Spectrex 40-40U, 40-40UB User Manual

Models 40/40U and UB
UV Flame Detectors
User Guide
8200 Market Blvd, Chanhassen, MN 55317, USA
Phone: +1 (973) 239 8398
Website: www.spectrex.net Email: spectrex.csc.rmtna@emerson.com
Legal Notice
The SPECTREX SharpEye Optical Flame Detector described in this document is the property of Rosemount.
No part of the hardware, software or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system or translated into any language or computer language, in any form or by any means, without prior written permission of Rosemount.
While great efforts have been made to assure the accuracy and clarity of this document, Rosemount assumes no liability resulting from any omissions in this document, or from misuse of the information obtained herein. The information in this document has been carefully checked and is believed to be entirely reliable with all of the necessary information included. Rosemount reserves the right to make changes to any products described herein to improve reliability, function, or design, and reserves the right to revise this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or changes. Rosemount does not assume any liability arising out of the application or any use of any product or circuit described herein; neither does it convey license under its patent rights or the rights of others.
Warranty
SPECTREX agrees to extend to Purchaser/Distributor a warranty on the SPECTREX supplied components of the SharpEye products. SPECTREX warrants to Purchaser/Distributor that the products are free from defects in materials and workmanship for a period of five (5) years, commencing with the date of delivery to Purchaser/Distributor. SPECTREX expressly excludes damage incurred in transit from the factory or other damage
due to abuse, misuse, improper installation, or lack of maintenance or “Act of God” which are above and beyond its
control. SPECTREX will, upon receipt of any defective product, transportation prepaid, repair or replace it at its sole
discretion if found to have been defective when shipped. Said repair or replacement is SPECTREX’S sole liability under this warranty and SPECTREX’S liability shall be limited to repair or replacement of the component found
defective and shall not include any liability for consequential or other damages. The customer is responsible for all freight charges and taxes due on shipments both ways. This warranty is exclusive of all other warranties express or implied.
TM40/40U Rev. (Af), February 2019
TM40/40U Rev. (Af), February 2019 v
Table of Contents
Table of Contents ............................................................................................ v
List of Figures ................................................................................................ ix
List of Tables ................................................................................................... x
1 About this Guide ...................................................................................... 11
1.1 Release History ..................................................................................... 12
1.2 Glossary and Abbreviations .................................................................... 12
1.3 Notifications ......................................................................................... 14
2 Product Overview .................................................................................... 15
2.1 Approvals............................................................................................. 15
2.2 Model and Types ................................................................................... 16
2.3 Features and Benefits ............................................................................ 18
2.4 Principles of Operation ........................................................................... 19
2.4.1 Hydrocarbon Fire Detection .............................................................. 19
2.4.2 Heated Optics ................................................................................. 19
2.4.3 HART Protocol ................................................................................ 19
2.4.4 RS-485 Modbus .............................................................................. 20
2.4.5 Product Certification ........................................................................ 20
2.5 Performance Considerations ................................................................... 22
2.5.1 Detection Sensitivity ....................................................................... 22
2.5.2 Cone of Vision ................................................................................ 24
2.5.3 False Alarm Prevention .................................................................... 25
2.5.4 Visual Indicators ............................................................................. 26
2.5.5 Output Signals ................................................................................ 26
2.5.6 Detector Status .............................................................................. 27
2.5.7 Auxiliary Relay as End-of-Line .......................................................... 29
2.6 Internal Detector Tests .......................................................................... 29
2.6.1 Continuous Feature Test .................................................................. 29
2.6.2 Response to Fault Indication ............................................................ 30
2.6.3 Built-In-Test (BIT) .......................................................................... 30
3 Installing the Detector ............................................................................ 33
3.1 General Guidelines ................................................................................ 33
3.1.1 Sensitivity ...................................................................................... 33
3.1.2 Wiring ........................................................................................... 33
vi SharpEye™ UV Flame Detectors User Guide
3.1.3 Spacing and Location ...................................................................... 33
3.1.4 Environment .................................................................................. 33
3.1.5 Aiming the Detector ........................................................................ 34
3.2 Unpacking the Product ........................................................................... 34
3.2.1 Checking the Product Type ............................................................... 34
3.3 Required Tools ...................................................................................... 34
3.4 Certification Instructions ........................................................................ 35
3.4.1 Special Instructions for Safe Use ....................................................... 35
3.4.2 General Instructions ........................................................................ 36
3.5 Installation Cables ................................................................................ 37
3.5.1 Conduit Installation ......................................................................... 37
3.6 Installing the Tilt Mount ......................................................................... 38
3.6.1 Tilt Mount Assembly ........................................................................ 39
3.7 Connecting the Detector ........................................................................ 40
3.7.1 Verifying the Detector Wiring ........................................................... 42
3.8 Configuring Your Detector ...................................................................... 43
3.8.1 Alarm Delay ................................................................................... 44
3.8.2 Address Setup ................................................................................ 44
3.8.3 Function Setup ............................................................................... 44
3.8.4 Heated Optics ................................................................................. 45
4 Operating the Detector ............................................................................ 47
4.1 Powering Up ......................................................................................... 47
4.2 Safety Precautions ................................................................................ 47
4.2.1 Default Functions Settings ............................................................... 48
4.3 Testing Procedures ................................................................................ 48
4.3.1 Automatic BIT Test ......................................................................... 49
4.3.2 Manual BIT Test .............................................................................. 49
4.3.3 Testing with Flame Simulator Model FS-1200 ..................................... 49
5 Maintenance and Troubleshooting ........................................................... 51
5.1 Maintenance ......................................................................................... 51
5.1.1 General Procedures ......................................................................... 51
5.1.2 Periodic Procedures ......................................................................... 51
5.1.3 Keeping Maintenance Records .......................................................... 52
5.2 Troubleshooting .................................................................................... 52
Appendix A: Specifications ....................................................................... 53
A.1 Technical Specifications ......................................................................... 53
TM40/40U Rev. (Af), February 2019 vii
A.2 Electrical Specifications .......................................................................... 54
A.2.1 Electrical Input Protection ................................................................ 54
A.3 Outputs ............................................................................................... 54
A.3.1 Electrical Interface .......................................................................... 54
A.3.2 Electrical Outputs ............................................................................ 55
A.3.3 Heated Optics ................................................................................. 56
A.4 Approvals............................................................................................. 57
A.4.1 Hazardous Area Approvals ............................................................... 57
A.4.2 Functional Approvals ....................................................................... 57
A.5 Mechanical Specifications ....................................................................... 57
A.5.1 Enclosure ....................................................................................... 58
A.5.2 Water and Dust Tight ...................................................................... 58
A.5.3 Electronic Modules .......................................................................... 58
A.5.4 Electrical Connection (2 entries) ....................................................... 58
A.5.5 Dimensions .................................................................................... 58
A.5.6 Weight .......................................................................................... 58
A.6 Environmental Specifications .................................................................. 58
A.6.1 High Temperature ........................................................................... 58
A.6.2 Low Temperature ............................................................................ 58
A.6.3 Humidity ........................................................................................ 59
A.6.4 Salt Fog ......................................................................................... 59
A.6.5 Dust .............................................................................................. 59
A.6.6 Vibration ........................................................................................ 59
A.6.7 Mechanical Shock............................................................................ 59
A.6.8 Electromagnetic Compatibility (EMC) ................................................. 59
Appendix B: Wiring Instructions ............................................................... 61
B.1 General Instructions for Electrical Wiring .................................................. 61
B.2 Calculation Formula ............................................................................... 61
B.3 Typical Wiring Configurations ................................................................. 63
Appendix C: RS-485 Communication Network .......................................... 67
C.1 RS-485 Overview .................................................................................. 67
Appendix D: Accessories ........................................................................... 69
D.1 Flame Simulator FS-1200 ....................................................................... 69
D.1.1 Ordering Information ....................................................................... 69
D.1.2 Unpacking ...................................................................................... 70
D.1.3 Operating Instructions ..................................................................... 70
viii SharpEye™ UV Flame Detectors User Guide
D.1.4 Range ........................................................................................... 71
D.1.5 Charging the Battery ....................................................................... 71
D.1.6 Battery Replacement ....................................................................... 72
D.2 Technical Specifications ......................................................................... 73
D.2.1 General ......................................................................................... 73
D.2.2 Electrical ........................................................................................ 73
D.2.3 Physical ......................................................................................... 73
D.2.4 EMI Compatibility ............................................................................ 74
D.3 Tilt Mount ............................................................................................ 75
D.4 Duct Mount .......................................................................................... 76
D.5 Weather Cover ..................................................................................... 77
D.6 Air Shield ............................................................................................. 78
Appendix E: SIL-2 Features ...................................................................... 79
E.1 40/40UB Flame Detector ....................................................................... 79
E.1.1 Safety Relevant Parameters ............................................................. 79
E.1.2 Guidelines for Configuring, Installing, Operating, and Service ............... 79
Appendix F: End of Line Resistor .............................................................. 81
Technical Support ......................................................................................... 84
TM40/40U Rev. (Af), February 2019 ix
List of Figures
Figure 1: Horizontal Field of View ........................................................................ 24
Figure 2: Vertical Field of View ............................................................................ 24
Figure 3: Indicator LED ...................................................................................... 26
Figure 4: Detector with Tilt Mount ....................................................................... 38
Figure 5: Tilt Mount Assembly ............................................................................. 39
Figure 6: Tilt Mount Assembly (dimensions in millimeters and inches) ..................... 39
Figure 7: Detector with Cover Removed ............................................................... 41
Figure 8: Wiring Terminals ................................................................................. 63
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2 Wiring) ............. 64
Figure 10: 0–20mA Wiring Option 1 (Sink 4-Wire) - Default ................................... 64
Figure 11: 0–20mA Wiring Option 1 (Converted to Source 3-Wire) .......................... 65
Figure 12: 0–20mA Wiring Option 1 (Non-isolated Sink 3-Wire) .............................. 65
Figure 13: 0–20mA Wiring Option 2 and 3 (Source 3-Wire available with the HART Protocol)
....................................................................................................................... 66
Figure 14: RS-485 Networking ............................................................................ 67
Figure 15: Flame Simulator FS-1200 ................................................................... 69
Figure 16: Flame Simulator Battery Replacement .................................................. 71
Figure 17: Tilt Mount ......................................................................................... 75
Figure 18: Duct Mount ....................................................................................... 76
Figure 19: Weather Cover .................................................................................. 77
Figure 20: Air Shield .......................................................................................... 78
Figure 21: End of Line Resistor Assembly ............................................................. 81
x SharpEye™ UV Flame Detectors User Guide
List of Tables
Table 1: Wiring Options ..................................................................................... 17
Table 2: Detector Versions ................................................................................. 17
Table 3: Fuel Sensitivity Ranges .......................................................................... 23
Table 4: Immunity to False Alarm Sources ........................................................... 25
Table 5: LED Indications .................................................................................... 26
Table 6: Available Output Types .......................................................................... 27
Table 7: Detector Status .................................................................................... 27
Table 8: Output Signals Versus Detector State ...................................................... 28
Table 9: Results of a Successful BIT .................................................................... 31
Table 10: Results of an Unsuccessful BIT ............................................................. 31
Table 11: Results of a Successful Manual BIT ........................................................ 32
Table 12: Results of an Unsuccessful Manual BIT .................................................. 32
Table 13: Tools ................................................................................................. 35
Table 14: Model 40/40U and UB Wiring Options .................................................... 42
Table 15: Functions ........................................................................................... 44
Table 16: Default Function Values ....................................................................... 48
Table 17: Results of Successful Flame Simulator Test ............................................ 50
Table 18: Troubleshooting Table ......................................................................... 52
Table 19: Electrical Specifications ........................................................................ 54
Table 20: Contact Ratings .................................................................................. 55
Table 21: 20mA Current Output .......................................................................... 55
Table 22: Electromagnetic Compatibility (EMC) ..................................................... 59
Table 23: Maximum DC Resistance at 68°F/20ºC for Copper Wire ........................... 61
Table 24: Wiring Length in Feet/Meters ................................................................ 61
Table 25: Wiring Connections ............................................................................. 63
Table 26: Sensitivity Ranges ............................................................................... 71
Table 27: Immunity Tests .................................................................................. 74
Table 28: Emission Tests .................................................................................... 74
About this Guide
TM40/40U Rev. (Af), February 2019 11
1 About this Guide
This guide describes the SharpEye Model 40/40U and UB UV Flame Detector and its features and provides instructions on how to install, operate, and maintain the detector.
Note:
This user guide should be read carefully by all individuals who have or will have responsibility for using, maintaining, or servicing the product.
This guide includes the following chapters and appendices:
Chapter 1, About this Guide, details the layout of the guide, includes the
release history, a glossary and abbreviations, and explains how notifications are used in the guide.
Chapter 2, Product Overview, provides a general overview of the product,
principles of operation, and performance considerations.
Chapter 3, Installing the Detector, describes how to install the detector
including preparations before installation, wiring and mode settings.
Chapter 4, Operating the Detector, describes how to power-up and test
the detector. The chapter also lists safety precautions you should take when operating the detector.
Chapter 5, Maintenance and Troubleshooting, describes basic
maintenance, troubleshooting, and support procedures.
Appendix A, Specifications, lists the detectors technical and other
specifications.
Appendix B, Wiring Instructions, lists the wiring instructions for
connecting the detector and also provides examples of typical wiring configurations.
Appendix C, RS-485 Communication Network, provides an overview of
the RS-485 communications network.
Appendix D, Accessories, describes the accessories available for the
detector.
Appendix E, SIL-2 Features, describes the special conditions for compliance
with EN 61508 for SIL 2 requirements according to TÜV.
Appendix F, End of Line Resistor, describes the option of adding an end of
line resistor.
About this Guide
12 SharpEye™ UV Flame Detectors User Guide
1.1 Release History
Rev
Date
Revision History
Prepared by
Approved by
0
May 2008
First Release
Ian Buchanan
Eric Zinn
1
September 2008
Second Release
Ian Buchanan
Eric Zinn 2
July 2010
Third Release
Ian Buchanan
Eric Zinn
3
August 2010
Fourth Release
Ian Buchanan
Eric Zinn
4
November 2010
Fifth Release
Ian Buchanan
Eric Zinn 5
June 2011
Sixth Release
Ian Buchanan
Eric Zinn
6
February 2013
Seventh Release
Ian Buchanan
Eric Zinn
7
July 2013
Eighth Release
Ian Buchanan
Eric Zinn
8
February 2015
Ninth Release
Ian Buchanan
Eric Zinn
9
June 2015
Tenth Release
Ian Buchanan
Eric Zinn
10
January 2016
Eleventh Release
Ian Buchanan
Eric Zinn
11
July 2016
Twelfth Release
Ian Buchanan
Eric Zinn
12
October 2016
Thirteenth Release
Jay Cooley
Ian Buchanan
13
January 2017
Fourteenth Release
Jay Cooley
Ian Buchanan
14
February 2017
Fifteenth Release
Jay Cooley
Ian Buchanan
Ae
March 2018
Sixteenth Release
Michal Heller
Udi Tzuri
Af
February 2019
Seventeenth Release
Michal Heller
Udi Tzuri
1.2 Glossary and Abbreviations
Abbreviation/Term
Meaning
Analog Video
Video values are represented by a scaled signal
ATEX
Atmosphere Explosives
AWG
American Wire Gauge
BIT
Built-In-Test
CMOS
Complementary Metal-Oxide Semiconductor image sensor
Digital Video
Each component is represented by a number representing a discrete quantization
DSP
Digital Signal Processing
EMC
Electromagnetic Compatibility
EMI
Electromagnetic Interference
About this Guide
TM40/40U Rev. (Af), February 2019 13
Abbreviation/Term
Meaning
EOL
End of Line
FOV
Field of View
HART
Highway Addressable Remote Transducer – communications protocol
IAD
Immune at Any Distance
IECEx
International Electro-Technical Commission Explosion
IP
Internet Protocol
IPA
Isopropyl Alcohol
IR
Infrared
IR3
Refers to the 3 IR sensors in the VID
JP5
Jet Fuel
LED
Light Emitting Diode
MODBUS
Serial communications protocol using Master-Slave messaging
N/A
Not Applicable
N.C.
Normally Closed
NFPA
National Fire Protection Association
N.O.
Normally Open NPT
National Pipe Thread
NTSC
National Television System Committee (a color encoding system)
PAL
Phase Alternation by Line (a color encoding system)
P/N
Part Number
RFI
Radio Frequency Interference
RTSP
Real Time Streaming Protocol
SIL
Safety Integrity Level
UNC
Unified Coarse Thread
VAC
Volts Alternating Current
About this Guide
14 SharpEye™ UV Flame Detectors User Guide
1.3 Notifications
This section explains and exemplifies the usage of warnings, cautions, and notes throughout this guide:
Warning:
This indicates a potentially hazardous situation that could result in serious injury and/or major damage to the equipment.
Caution:
This indicates a situation that could result in minor injury and/or damage to the equipment.
Note:
This provides supplementary information, emphasizes a point or procedure, or gives a tip to facilitate operation.
Product Overview
TM40/40U Rev. (Af), February 2019 15
2 Product Overview
There are 2 versions of the 40/40 Series UV Flame Detectors: Model 40/40U and model 40/40UB, which also includes a Built-in-Test (BIT) feature.
The 40/40UV Flame Detectors detect hydrocarbon-based fuels and gas fires, invisible hydrogen flames and fires from hydride, ammonia, saline, and other organic fires.
Note:
This type of detector should not be exposed to a UV radiation source, such as welding, sparks, or an electronic arc, as it will result in a false alarm.
All 40/40 series detectors include a heated optical window for improved performance in ice, snow, and condensation conditions.
Detection performance can be easily adapted to all environments, applications,
and requirements, by changing the detector’s configuration parameters.
Adjusting these parameters, as well as performing other maintenance and monitoring tasks, is possible by means of RS-485-based Modbus communication or HART communication (in models with 0–20mA output).
Warning:
The detector is not field-repairable due to the meticulous alignment and calibration of the sensors and the respective circuits. Do not attempt to modify or repair the internal circuits or change their
settings, as this will impair the system’s performance and void the
SPECTREX product warranty.
The SharpEye 40/40 detector is designed to operate as a stand-alone unit directly connected to an alarm system or an automatic fire extinguishing system. The detector can also be a part of a more complex system, where many detectors and other devices are integrated through a common control unit.
2.1 Approvals
The detector enclosure is ATEX certified Exd flameproof with an integral, segregated, rear, Exe terminal compartment (avoiding exposure of the sensors and electronics to the surrounding environment). Hence the combined approval:
Ex II 2G D
Ex db eb op is IIC T4 Gb Ex tb op is IIIC T96°C Db (–55°C ≤ Ta ≤ +75°C)
Product Overview
16 SharpEye™ UV Flame Detectors User Guide
Or Ex II 2G D
Ex db eb op is IIC T4 Gb Ex tb op is IIIC T106°C Db (–55°C ≤ Ta ≤ +85°C)
2.2 Model and Types
The 40/40U and UB F/IR Flame Detector is provided in various configurations depending on:
UV models
Wiring options
Temperature ranges
Type of cable entries
Housing material type
Required approval
The configuration detail is included in the product part number on the product label and takes the form: 40/40U and UB-XXXXX, where XXXXX defines the model according to the above requirements.
To modify the default or pre-ordered configuration and perform maintenance tasks, please refer to the HART Protocol TM777030, the RS-485 Manual TM777050 or TM777060.
The P/Ns are defined as:
Product Overview
TM40/40U Rev. (Af), February 2019 17
Note:
Aluminum housing is not available in the FM version.
Table 1 describes the wiring options in detail.
Table 1: Wiring Options
Wiring Option
Connections Provided
1
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.
0–20mA
Sink
RS-485
HART
2
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.,
N.C.
0–20mA
Source
RS-485
HART
3
Power
Manual
BIT
Fault
Relay
N.O.
Alarm
Relay
N.O.,
N.C.
0–20mA
Source
RS-485
HART
4
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.
Auxiliary
N.O.
RS-485
-
5
Power
Manual
BIT
Fault
Relay
N.O.
Alarm
Relay
N.O.
Auxiliary
N.O.
RS-485
-
Note:
Wiring option 1 is the default. The mA sink output can be altered to source type, with a link between Terminals 1 and 8. No other wiring options can be changed onsite.
Table 2: Detector Versions
Detector Version
Description
U
UV without BIT
UB
UV with BIT
Product Overview
18 SharpEye™ UV Flame Detectors User Guide
For example, product number 40/40U and UB-321SC has the following options:
Detector Version : UV, without BIT
Wiring Option: 3 (Power, Manual BIT, RS-485, 0–20mA [Source] with the
HART protocol, Fault Relay [N.O.], Alarm Relay [N.O., N.C.])
Temperature Range: 2 (85°C)
Cable Entry: 1 (M25)
Housing : S (Stainless steel)
Approval: C (ATEX, IECEx)
Note:
Check your specific part numbers against the information in Checking the Product Type on page 34.
2.3 Features and Benefits
UV spectrum design
Built-In-Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on page
30).
Heated Window: Prevents effects of ice, snow, and condensation.
Electrical Interface:
Dry contact relays
Communication network RS-485
0–20mA output
HART Protocol: Communication protocol (see HART Protocol on page 19).
Exde: Integral junction box for easy wiring.
SIL-2: TÜV approved (model 40/40UB only).
Hazardous Area Certification: ATEX, IECEx, FM, CSA.
Functionality Approval:
EN54-10 approved by VdS
FM approved per FM3260
Accessories are approved as part of ATEX and IECEx approval.
Product Overview
TM40/40U Rev. (Af), February 2019 19
2.4 Principles of Operation
This section describes the principles of operation for the 40/40U and UB.
2.4.1 Hydrocarbon Fire Detection
The Model 40/40U and UB Flame Detector is an electronic device designed to sense the occurrence of fire and flames, and subsequently activate an alarm or an extinguishing system directly or through a control circuit.
The UV Flame Detector is a single spectrum optical detector sensitive to the UV radiation spectrum that is present in fires. The detector monitors the protected volume, by measuring the radiation intensity in it, within the frequency range of the electromagnetic spectrum, namely the Ultra-Violet (UV).
The detector senses one channel in which appropriate detection pulses are registered, and further analyzed for frequency, intensity and duration.
Sensing Element
The UV sensor is sensitive to radiation over the range of 0.185–0.260µm. The UV channel incorporates a special logic circuit that eliminates false alarms caused by solar radiation and other non-fire UV sources. Furthermore, the UV channel’s sensitivity is stabilized over the working temperature range.
Detection Levels
Detection of radiation in the UV channel, with an intensity that exceeds the detector’s preset warning level results in a:
Warning signal
Alarm signal
2.4.2 Heated Optics
The SharpEye 40/40 Flame Detector uses heated optics. The heater increases the temperature of the optical surface by 5–8°F / ~3–5°C above the ambient temperature to improve performance in ice, condensation, and snow conditions.
The heated optics can be set to one of the following:
Not operated.
On continuously.
Automatic, per temperature change (default): you can define the start
temperature below which the window is heated. (The default is 41°F/5°C.) This temperature can be defined from 32°F/0°C to 86°F/30°C. The heating stops when the temperature is 27°F/15°C above the start temperature.
For more information, see Configuring Your Detector on page 43.
2.4.3 HART Protocol
The SharpEye 40/40 Flame Detectors use the HART protocol. HART Communication is a bi-directional industrial field communication protocol
used to communicate between intelligent field instruments and host systems.
Product Overview
20 SharpEye™ UV Flame Detectors User Guide
HART is the global standard for smart process instrumentation and the majority of smart field devices installed in plants worldwide are HART-enabled. HART is available in wiring options 1, 2, and 3 (see Table 1).
HART technology is easy to use and very reliable. Through the HART connection, you are able to perform:
Detector setup
Detector troubleshooting
Detector health and status
For more details, refer to the HART Manual TM777030.
2.4.4 RS-485 Modbus
For more advanced communications, the 40/40U and UB detector has an RS-485 Modbus-compatible output that provides data communication from a network (up to 247 detectors) to a host computer or universal controller for central monitoring. This feature allows for reduced installation costs, easy maintenance, and local or remote diagnostic tools.
2.4.5 Product Certification
The 40/40U and UB Flame Detectors have the following certifications:
ATEX, IECEx, page 20
FM, CSA, page 21
SIL-, page 21
EN54-10, page 21
Inmetro (UL), page 21
TR CU/EAC, page 21
2.4.5.1 ATEX, IECEx
The 40/40U and UB Optical Flame Detector is certified to: ATEX per SIRA 07ATEX1250X and IECEx per IECEx SIR 07.0085X
Ex II 2G D Ex db eb op is IIC T4 Gb Ex tb op is IIIC T96°C Db
(–55°C ≤ Ta ≤ +75°C) Or Ex II 2G D Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db (–55°C ≤ Ta ≤ +85°C)
Product Overview
TM40/40U Rev. (Af), February 2019 21
The accessories, tilt mount P/N 40/40-001, weather cover P/N 777163 and P/N 777268, duct mount P/N 777670, and air shield P/N 777650 are included in the approval.
This product is suitable for use in hazardous Zones 1 and 2 with IIC gas group vapors present, and Zones 21 and 22 with IIIC dust type present.
2.4.5.2 FM, CSA
The 40/40U and UB Optical Flame Detector is certified for FM and CSA Explosion Proof and Functionality per FM3260:
Class I, Division 1, Groups B, C, and D.
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
For more details see FM Report Project ID3029553, and CSA Report No.
2451134.
2.4.5.3 SIL-2 (TÜV) (Model 40/40UB only)
The 40/40UB Optical Flame Detector is certified for the SIL-2 requirement per IEC 61508.4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
Alert signal via 0–20mA current loop.
Or
Alert signal via alarm relay and fault relay
For more details and guidelines for configuring, installing, operating, and
service, see SIL-2 Features on page 79 and TÜV Report No. 968/EZ - 348.
2.4.5.4 EN54-10
The 40/40U and UB Flame Detector is certified to EN54-10 and CPD.
The detector has been tested and approved per EN54-10 by VdS.
This test includes a functional test, environmental test, EMI/EMC test, and
software check.
For more details see VdS Reports Numbers BMA 12119 and BMA 12120.
2.4.5.5 Inmetro (UL)
The 40/40U and UB Flame Detectors are in compliance with the standards ABNT NBR IEC 60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC 60079-7, ABNT NBR IEC 60079-18, ABNT NBR IEC 60079-31, and INMETRO decree No. 179 as of May 18th, 2010. Further details may be found on Certificate of Compliance No. UL-BR
16.065XX.
2.4.5.6 TR CU/EAC
The 40/40U, UB Flame Detectors are in compliance with the standard TR CU 012/2011 per:
1 Ex db eb op is IIC T4 Gb X
Product Overview
22 SharpEye™ UV Flame Detectors User Guide
Ex tb op is IIIC T96°C Db X (–55°C Ta +75°C)
Or 1 Ex db eb op is IIC T4 Gb X Ex tb op is IIIC T106°C Db X (–55°C Ta +85°C)
Or 1 Ex db eb mb op is II T4 Gb X Ex tb op is IIIC T98°C Db X (–55°C Ta +75°C)
For more details, see TR CU certificate No. ТC RU C- US.МЮ62.В.05536.
2.5 Performance Considerations
This section describes performance aspects of the 40/40U and UB.
2.5.1 Detection Sensitivity
Detection sensitivity is the maximum distance at which the detector reliably detects a specific size of fire and typical type of fuel (standard fire).
2.5.1.1 Standard Fire
Defined as a 1ft2/0.1m2 n-heptane pan fire, with maximum wind speed of
6.5ft/sec / 2m/sec.
2.5.1.2 Sensitivity Ranges
The detector has 2 response levels:
Warning (Pre-alarm)
Alarm
The detection distance for the alarm level is 50ft/15m from a standard fire.
The detection distance for the warning level is approximately 10% higher than for the alarm distance.
For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for the detector is 0.005 (1/m).
Note:
Zeta parameters may vary significantly with changes in temperature, air pressure, humidity, visibility conditions, etc.
Product Overview
TM40/40U Rev. (Af), February 2019 23
2.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft
2
/0.1m2 and is defined as 100%
sensitivity.
For fuel fire – standard pan fire size: 1ft
2
/0.1m2.
For gas flame – 30”/0.75m high, 10”/0.25m width plume fire.
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type of Fuel
Max. Distance (ft/m)
40/40U and UB
Gasoline
50/15
N-Heptane
50/15
Methane1
43/13
LPG1
43/13
Hydrogen1
39/12
JP5
37/11
Kerosene
37/11
Diesel Fuel
37/11
Ethanol 95%
37/11
IPA
37/11
Polypropylene
33/10
Methanol
25/7.5
Silane2
22/7
Paper
20/6
1
30”/0.75m high, 10”/0.25m width plume fire
2
20”/0.5m high, 8”/0.2m width plume fire
Product Overview
24 SharpEye™ UV Flame Detectors User Guide
2.5.2 Cone of Vision
Horizontal: 100°
Figure 1: Horizontal Field of View
Vertical: +50° (down), –45° (up)
Figure 2: Vertical Field of View
Product Overview
TM40/40U Rev. (Af), February 2019 25
2.5.3 False Alarm Prevention
To prevent false alarms, the detector will not alarm or react to the radiation sources specified in Table 4.
Table 4: Immunity to False Alarm Sources
Radiation Source
Immunity Distance ft/m
Indirect or reflected sunlight
IAD
Vehicle headlights (low beam) conforming to MS53023-1
IAD
Incandescent frosted glass light, 300W
IAD
Fluorescent light with white enamel reflector, standard office or shop, 70W (or 2 35W)
IAD
Electric arc [12mm / 15/32” gap at 4000V alternating current, 60Hz]
IAD
Ambient light extremes (darkness to bright light with snow, water, rain, desert glare, and fog)
IAD
Bright colored clothing, including red and safety orange
IAD
Blue-green dome light conforming to M251073-1
IAD
Flashlight (MX 991/U)
IAD
Radiation heater, 3000W
IAD
Radiation heater, 1000W with fan
IAD
Lit cigar
5/1.5
Lit cigarette
5/1.5
Match, wood, stick including flare up
16.5/5
Notes:
IAD = Immune at Any Distance
All sources are chopped from 0 to 20Hz
Product Overview
26 SharpEye™ UV Flame Detectors User Guide
2.5.4 Visual Indicators
One 3-color LED indicator is located inside the detector window, as shown in Figure 3. The detector statuses are listed in Table 5.
Table 5: LED Indications
Detector Status
LED color
LED mode
Fault, BIT Fault
Yellow
4Hz - flashing
Normal
Green
1Hz - flashing
Warning
Red
2Hz - flashing
Alarm
Red
Steady
Figure 3: Indicator LED
2.5.5 Output Signals
Outputs are available according to the default configuration or the wiring options selected for the 40/40U and UB detector. Determine the outputs for your model according to Table 6.
The detector incorporates several types of output suitable to different control systems:
0–20mA (stepped) with HART
Relays (alarm, fault, auxiliary)
RS-485 Modbus
Indicator LED
Product Overview
TM40/40U Rev. (Af), February 2019 27
Table 6: Available Output Types
Output Type
Version
Detector Status
Alarm Relay
40/40U and UB – Options 1XXXX, 4XXXX, and 5XXXX
The relay is N.O.
40/40U and UB – Options 2XXXX and 3XXXX
The relay is N.O. and N.C.
Auxiliary Relay
40/40U and UB – Options 4XXXX and 5XXXX
The relay is N.O.
Fault Relay
40/40U and UB – Options 1XXXX, 2XXXX, and 4XXXX
The relay is N.C. energized
40/40U and UB – Options 3XXXX and 5XXXX
The relay is N.O. energized
0–20mA Current Output
40/40U and UB – Option 1XXXX
Sink with the HART protocol, (can be changed to Source – see Figure 10, Figure 11, and Figure
12)
40/40U and UB – Options 2XXXX and 3XXXX
Source with the HART protocol
RS-485
All versions
Modbus protocol
2.5.6 Detector Status
The possible detector function statuses are listed in Table 7. A more detailed fault analysis can be seen via HART or RS-485.
Table 7: Detector Status
Status
Description
Normal
Normal operation.
BIT
Built-In-Test being performed.
Warning
Fire detected - changed to Warning (pre-alarm state).
Alarm
Fire detected - changed to Fire Alarm state.
Latched Alarm (Optional)
The alarm outputs remain latched on following detection of a fire that has already been extinguished.
BIT Fault
A fault is detected during BIT sequence or other electric failure. The detector will continue to detect for fire.
Fault
A fault is detected when the power supply is too low, due to a software fault, or due to an electrical failure. The detector will NOT detect fire in this condition.
Product Overview
28 SharpEye™ UV Flame Detectors User Guide
In each state, the detector activates different outputs, as specified in Table 8.
Table 8: Output Signals Versus Detector State
Detector State
LED Indicator
LED Mode
Alarm Relay
Auxiliary Relay
Fault Relay
mA output
Normal
Green
1Hz
Off
Off
On
4mA
Warning
Red
2Hz
Off
On4
On
16mA
Alarm1
Red
Constant
On
On
On
20mA
Latched2
Red
Constant
On Off
On
20mA
On4
On
20mA
BIT Fault3
Yellow
4Hz
Off
Off
Off
2mA
Warning at BIT Fault
Red
2Hz
Off
On4
Off
16mA
Alarm at BIT Fault
Red
Constant
On
On
Off
20mA Fault
Yellow
4Hz
Off
Off
Off
0mA
1
The alarm outputs are activated while alarm conditions exist and will stop approximately 5
seconds after the fire is no longer detected.
2
The alarm state can be optionally latched via programmed function (default is non-latched).
3
The detector will remain in BIT Fault state until it has passed a successful BIT.
4
The auxiliary relay can be activated at the warning level or alarm level, depending on
programmed function.
Note:
The outputs depend on the wiring options.
2.5.6.1 Optional Latching
Alarms are set as non-latching by default. However, the detector includes a latched alarm output capability, which operates according to the programmed function.
If selected, upon detection of a fire, the detection signal is latched until a manual reset is performed (disconnecting the power supply, or performing a manual BIT (see Manual BIT on page 31).
Latching affects the alarm relay, 0–20mA output, the alarm LED (the auxiliary relay will be latched only when the programmable function auxiliary relay is set to yes.
Product Overview
TM40/40U Rev. (Af), February 2019 29
Notes:
The auxiliary relay is available only in models with suffix – 4XXXX
and 5XXXX
The 0–20mA is available only in models with suffix – 1XXXX,
2XXXX, and 3XXXX
2.5.7 Auxiliary Relay as End-of-Line
The auxiliary relay can be used as End-of-Line in models with suffix – 4XXXX and 5XXXX only. In this case, the auxiliary relay is active as long as the detector is powered.
2.6 Internal Detector Tests
The detector performs 2 types of self-tests:
Continuous Feature Test, page 29
Built-In-Test (BIT), page 30
2.6.1 Continuous Feature Test
During normal operation, the detector tests itself continuously and indicates a fault if a failure is found. This type of test complies with SIL-2 requirements.
The detector continuously tests:
Input voltage level
All internal regulator voltage levels
Voltage level status of sensor and sensor circuitry for noise or disconnection
in the electronic circuitry
0–20mA level output
Relays and heater operation
Processor watchdog
Software
Memory
Oscillator frequency
Product Overview
30 SharpEye™ UV Flame Detectors User Guide
2.6.2 Response to Fault Indication
If a failure is found, the detector indicates by:
Fault relay:
Opens in wiring options 1, 2, and 4
Closes in wiring options 3 and 5
0-20mA: indicates fault (0mA or 2mA) in wiring options 1, 2, and 3
LED – yellow flashes (4Hz)
Correcting the fault
The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.
2.6.3 Built-In-Test (BIT)
The detector’s Built-In-Test (BIT) also checks the following:
Electronic circuitry
Sensors
Window cleanliness
The detector can be set to perform the BIT in the following modes:
Automatically and manually
Manually only
Note:
In Manual BIT, the outputs may also be tested and Control System “inhibit” should be applied if this could initiate other systems.
2.6.3.1 How the BIT Operates
The detector's status remains unchanged if the result of a BIT is the same as
the current status (normal or BIT fault).
The detectors status changes (from normal to BIT fault or vice versa) if the
BIT differs from the current status.
Note:
In BIT fault status the detector can continue to detect a fire.
Product Overview
TM40/40U Rev. (Af), February 2019 31
2.6.3.2 Automatic BIT
The detector automatically performs a BIT every 15 minutes. A successful BIT sequence does not activate any indicator.
All outputs of BIT results function as described in Table 9 and Table 10, and the BIT is automatically executed every 1 minute.
This sequence continues until a successful BIT occurs, when the detector resumes normal operation.
Table 9: Results of a Successful BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: remains closed
Wiring options 3 and 5: remains open
0–20mA Output
Wiring options 1, 2, and 3: normal (4mA) Power LED
Green, flashing, 1Hz on (normal)
Table 10: Results of an Unsuccessful BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: changes to open Wiring options 3 and 5: changes to closed
0–20mA Output
Wiring options 1, 2, and 3: BIT fault (2mA) Power LED
Yellow, flashing, 4Hz
BIT Procedure
Performed every 1 minute
2.6.3.3 Manual BIT
The BIT is manually initiated by momentarily connecting Terminal 3 with Terminal 2 (or a switch across these terminals in the safe area).
The results of a successful and unsuccessful Manual BIT are listed in Table 11 and Table 12.
Product Overview
32 SharpEye™ UV Flame Detectors User Guide
Table 11: Results of a Successful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: remains Closed (Normal)
Wiring options 3 and 5: remains Open (Normal)
Alarm Relay
Activated for 3 sec (only when the function alarm BIT is set to YES)
Auxiliary Relay
For wiring options 4 and 5: is activated for 3 sec (only when the function auxiliary BIT is set to Yes)
0–20mA Output
Wiring options 1, 2, and 3:
Initiates 20mA only when the function alarm BIT is set
to Yes
Initiates 16mA when the function auxiliary BIT is set to
Yes and the function alarm BIT is set to No
Power LED
Green, Flashing, 1Hz
Table 12: Results of an Unsuccessful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: changes to Open
Wiring options 3 and 5:changes to Closed
0–20mA Output
Wiring options 1, 2, and 3: Indicates BIT Fault (2mA) Power LED
Yellow, Flashing, 4Hz
2.6.3.4 Manual BIT Only
The BIT is initiated manually by momentarily connecting Terminal Number 3 with Terminal Number 2 (or a switch across these terminals in the safe area).
Installing the Detector
TM40/40U Rev. (Af), February 2019 33
3 Installing the Detector
This chapter provides basic guidelines for installing the detector. It does not attempt to cover all of the standard practices and codes of installation. Rather, it emphasizes specific points of consideration and provides some general rules for qualified personnel. Wherever applicable, special safety precautions are stressed.
3.1 General Guidelines
To ensure optimal performance and an efficient installation, consider the following guidelines:
3.1.1 Sensitivity
To determine the level of sensitivity, consider the following:
Size of fire at the required distance to be detected
Type of flammable materials
3.1.2 Wiring
The wire gauge must be designed according to the distance from the detector
to the controller and the number of detectors on the same power line. See Wiring Instructions on page 61.
To fully comply with EMC directive and protect against interference caused by
RFI and EMI, the cable to the detector must be shielded and the detector must be grounded. The shield should be grounded at the detector end.
3.1.3 Spacing and Location
The number of detectors and their locations in the protected area are
determined by:
Size of the protected area
Sensitivity of the detectors
Obstructed lines of sight
Cone of view of the detectors
3.1.4 Environment
Dust, snow, or rain can reduce the detectors sensitivity and require more
maintenance activities.
The presence of high intensity flickering IR sources may affect sensitivity.
Installing the Detector
34 SharpEye™ UV Flame Detectors User Guide
3.1.5 Aiming the Detector
The detector should be aimed toward the center of the detection zone and
have a completely unobstructed view of the protected area.
Whenever possible, the detector face should be tilted down at a 45º angle to
maximize coverage and prevent accumulation of dust and dirt.
Do not start an installation unless all conceivable considerations regarding
detection location have been taken into account.
Installation should comply with NFPA 72E or any other local and international regulations and standards, as applicable to flame detectors and installation of Ex approved products.
3.2 Unpacking the Product
Upon receipt of your detector, verify that you have received the following contents:
Delivery form
Flame detector
Plastic weather cover
User manual
Quality document
Tool keys (per shipment)
Check and record the following:
Verify the appropriate Purchase Order.
Record the Part Number (P/N) and Serial Number of the detectors, and the
installation date in an appropriate logbook.
Verify that all components required for the detector installation are readily
available before beginning the installation. If the installation is not completed in a single session, secure and seal the detectors and conduits/cable entries.
3.2.1 Checking the Product Type
Check that your product has the configuration/options that you ordered. Check the detailed part number on the label and compare this information with the descriptions contained in Model and Types on page 16.
3.3 Required Tools
The detector can be installed using general-purpose common tools and equipment. Table 13 lists the specific tools required to install the detector.
Installing the Detector
TM40/40U Rev. (Af), February 2019 35
Table 13: Tools
Tool
Function
Comments
Hex key 3/16”
Open and close detector cover (for wiring)
Part of the kit
Hex key 1/4”
Mount the detector on the tilt mount
Part of the kit
Flat screwdriver 6mm
Connect ground terminal
Standard tool
Flat screwdriver
2.5mm
Connect wires to the terminal blocks
Standard tool
For wiring, use color-coded conductors or suitable wire markings or labels. 12– 20AWG / 0.5–3.5mm² wires may be used for site wiring. The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit, in compliance with specifications (see General Instructions for Electrical Wiring on page 61).
3.4 Certification Instructions
Warning:
Do not open the detector, even when isolated, in the presence of any open flame.
3.4.1 Special Instructions for Safe Use
The dimensions of the flame paths are other than the relevant minimum or maximum, as required by Table 2 of EN 60079-1:2014, as detailed below:
Flame Path Location
Type of Joint
Maximum Gap, ic
Minimum Length, L
Sapphire window
Flanged
0.04mm
10.5mm
Main spigot
Cylindrical
0.15mm
15.5mm
Gaps, ic, should not be modified to be any larger, and lengths, L, should not
be modified to be any shorter than the values shown in the table above.
Units may be painted or fitted with optional accessories, some of which are
made of a non-metallic material or have a non-metallic coating which could potentially generate an ignition-capable level of electrostatic charge under certain extreme conditions. Therefore, these units should not be installed in a location where they may be subjected to external conditions (such as high­pressure steam) which might cause a build-up of electrostatic charges on the non-conducting surfaces. Cleaning of the equipment (except window) should be done only with a damp cloth.
Installing the Detector
36 SharpEye™ UV Flame Detectors User Guide
The 3 fastening screws used to screw on the cover of the flameproof
compartment have a yield stress of 344N/mm². Any replacement fasteners must have a yield stress of at least this value.
When the duct mount is fitted and the equipment is intended to be mounted
to a heated/cooled air duct/process vessel, it should be verified that the temperature of the air duct/process vessel should not be capable of heating or cooling any part of the equipment enclosure to a temperature outside the marked maximum ambient temperature range prior to switching the equipment on, when taking into account surrounding ambient temperature.
3.4.2 General Instructions
The cable entry point may exceed 167°F/75°C. Suitable precautions should be
taken when selecting the cable.
The equipment may be used with flammable gases and vapors with apparatus
groups IIA, IIB, and IIC:
T4 in the ambient temperature range: -67°F/-55°C to +167°F/+75°C.
T4 in the ambient temperature range: -67°F/-55°C to +185°F/+85°C.
Installation should be carried out by suitably trained personnel in accordance
with the applicable code of practice such as. EN 60079-14:1997.
Inspection and maintenance of this equipment should be carried out by
suitably trained personnel in accordance with the applicable code of practice such as EN 60079-17.
Repair of this equipment should be carried out by suitably trained personnel
in accordance with the applicable code of practice such as EN 60079-19.
The certification of this equipment relies upon the following materials used in
its construction:
Enclosure: 316L Stainless Steel or Aluminum
Window: Sapphire Glass
If the equipment is likely to come into contact with aggressive substances,
then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection provided by the equipment is not compromised:
Aggressive substances: acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: regular checks as part of routine inspections or
establishing from the material’s data sheets that it is resistant to specific
chemicals.
Installing the Detector
TM40/40U Rev. (Af), February 2019 37
3.5 Installation Cables
The following guideline for the cable installation:
All cables to the detector must be well shielded in order to comply with EMC
requirement (see Table 22).
Ground the detector to the nearest ground point (not more than 3m from the
detector location).
Install the detector with the cable entries placed downwards.
3.5.1 Conduit Installation
The conduit used for the cabling must comply with the following:
To avoid water condensation or water in the detector, install the detector with
the conduits placed downward to include drain holes.
When using the optional tilt mount, use flexible conduits for the last portion
connecting to the detector.
For installations in atmospheres as defined in group B of the NFPA 72E, seal
the conduits inlets.
When pulling the cables through the conduits, ensure that they are not
tangled or stressed. Extend the cables about 30cm/12 beyond the detector location to accommodate wiring after installation.
After the conductor cables have been pulled through the conduits, perform a
continuity test.
Installing the Detector
38 SharpEye™ UV Flame Detectors User Guide
3.6 Installing the Tilt Mount
The tilt mount (P/N 40/40-001) enables the detector to be rotated up to 60º in all directions.
Figure 4 shows the detector mounted on the tilt mount.
Figure 4: Detector with Tilt Mount
Installing the Detector
TM40/40U Rev. (Af), February 2019 39
3.6.1 Tilt Mount Assembly
Figure 5 shows the tilt mount assembly.
Figure 5: Tilt Mount Assembly
Figure 6 shows the tilt mount assembly with dimensions in both millimeters and inches.
Figure 6: Tilt Mount Assembly (dimensions in millimeters and inches)
Tilt Mount
Tilt Holding Plate
Horizontal Locking Screw
Vertical Locking
Screw
Detector Holding
Plate
Installing the Detector
40 SharpEye™ UV Flame Detectors User Guide
To install the tilt mount and detector:
1 Place the tilt mount in its designated location and secure it with 4 fasteners
through 4 holes 7mm in diameter. Use the 4 screws and spring washers according to the kit.
Note:
Removing the detector for maintenance purpose does not require the tilt mount to be removed.
2 Unpack the detector. 3 Place the detector with its conduit/cable entries pointing downwards on the
holding plate of the tilt mount. Secure the detector with 5/16” 18 UNC x 1” screw to the tilt mount.
4 Release the horizontal and vertical locking screws using 3/16 hex key so that
the detector can be rotated. Point the detector towards the protected area and make certain that the view of the area is unobstructed. Secure the detector in that position by tightening the locking screws on the tilt mount, making sure the detector is in the correct position.
The detector is now correctly located, aligned, and ready to be connected to the system.
3.7 Connecting the Detector
This section describes how to connect the electric cabling to the detector (Figure
7).
To connect the detector to the electrical cables:
1 Disconnect the power. 2 Remove the back cover of the detector by removing 3 socket head-screws in
the cover bolts. The terminal chamber is now revealed.
3 Remove the protective plug mounted on the detector conduit/cable entry; pull
the wires through the detector inlet.
4 Use a 3/4” – 14 NPT explosion-proof conduit connection or M25x1.5
flameproof gland to assemble the cable/conduit to the detector.
Installing the Detector
TM40/40U Rev. (Af), February 2019 41
Figure 7: Detector with Cover Removed
5 Connect the wires to the required terminals on the terminal board according
to the wiring diagram (Figure 7) and Table 14.
6 Connect the grounding (earth) wire to the ground (earth) screw outside the
detector (earth terminal). The detector must be well grounded to earth ground.
7 Verify the wiring.
Warning:
Improper wiring may damage the detector.
8 Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the back cover (Figure 7).
9 Place and secure the detector’s back cover by screwing the 3 socket-head-
screws in the cover bolts (Figure 4).
Earth Terminal
Terminal Chamber
Terminals
Internal Earth
Terminal
Detector Holding Screw
Conduit/Cable
Inlet
Installing the Detector
42 SharpEye™ UV Flame Detectors User Guide
3.7.1 Verifying the Detector Wiring
The detector has 5 output wiring options within the Exde integral terminal section of the enclosure. There are 12 terminals labeled 1–12.
Table 14 describes the function of each terminal for all the wiring options.
Table 14: Model 40/40U and UB Wiring Options
Wire Terminal No.
Option 1 Default
Option 2
Option 3
Option 4
Option 5
1
+24VDC
+24VDC
+24VDC
+24VDC
+24VDC
2
0VDC
0VDC
0VDC
0VDC
0VDC
3
Manual Bit
Manual
Bit
Manual Bit
Manual Bit
Manual Bit
4
Fault
Relay N.C.
Fault
Relay
N.C.
Fault Relay
N.O.
Fault
Relay N.C.
Fault
Relay N.O.
5
6
Alarm
Relay N.O.
Alarm
Relay
N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
7
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
8
0–20mA
In
Alarm
Relay
N.C.
Alarm
Relay N.C.
Auxiliary
N.O.
Auxiliary
N.O.
9
0–20mA
Out*
0–20mA
Out*
0–20mA
Out*
Auxiliary
C
Auxiliary C
10
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
Available with the HART protocol.
Installing the Detector
TM40/40U Rev. (Af), February 2019 43
Notes:
RS-485 is used for the communication network as specified in
Appendix Appendix C: (Terminals 10, 11, and 12) and to connect (in a safe area) to a PC or laptop for configuration and diagnostics.
Alarm relay:
N.O. contact in wiring options 1, 4, and 5.
N.O. and N.C. in wiring options 2 and 3.
0–20mA is “Sink” in option 1 and “Source” in options 2 and 3.
0–20mA options 1, 2, and 3 are available with the HART protocol.
In wiring option 1, link Terminals 1 and 8 to change the mA output
to “Source.”
The fault output is N.C. energized SPST relay. The contacts are
closed when the detector is in its normal operational condition in options 1, 2, and 4, and available as N.O. energized in options 3 and 5.
The auxiliary output is N.O. (SPST) relay. Depending on the
function configuration, the auxiliary relay may act in parallel with the alarm relay to activate another external device, or it may provide a warning signal.
3.8 Configuring Your Detector
You can reprogram the function setup using the RS-485 connection or the HART protocol as follows:
HART Protocol: Refer to Manual TM777030 for programming instructions. These functions enable you to set:
Alarm delay
Address setup
Mode of operation
Heated optics operation
The factory default settings listed for each function include:
Alarm Delay – 3 sec
Alarm Latch – No
Auxiliary Relay – No
Automatic BIT – Yes
Alarm BIT – No
Auxiliary BIT - No
EOL – No
Heated Optics – Auto
Temperature – 41°F/5°C
Installing the Detector
44 SharpEye™ UV Flame Detectors User Guide
3.8.1 Alarm Delay
The detector is equipped with an alarm delay option, which provides programmable time delays with settings at:
Anti-flare (default)
Note:
The anti-flare mode is selected to prevent false alarms in locations where fast flares may be present. The time delay for fire alarms in this mode ranges from 2.5–15 seconds, and is usually less than 10 seconds.
0, 3, 5, 10, 15, 20, or 30 seconds When an alarm (detection) level condition occurs, the detector delays the
execution of the alarm outputs by the specified period of time. The detector then evaluates the condition for 3 seconds. If the alarm level is still present, the alarm outputs are activated. If this condition no longer exists, the detector returns to its standby state.
The alarm delay option affects the output relays and the 0–20mA. The LEDs and outputs indicate warning levels during the delay time only if the fire condition exists.
3.8.2 Address Setup
The detector provides up to 247 addresses that can be changed with the RS-485 communication link or the HART protocol.
3.8.3 Function Setup
You can select the desired functions as detailed in Table 15.
Table 15: Functions
Function
Setting
Alarm Latch
Yes: Enable alarm latching.
No: Disable alarm latching (default).
Auxiliary Relay*
Yes: Activate auxiliary relay at warning level.
No: Activate Auxiliary Relay at Alarm level
(default).
Automatic BIT
Yes: Perform automatic & Manual BIT (default).
No: Perform Manual BIT only.
Alarm BIT
Yes: Successful Manual BIT activates the Alarm
Relay for approximately 3 seconds (default).
No: Successful Manual BIT does not activate the
Alarm Relay.
Installing the Detector
TM40/40U Rev. (Af), February 2019 45
Auxiliary BIT
Yes: Successful Manual BIT activates the
Auxiliary Relay for approximately 3 seconds (default).
No: Successful Manual BIT does not activate the
Auxiliary Relay.
EOL*
Yes: Auxiliary relay is used as End-of-Line.
No: Auxiliary relay operates in accordance with
Functions 2 and 5 (default).
Only available in Models 40/40U and UB-4XXXX and 5XXXX
3.8.4 Heated Optics
The heated optics can be defined as one of the following modes:
Heated Mode
Off: Not operated
On: Continuously
Auto: Per temperature change
In Auto mode, the default Heat On setting is 41°F/5°C. Heating stops when the temperature is 27°F/15°C above the start temperature.
You can define the start temperature below which the window will be heated. The temperature can be defined between 32–86°F / 0–30°C.
Operating the Detector
TM40/40U Rev. (Af), February 2019 47
4 Operating the Detector
This chapter describes how to power up and test the detector. It also includes some very important safety checks that you should complete before operating the detector.
4.1 Powering Up
This section describes how to power up the detector. Follow these instructions carefully to obtain optimal performance from the detector over its lifecycle:
To turn on the detector:
1 Turn on the power. 2 Wait up to 60 seconds for the detector to finish the start-up procedure.
Powering up initiates the following sequence of events:
The yellow LED flashes at 4Hz.
BIT is executed.
If successful, the green LED flashes at 1Hz, the fault relay contacts close, and mA output is 4mA.
3 Enter Normal mode.
Caution:
The majority of detectors are used in the default non-latched alarm mode. Only perform a reset when the latched alarm option has been programmed.
To reset the detector when it is in a latched alarm state:
Disconnect power (Terminal Number 1 or Terminal Number 2).
or
Initiate a Manual BIT.
4.2 Safety Precautions
After powering-up, the detector requires almost no attention in order to function properly, but the following should be noted:
Follow the instructions in this guide and refer to the drawings and
specifications.
Do not expose the detector to radiation of any kind unless required for testing
purposes.
Do not open the detector housing while power is connected.
Operating the Detector
48 SharpEye™ UV Flame Detectors User Guide
Do not open the electronic compartment. This part should be kept closed at
all times and only opened in the factory. Opening the electronic component side invalidates the warranty.
You should only access the wiring compartment to wire or remove the
detector, or to access RS-485 terminals for maintenance.
External devices, such as automatic extinguishing systems, must be
disconnected or disabled before carrying out any maintenance.
4.2.1 Default Functions Settings
Table 16 lists the default function configuration supplied with the detector.
Table 16: Default Function Values
Function
Value
Notes
Alarm Delay
3 secs
Alarm Latch
No
Auxiliary Relay
No
In wiring options 1, 2, and 3 the auxiliary relay is not available. This function is not used.
Automatic BIT
Yes
Alarm BIT
No
Auxiliary BIT
No
In wiring options 1, 2, and 3 the auxiliary relay is not available. This function is not used.
EOL
No
In wiring options 1, 2, and 3 the auxiliary relay is not available. This function is not used.
Heat Mode
Auto
Heat On
41°F/5°C
The detector starts heating the window for any temperature below this value (in degrees Celsius).
In order to change the default function, use:
USB RS-485 Harness Kit P/N 794079. Refer to Manual TM777050 for
programming instructions when using the USB RS-485 Harness Kit.
HART protocol, refer to Manual TM777030 for instructions.
4.3 Testing Procedures
This section describes the proof testing procedure for proper operation of the detector. The detector can be tested using the Manual BIT or the SPECTREX Flame Simulator FS-1200.
The detector performs internal tests continuously and automatic BIT tests every 15 minutes. For more details refer to Built-In-Test (BIT) on page 30.
Operating the Detector
TM40/40U Rev. (Af), February 2019 49
4.3.1 Automatic BIT Test
Check that the indicators show normal conditions. See Powering Up on page 47.
4.3.2 Manual BIT Test
Caution:
If the function setup alarm BIT and/or auxiliary BIT are set to Yes (default is No), the alarm, auxiliary relay and 0–20mA outputs are activated during a Manual BIT. Therefore, automatic extinguishing systems or any external devices that may be activated during BIT must be disconnected.
To perform a Manual BIT:
Verify that the detector is in Normal Mode. Initiate Manual BIT. The results of successful and unsuccessful manual BITs
are detailed in Table 11 and
Table 12.
4.3.3 Testing with Flame Simulator Model FS-1200
The Flame Simulator Model FS-1200 can be used to simulate exposure of the detector to a real fire condition. The detector is exposed to radiation at the required detection level. As a result, the detector will generate a Fire Alarm signal. See Flame Simulator FS-1200 on page 69 for more information.
Caution:
If the detector is exposed to a flame simulator, the alarm and accessory relays and 0–20mA are activated during the simulation. Therefore, automatic extinguishing systems and any external devices which may be activated during this process must be disconnected.
To perform a flame simulator test:
1 Power up the system and wait up to 60 seconds for the detector to turn to a
normal state. The Power LED turns on.
2 Aim the SPECTREX Flame Simulator Model FS- at the target point of the
detector (Figure 15), such that the radiation emitted by it is facing directly towards the detector. (See Flame Simulator FS-1200 on page 69).
3 Press the operation button once. After few seconds, a successful test shows
the results listed in Table 17. The detector is now ready for operation.
Operating the Detector
50 SharpEye™ UV Flame Detectors User Guide
Table 17: Results of Successful Flame Simulator Test
Component
Action
Notes
0–20mA
Turn to 20mA
For a few seconds and then returns to 4mA
Alarm Relay
Activated
For a few seconds and then returns to Normal
Auxiliary Relay
Activated
For a few seconds and then returns to Normal
Fault Relay
Remains active during the test
LED
Red, steady
Maintenance and Troubleshooting
TM40/40U Rev. (Af), February 2019 51
5 Maintenance and Troubleshooting
This chapter deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact SPECTREX or its authorized distributor for assistance.
5.1 Maintenance
This section describes the basic maintenance steps that should be taken to keep the detector in good working condition.
5.1.1 General Procedures
Maintenance should be performed by suitably qualified personnel, who are familiar with local codes and practice. Maintenance requires ordinary tools.
5.1.1.1 Cleaning
The detector must be kept as clean as possible. Clean the viewing window and the reflector of the flame detector periodically.
The frequency of cleaning operations depends upon the local environmental conditions and specific applications. The fire detection system designer will give his recommendations.
To clean the detector viewing window and reflector:
1 Disconnect power to the detector before proceeding with any maintenance
including window/lens cleaning.
2 Use water and detergent, and then rinse the viewing window with clean
water.
3 Where dust, dirt, or moisture accumulates on the window, first clean with a
soft optical cloth and detergent only, and then rinse with clean water.
5.1.2 Periodic Procedures
In addition to preventive cleaning and maintenance, the detector should be functionally tested every 6 months or as dictated by local codes and regulations. These tests should also be conducted if the detector has been opened for any reason.
5.1.2.1 Power-Up Procedure
Perform the power-up procedure every time power is restored to the system. Follow the instructions described in Powering Up on page 47.
5.1.2.2 Functional Test Procedure
Perform a functional test of the detector as described in Internal Detector Tests on page 29.
Maintenance and Troubleshooting
52 SharpEye™ UV Flame Detectors User Guide
5.1.3 Keeping Maintenance Records
Maintenance operations performed on a detector should be recorded in a log book. The record should include the following:
Installation date
Contractor
Serial and tag number
Entries for every maintenance operation performed, including a description of
the operation, date, and personnel ID
If a unit is sent to SPECTREX or a distributor for service, a copy of the maintenance records should accompany it.
5.2 Troubleshooting
This section is a guide to correct problems which may happen during normal operation.
Table 18: Troubleshooting Table
Problem
Cause
Corrective Action
LEDs Off Fault Relay at N.O. 0–20mA at 0mA
No power to the unit
Check that the correct power
is sent to the detector.
Check power polarity.
Check wiring in the detector.
Send the detector back for
repairs.
Yellow/amber LED flashes at 4Hz Fault Relay at N.O. 0–20mA at 0mA
Fault Detector
Low Voltage\
Faulty Detector
Check the voltage at the
detector; verify at least 24V at the detector terminal.
Send the detector back for
repairs.
Yellow/amber LED flashes at 4Hz Fault Relay at N.O. 0–20mA at 2mA
BIT Fault
Faulty Detector
Clean detector window.
Re-power the detector.
Replace the detector.
Red LED constantly on
If no fire exists, then detector alarm latched
Perform a Reset.
Alarm Relay at On 0–20mA at 20mA
Alarm condition
Check cause of alarm.
If no alarm, re-power the
detector.
Send the detector back for
repairs.
Specifications
TM40/40U Rev. (Af), February 2019 53
Appendix A: Specifications
A.1 Technical Specifications
Spectral Response
UV 0.185–0.260 µm
Detection Range (at highest
sensitivity setting for 1ft2/0.1m2 pan fire)
Fuel
ft/m
Fuel
ft/m
n-Heptane
50/15
Kerosene
37/11
Gasoline
50/15
Ethanol 95%
37/11
Methane1
43/13
IPA (Isopropyl Alcohol)
37/11
LPG1
43/13
Polypropylene Pellets
33/10
Hydrogen1
39/12
Methanol
25/7.5
Diesel Fuel
37/11
Silane2
22/7
1
30”/0.75m high, 10”/0.25m width plume fire
2
20”/0.5m high, 8”/0.2m width plume fire
Response Time
Typically 3 seconds
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
1ft2/0.1m2 n-heptane pan fire from 50ft/15m
Fields of View
Horizontal 100, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)
Specifications
54 SharpEye™ UV Flame Detectors User Guide
A.2 Electrical Specifications
Table 19: Electrical Specifications
Operating Voltage
Status
All Outputs
Without 0–20mA
Power Consumption (Max. 24VDC)
Normal
1.61W
1.56W
Normal when heater on
2.28W
2.16W
Alarm
2.64W
2.28W
Alarm when heater on
3.24W
2.88W
Maximum Current (Max. 24VDC)
Normal
70mA
65mA
Normal when heater on
95mA
90mA
Alarm
110mA
95mA
Alarm when heater on
135mA
120mA
Power Consumption (Max. 18–32VDC)
Normal
1.95W
1.85W
Normal when heater on
2.56W
2.45W
Alarm
3.04W
2.56W
Alarm when heater on
3.68W
3.2W
Maximum Current (Max. 18–32VDC)
Normal
90mA
85mA
Normal when heater on
105mA
100mA
Alarm
130mA
115mA
Alarm when heater on
160mA
145mA
A.2.1 Electrical Input Protection
The input circuit is protected against voltage-reversed polarity, voltage transients, surges, and spikes according to MIL-STD-1275B.
A.3 Outputs
A.3.1 Electrical Interface
There are 5 output wiring options. These options are defined at the factory per the customer order and cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 61 for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is option 1. The wiring arrangement is identified on the detector by the part number (see Model and Types on page 16).
Option 1: Power, RS-485, 0–20mA (Sink), Fault I Relay (N.C.), Alarm Relay,
(N.O.) (see Figure 7).
Option 2: Power, RS-485, 0–20mA (Source) and HART protocol, Fault Relay
(N.O.), Alarm Relay, (N.O.), (N.C.).
Specifications
TM40/40U Rev. (Af), February 2019 55
Option 3: Power, RS-485, 0–20mA (Source) and HART protocol, Fault Relay
(N.O.), Alarm Relay (N.O., N.C.).
Option 4: Power, RS-485, Fault Relay (N.C.), Auxiliary Relay (N.O.), Alarm
Relay, (N.O.).
Option 5: Power, RS-485, Fault Relay (N.O.), Auxiliary Relay (N.O.), Alarm
Relay, (N.O.).
A.3.2 Electrical Outputs
A.3.2.1 Dry Contact Relays
Table 20: Contact Ratings
Relay Name
Type
Normal Position
Maximum Rating
Alarm
SPDT
N.O., N.C.
2A at 30DVC
Auxiliary
SPST
N.O.
2A at 30VDC
Fault
1 2
SPST
N.C. or N.O.
2A at 30VDC
1
The fault relay (in wiring options 1, 2, and 4) is normally energized closed during normal
operation of the detector. The relay is de-energized open in a fault condition or low voltage situation.
2
In wiring options 3 and 5 the relay is normally energized open during normal operation of the
detector. The relay is de-energized close contact in a fault condition or low voltage situation.
A.3.2.2 0–20mA Current Output
The 0–20mA can be Sink or Source according to the wiring option source (see General Instructions for Electrical Wiring on page 61). The maximum permitted load resistance is 600Ω.
Table 21: 20mA Current Output
State
Output
Fault
0 +1mA
BIT fault
2mA±10%
Normal
4mA±10%
Warning
16mA±5%
Alarm
20mA±5%
Specifications
56 SharpEye™ UV Flame Detectors User Guide
A.3.2.3 HART Protocol
The HART protocol is a digital communication signal at a low level on top of the 0–20mA. This bi-directional field communication protocol is used to communicate between intelligent field instruments and the host system. HART is available in wiring options 2 and 3.
Through the HART protocol the detector can:
Display setup
Reconfigure setup
Display detector status and definition
Perform detector diagnostics
Troubleshoot
For more details refer to HART Manual TM777030.
A.3.2.4 Communication Network
The detector is equipped with an RS-485 communication link that can be used in installations with computerized controllers.
The communications protocol is Modbus compatible.
This protocol is a standard and widely used.
It enables continuous communication between a standard Modbus controller
(Master device) and a serial Network of up to 247 detectors.
A.3.3 Heated Optics
The front window can be heated to improve performance in ice, condensation, and snow conditions. The heater increases the temperature of the optical surface by 5–8°F / 3–5°C above the ambient temperature. The heated optics can be configured in 3 ways:
Off: The optics are not heated
On: The optics are heated continuously
Auto: Operated only when the change of temperature requires the heating
(default)
In Auto mode the start heating temperature can be defined between 32–86°F / 0–30°C. The detector stops heating the window when the temperature is 27°F/15°C above the start temperature.
Specifications
TM40/40U Rev. (Af), February 2019 57
A.4 Approvals
A.4.1 Hazardous Area Approvals
FM, CSA
Class I Div. 1 Groups B, C, and D;
Class II/III Div. 1 Groups E, F, and G
ATEX, IECEx
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96°C Db
(–55°C ≤ Ta ≤ +75°C)
Or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db
(–55°C ≤ Ta ≤ +85°C)
TR CU / EAC
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T96°C Db X
(–55°C Ta +75°C)
Or
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T106°C Db X
(–55°C Ta +85°C)
Or
1 Ex db eb mb op is II T4 Gb X
Ex tb op is IIIC T98°C Db X
(–55°C Ta +75°C)
A.4.2 Functional Approvals
EN54-10 approved per VdS
FM approved per FM3260
A.5 Mechanical Specifications
Specifications
58 SharpEye™ UV Flame Detectors User Guide
A.5.1 Enclosure
Stainless Steel 316
Or
Aluminum, heavy duty copper free (less than 1%), red epoxy enamel finish
A.5.2 Water and Dust Tight
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
A.5.3 Electronic Modules
Conformal coated
A.5.4 Electrical Connection (2 entries)
¾ - 14NPT conduit
Or
M25 x 1.5
A.5.5 Dimensions
4” x 4.6” x 6.18” / 101.6 x 117 x 157 mm
A.5.6 Weight
Stainless Steel: 6.1lb/2.8kg
Aluminum: 2.8lb/1.3kg
A.6 Environmental Specifications
The SharpEye 40/40U and UB is designed to withstand harsh environmental conditions.
A.6.1 High Temperature
Designed to meet MIL-STD-810C, Method 501.1 Procedure II
Operating temperature: +167°F/+75 °C
Storage temperature: +185 °F/+85 °C
A.6.2 Low Temperature
Designed to meet MIL-STD-810C, Method 502.1, Procedure I
Operating temperature: –57°F/–50°C
Storage temperature: –65°F/–55°C
Specifications
TM40/40U Rev. (Af), February 2019 59
A.6.3 Humidity
Designed to meet MIL-STD-810C, Method 507.1, Procedure IV
Relative humidity of up to 95% for the operational temperature range
A.6.4 Salt Fog
Designed to meet MIL-STD-810C, Method 509.1, Procedure I
Exposure to a 5% salt solution fog for 48 hours
A.6.5 Dust
Designed to meet MIL-STD-810C, Method 510.1, Procedure I
Exposure to a dust concentration of 0.3g/ft
2
at a velocity of 1750fpm, for 12
hours
A.6.6 Vibration
Designed to meet MIL-STD-810C, Method 514.2, Procedure VIII
Vibration at an acceleration of 1.1g within the frequency range of 5–30Hz,
and an acceleration of 3g within the frequency range of 30–500Hz
A.6.7 Mechanical Shock
Designed to meet MIL-STD-810C, Method 516.2, Procedure I
Mechanical Shock of 30g half-sine wave, for 11 msec
A.6.8 Electromagnetic Compatibility (EMC)
Table 22: Electromagnetic Compatibility (EMC)
Test Standard
Level Per
Electrostatic Discharge ESD
IEC 61000-4-2
EN 50130-4
Radiated EM Field
IEC 61000-4-3
EN 50130-4
Electrical Fast Transients
IEC 61000-4-4
EN 50130-4
Surge
IEC 61000-4-5
EN 50130-4
Conducted Disturbances
IEC 61000-4-6
EN 50130-4
Power Frequency Magnetic Field
IEC 61000-4-8
EN 50130-4 Radiated Emission
IEC 61000-6-3
EN 55022
Conducted Emission
IEC 61000-6-3
EN 55022
Immunity to Main Supply Voltage Variations
IEC 61000-4-29
EN 50130-4
Specifications
60 SharpEye™ UV Flame Detectors User Guide
Caution:
To fully comply with EMC directive 2014/30/EU and protect against interference caused by RFI and EMI, the cable to the detector must be shielded and the detector must be grounded. The shield should be grounded at the detector end.
Wiring Instructions
TM40/40U Rev. (Af), February 2019 61
Appendix B: Wiring Instructions
B.1 General Instructions for Electrical Wiring
Follow the instructions detailed in this section for determining the correct wire gauge to be used for the installation.
1 Use Table 23 to determine the required wire gauge/size for general wiring,
such as relay wiring. Calculate the permitted voltage drop with respect to load current, wire gauge, and length of wires.
Table 23: Maximum DC Resistance at 68°F/20ºC for Copper Wire
AWG No.
mm2
Ohm per 100ft
Ohm per 100m
20
0.51–0.61
1.07
3.50
18
0.81–0.96
0.67
2.20
16
1.22–1.43
0.43
1.40
14
1.94–2.28
0.27
0.88
2 Use Table 24 to select wire gauge for power supply wires. DO NOT connect
any circuit or load to detectors’ supply inputs.
Select number of detectors connected in 1 circuit.
Select wiring length per your installation requirements.
Refer to power supply range for voltage extreme applied.
Table 24: Wiring Length in Feet/Meters
Number of Detectors
Recommended Wire Diameter (AWG)
Power Supply Range (VDC)
24
18
16
14 - -
22–32
20
18
16
14 - -
22–32
16
20
18
16
14 - 22–32
12
20
18
16
14 - 20–32
8
20
18
16
14 - 20–32
4 and less
20
18
16
16
14
20–32
ft/m
164/50
328/100
492/150
656/200
820/240
Max. Length from Power Supply to Last Detector
B.2 Calculation Formula
Wiring Instructions
62 SharpEye™ UV Flame Detectors User Guide
Use the following formula to calculate minimum wire gauge per wire length between the power supply (controller) and the detector, considering the number of detectors on the same power line, where:
L = Actual wire length between the detector and the power supply
N = Number of detectors per loop
R = Resistance of wire per 100m (see Table 23)
V = Voltage drop on the wire
Calculate the voltage drop on the wire as follows:
V = 2L x R x N x 0.2A
100
20+V = Minimum required voltage of the power supply
0.2A is the maximum power consumption of the detector
For example, if N=1 (1 detector in loop)
L = 1000m
Wire size = 1.5mm² (see Table 24, the resistance per 100m for 1.5mm² is
1.4Ω)
Calculate the voltage drop in the wire as follows:
2 x 1000 x 1.4Ω x 1 x 0.2A = 5.6V
100
The minimum voltage of the power supply should be 20V + 5.6V = 25.6V
Wiring Instructions
TM40/40U Rev. (Af), February 2019 63
B.3 Typical Wiring Configurations
This section describes examples of typical wiring configurations.
Figure 8: Wiring Terminals
Table 25: Wiring Connections
Wiring Option
Detector Model
Terminals
5 8 9
1
40/40U and UB-1XXXX
Fault Relay (N.C.)
0–20mA (Sink)
0–20mA (Sink)
2
40/40U and UB -2XXXX
Fault Relay (N.C.)
Alarm Relay (N.C.)
0–20mA (Source)
3
40/40U and UB -3XXXX
Fault Relay (N.O.)
Alarm Relay (N.C.)
0–20mA (Source)
4
40/40U and UB -4XXXX
Fault Relay (N.C.)
Auxiliary Relay (N.O.)
Auxiliary Relay (N.O.)
5
40/40U and UB -5XXXX
Fault Relay (N.O.)
Auxiliary Relay (N.O.)
Auxiliary Relay (N.O.)
Wiring Instructions
64 SharpEye™ UV Flame Detectors User Guide
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2 Wiring)
Figure 10: 0–20mA Wiring Option 1 (Sink 4-Wire) - Default
Wiring Instructions
TM40/40U Rev. (Af), February 2019 65
Figure 11: 0–20mA Wiring Option 1 (Converted to Source 3-Wire)
Figure 12: 0–20mA Wiring Option 1 (Non-isolated Sink 3-Wire)
Wiring Instructions
66 SharpEye™ UV Flame Detectors User Guide
Figure 13: 0–20mA Wiring Option 2 and 3 (Source 3-Wire available with the HART
Protocol)
Note:
There are no 0–20mA outputs in wiring options 4 and 5.
RS-485 Communication Network
TM40/40U Rev. (Af), February 2019 67
Appendix C: RS-485 Communication Network
C.1 RS-485 Overview
By using the RS-485 network capability of the UV detector and additional software, it is possible to connect up to 32 detectors in an addressable system with 4 wires only (2 for power and 2 for communication). Using repeaters, the number of detectors can be much larger (32 detectors for each repeater) up to 247 on the same 4 wires. When using the RS-485 network, it is possible to read each detector status (FAULT, WARNING, and ALARM) and to initiate a BIT for each detector individually.
For more details, contact SPECTREX.
Figure 14: RS-485 Networking
Accessories
TM40/40U Rev. (Af), February 2019 69
Appendix D: Accessories
This appendix describes the accessories that can help you maximize fire detection with the SharpEye UV/IR Flame Detector.
D.1 Flame Simulator FS-1200
The Flame Simulator FS-1200 is designed specifically for use with SharpEye Flame Detectors. The Flame Simulator includes a halogen lamp that emits UV and IR radiation. This energy is accumulated by a reflector directed towards the detector. This allows the detectors to be tested under simulated fire conditions without the associated risks of an open flame.
Figure 15: Flame Simulator FS-1200
D.1.1 Ordering Information
The P/N of the Flame Simulator Kit is 380114-2. The kit is supplied in a carry case that includes:
Flame Simulator FS-1200
Charger
Tool Kit
Technical Manual TM380102
Accessories
70 SharpEye™ UV Flame Detectors User Guide
D.1.2 Unpacking
Verify that you have received the following contents:
Delivery form
Flame simulator with integral battery
Battery charger
Tool keys
User manual
FAT forms
EU declaration
Storage case
D.1.3 Operating Instructions
Warning:
Do not open the flame simulator to charge the batteries or for any other reason in a hazardous area.
Caution:
The following test simulates a real fire condition and may activate the extinguishing system or other alarms. If activation is not desired, disconnect/inhibit them before the test and reconnect after the simulation.
To simulate a fire:
1 Verify you are at the correct distance from the detector according to the type
of detector and the detector sensitivity.
2 Using the mechanical sight, aim the flame simulator toward the center of the
detector. Push the activate button, and then use the laser spot for fine adjustment
toward the center of the detector.
3 Keep the simulator aimed at the detector for up to 50 seconds, until you
trigger an alarm.
4 Wait 20 seconds before repeating the test.
Accessories
TM40/40U Rev. (Af), February 2019 71
D.1.4 Range
Table 26: Sensitivity Ranges
Detector Types
Detector Sensitivity Setting (ft/m)
Maximum Testing Distance (ft/m)
40/40U - UB
50/15
20/6
Notes:
The minimum distance from the detector is 20”/50cm.
At extreme temperatures, there is a 15% maximum reduction in
the range.
Warning:
Keep the flame simulator in a safe place when not in use.
D.1.5 Charging the Battery
The flame simulator uses lithium-ion batteries as a rechargeable power source. When the batteries are fully charged, the simulator operates at least 1,000 times without having to be recharged. The simulator will not operate when the voltage from the batteries is lower than the required operational level.
1
Simulator
3
Locking Disc
2
Battery Pack
4
Back Cover
Figure 16: Flame Simulator Battery Replacement
Accessories
72 SharpEye™ UV Flame Detectors User Guide
To charge the battery:
Caution:
Place the flame simulator on a table in a safe area, not exceeding 104°F/40°C.
1 Release the locking screw. 2 Unscrew the battery back cover (Item 4) counterclockwise. 3 Unscrew the locking disc (Item 3) clockwise. 4 Pull out the battery from the flame simulator. 5 Connect the battery to the charger. 6 Charge for a maximum of 2–3 hours. 7 Disconnect the charger. 8 Insert the battery into the Flame Simulator. 9 Screw on the locking disc (Item 3). 10 Screw on the back cover (Item 4). 11 Lock the back cover with the locking screw.
D.1.6 Battery Replacement
To replace the battery:
Note:
The item numbers shown in this procedure can all be found in Figure 16.
1 Place the flame simulator on a table in a safe area, not exceeding
104°F/40°C.
2 Release the locking screw. 3 Unscrew the battery back cover (Item 4) counterclockwise. 4 Unscrew the locking disc (Item 3) clockwise. 5 Pull out the battery from the flame simulator. 6 Insert the new battery pack in the simulator housing. Use only SPECTREX
battery pack, P/N 380004.
7 Screw on the locking disc (Item 3). 8 Screw on the back cover (Item 4). 9 Lock the back cover with the locking screw.
Accessories
TM40/40U Rev. (Af), February 2019 73
Note:
For more information refer to TM380102.
D.2 Technical Specifications
D.2.1 General
Temperature Range: –4°F to +122ºF / –20ºC to +50ºC
Vibration Protection: 1g (10–50Hz)
D.2.2 Electrical
Power: 14.8V (4 X 3.7V rechargeable lithium-ion battery)
Max. Current: 4A
Battery Capacity: 2.2AH
Charging Time: 2A at 2hr
D.2.3 Physical
Dimensions: 230 x 185 x 136 mm
Weight: 5.5lb/2.5kg
Enclosure: aluminum, heavy duty copper free, black zinc coating
Explosion proof enclosure:
ATEX & IECEx
Ex II 2 G D
Ex d ib op is IIB +H2 T5 Gb
–20°C to +50°C / –4°F to +122°F
Accessories
74 SharpEye™ UV Flame Detectors User Guide
D.2.4 EMI Compatibility
Table 27: Immunity Tests
Immunity Tests
Title
Basic Standard
Level to be tested
Electrostatic Discharge (ESD)
IEC 61000-4-2
6kV/8kV contact/air
Radiated Electromagnetic Field
IEC 61000-4-3
20V/m (80MHz–1GHz) 10V/m (1.4–2GHz) 3V/m (2.0–2.7GHz)
Conducted Disturbances
IEC 61000-4-6
10Vrms (150kHz–80MHz)
Immunity to Main Supply Voltage Variations
MIL-STD-1275B
Table 28: Emission Tests
Emission Tests
Title
Basic Standard
Level to be Tested
Class
Radiated Emission
IEC 61000-6-3,
40dbuv/m (30–230MHz), 47dbuv/m (230MHz–1GHz)
Like Class B of EN 55022
Accessories
TM40/40U Rev. (Af), February 2019 75
D.3 Tilt Mount
The tilt mount (P/N 40/40-001) provides accurate directional selection for optimum area coverage.
Figure 17: Tilt Mount
Accessories
76 SharpEye™ UV Flame Detectors User Guide
D.4 Duct Mount
The duct mount (P/N 777670) is suitable for use with the SharpEye 40/40 Series Optical Flame Detector 40/40U-UB, for both the aluminum and st.st. enclosure.
The duct mount allows flame detection in areas where high temperatures exist or where the detector cannot be installed inside the area. It comprises a special duct mount arrangement with a specific optical window to allow installation in high temperature duct applications.
The duct mount limits the cone of vision of the installed detector to 65° horizontal and 65° vertical.
The temperature allowed for the duct mount to be installed is: –55°C to +200°C / –67°F to +392°F.
For more instructions refer to TM777670.
Figure 18: Duct Mount
Accessories
TM40/40U Rev. (Af), February 2019 77
D.5 Weather Cover
The weather cover (P/N 777163) protects the detector from different weather conditions, such as snow and rain.
Figure 19: Weather Cover
Accessories
78 SharpEye™ UV Flame Detectors User Guide
D.6 Air Shield
The air shield (P/N 777650) is suitable for use with the SharpEye 40/40 Series Optical Flame Detector 40/40U-UB, for both the aluminum and st.st. enclosures.
Optical flame detectors are often used in highly polluted or dirty areas that force maintenance personnel to access the detector frequently in order to clean its optical window. The special air shield, developed for SharpEye 40/40 series optical flame detectors, allows their installation under environmental conditions where they may be exposed to oil vapors, sand, dust, and other particulate matter.
The temperature of the air supply to the air shield should not exceed 60°C/140°F at any time.
Air pressure source: Clean, dry, and oil-free air
Pressure: 2–3 bar / 30–45 psi
Fitting: 7/16 – 20UNF-2A
Operation Temperature: –55°C to +85°C / –67°F to +185°F
For more instructions, refer to TM777650.
Figure 20: Air Shield
SIL-2 Features
TM40/40U Rev. (Af), February 2019 79
Appendix E: SIL-2 Features
E.1 40/40UB Flame Detector
This appendix details the special conditions for compliance with the requirements of EN 61508 for SIL 2.
The 40/40UB Flame Detector can only be used in low demand mode applications. See IEC 61508.4, Chapter 3.5.12.
E.1.1 Safety Relevant Parameters
Perform the following functional checks of the detector every 30 days:
HFT: 0
PFD: 2.5 x 10
–5
(≈ 0.2% of SIL-2) if only alarm relay is used for alerting.
PFD: 2.8 x 10
–5
(≈ 0.3% of SIL-2) if 4–20mA interface is used as alarm.
SFF: 97% fulfills the conditions of EN 61508 for SIL2
E.1.2 Guidelines for Configuring, Installing, Operating, and Service
The alert conditions according to SIL 2 can be implemented by an:
Alert signal via 20mA current loop
Or
Alert signal via alarm relay and the fault relay
E.1.2.1 Conditions for Safe Operating
The flame detector must consist only of the approved hardware and software
modules.
The 24V power supply must fulfill the requirements for PELV/SELV of EN
60950.
The automatic BIT (Built-In-Test) must be activated.
The setup parameters must be verified (as described in Using the 0–20mA
Interface for Alerting on page 79, and in Using the Alarm Relay Contact for Alerting on page 80.
The function of the 40/40 Flame Detector (flame detection, function of the 0–
20mA interface, and relay functions) must be checked completely.
SIL-2 Features
80 SharpEye™ UV Flame Detectors User Guide
E.1.2.2 Using the 0–20mA Interface for Alerting
The following parameters should be set:
Automatic BIT test = on
Connected to 0–20mA Terminals
The following allowed output current must be supervised with an accuracy of
± 5%:
Normal State = 4mA
Warning State = 16mA
Alarm State = 20mA
The receiving device must be programmed to indicate a fault condition when
current levels reach overcurrent or undercurrent.
E.1.2.3 Using the Alarm Relay Contact for Alerting
The following parameters should be set:
Automatic BIT Test = on
Connected to N.C. contact of alarm relay terminals
Connected to fault relay terminals
The relay contacts (“alarm” and “faulty relay”) must be protected with a fuse
rated at 0.6 of the nominal specified relay contact current.
The maximum contact rating that is allowed per SIL-2 is 30VDC.
The contact of the alarm relay opens if there is a fire alarm.
During the forwarding and evaluation of the alarm, the relay contact opens.
The alarm relay can be used as low demand only.
E.1.2.4 Other
The complete function of the flame detector (flame detection, function of the
0–20mA interface, and the relays must be examined at least every 6 or 12 months (see Safety Relevant Parameters on page 79), or whenever the flame detector must be switched off and on.
The window of the sensor must be examined at appropriate time intervals for
partial contamination.
Caution:
The HART and the RS-485 interfaces must not be used for the transmission of safety-related data.
End of Line Resistor
TM40/40U Rev. (Af), February 2019 81
Appendix F: End of Line Resistor
The 40/40 series can be equipped with an EOL resistor inside the flameproof 'd' terminal compartment.
The EOL resistor can be situated in the rear part which is Ex e or Ex d , depending on the application. When the resistor is assembled, the rear part can be used as Ex d only.
To meet the allowed power consumption, the total resistance should be higher than 1.5KΩ.
Figure 21: End of Line Resistor Assembly
Technical Support
For technical assistance or support, contact:
8200 Market Blvd Chanhassen, MN 55317 USA
Phone: +1 (973) 239 8398 Email: spectrex@spectrex.net Website: spectrex.csc.rmtna@emerson.com
Loading...