200’ 300’ 400’ 500’
HP AMPERES AMPS
115/230 VOLT SINGLE PHASE WIRE SIZE
1 15.3/7.6 20/15 12/14 8/14 6/14 6/12 4/10
1-1/2 19.2/9.6 25/15 10/14 8/14 6/12 4/10 4/10
2 24.0/12.0 30/15 10/14 6/14 6/12 4/10 4/10
2-1/2 26.0/12.0 30/15 10/14 16/14 4/12 4/10 4/10
230/460 VOLT THREE PHASE WIRE SIZE
1 3.6/1.8 15/15 14/14 14/14 14/14 14/14 14/14
1-1/2 4.7/2.35 15/15 14/14 14/14 14/14 14/14 14/14
2 6.8/3.4 15/15 14/14 14/14 14/14 12/14 12/14
2-1/2 8.5/4.25 15/15 14/14 14/14 14/14 12/14 10/14
200/400 VOLT THREE PHASE WIRE SIZE
1 3.8/1.9 15/15 14/14 14/14 14/14 14/14 14/14
*A Fusetron is recommended instead of a fuse in any motor circuit.
IMPORTANT: BE SURE lead wire opening on end of
motor is fully sealed when conduit or a pressure switch
is not used. Failure to seal it properly will allow dirt, rain,
bugs, etc. to enter back compartment of motor through
conduit opening and cause switch malfunction.