Warning: This manual should be read carefully by all individuals
who have or will have responsibility for using, maintaining or
servicing the product.
The Detector is not field-repairable due to the meticulous
alignment and calibration of the sensors and the respective
circuits. Do not attempt to modify or repair the internal circuits
or change their settings, as this will impair the system's
performance and void the Spectrex, Inc. Product warranty.
The SharpEye Optical Flame Detector described in this document is the property of Spectrex,
Inc.
No part of the hardware, software or documentation may be reproduced, transmitted,
transcribed, stored in a retrieval system or translated into any language or computer language,
in any form or by any means, without prior written permission of Spectrex, Inc.
While great efforts have been made to assure the accuracy and clarity of this document,
Spectrex, Inc. assumes no liability resulting from any omissions in this document, or from
misuse of the information obtained herein. The information in this document has been carefully
checked and is believed to be entirely reliable with all of the necessary information included.
Spectrex Inc. reserves the right to make changes to any products described herein to improve
reliability, function, or design, and reserves the right to revise this document and make
changes from time to time in content hereof with no obligation to notify any persons of
revisions or changes. Spectrex, Inc. does not assume any liability arising out of the application
or any use of any product or circuit described herein; neither does it convey license under its
patent rights or the rights of others
Warranty
SPECTREX INC. Agrees to extend to Purchaser/Distributor a warranty on the SPECTREX
supplied components of the SharpEye products. SPECTREX warrants to Purchaser/Distributor
that the products are free from defects in materials and workmanship for a period of five (5)
years, commencing with the date of delivery to Purchaser/Distributor. SPECTREX expressly
excludes damage incurred in transit from the factory or other damage due to abuse, misuse,
improper installation, or lack of maintenance or “Act of God” which are above and beyond its
control. SPECTREX will, upon receipt of any defective product, transportation prepaid, repair or
replace it at its sole discretion if found to have been defective when shipped. Said repair or
replacement is SPECTREX’S sole liability under this warranty and SPECTREX’S liability shall be
limited to repair or replacement of the component found defective and shall not include any
liability for consequential or other damages. The customer is responsible for all freight charges
and taxes due on shipments both ways. This warranty is exclusive of all other warranties
express or implied.
Legal Notice iii
SharpEyeTM IR3 Flame Detector User Guide
Rev
Date
Revision History
Prepared by
Approved by
0
May 20, 2008
First Release
Ian Buchanan
Eric Zinn
1
Sept 22, 2008
Second Release
Ian Buchanan
Eric Zinn
2
July, 2010
Third Release
Ian Buchanan
Eric Zinn
3
August 2010
Fourth Release
Ian Buchanan
Eric Zinn
4
November 2010
Fifth Release
Ian Buchanan
Eric Zinn
5
February 2013
Sixth Release
Ian Buchanan
Eric Zinn
6
July 2013
Seventh Release
Ian Buchanan
Eric Zinn
Release History
iv
About this Guide
This guide describes the SharpEye Model 40/40I Triple IR (IR3) Flame
Detector and its features and provides instructions on how to install, operate
and maintain the detector.
This guide includes the following chapters and appendixes:
Chapter 1, Introduction, provides a general overview of the product,
principles of operation, and performance considerations.
Chapter 2, Installing the Detector, describes how to install the
detector including preparations before installation, wiring and mode
settings.
Chapter 3, Operating the Detector, describes how to power-up and
test the detector. The chapter also lists safety precautions you should
take when operating the detector.
Chapter 4, Maintenance and troubleshooting, describes basic
maintenance procedures, and troubleshooting and support procedures.
Appendix A, TechnicalSpecifications: Lists the detectors technical
and other specifications.
Appendix B, Wiring Instructions, lists the wiring instructions for
connecting the detector and also provides examples of typical wiring
configurations.
Appendix C, RS-485 Communication Network, provides an overview
of the RS-485 communications network.
Appendix D, Accessories, describes the accessories available for the
detector.
Appendix E, SIL-2 Features, describes the special conditions to
comply with the requirements of EN 61508 for SIL 2 according to TUV.
The SharpEye 40/40I is a flame detector that utilizes improved IR3
technology to provide state-of-the-art fire protection. The 40/40I uses
patented digital signal processing to analyze the spectral and dynamic
characteristics of the measured infrared radiation, to identify fire events
with exceptional sensitivity and extreme immunity to false alarms.
All 40/40 series detectors include a heated optical window for improved
performance in icing, snow and condensation conditions.
Detection performance can be easily adapted to all environments,
applications and requirements, by changing the detector’s configuration
parameters. Adjusting these parameters, as well and performing other
maintenance and monitoring tasks, is possible by means of RS485-based
Modbus communication or HART communication (in models with 0-20mA
output).
The detector enclosure is ATEX certified Exd flameproof with an integral,
segregated, rear, Exe terminal compartment (avoiding exposure of the
sensors and electronics to surrounding environment). Hence the combined
approval:
Ex II 2 G D
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
or
Ex de IIC T4 Ta -55°C to +85°C
Ex tD A21 IP66/X7 T105°C
The SharpEye 40/40 detectors are designed to operate as a stand-alone unit
directly connected to an alarm system or an automatic fire extinguishing
system. The detector can also be a part of a more complex system, where
many detectors and other devices are integrated through a common control
unit.
Overview 1
SharpEyeTM IR3 Flame Detector User Guide
*
40/40I XXXXX
Ex Approval
Wiring
Configuration
Temperature
Electrical
Entries
Housing
F – FM / CSA
C - ATEX / IECEx
1 - 75°C
2 - 85°C
1 - M25
2 - ¾" NPT
See Table 1
S - Stainless Steel
A - Aluminum
1.2 Model and Types
The 40/40I is provided in various configurations depending on:
Wiring options
Temperature ranges
Type of cable entries
Housing type
Required approval
The configuration detail is included in the product part number on the
product label and takes the form: 40/40I XXXXX, where XXXXX defines the
model according to the above requirements.
To modify the default or pre-ordered configuration and perform
maintenance tasks, please refer to the HART Protocol TM777030, the
RS-485 Manual TM 777050 or TM777070.
The Part Numbers are defined as:
Note: *Aluminum housing is available in ATEX/IECEx version only.
Table 1 describes the wiring options in detail.
2 Model and Types
TM 40/40I, Rev (6) July 2013
Wiring
Option
Connections Provided
1
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.
0-20mA
Sink
RS-485
-
2
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.,
N.C.
0-20mA
Source
RS-485
HART
3
Power
Manual
BIT
Fault
Relay
N.O.
Alarm
Relay
N.O.,
N.C.
0-20mA
Source
RS-485
HART
4
Power
Manual
BIT
Fault
Relay
N.C.
Alarm
Relay
N.O.
Auxiliary
N.O.
RS-485
-
5
Power
Manual
BIT
Fault
Relay
N.O.
Alarm
Relay
N.O.
Auxiliary
N.O.
RS-485
-
Table 1: Wiring Options
Note: Wiring option 1 is default. The mA 'Sink' output can be altered to
'Source' type, with a link between terminals 1 and 8. No other wiring options
can be changed on site.
For example, product number 40/40I-321SC has the following options:
Wiring Option: 3 (Power, Manual BIT, RS-485, 0-20mA (Source) with
the HART protocol, Fault Relay (N.O.), Alarm Relay (N.O., N.C.))
Temperature Range: 2 (85°C)
Cable Entry: 1 (M25)
Housing : S (Stainless Steel)
Approval: C (ATEX, IECEx)
Note: Check your specific part numbers against the information in Checking
the Product Type on page 20.
Model and Types 3
SharpEyeTM IR3 Flame Detector User Guide
1.3 Features and Benefits
Detection Range: Up to 215 ft. (65m) for a 1 ft2 (0.1m2) n-heptane fire.
Ultra High Immunity to False Alarms: See Table 4 on page 11.
Advanced Digital Processing of the Dynamic Characteristics of Fire:
Flickering, threshold correlation and ratio.
Multi IR Channels: Between 2-5 microns.
Field Programmable Sensitivity: Four ranges to avoid zone crossover.
Built In Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on
The SharpEye 40/40I detector is designed to detect flames in which carbon
dioxide (CO2) is produced in the combustion process. These include all
hydrocarbon flames, as well as other types of flames and burning materials
such as wood or alcohol.
4 Features and Benefits
TM 40/40I, Rev (6) July 2013
The detector’s principle of operation is based on patented IR3 technology.
This technology identifies the unique spectral signature that hot CO2 has in
the infrared (IR), namely a peak of the intensity at wavelengths 4.2 to 4.7µ.
The original IR3 technique (such as implemented in the SharpEye 20/20I
flame detector) utilizes three infrared sensors, each sensitive to its own
wavelength range. The first sensor is sensitive to wavelengths within the
emission peak of hot CO2. The other two sensors are sensitive to
wavelengths above and below this peak. In the event of fire, the signal
measured in the first sensor is significantly higher than those measured in
the other two sensors. In order to issue a fire alarm, the detector requires
that this occurs, as well as other conditions (for example, radiation is
flickering in frequencies typical of flames). If exposed to non-fire radiation
sources, the specific conditions required does not occur, and the detector
does not react.
The SharpEye 40/40I further includes an additional IR sensor, sensitive to a
different band within the emission peak of hot CO2. The signal of this sensor
is compared to those of the other three. This increases sensitivity for some
types of flames. (For example, gas flames).
1.4.2 Heated Optics
The SharpEye 40/40 Flame Detectors use heated optics. The heater
increases the temperature of the optical surface by 5-8°F (~3-5°C) above
the ambient temperature to improve performance in icing, condensation and
snow conditions.
The heated optics can be set to one of the following:
Not operated
On continuously
Automatic, per temperature change (default): you can define the start
temperature below which the window is heated. (The default is 41°F
(5°C).) This temperature can be defined between 32°F (0°C) to 122°F
(50°C). The heating stops when the temperature is 27°F (15°C) above
the start temperature.
For more information, see Configuring your Detector on page 29.
1.4.3 HART Protocol
The 40/40 Flame Detectors use the HART protocol.
HART Communication is a bi-directional industrial field communication
protocol used to communicate between intelligent field instruments and host
systems. HART is the global standard for smart process instrumentation and
the majority of smart field devices installed in plants worldwide are HARTenabled. HART is available in wiring options 2 and 3, see Table 1, page 3.
HART technology is easy to use and very reliable.
Principles of Operation 5
SharpEyeTM IR3 Flame Detector User Guide
Through the HART connection, you are able to perform:
Detector set-up
Detector troubleshooting
Detector health and status
For more details, refer to the HART Manual TM 777030.
1.4.4 RS-485 Modbus
For more advanced communications, the 40/40I detector has an RS 485
Modbus-compatible output that provides data communication from a
network (up to 247 detectors) to a host computer or universal controller for
central monitoring. This feature allows for reduced installation costs, easy
maintenance and local or remote diagnostic tools.
1.4.5 Product Certification
The 40/40I Flame Detectors have the following certifications:
ATEX Ex II 2 GD per SIRA 07ATEX1250 and IECEx SIR. 07.0085
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
Ex de IIC T4 Ta -55°C to +85°C
Ex tD A21 IP66/X7 T105°C
This product is suitable to use in hazardous zones 1 and 2 with IIC gas
group vapors present.
1.4.5.2 FM, CSA
The 40/40I Flame Detector is certified to FM and CSA Explosion Proof and
Functionality per FM3260:
Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
Fuel Test Response including: Gasoline, N-Heptane, Diesel, JP5,
Detection sensitivity is the maximum distance at which the detector reliably
detects a specific size of fire and typical type of fuel (standard fire).
1.5.1.1 Standard Fire
Defined as a 1ft2 / 0.1m2 n-heptane pan fire, with maximum wind speed of
6.5 ft./sec (2 m/sec).
Performance Considerations 7
SharpEyeTM IR3 Flame Detector User Guide
Level
Response Time (sec)
Sensitivity Range- ft. (m)
1
3
50 (15)
2 Default 5 100 (30)
3
8
150 (45)
4
10
215 (65)
1.5.1.2 Sensitivity Ranges
The detector has four user-selectable sensitivity ranges. For each range
there are two response levels.
WARNING (Pre-alarm)
ALARM
The detection distance, for the WARNING level, is approximately 10% higher
than the ALARM distance.
Alarm response times for a standard fire at a specified range are shown
Table 2.
Table 2: Sensitivity Range Levels
For some typical ambient conditions the Zeta parameter as defined in NFPA
72 for the detector is 0.005 (1/meter).
Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, and so on.
8 Performance Considerations
TM 40/40I, Rev (6) July 2013
Type Of Fuel
Percent of Max. Distance
at each Sensitivity Range
Max. Distance
(ft./m)
Gasoline
100%
215 / 65
N-Heptane
100%
215 / 65
JP5
70%
150 / 45
Kerosene
70%
150 / 45
Diesel Fuel
70%
150 / 45
Ethanol 95%
60%
135 / 40
IPA
60%
135 / 40
Methanol
55%
115 / 35
Methane
45%
100 / 30
LPG
45%
100 / 30
Paper
35%
33 / 10
Polypropylene
15%
16 / 5
1.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft2 (0.1m2) and is defined as
100% sensitivity.
For fuel fire – standard pan fire size: 1 ft2 (0.1 m2).
For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Performance Considerations 9
SharpEyeTM IR3 Flame Detector User Guide
1.5.2 Cone of Vision
Horizontal: 100°
Figure 1: Horizontal Field of View
Vertical: +50° (down) , -45° (up)
Figure 2: Vertical Field of View
10 Performance Considerations
TM 40/40I, Rev (6) July 2013
Radiation Source
Immunity
Distance ft. (m)
Indirect or reflected sunlight
IAD
Vehicle headlights (low beam) conforming to
MS53023-1
IAD
Incandescent frosted glass light, 300 W
IAD
Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)
IAD
Electric arc [12mm (15/32") gap at 4000 V alternating
current, 60 Hz]
IAD
Arc welding [6 mm (5/16") rod; 210 A]
See Table 5
Ambient light extremes (darkness to bright light with
snow, water, rain, desert glare and fog)
IAD
Bright colored clothing, including red and safety
orange
Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55
or equivalent)
>6.5 (2)
Blue-green dome light conforming to M251073-1
IAD
Flashlight (MX 991/U)
IAD
Radiation heater, 3000 W
>3 (1)
Radiation heater, 1000 W with fan
IAD
Quartz lamp (1000 W)
>3 (1)
Mercury vapor lamp
IAD
Grinding metal
IAD
Lit cigar
>1 (0.3)
Lit cigarette
>1 (0.3)
Match, wood, stick including flare up
>13 (4)
1.5.3 False Alarms Prevention
To prevent false alarms, the detector will not alarm or react to the radiation
sources specified in Table 4.
Table 4: Immunity to False Alarm Sources
Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20 Hz.
Performance Considerations 11
SharpEyeTM IR3 Flame Detector User Guide
Sensitivity Setting
Detection Range
Immunity Distance
1
50 ft. (15m)
>6 ft. (2m)
2
100 ft. (30m)
>12 ft. (4m)
3
150 ft. (45m)
>17 ft. (6m)
4
215 ft. (65m)
>25 ft. (7.5m)
Detector Status
LED color
LED mode
Fault, BIT Fault
Yellow
4 Hz - flashing
Normal
Green
1 Hz - flashing
Warning
Red
2 Hz - flashing
Alarm
Red
Steady
Indicator LED
Table 5: Welding Immunity Distance
1.5.4 Visual Indicators
One 3-color LED indicator is located inside the detector window, as shown in
Figure 3. The detector statuses are listed in Table 6.
Table 6: LED Indications
12 Performance Considerations
Figure 3: Indication LED
TM 40/40I, Rev (6) July 2013
Output Type
Version
Detector Status
Alarm relay
40/40I – Options 1XXXX,
4XXXX, 5XXXX
The relay is N.O.
40/40I – Options 2XXXX,
3XXXX
The relay is N.O. and N.C.
Auxiliary relay
40/40I – Options 4XXXX
and 5XXXX
The relay is N.O.
Fault relay
40/40I – Options 1XXXX,
2XXXX, 4XXXX
The relay is N.C. energized
40/40I – Options 3XXXX,
5XXXX
The relay is N.O. energized
0-20mA
current output
40/40I – Option 1XXXX
SINK Option, (can be
changed to Source – see
Figure 10, Figure 11 and
Figure 12)
40/40I – Options 2XXXX
and 3XXXX
SOURCE Option with the
HART protocol
RS-485
All versions
Modbus protocol
1.5.5 Output Signals
Outputs are available according to the default configuration or the wiring
options selected for the 40/40I detector. Determine the outputs for your
model according to Table 7.
The detector incorporates several types of output suitable to different
control systems:
Fire detected - changed to Warning (pre-alarm state).
Alarm
Fire detected - changed to Fire Alarm state.
Latched Alarm
(Optional)
The alarm outputs remain latched on following detection
of a fire that has already been extinguished.
BIT Fault
A fault is detected during BIT sequence or other electric
failure. The detector will continue to detect for fire.
Fault
A fault is detected when the power supply is too low or
due to a software fault or electrical failure. The detector
will NOT detect fire in this condition.
Detector
State
LED
Indicator
LED
Mode
Alarm
Relay
Auxiliary
Relay
Fault
Relay
mA
output
Normal
Green
1Hz
Off
Off
On
4 mA
Warning
Red
2Hz
Off
On
(4)
On
16 mA
Alarm
(1)
Red
Constant
On
On
On
20 mA
Latch
(2)
Red
Constant
On
Off
On
20 mA
On
(4)
On
20 mA
BIT Fault
(3)
Yellow
4Hz
Off
Off
Off
2 mA
Warning at
BIT Fault
Red
2Hz
Off
On
(4)
Off
16 mA
Alarm at
BIT Fault
Red
Constant
On
On
Off
20 mA
Fault
Yellow
4Hz
Off
Off
Off
0 mA
1.5.6 Detector Status
The possible detector function statuses are listed in Table 8. A more detailed
fault analysis can be seen via HART or RS485.
Table 8: Detector Status
In each state, the detector activates different outputs, as specified in
Table 9.
Table 9: Output Signals versus Detector State
Notes:
1 The alarm outputs are activated while alarm conditions exist and will
stop approximately 5 seconds after the fire is no longer detected.
2 The Alarm state can be optionally latched via programmed function.
(Default is non-latching).
3 The detector will remain in BIT Fault state until it has passed a
successful BIT.
14 Performance Considerations
TM 40/40I, Rev (6) July 2013
4 The Auxiliary Relay can be activated at the Warning level or Alarm level,
depending on programmed function.
5The outputs depend on the wiring options.
1.5.6.1 Optional Latching
Alarms are set as non-latching by default. However, the detector includes a
latched alarm output capability, which operates according to the
programmed function.
If selected, upon detection of a fire, the detection signal is latched until a
manual reset is performed (disconnecting the power supply or performing a
manual BIT (see Manual BIT on page 18).
Latching affects the Alarm Relay, 0-20mA output, the Alarm LED (the
Auxiliary Relay will be latched only when the programmable function
Auxiliary Relay is set to YES.
Notes:
The Auxiliary Relay is available only in Models with suffix – 4XXXX and
5XXXX
The 0-20mA is available only in Models with suffix – 1XXXX, 2XXXX,
3XXXX
1.5.7 Auxiliary Relay as End-of-Line Resistor
The Auxiliary Relay can be used as End-of-Line (EOL) resistance in Models
with suffix-4XXXX, and 5XXXX only. In this case, the Auxiliary Relay is
active as long as the detector is not in Fault state.
During normal operation, the detector tests itself continuously and indicates
a fault if a failure is found. This type of test complies with SIL-2
requirements.
The detector continuously tests:
Input voltage level
All internal regulator voltage level
Voltage level status of sensor and sensor circuitry for noise or
disconnection in the electronic circuitry
0-20mA level output
Relays and heater operation
Internal Detector Tests 15
SharpEyeTM IR3 Flame Detector User Guide
Processor Watch dog
Software
Memory
Oscillator frequency
Response to Fault Indication
If a failure is found, the detector indicates by:
Fault relay:
Opens in wiring option 1, 2, and 4
Closes in wiring option 3 and 5
0-20mA: indicates Fault (0mA or 2mA) in wiring option 1, 2, 3
LED – Yellow flashes (4 Hz)
Correcting the Fault
The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.
1.6.2 Built-In-Test (BIT)
The detector’s Built-In-Test (BIT) also checks the following:
The detector can be set to perform the BIT in the following modes:
Automatically and manually
Manually only
Note: In Manual BIT, the outputs may also be tested and Control System
‘inhibit’ should be applied if this could initiate other systems.
1.6.2.1 How the BIT Operates
The detector's status remains unchanged if the result of a BIT is the
same as the current status (NORMAL or BIT Fault)
the detectors’ status is changed (from Normal to BIT Fault or vice versa)
if the BIT differs from the current status
Note:In ‘BIT Fault’ status the detector can continue to detect a fire.
16 Internal Detector Tests
TM 40/40I, Rev (6) July 2013
Output
Result
Fault relay
Model 1XXX, 2XXX, 4XXX Wiring options 1, 2, 4:
remains CLOSED
Model 3XXX, 5XXX Wiring options 3 and 5: remains
OPEN
0-20mA
output
Wiring option 1, 2, 3: Normal (4 mA)
Power LED
Green, Flashing, 1 Hz On (Normal)
Output
Result
Fault relay
Wiring option 1, 2, 4: changes to Open
Wiring option 3 and 5: changes to Closed
0-20mA output
Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED
Yellow, Flashing, 4 Hz
BIT procedure
Performed every 1 minute
1.6.2.2 Automatic BIT
The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.
All outputs of BIT results will function as described in Table 10 and Table 11,
and the BIT will be automatically executed every 1 minute.
This continues until a successful BIT occurs, when the detector resumes
normal operation.
Table 10: Results of a Successful BIT
Table 11: Results of an Unsuccessful BIT
Internal Detector Tests 17
SharpEyeTM IR3 Flame Detector User Guide
Output
Result
FAULT relay
Wiring options 1, 2, and 4: remains CLOSED (Normal)
Wiring options 3 and 5: remains OPEN (Normal)
ALARM relay
Activated for 3 sec (only when the function Alarm BIT is
set to YES)
AUXILIARY
relay
For wiring options 4 and 5: is activated for 3 sec (only
when the function Auxiliary BIT is set to YES)
0-20mA
output
Wiring option 1, 2, 3:
Initiates 20 mA only when the function Alarm BIT is set
to YES
Initiates 16 mA when the function Auxiliary BIT is set
to YES and the function Alarm BIT is set to NO
POWER LED
Green, Flashing, 1 Hz
Output
Result
FAULT relay
Wiring option 1, 2, 4: changes to OPEN
Wiring option 3 and 5:changes to CLOSED
0-20mA
output
Wiring option 1, 2, 3: Indicates BIT FAULT (2mA)
POWER LED
Yellow, Flashing, 4 Hz
1.6.2.3 Manual BIT
The BIT is manually initiated by momentarily connecting Terminal 3 with
Terminal 2 (or a switch across these terminals in the safe area).
The results of a successful and unsuccessful Manual BIT are listed in
Table 12 and Table 13.
Table 12: Results of a Successful Manual BIT
Table 13: Results of an Unsuccessful Manual BIT
1.6.2.4 Manual BIT only selected
The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 or a switch across these terminals in the safe area.
18 Internal Detector Tests
2 Installing the Detector
General Guidelines
page 19
Unpacking the Product
page 20
Required Tools
page 21
Certification Instructions
page 22
Installation Cables
page 23
Installing the Tilt Mount (part no. 40/40-001)
page 24
Connecting the Detector
page 26
Configuring your Detector
page 29
➣ In this chapter…
This chapter provides basic guidelines for installing the detector. It does not
attempt to cover all of the standard practices and codes of installation.
Rather, it emphasizes specific points of consideration and provides some
general rules for qualified personnel. Wherever applicable, special safety
precautions are stressed.
2.1 General Guidelines
To ensure optimal performance and an efficient installation, consider the
following guidelines:
Sensitivity: To determine the level of sensitivity, consider the following:
Size of fire at the required distance to be detected
Type of flammable materials
Wiring:
The wire gauge must be designed according to the distance from the
detector to the controller and the number of detectors on the same
power line. See Wiring Instructions on page 49.
To fully comply with EMC directive and protect against interference
caused by RFI and EMI, the cable to the detector must be shielded
and the detector must be grounded. The shield should be grounded
at the detector end.
Spacing and Location: The number of detectors and their locations in
the protected area are determined by:
Size of the protected area
Sensitivity of the detectors
Obstructed lines of sight
Cone of view of the detectors
General Guidelines 19
SharpEyeTM IR3 Flame Detector User Guide
Environment:
Dust, snow or rain can reduce the detectors sensitivity and require
more maintenance activities.
The presence of high intensity flickering IR sources may affect
sensitivity.
Aiming the Detector:
The detector should be aimed toward the center of the detection
zone and have a completely unobstructed view of the protected area.
Whenever possible, the detector face should be tilted down at a 45º
angle to maximize coverage and prevent accumulation of dust and
dirt.
Do not start an installation unless all conceivable considerations
regarding detection location have been taken into account.
Installation should comply with NFPA 72E or any other local and International regulations and standards, as applicable to flame
detectors and installation of Ex approved products.
2.2 Unpacking the Product
Upon receipt of your detector, check and record the following:
1 Verify the appropriate Purchase Order.
Record the Part Number (P/N) and Serial Number of the detectors, and
the installation date in an appropriate Log-book.
2 Open the package before installation and visually inspect the detector.
3 Verify that all components required for the detector installation are
readily available before beginning the installation. If the installation is
not completed in a single session, secure and seal the detectors and
conduits / cable entries.
2.2.1 Checking the Product Type
Check that your product has the configuration / options that you ordered.
Check the detailed part number on the label and compare this information
with the descriptions contained in Model and Types on page 2.
20 Unpacking the Product
TM 40/40I, Rev (6) July 2013
Tool
Function
Hex Key 3/16 inch
Mount the detector on the tilt mount.
Open and close detector cover (for wiring)
Flat Screw Driver 4 mm
Connect ground terminal
Flat Screw Driver 2.5 mm
Connect wires to the terminal blocks
2.3 Required Tools
The detector can be installed using general-purpose common tools and
equipment. Table 14 lists the specific tools required to install the detector.
Table 14: Tools
For wiring, use color-coded conductors or suitable wire markings or labels.
12 to 20 AWG (0.5 mm² to 3.5 mm²) wires may be used for site wiring. The
selection of wire gauge should be based on the number of detectors used on
the same line and the distance from the control unit, in compliance with
specifications (see General Instructions for Electrical Wiring on page 49).
Required Tools 21
SharpEyeTM IR3 Flame Detector User Guide
Warning: Do not open the detector, even when isolated, when
flammable atmosphere present.
2.4 Certification Instructions
Use the following certification instructions:
The cable entry point may exceed 167°F (75°C). Suitable precautions
should be taken when selecting the cable.
The equipment may be used with flammable gases and vapors with
apparatus groups IIA, IIB and IIC:
T5 in the ambient temperature range: –67°F (–55°C) to +167°F
(+75°C).
T4 in the ambient temperature range: –67°F (–55°C) to +185°F
(+85°C).
Installation shall be carried out by suitably trained personnel in
accordance with the applicable code of practice such as. EN 60079-
14:1997.
Inspection and maintenance of this equipment shall be carried out by
suitably trained personnel in accordance with the applicable code of
practice such as EN 60079-17.
Repair of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice such as EN
60079-19.
The certification of this equipment relies upon the following materials
used in its construction:
Enclosure: 316L Stainless Steel or Aluminum
Window: Sapphire Glass
If the equipment is likely to come into contact with aggressive
substances, then it is the responsibility of the user to take suitable
precautions that prevent it from being adversely affected, thus ensuring
that the type of protection provided by the equipment is not
compromised:
Aggressive substances: acidic liquids or gases that may attack
metals, or solvents that may affect polymeric materials.
Suitable precautions: regular checks as part of routine inspections or
establishing from the material’s data sheets that it is resistant to
specific chemicals.
22 Certification Instructions
TM 40/40I, Rev (6) July 2013
2.5 Installation Cables
Follow the following guideline for the cable installation:
All cables to the detector must be well shielded in order to comply with
EMC requirement (see Technical Specifications on page 60).
Ground the detector to the nearest ground point (not more than 3m
from the detector location).
Install the detector with the cable entries placed downwards.
2.5.1 Conduit Installation
The conduit used for the cabling must comply with the following:
To avoid water condensation water in the detector, install the detector
with the conduits placed downward, that include drain holes.
When using the optional tilt mount, use flexible conduits for the last
portion connecting to the detector.
For installations in atmospheres as defined in group B of the NFPA 72E,
seal the conduits inlets.
When pulling the cables through the conduits, ensure that they are not
tangled or stressed. Extend the cables about 30 cm. (12 in.) beyond the
detector location to accommodate wiring after installation.
After the conductor cables have been pulled through the conduits,
perform a continuity test.
Installation Cables 23
SharpEyeTM IR3 Flame Detector User Guide
2.6 Installing the Tilt Mount (part no. 40/40-001)
The Tilt Mount enables the detector to be rotated up to 60º in all directions.
Figure 4 shows the Detector mounted on the Tilt Mount.
Figure 4: Detector with Tilt Mount
24 Installing the Tilt Mount (part no. 40/40-001)
TM 40/40I, Rev (6) July 2013
Tilt Mount
Tilt Holding Plate
Horizontal
Locking Screw
Vertical Locking
Screw
Detector Holding
Plate
2.6.1 Tilt Mount Assembly
Figure 5 shows the Tilt Mount Assembly.
Figure 5: Tilt Mount Assembly
Figure 6 shows the Tilt Mount Assembly with dimension in both millimeters
and inches.
Figure 6: Tilt Mount Assembly (dimensions in mm and inches)
Installing the Tilt Mount (part no. 40/40-001) 25
SharpEyeTM IR3 Flame Detector User Guide
➣ To install the Tilt Mount and Detector:
1 Place the tilt mount in its designated location and secure it with four (4)
fasteners through four (4) holes 7 mm in diameter. Use the four (4)
screws and spring washers according to the kit.
Note: Removing the detector for maintenance purpose does not require
the Tilt Mount to be removed.
2 Unpack the detector.
3 Place the detector with its conduit/cable entries pointing downwards on
the holding plate of the tilt mount. Secure the detector with 5/16" 18 UNC
x 1" screw to the tilt mount.
4 Release the Horizontal and Vertical Locking Screws using
such that the detector can be rotated. Point the detector towards the
protected area and make certain that the view of the area is
unobstructed. Secure the detector in that position by tightening the
locking screws on the tilt mount. (Make sure the detector is in the
correct position.)
The detector is now correctly located, aligned and ready to be connected
to the system.
3
/16" Hex Key
2.7 Connecting the Detector
This section describes how to connect the electric cabling to the detector
(Figure 7).
➣ To connect the detector to the electrical cables
1 Disconnect the power.
2 Remove the back cover of the detector by removing three (3) socket
head-screws in the cover bolts. The terminal chamber is now revealed.
3 Remove the protective plug mounted on the Detector Conduit/Cable
entry; pull the wires through the Detector Inlet.
26 Connecting the Detector
TM 40/40I, Rev (6) July 2013
Earth
Terminal
Terminal
Chamber
Terminals
Internal Earth
Terminal
Detector Holding
Screw
Conduit / Cable
Inlet
4 Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5
flameproof gland to assemble the cable / conduit to the detector.
Figure 7: Detector with Cover Removed
5 Connect the wires to the required terminals on the Terminal Board
according to the wiring diagram (Figure 7) and Table 15.
6 Connect the grounding (earth) wire to the ground (earth) screw outside
the detector (Earth Terminal). The detector must be well grounded to
earth ground.
7 Verify the wiring. Improper wiring may damage the detector.
8 Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the
back cover (Figure 7).
9Place and secure the detector’s back cover by screwing the three (3)
socket-head-screws in the Cover Bolts (Figure 4).
Connecting the Detector 27
SharpEyeTM IR3 Flame Detector User Guide
Wire
Terminal
No.
Option 1
Default
Option 2
Option 3
Option 4
Option 5
1
+24 VDC
+24 VDC
+24 VDC
+24 VDC
+24 VDC
2
0 VDC
0 VDC
0 VDC
0 VDC
0 VDC
3
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
4
Fault
Relay N.C.
Fault
Relay N.C.
Fault
Relay N.O.
Fault
Relay N.C.
Fault
Relay N.O.
5
6
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
7
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
8
0-20mA
In
Alarm
Relay N.C.
Alarm
Relay N.C.
Auxiliary
N.O.
Auxiliary
N.O.
9
0-20mA
Out
0-20mA
Out*
0-20mA
Out*
Auxiliary
C
Auxiliary C
10
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
2.7.1 Verifying the Detector Wiring
The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.
For more information on the wiring options, see Wiring Instructions on
page 49.
For mA wiring options see Figure 10, Figure 11, Figure 12, and Figure 13.
For relay connection options see Figure 9.
Table 15 describes the function of each terminal for all the wiring options.
Table 15: Model 40/40I Wiring Options
*Available with the HART protocol.
Notes:
RS-485 is used for communication network as specified in Appendix C
(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.
Alarm relay:
N.O. energized contact in wiring options 1, 4, 5.
N.O. and N.C. energized in options 2 and 3.
28 Connecting the Detector
TM 40/40I, Rev (6) July 2013
0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.
0-20mA 'Source' in options 2 and 3 available with the HART protocol.
In Wiring Option 1, link Terminals 1 and 8 to change the mA output to
‘Source’.
The Fault output is N.C. energized SPST relay. The contacts are closed
when the Detector is in its normal operational condition in options 1, 2
and 4, and available as N.O. energized in options 3 and 5.
The Auxiliary output is N.O. energized (SPST) relay. The Auxiliary Relay
may act in parallel with the ALARM relay to activate another external
device or it may provide a warning signal, depending on the function
configuration.
2.8 Configuring your Detector
You can reprogram the function setup using the RS-485 connection or using
the HART protocol as follows:
Mini Laptop Kit (P/N 777820): The mini laptop, pre-loaded with the
Spectrex host software, enables you to re-configure settings or perform
diagnostics on all 40/40 series flame detectors.
Refer to manual TM777070 for programming instructions when using the
Mini Laptop Kit.
USB RS485 Harness Kit (P/N 794079-5): The USB RS485 Harness Kit
with RS485/USB converter, used with the Spectrex host software,
enables you to connect to any available PC or laptop to re-configure
settings or perform diagnostics on all 40/40 series flame detectors.
Refer to manual TM777050 for programming instructions when using the
USB RS485 Harness Kit.
HART Protocol: Refer to Manual TM 777030 for programming
The factory Default settings listed for each function are:
Sensitivity – 30
Alarm Delay – A
Alarm Latch – No
Auxiliary Relay – No
Automatic BIT – Yes
Configuring your Detector 29
SharpEyeTM IR3 Flame Detector User Guide
Sensitivity Setting
Detector Distance
feet
Detector Distance
meters
15
50
15
30 (default)
100
30
45
150
45
60
215
65
Alarm BIT – No
Auxiliary BIT – No
EOL – No
Heated Optics – Auto
Temperature – 41°F (5°C)
2.8.1 Sensitivity
The detector offers four (4) sensitivity settings. The settings refer to an
n-heptane or gasoline fire of 1ft² (0.1m²), from low sensitivity of 50 ft.
(15m) to 215 ft. (65m). For other types of fuel sensitivity, refer to Table 3.
Table 16: Sensitivity Settings
2.8.2 Alarm Delay
The detector is equipped with an Alarm Delay option, which provides
programmable time delays with settings at:
Antiflare* (default)
*The Antiflare mode is selected to prevent false alarms in locations
where fast flares may be present. The Time Delay for fire alarms in this
mode ranges from 2.5 to 15 seconds (usually, less than 10 seconds).
Other delays settings are available:
0, 3, 5, 10, 15, 20 or 30 seconds
When an Alarm (Detection) level condition occurs, the detector delays the
execution of the Alarm outputs by the specified period of time. The detector
then evaluates the condition for 3 seconds. If the Alarm level is still present,
the Alarm outputs are activated. If this condition no longer exists, the
detector returns to its standby state.
The Alarm delay option affects the output relays and the 0-20mA. The LEDs
and outputs indicate warning levels during the delay time only if the fire
condition exists.
2.8.3 Address Set-up
The detector provides up to 247 addresses that can be changed with the
RS485 communication link or the HART protocol.
Yes: Activate Auxiliary Relay at Warning level.
No: Activate Auxiliary Relay at Alarm level
(default).
Automatic BIT
Yes: Perform Automatic & Manual Bit (default).
No: Perform Manual Bit only.
Alarm BIT
Yes: Successful Manual Bit activates the Alarm
Relay for approximately 3 seconds (default).
No: Successful Manual Bit does not activate the
Alarm Relay.
Auxiliary BIT**
Yes: Successful Manual Bit activates the
Auxiliary Relay for approximately 3 seconds
(default).
No: Successful Manual Bit does not activate the
Auxiliary Relay.
EOL**
Yes: Auxiliary Relay is used as End of Line.
No: Auxiliary Relay operates in accordance with
Function 2 and 5 (default).
2.8.4 Function Set-up
You can select the desired functions as detailed in Table 17.
Table 17: Functions
Note: ** only available in Model 40/40I-4XXXX and 5XXXX
Configuring your Detector 31
SharpEyeTM IR3 Flame Detector User Guide
2.8.5 Heated Optics
The heated optics can be defined as one of the following modes:
Heated Mode
OFF: Not operated
On: Continuously
AUTO: Per temperature change
In AUTO mode, the default HEAT ON setting is 41°F (5°C). Heating stops
when the temperature is 27°F (15°C) above the start temperature.
You can define the start temperature below which the window will be
heated. The temperature can be defined between 32°F and 122°F (0°C to
50°C).
32 Configuring your Detector
3 Operating the Detector
Powering Up
page 33
Safety Precautions
page 34
Testing Procedures
page 35
➣ In this chapter…
This chapter describes how to power up and test the detector. It also
includes some very important safety checks that you should make before
operating the detector.
3.1 Powering Up
This section describes how to power up the detector. Follow these
instructions carefully to obtain optimal performance from the detector over
its life cycle:
➣ To power up the detector:
1 Turn on the power.
2 Wait approximately 60 seconds for the detector to finish the start-up
procedure.
Applying power initiates the following sequence of events:
The yellow LED flashes at 4 Hz.
BIT is executed.
If successful, the green LED flashes at 1 Hz and the FAULT relay contacts
close, mA output is 4 mA.
3 Enter to Normal mode.
Note: The majority of detectors are used in the default non-latching alarm
mode. Only perform a Reset when the Latching alarm option has been
programmed.
➣ To reset a detector when in it is in a LATCHED ALARM state:
Do one of the following:
Disconnect power (Terminal Number 1 or Terminal Number 2).
or
Initiate a Manual BIT.
Powering Up 33
SharpEyeTM IR3 Flame Detector User Guide
Function
Value
Notes
Sensitivity
30
Alarm Delay
A
Antiflare.
Alarm Latch
No
Auxiliary Relay
No
In wiring options 1, 2, 3 the Auxiliary
Relay is not available. This function is not
used.
Automatic BIT
Yes
Alarm BIT
No
Auxiliary BIT
No
In wiring options 1, 2, 3 the Auxiliary
Relay is not available. This function is not
used.
EOL
No
In wiring options 1, 2, 3 the Auxiliary
Relay is not available. This function is not
used.
Heat Mode
Auto
Heat On
41°F
(5°C)
The detector starts heating the window
for any temperature below this value (in
degrees Celsius).
3.2 Safety Precautions
After powering-up, the detector requires almost no attention in order to
function properly, but the following should be noted:
Follow the instructions in this guide and refer to the drawings and
specifications.
Do not expose the detector to radiation of any kind unless required for
testing purposes.
Do not open the detector housing, while power is applied.
Do not open the electronic compartment. This part should be kept closed
at all times and only opened in the factory. Opening the electronic
component side invalidates the warranty.
You should only access the wiring compartment to wire or remove the
detector or access RS485 terminals for maintenance.
Disconnect or disable external devices, such as automatic extinguishing
systems before carrying out any maintenance.
3.2.1 Default Functions Settings
Table 18 lists the default function configuration supplied with the detector.
Table 18: Default Function Values
In order to change the default function use:
Mini Laptop Kit P/N 777820. Refer to manual TM777070 for
programming instructions when using the Mini Laptop Kit.
34 Safety Precautions
TM 40/40I, Rev (6) July 2013
USB RS485 Harness Kit P/N 794079-5. Refer to manual TM777050
for programming instructions when using the USB RS485 Harness
Kit.
HART protocol, refer to Manual TM777030 for instructions.
3.3 Testing Procedures
This section describes the proof testing procedure for proper operation of
the detector. The detector can be tested using the Manual Built-in-Test or
the Spectrex Fire Simulator -20/20-310.
The detector performs internal test continuously and automatic BIT test
every 15 minutes for more details refer to Built-In-Test (BIT) on page 16.
This section includes the following topics:
Automatic BIT Test, page 35
Manual BIT Test. page 35
Testing with Fire Simulator Model 20/20-310, page 35
3.3.1 Automatic BIT Test
Check that the indicators show normal conditions. See Powering Up on
page 33.
3.3.2 Manual BIT Test
Important: If the function setup Alarm BIT and/or Auxiliary BIT are set
to Yes (default No), the Alarm, Auxiliary Relay and 0-20mA outputs are
activated during a Manual BIT. Therefore, automatic extinguishing systems
or any external devices that may be activated during BIT must be
disconnected.
➣ To perform a Manual BIT:
1 Verify that the detector is Normal Mode.
2 Initiate Manual BIT. The results of successful and unsuccessful manual
BITs are detailed in Table 12 and Table 13.
3.3.3 Testing with Fire Simulator Model 20/20-310
The Fire Simulator Model 20/20-310 can be used to simulate exposure of
the detector to a real fire condition. The detector is exposed to radiation at
the required detection level. As a result, the detector will generate a Fire
Alarm signal. See Long Range IR3 Fire Simulator on page 57 for more
information.
Important: If the detector is exposed to a fire simulator, the Alarm and
Accessory Relays and 0-20mA are activated during the simulation.
Therefore, automatic extinguishing systems or any external devices, which
may be activated during this process, must be disconnected.
Testing Procedures 35
SharpEyeTM IR3 Flame Detector User Guide
Component
Action
Notes
0-20mA
Turn to 20mA
For a few seconds and then return to
4mA
Alarm Relay
Activated
for a few seconds and then returns to
Normal
Auxiliary Relay
Activated
for a few seconds and then returns to
Normal
Fault Relay
Remains active
during the test
LED
Red, steady
➣ To perform Fire Simulator Test:
1 Power up the system and wait up to 60 seconds for the detector to turn
to a normal state. The Power LED turns on.
2 Aim the Spectrex Fire Simulator Model 20/20-310 at the target point of
the detector (Figure 14), in a way that the radiation emitted by it is
facing directly towards the detector. (See Long Range IR3 on page 57).
3 Press the operation button once. After few seconds, a successful test
shows the results shown in Table 19.
Table 19: Results of Successful Fire Simulator Test
The detector is now ready for operation.
36 Testing Procedures
4 Maintenance and Troubleshooting
Maintenance
page 37
Troubleshooting
page 39
➣ In this chapter…
This chapter deals with preventive maintenance, describes possible faults in
detector operation and indicates corrective measures. Ignoring these
instructions may cause problems with the detector and may invalidate the
warranty. Whenever a unit requires service, please contact Spectrex or its
authorized distributor for assistance.
4.1 Maintenance
This section describes the basic maintenance steps that should be taken to
keep the detector in good working condition and includes the following
topics:
Maintenance should be performed by suitably qualified personnel, who are
familiar with local codes and practice. Maintenance requires ordinary tools.
4.1.1.1 Cleaning
The detector must be kept as clean as possible. Clean the viewing window
and the reflector of the Flame Detector periodically.
The frequency of cleaning operations depends upon the local environmental
conditions and specific applications. The fire detection system designer will
give his recommendations.
➣ To clean the detector viewing window and reflector:
1 Disconnect power to the detector before proceeding with any
maintenance including window/lens cleaning.
2 Use water and detergent, and then rinse the viewing window with clean
water.
3 Where dust, dirt or moisture accumulates on the window, first clean it
with a soft optical cloth and detergent, and then rinse with clean water.
Maintenance 37
SharpEyeTM IR3 Flame Detector User Guide
4.1.2 Periodic Procedures
In addition to preventive cleaning and maintenance, the detector should be
functionally tested every six months or as dictated by local codes and
regulations. These tests should also be carried out if the detector has been
opened for any reason.
4.1.2.1 Power-Up Procedure
Perform Power-Up procedure every time power is restored to the system.
Follow the instructions described in Powering Up on page 33.
4.1.2.2 Functional Test Procedure
Perform a functional test of the detector as described in Internal Detector
Tests on page 15.
4.1.3 Keeping Maintenance Records
It is recommended that maintenance operations performed on a detector
are recorded in a Log-book. The record should include the following:
Installation date, and contractor
Serial and tag no.
Entries for every maintenance operation performed, including the
description of the operation, date and personnel ID.
If a unit is sent to Spectrex or a distributor for service, a copy of the
maintenance records should accompany it.
38 Maintenance
TM 40/40I, Rev (6) July 2013
Problem
Cause
Corrective Action
LEDs Off
Fault Relay at N.O
0-20mA at 0mA
No power at the
unit
Check that the correct power
is sent to the detector.
Check power polarity.
Check wiring in the detector.
Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O
0-20mA at 0mA
Fault Detector
Low Voltage
Faulty Detector
Check the voltage at the
detector; verify at least 24V
at the detector terminal.
Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O
0-20mA at 2mA
BIT Fault
Faulty Detector
Clean detector window.
Re-power the detector.
Replace the detector.
Red LED
constantly on
If no fire exists,
then, detector
alarm latched
Perform Reset to the detector.
Alarm Relay at On
0-20mA at 20mA
Alarm condition
Check cause for alarm.
If no alarm, re-power the
detector.
Send the detector back for
repairs.
4.2 Troubleshooting
This section is intended to be a guide to correct problems which may happen
during normal operation.
Table 20: Troubleshooting Table
Troubleshooting 39
SharpEyeTM IR3 Flame Detector User Guide
40 Troubleshooting
Appendices
Appendices 41
SharpEyeTM IR3 Flame Detector User Guide
42 Appendices
A Specifications
Technical Specifications
page 43
Electrical Specifications
page 44
Outputs
page 44
Approvals
page 46
Mechanical Specifications
page 47
Environmental Specifications
page 47
Spectral Response
Three IR Bands
Detection Range
(at highest Sensitivity
Setting for 1ft2 (0.1m2) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
215 / 65
Kerosene
150 / 45
Gasoline
215 / 65
Ethanol 95%
135 / 40
Diesel Fuel
150 / 45
Methanol
115 / 35
JP5
150 / 45
IPA (Isopropyl
Alcohol)
135 / 40
Methane*
100 / 30
Polypropylene
Pellets
16 / 5
LPG*
100 / 30
Office Paper
33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
4 Sensitive ranges for 1 ft2 (0.1m2) n-heptane pan fire from
50 ft. (15m) to 215 ft. (65m)
Fields of View
Horizontal 100, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)
➣ In this appendix…
A.1 Technical Specifications
Technical Specifications 43
SharpEyeTM IR3 Flame Detector User Guide
Operating
Voltage
Status
All
Outputs
Without
0-20mA
Power
Consumption
(Max. 24VDC)
Normal
1.61W
1.56W
Normal when Heater On
2.28W
2.16W
Alarm
2.64W
2.28W
Alarm when Heater On
3.24W
2.88W
Maximum Current
(Max. 24VDC)
Normal
70mA
65mA
Normal when Heater On
95mA
90mA
Alarm
110mA
95mA
Alarm when Heater On
135mA
120mA
Power
Consumption
(Max. 18-32VDC)
Normal
1.95W
1.85W
Normal when Heater On
2.56W
2.45W
Alarm
3.04W
2.56W
Alarm when Heater On
3.68W
3.2W
Maximum Current
(18-32VDC)
Normal
90mA
85mA
Normal when Heater On
105mA
100mA
Alarm
130mA
115mA
Alarm when Heater On
160mA
145mA
Electrical Input Protection
The input circuit is protected against
voltage-reversed polarity, voltage transients,
surges and spikes according to MIL-STD1275B
Electrical
Interface
There are five output-wiring options. These options must
be defined at the factory per the customer order and
cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 49
for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The
wiring arrangement is identified on the detector by the
part number (see Model and Types on page 2).
Option 1: Power, RS-485, 0-20mA (Sink), Fault I
Relay (N.C), Alarm Relay, (N.O) (see Figure 7).
Option 2: Power, RS-485, 0-20mA (Source) and
A.2 Electrical Specifications
Operating Voltage: 18-32 VDC
Power Consumption: Table 21
1. The Fault relay (in wiring options 1, 2, 4) is
normally energized closed during normal operation
of the detector. The relay is de-energized open if a
fault condition or low voltage situation.
2. In wiring options 3, 5 the relay is normally
energized open during normal operation of the
detector. The relay is de-energized close contact if
a fault condition or low voltage situation occurs.
0-20mA Current Output: The 0-20mA can be Sink
or Source according to the wiring option source (see
General Instructions for Electrical Wiring on page 49).
The maximum permitted load resistance is 600Ω.
Table 23: 20 mA Current Output
State
Output
Fault
0 +1 mA
BIT Fault
2 mA±10%
Normal
4 mA±10%
Warning
16 mA±5%
Alarm
20 mA±5%
HART Protocol
The HART protocol is a digital communication signal at
a low level on top of the 0-20mA. This is a bidirectional field communication protocol used to
communicate between intelligent field instruments
Troubleshooting 45
SharpEyeTM IR3 Flame Detector User Guide
and the host system. HART is available in wiring
options 2 and 3.
Through the HART protocol the detector can:
Display set-up
Reconfigure the set-up
Display detector status and definition
Perform detector diagnostics
Troubleshoot
For more details refer to HART Manual TM777030.
Communication Network: The detector is equipped
with an RS-485 communication link that can be used
in installations with computerized controllers.
The communications protocol is Modbus compatible.
This protocol is a standard and widely used.
It enables continuous communication between a
standard Modbus controller (Master device) and a
serial Network of up to 247 detectors.
Heated
Optics
The front window can be heated to improve performance
in icing, condensation and snow conditions. The heater
increases the temperature of the optical surface by 5-8°F
(3-5°C) above the ambient temperature. The heated
optics can be configured in three ways:
Off: The optics are not heated
On: The optics are heated continuously
Auto: Operated only when the change of temperature
requires the heating. (default)
In Auto mode the start heating temperature can be
defined between 32°F - 122°F (0°C - 50°C). The detector
stops heating the window when the temperature is 27°F
(15°C) above the start temperature.
Hazardous Area
Approvals
FM, CSA
Class I Div. 1 Groups B, C and D;
Class II/III Div. 1 Groups E, F and G.
ATEX, IECEx
Ex II 2 G D
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
or
Ex de IIC T4 Ta -55°C to +85°C
Ex tD A21 IP66/X7 T105°C
Functional
Approvals
EN54-10 approved by VdS
FM approved per FM3260
A.4 Approvals
46 Approvals
TM 40/40I, Rev (6) July 2013
Enclosure
Stainless Steel 316
or
Aluminum, heavy duty copper free (less than 1%),
red epoxy enamel finish
Water and Dust
Tight
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
Electronic
Modules
Conformal coated
Electrical
Connection
(two entries)
¾" - 14NPT conduit
or
M25 x 1.5
Dimensions
4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Weight
Stainless Steel: 6.1 lb. (2.8 kg)
Aluminium: 2.8 lb. (1.3 kg)
frames/cubic ft. at a velocity of 1750 fpm, for
12 hours
A.5 Mechanical Specifications
A.6 Environmental Specifications
The SharpEye 40/40I is designed to withstand harsh environmental
conditions.
Troubleshooting 47
SharpEyeTM IR3 Flame Detector User Guide
Vibration
Designed to meet MIL-STD-810C, method
514.2, procedure VIII
Vibration at an acceleration of 1.1g within the
frequency range of 5-30 Hz, and an
acceleration of 3g within the frequency range
of 30-500 Hz
Mechanical Shock
Designed to meet MIL-STD-810C, method
516.2, procedure I
Mechanical Shock of 30g half-sine wave, for
11 msec
Electromagnetic
Compatibility (EMC)
See Table 24
Test Standard
Level Per
Electrostatic Discharge ESD
IEC 61000-4-2
IEC 61326-3
Radiated EM Field
IEC 61000-4-3
IEC 61326-3
Electrical Fast Transients
IEC 61000-4-4
IEC 61326-3
Surge
IEC 61000-4-5
IEC 61326-3
Conducted Disturbances
IEC 61000-4-6
IEC 61326-3
Power Ferq. Magnetic Field
IEC 61000-4-8
IEC 61326-3
Radiated Emission
IEC 61000-6-3
EN 55022
Conducted Emission
IEC 61000-6-3
EN 55022
Immunity to Main Supply
Voltage Variations
MIL-STD-1275B
Table 24: Electromagnetic Compatibility (EMC)
To fully comply with EMC directive and protect against interference caused
by RFI and EMI, the cable to the detector must be shielded and the detector
must be grounded. The shield should be grounded at the detector end.
48 Environmental Specifications
B Wiring Instructions
General Instructions for Electrical Wiring
page 49
Typical Wiring Configurations
page 51
AWG #
mm2
Ohm per 100 ft.
Ohm per 100 m
26
0.12 - 0.15
4.32
14.15
24
0.16 - 0.24
3.42
11.22
22
0.30 - 0.38
1.71
5.60
20
0.51 - 0.61
1.07
3.50
18
0.81 - 0.96
0.67
2.20
16
1.22 - 1.43
0.43
1.40
14
1.94 - 2.28
0.27
0.88
12
3.09 - 3.40
0.17
0.55
10
4.56 - 6.64
0.11
0.35
➣ In this appendix…
B.1 General Instructions for Electrical Wiring
Follow the instructions detailed in this section for determining the correct
wire gauge to be used for the installation.
1 Use Table 25 to determine the required wire gauge /size for general
wiring, such as relay wiring. Calculate the permitted voltage drop with
respect to load current, wire gauge and length of wires.
Table 25: Maximum DC resistance at 68°F (20ºC) for copper wire
2 Use Table 26 to select wire gauge for power supply wires. DO NOT
connect any circuit or load to detectors’ supply inputs.
Select Number of detectors connected in one circuit.
Select wiring Length per your installation requirements.
Refer to Power Supply Range for voltage extreme applied.
General Instructions for Electrical Wiring 49
SharpEyeTM IR3 Flame Detector User Guide
Number
of
Detectors
Recommended Wire Diameter (AWG)
Power
Supply
Range
(VDC)
24
18
16
14 - -
22-32
20
18
16
14 - -
22-32
16
20
18
16
14
-
22-32
12
20
18
16
14
-
20-32
8
20
18
16
14
-
20-32
4 and less
20
18
16
16
14
20-32
Ft (m)
164
(50)
328
(100)
492
(150)
656
(200)
820
(240)
Max. Length from Power Supply to Last
Detector
Table 26: Wiring length in feet (meter)
Calculation Formula
Use the following formula to calculate minimum wire gauge per wire length
between the power supply (controller) and the detector, considering the
number of detectors on the same power line, where:
L = Actual wire length between the detector and the power supply.
N = Number of detectors per loop.
R = Resistance of wire per 100 m (see Table 26).
V = Voltage drop on the wire.
Calculate the voltage drop on the wire as follows:
V = 2L x R x N x 0.2A
100
20+V = Minimum required voltage of the power supply
0.2A is the maximum power consumption of the detector
For example,
If N=1 (1 detector in loop)
L=1000m
Wire size = 1.5mm² (see Table 25, the resistance per 100m for 1.5mm² is
1.4Ω)
You calculate the voltage drop in the wire as follows:
2 x 1000 x 1.4Ω x 1 x 0.2A = 5.6V
100
The minimum voltage of the power supply should be 20V + 5.6V = 25.6V
50 General Instructions for Electrical Wiring
TM 40/40I, Rev (6) July 2013
B.2 Typical Wiring Configurations
This section describes examples of typical wiring configurations.
Figure 8: Wiring Terminals
Typical Wiring Configurations 51
SharpEyeTM IR3 Flame Detector User Guide
Wiring
Option
Detector
Model
Terminals
5 8 9
1
40/40I-
1XXXX
Fault Relay
(N.C)
0-20mA
(Sink)
0-20mA
(Sink)
2
40/40I-
2XXXX
Fault Relay
(N.C)
Alarm Relay
(N.C)
0-20mA
Source
3
40/40I-
3XXXX
Fault Relay
(N.O)
Alarm Relay
(N.C)
0-20mA
Source
4
40/40I-
4XXXX
Fault Relay
(N.C)
Auxiliary
Relay (N.O)
Auxiliary
Relay (C)
5
40/40I-
5XXXX
Fault Relay
(N.O)
Auxiliary
Relay (N.O)
Auxiliary
Relay (C)
Table 27: Wiring Connections
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2
Wiring)
Figure 13: 0-20mA Wiring Option 2 and 3 (Source 3-Wire available
with the HART Protocol)
Note: There are no 0-20mA outputs in wiring options 4 and 5.
54 Typical Wiring Configurations
C RS-485 Communication Network
RS-485 Overview
page 55
➣ In this appendix…
C.1 RS-485 Overview
By using the RS-485 network capability of the IR3detector and additional
software, it is possible to connect up to 32 detectors in an addressable
system with four (4) wires only (2 for power and 2 for communication).
Using repeaters, the number of detectors can be much larger (32 detectors
for each repeater) up to 247 on the same four (4) wires. When using the
RS-485 network, it is possible to read each detector status (FAULT,
WARNING, and ALARM) and to initiate a BIT to each detector individually.
For more details, consult Spectrex.
Figure 14: RS-485 Networking
RS-485 Overview 55
SharpEyeTM IR3 Flame Detector User Guide
56 RS-485 Overview
D Accessories
Long Range IR3 Fire Simulator
page 57
Tilt Mount - P/N 40/40-001
page 60
Duct Mount P/N 777670
page 61
Weather Protection - P/N 777163
page 62
Laser Detection Coverage Pointer - P/N 777166
page 63
Air Shield - P/N 777650
page 64
➣ In this appendix…
This appendix describes the accessories that can help you maximize fire
detection with the SharpEye IR3flame detector:
D.1 Long Range IR3 Fire Simulator
The SharpEye IR3 Long Range Fire Simulator 20/20-310 is designed
specifically for use with SharpEye flame detectors. The Fire Simulator emits
IR radiation in a unique sequential pattern corresponding to and
recognizable by the detector as fire. This allows the detectors to be tested
under simulated fire conditions without the associated risks of an open
flame.
There is an optional beam collimator, model no. 20/20-190, specially
designed for extended test range.
Figure 15: SharpEye Long Range Fire Simulator 20/20-310
Long Range IR3 Fire Simulator 57
SharpEyeTM IR3 Flame Detector User Guide
Target Point
D.1.1 Unpacking
Verify that you have received the following contents:
Delivery form
Fire Simulator with integral batteries
Battery charger
Optional Beam Collimator
Storage case
D.1.2 Operating Instructions
Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
➣ To simulate a fire:
1 Aim the Fire Simulator towards the detector’s Target Point
Figure 16: 40/40I IR3 Detector Target Point
2 When testing keep a distance of at least 50 cm (20 inches) from the
detector.
3 Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).
58 Long Range IR3 Fire Simulator
TM 40/40I, Rev (6) July 2013
Sensitivity
Detection
Range (ft. / m)
Standard Test
Range (ft. / m)
Extended Test
Range (ft. / m)
1 (Low)
50 / 15
3.8 / 1.2
7 / 2.2
2
100 / 30
7 /2.2
14.5 / 4.5
3
150 / 45
10 / 3.2
22 / 7
4 (High)
215 / 65
14.5 / 4.5
29 / 9
4 Wait 20 seconds before repeating the test.
5 Verify that the optical window is clean.
D.1.3 Range
Table 28: Sensitivity Ranges
Notes:
The minimum distance from the detector is 20 inches (50 cm).
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the
range.
Important: Keep the Fire Simulator in a safe place when not in use.
D.1.4 Charging the Battery
The Fire Simulator uses NiCd batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates for at least 60
times without recharging. An internal buzzer is sounded when the voltage
from the batteries is lower than the required operational level.
➣ To charge the battery:
1 Place the Fire Simulator on a table in a safe area.
2 Turn the sealed plug (next to the operation button) counter-clockwise
with a suitable wrench.
3 Connect the battery charger.
4 Charge for a maximum of 14 hours.
5 Disconnect the charger.
6 Tighten the sealed plug clockwise.
Warning: Charge the simulator only when the battery is fully discharged.
During activation of the flame simulator, buzzer activation indicates that the
battery is discharged.
Long Range IR3 Fire Simulator 59
SharpEyeTM IR3 Flame Detector User Guide
Mechanical
Explosion Proof Enclosure:
NFPA (designed to meet)
Class I, Division 1 & 2 Groups B, C and D
Class II, Division 1 & 2 Groups E, F and G
ATEX EX II2G NEMKO 02ATEX255
EExd IIB T5 50°C per En 50-014 & EN50-018
Electrical
Power: 8 VDC Max.
6 x Rechargeable 1.2 VDC NiCd Batteries
Current: 2.5A Avg.
Charge: 400 mA for 14 Hours
Environment
Temperature Range:-4 to +122ºF (-20 to +50ºC)
Vibration Protection: 1g (10-50hz)
Water and Dust: IP 67 per EN 60529
Physical
Dimensions: 11.5 x 10.1 x 3.9 in
(292 x 258 x 100 mm)
Weight; 7.5 lb. (3.4 Kg)
D.1.5 Technical Specifications
D.2Tilt Mount - P/N 40/40-001
The Tilt mount provides accurate directional selection for optimum area
coverage.
Figure 17: Tilt Mount
60 Tilt Mount - P/N 40/40-001
TM 40/40I, Rev (6) July 2013
D.3 Duct Mount P/N 777670
The Duct Mount enables flame detection in areas where high temperatures
exist or where the detector cannot be installed inside the area. It comprises
a special duct mount arrangement with a specific optical window to allow
installation in high temperature duct applications. The mount can be used
with all Spectrex 40/40 Series flame detectors.
Figure 18: Duct Mount
Duct Mount P/N 777670 61
SharpEyeTM IR3 Flame Detector User Guide
D.4 Weather Protection - P/N 777163
The weather protector protects the detector from different weather
conditions, such as snow and rain.
Figure 19: Weather Protection
62 Weather Protection - P/N 777163
TM 40/40I, Rev (6) July 2013
D.5 Laser Detection Coverage Pointer - P/N 777166
The Laser Detection Coverage Pointer evaluates detector coverage on-site.
The device is an add-on accessory that enables designers and installers to
optimize detector location and assess the actual coverage of installed
detectors.
The device is universal and can be used with all 40/40 SharpEye Optical
Flame Detectors.
Figure 20: Laser Detection Coverage Pointer
Laser Detection Coverage Pointer - P/N 777166 63
SharpEyeTM IR3 Flame Detector User Guide
D.6 Air Shield - P/N 777650
The Air Shield enables you to install the detector in dirty areas and using
compressed air, keep the window clean. This prevents the accumulation of
dirt on the window and enables the detector to continue to operate under
harsh conditions.
When the air shield is fitted on the detector, it reduces the cone of vision of
the detector by ±5° in each direction.
Figure 21: Air Shield
64 Air Shield - P/N 777650
E SIL-2 Features
40/40I Flame Detector
page 65
➣ In this appendix…
E.1 40/40I Flame Detector
This appendix details the special conditions to comply with the requirements
of EN 61508 for SIL 2.
The 40/40I Flame Detector can only be used in low or high demand mode
applications, see IEC 61508.4, Chapter 3.5.12.
E.1.1 Safety Relevant Parameters
Perform the following functional checks of the detector:
Alternative 1: Functional check of the detector every 180 days:
HFT: 0
PFD: 3.0 x 10 -4 (≈ 3% of SIL-2) if only Alarm Relay is used for
alerting.
PFD: 3.2 x 10 -4 (≈ 3.2% of SIL-2) if 0-20mA – interface is used as
alarm.
PFH: 1.5 x 10 –7 1/h (≈ 14.9% of SIL-2) for 0-20mA application.
SFF: 95% fulfills the conditions of EN 61508 for SIL2
Alternative 2: Functional check of the detector every 365 days:
HFT: 0
PFD: 4.5 x 10 -4 (≈ 4.5% of SIL-2) if only Alarm Relay is used for
alerting.
PFD: 4.9 x 10 -4 (≈ 4.9% of SIL-2) if 0-20mA – interface is used
signal current as alarm.
PFH: 1.5 x 10 –7 1/h (≈ 14.9% of SIL-2) for 0-20mA application.
SFF: 95% fulfills the conditions of EN 61508 for SIL2
E.1.2 Guidelines for Configuring, Installing, Operating and
Service
The alert conditions according to SIL 2 can be implemented by an:
Alert signal via 20mA current loop
or
Alert signal via alarm relay and the fault relay
40/40I Flame Detector 65
SharpEyeTM IR3 Flame Detector User Guide
E.1.2.1 Conditions for Safe Operating
1 The flame detector shall consist only of the approved hardware and
software modules.
2 The 24V power supply must fulfill the requirements for PELV / SELV of
EN 60950.
3 The automatic BIT (Built-In-Test) must be activated.
4 The set-up parameters must be verified (as described in
Using the 0-20mA Interface for Alerting on page 66, point 1 and in Using
the Alarm Relay Contact for Alerting on page 66, point 1) and the
function of the 40/40 Flame Detector (flame detection, function of the
0-20mA interface, relay functions) must be checked completely.
E.1.2.2 Using the 0-20mA Interface for Alerting
1 The following parameters shall be set:
AUTOMATIC BIT test = on
Connected to 0-20mA Terminals
2 The following allowed output current must be supervised with an
accuracy of ± 5%:
Normal State = 4mA
Warning State = 16mA
Alarm State = 20mA
3 The output current must be supervised regarding the over-and under run
of the 0-20mA.
4 The 0-20mA can be used as low and high demand mode.
E.1.2.3 Using the Alarm Relay Contact for Alerting
1 The following parameters shall be set:
AUTOMATIC BIT Test = on
Connected to N.C contact of Alarm Relay Terminals
Connected to Fault Relay Terminals
2The relay contacts (“alarm” – and “faulty relay”) must be protected with
a fuse rated at 0.6 of the nominal specified relay contact current.
3 The maximum contact rating that is allowed per SIL-2 is 30VDC.
4 It is to be considered that the contact of the Alarm Relay opens if there
is a fire alarm.
5 During the forwarding and evaluation of the alarm it must be noted that
the relay contact opens.
6 The alarm relay can be used as low demand only.
66 40/40I Flame Detector
TM 40/40I, Rev (6) July 2013
E.1.2.4 Other
1 The complete function of the flame detector (flame detection, function of
the 0-20mA interface, the relays) must be examined at least every six or
twelve months (see Safety Relevant Parameters on page 65, when the
flame detector must be switched OFF and ON.
2 The window of the sensor must be examined at appropriate time
intervals for partial contamination.
3 The HART and the RS 485 interfaces must not be used for the
transmission of the safety-related data.
40/40I Flame Detector 67
Technical Support
For all technical assistance or support, contact:
218 Little Falls Road
Cedar Grove, NJ 07009, USA
Tel: +1 (973) 239 8398
Fax: +1 (973) 239 7614
Email: spectrex@spectrex.net
Web-site: www.spectrex.net
Your Local Office:
SPECTREX INC.
Texas (USA)
Mr. Jay Cooley, Regional Sales Manager:
16203 Park Row, Suite 150
Houston, Texas 77084
USA
Phone: +1 (832) 321 5229
Email: jay@spectrex.net
Europe
Mr. Ian Buchanan, Regional Manager:
6 Applecross Road
Glasgow G66 3TJ
United Kingdom