SMA Windy Boy 1100, Windy Boy 1700 Operating Instructions Manual

Windy Boy 1100 Windy Boy 1700 Inverter for Wind Energy Power Plants
Operating Instructions Version 1.0 WB11_17-11:FE4205
TBE-WB11-17
SMA Technologie AG Revision History
Revision History
Document number Changes Author
Operating Instructions WB11_17-11:FE4205 Page 3
SMA Technologie AG
Page 4 WB11_17-11:FE4205 Operating Instructions
SMA Technologie AG Explanation of Symbols used in this Document
Explanation of Symbols used in this Document
This symbol indicates information that is essential for a trouble-free and safe operation of the product. Please read these sections care­fully in order to avoid any damages of the equipment and for op­timal personal protection.
This symbol indicates information that is required for the optimal operation of the product. Read these sections carefully in order to ensure an optimal ope­ration of the product and all its features.
This symbol indicates an example.
Operating Instructions WB11_17-11:FE4205 Page 5
Legal Restrictions SMA Technologie AG
Liability exclusion
The information contained in this documentation are the property of SMA Technologie AG. No part of this documentation may be published without written permission from SMA Technologie AG. A reproduction for internal purposes for the evaluation of the product or an appropriate application is permitted and does not require authorization.
All information are based on our "General Terms and Conditions of Delivery of SMA Technologie AG”. The content of this documentation is reviewed continuously and adjusted, if necessary. SMA Technologie AG provides this documentation without exclusion of deviations and without warranty of completeness. You will find the current version on the Internet at www.SMA.de or can obtain it via the usual sales channels. Warranty or liability claims for all kinds are excluded in case of damages due to:
• Inappropriate use of the product
• Operation of the product in an improper environment
• Operation of the product without considering the relevant safety regulations
• Non-fulfillment of the warnings or safety instructions described in the documentation for the product
• Operation of the product under faulty conditions concerning security and protection
• Arbitrary changing of the product or the provided software
• Failure of the product due to interference of connected or contiguous devices out of legal limit values
• Disasters and force majeure
Software Licensing
The use of the provided software by SMA Technologie AG is subject to the following conditions: The software may be reproduced for internal purposes and installed on any number of computers. Provided source codes can be changed and adjusted on the company’s own authority according to the internal purpose. Driver may be ported to other operating systems as well. No part of the source codes may be published without written permission of SMA Technologie AG. Sublicensing of the software is not acceptable.
Liability limitation: SMA Technologie AG disclaims liability for any direct or indirect consequential damages arising from the use of the software produced by SMA Technologie AG. The same applies for the provision and/or non-provision of support.
Provided software not produced by SMA Technologie AG is subject to the respective licensing and liability agreements of the manufacturer.
Trademarks
All brand and product names used herein are trademarks or registered trademarks of their respective holders, although they may not be specifically designated as such.
SMA Technologie AG Hannoversche Strasse 1-5 34266 Niestetal Germany Tel. (+49) 5 61 95 22 – 0 Fax (+49) 5 61 95 22 – 100
www.SMA.de
E-Mail: info@SMA.de
© 2005 SMA Technologie AG. All rights reserved.
Page 6 WB11_17-11:FE4205 Operating Instructions
SMA Technologie AG Table of Contents
Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Appropriate usage of the Windy Boy . . . . . . . . . . . . . . . . . . .13
3.2 Device construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.3.1 Normal operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.3.2 Critical, faulty operation . . . . . . . . . . . . . . . . . . . . . . . . .18
3.3.3 Non-critical, faulty operation . . . . . . . . . . . . . . . . . . . . . .18
3.3.4 Description of the operational status . . . . . . . . . . . . . . . .19
3.4 Messages in the optional display . . . . . . . . . . . . . . . . . . . . . .26
4 Setting the display language . . . . . . . . . . . . . . . . . . 29
5 Turbine operation . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.2 Characteristic curve function. . . . . . . . . . . . . . . . . . . . . . . . . .31
5.3 Characteristic curve operation in "Turbine" operating mode . . .34
5.4 General setting example . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
6 Maintenance and care. . . . . . . . . . . . . . . . . . . . . . . 37
7 Expansions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.1 Sunny Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
7.2 Sunny Data via Powerline . . . . . . . . . . . . . . . . . . . . . . . . . . .40
7.3 Sunny Data over RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
7.4 Sunny Data over RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
7.5 Sunny Beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
7.6 Sunny Data Control over Sunny Beam . . . . . . . . . . . . . . . . . .42
7.7 Sunny Boy Control Light. . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
7.8 Sunny Boy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
7.9 Sunny Boy Control Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
7.10 Sunny Data Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
7.11 Sunny WebBox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
7.12 Sunny Portal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
7.13 Sunny TV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
8 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1 Windy Boy 1100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
8.1.1 DC connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
8.1.2 Grid connection data . . . . . . . . . . . . . . . . . . . . . . . . . . .48
8.1.3 General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
8.2 Windy Boy 1700. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
8.2.1 DC connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Operating Instructions WB11_17-11:FE4205 Page 7
Table of Contents SMA Technologie AG
8.2.2 Grid connection data . . . . . . . . . . . . . . . . . . . . . . . . . . .51
8.2.3 General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
9 General information. . . . . . . . . . . . . . . . . . . . . . . . . 53
9.1 Measurement channels and messages. . . . . . . . . . . . . . . . . . .53
9.1.1 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.1.2 Windy Boy operating parameters . . . . . . . . . . . . . . . . . .55
9.2 Fault messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
9.3 Declaration of conformity (CE) . . . . . . . . . . . . . . . . . . . . . . .61
9.4 Import certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
10 Stand-alone systems. . . . . . . . . . . . . . . . . . . . . . . . . 63
11 Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Page 8 WB11_17-11:FE4205 Operating Instructions
SMA Technologie AG Introduction

1 Introduction

The installation of the Windy Boy 1100 / 1700 may only be done by qualified technicians. The installer must be approved by the utility company. Please read the installation guide carefully before you begin with the installation. The installation of utility interactive power sources must be compliant with all applicable regulations of the utility company and with all applicable regulations and standards.
The Windy Boy inverters make it possible to operate small wind turbines as grid-con­nected systems. Grid-connected means that the energy generated by the wind turbine can be fed directly into an existing house power grid, a stand-alone power system, or the mains grid.
To this end, the inverter converts the direct current (DC) from permanent-magnet wind turbines, which varies with speed, into grid-compatible alternating current (AC). The inverter requires the constant presence of mains-grid voltage!
The Windy Boy complies with all the VDEW (Verband der Elektrizitätswirtschaft – German Electricity Industry Association) regulations for the connection and parallel operation of electrical power units to the low-voltage grid of the electricity supply company. This also encompasses the regulations of the German Professional Associ­ation for Precision Engineering and Electro technology relating to "Automatic switch­ing of electrical power units" (SMA grid guard) and/or DIN VDE 0126. In addition to this, the Windy Boy conforms to the electromagnetic tolerance regulations and the low-voltage regulations of the relevant combined European norms, as confirmed in the CE conformity declaration (9.3 "Declaration of conformity (CE)” (page 61)).
The documentation provided here covers all such topics that are of interest when op­erating the Windy Boy inverters. In addition to explanations of the operational meth­ods of the device and detailed technical data, advice as to data capture and analysis is also provided.
Information relating to the installation and commissioning of the Windy Boy should be taken from the installation instructions delivered with the device. The Windy Boy inverter has a special operation mode for wind turbines which allows performance adjustment to the characteristic curve of the generator. In this way you will obtain maximum yields from your wind turbine.
A wide input voltage range, high efficiency and a freely configurable output charac­teristic curve with the highest level of reliability are only some of the properties that are useful for your grid-connected system, or in a stand-alone system when combined with the Sunny Island.
Operating instructions WB11_17-11:FE4205 Page 9
Introduction SMA Technologie AG
The Windy Boy is compatible with all SMA communication products (RS232, RS485, Powerline, Wireless, Display), providing numerous possibilities for diagnosis, data vi­sualization and remote maintenance of your small wind turbine system.
For stand-alone systems, that use the Sunny Island: Please configure your Windy Boy according to the specifications in the Sunny Island manual.
Configuration of the V/I properties of the Windy Boy with respect to your wind turbine: the parameters U
Start, UDCWindStart and UDCWindMax must be
PV
configured to guarantee optimum operation of your Windy Boy with your wind turbine. The configuration process is described in chapter 5 "Turbine opera­tion” (page 31).
Apart from the parameter settings, the Windy Boy is identical to the Sunny Boy pho­tovoltaic inverter and can therefore also be used as a PV inverter. Please download the Sunny Boy manual from www.SMA.de. If you are planning to use the Windy Boy in a photovoltaic system please contact us on the SMA hotline.
Page 10 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Safety Information

2 Safety Information

Opening of the device, and any
•electrical installation,
•repair or
•modification
Betrieb
Photovoltaik-Stringwechselrichter
Operation
Photovoltaic string
Erdschluss
in verter
Earth
F
ault Störung Failure
The temperature of individual parts of the case of the Windy Boy ­in particular the temperature of the heatsink - can reach over 60 °C in normal operation. There is the danger of burn injury when these parts are touched!
The Windy Boy contains an independent mains disconnection device, the "SMA grid guard". It ensures that the Windy Boy complies with the VDEW (Verband der Elektrizitätswirtschaft – German Electricity Industry Association) regula­tions for the connection and parallel operation of electrical power units to the low-voltage grid of the electricity supply company (EVU) and with DIN VDE 0126, which forms a part of these regulations.
of the Windy Boy may only be performed by qualified electrical personnel. Even when no external voltage is present, the device can still contain high voltages and the danger of electrical shock.
Operating instructions WB11_17-11:FE4205 Page 11
Safety Information SMA Technologie AG
Page 12 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description

3 Unit description

3.1 Appropriate usage of the Windy Boy

The Windy Boy is designed for the conversion of DC voltage from a wind turbine (permanent magnet generator) into AC voltage for feeding into the public mains grid. The technical data is described in more detail in chapter 8 "Technical data” (page 47).
Overvoltage protection
Windy
Boy
Net z w
e c h
G
s e
r i
l
d
r i
c t i
h
e
t
d
e
r i n
f
ü
ve
r
r
W te r
i
n
f
d
o
e
r
n
w
e r
i
n
g
d
i e
t
a
u
n r b
l
a i n
g e
e
s
Control unit
Control unit
n
Wind
Generator
Converter
Rectifier
Windy Boy
Public mains grid
Many wind turbine manufacturers offer an extra over-voltage protection module. These components prevent the destruction of the downstream inverter in the case of overvoltage.
Overvoltage can occur under the following conditions:
• High turbine rotation speeds under strong wind conditions
• An increase in turbine rotation speed caused by load-shedding when the inverter is disconnected from the mains grid e.g. in the case of mains interference or po­wer outage.
The overvoltage protection system has the following tasks:
• When a pre-defined voltage is reached, the inverter is disconnected from the ge­nerator and a short-circuit slows the generator and/or brings it to a standstill.
• Some devices reduce the turbine rotation speed, and thus the generator output voltage, by switching in a resistor assembly (Dumpload). The electrical energy ge­nerated by the turbine is then converted to heat.
In grid-connected systems, we recommend the use of one of the electronic protection mechanisms described here. Please note that overvoltage on the inverter can lead to destruction of the device. In addition to this, you lose the right to all warranty claims
- even if the maximum input voltage of the inverter is only exceeded for a short time.
Operating instructions WB11_17-11:FE4205 Page 13
Unit description SMA Technologie AG
The electronic protection systems described here are preferable to mechanical solu­tions (pitch control, "turning out of the wind") in every case.
Any other use of the Windy Boy leads to loss of the right to all warranty claims.
The presence of excessive input voltage can lead to irreparable damage! Immediately disconnect the DC input of the Windy Boy.
When the Windy Boy receives an excessive DC input voltage, it automatically disconnects from the mains network and no longer feeds power into the grid. When the Windy Boy is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy!
Page 14 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description

3.2 Device construction

An attractive, functional design is one of the major design objectives of the entire Windy Boy product range. In its basic configuration, the Windy Boy has the proven status display consisting of three LEDs. An extra display can be provided already in­stalled or can be retrofitted.
As long as it is installed and commissioned according to the technical specifications, the Windy Boy can be operated without any further modification or configuration. The device parameters can however be modified, if required.
Windy Boy 1100/1700 Enclosure IP65 (outside installation possible)
SMA grid guard
Transformer
Optional
display
(IP65)
Bridge
Optional communi-
cation
interface
RS232 RS485
Powerline
Radio
+
+
DC input with 2x2 DC connectors
Characteristic
wind curve
Overvoltage
protection:
Thermally monitored
varistors
An extra communications interface is required for ideal adapta­tion of the Windy Boy to suit the particular wind turbine being used, and this can also be used for reporting operation data. For further details, please refer to chapter 7 "Expansions” (page 39).
L
N
AC plug
PE
Operating instructions WB11_17-11:FE4205 Page 15
Unit description SMA Technologie AG
All DC connections and connections for the mains grid, as well as any optional com­munications connections are to be found on the underside of the Windy Boy. Each of the + and - DC connections are internally connected in parallel within the Windy Boy.
Plug connector for DC
+
Plug connector for DC -
Opening for optional communication
via RS232, RS485 or Radio (for PG16)
AC plug for the
mains supply connection
Page 16 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description

3.3 Operating modes

The operational status is displayed using three light-emitting diodes (LEDs) in the cov­er of the Windy Boy. To allow the device to signal its operational status via the inte­grated LEDs, the Windy Boy must be connected to the DC side of the system. There must be enough wind energy present, so that the Windy Boy has adequate DC volt­age.
Pac 903W Upv 330V
Netzwechselrichter für Windenergieanlagen Grid tied inverter for wind turbines
Especially in the first year of operation, the operator of the system should check this display under different wind speeds.
A complete description of the possible displays can be found in chapter 3.3.4 "De­scription of the operational status” (page 19). These can be split into three catego­ries:

3.3.1 Normal operation

As long as the green control LED is on, or blinking, the Windy Boy is operating nor­mally. The simultaneous illumination of all three LEDs is also an indication of normal operation ("Initialization"). All other displays are a sign of abnormal operation.
Operating instructions WB11_17-11:FE4205 Page 17
Unit description SMA Technologie AG

3.3.2 Critical, faulty operation

A comprehensive safety concept limits the number of critical conditions that can occur to a single situation:
Input voltage exceeds the permitted value
This is indicated by the following blink-code on the yellow LED:
The yellow LED illuminates 4 times
LED on
LED off
3s 1s1s 1s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The presence of excessive input voltage can lead to irreparable damage! Immediately disconnect the DC input of the Windy Boy.
12
34
When the Windy Boy receives an excessive DC input voltage, it automatically disconnects from the mains network and no longer feeds power into the grid. When the Windy Boy is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy!

3.3.3 Non-critical, faulty operation

All other fault codes indicate some form of faulty operation, which are not usually dangerous to people or equipment, but which should nevertheless be investigated and corrected.
Despite all precautions, it is possible that other faults may occur that cannot be dis­played (e.g. failure of the status display). In order to recognize such faults, the oper­ator of the system should use the explanations in chapter 3.3.4 "Description of the operational status” (page 19) to check the plausibility of the displayed status. Further detailed diagnoses are possible using the communication options detailed in chapter 7 "Expansions” (page 39).
Page 18 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description

3.3.4 Description of the operational status

No (or low) input voltage
The Windy Boy is in Standby mode. This situation occurs when the input perfor-
All LEDs are off.
Initialization
All LEDs are on.
mance is too low for feeding the mains grid (DC input voltage < approx. 80 V) and for satisfying the on-board power re­quirements.
The on-board computer of the Windy Boy is presently in the initialization pro­cess. The DC input voltage of the Windy Boy lies between approx. 80 V and ap­prox. 120 V. The power is adequate for the on-board power requirements but in­sufficient for mains-grid feed-in or for data transmission.
Working mode
The Windy Boy has successfully passed the measurement electronics and SMA
Green LED is on.
Operating instructions WB11_17-11:FE4205 Page 19
grid guard self-tests and has begun feed­in operation.
The Windy Boy is working normally and is feeding electricity into the mains grid. It is converting the DC voltage from the wind turbine according to the V/I char­acteristic curve defined by <U
WindStart> and <UDCWindMax>
<U
DC
Start>,
PV
(chapter 5 “Turbine operation" on page 31).
Unit description SMA Technologie AG
Stop
The Windy Boy is in Stop mode. Among other functions, the measurement elec-
1s
Green LED blinks 3 times per second.
tronics are calibrated and then finally, the device switches to "Waiting" mode.
The "Stop" mode can also be manually set by the system operator via the Sunny Boy Control or the Sunny Data PC pro­gram. In this case, the Windy Boy re­mains in "Stop" mode until a new operating mode ("MPP mode", "Turbine mode") has been set.
Maintenance, grid monitoring
The Windy Boy checks if the initial condi­tions necessary for feeding the mains
1s
The green LED blinks once per second.
supply are satisfied (e.g. start voltage) and then begins monitoring the mains network.
Derating
The temperature monitoring of the
1s
The green LED turns off briefly once per second.
Windy Boy has reduced the output per­formance to prevent the device from overheating. If this occurs often, then this is an indication of inadequate heat dissi­pation.
To avoid unnecessary reductions in yield, in this case it should be checked if the Windy Boy can be mounted in a bet­ter position with better ventilation.
Page 20 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description
Defective varistor or insulation fault
The green LED blinks once per second.
The red LED is continuously on.
Consult trained electrical personnel to correct the fault. You should also read about this issue in the "Installation manual".
The red LED of the Windy Boy illuminates continuously. A ground fault exists or one of the thermally monitored varistors on the DC input is defective as a result of overvoltage.
Constant operational limiting
This message is displayed if a fault devel­ops in the grid monitoring and/or the in­dependent disconnection device (SMA
The yellow LED is continuously on.
grid guard). The Sunny Boy has detected a fault in the SMA grid guard during an internal test and has disabled the mains supply feed-in.
This usually indicates a fault that cannot be corrected on site. Please consult the manufacturer (chapter 11 "Contact” (page 65)) and discuss further action to solve the problem with them.
Operating instructions WB11_17-11:FE4205 Page 21
Unit description SMA Technologie AG
Mains supply fault
The yellow LED illuminates 2 times
LED on
LED off
12
3s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 2 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The Windy Boy indicates a mains supply fault with this message, which can have the following causes:
• Low mains supply voltage (VAC < "Vac-Min")
• High mains supply voltage (VAC > "Vac-Max")
• Low mains supply frequency (fAC < "Fac-Min")
• High mains supply frequency (fAC > "Fac-Max")
• A change in mains supply frequency ("dFac")
Check if a general mains supply dropout has occurred (check the operation of other mains supply devices), and check if the fuse of the feed-in connection of the Windy Boy is intact.
If none of these faults can be found, then the mains supply connec­tion of the Windy Boy must be checked by qualified electrical per­sonnel.
Page 22 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description
Mains supply impedance is too high
The yellow LED illuminates 3 times
LED off
LED on
5s
The message is repeated 3 times and then begins again.
12
3s 1s
3
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 3 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The Windy Boy has detected a fault relating to an unacceptable impedance in the mains supply. If the Windy Boy frequently displays this fault during mains monitoring, the cause can be a mains impedance that is too high. An electrician can usually assist with this problem by increasing the cross section of the mains connection cable. Other measures can be taken to correct this problem, but they require the agreement and cooperation of the electricity supplier.
Operating instructions WB11_17-11:FE4205 Page 23
Unit description SMA Technologie AG
Input voltage too high
The yellow LED illuminates 4 times
LED off
LED on
5s
The message is repeated 3 times and then begins again.
12
3s 1s1s 1s 1s
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
Immediately disconnect the DC input of the Windy Boy. The pres­ence of excessive input voltage can lead to irreparable damage! Make sure that the input voltage never exceeds 400 V.
When the Windy Boy receives an excessive DC input voltage, it automatically disconnects from the mains network and no longer feeds power into the grid. When the Windy Boy is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy!
34
Page 24 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Unit description
Device faults
The yellow LED illuminates 5 times
LED off
LED on
5s
The message is repeated 3 times and then begins again.
12
3s 1s1s 1s 1s
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 5 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The Windy Boy is in a condition that prevents it from entering normal operation. There is possibly a defect in the Windy Boy.
If this often occurs, the device must be checked by qualified electri­cal personnel.
345
Operating instructions WB11_17-11:FE4205 Page 25
Unit description SMA Technologie AG

3.4 Messages in the optional display

If this often occurs, the device must be checked by qualified electri­cal personnel.
The Windy Boy can be factory fitted with an LCD display in the lid of the case.
Windy
Boy
Betrieb
Pac 903W
Operation
Upv 330V
Erdschluss Earth
F
Netzwechselrichter für Windenergieanlagen Grid tied inverter for wind
The display can also be retrofitted (SMA order code, "SB-Display", language speci­fication to be provided when ordering).
ault
Störung
t
urbines
Failure
Switching on the display illumination
The background illumination is switched on by tapping on the lid of the case. Tapping again switches the display to the next message.
After 2 minutes, the illumination switches off automatically.
Display messages in the startup phase
SunnyBoy 1700
WRxxx
Initialization phase
BFR Version 2.00 SRR Version 2.00
Initialization phase
Page 26 WB11_17-11:FE4205 Operating instructions
The following messages are displayed during the startup phase of the Windy Boy 1700 and are iden­tical to those in the Windy Boy 1100. Since the Windy Boy is identically to the Sunny Boy, apart from the mode of operation, the display shows "Sun­ny Boy“.
After 6 seconds, the firmware version of the opera­tion control unit (BFR) and the current control unit (SRR) are displayed.
SMA Technologie AG Unit description
Display message during operation
The display shows the most important operational information of the Windy Boy in a continuous cycle. The following three diagrams serve to clarify the messages. Every message is displayed for 5 seconds. Then the cycle begins again.
The energy generated today and the current opera­tional status are first displayed.
E-today 3.86 Status Turbine
Energy sum since the last activation, and
the current operational status
Note: The amount of energy shown under "E-today" does not necessarily reflect the amount of energy produced over the last 24 hours. This is rath­er the energy produced by the Windy Boy since the last deactivation/ac­tivation (wind turbine standstill).
Subsequently, the current feed-in power and the out­put voltage are displayed.
This is then followed by the total energy produced so far and the operational hours of the device.
Pac 903W Vac 195V
Current feed-in power and
AC voltage
E-total 724,4kWh h-total 512h
Total amount of energy produced and the
total number of operating hours
Fault displays
If an operational fault develops, the display immedi­ately switches to "Disturbance" and the background illumination is switched on.
The cause of the fault is displayed for 5 seconds in the second line of the display.
Disturbance
Vac-Bfr
Fault display
If a measured value is responsible for the fault condi-
tion, then the value measured at the time of the fault is displayed. If another measurement is possible, the current value is displayed in the second line.
at: 261V present: 245V
Display of the values measured
during the fault
After another 5 seconds, normal operational information is again displayed.
If the fault is still present, the fault display starts again from the beginning. An over­view of the status and fault messages can be found in chapter 9.2 "Fault messages” (page 58) of this document.
Operating instructions WB11_17-11:FE4205 Page 27
Unit description SMA Technologie AG
Faults
ROM
Fault displays
of the Firmware EEPROM
"Fehler ROM" indicates, that the Windy Boy has re­cognized a fault in the Firmware EEPROM. Contact SMA to correct the fault.
Special display in the case of excessive DC input voltage
!PV-Overvoltage!
DISCONNECT DC
Overvoltage displays
Immediately disconnect the DC input of the Windy Boy. The pres­ence of excessive input voltage can lead to irreparable damage! Make sure that the input voltage never exceeds 400 V.
Before placing the device back into operation, the input voltage must be checked before reconnecting the DC voltage to the Windy Boy! Since the Windy Boy is identical to the Sunny Boy, apart from the mode of operation, the display shows "PV" (Photovoltaic) as its input source.
When the Windy Boy receives an excessive DC input voltage, it automatically disconnects from the mains network and no longer feeds power into the grid. When the Windy Boy is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy.
If an excessive DC input voltage is present on the Windy Boy, then this is indicated by rapid blinking of the background illumination and a corresponding message.
Page 28 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Setting the display language

4 Setting the display language

The display language is set using the switches on the underside of the SB-LCD com­ponents.
Since the cover must be removed, please ask a qualified electrician to disconnect the DC and AC connections from the Windy Boy, ac­cording to the installation instructions.
Position of the switches for language configuration
E-Total 124.4kWh h-Total 512h
S1
S1
AS2AB B
AS2ABB
PE
L
N
Language Switch S2 Switch S1
German B B English B A French A B Spanish A A
Operating instructions WB11_17-11:FE4205 Page 29
E-Total 124.4kWh h-Total 512h
S2
S1
S2
A
A
S1
AB B
ABB
Setting the display language SMA Technologie AG
Page 30 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Turbine operation

5 Turbine operation

5.1 Overview

The Windy Boy is a single phase inverter that converts DC current into AC current and feeds the energy generated by a wind turbine into an existing mains grid.
The Windy Boy is externally identical to the Sunny Boy inverter for photovoltaic sys­tems.
The Windy Boy inverter has a special operational mode for wind generators howe­ver, which allows performance adjustment to the characteristic curves of many diffe­rent manufacturers' generators ("Turbine" operating mode). In this way maximum yields can be obtained from your wind turbine.
The mechanical power of the wind turbine is presented to the inverter in the form of a direct, rotation speed variable DC voltage (RPM) and current intensity (torque).
Most small wind turbines have a so-called permanent magnet generator and a down­stream rectifier for converting the variable frequency AC generator voltage into DC current.

5.2 Characteristic curve function

The "Turbine" operating mode of the Windy Boy uses a programmable power/volta­ge curve to regulate the input current depending on the generator voltage (V/I cha­racteristic curve).
Every wind generator is designed to have an optimum working point for voltage and current, at different rotational speeds or wind speeds. This behavior is not linear.
The Windy Boy uses an approximation based on a simple ramp function. The function can be programmed by the user so that it comes close to the behavior of the wind generator being used and thus provides power adaptation.
Operating instructions WB11_17-11:FE4205 Page 31
Turbine operation SMA Technologie AG
The diagram shows the ramp function of a typical Windy Boy power/voltage curve. The feed-in AC power depending on the DC input voltage of the inverter is shown here. The adjustable parameters U
Start, UDCWindStart and UDCWindMax are
PV
used to adapt the power/voltage curve of the Windy Boy to the wind generator be­ing used.
Operating Mode: Turbine
Pac / Pac-max
0
50
100 150 200 250
300
350 400
Vdc V
The correct configuration of the parameters shown in the diagram is absolutely nec­essary to guarantee optimum operation with wind generators from different manufac­turers.
The basic parameters of a Windy Boy (factory settings) are shown in the following table.
Page 32 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Turbine operation
Name WB 1100 WB 1700 Unit Description
Defines the voltage at the
UpvStart
180 (150 ... 400)
180 (150 ... 400)
V
DC
moment when the Windy Boy is ready to perform a mains-grid synchronization.
Defines the voltage at the
UdcWind­Start
190 (1 ... 800)
190 (1 ... 800)
V
DC
moment when the Windy Boy is ready to begin feed­ing power into the mains grid.
Defines the voltage at the
UdcWind­Max
330 (1 ... 800)
330 (1 ... 800)
V
DC
moment when the Windy Boy begins feeding maxi­mum power into the mains grid.
Controls a delayed startup of the characteristic curve,
P-Wind­Ramp
200 (10 ... 2000)
280 (10 ... 2000)
W/sec
only after the Windy Boy has been switched on. This avoids the generator being suddenly presented with a heavy load.
T-Start
T-Stop
10 (5 ... 300)10(5 ... 300)
2 (1 ... 3600)2(1 ... 3600)
sec
sec
Start Timer Mains synchroni­zation.
Stop Timer Aborting the sup­ply of power and switching off.
The correct configuration of the parameters above is absolutely necessary to guaran­tee optimum operation with generators from different manufacturers. Preconditions for changing the operating parameters are described in chapter 5.4 "General setting example” (page 35).
To perform the configuration process, the DC input voltage must be greater than <UpvStart> and the Windy Boy must be connected to the mains grid.
Operating instructions WB11_17-11:FE4205 Page 33
Turbine operation SMA Technologie AG
5.3 Characteristic curve operation in "Turbine" opera-
ting mode
Please note: The linear characteristic curve of the Windy Boy only approxi­mates the actual characteristics of a real wind generator. Consult the manufac­turer of your wind generator for the typical characteristics of your generator before changing the characteristic curve parameters.
As soon as the DC input voltage defined in the parameter <UpvStart> is reached, the inverter begins a number of self tests, measurement processes and synchronizes with the mains grid. If the self tests are successfully completed, and the DC input voltage remains above the value defined in <UpvStart> for the time defined in <T-Start>, the inverter connects to the mains grid.
As soon as the DC input voltage reaches the value defined in <UdcWindStart>, the inverter begins feeding power into the mains grid. As you can see from the charac­teristic curve, the power fed into the mains grid rises with the DC input voltage.
As soon as the DC input voltage reaches the value defined in the parameter <Udc­WindMax>, the Windy Boy feeds the mains grid with the maximum possible power. If the input voltage continues to rise, the Windy Boy continues to feed the mains grid at maximum power.
The characteristic curve ends at the maximum permissible input voltage of the Windy Boy, which must never be exceeded.
If the wind strength is so low that the DC input voltage falls below <UpvStart>, then the inverter ceases feeding power into the mains grid for the period defined in <T­Stop>.
If the DC input voltage increases again, then the Windy Boy will again operate ac­cording to the characteristic curve.
If the DC input voltage falls below the internally calculated minimum operating value of <Umin>, then there is insufficient energy for the on-board electronics and the Win­dy Boy will switch off.
If the DC input voltage lies between <Umin> and <UpvStart> for the time defined by <T-Stop>, then the inverter will also switch off.
After the switch-off process, the whole process begins anew.
Only change the operating parameters when you know exactly what you are doing!
Page 34 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Turbine operation

5.4 General setting example

Please note that the following example only represents a starting point for operating with a wind generator.
• <UpvStart> is set to the lowest possible value: This achieves an early switch-on of the Windy Boy.
• <UdcWindStart> is set to the same value of <UpvStart>: This achieves an early mains grid feed-in. If the wind turbine does not properly start, or the inverter frequently switches on and off, it is recommended that you increase <UdcWindStart> in (e.g.) 10 V steps.
• <UdcWindMax> is initially set to approx. 10 % below the maximum MPP voltage of the Windy Boy: In this case the slope of the ramp function is relatively flat. The maximum output power is this only reached with a relatively high DC input voltage, which avoids "braking" of the wind generator through excessive power consumption. This set­ting is especially suitable in locations with little or weak wind. Once the properties of the wind generator are known, then the reduction of the <UdcWindMax> pa­rameter may be necessary, in order to extract the maximum power from the wind generator even at low DC input voltages (low wind speeds). The ramp function will then be steeper.
Contact the manufacturer of your wind generator for the typical properties of your generator (voltage/power characteristic).
• <T-Stop> is set to the maximum value: Here, the inverter remains connected to the mains grid, even at low DC input vol­tage levels, and "waits" for the next gust of wind. This delays an early switch-off of the inverter.
• <T-Start> is set to the minimum value: This achieves a reduction of the switch-on time (please observe the regulations of the energy supplier responsible).
Only change the operating parameters when you know exactly what you are doing!
Operating instructions WB11_17-11:FE4205 Page 35
Turbine operation SMA Technologie AG
Page 36 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Maintenance and care

6 Maintenance and care

Because the Windy Boy can be used outdoors in places that are difficult to access, the Windy Boy has been constructed for low maintenance. To guarantee safe oper­ation, it is usually adequate to check the device visually for damage approximately every two months. It should also be checked if the red LED is illuminated and, if nec­essary, remove the fault by referring to chapter 3.3.4 "Description of the operational status” (page 19).
In the interests of maximum yield, the operator should check, weekly if possible, un­der various conditions of wind, if the display of the Windy Boy indicates plausible normal operation (cf. chapter 3.3.4 "Description of the operational status” (page 19)). Naturally, this information can be obtained by using one of the commu­nication options.
Cleaning of the Windy Boy is only necessary when the heat dissipation is limited by dirty cooling fins or a dirty space between the Windy Boy and the wall. The dirt should be carefully removed with an appropriate soft brush or paintbrush.
If the LEDs are so dirty that they can no longer be seen, then they can be cleaned with a damp cloth. Solvents, abrasives or corrosive liquids must not be used!
Operating instructions WB11_17-11:FE4205 Page 37
Maintenance and care SMA Technologie AG
Page 38 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Expansions

7 Expansions

As with all inverters in the Sunny Boy family, the Windy Boy can also be expanded with a range of communication interfaces. This provides the operator with the possi­bility of requesting detailed operational data and error messages, for subsequent analysis on a PC using (e.g.) the free software available from SMA.
The data can currently be transferred in five different ways:
• using Powerline
• using a separate RS485 cable
• using a separate RS232 cable
• using a wireless link (Sunny Beam)
• using a USB-Service-Interface (USBPBS)
The wind turbine can be monitored by the Windy Boy in a number of different ways. SMA offers a range of products for this purpose, allowing you to install a tailor-made monitoring system for your system. If you require detailed information about the Win­dy Boy products, please request the Sunny Family catalogue or visit www.SMA.de. In the following sections the currently available communications options are schemati­cally described.

7.1 Sunny Data

Sunny Data is a PC program for direct monitoring of your system. The connection of the Sunny Boys or the Sunny Mini Centrals with the PC is described in the fol­lowing sections.
Operating instructions WB11_17-11:FE4205 Page 39
Expansions SMA Technologie AG

7.2 Sunny Data via Powerline

"Wireless" communication via the mains power line (up to 50 Windy Boys) Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back and
the PC must be equipped with an SWR-COM / USB-COM plug modem. The connec­tion of the PC using SWR-COM / USB-COM is described in the SWR-COM / USB­COM documentation.
SWR-COM
socket connector
SWR1100E
Bet r
Phot
ieb
ovolt
O pera
Pho
ai k-S
ti
to
on
t
vo
r
ing l ta
w i c
e
c
s tr
hs
i
Er
ng
elr
dschlu
ic i nvert
ht
e
r
s
Ear
e
s
r
t h
F a ul
t S t ö r u
ng Fail u
r
e
SWR1100E
B etrie
Pho t
ovolt
Operation
P
ai h ot
k-Stri
o vo
ng
lta
w
ic
e
c
s
t
hs
ri
Er
ng
elri
ds
i
c
n
c
hter
ve
h l uss
rt
Eart
er
h
F a u
lt St ö r u
ng Fai l ure
max. 50
SWR1100E
Be
trie
b
Pho
b
tovolt
Ope
P
ai
r
h
at
ot
k-Strin
io
o
n
vo lt
g
aic
w e
c
s t
hs
ri
Er
ng
elr
ds
ic i n
chl
hter ve
u
r ter
s
Ear
s t h F
a
ul
t
S
t örun g
Fai
l ure
PC with
Sunny Data
Powerline

7.3 Sunny Data over RS232

Communication via a cable (a single Windy Boy) Prerequisites: The Windy Boy must be equipped with an RS232 Piggy-Back, the con-
nection to the PC usually occurs directly over the COM1 or COM2 port of the PC. The installation of the RS232 cable is described in the installation instructions of the Windy Boy.
PC with
Sunny Data
S W
R
Betrieb
1 1
Photovoltaik-Stringwechselrichter
0
Operati
0
E
Photovoltaicstringinverter
on Erdschluss Earth F
ault
Störung Failure
RS232
Page 40 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Expansions

7.4 Sunny Data over RS485

Communication via a cable (up to 50 Windy Boys) Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the con-
nection with the PC usually occurs via an RS485/RS232 interface converter connect­ed to the COM1 or COM2 port or via an RS485/USB interface converter connected to the USB port. The installation of the RS232 cable is described in the installation instructions of the Windy Boy.
Interface­converter
(RS485/RS232)
i-7520
S W
R
Betrieb
1 1
Ph otovol
0
Operation
0 E
Photovolta
t aik-Str
in
gw i c
ec s tring
h
s
Erdschluss
elri
i
c
nverter
hte
r
E arth
F ault
Stö rung Fai lur
e
S W
R 1
1
Photovol
0
0 E
Ph
t aik-Str
otovol
i
ngwechselr t aic s
tri
n
g
i
i
chter nv er
t
e
r
max. 50
S W
Betrieb Operat
i
on Er ds chl
uss E arth
F
ault
Störun
g Failu
r
e
R
Betrieb
1 1
P h otovolt
0
Operation
0 E
Photovoltaic
a ik-Stri n
gw e chselri
s tring
Erd s
i
c
nverter
chluss
hte
r
Earth
F a u
lt Stö ru
n
g Fai lur
e
RS232
PC with
Sunny Data
RS485
Interface-
converter
(RS485/USB)
i-7561
S W
R
B
1
etrie
1
Ph
b
o
0
t
o
Ope
0
voltaik
E
Photovoltaic
ra tio
- String
n
w
echselric s tring
E rds
i
nverter
ch
h ter
lus
Earth
s F au
lt Störung Failure
S W
R 1
1
Photovoltaik-Stringwechselrichter
0
0 E
Photovoltaic
s
trin g
i nverter
max. 50
S W
Bet r ieb Operation
Erdschluss Earth
F ault
Störung Failure
R
Bet
1
ri
1
Ph
eb
o
0
t ov
Operat
0
olta
E
Ph
i
otovo
k-
i on
S t r in
lt
gw ai c
echsel s t r i
E
n
rds
g
r
ic i n
ch
h ver
ter
lu
te
s
Earth
s
r
F a
ult Störung Failure
USB
PC with
Sunny Data
RS485
Operating instructions WB11_17-11:FE4205 Page 41
Expansions SMA Technologie AG

7.5 Sunny Beam

Simple wireless system monitoring for up to 4 Windy Boys. Prerequisites: The Windy Boys must be equipped with a wireless Piggy-Back and a
Sunny Beam must be present at an appropriate distance. The installation of the wire­less Piggy-Back is described in the Sunny Beam user manual.
Sunny Beam
max. 4
S
W R
Be
1
t rieb
1
Photov
0
Ope
0
o
E
l
Photov
ta
rat
i k-Stringwec
ion
o
ltaic s tri
h selricht
Erds
n g i n
ch
v er
lus
e r
ter
E
s
art
h F aul
t
Störun
g F ailure
S
W R
Betri
1
1
Ph
eb
otov
0
O
0
ol
p
E
e
Pho
ta
rat
i
k
-S
i
t
on
ovol
t r
i n
t
g
a
wechs
i
c s tr i
Erdsc
n
e
g
lr
i
i
chter
nv
h
e
lu
rter
s
Eart
s h F aul
t S törun
g F ailure
S W
R
Be
1
t ri
1
Ph
eb
otov
0
O
0
ol
p
E
erati
Pho
ta i k
-
t
o
ovol
S t
n
r in
t
g
a
wechs i c s tr
i
E
n
e
rds
g
lr i
i
chter
nv
ch
e
lu
rter
ss
Eart
h F a
u l
t S t
ö ru ng
Failure

7.6 Sunny Data Control over Sunny Beam

Communication with a PC over Sunny Beam (up to 4 Windy Boys) Prerequisites: All 4 Windy Boys must be equipped with a wireless Piggy-Back and ac-
cessible to Sunny Beam for system monitoring. The Sunny Beam is connected to the PC via an USB cable. The installation of the wireless Piggy-Backs and the connection to the PC is described in the Sunny Beam user manual.
Sunny Beam
S W
R
Betrieb
1
1
Photovoltaik-Stringwechselrichter
0
Operation
0
E
Photovoltaic
s tring
Erdschluss
i
nverter
Earth
F ault
Störung Failure
S W
R
Betrieb
1 1
Photovoltaik-Stringwechsel
0
Operation
0 E
Photovolt
aic
s tring
E rd
richter
schluss
i nverter
Earth
F au l
t Störung Failure
S W R
Betrieb
1 1
Photovoltaik-Stringwechselrichter
0
Operation
0 E
Photovolt
aic s tring
E rdschluss
i nverter
Earth
F ault
Störung Failure
max. 4
USB
PC with
Sunny Data
Page 42 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Expansions

7.7 Sunny Boy Control Light

The simple data logger for PV systems with up to 10 Windy Boys. The connection be­tween the Sunny Boy Control Light and the Windy Boys occurs over Powerline.
Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back. The installation is described in detail in the Sunny Boy Control Light documentation.
Sunny Boy
Control Light
S
W R
Be
1
t rie
1
P h
b
ot
0
o
Ope
0
voltaik-Stri
E
P
rat
hotov
ion
ol
n
taic
gw
ec s t
h
rin
s
Erds
el
g
r i
i
c
n
c
h
v
h
t
erter
lu
e r
ss
Earth
F au
l t
St
ö r
ung F a
i
l
u
re
S
W R
B
1
etrie
1
Ph
b
otov
0
Ope
0
ol
E
Photovolta
ta
r at
i k-Stri
ion
n g
wech i c s t r
sel
i
E
n
rds
g
r i
i
ch
n
c
v
hlus
t
er
e
r
t
Earth
e
s
r
F au
l S t
ö
rung F ail
ure
max. 10
t
S W
R
B
1
etri
1
Ph
eb
otov
0
Oper
0
ol
E
Photovol
ta
at
i k-Stri
ion
n
t
g
a
wech i c s t
r
sel
i
E
n
rds
g
r
i
i
c
n
c
ht
v
hlus
er
e r
t
Earth
e
s
r
F aul
t
S
t ö
rung F ail
ure
PAC1273 W
Powerline

7.8 Sunny Boy Control

The simple data logger for systems with up to 50 Windy Boys. The connection be­tween the Sunny Boy Control and the Windy Boys can be achieved as follows:
Powerline - "Wireless" communication via the mains power line Prerequisites: All the Windy Boys must be equipped with a Powerline Piggy-Back.
Sunny Boy
Control
S W
R
Be
1
tr
1
Photovoltaik
i eb
0
Operation
0 E
Photovoltaic
- Str i ngw
e chselri
s tring
Erdschluss
i
ch
nverter
t e
r
Earth
F ault
St ö run
g Fail ure
S W
R
Betrieb
1 1
P h o
0
t o
Operation
0
vo lt
E
Photovoltaic
aik
-S tr in gw e
ch
s tring
se
Erdschluss
lri
i
ch
nverter
ter
E ar t h
S t öru Fail u
RS485 Communication via a cable Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the Sun-
ny Boy Control must be equipped with an RS485 Piggy-Back on the "COM1 - Sunny Boy" interface.
max. 50
F ault
n g re
S W
R
Be
1
trieb
1
Photovo
0
Operation
0
l
E
Photovoltaic
taik-Stringwechselrichter
s tring
Erds
i nverter
c hluss
Earth
F ault
Stör
u ng
Fai
l ur e
PA
C
1 2
7 3
W
Powerline
Sunny Boy
Control
S W
R
Betrieb
1 1
Photovoltaik-Stringwechselrichter
0
Operation
0 E
Photovoltaic
s tring
Erdschluss
i nverter
Earth F
ault
Störung Failure
S
W
R
Betrieb
1 1
Photovoltaik-Stringwechselrichter
0
Operation
0 E
Photovoltaic
s
tring
Erdschluss
i nverter
Earth
Störung Failure
max. 50
F ault
S W
R
Betrieb
1
1
Photovoltaik-Stringwechselrichter
0
Operation
0 E
Photovoltaic
s
tring
Erdschluss
i nverter
Earth
F ault
Störung Failure
PA
C 1
2 7 3
W
RS485
Operating instructions WB11_17-11:FE4205 Page 43
Expansions SMA Technologie AG

7.9 Sunny Boy Control Plus

The data logger for systems with up to 50 Windy Boys, an additional interface for connection to PCs or large displays and additional connection possibilities for digital and analog inputs and outputs.
Prerequisites: See Sunny Boy Control.

7.10 Sunny Data Control

This is a PC program for system monitoring and visualization on a PC for systems with a Sunny Boy Control.
Prerequisites: A system with a Sunny Boy Control, Sunny Boy Control Plus or Sunny Boy Control Light with a connection to a PC.
Connection also
possible via Modem
Visualization
S
W R
Betrieb
1 1
Ph
ot
0
ovoltaik-Strin
Operation
0
E
Photovoltaic
g
wech s tring
s
Erdschluss
elrichte i nverter
r
Ear
th F ault
Störung Failur
e
.
.
.
S W
R
Betrieb
1
1
Photovoltaik-Stringwechselrichter
0
Operation
0 E
Photovoltaic
s tring
Erdschluss
i nverter
Earth
F ault
Störung Failu re
S
W R
Betrieb
1 1
P hotovolt
0
Operation
0
E
Photovoltaic
aik-Str
i ngwechselrichter
s tring
Erdschluss
i nverter
Earth
F ault
Störung Failure
.
.
.
Data evaluation
with Excel
with Sunny Data
Control
Remote Desktop
Internet
presentation
with
SDC-Agent
Internet
presentation
with
SMA-Portal
The connection between the PC and the Sunny Boy Control can occur via modem if required. Large sys­tems with more than 50 Windy Boys can be monitored by coupling several Sunny Boy Controls together.
Page 44 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Expansions

7.11 Sunny WebBox

The Sunny WebBox is a versatile inexpensive platform for system visualization direct­ly on a PC or via the Internet using the Sunny Portal. The Sunny WebBox will be avail­able from the 2nd quarter of 2005.
PC via
Telephone
Connection
S W
R
Betr
1 1
Phot
i eb
0
o
O
0
v o
p
l
E
eration
P
t
ai
ho
k
-S t o
t
v
r
o
i
ngwechs l t
a
i
c
s
t
r
i
Erdsc
ng
e
lricht i n v
h
e
luss
e
r
r
t
E
e
ar
r
th F a ult
Störu
n
g F a
i
lu
re
Sunny
.
.
.
RS485 (
RS232*) Powerline*)
( (Radio*)
S
W R
B
1
et
rieb
1
P hoto
0
Operation
0
v o
E
l
P
t ai
h
otovoltaic
k
- St rin
gwec s tring
h
selrichter
Erdschluss
i
nv
e
rter
E a
r th F ault
Störung F a
il ure
External
Sensors
WebBox
Memory Card
Hub
LAN
LAN
LAN
Modem
Sunny
Portal
(Internet)
External
Display
PC
S W R
B
1
etr
1
Photovoltaik-Stringwechselrichter
ie
b
0
Oper
0
E
Photovoltaic
at
ion
s
tring
Erdschluss
i
nverter
Earth
F ault
Störung Failure
* Communication with Sunny WebBox via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
LAN

7.12 Sunny Portal

The Sunny Portal is a high performance interface from SMA for the monitoring and presentation of your sys­tem in the Internet. Details can be obtained from the Sunny Family catalog or directly under www.SUNNY­PORTAL.de.
Operating instructions WB11_17-11:FE4205 Page 45
Expansions SMA Technologie AG

7.13 Sunny TV

Sunny TV is an accessory for Windy Boy inverters, which displays the system data and the current performance on a monitor or video projector. It is suitable for the presentation of large systems in lobbies and entrance halls as well as in private ar­eas.
Video Projector TV Set
S
S
u
u
n
n
n
n
y
y
T
T
V
Sunny TV
Sunny TV
Pac = 7,450 W
S
W
R
B
1
etrieb
1
P
h
o
0
to
Op
0
v
olt
E
er
P
aik
h
a
o
ti
-
t
on
ov
S t r
o
i
n l t
gwe a i c
ch
s
tr
sel
i
Er
n
g
d
r i
sc
i
ch
nv
h
ter
e
luss
rt
Ea
e r
r t h
F aul t
St
ör un
g
F
a i lur
e
.
.
.
Pac = 7,450 W
Sunny TV
RS485 (
RS232*) Powerline*)
(
S
W
R
B
1
etrieb
1
Pho
0
t ovoltai
O
0
peration
E
Photovoltaic
k
-Stringw e chselrich
s tring
Erdschluss
i nverter
te r
Earth F
ault
Störung Failur e
(Radio*)
Video-Out
Configuration
with PC
V
P
P
a
a
c
c
=
=
7
7
,
,
4
4
5
5
0
0
W
W
PC Monitor
S
u
n
n
y
T
V
P
a
c
=
7
,
4
5
0
W
S u n
n y T
V
S W
R
Betrieb
1
1
P h ot
0
ovoltai
Operation
0 E
Ph ot
k
-
ovoltaic
S trin
gwec
s tring
h s
Erdschluss
e
lricht i nverte
e r
E a
r
r th
F ault
Störung Failur
e
* Communication with Sunny TV via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
Page 46 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Technical data

8 Technical data

8.1 Windy Boy 1100

8.1.1 DC connection data

Max. input open circuit voltage U Input voltage, MPP range U Nominal DC operating voltage U Max. input current I Max. input power P Recommended generator pow-
er at 5000 full-load hours / year Recommended generator pow-
er at 2500 full-load hours / year
DC 0 DC DC nom
DC max
DC max
P
turb max
P
turb max
All-pole isolator on the DC input side
Overvoltage protection Thermally monitored varistors DC voltage ripple U
SS
Personal protection Insulation monitoring (Riso > 1 MΩ) Operating consumption < 5 W (standby) Reverse polarity protection Short circuit diode
400 V 139 V ... 400 V DC 180 V 10 A 1210 W
800 W
900 W
DC plug connector
< 10 % of the input voltage
Operating instructions WB11_17-11:FE4205 Page 47
Technical data SMA Technologie AG

8.1.2 Grid connection data

Nominal output power P Peak output power P Nominal output current I Harmonic distortion of output
current
Operating range, grid voltage U
Operating range, grid frequen­cy
All-pole isolator grid side
ACnom ACmax
ACnom
THD
AC
f
AC
IAC
1000 W 1100 W
4.4 A
< 4 % (PAC > 0.5 P
198 ... 260 V AC (180 ... 265 V programmable)
49.8 ... 50.2 Hz / 59.8 ... 60.2 Hz (45.5 ... 54.5 Hz / 55.5 ... 64.5 Hz programmable)
Independent disconnection device (SMA grid guard)
Phase shift angle (relative to the fundamental
cos Phi 1
wave of the current) Overvoltage category III
Test voltage (50 Hz)
Test surge voltage
Own consumption in standby mode
1.4 kV (1 s routine testing / 5 s type testing)
4 kV (1.2/50 ms) (serial interface: 6 kV)
0.1 W
ACnom
)
Page 48 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Technical data

8.1.3 General data

For a detailed description of the device, see chapter 3 "Unit description” (page 13) of this manual.
General data
Protection type to DIN EN 60529 IP65 External temperature range -25° C to +60° C Dimensions (w x h x d) 322 mm x 320 mm x 180 mm Weight 21 kg (approx.)
External interfaces
Data transfer (mains cable) Optional Data transfer (data cable) Optional, RS232 / RS485 Data transfer (wireless) Optional
Efficiency
Max. efficiency η
max
The efficiency of the Windy Boy is heavily dependent on the DC input voltage. The lower the input voltage the higher is the efficiency.
> 93,0 %
94
93
92
91
90
89
88
87
Overall efficiency [%]
86
85
84
0
Operating instructions WB11_17-11:FE4205 Page 49
200 400300100 500 700600
Output power [W]
Windy Boy 1100
800 900 1000 1100
Technical data SMA Technologie AG

8.2 Windy Boy 1700

8.2.1 DC connection data

Max. input open circuit voltage U Input voltage, MPP range U Nominal DC operating voltage U Max. input current I Max. input power P Recommended generator power
at 5000 full-load hours / year Recommended generator power
at 2500 full-load hours / year
DC 0 DC DC nom
DC max
DC max
P
turb max
P
turb max
All-pole isolator on the DC input side
Overvoltage protection Thermally monitored varistors Voltage ripple U
PP
Personal protection Insulation monitoring (Riso > 1 MΩ) Operating consumption < 4 W Reverse polarity protection Short circuit diode
400 V 139 V ... 400 V DC 180 V
12.6 A 1850 W
1240 W
1395 W
DC plug connector
< 4 % of the input voltage
Page 50 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Technical data

8.2.2 Grid connection data

Nominal output power P Peak output power P Nominal output current I
ACnom ACmax
ACnom
1550 W 1700 W
6.5 A
Harmonic distortion of output cur­rent (at K
> 0.5 P
P
AC
Unom
< 2 %,
ACnom
)
Operating range, grid voltage V
THD
AC
< 4 %
IAC
198 ... 260 V AC (180 ... 265 V programmable)
49.8 ... 50.2 Hz / 59.8 ... 60.2 Hz
Operating range, grid frequency f
AC
(45.5 ... 54.5 Hz / 55.5 ... 64.5 Hz programmable)
All-pole isolator grid side
Independent disconnection device (SMA grid guard)
Phase shift angle (relative to the fundamental wave
cos ϕ 1
of the current) Overvoltage category III
Test voltage (50 Hz)
Test surge voltage
Own consumption in standby mode
1.4 kV (1 s routine testing / 5 s type testing)
4 kV (1.2/50 ms) (serial interface: 6 kV)
0.1 W
Operating instructions WB11_17-11:FE4205 Page 51
Technical data SMA Technologie AG

8.2.3 General data

For a detailed description of the device, see chapter 3 "Unit description” (page 13) of this manual.
General data
Protection type to DIN EN 60529 IP65 Dimensions (w x h x d) 434 mm x 295 mm x 214 mm Weight 25 kg (approx.)
External interfaces
Data transfer (mains cable) Optional Data transfer (separate data cable) Optional, RS232 / RS485 Data transfer (wireless) Optional
Efficiency
Max. efficiency η
max
The efficiency of the Windy Boy is heavily dependent on the DC input voltage. The lower the input voltage, the higher the efficiency.
94
93
92
91
90
89
88
87
Overall efficiency [%]
86
85
84
0
200 400 600
> 93,5 %
Windy Boy 1700
800 1000 1200
1400 1600
Output power [W]
Page 52 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG General information

9 General information

9.1 Measurement channels and messages

If your Windy Boy is equipped with a communication component, then numerous measurement channels and messages can be consulted. These can be useful for both performance improvement and for fault prevention.
The following abbreviations apply:
BFR: Operation control unit
SRR: Current control unit
E-total Total amount of feed-in energy Fac Grid frequency Faults Fault type display under "Disturbance" status h-total Total hours of mains supply feed-in operation Iac-Ist Grid current
Ipv DC current Netz-Ein Total number of mains supply switch-ons Pac Mains supply performance provided Riso Insulation resistance of the system to the mains supply connection Seriennummer Serial number of the Windy Boy Status Display of the current operational status Uac Grid voltage Upv-Ist DC input voltage Upv-Soll Nominal DC voltage Zac Mains supply impedance
The measurement channels provide information in German (e.g."Fehler“), or in English (e.g. "Error“), depending on which software you are using (Sunny Data or Sunny Data Control).
Operating instructions WB11_17-11:FE4205 Page 53
General information SMA Technologie AG

9.1.1 Status messages

The Windy Boy produces a range of status messages, depending on the mode in which it is currently operating. The status messages can vary, depending on the type of communication system you are using.
Overtemperature in inverter ("WR"). The Windy Boy reduces its performance to avoid overheating the device. To avoid unneces-
Derating
Mpp
Island Mode
grid mon.
Offset Offset compensation of the measurement electronics
disturb.
Stop
Turbine Mode
V-Const
waiting The switch-on conditions are not (yet) satisfied. Zuschalt Connection to mains grid.
sary yield losses, the configuration and string size should be checked. Check if the Windy Boy can be located in a better posi­tion with better ventilation, thus providing better heat dissipation.
The Windy Boy is operating in MPP mode. The Windy Boy takes the highest possible performance from the PV generator. MPP is the standard display when operating with normal sunshine (PV operation only).
The Windy Boy is in Island Mode. This mode is specially con­ceived for operation in a stand alone power system with a Sunny Island as network controller. More information about this topic can be obtained from the Sunny Island operating manual under the category "Droop Mode".
Testing the mains supply status (mains impedance), relay tests etc. This message appears during the startup phase, before the Windy Boy is connected to the mains supply. This message mainly ap­pears when there is little or no wind.
Fault (see table "Fault messages") This fault occurs for reasons of safety and prevents the Windy Boy from connecting to the mains network. This mode can also be man­ually set.
Interruption of operation after a fault. This status can also be man­ually set.
Default setting for Windy Boy inverters. The input voltage is con­verted according to the V/I function U
WindMax. See chapter 5 "Turbine operation” (page 31).
C
Start, UDCStart and U
PV
Constant current operation (the input voltage is predefined. The Windy Boy operates in neither MPP mode nor Turbine mode). In some cases, this can be set as the operational mode.
D-
Page 54 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG General information

9.1.2 Windy Boy operating parameters

Unauthorized changes to the operating parameters may result in:
• Injury or accidents as a result of changing the internal safety routines in the Windy Boy,
• Voiding the Windy Boy's operating approval certificate,
• Voiding the Windy Boy's guarantee
Never change the parameters of your Windy Boy without explicit authorization and instructions.
Name Unit
Betriebsart / Operating Mode
Default GER/ENS Used for setting the country specific
dFac-MAX Hz/s 0.005 ... 4.0 0.25 Maximum "Mains frequency change"
dZac-MAX mOhm 0 ... 20000 350 Maximum "Mains impedance change"
E_Total kWh 0 ... 200000 Total energy yield (E_Total) and total
h_Total h 0 ... 200000
Fac-delta- Hz 0 ... 4.5 0.19 Maximum frequency, above (Fac-
Fac-delta+ Hz 0 ... 4.5 0.19
Val ue r ang e
(WB 1100 /
WB 1700)
MPP UKonst Stop Turbine M od e
Factory settings
(WB 1100 /
WB 1700)
Turbine Operating mode of the Windy Boy
MPP: Maximum Power Point UKonst: Constant voltage mode (Desired voltage is defined in "Usoll­Kons t") Stop: Disconnection from mains network, no operation Turbine: Operating mode for wind turbines, the input voltage is converted according to the V/I function defined by U
U
DC
information.
before the mains monitoring system disconnects the device from the mains supply.
before the mains monitoring system disconnects the device from the mains supply.
hours of operation (h_Total) for the inverter. This change may be necessary when you exchange your Windy Boy and want to use the data from the old device.
Delta+) and below (Fac-Delta-) the mains frequency of 50 Hz, before the mains monitoring system disconnects the device from the mains supply.
Description
Start, UDCWindStart and
PV
WindMax.
Operating instructions WB11_17-11:FE4205 Page 55
General information SMA Technologie AG
Name Unit
Val ue r ang e
(WB 1100 /
WB 1700)
I-NiTest mA 0 ... 8000 8000 Activation (8000) and deactivation (0)
Factory settings
(WB 1100 /
WB 1700)
Description
of the automatic leakage current measurement. This parameter only functions when the Windy Boy is deactivated (disconnected on the AC side) or in "Stop" mode.
Inst.-Code Parameters for mains grid monitoring
can only be changed after entering the "SMA grid guard" password.
KI-Wind-Reg 0 ... 0,25 0,005 Control speed (only possible in Turbine
mode!)
KP-Wind-Reg 0 ... 0,25 0,117 Control speed (only possible in Turbine
mode!)
P-Wind-Ramp W/s 10 ... 2000 200/280 Slow startup during mains-grid
connection (only possible in Turbine mode!)
Speicher-­funktion / Memory function
Default, parameter, Reset Betriebsdaten, Reset Fehler
none Default parameter: Returns all
parameter values to the factory setting. Reset Betriebsdaten: Returns all user level parameter values to the factory setting. Reset Fehler: Resets a permanent fault.
Speicher(n) / Store / Storage
Permanent volatile
Permanent Permanent: Modified parameters are
stored in the EEPROM and can be used even when the Windy Boy has been restarted. Volatile: Prevents the parameters from being stored in the EEPROM, the parameters are stored until the next restart.
T-Start sec 5 ... 300 10 Start timer for mains-grid
synchronization. (only possible in Turbine m ode! )
T-Stop sec 1 ... 3600 2 Stop timer for stopping operation and
switching off. (only possible in Turbine mode!)
Uac-Min / Vac-Min
Uac-Max / Vac-Max
WindMax V 1 ... 800 330 UDCWindMax represents the highest
U
DC
V 180 ... 300 198 Lower (Uac-Min) and upper (Uac-Max)
V 180 ... 300 260
limits of the acceptable AC voltage (self contained power system recognition).
point of the function (please read more about this topic in chapter 5 "Turbine operation” (page 31)). (only possible in Turbine mode!)
WindStart V 1 ... 800 190 UDCWindStart represents the lowest
U
DC
point of the function (please read more about this topic in chapter 5 "Turbine operation” (page 31)). (only possible in Turbine mode!)
Page 56 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG General information
Name Unit
Usoll-Konst / Vconst­Setpoint
U
Start V 150 ... 400 180 UPVStart is the parameter defining the
PV
V 150 ... 430 330 ... 410 Desired DC voltage for constant
Val ue r ang e
(WB 1100 /
WB 1700)
Factory settings
(WB 1100 /
WB 1700)
Description
operational voltage. These parameters are only important when the "Betriebsart" parameter is set to U­Kons t.
voltage at which the Windy Boy is capable of connecting to the system. 180 V is the recommended voltage for the Windy Boy 1100 and the Windy Boy 1700. Reducing this voltage parameter can lead to numerous unnecessary connection attempts. Increasing this voltage parameter can lead to energy losses since the Windy Boy does not immediately connect to the system.
The following parameters are displayed in the parameter list but cannot be modified:
Name Unit Value range
Plimit W 1100 / 1700 Upper limit for AC output power
SMA-SN Serial number of the Windy Boy
Software-BFR Firmware version of the operation
Software-SRR Firmware version of the current control
(WB1100/
1700)
Factory settings
(WB1100/
170 0)
Description
control unit (BFR)
unit (SRR)
Operating instructions WB11_17-11:FE4205 Page 57
General information SMA Technologie AG

9.2 Fault messages

If a fault develops, the Windy Boy generates a message, which is dependent on the operational mode and the type of fault.
Fault code Description
Bfr-Srr
NUW-FAC
NUW-UAC
NUW-ZAC
dZac-Bfr dZac-Srr
EEPROM
EEPROM dBh
EeRestore
Fac-Bfr Fac-Srr
Internal measurement comparison fault: the Windy Boy found too large a difference between values provided by the BFR and SRR. Contact SMA.
The changes in mains impedance exceed the permissible range ("Bfr" or "Srr" is an internal message that has no meaning for the us­er).
The Windy Boy disconnects from the mains grid or stand-alone grid, to avoid potential damage. If possible, check the mains impedance and check how often major deviations occur. If repeated variations occur and this is causing "dZac-Bfr" or "dZac-Srr" faults, ask the elec­tricity provider if they agree to a modification of the operating pa­rameters. Discuss the proposed parameters with the SMA hotline.
A data transfer fault occurred during reading or writing of data from the EEPROM, the data is not relevant for safe operation - this fault has no effect on performance.
Data EEPROM is defective, the device has switched itself off because the loss of important functions has disabled the Windy Boy. Contact SMA.
One of the duplicate data sets in the EEPROM is defective and has been reconstructed without loss of data.
The mains frequency has exceeded the permissible range ("Bfr" or "Srr" is an internal message that has no meaning for the user). The Windy Boy disconnects from the mains grid or stand-alone grid, to avoid potential damage. Check the mains frequency and mains con­nections on the Windy Boy. If the mains frequency lies outside the permissible range because of local conditions, ask the electricity pro­vider if they agree to a modification of the operating parameters.
If the mains frequency lies within an acceptable range and "Fac-Bfr" or "Fac-Srr" faults are still being displayed, please contact the SMA hotline.
Overcurrent on the AC side. This fault code is displayed if the current
Imax
in the AC network is larger than specified. Check your system config­uration and the mains supply conditions.
Page 58 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG General information
Fault code Description
K1-Schliess / K1-Close
K1-Trenn /
Fault during relay test. Please contact SMA if this fault occurs often
or repeatedly. K1-Open NUW-Mes Measurement difference between BFR and SRR: Fac, Uac or Zac.
Offset
Rechner / NuW-Time­out
Fault in the acquisition of measurement data. Contact SMA if this
fault occurs frequently.
Functional fault in one of the two microcontrollers. Please contact
SMA if this fault occurs often or repeatedly.
A grounding fault exists or one of the thermally monitored varistors
Riso
on the DC input is defective as a result of overvoltage. Consult
trained electrical personnel to correct the fault. You can find Instruc-
tions on how to change the varistors in the "Installation manual".
ROM
The Windy Boy firmware is faulty. Contact SMA if this fault occurs
frequently.
The mains voltage has exceeded the permissible range ("Bfr" or "Srr"
is an internal message that has no meaning for the user). The Uac
fault can have the following causes:
• Mains supply disconnected (circuit breaker or fuse)
• Broken AC cable or
Uac-Bfr / Vac-Bfr
Uac-Srr / Vac-Srr
• AC cable has a high internal resistance
For reasons of safety, the Windy Boy disconnects itself from the
mains network. Check the mains voltage and mains connections on
the Windy Boy. If the mains voltage lies outside the acceptable
range because of local conditions, ask the electricity provider if the
voltage can be adjusted at the feed-in point or if they agree to chang-
es in the values of the monitored operational limits.
If the mains voltage lies within an acceptable range and "Uac-Bfr" or
"Uac-Srr" faults are still being displayed, please contact the SMA
hotline.
Over voltage on DC input
UpvMax / Vpv-Max
Immediately disconnect the DC input of the Windy Boy. Otherwise
the Windy Boy could be severely damaged! Check the configuration
of your system and measure the DC voltage before reconnecting the
Windy Boy to the DC voltage. Watchdog Fault in the program code flow monitoring.
Operating instructions WB11_17-11:FE4205 Page 59
General information SMA Technologie AG
Fault code Description
The mains impedance has exceeded the permissible range ("Bfr“ or
"Srr“ is an internal message that has no meaning for the user). The
Windy Boy disconnects from the mains grid or stand-alone grid, to
avoid potential damage. The impedance is calculated from the mains
supply impedance and the impedance of the mains connection cable Zac-Bfr/
Zac-Srr
(AC cable) of the Windy Boy.
Check the mains voltage and mains connections on the Windy Boy.
Use a mains connection cable with an adequate cross section (= low
impedance), and observe the advice to this effect in the installation
instructions in chapter 4.3. If the mains impedance is still too high,
then ask the electricity provider if the characteristics of the mains sup-
ply at the feed-in point can be altered.
Page 60 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG General information

9.3 Declaration of conformity (CE)

CE Declaration of Conformity
for utility interactive inverters
Product: Windy Boy Type: WB 700, WB 1100, WB 1700, WB 2500, WB 2800i,
We declare that the above specified devices are compliant with the regulations of the European Community, in terms of the design and the version fabricated by SMA. This especially applies for the EMC Regulation defined in 89/336/EWG and the low voltage regulation defined in 73/23/EWG.
The devices are compliant with the following standards:
EMC: Emission: DIN EN 61000-6-3: 2002-08
Utility Interference: DIN EN 61000-3-3: 2002-05
Immunity: DIN EN 61000-6-1: 2002-08
Safety: DIN EN 50178: 1998-04 Semiconductor-Converter: DIN EN 60146-1-1: 1994-03
The above mentioned devices are therefore marked with a CE sign.
WB 3000
DIN EN 61000-6-4: 2002-08 DIN EN 55022: 2003-09, class B
DIN EN 61000-3-2: 2001-12
DIN EN 61000-6-2: 2002-08
Niestetal, 2nd of January 2005
SMA Technologie AG
i.V. Frank Greizer
(Head of Development Department Solar Technology)
SMA Technologie AG
Hannoversche Straße 1-5 34266 Niestetal Tel. +49 561 9522–0 Fax +49 561 9522–100 www.SMA.de info@SMA.de
WB-K16A-CE-12:BE2905
Operating instructions WB11_17-11:FE4205 Page 61
General information SMA Technologie AG

9.4 Import certificate

The Windy Boy string inverter is equipped with the "SMA grid guard" independent disconnection device and it is covered by the industrial trade association "SMA grid guard" import certificate.
Page 62 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Stand-alone systems

10 Stand-alone systems

The Windy Boy is suitable for use in stand-alone systems based on the Sunny Island. The Windy Boy requires extra settings for this to ensure optimum operation and also to achieve deactivation of the standard mains grid monitoring settings. Please obtain all further relevant information from the Sunny Island manuals.
Sunny Island
4248
or
Sunny Boy
Windy Boy
AC
bus
Consumers
Generator
Public Utility
Mini CHP
Operating instructions WB11_17-11:FE4205 Page 63
Stand-alone systems SMA Technologie AG
Page 64 WB11_17-11:FE4205 Operating instructions
SMA Technologie AG Contact

11 Contact

If you have any questions or technical problems concerning the Windy Boy, please contact our service hotline. Please have the following information available when you contact SMA:
• Inverter type
• Connected wind turbine
• Communication
• Serial number of the Windy Boy
Address:
SMA Technologie AG Hannoversche Strasse 1 - 5 34266 Niestetal Germany
Tel.:+49 561 95 22 - 499 Fax:+49 561 95 22 - 4699 hotline@SMA.de www.SMA.de
Operating instructions WB11_17-11:FE4205 Page 65
Contact SMA Technologie AG
Page 66 WB11_17-11:FE4205 Operating instructions
Sales SMA Solar Technology
www.SMA.de
Rosendahl Industrievertretungen Adolf-Dembach-Strasse 1 47829 Krefeld Germany Tel. +49 2151 45678 90 Fax +49 2151 45678 99
SMA Technologie AG
SMA Solar Technology China
International Metro Center, Building A, City Square No. Jia 3, Shilipu Road, Changyang District 100025 Beijing, P.R. China Tel. +86 10 65 58 78 15 www.SMA-CHINA.com
SMA America, Inc.
12438 Loma Rica Drive, Unit C Grass Valley, CA 95945, USA Tel. +1 530 273 4895 www.SMA-AMERICA.com
SMA Spain
Rosendahl Técnica Energética, S.L. Decages S.A. Balmes, 297, 1er, 2a 08006 Barcelona, Spain Freecall +800 SUNNYBOY
Freecall +800 78669269
SMA Italy
Rosendahl Tecnologie Energetiche S.r.I. Via Lorenzo Valla, 16 20141 Milano, Italy Freecall +800 SUNNYBOY
Freecall +800 78669269
Innovation in Systems Technology
Seite 68 WB11-17-11:FD2805 Betriebsanleitung
for the Success of Photovoltaics
Loading...