SMA WB 5000 User Manual

Windy Boy 5000 Windy Boy 6000 Inverter for Wind Energy Power Plants
Operating Instructions Version 1.0 WB50_60-11:FE4105
TBE-WB50-60
SMA Technologie AG Revision Histroy
Revision History
WB50_60-11:FE4105 First issue Welzel
Operating Instructions WB50_60-11:FE4105 Page 3
SMA Technologie AG
Page 4 WB50_60-11:FE4105 Operating Instructions
SMA Technologie AG Explanation of Symbols used in this Document
Explanation of Symbols used in this Document
This symbol indicates information that is essential for a trouble-free and safe operation of the product. Please read these sections care­fully in order to avoid any damages of the equipment and for op­timal personal protection.
This symbol indicates information that is required for the optimal operation of the product. Read these sections carefully in order to ensure an optimal ope­ration of the product and all its features.
This symbol indicates an example.
Operating Instructions WB50_60-11:FE4105 Page 5
Legal Restrictions SMA Technologie AG
Liability exclusion
The information contained in this documentation are the property of SMA Technologie AG. No part of this documentation may be published without written permission from SMA Technologie AG. A reproduction for internal purposes for the evaluation of the product or an appropriate application is permitted and does not require authorization.
All information are based on our "General Terms and Conditions of Delivery of SMA Technologie AG”. The content of this documentation is reviewed continuously and adjusted, if necessary. SMA Technologie AG provides this documentation without exclusion of deviations and without warranty of completeness. You will find the current version on the Internet at www.SMA.de or can obtain it via the usual sales channels. Warranty or liability claims for all kinds are excluded in case of damages due to:
• Inappropriate use of the product
• Operation of the product in an improper environment
• Operation of the product without considering the relevant safety regulations
• Non-fulfillment of the warnings or safety instructions described in the documentation for the product
• Operation of the product under faulty conditions concerning security and protection
• Arbitrary changing of the product or the provided software
• Failure of the product due to interference of connected or contiguous devices out of legal limit values
• Disasters and force majeure
Software Licensing
The use of the provided software by SMA Technologie AG is subject to the following conditions: The software may be reproduced for internal purposes and installed on any number of computers. Provided source codes can be changed and adjusted on the company’s own authority according to the internal purpose. Driver may be ported to other operating systems as well. No part of the source codes may be published without written permission of SMA Technologie AG. Sublicensing of the software is not acceptable.
Liability limitation: SMA Technologie AG disclaims liability for any direct or indirect consequential damages arising from the use of the software produced by SMA Technologie AG. The same applies for the provision and/or non-provision of support.
Provided software not produced by SMA Technologie AG is subject to the respective licensing and liability agreements of the manufacturer.
Trademarks
All brand and product names used herein are trademarks or registered trademarks of their respective holders, although they may not be specifically designated as such.
SMA Technologie AG Hannoversche Strasse 1-5 34266 Niestetal Germany Tel. (+49) 5 61 95 22 – 0 Fax (+49) 5 61 95 22 – 100
www.SMA.de
E-Mail: info@SMA.de
© 2005 SMA Technologie AG. All rights reserved.
Page 6 WB50_60-11:FE4105 Operating Instructions
SMA Technologie AG Table of Contents
Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Appropriate usage of the Windy Boy 5000 / 6000. . . . . . . . .13
3.2 Device construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.3.1 Normal operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.3.2 Critical, faulty operation . . . . . . . . . . . . . . . . . . . . . . . . .18
3.3.3 Non-critical, faulty operation . . . . . . . . . . . . . . . . . . . . . .18
3.3.4 Description of the operational status . . . . . . . . . . . . . . . .19
3.4 Messages in the optional display . . . . . . . . . . . . . . . . . . . . . .25
4 Setting the display language . . . . . . . . . . . . . . . . . . 29
5 Maintenance and care. . . . . . . . . . . . . . . . . . . . . . . 31
6 Turbine operation . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
6.2 Characteristic curve function. . . . . . . . . . . . . . . . . . . . . . . . . .33
6.3 Characteristic curve operation in "Turbine" operating mode . . .36
6.4 General setting example . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
7 Maintenance and care. . . . . . . . . . . . . . . . . . . . . . . 39
8 Expansions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.1 Sunny Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
8.2 Sunny Data via Powerline . . . . . . . . . . . . . . . . . . . . . . . . . . .42
8.3 Sunny Data over RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
8.4 Sunny Data over RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
8.5 Sunny Beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
8.6 Sunny Data Control over Sunny Beam . . . . . . . . . . . . . . . . . .44
8.7 Sunny Boy Control Light. . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
8.8 Sunny Boy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
8.9 Sunny Boy Control Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
8.10 Sunny Data Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
8.11 Sunny WebBox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
8.12 Sunny Portal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
8.13 Sunny TV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
9 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
9.1 Windy Boy 5000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
9.1.1 DC connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
9.1.2 Grid connection data . . . . . . . . . . . . . . . . . . . . . . . . . . .50
9.1.3 General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
9.2 Windy Boy 6000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Operating Instructions WB50_60-11:FE4105 Page 7
Table of Contents SMA Technologie AG
9.2.1 DC connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
9.2.2 Grid connection data . . . . . . . . . . . . . . . . . . . . . . . . . . .53
9.2.3 General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
10 General information. . . . . . . . . . . . . . . . . . . . . . . . . 55
10.1 Measurement channels and messages. . . . . . . . . . . . . . . . . . .55
10.1.1 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.1.2 Windy Boy 5000 / 6000 Operating parameters . . . . . . .57
10.2 Fault messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
10.3 Declaration of conformity (CE) . . . . . . . . . . . . . . . . . . . . . . .63
10.4 Import certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
11 Stand-alone systems. . . . . . . . . . . . . . . . . . . . . . . . . 65
12 Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Page 8 WB50_60-11:FE4105 Operating Instructions
SMA Technology AG Introduction

1 Introduction

The installation of the Windy Boy 5000 / 6000 may only be done by qualified technicians. The installer must be approved by the utility company. Please read the installation guide carefully before you begin with the installation. The installation of utility interactive power sources must be compliant with all applicable regulations of the utility company and with all applicable regulations and standards.
The Windy Boy inverters make it possible to operate small wind turbines as grid­connected systems. Grid-connected means that the energy generated by the wind turbine can be fed directly into an existing house power grid, a stand-alone power system, or the mains supply.
To this end, the Windy Boy converts the direct current (DC) from permanent-magnet wind turbines, which vary with speed, into grid-compatible alternating current (AC). The Windy Boy requires the constant presence of mains supply voltage!
The Windy Boy 5000 / 6000 complies with all the VDEW (Verband der Elektrizitätswirtschaft – German Electricity Industry Association) regulations for the connection and parallel operation of electrical power units to the low-voltage grid of the electricity supply company. This also encompasses the regulations of the German Professional Association for Precision Engineering and Electro technology relating to "Automatic switching of electrical power units" (SMA grid guard) and/or DIN VDE
0126. In addition to this, the Windy Boy 5000 / 6000 conforms to the electromagnetic tolerance regulations and the low-voltage regulations of the relevant combined European norms, as confirmed in the CE conformity declaration (10.3 "Declaration of conformity (CE)” (page 63)).
The documentation provided here covers all such topics that are of interest when operating Windy Boy 5000 / 6000 inverters. In addition to explanations of the operational methods of the device and detailed technical data, advice as to data capture and analysis is also provided.
Information relating to the installation and commission of the Windy Boy 5000 / 6000 should be taken from the installation instructions delivered with the device. The Windy Boy 5000 / 6000 inverter has a special operational mode for wind turbines which allows performance adjustment to the characteristic curve of the generator. In this way you will obtain maximum yields from your wind turbine.
A wide input voltage range, high efficiency and a freely configurable output characteristic curve with the highest level of reliability are only some of the properties that are useful for your grid-connected system, or in a stand-alone system when combined with the Sunny Island.
Operating instructions WB50_60-11:FE4105 Page 9
Introduction SMA Technology AG
The Windy Boy 5000 / 6000 is compatible with all SMA communications products (RS232, RS485, Powerline, Wireless, Display), providing numerous possibilities for diagnosis, data visualization and remote maintenance of your small wind turbine system.
For stand-alone systems, that use the Sunny Island: Please configure your Windy Boy 5000 / 6000 according to the specifications in the Sunny Island manual.
Configuration of the V/I properties of the Windy Boy 5000 / 6000 with respect to your wind turbine: the parameters U
WindMax must be configured to guarantee optimum operation of your
U
DC
Start, UDCWindStart and
PV
Windy Boy 5000 / 6000 with your wind turbine. The configuration process is described in chapter 6 "Turbine operation” (page 33).
Apart from the parameter settings, the Windy Boy 5000 / 6000 is identical to the Sunny Mini Central photovoltaic inverter and can therefore also be used as a PV inverter. Please download the Sunny Mini Central manual from www.SMA.de, and if you are planning to use the Windy Boy 5000 / 6000 in a photovoltaic system please contact us on the SMA hotline.
Page 10 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Safety information

2 Safety information

Opening of the device, and any
•electrical installation,
Windy
Boy
P a
c U p
v
9
0
3 W
3
3
N
0
et
z
V
w
e c h
G
se
r
i
l
d
r i
c t ie
h
t
d
er
in
f
ver
ü r
W
te
r
in
f
d
o
e r w
n
e
i
rg n d
i
ea t u
n r b
la
i n
g
e
e
s
n
The temperature of individual parts of the case of the Windy Boy 5000 / 6000 - in particular the temperature of the heatsink - can reach 60 °C in normal operation. Touching could result in burns!
The Windy Boy 5000 / 6000 contains an independent mains disconnection device, the "SMA grid guard". It ensures that the Windy Boy 5000 / 6000 complies with the VDEW (Verband der Elektrizitätswirtschaft – German Electricity Industry Association) regulations for the connection and parallel operation of electrical power units to the low-voltage grid of the electricity supply company and with DIN VDE 0126 (4.99), which forms a part of these regulations.
•repair or
•modification
of the Windy Boy 5000 / 6000 may only be performed by qualified electrical personnel. Even when no external voltage is present, the device can still contain high voltages and the danger of electrical shock.
Operating instructions WB50_60-11:FE4105 Page 11
Safety information SMA Technology AG
Page 12 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description

3 Unit description

3.1 Appropriate usage of the Windy Boy 5000 / 6000

The Windy Boy 5000 / 6000 is designed for the conversion of DC voltage from a wind turbine (permanent magnet generator) into AC voltage for feeding into the public mains supply. The technical data are described in more detail in chapter 9 "Technical data” (page 49).
Net
z w
e c
h s e
l r i c
G
h
r
t
i
e
d
r
t
f
i
ü
e
r
d
W i n
i
ve
n d
r
e
te
n
r
e
f
r
o
g
r
i e
w
a
i
n
n
l
d
a
g t u
e
r
n b i
n e
Overvoltage Protection
Control unit
Control unit
s
Windy
Boy
P a
c
Upv
903W
3
30V
Net z
w e c h
G
s
r
e
i
l
d
r i
c t i
h e
t d
e
r
i
n
f
ve
ü r
r
W te r
i n
f
d
o
e
r
n
w
e
i
r
n
g
d
i e
t
a
u
n r b
l
a
i n
g
e
e
s
n
Wind Generator
Converter
Rectifier
Windy Boy
Public Mains Grid
Many wind turbine manufacturers offer an extra over-voltage protection module. These components prevent the destruction of the downstream Windy Boy in the case of overvoltage.
Overvoltage can occur under the following conditions:
• High turbine rotation speeds under strong wind conditions
• An increase in turbine rotation speed caused by load-shedding when the Windy Boy is disconnected from the mains supply e.g. in the case of mains interference or power outage.
The overvoltage protection system has the following tasks:
• When a pre-defined voltage is reached, the Windy Boy is disconnected from the generator and a short-circuit slows the generator and/or brings it to a standstill.
• Some devices reduce the turbine rotation speed, and thus the generator output voltage, by switching in a resistor assembly (Dumpload). The electrical energy generated by the turbine is then converted to heat.
Operating instructions WB50_60-11:FE4105 Page 13
Unit description SMA Technology AG
In grid-connected systems, we recommend the use of one of the electronic protection mechanisms described here. Please note that overvoltage on the Windy Boy can lead to destruction of the device. In addition to this, you lose the right to all warranty claims - even if the maximum input voltage of the Windy Boy is only exceeded for a short time.
The electronic protection systems described here are preferable to mechanical solutions (pitch control, "turning out of the wind") in every case.
Any other use of the Windy Boy 5000 / 6000 leads to loss of the right to all warranty claims.
In case of overvoltage, immediately disconnect the DC input of the Windy Boy 5000 / 6000! The presence of excessive input voltage can lead to irreparable damage!
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it automatically disconnects from the mains supply and no longer feeds power into the grid. When the Windy Boy 5000 / 6000 is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy 5000 / 6000!
Page 14 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description

3.2 Device construction

An attractive, functional design is one of the major design objectives of the entire Windy Boy 5000 / 6000 product range. In its basic configuration, the Windy Boy 5000 / 6000 has the proven status display consisting of three LEDs. An extra display can be provided already installed or can be retrofitted.
As long as it is installed and commissioned according to the technical specifications, the Windy Boy 5000 / 6000 can be operated without any further modification or configuration. The device parameters can however be modified, if required.
+
Windy Boy 5000 / 6000 Enclosure IP54 (outside installation possible)
DC - input with 4 x 2 DC connectors
+
+
+
Characte-
ristic wind
curve
Overvoltage
protection:
Thermally monitored
varistors
Bridge
Optional
display
(IP65)
Optional
communi-
cations
interface:
RS232 RS485
Powerline
Transformer
OptiCool
SMA
Grid Guard
R
An extra communications interface is required for ideal adaptation of the Windy Boy 5000 / 6000 to suit the particular wind turbine being used, and this can also be used for reporting operation data. For further details, please refer to chapter 8 "Expansions” (page 41).
L
N
AC - output with terminals
PE
Operating instructions WB50_60-11:FE4105 Page 15
Unit description SMA Technology AG
All DC connections and connections for the mains supply, as well as any optional communications connections are to be found on the underside of the Windy Boy 5000 / 6000. Each of the + and - DC connections are internally connected in parallel within the Windy Boy 5000 / 6000.
Plug connector for DC+
Plug connector for DC-
Cable opening for the mains supply connection
Opening for optional communication via RS232, RS485 or radio (PG16)
Page 16 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description

3.3 Operating modes

The operational status is displayed using three light-emitting diodes (LEDs) in the cover of the Windy Boy 5000 / 6000. To allow the device to signal its operational status via the integrated LEDs, the Windy Boy 5000 / 6000 must be connected to the DC side of the system. There must be enough wind energy present, so that the Windy Boy 5000 / 6000 has adequate DC voltage.
Windy
Boy
Pac 903W Upv 330V
Netzwechselrichter für Windenergieanlagen Grid tied inverter for wind turbines
Especially in the first year of operation, the operator of the system should check this display under different wind speeds.
A complete description of the possible displays can be found in chapter 3.3.4 "Description of the operational status” (page 19). These can be split into three categories:

3.3.1 Normal operation

As long as the green control LED is on, or blinking, the Windy Boy 5000 / 6000 is operating normally. The simultaneous illumination of all three LEDs is also an indication of normal operation ("Initialization"). All other displays are a sign of abnormal operation.
Operating instructions WB50_60-11:FE4105 Page 17
Unit description SMA Technology AG

3.3.2 Critical, faulty operation

A comprehensive safety concept limits the number of critical conditions that can occur to a single situation:
Input voltage exceeds the permitted value
This is indicated by the following blink-code on the yellow LED:
The yellow LED illuminates 4 times
LED on
LED off
3s 1s1s 1s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The presence of excessive input voltage can lead to irreparable damage! Immediately disconnect the DC input of the Windy Boy 5000 / 6000.
12
34
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it automatically disconnects from the mains supply and no longer feeds power into the grid. When the Windy Boy 5000 / 6000 is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy 5000 / 6000!

3.3.3 Non-critical, faulty operation

All other fault codes indicate some form of faulty operation, which are not usually dangerous to people or equipment, but which should nevertheless be investigated and corrected.
Despite all precautions, it is possible that other faults may occur that cannot be displayed (e.g. failure of the status display). In order to recognize such faults, the operator of the system should use the explanations in chapter 3.3.4 "Description of the operational status” (page 19) to check the plausibility of the displayed status. Further detailed diagnoses are possible using the communications options detailed in chapter 8 "Expansions” (page 41).
Page 18 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description

3.3.4 Description of the operational status

No (or low) input voltage
The Windy Boy 5000 / 6000 is in Standby mode. This situation occurs
All LEDs are off.
Initialization
All LEDs are on.
Working mode
Green LED is on.
when the input performance at the Windy Boy 5000 / 6000 is too low for feeding the mains supply (DC input voltage < approx. 80 V) and for satisfying the on-board power requirements.
The on-board computer of the Windy Boy 5000 / 6000 is presently in the initialization process. The DC input voltage of the Windy Boy 5000 / 6000 lies between approx. 80 V and approx. 120 V. The power is adequate for the on­board power requirements but insufficient for mains supply feed-in or for data transmission.
The Windy Boy 5000 / 6000 has successfully passed the measurement electronics and SMA grid guard self-tests and has begun feed-in operation.
The Windy Boy 5000 / 6000 is working normally and is feeding electricity into the mains supply. It is converting the DC voltage from the wind turbine according to the V/I characteristic curve defined by
Start, UDCWindStart and
U
PV
WindMax (chapter 5 “Turbine
U
DC
operation" on page 33).
Operating instructions WB50_60-11:FE4105 Page 19
Unit description SMA Technology AG
Stop
The Windy Boy 5000 / 6000 is in Stop mode. Among other functions, the
1s
Green LED blinks 3 times per second.
measurement electronics are calibrated and then finally, the device switches to "Waiting" mode.
The "Stop" mode can also be manually set by the system operator via the Sunny Boy Control or the Sunny Data PC program. In this case, the Windy Boy 5000 / 6000 remains in "Stop" mode until a new operating mode ("MPP mode", "Turbine mode") has been set.
Maintenance, grid monitoring
The Windy Boy 5000 / 6000 checks if
1s
The green LED blinks once per second.
the initial conditions necessary for feeding the mains supply are satisfied (e.g. start voltage) and then begins monitoring the mains supply.
Derating
The temperature monitoring of the
1s
The green LED turns off briefly once per
Page 20 WB50_60-11:FE4105 Operating instructions
Windy Boy 5000 / 6000 has reduced the output performance to prevent the device from overheating. If this occurs often, then this is an indication of inadequate heat dissipation.
To avoid unnecessary reductions in yield, in this case it should be checked if the Windy Boy 5000 / 6000 can be mounted in a better position with better ventilation.
SMA Technology AG Unit description
Insulation fault
The green LED blinks once per second.
The red LED is continuously on.
Consult trained electrical personnel to correct the fault using the "Installation manual".
The Windy Boy 5000 / 6000 indicates a ground fault by illuminating the red LED.
Defective varistor
The green LED is continuously on.
The red LED is continuously on.
At least one of the two thermally monitored varistors on the DC input side of the device has become highly resistive and thus no longer functions correctly.
Consult trained electrical personnel to correct the fault using the "Installation manual".
Constant operational limiting
This message is displayed if a fault develops in the grid monitoring and/or the independent disconnection device
The yellow LED is continuously on.
Operating instructions WB50_60-11:FE4105 Page 21
(SMA grid guard). The Windy Boy 5000 / 6000 has detected a fault in the SMA grid guard during an internal test and has disabled the mains supply feed-in.
This usually indicates a fault that cannot be corrected on site. Please consult the manufacturer (chapter 12 "Contact” (page 67)) and discuss further action to solve the problem with them.
Unit description SMA Technology AG
Mains supply fault
The yellow LED illuminates 2 times
LED on
LED off
12
3s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 2 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The Windy Boy 5000 / 6000 indicates a mains supply fault with this message, which can have the following causes:
• Low mains supply voltage (VAC < "Vac-Min")
• High mains supply voltage (VAC > "Vac-Max")
• Low mains supply frequency (fAC < "Fac-Min")
• High mains supply frequency (fAC > "Fac-Max")
• A change in mains supply frequency ("dFac")
Check if a general mains supply dropout has occurred (check the operation of other mains supply devices), and check if the fuse of the feed-in connection of the Windy Boy 5000 / 6000 is intact.
If one of these faults can be found, then the mains supply connection of the Windy Boy 5000 / 6000 must be checked by qualified electrical personnel.
Page 22 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description
Mains supply impedance is too high
The yellow LED illuminates 3 times
LED off
LED on
3s 1s
5s
The message is repeated 3 times and then begins again.
12
3
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 3 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
The Windy Boy 5000 / 6000 has detected a fault relating to an unacceptable impedance in the mains supply. If the Windy Boy 5000 / 6000 frequently displays this fault during mains monitoring, the cause can be a mains impedance that is too high. An electrician can usually assist with this problem by increasing the cross section of the mains connection cable. Other measures can be taken to correct this problem, but they require the agreement and cooperation of the electricity supplier.
Input voltage too high
The yellow LED illuminates 4 times
LED off
LED on
3s 1s1s 1s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
12
34
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The presence of excessive input voltage can lead to
irreparable damage! Make sure that the input voltage never exceeds 600 V.
Operating instructions WB50_60-11:FE4105 Page 23
Unit description SMA Technology AG
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it automatically disconnects from the mains supply and no longer feeds power into the grid. When the Windy Boy 5000 / 6000 is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy 5000 / 6000!
Device faults
The yellow LED illuminates 5 times
LED off
LED on
3s 1s1s 1s 1s
5s
The message is repeated 3 times and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins displaying the blink code of: 3 seconds off and then 5 times briefly on. This code is displayed three times in succession. If the fault is still present, the fault display starts again from the beginning.
If the device fault leads to a major reduction in normal operation, the Windy Boy and the entire system installation should be checked by an electrician.
12
345
Page 24 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description

3.4 Messages in the optional display

The Windy Boy 5000 / 6000 can be factory fitted with an LCD display in the lid of the case.
Windy
Boy
Pac 903W Upv 330V
Netzwechselrichter für Windenergieanlagen Grid tied inverter for wind turbines
The display can also be retrofitted (SMA order code, "SB-Display", language specification to be provided when ordering).
Switching on the display illumination
The background illumination is switched on by tapping on the lid of the case. Tapping again switches the display to the next message.
After 2 minutes, the illumination switches off automatically.
Display messages in the startup phase
The following messages are displayed during the startup phase of the Windy Boy 6000 and are identical to those in the Windy Boy 5000. Since the Windy Boy 5000 / 6000 is identically to the Sunny Mini Central, apart from the mode of operation, the display shows "Sunny Mini Central“.
After 6 seconds, the firmware version of the operation control unit (BFR) and the current control unit (SRR) are displayed.
Operating instructions WB50_60-11:FE4105 Page 25
SMC6000
WR6K-003
Initialization phase
BFR Version 2.52 SRR Version 2.49
Initialization phase
Unit description SMA Technology AG
p
g
Display message during operation
The display shows the most important operational information of the Windy Boy 5000 / 6000 in a continuous cycle. The following three diagrams serve to clarify the messages. Every message is displayed for 5 seconds. Then the cycle begins again.
E-today 3.86
Status Turbine
Energy sum since the last activation, and
the current operational status
operational status are first displayed.
The amount of energy shown under "E-today" does not necessarily reflect the amount of energy produced over the last 24 hours. This is rather the energy produced by the Windy Boy 5000 / 6000 since the last deactivation/ activation.
The energy generated today and the current
Pac 903W Vac 195V
Current feed-in power and
AC voltage
E-total 724.4kWh h-total 512h
Total amount of energy produced and the
total number of o
erating hours
Subsequently, the current feed-in power and the output voltage are displayed.
This is then followed by the total energy produced so far and the operational hours of the device.
Fault displays
Disturbance
Vac-Bfr
Fault display
If an operational fault develops, the display immediately switches to "Disturbance" and the background illumination is switched on.
The cause of the fault is displayed for 5 seconds in the second line of the display.
at: 261V present: 245V
Display of the values measured
durin
the fault
If a measured value is responsible for the fault
condition, then the value measured at the time of the fault is displayed. If another measurement is possible, the current value is displayed in the second line.
After another 5 seconds, normal operational information is again displayed.
If the fault is still present, the fault display starts again from the beginning. An overview of the status and fault messages can be found in chapter 10.2 "Fault messages” (page 60) of this document.
Page 26 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Unit description
“Error ROM“ indicates, that the Windy Boy 5000 / 6000 has recognized a fault in the Firmware EEPROM. Contact SMA to correct the fault.
Error
ROM
Fault displays
of the Firmware EEPROM
Special display in the case of excessive DC input voltage
If an excessive DC input voltage is present on the Windy Boy 5000 / 6000, then this is indicated by rapid blinking of the background illumination and a corresponding message.
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The presence of excessive input voltage can lead to
irreparable damage! Make sure that the input voltage never exceeds 600 V.
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it automatically disconnects from the mains supply and no longer feeds power into the grid. When the Windy Boy 5000 / 6000 is in operation, you must always first disconnect the AC voltage (mains supply) and only then should you disconnect the DC voltage from the Windy Boy 5000 / 6000.
Before placing the device back into operation, the input voltage must be checked before reconnecting the DC voltage to the Windy Boy 5000 / 6000! Since the Windy Boy 5000 / 6000 is identical to the Sunny Mini Central, apart from the mode of operation, the display of the Windy Boy 5000 / 6000 shows "PV" (Photovoltaic) as its input source.
!PV-Overvoltage!
DISCONNECT DC
Overvoltage displays
Operating instructions WB50_60-11:FE4105 Page 27
Unit description SMA Technology AG
Page 28 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Setting the display language

4 Setting the display language

The display language is set using the switches on the underside of the SB-LCD components.
Since the cover must be removed, please ask a qualified electrician to disconnect the DC and AC connections from the Windy Boy 5000 / 6000, according to the installation instructions.
Position of the switches for setting the display language
E-Total 124.4kWh h-Total 512h
S1
S1
AS2AB B
AS2ABB
C B A
2357
SMC60-AST
V
0 4
0 V
2
Potter & Brumfield Potter & Brumfield Potter & Brumfield
+ +
+ +
MC MC MC MC
- - - -
VN30.15/00858
N
L
NL1
230Vac:
MCMC
MC
MC
PE
Language Switch S2 Switch S1
German B B English B A French A B Spanish A A
Operating instructions WB50_60-11:FE4105 Page 29
E-Total 124.4kWh h-Total 512h
S2
S2
A
A
S1
S1
AB B
ABB
Setting the display language SMA Technology AG
Page 30 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Maintenance and care

5 Maintenance and care

Because the Windy Boy 5000 / 6000 can be used outdoors in places that are difficult to access, it has been constructed for low maintenance.
In the interests of maximum yield, the operator should check, weekly if possible, under various conditions of wind, if the displays of the Windy Boy 5000 / 6000 indicate plausible normal operation (cf. chapter 3.3.4 "Description of the operational status" (page19)). Naturally, this information can be obtained by using one of the communications options.
The cleaning intervals are dependent from the ambient conditions. Make sure that enough air can flow through the fan guards. With that you can contribute to an optimum yield of your system.
If the LEDs are so dirty that they can no longer be seen, then they can be cleaned with a damp cloth. Solvents, abrasives or corrosive liquids must not be used!
A detailed description of how to clean the fans can be found in the installation manual of the Windy Boy 5000 / 6000.
Operating instructions WB50_60-11:FE4105 Page 31
Maintenance and care SMA Technology AG
Page 32 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Turbine operation

6 Turbine operation

6.1 Overview

The Windy Boy 5000 / 6000 is a single phase inverter that converts DC current into AC current and feeds the energy generated by a wind turbine into an existing mains supply.
The Windy Boy 5000 / 6000 is externally identical to the Sunny Mini Central inverter for photovoltaic systems.
The Windy Boy 5000 / 6000 inverter has a special operational mode for wind generators however, which allows performance adjustment to the characteristic curves of many different manufacturers' generators ("Turbine" operating mode). In this way maximum yields can be obtained from your wind turbine.
The mechanical power of the wind turbine is presented to the Windy Boy in the form of a direct, rotation speed variable DC voltage (RPM) and current intensity (torque).
Most small wind turbines have a so-called permanent magnet generator and a downstream rectifier for converting the variable frequency AC generator voltage into DC current.

6.2 Characteristic curve function

The "Turbine" operating mode of the Windy Boy 5000 / 6000 uses a programmable power/voltage curve to regulate the input current depending on the generator voltage (V/I characteristic curve).
Every wind generator is designed to have an optimum working point for voltage and current, at different rotational speeds or wind speeds. This behavior is not linear.
The Windy Boy 5000 / 6000 uses an approximation based on a simple ramp function. The function can be programmed by the user so that it comes close to the behavior of the wind generator being used and thus provides power adaptation.
Operating instructions WB50_60-11:FE4105 Page 33
Turbine operation SMA Technology AG
The diagram shows the ramp function of a typical Windy Boy 5000 / 6000 power/ voltage curve. The feed-in AC power depending on the DC input voltage of the Windy Boy is shown here. The adjustable parameters U U
WindMax are used to adapt the power/voltage curve of the Windy Boy 5000
DC
Start, UDCWindStart and
PV
/ 6000 to the wind generator being used.
Operating Mode: Turbine
Pac / Pac-max
200 350 400 450 500 550 600
330
Vdc V
The correct configuration of the parameters shown in the diagram is absolutely necessary to guarantee optimum operation with wind generators from different manufacturers.
The basic parameters of a Windy Boy 5000 / 6000 (factory settings) are shown in the following table.
Page 34 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Turbine operation
Name WB 5000 WB 6000 Unit Description
UpvStart 300
(250 ... 600)
300 (250 ... 600)
V
DC
Defines the voltage at the moment when the Windy Boy 5000 / 6000 is ready to perform a mains supply synchronization.
UdcWindStart 330
(1 ... 800)
330 (1 ... 800)
V
DC
Defines the voltage at the moment when the Windy Boy 5000 / 6000 is ready to begin feeding power into the mains supply.
UdcWindMax 550
(1 ... 800)
550 (1 ... 800)
V
DC
Defines the voltage at the moment when the Windy Boy 5000 / 6000 begins feeding maximum power into the mains supply.
P-Wind-Ramp 500
(10 ... 2000)
500 (10 ... 2000)
W/sec Controls a delayed startup
of the characteristic curve, only after the Windy Boy 5000 / 6000 has been switched on. This avoids the generator being suddenly presented with a heavy load.
T-Start 10
(5 ... 1600)
T-Stop 2
(1 ... 3600)2(1 ... 3600)
10 (5 ... 1600)
sec Start Timer Mains
synchronization.
sec Stop Timer Aborting the
supply of power and switching off.
The correct configuration of the parameters above is absolutely necessary to guarantee optimum operation with generators from different manufacturers. Preconditions for changing the operating parameters are described in chapter 6.4 "General setting example” (page 37).
To perform the configuration process, the DC input voltage must be greater than <UpvStart> and the Windy Boy 5000 / 6000 must be connected to the mains supply.
Operating instructions WB50_60-11:FE4105 Page 35
Turbine operation SMA Technology AG
6.3 Characteristic curve operation in "Turbine"
operating mode
Please note: The linear characteristic curve of the Windy Boy 5000 / 6000 only approximates the actual characteristics of a real wind generator. Consult the manufacturer of your wind generator for the typical characteristics of your generator before changing the characteristic curve parameters.
As soon as the DC input voltage defined in the parameter <UpvStart> is reached, the Windy Boy begins a number of self tests, measurement processes and synchronizes with the mains supply. If the self tests are successfully completed, and the DC input voltage remains above the value defined in <UpvStart> for the time defined in <T­Start>, the Windy Boy connects to the mains supply.
As soon as the DC input voltage reaches the value defined in <UdcWindStart>, the Windy Boy begins feeding power into the mains supply. As you can see from the characteristic curve, the power fed into the mains supply rises with the DC input voltage.
As soon as the DC input voltage reaches the value defined in the parameter <UdcWindMax>, the Windy Boy 5000 / 6000 feeds the mains supply with the maximum possible power. If the input voltage continues to rise, the Windy Boy 5000 / 6000 continues to feed the mains supply at maximum power.
The characteristic curve ends at the maximum permissible input voltage of the Windy Boy 5000 / 6000, which must never be exceeded.
If the wind strength is so low that the DC input voltage falls below <UpvStart>, then the Windy Boy ceases feeding power into the mains supply for the period defined in <T-Stop>.
If the DC input voltage increases again, then the Windy Boy will again operate according to the characteristic curve.
If the DC input voltage falls below the internally calculated minimum operating value of <Vmin>, then there is insufficient energy for the on-board electronics and the Windy Boy will switch off.
If the DC input voltage lies between <Vmin> and <UpvStart> for the time defined by <T-Stop>, then the Windy Boy will also switch off.
After the switch-off process, the whole process begins anew.
Only change the operating parameters when you know exactly what you are doing!
Page 36 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Turbine operation

6.4 General setting example

Please note that the following example only represents a starting point for operating with a wind generator.
• <UpvStart> is set to the lowest possible value: This achieves an early switch-on of the Windy Boy 5000 / 6000.
• <UdcWindStart> is set to the same value of <UpvStart>: This achieves an early mains supply feed-in. If the wind turbine does not properly start, or the Windy Boy frequently switches on and off, i t is rec ommended that you increase <UdcWindStart> in (e.g.) 10 V steps.
• <UdcWindMax> is initially set to approx. 10 % below the maximum MPP voltage of the Windy Boy 5000 / 6000: In this case the slope of the ramp function is relatively flat. The maximum output power is only reached with a relatively high DC input voltage, which avoids "braking" of the wind generator through excessive power consumption. This setting is especially suitable in locations with little or weak wind. Once the properties of the wind generator are known, then the reduction of the <UdcWindMax> parameter may be necessary, in order to extract the maximum power from the wind generator even at low DC input voltages (low wind speeds). The ramp function will then be steeper.
Contact the manufacturer of your wind generator for the typical properties of your generator (voltage/power characteristic).
• <T-Stop> is set to the maximum value: Here, the Windy Boy remains connected to the mains supply, even at low DC input voltage levels, and "waits" for the next gust of wind. This delays an early switch-off of the Windy Boy.
• <T-Start> is set to the minimum value: This achieves a reduction of the switch-on time (please observe the regulations of the energy supplier responsible).
Only change the operating parameters when you know exactly what you are doing!
Operating instructions WB50_60-11:FE4105 Page 37
Turbine operation SMA Technology AG
Page 38 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Maintenance and care

7 Maintenance and care

Because the Windy Boy 5000 / 6000 can be used outdoors in places that are difficult to access, the Windy Boy has been constructed for low maintenance. To guarantee safe operation, it is usually adequate to check the device visually for damage appro­ximately every two months. It should also be checked if the red LED is illuminated and, if necessary, remove the fault by referring to chapter 3.3.4 "Description of the operational status” (page 19).
In the interests of maximum yield, the operator should check, weekly if possible, un­der various conditions of solar irradiation, if the displays of the Windy Boy 5000 / 6000 indicate plausible normal operation (cf. chapter 3.3.4 "Description of the ope­rational status” (page 19)). Naturally, this information can be obtained by using one of the communications options.
Cleaning of the Windy Boy is only necessary when the heat dissipation is limited by dirty cooling fins or a dirty space between the Windy Boy and the wall. The dirt should be carefully removed with an appropriate soft brush or paintbrush.
If the LEDs are so dirty that they can no longer be seen, then they can be cleaned with a damp cloth. Solvents, abrasives or corrosive liquids must not be used!
Operating instructions WB50_60-11:FE4105 Page 39
Maintenance and care SMA Technology AG
Page 40 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Expansions

8 Expansions

As with all inverters in the Sunny Boy family, the Windy Boy 5000 / 6000 can also be expanded with a range of communications interfaces. This provides the operator with the possibility of requesting detailed operational data and error messages, for subsequent analysis on a PC using (e.g.) the free software available from SMA.
The data can currently be transferred in five different ways:
• using Powerline
• using a separate RS485 cable
• using a separate RS232 cable
• using a wireless link (Sunny Beam)
• using a separate USB-Service-Interface (USBPBS)
The wind turbine can be monitored by the Windy Boy 5000 / 6000 in a number of different ways. SMA offers a range of products for this purpose, allowing you to install a tailor-made monitoring system for your system. If you require detailed information about the Windy Boy products, please request the Sunny Family catalog or visit www.SMA.de. In the following sections the currently available communications options are schematically described.

8.1 Sunny Data

Sunny Data is a PC program for direct monitoring of your system. The connection of the Windy Boys to a PC is described in the following sections.
Operating instructions WB50_60-11:FE4105 Page 41
Expansions SMA Technology AG

8.2 Sunny Data via Powerline

"Wireless" communication via the mains power line (up to 50 Windy Boys) Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back and
the PC must be equipped with an SWR-COM plug modem. The connection of the PC using SWR-COM is described in the SWR-COM documentation.
SWR-COM
socket connector
P h
B
o
e t
t
r
o P h
B
o
e t
t
r
o
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h i
s c
e
l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u
r e
P h
B
o
e t
t
r
o
i e b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a r
t h F a u
l t
S t ö r
u n
g F a i l
u
r
e
max. 50
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c
ta
h
i
s
c
e
l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u n
g F a i l u r
e
PC with
Sunny Data
Control
Powerline

8.3 Sunny Data over RS232

Communication via a cable (a single Windy Boy 5000 / 6000) Prerequisites: The Windy Boy must be equipped with an RS232 Piggy-Back, the
connection to the PC usually occurs directly over the COM1 or COM2 port of the PC. The installation of the RS232 cable is described in the installation instructions of the Windy Boy 5000 / 6000.
PC with
P h
B
o
e t r
t
i
o
e b
v o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h i
s c
e
l
i
r
n
E
ic
v
r d
h
e
s
c
r
t e
h
t
e
l
r
u
E
r
s
s a r t
h
F
a
u
l t
S t ö r
u
n
g F a i l u
r
e
Sunny Data
Page 42 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Expansions

8.4 Sunny Data over RS485

Communication via a cable (up to 50 Windy Boys) Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the
connection with the PC usually occurs via an RS485/RS232 interface converter connected to the COM1 or COM2 port or via an RS485/USB interface converter connected to the USB port. The installation of the RS232 cable is described in the installation instructions of the Windy Boy 5000 / 6000.
Interface
Converter
P h
B
o
e t
t
r
o P h
B
o
e t
t
r
o
i e b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u E
r
s
s
a r t h F a u
l t
S t ö r u n g F a i l u r e
P h
B
o
e t
t
r
o
i e b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c
t
a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u E
r
s s
a r t h F a
u l t
S t ö r u n g F a i l u r e
max. 50
i e b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u E
r
s s
a r t h F a u
l t
S t ö r u n g F a i l u r e
(RS485/RS232
PC with
Sunny Data
RS232
RS485

8.5 Sunny Beam

Simple wireless system monitoring for up to 4 Windy Boys. Prerequisites: The Windy Boys must be equipped with a wireless Piggy-Back and a
Sunny Beam must be present at an appropriate distance. The installation of the wireless Piggy-Back is described in the Sunny Beam user manual.
Sunny Beam
P h
B
o
e
t
t
r
o
i e b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h
i
s
c
e l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a
r t h F a u l t
S t
ö r u n
g F a
i
l
u
r
e
P h o
t o v o
l
P
t a
h
i
o
k
t
-
o
W v o
e
l
c
t a
h
i
s
c
e l
i
r
n
i
v
c
h
e
r
t
e t e
r
r
max. 4
B e t r i e
b O p e r a
t
i
o
n E r d s c h
l
u E
s
s
a r t h
F
a
u
l
t
S t ö r u n
g F a i l u r
e
P h
B
o
e t
t
r
o
i e b
v o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c
t
a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t
h F a u
l t
S t ö r
u n
g F a i l u
r
e
Operating instructions WB50_60-11:FE4105 Page 43
Expansions SMA Technology AG

8.6 Sunny Data Control over Sunny Beam

Communication with a PC over Sunny Beam (up to 4 Windy Boys) Prerequisites: All 4 Windy Boys must be equipped with a wireless Piggy-Back and
accessible to Sunny Beam for system monitoring. The Sunny Beam is connected to the PC via an USB cable. The installation of the wireless Piggy-Backs and the connection to the PC is described in the Sunny Beam user manual.
Sunny Beam
P
h
B
o
e t
t
r
o
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c
t
a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u r
e
P h o
t o v o
l
P
t a
h
i
o
k
t
-
o
W v o
e
l
c t a
h i
s c
e
l
i
r
n
i
v
c h
e
r
t
e t e
r r
max. 4
B e t r
i e
b O p e
r
a
t
i
o
n E r d s
c
h
l
u E
s
s
a r t
h
F
a
u
l t
S t ö r
u
n
g F a i l u
r
e
P
h
B
o
e t
t
r
o
i e b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c
t
a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h
F a u l t
S
t ö r u n
g
F
a i l u r e
USB
PC with
Sunny Data

8.7 Sunny Boy Control Light

The simple data logger for systems with up to 10 Windy Boys. The connection between the Sunny Boy Control Light and the Windy Boys occurs via Powerline.
Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back. The installation is described in detail in the Sunny Boy Control Light documentation.
Sunny Boy
Control
PAC
Light
1273
W
Ph
B
o
e t r
to
Ph
B
otovo
e t r i
e b
O
lta
Ph
p e
r
ik-W
otovo
a t i o n
ech lta ic inver
selr
E
ic
r d
hte
s c
h
ter
l
r
u
E
s
s a r t h
F
a
u
l
t
S t ö r u
n
g F a i l u
r
e
Ph
B
ot
e t r i
o
e b
vo
O
lt
P
p
a
ho
e r
ik
a
t
t
-W
i
ov
o n
o
e
lta
c hs
ic
el
i
ri
nv
E
ch
r d
e
s
r
c
te
h
te
l
r
u
E
r
s
s a r t h F
a
u
l
t
S t ö r u n
g F a i l u r e
max. 10
i e
b
vo
O
l
P
ta
p
h
e r
ik-
ot
a t i
ov
o
W
n
ol
e
c
ta
h
i
se
c
lr
in
E
ic
ve
r d
hte
s
r
c
h
te
l
r
u
E
r
s
s a r t h
F
a
u
l
t
S t ö r u
n
g F a i l u
r
e
Powerline
Page 44 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Expansions

8.8 Sunny Boy Control

The simple data logger for systems with up to 50 Windy Boys. The connection between the Sunny Boy Control and the Windy Boys can be achieved as follows:
Powerline - "Wireless" communication via the mains power line Prerequisites: All the Windy Boys must be equipped with a Powerline Piggy-Back.
Sunny Boy
P h
B
o
e t
t
r
o P h
B
o
e t
t
r
o
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h i
s c
e
l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u
r
e
P h
B
o
e t
t
r
o
i e b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a r
t h F a u
l t
S t ö r
u n
g F a i l
u
r
e
max. 50
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h
i
s
c
e
l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u n
g F a i l u r
e
Powerline
RS485 Communication via a cable Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the
Sunny Boy Control must be equipped with an RS485 Piggy-Back on the "COM1 ­Sunny Boy" interface.
P h
B
o
e t
t
r
o P h
B
o
e t
t
r
o
i e
b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u n
g F a i l u r
e
P h
B
o
e t
t
r
o
i e b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s s
a r t
h F a u
l t
S t ö r
u n
g F a i l u
r
e
max. 50
i e b
v o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v o
e
l
c t a
h
i
s
c
e l
i
r
n
E
i
v
c
r d
h
e
s
r
t
c
e
h
t e
l
r
u
E
r
s s
a r t h F
a u l t
S t ö r u n
g F a i l u r e
Control
PA
C
1
2 7
3
W
Sunny Boy
Control
PA
C
1
2 7
3
W
RS485

8.9 Sunny Boy Control Plus

The data logger for systems with up to 50 Windy Boys, an additional interface for connection to PCs or large displays and additional connection possibilities for digital and analog inputs and outputs. Prerequisites: See Sunny Boy Control.
Operating instructions WB50_60-11:FE4105 Page 45
Expansions SMA Technology AG

8.10 Sunny Data Control

This is a PC program for system monitoring and visualization on a PC for systems with a Sunny Boy Control.
Prerequisites: A system with a Sunny Boy Control, Sunny Boy Control Plus or Sunny Boy Control Light with a connection to a PC.
Connection also
possible via Modem
P
h
B
o
e t r
to
i e b
vo
O
lta
P
p
h
e r
i
o
a
k-
t
to
i o
W
n
vo
ec lt a
hse
ic
l
i
r
n
E
i c
ve
r d
h
s c
r
te
h
te
l
r
u
E
r
s
s a r t h F
a
u
l
t
S
t ö r u n g
F
a i l u r e
.
.
.
P
ho
B
e t r
tov
i e b
olt
O
Ph
p
ai
e r
oto
a
k-
t
i
o
W
n
vo
ec lt aic
hs
el
inv
rich
E
r d
er
s c
te
h
t
er
l
r
u
E
s
s a r t h F
a
u
l
t
S
t ö r u n g
F
a i l u r e
Ph
B
o
e t r
t
i
o
e b
v olt
O
Pho
p
aik
e r a
t
to
-W
i
o
n
vo
ech
lta
ic i
s elr
nve
E
ich
r d s c
r
te
h
te
l
r
u
E
r
s
s a r t h F
a
u
l
t
S
t ö r u n g
F
a i l u r e
.
.
.
Data evaluation
with Excel
Visualization
with Sunny Data
Control
Remote Desktop
Internet
presentation
with
SDC-Agent
Internet
presentation
with
SMA-Portal
The connection between the PC and the Sunny Boy Control can occur via modem if required. Large systems with more than 50 Windy Boys can be monitored by coupling several Sunny Boy Controls together.
Page 46 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Expansions

8.11 Sunny WebBox

The Sunny WebBox is a versatile inexpensive platform for system visualization directly on a PC or via the Internet using the Sunny Portal. The Sunny WebBox will be available from the 2nd quarter of 2005.
PC via
Telephone
P h
B
o
e
t
r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i c
v
r d
h
e
s c
t
r
e
h
t
e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u
r
e
Sunny
.
.
.
RS485 (
RS232*) Powerline*)
(
P h
B
o
e t r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i c
v
r d
h
e
s c
t
r
e
h
t
e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u
r
e
(Radio*)
WebBox
Connection
Hub
Memory Card
External Sensors
LAN
P h
B
o
e t r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c t a
h i
s
c
e l
i
r
n
E
i c
v
r d
h
e
s c
t
r
e
h
t
e
l
r
u
E
r
s s
a r t h
F a u l t
S t ö r u
n
g F a i l u
r e
LAN
LAN
LAN
Modem
Sunny
Portal
(Internet)
External Display
PC
* Communication with Sunny WebBox via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
Operating instructions WB50_60-11:FE4105 Page 47
Expansions SMA Technology AG

8.12 Sunny Portal

The Sunny Portal is a high performance interface from SMA for the monitoring and presentation of your system in the Internet. Details can be obtained from the Sunny Family catalog or directly under www.SUNNY­PORTAL.de.

8.13 Sunny TV

Sunny TV is an accessory for Windy Boy inverters, which displays the system data and the current performance on a monitor or video projector. It is suitable for the presentation of large systems in lobbies and entrance halls as well as in private areas.
Video Projector TV Set
S
S
u
u
n
n
n
n
y
y
T
T
V
Sunny TV
Sunny TV
Pac = 7,450 W
P h
B
o
e
t
to
r i e b
vo
O
l
Ph
tai
p e r
o
a
k-
t
to
i o
W
n
v ol
e
c
ta
h
ic
se
i
lri
nv
E
ch
r
d
e
s
r
c
te
h
te
l
r
u
E
r
s s
a
r t h F a u l t
S t
ö r u n
g F a
i
l
u
r
e
.
.
.
Pac = 7,450 W
Sunny TV
RS485 (
P ho
B e
t
to
r
i
e
b
vo
O
lta
P
p
hot
e
r
ik-W
a
t
i
o
o
n
vo
e
lta
ch
ic i
se lri
nv
E
chter
r
d
e
s
r
c
h
ter
l
u E
s
s a
r
t
h
F
a
u
l
t
S t
ö
r
u
n
g F a
i
l
u
r
e
RS232*) Powerline*)
( (Radio*)
Video-Out
V
P
P
a
a
c
c
=
=
7
7
,4
,4
5
5
0
0
W
W
PC Monitor
S
u
n
n
y
T
V
P
a
c
=
7
,4
5
0
W
S u
n n y
T V
Configuration
P hot
B e
t
r
ovolta
i
e
b O
P
p
hoto
e
r
ik-W
a
t
i
o
n
volta
echs
ic inv
elri
E
ch
r
d
er
s
c
te
h
t er
l
r
u E
s
s a
r
t
h
F
a
u
l
t
S t
ö
r
u
n
g F a
i
l
u
r
e
* Communication with Sunny TV via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
with PC
Page 48 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Technical data

9 Technical data

9.1 Windy Boy 5000

9.1.1 DC connection data

Max. input open circuit voltage V Input voltage, MPP range V Nominal DC operating voltage V Max. input current I Max. input power P Recommended generator power
DC 0
DC
DC nom
DC max
DC max
P
turb max
at 5,000 full-load hours / year Recommended generator power
P
turb max
at 2,500 full-load hours / year All-pole isolator on the DC input
side Overvoltage protection Thermally monitored varistors DC voltage ripple U
SS
Personal protection Insulation monitoring (Riso > 1 MΩ) Own consumption in standby
mode Reverse polarity protection Short circuit diode
600 V 246 V ... 600 V DC 270 V 26 A 5750 W 4000 W
4500 W
DC plug connector
< 10% of the input voltage
< 7 W (standby)
Operating instructions WB50_60-11:FE4105 Page 49
Technical data SMA Technology AG

9.1.2 Grid connection data

Nominal output power P Peak output power P Nominal output current I Harmonic distortion of output
ACnom
ACmax
ACnom
THD
IAC
5000 W 5500 W 21,7 A < 4 % (PAC > 0.5 P
ACnom
)
current Operating range, grid voltage V
AC
198 ... 260 V AC (180 ... 265 V AC programmable)
Operating range, grid frequency
f
AC
49.8 ... 50.2 Hz / 59.8 ... 60.2 Hz (45.5 ... 54.5 Hz programmable)
All-pole isolator grid side Independent disconnection device
(SMA grid guard)
Phase shift angle
cos j 1 (based on the current's fundamental frequency)
Overvoltage category III
Test voltage (50 Hz) 2 kV (1 s routine testing / 60 s type
testing)
Test surge voltage 4 kV (1.2 / 50 µs) type testing
(serial interface: 6 kV)
Own consumption in standby
0.25 W
mode
Page 50 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Technical data

9.1.3 General data

For a detailed description of the device, see chapter 3 "Unit description” (page 13) of this manual.
General data
Protection category per DIN EN 60529
External temperature range -25° C to +60° C Dimensions (w x h x d) 430 mm x 600 mm x 450 mm Weight 63 kg (approx.)
External interfaces
Data transfer (mains cable) Optional Data transfer (data cable) optional, RS232 / RS485, electrically
Data transfer (wireless) Optional
Efficiency
Max. efficiency η
The efficiency of the Windy Boy 5000 / 6000 is heavily dependent on the DC input voltage.
max
IP54
separated
> 95,6 %
96
95
94
93
92
Overall Efficiency [%]
91
90
0 2000 3000 4000 5000 6000
Operating instructions WB50_60-11:FE4105 Page 51
250 V
300 V
400 V
500 V
Windy Boy 5000
1000
Output Power [W]
Technical data SMA Technology AG

9.2 Windy Boy 6000

9.2.1 DC connection data

Max. input open circuit voltage U Input voltage, MPP range U Nominal DC operating voltage U Max. input current I
DC 0
DC
DC nom
DC max
Max. input power DC Recommended generator power
P
turb max
at 5,000 full-load hours / year Recommended generator power
P
turb max
at 2500 full-load hours / year All-pole isolator on
the DC input side Overvoltage protection Thermally monitored varistors Voltage ripple U
PP
Personal protection Insulation monitoring (Riso > 1 MΩ) Own consumption in standby
mode Reverse polarity protection Short circuit diode
600 V 246 V ... 600 V DC 270 V
26.0 A 6300 W
max
4400 W
4950 W
DC plug connector
< 10% of the input voltage
< 7 W
Page 52 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Technical data

9.2.2 Grid connection data

Nominal output power P Peak output power P Nominal output current I Harmonic distortion of output
current (at K
> 0.5 P
P
AC
Unom
ACnom
< 2 %,
)
Operating range, grid voltage V
ACnom
ACmax
ACnom
THD
AC
5500 W 6000 W
24.0 A < 4 %
IAC
198 ... 260 V AC (180 ... 265 V AC programmable)
Operating range, grid frequency f
AC
49.8 ... 50.2 Hz / 59.8 ... 60.2 Hz (45.5 ... 54.5 programmable)
All-pole isolator grid side Independent disconnection device
(SMA grid guard)
Phase shift angle
cos j 1 (based on the current's fundamental frequency)
Overvoltage category III Test voltage (50 Hz) 2 kV (1 s routine testing / 60 s type
testing)
Test surge voltage 4 kV (1.2 / 50 µs) type testing
(serial interface: 6 kV)
Own consumption in standby
0.25 W
mode
Operating instructions WB50_60-11:FE4105 Page 53
Technical data SMA Technology AG

9.2.3 General data

For a detailed description of the device, see chapter 3 "Unit description” (page 13) of this manual.
General data
Protection category per DIN EN 60529 IP54 Dimensions (w x h x d) 430 mm x 600 mm x 450 mm Weight 63 kg (approx.)
External interfaces
Data transfer (mains cable) Optional Data transfer (separate data cable) optional, RS232 / RS485,
electrically separated
Data transfer (wireless) Optional
Efficiency
Max. efficiency η
max
The efficiency of the Windy Boy 5000 / 6000 is heavily dependent on the DC input voltage. The lower the input voltage, the higher the efficiency.
> 96,0 %
96
95
94
93
92
Overall Efficiency [%]
91
90
0 2000 3000 4000 5000 6000
Page 54 WB50_60-11:FE4105 Operating instructions
250 V
300 V
400 V
500 V
Windy Boy 6000
1000
Output Power [W]
SMA Technology AG General information

10 General information

10.1 Measurement channels and messages

If your Windy Boy 5000 / 6000 is equipped with a communications component, then numerous measurement channels and messages can be consulted. These can be useful for both performance improvement and for fault prevention.
The following abbreviations apply:
BFR: Operation control unit
SRR: Current control unit
E-Total Total amount of feed-in energy Fac Grid frequency Fehler / Error Fault type display under "Disturbance" status h-Total Total hours of mains supply feed-in operation Iac-Ist Mains supply current
Ipv DC current Netz-Ein /
Power on Pac Mains supply performance provided Riso Insulation resistance of the system to the mains supply connection Seriennummer /
Serial number Status / State Display of the current operational status Uac / Vac Grid voltage Upv-Ist / Vpv DC input voltage Upv-Soll /
Vpv-Setpoint Zac Mains supply impedance
Total number of mains supply switch-ons
Serial number of the Windy Boy
Nominal DC voltage
The measurement channels provide information in German (e.g."Fehler“), or in English (e. g. "Error“), depending on which software you are using (Sunny Data or Sunny Data Control).
Operating instructions WB50_60-11:FE4105 Page 55
General information SMA Technology AG

10.1.1 Status messages

The Windy Boy 5000 / 6000 produces a range of status messages, depending on the mode in which it is currently operating. The status messages can vary, depending on the type of communications system you are using.
Derating Overtemperature in inverter ("WR"). The Windy Boy 5000 /
6000 reduces its performance to avoid overheating the device. To avoid unnecessary yield losses, the configuration and string size should be checked. Check if the Windy Boy 5000 / 6000 can be located in a better position with better ventilation, thus providing better heat dissipation.
Mpp The Windy Boy 5000 / 6000 is operating in MPP mode. The
Windy Boy 5000 / 6000 takes the highest possible performance from the PV generator. MPP is the standard display when operating with normal sunshine (PV operation only).
Island Mode The Windy Boy 5000 / 6000 is in Island Mode. This mode is
specially conceived for operation in a stand alone power system with a Sunny Island as network controller. More information about this topic can be obtained from the Sunny Island operating manual under the category "Droop Mode".
grid mon. Testing the mains supply status (mains impedance), relay tests etc.
This message appears only during the startup phase, before the Windy Boy 5000 / 6000 is connected to the mains supply. This
message mainly appears when there is little or no wind. Offset Offset compensation of the measurement electronics disturb. Fault (see table "Fault messages")
This fault occurs for reasons of safety and prevents the Windy Boy
5000 / 6000 from connecting to the mains supply. This mode can
also be manually set. Stop Interruption of operation after a fault. This status can also be
manually set. Turbine Mode Default setting for Windy Boy 5000 / 6000 inverters. The input
voltage is converted according to the V/I function U
U
Start and UDCWindMax. See chapter 6 "Turbine operation”
DC
(page 33). V-Const Constant voltage operation (the input voltage is predefined. The
Windy Boy 5000 / 6000 operates in neither MPP mode nor
Turbine mode). In some cases, this can be set as the operational
mode. waiting The switch-on conditions are not (yet) satisfied.
PV
Start,
Page 56 WB50_60-11:FE4105 Operating instructions
SMA Technology AG General information

10.1.2 Windy Boy 5000 / 6000 Operating parameters

Unauthorized changes to the operating parameters may result in:
• Injury or accidents as a result of changing the internal safety
routines in the Windy Boy 5000 / 6000,
• Voiding of the Windy Boy 5000 / 6000 operating approval
certificate
• Voiding of the Windy Boy 5000 / 6000 warranty
Never change the parameters of your Windy Boy 5000 / 6000 without explicit authorization and instructions.
Name Unit Value range
Betriebsart / Operating Mode
Default GER/ENS Used for setting the country specific
dFac-MAX Hz/s 0.005 ... 4,0 0,25 Maximum "Mains frequency change"
dZac-MAX mOhm 0 ... 20000 350 Maximum "Mains impedance change"
E_Total kWh 0 ... 200000 Total energy yield (E_Total) and total
h_Total h 0 ... 200000
Fac-delta- Hz 0 ... 4,5 0,19 Maximum frequency, above (Fac-
Fac-delta+ Hz 0 ... 4,5 0,19
(WB 5000 / WB 6000)
MPP UKonst Stop Turbine Mode Insel Mode
Factory settings (WB 5000 /WB
6000)
Turbine Operating mode of the Windy Boy
Description
5000 / 6000: MPP: Maximum Power Point UKonst: Constant voltage mode (Desired voltage is defined in "Usoll­Konst") Stopp: Disconnection from mains supply, no operation Turbine: Operating mode for wind turbines, the input voltage is converted according to the V/I function defined by
Start, UDCWindStart and
U
PV
U
WindMax.
DC
information.
before the mains monitoring system disconnects the device from the mains supply.
before the mains monitoring system disconnects the device from the mains supply.
hours of operation (h_Total) for the Windy Boy. This change may be necessary when you exchange your Windy Boy 5000 / 6000 and want to use the data from the old device.
Delta+) and below (Fac-Delta-) the mains frequency of 50 Hz, before the mains monitoring system disconnects the device from the mains supply.
Operating instructions WB50_60-11:FE4105 Page 57
General information SMA Technology AG
Name Unit Value range
(WB 5000 / WB 6000)
Factory settings (WB 5000 /WB
Description
6000)
I-NiTest mA 0 ... 25000 16000 Activation (16000) and deactivation (0)
of the automatic leakage current measurement. This parameter only functions when the Windy Boy is deactivated (disconnected on the AC side) or in "Stop" mode.
Inst.-Code Parameters for mains supply monitoring
can only be changed after entering the "SMA grid guard" password.
KI-Wind-Reg 0 ... 0,25 0,005 Control speed (only possible in Turbine
KP-Wind-Reg 0 ... 0,25 0,117 Control speed (only possible in Turbine
P-Wind-Ramp W/s 10 ... 2000 500 Slow startup during mains supply
mode!)
mode!)
connection (only possible in Turbine mode!)
Speicher-­funktion / Memory function
Default,
Parameter,
Reset
Betriebsdaten,
Reset Fehler
none Default parameter: Returns all
parameter values to the factory setting. Reset Betriebsdaten: Returns all user level parameter values to the factor y setting. Reset Fehler: Resets a permanent fault.
Speichern/ store
Permanent, volatile
Permanent Permanent: Modified parameters are
stored in the EEPROM and can be used even when the Windy Boy has been restarted. Volatile: Prevents the parameters from being stored in the EEPROM, the parameters are stored until the next restart.
T-Start sec 5 ... 300 10 Start timer for mains supply
synchronization. (only possible in Turbine mode!)
T-Stop sec 1 ... 3600 2 Stop timer for stopping operation and
switching off. (only possible in Turbine mode!)
Uac-Min / Vac-Min
Uac-Max /
V 180 ... 300 198 Lower (Uac-Min) and upper (Uac-Max)
limits of the acceptable AC voltage (self
V 180 ... 300 260
contained power system recognition).
Vac-Max
WindMax V 1 ... 800 550 UDCWindMax represents the highest
U
DC
point of the function (please read more about this topic in chapter 6 "Turbine operation” (page 33)). (only possible in Turbine mode!)
Page 58 WB50_60-11:FE4105 Operating instructions
SMA Technology AG General information
Name Unit Value range
UDCWindStart V 1 ... 800 330 UDCWindStart represents the lowest
Usoll-Konst / Vconst­Setpiont
Start V 250 ... 600 300 UPVStart is the parameter defining the
U
PV
V 250 ...600 600 Desired DC voltage for constant
(WB 5000 / WB 6000)
Factory settings (WB 5000 /WB
6000)
Description
point of the function (please read more about this topic in chapter 6 "Turbine operation” (page 33)). (only possible in Turbine mode!)
operational voltage. These parameters are only important when the "Betriebsart" parameter is set to U­Konst.
voltage at which the Windy Boy is capable of connecting to the system. 180 V is the recommended voltage for the Windy Boy 5000 and the Windy Boy 6000. Reducing this voltage parameter can lead to numerous unnecessary connection attempts. Increasing this voltage parameter can lead to energy losses since the Windy Boy does not immediately connect to the system.
The following parameters are displayed in the parameter list but cannot be modified:
Name Unit Value range
Plimit W 5000 / 6000 5000 / 6000 Upper limit for AC output power
SMA-SN Serial number of the Windy Boy 5000
Software-BFR / Firmware-BFR
Software-SRR / Firmware-SRR
(WB5000/
6000)
Factory settings
(WB5000/
6000)
Description
/ 6000
Firmware version of the operation control unit (BFR)
Firmware version of the current control unit (SRR)
Operating instructions WB50_60-11:FE4105 Page 59
General information SMA Technology AG

10.2 Fault messages

If a fault develops, the Windy Boy 5000 / 6000 generates a message, which is dependent on the operational mode and the type of fault.
Fault code Description
Bfr-Srr
NUW-FAC
NUW-UAC
NUW-ZAC dZac-Bfr
dZac-Srr
EEPROM A data transfer fault occurred during reading or writing of data from
EEPROM dBh
EeRestore One of the duplicate data sets in the EEPROM is defective and has
Fac-Bfr Fac-Srr
Internal measurement comparison fault: the Windy Boy 5000 / 6000 found a too large difference between values provided by the BFR and SRR. Contact SMA.
The changes in mains impedance exceed the permissible range ("Bfr" or "Srr" is an internal message that has no meaning for the user).
The Windy Boy 5000 / 6000 disconnects from the mains supply or stand-alone grid, to avoid potential damage. If possible, check the mains impedance and check how often major deviations occur. If repeated variations occur and this is causing "dZac-Bfr" or "dZac­Srr" faults, ask the electricity provider if they agree to a modification of the operating parameters. Discuss the proposed parameters with the SMA hotline.
the EEPROM. The data is not relevant for safe operation - this fault has no effect on performance.
Data EEPROM is defective. The device has switched itself off because the loss of important functions has disabled the Windy Boy 5000 / 6000. Contact SMA.
been reconstructed without loss of data. The mains frequency has exceeded the permissible range ("Bfr" or
"Srr" is an internal message that has no meaning for the user). The Windy Boy 5000 / 6000 disconnects from the mains supply or stand­alone grid, to avoid potential damage. Check the mains frequency and mains connections on the Windy Boy 5000 / 6000. If the mains frequency lies outside the permissible range because of local conditions, ask the electricity provider if they agree to a modification of the operating parameters.
If the mains frequency lies within an acceptable range and "Fac-Bfr" or "Fac-Srr" faults are still being displayed, please contact the SMA hotline.
Page 60 WB50_60-11:FE4105 Operating instructions
SMA Technology AG General information
Fault code Description
Imax Overcurrent on the AC side. This fault code is displayed if the current
in the AC network is larger that specified. Check your system configuration and the mains supply conditions.
K1-Schliess / K1-Close
Fault during relay test. Please contact SMA if this fault occurs often or repeatedly.
K1-Trenn / K1-Open
NUW-Mes Measurement difference between BFR and SRR: Fac, Uac or Zac. Offset Fault in the acquisition of measurement data. Contact SMA if this
fault occurs frequently.
Rechner / NuW-
Functional fault in one of the two microcontrollers. Please contact SMA if this fault occurs often or repeatedly.
Timeout Riso A grounding fault exists or one of the thermally monitored varistors
on the DC input is defective as a result of overvoltage. Consult trained electrical personnel to correct the fault. You can find Instructions on how to change the varistors in the "Installation manual".
ROM The Windy Boy 5000 / 6000 firmware is faulty. Contact SMA if this
fault occurs frequently.
Uac-Bfr / Vac-Bfr
The mains voltage has exceeded the permissible range ("Bfr" or "Srr" is an internal message that has no meaning for the user). The Uac fault can have the following causes:
Uac-Srr / Vac-Srr
• Mains supply disconnected (circuit breaker or fuse)
• Broken AC cable or
• AC cable has a high internal resistance
For reasons of safety, the Windy Boy 5000 / 6000 disconnects itself from the mains supply. Check the mains voltage and mains connections on the Windy Boy 5000 / 6000. If the mains voltage lies outside the acceptable range because of local conditions, ask the electricity provider if the voltage can be adjusted at the feed-in point or if they agree to changes in the values of the monitored operational limits.
If the mains voltage lies within an acceptable range and "Uac-Bfr" or "Uac-Srr" faults are still being displayed, please contact the SMA hotline.
Operating instructions WB50_60-11:FE4105 Page 61
General information SMA Technology AG
Fault code Description
UpvMax /
Over voltage on DC input
Vpv-Max
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The Windy Boy 5000 / 6000 may otherwise be damaged seriously! Check the configuration of your system and measure the DC voltage before reconnecting the Windy Boy 5000 / 6000 to the
DC voltage. Watchdog Fault in the program code flow monitoring. Zac-Bfr/
Zac-Srr
The mains impedance has exceeded the permissible range ("Bfr“ or
"Srr“ is an internal message that has no meaning for the user). The
Windy Boy 5000 / 6000 disconnects from the mains supply or stand-
alone grid, to avoid potential damage. The impedance is calculated
from the mains supply impedance and the impedance of the mains
connection cable (AC cable) of the Windy Boy 5000 / 6000.
Check the mains impedance and mains connections on the Windy
Boy 5000 / 6000. Use a mains connection cable with an adequate
cross section (= low impedance), and observe the advice to this
effect in the installation guide in chapter 4.3. If the mains impedance
is still too high, then ask the electricity provider if the characteristics
of the mains supply at the feed-in point can be altered.
Page 62 WB50_60-11:FE4105 Operating instructions
SMA Technology AG General information

10.3 Declaration of conformity (CE)

CE Declaration of Conformity
for utility interactive inverters
Product: Windy Boy Type: WB 3300, WB 3800, WB 5000, WB 6000
We declare that the above specified devices are compliant with the regulations of the European Community, in terms of the design and the version fabricated by SMA. This especially applies for the EMC Regulation defined in 89/336/EWG and the low voltage regulation defined in 73/23/EWG.
The devices are compliant with the following standards:
EMC: Emission: DIN EN 61000-6-3: 2002-08
Utility Interference: DIN EN 61000-3-11: 2001-04
Immunity: DIN EN 61000-6-1: 2002-08
Safety: DIN EN 50178: 1998-04 Semiconductor-Converter: DIN EN 60146-1-1: 1994-03
DIN EN 61000-6-4: 2002-08 DIN EN 55022: 2003-09, Class B
DIN EN 61000-3-12: 2004-06 (Draft)
DIN EN 61000-6-2: 2002-08
The above mentioned devices are therefore marked with a CE sign.
Niestetal, 20th of June 2005 SMA Technologie AG
i.V. Frank Greizer
(Head of Development Department Solar Technology)
SMA Technologie AG
Hannoversche Strasse 1-5 34266 Niestetal Tel. +49 561 9522–0 Fax +49 561 9522–100 www.SMA.de info@SMA.de
WB-G16A-CE-12:BE2905
Operating instructions WB50_60-11:FE4105 Page 63
General information SMA Technology AG

10.4 Import certificate

The Windy Boy 5000 / 6000 string inverter is equipped with the "SMA grid guard" independent disconnection device and it is covered by the industrial trade association "SMA grid guard" import certificate.
Page 64 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Stand-alone systems

11 Stand-alone systems

The Windy Boy 5000 / 6000 is suitable for use in stand-alone systems based on the Sunny Island. The Windy Boy 5000 / 6000 requires extra settings for this to ensure optimum operation and also to achieve deactivation of the standard mains supply monitoring settings. Please obtain all further relevant information from the Sunny Island manuals.
Sunny Island
4248
or
Sunny Boy
Windy Boy
AC
bus
Consumers
Generator
Public Utility
Mini CHP
Operating instructions WB50_60-11:FE4105 Page 65
Stand-alone systems SMA Technology AG
Page 66 WB50_60-11:FE4105 Operating instructions
SMA Technology AG Contact

12 Contact

If you have any questions or technical problems concerning the Windy Boy 5000 / 6000, please contact our service hotline. Please have the following information available when you contact SMA:
• Inverter type
• Type of wind turbine and AC/DC converter
• Type of overvoltage protection
• Communication
• Serial number of the Windy Boy 5000 / 6000
Address:
SMA Technologie AG Hannoversche Strasse 1 - 5 34266 Niestetal Germany
Tel.:+49 561 95 22 - 499 Fax:+49 561 95 22 - 4699 hotline@SMA.de www.SMA.de
Operating instructions WB50_60-11:FE4105 Page 67
Contact SMA Technology AG
Page 68 WB50_60-11:FE4105 Operating instructions
Sales SMA Solar Technology
www.SMA.de
Rosendahl Industrievertretungen Adolf-Dembach-Strasse 1 47829 Krefeld Germany Tel. +49 2151 45678 90 Fax +49 2151 45678 99
SMA Technologie AG
SMA Solar Technology China
International Metro Center, Building A, City Square No. Jia 3, Shilipu Road, Changyang District 100025 Beijing, P.R. China Tel. +86 10 65 58 78 15 www.SMA-CHINA.com
SMA America, Inc.
12438 Loma Rica Drive, Unit C Grass Valley, CA 95945, USA Tel. +1 530 273 4895 www.SMA-AMERICA.com
SMA Spain
Rosendahl Técnica Energética, S.L. Decages S.A. Balmes, 297, 1er, 2a 08006 Barcelona, Spain Freecall +800 SUNNYBOY
Freecall +800 78669269
SMA Italy
Rosendahl Tecnologie Energetiche S.r.I. Via Lorenzo Valla, 16 20141 Milano, Italy Freecall +800 SUNNYBOY
Freecall +800 78669269
Innovation in Systems Technology
Seite 70 WB50-60-11:FD2805 Betriebsanleitung
for the Success of Photovoltaics
Loading...