Windy Boy 5000
Windy Boy 6000
Inverter for Wind Energy Power Plants
Operating Instructions Version 1.0 WB50_60-11:FE4105
TBE-WB50-60
SMA Technologie AGRevision Histroy
Revision History
Document numberChangesAuthor
WB50_60-11:FE4105First issueWelzel
Operating InstructionsWB50_60-11:FE4105Page 3
SMATechnologie AG
Page 4WB50_60-11:FE4105Operating Instructions
SMA Technologie AGExplanation of Symbols used in this Document
Explanation of Symbols used in this Document
This symbol indicates information that is essential for a trouble-free
and safe operation of the product. Please read these sections carefully in order to avoid any damages of the equipment and for optimal personal protection.
This symbol indicates information that is required for the optimal operation of
the product. Read these sections carefully in order to ensure an optimal operation of the product and all its features.
This symbol indicates an example.
Operating InstructionsWB50_60-11:FE4105Page 5
Legal RestrictionsSMA Technologie AG
Liability exclusion
The information contained in this documentation are the property of SMA Technologie AG. No part of this
documentation may be published without written permission from SMA Technologie AG. A reproduction for
internal purposes for the evaluation of the product or an appropriate application is permitted and does not
require authorization.
All information are based on our "General Terms and Conditions of Delivery of SMA Technologie AG”.
The content of this documentation is reviewed continuously and adjusted, if necessary. SMA Technologie
AG provides this documentation without exclusion of deviations and without warranty of completeness. You
will find the current version on the Internet at www.SMA.de or can obtain it via the usual sales channels.
Warranty or liability claims for all kinds are excluded in case of damages due to:
• Inappropriate use of the product
• Operation of the product in an improper environment
• Operation of the product without considering the relevant safety regulations
• Non-fulfillment of the warnings or safety instructions described in the documentation for the product
• Operation of the product under faulty conditions concerning security and protection
• Arbitrary changing of the product or the provided software
• Failure of the product due to interference of connected or contiguous devices out of legal limit values
• Disasters and force majeure
Software Licensing
The use of the provided software by SMA Technologie AG is subject to the following conditions:
The software may be reproduced for internal purposes and installed on any number of computers. Provided
source codes can be changed and adjusted on the company’s own authority according to the internal
purpose. Driver may be ported to other operating systems as well. No part of the source codes may be
published without written permission of SMA Technologie AG. Sublicensing of the software is not
acceptable.
Liability limitation: SMA Technologie AG disclaims liability for any direct or indirect consequential damages
arising from the use of the software produced by SMA Technologie AG. The same applies for the provision
and/or non-provision of support.
Provided software not produced by SMA Technologie AG is subject to the respective licensing and liability
agreements of the manufacturer.
Trademarks
All brand and product names used herein are trademarks or registered trademarks of their respective
holders, although they may not be specifically designated as such.
SMA Technologie AG
Hannoversche Strasse 1-5
34266 Niestetal
Germany
Tel. (+49) 5 61 95 22 – 0
Fax (+49) 5 61 95 22 – 100
The installation of the Windy Boy 5000 / 6000 may only be done
by qualified technicians. The installer must be approved by the
utility company. Please read the installation guide carefully before
you begin with the installation. The installation of utility interactive
power sources must be compliant with all applicable regulations of
the utility company and with all applicable regulations and
standards.
The Windy Boy inverters make it possible to operate small wind turbines as gridconnected systems. Grid-connected means that the energy generated by the wind
turbine can be fed directly into an existing house power grid, a stand-alone power
system, or the mains supply.
To this end, the Windy Boy converts the direct current (DC) from permanent-magnet
wind turbines, which vary with speed, into grid-compatible alternating current (AC).
The Windy Boy requires the constant presence of mains supply voltage!
The Windy Boy 5000 / 6000 complies with all the VDEW (Verband der
Elektrizitätswirtschaft – German Electricity Industry Association) regulations for the
connection and parallel operation of electrical power units to the low-voltage grid of
the electricity supply company. This also encompasses the regulations of the German
Professional Association for Precision Engineering and Electro technology relating to
"Automatic switching of electrical power units" (SMA grid guard) and/or DIN VDE
0126. In addition to this, the Windy Boy 5000 / 6000 conforms to the
electromagnetic tolerance regulations and the low-voltage regulations of the relevant
combined European norms, as confirmed in the CE conformity declaration (10.3
"Declaration of conformity (CE)” (page 63)).
The documentation provided here covers all such topics that are of interest when
operating Windy Boy 5000 / 6000 inverters. In addition to explanations of the
operational methods of the device and detailed technical data, advice as to data
capture and analysis is also provided.
Information relating to the installation and commission of the Windy Boy 5000 /
6000 should be taken from the installation instructions delivered with the device. The
Windy Boy 5000 / 6000 inverter has a special operational mode for wind turbines
which allows performance adjustment to the characteristic curve of the generator. In
this way you will obtain maximum yields from your wind turbine.
A wide input voltage range, high efficiency and a freely configurable output
characteristic curve with the highest level of reliability are only some of the properties
that are useful for your grid-connected system, or in a stand-alone system when
combined with the Sunny Island.
Operating instructionsWB50_60-11:FE4105Page 9
IntroductionSMA Technology AG
The Windy Boy 5000 / 6000 is compatible with all SMA communications products
(RS232, RS485, Powerline, Wireless, Display), providing numerous possibilities for
diagnosis, data visualization and remote maintenance of your small wind turbine
system.
For stand-alone systems, that use the Sunny Island: Please configure your
Windy Boy 5000 / 6000 according to the specifications in the Sunny Island
manual.
Configuration of the V/I properties of the Windy Boy 5000 / 6000 with respect
to your wind turbine: the parameters U
WindMax must be configured to guarantee optimum operation of your
U
DC
Start, UDCWindStart and
PV
Windy Boy 5000 / 6000 with your wind turbine. The configuration process is
described in chapter 6 "Turbine operation” (page 33).
Apart from the parameter settings, the Windy Boy 5000 / 6000 is identical to the
Sunny Mini Central photovoltaic inverter and can therefore also be used as a PV
inverter. Please download the Sunny Mini Central manual from www.SMA.de, and
if you are planning to use the Windy Boy 5000 / 6000 in a photovoltaic system
please contact us on the SMA hotline.
Page 10WB50_60-11:FE4105Operating instructions
SMA Technology AGSafety information
2 Safety information
Opening of the device, and any
•electrical installation,
Windy
Boy
P
a
c
U
p
v
9
0
3
W
3
3
N
0
et
z
V
w
e
c
h
G
se
r
i
l
d
r
i
c
t
ie
h
t
d
er
in
f
ver
ü
r
W
te
r
in
f
d
o
e
r
w
n
e
i
rg
n
d
i
ea
t
u
n
r
b
la
i
n
g
e
e
s
n
The temperature of individual parts of the case of the Windy Boy
5000 / 6000 - in particular the temperature of the heatsink - can
reach 60 °C in normal operation. Touching could result in burns!
The Windy Boy 5000 / 6000 contains an independent mains disconnection
device, the "SMA grid guard". It ensures that the Windy Boy 5000 / 6000
complies with the VDEW (Verband der Elektrizitätswirtschaft – German
Electricity Industry Association) regulations for the connection and parallel
operation of electrical power units to the low-voltage grid of the electricity
supply company and with DIN VDE 0126 (4.99), which forms a part of these
regulations.
•repair or
•modification
of the Windy Boy 5000 / 6000 may only be
performed by qualified electrical personnel.
Even when no external voltage is present,
the device can still contain high voltages and
the danger of electrical shock.
Operating instructionsWB50_60-11:FE4105Page 11
Safety informationSMA Technology AG
Page 12WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
3 Unit description
3.1 Appropriate usage of the Windy Boy 5000 / 6000
The Windy Boy 5000 / 6000 is designed for the conversion of DC voltage from a
wind turbine (permanent magnet generator) into AC voltage for feeding into the
public mains supply. The technical data are described in more detail in chapter 9
"Technical data” (page 49).
Net
z
w
e
c
h
s
e
l
r
i
c
G
h
r
t
i
e
d
r
t
f
i
ü
e
r
d
W
i
n
i
ve
n
d
r
e
te
n
r
e
f
r
o
g
r
i
e
w
a
i
n
n
l
d
a
g
t
u
e
r
n
b
i
n
e
Overvoltage Protection
Control unit
Control unit
s
Windy
Boy
P
a
c
Upv
903W
3
30V
Net
z
w
e
c
h
G
s
r
e
i
l
d
r
i
c
t
i
h
e
t
d
e
r
i
n
f
ve
ü
r
r
W
te
r
i
n
f
d
o
e
r
n
w
e
i
r
n
g
d
i
e
t
a
u
n
r
b
l
a
i
n
g
e
e
s
n
Wind Generator
Converter
Rectifier
Windy Boy
Public Mains Grid
Many wind turbine manufacturers offer an extra over-voltage protection module.
These components prevent the destruction of the downstream Windy Boy in the case
of overvoltage.
Overvoltage can occur under the following conditions:
• High turbine rotation speeds under strong wind conditions
• An increase in turbine rotation speed caused by load-shedding when the Windy
Boy is disconnected from the mains supply e.g. in the case of mains interference
or power outage.
The overvoltage protection system has the following tasks:
• When a pre-defined voltage is reached, the Windy Boy is disconnected from the
generator and a short-circuit slows the generator and/or brings it to a standstill.
• Some devices reduce the turbine rotation speed, and thus the generator output
voltage, by switching in a resistor assembly (Dumpload). The electrical energy
generated by the turbine is then converted to heat.
Operating instructionsWB50_60-11:FE4105Page 13
Unit descriptionSMA Technology AG
In grid-connected systems, we recommend the use of one of the electronic protection
mechanisms described here. Please note that overvoltage on the Windy Boy can lead
to destruction of the device. In addition to this, you lose the right to all warranty
claims - even if the maximum input voltage of the Windy Boy is only exceeded for a
short time.
The electronic protection systems described here are preferable to mechanical
solutions (pitch control, "turning out of the wind") in every case.
Any other use of the Windy Boy 5000 / 6000 leads to loss of the right to all warranty
claims.
In case of overvoltage, immediately disconnect the DC input of the
Windy Boy 5000 / 6000! The presence of excessive input voltage
can lead to irreparable damage!
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000!
Page 14WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
3.2 Device construction
An attractive, functional design is one of the major design objectives of the entire
Windy Boy 5000 / 6000 product range. In its basic configuration, the Windy Boy
5000 / 6000 has the proven status display consisting of three LEDs. An extra display
can be provided already installed or can be retrofitted.
As long as it is installed and commissioned according to the technical specifications,
the Windy Boy 5000 / 6000 can be operated without any further modification or
configuration. The device parameters can however be modified, if required.
+
Windy Boy 5000 / 6000 Enclosure IP54 (outside installation possible)
DC - input with 4 x 2 DC connectors
+
+
+
Characte-
ristic
wind
curve
Overvoltage
protection:
Thermally
monitored
varistors
Bridge
Optional
display
(IP65)
Optional
communi-
cations
interface:
RS232
RS485
Powerline
Transformer
OptiCool
SMA
Grid Guard
R
An extra communications interface is required for ideal adaptation
of the Windy Boy 5000 / 6000 to suit the particular wind turbine
being used, and this can also be used for reporting operation data.
For further details, please refer to chapter 8 "Expansions”
(page 41).
L
N
AC - output with terminals
PE
Operating instructionsWB50_60-11:FE4105Page 15
Unit descriptionSMA Technology AG
All DC connections and connections for the mains supply, as well as any optional
communications connections are to be found on the underside of the Windy Boy
5000 / 6000. Each of the + and - DC connections are internally connected in parallel
within the Windy Boy 5000 / 6000.
Plug connector
for DC+
Plug connector
for DC-
Cable opening for the
mains supply connection
Opening for optional communication via
RS232, RS485 or radio (PG16)
Page 16WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
3.3 Operating modes
The operational status is displayed using three light-emitting diodes (LEDs) in the
cover of the Windy Boy 5000 / 6000. To allow the device to signal its operational
status via the integrated LEDs, the Windy Boy 5000 / 6000 must be connected to the
DC side of the system. There must be enough wind energy present, so that the Windy
Boy 5000 / 6000 has adequate DC voltage.
Windy
Boy
Pac 903W
Upv 330V
Netzwechselrichter für Windenergieanlagen
Grid tied inverter for wind turbines
Especially in the first year of operation, the operator of the system should
check this display under different wind speeds.
A complete description of the possible displays can be found in chapter 3.3.4
"Description of the operational status” (page 19). These can be split into three
categories:
3.3.1 Normal operation
As long as the green control LED is on, or blinking, the Windy Boy 5000 / 6000 is
operating normally. The simultaneous illumination of all three LEDs is also an
indication of normal operation ("Initialization"). All other displays are a sign of
abnormal operation.
Operating instructionsWB50_60-11:FE4105Page 17
Unit descriptionSMA Technology AG
3.3.2 Critical, faulty operation
A comprehensive safety concept limits the number of critical conditions that can occur
to a single situation:
Input voltage exceeds the permitted value
This is indicated by the following blink-code on the yellow LED:
The yellow LED
illuminates 4 times
LED on
LED off
3s1s1s1s 1s
5s
The message is repeated 3 times
and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
The presence of excessive input voltage can lead to irreparable
damage! Immediately disconnect the DC input of the Windy Boy
5000 / 6000.
12
34
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000!
3.3.3 Non-critical, faulty operation
All other fault codes indicate some form of faulty operation, which are not usually
dangerous to people or equipment, but which should nevertheless be investigated
and corrected.
Despite all precautions, it is possible that other faults may occur that cannot be
displayed (e.g. failure of the status display). In order to recognize such faults, the
operator of the system should use the explanations in chapter 3.3.4 "Description of
the operational status” (page 19) to check the plausibility of the displayed status.
Further detailed diagnoses are possible using the communications options detailed in
chapter 8 "Expansions” (page 41).
Page 18WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
3.3.4 Description of the operational status
No (or low) input voltage
The Windy Boy 5000 / 6000 is in
Standby mode. This situation occurs
All LEDs are off.
Initialization
All LEDs are on.
Working mode
Green LED is on.
when the input performance at the
Windy Boy 5000 / 6000 is too low for
feeding the mains supply (DC input
voltage < approx. 80 V) and for
satisfying the on-board power
requirements.
The on-board computer of the Windy
Boy 5000 / 6000 is presently in the
initialization process. The DC input
voltage of the Windy Boy 5000 / 6000
lies between approx. 80 V and approx.
120 V. The power is adequate for the onboard power requirements but
insufficient for mains supply feed-in or for
data transmission.
The Windy Boy 5000 / 6000 has
successfully passed the measurement
electronics and SMA grid guard self-tests
and has begun feed-in operation.
The Windy Boy 5000 / 6000 is working
normally and is feeding electricity into
the mains supply. It is converting the DC
voltage from the wind turbine according
to the V/I characteristic curve defined by
Start, UDCWindStart and
U
PV
WindMax (chapter 5 “Turbine
U
DC
operation" on page 33).
Operating instructionsWB50_60-11:FE4105Page 19
Unit descriptionSMA Technology AG
Stop
The Windy Boy 5000 / 6000 is in Stop
mode. Among other functions, the
1s
Green LED blinks 3
times per second.
measurement electronics are calibrated
and then finally, the device switches to
"Waiting" mode.
The "Stop" mode can also be manually
set by the system operator via the Sunny
Boy Control or the Sunny Data PC
program. In this case, the Windy Boy
5000 / 6000 remains in "Stop" mode
until a new operating mode ("MPP
mode", "Turbine mode") has been set.
Maintenance, grid monitoring
The Windy Boy 5000 / 6000 checks if
1s
The green LED blinks
once per second.
the initial conditions necessary for
feeding the mains supply are satisfied
(e.g. start voltage) and then begins
monitoring the mains supply.
Derating
The temperature monitoring of the
1s
The green LED turns
off briefly once per
Page 20WB50_60-11:FE4105Operating instructions
Windy Boy 5000 / 6000 has reduced
the output performance to prevent the
device from overheating. If this occurs
often, then this is an indication of
inadequate heat dissipation.
To avoid unnecessary reductions in
yield, in this case it should be checked if
the Windy Boy 5000 / 6000 can be
mounted in a better position with better
ventilation.
SMA Technology AGUnit description
Insulation fault
The green LED blinks
once per second.
The red LED is
continuously on.
Consult trained electrical personnel to correct the fault using the
"Installation manual".
The Windy Boy 5000 / 6000 indicates a
ground fault by illuminating the red LED.
Defective varistor
The green LED is
continuously on.
The red LED is
continuously on.
At least one of the two thermally
monitored varistors on the DC input side
of the device has become highly resistive
and thus no longer functions correctly.
Consult trained electrical personnel to correct the fault using the
"Installation manual".
Constant operational limiting
This message is displayed if a fault
develops in the grid monitoring and/or
the independent disconnection device
The yellow LED is
continuously on.
Operating instructionsWB50_60-11:FE4105Page 21
(SMA grid guard). The Windy Boy 5000
/ 6000 has detected a fault in the SMA
grid guard during an internal test and
has disabled the mains supply feed-in.
This usually indicates a fault that cannot
be corrected on site. Please consult the
manufacturer (chapter 12 "Contact”
(page 67)) and discuss further action to
solve the problem with them.
Unit descriptionSMA Technology AG
Mains supply fault
The yellow LED
illuminates 2 times
LED on
LED off
12
3s 1s
5s
The message is repeated 3 times
and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 2 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
The Windy Boy 5000 / 6000 indicates a mains supply fault with this message, which
can have the following causes:
• Low mains supply voltage (VAC < "Vac-Min")
• High mains supply voltage (VAC > "Vac-Max")
• Low mains supply frequency (fAC < "Fac-Min")
• High mains supply frequency (fAC > "Fac-Max")
• A change in mains supply frequency ("dFac")
Check if a general mains supply dropout has occurred (check the operation of other
mains supply devices), and check if the fuse of the feed-in connection of the Windy
Boy 5000 / 6000 is intact.
If one of these faults can be found, then the mains supply
connection of the Windy Boy 5000 / 6000 must be checked by
qualified electrical personnel.
Page 22WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
Mains supply impedance is too high
The yellow LED
illuminates 3 times
LED off
LED on
3s 1s
5s
The message is repeated 3 times
and then begins again.
12
3
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 3 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
The Windy Boy 5000 / 6000 has detected a fault relating to an unacceptable
impedance in the mains supply. If the Windy Boy 5000 / 6000 frequently displays
this fault during mains monitoring, the cause can be a mains impedance that is too
high. An electrician can usually assist with this problem by increasing the cross section
of the mains connection cable. Other measures can be taken to correct this problem,
but they require the agreement and cooperation of the electricity supplier.
Input voltage too high
The yellow LED
illuminates 4 times
LED off
LED on
3s1s1s1s 1s
5s
The message is repeated 3 times
and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
12
34
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The presence of excessive input voltage can lead to
irreparable damage! Make sure that the input voltage never
exceeds 600 V.
Operating instructionsWB50_60-11:FE4105Page 23
Unit descriptionSMA Technology AG
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000!
Device faults
The yellow LED
illuminates 5 times
LED off
LED on
3s1s1s1s 1s
5s
The message is repeated 3 times
and then begins again.
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 5 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
If the device fault leads to a major reduction in normal operation,
the Windy Boy and the entire system installation should be
checked by an electrician.
12
345
Page 24WB50_60-11:FE4105Operating instructions
SMA Technology AGUnit description
3.4 Messages in the optional display
The Windy Boy 5000 / 6000 can be factory fitted with an LCD display in the lid of
the case.
Windy
Boy
Pac 903W
Upv 330V
Netzwechselrichter für Windenergieanlagen
Grid tied inverter for wind turbines
The display can also be retrofitted (SMA order code, "SB-Display", language
specification to be provided when ordering).
Switching on the display illumination
The background illumination is switched on by tapping on the lid of the case. Tapping
again switches the display to the next message.
After 2 minutes, the illumination switches off automatically.
Display messages in the startup phase
The following messages are displayed during the
startup phase of the Windy Boy 6000 and are
identical to those in the Windy Boy 5000. Since the
Windy Boy 5000 / 6000 is identically to the Sunny
Mini Central, apart from the mode of operation, the
display shows "Sunny Mini Central“.
After 6 seconds, the firmware version of the
operation control unit (BFR) and the current control
unit (SRR) are displayed.
Operating instructionsWB50_60-11:FE4105Page 25
SMC6000
WR6K-003
Initialization phase
BFR Version 2.52
SRR Version 2.49
Initialization phase
Unit descriptionSMA Technology AG
p
g
Display message during operation
The display shows the most important operational information of the Windy Boy
5000 / 6000 in a continuous cycle. The following three diagrams serve to clarify the
messages. Every message is displayed for 5 seconds. Then the cycle begins again.
E-today 3.86
Status Turbine
Energy sum since the last activation, and
the current operational status
operational status are first displayed.
The amount of energy shown under "E-today" does not necessarily reflect the
amount of energy produced over the last 24 hours. This is rather the energy
produced by the Windy Boy 5000 / 6000 since the last deactivation/
activation.
The energy generated today and the current
Pac 903W
Vac 195V
Current feed-in power and
AC voltage
E-total 724.4kWh
h-total 512h
Total amount of energy produced and the
total number of o
erating hours
Subsequently, the current feed-in power and the
output voltage are displayed.
This is then followed by the total energy produced so
far and the operational hours of the device.
Fault displays
Disturbance
Vac-Bfr
Fault display
If an operational fault develops, the display
immediately switches to "Disturbance" and the
background illumination is switched on.
The cause of the fault is displayed for 5 seconds in
the second line of the display.
at: 261V
present: 245V
Display of the values measured
durin
the fault
If a measured value is responsible for the fault
condition, then the value measured at the time of the
fault is displayed. If another measurement is
possible, the current value is displayed in the second
line.
After another 5 seconds, normal operational information is again displayed.
If the fault is still present, the fault display starts again from the beginning. An
overview of the status and fault messages can be found in chapter 10.2 "Fault
messages” (page 60) of this document.
Page 26WB50_60-11:FE4105Operating instructions
SMATechnology AGUnit description
“Error ROM“ indicates, that the Windy Boy 5000 /
6000 has recognized a fault in the Firmware
EEPROM. Contact SMA to correct the fault.
Error
ROM
Fault displays
of the Firmware EEPROM
Special display in the case of excessive
DC input voltage
If an excessive DC input voltage is present on the
Windy Boy 5000 / 6000, then this is indicated by
rapid blinking of the background illumination and a
corresponding message.
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The presence of excessive input voltage can lead to
irreparable damage! Make sure that the input voltage never
exceeds 600 V.
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000.
Before placing the device back into operation, the input voltage must be
checked before reconnecting the DC voltage to the Windy Boy 5000 / 6000!
Since the Windy Boy 5000 / 6000 is identical to the Sunny Mini Central, apart
from the mode of operation, the display of the Windy Boy 5000 / 6000 shows
"PV" (Photovoltaic) as its input source.
!PV-Overvoltage!
DISCONNECT DC
Overvoltage displays
Operating instructionsWB50_60-11:FE4105Page 27
Unit descriptionSMA Technology AG
Page 28WB50_60-11:FE4105Operating instructions
SMA Technology AGSetting the display language
4 Setting the display language
The display language is set using the switches on the underside of the SB-LCD
components.
Since the cover must be removed, please ask a qualified electrician
to disconnect the DC and AC connections from the Windy Boy 5000
/ 6000, according to the installation instructions.
Position of the switches for
setting the display language
E-Total 124.4kWhh-Total 512h
S1
S1
AS2ABB
AS2ABB
C
B
A
2357
SMC60-AST
V
0
4
0 V
2
Potter & Brumfield Potter & Brumfield Potter & Brumfield
+ +
+ +
MC MCMC MC
- - - -
VN30.15/00858
N
L
NL1
230Vac:
MCMC
MC
MC
PE
LanguageSwitch S2Switch S1
GermanBB
EnglishBA
FrenchAB
SpanishAA
Operating instructionsWB50_60-11:FE4105Page 29
E-Total 124.4kWhh-Total 512h
S2
S2
A
A
S1
S1
ABB
ABB
Setting the display languageSMA Technology AG
Page 30WB50_60-11:FE4105Operating instructions
SMA Technology AGMaintenance and care
5 Maintenance and care
Because the Windy Boy 5000 / 6000 can be used outdoors in places that are difficult
to access, it has been constructed for low maintenance.
In the interests of maximum yield, the operator should check, weekly if possible,
under various conditions of wind, if the displays of the Windy Boy 5000 / 6000
indicate plausible normal operation (cf. chapter 3.3.4 "Description of the operational
status" (page19)). Naturally, this information can be obtained by using one of the
communications options.
The cleaning intervals are dependent from the ambient conditions. Make sure that
enough air can flow through the fan guards. With that you can contribute to an
optimum yield of your system.
If the LEDs are so dirty that they can no longer be seen, then they can be cleaned
with a damp cloth. Solvents, abrasives or corrosive liquids must not be used!
A detailed description of how to clean the fans can be found in the installation
manual of the Windy Boy 5000 / 6000.
Operating instructionsWB50_60-11:FE4105Page 31
Maintenance and careSMA Technology AG
Page 32WB50_60-11:FE4105Operating instructions
SMA Technology AGTurbine operation
6 Turbine operation
6.1 Overview
The Windy Boy 5000 / 6000 is a single phase inverter that converts DC current into
AC current and feeds the energy generated by a wind turbine into an existing mains
supply.
The Windy Boy 5000 / 6000 is externally identical to the Sunny Mini Central inverter
for photovoltaic systems.
The Windy Boy 5000 / 6000 inverter has a special operational mode for wind
generators however, which allows performance adjustment to the characteristic
curves of many different manufacturers' generators ("Turbine" operating mode). In
this way maximum yields can be obtained from your wind turbine.
The mechanical power of the wind turbine is presented to the Windy Boy in the form
of a direct, rotation speed variable DC voltage (RPM) and current intensity (torque).
Most small wind turbines have a so-called permanent magnet generator and a
downstream rectifier for converting the variable frequency AC generator voltage into
DC current.
6.2 Characteristic curve function
The "Turbine" operating mode of the Windy Boy 5000 / 6000 uses a programmable
power/voltage curve to regulate the input current depending on the generator
voltage (V/I characteristic curve).
Every wind generator is designed to have an optimum working point for voltage and
current, at different rotational speeds or wind speeds. This behavior is not linear.
The Windy Boy 5000 / 6000 uses an approximation based on a simple ramp
function. The function can be programmed by the user so that it comes close to the
behavior of the wind generator being used and thus provides power adaptation.
Operating instructionsWB50_60-11:FE4105Page 33
Turbine operationSMA Technology AG
The diagram shows the ramp function of a typical Windy Boy 5000 / 6000 power/
voltage curve. The feed-in AC power depending on the DC input voltage of the
Windy Boy is shown here. The adjustable parameters U
U
WindMax are used to adapt the power/voltage curve of the Windy Boy 5000
DC
Start, UDCWindStart and
PV
/ 6000 to the wind generator being used.
Operating Mode: Turbine
Pac / Pac-max
200350400450500550600
330
Vdc V
The correct configuration of the parameters shown in the diagram is absolutely
necessary to guarantee optimum operation with wind generators from different
manufacturers.
The basic parameters of a Windy Boy 5000 / 6000 (factory settings) are shown in
the following table.
Page 34WB50_60-11:FE4105Operating instructions
SMATechnology AGTurbine operation
NameWB 5000WB 6000UnitDescription
UpvStart300
(250 ... 600)
300
(250 ... 600)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 is ready to
perform a mains supply
synchronization.
UdcWindStart 330
(1 ... 800)
330
(1 ... 800)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 is ready to
begin feeding power into the
mains supply.
UdcWindMax 550
(1 ... 800)
550
(1 ... 800)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 begins
feeding maximum power
into the mains supply.
P-Wind-Ramp500
(10 ... 2000)
500
(10 ... 2000)
W/secControls a delayed startup
of the characteristic curve,
only after the Windy Boy
5000 / 6000 has been
switched on. This avoids the
generator being suddenly
presented with a heavy
load.
T-Start10
(5 ... 1600)
T-Stop2
(1 ... 3600)2(1 ... 3600)
10
(5 ... 1600)
secStart Timer Mains
synchronization.
secStop Timer Aborting the
supply of power and
switching off.
The correct configuration of the parameters above is absolutely necessary to
guarantee optimum operation with generators from different manufacturers.
Preconditions for changing the operating parameters are described in chapter 6.4
"General setting example” (page 37).
To perform the configuration process, the DC input voltage must be greater
than <UpvStart> and the Windy Boy 5000 / 6000 must be connected to the
mains supply.
Operating instructionsWB50_60-11:FE4105Page 35
Turbine operationSMA Technology AG
6.3 Characteristic curve operation in "Turbine"
operating mode
Please note: The linear characteristic curve of the Windy Boy 5000 / 6000 only
approximates the actual characteristics of a real wind generator. Consult the
manufacturer of your wind generator for the typical characteristics of your
generator before changing the characteristic curve parameters.
As soon as the DC input voltage defined in the parameter <UpvStart> is reached, the
Windy Boy begins a number of self tests, measurement processes and synchronizes
with the mains supply. If the self tests are successfully completed, and the DC input
voltage remains above the value defined in <UpvStart> for the time defined in <TStart>, the Windy Boy connects to the mains supply.
As soon as the DC input voltage reaches the value defined in <UdcWindStart>, the
Windy Boy begins feeding power into the mains supply. As you can see from the
characteristic curve, the power fed into the mains supply rises with the DC input
voltage.
As soon as the DC input voltage reaches the value defined in the parameter
<UdcWindMax>, the Windy Boy 5000 / 6000 feeds the mains supply with the
maximum possible power. If the input voltage continues to rise, the Windy Boy 5000
/ 6000 continues to feed the mains supply at maximum power.
The characteristic curve ends at the maximum permissible input voltage of the Windy
Boy 5000 / 6000, which must never be exceeded.
If the wind strength is so low that the DC input voltage falls below <UpvStart>, then
the Windy Boy ceases feeding power into the mains supply for the period defined in
<T-Stop>.
If the DC input voltage increases again, then the Windy Boy will again operate
according to the characteristic curve.
If the DC input voltage falls below the internally calculated minimum operating value
of <Vmin>, then there is insufficient energy for the on-board electronics and the
Windy Boy will switch off.
If the DC input voltage lies between <Vmin> and <UpvStart> for the time defined by
<T-Stop>, then the Windy Boy will also switch off.
After the switch-off process, the whole process begins anew.
Only change the operating parameters when you know exactly what you are
doing!
Page 36WB50_60-11:FE4105Operating instructions
SMA Technology AGTurbine operation
6.4 General setting example
Please note that the following example only represents a starting point for operating
with a wind generator.
• <UpvStart> is set to the lowest possible value:
This achieves an early switch-on of the Windy Boy 5000 / 6000.
• <UdcWindStart> is set to the same value of <UpvStart>:
This achieves an early mains supply feed-in. If the wind turbine does not properly
start, or the Windy Boy frequently switches on and off, i t is rec ommended that you
increase <UdcWindStart> in (e.g.) 10 V steps.
• <UdcWindMax> is initially set to approx. 10 % below the maximum MPP voltage
of the Windy Boy 5000 / 6000:
In this case the slope of the ramp function is relatively flat. The maximum output
power is only reached with a relatively high DC input voltage, which avoids
"braking" of the wind generator through excessive power consumption. This
setting is especially suitable in locations with little or weak wind. Once the
properties of the wind generator are known, then the reduction of the
<UdcWindMax> parameter may be necessary, in order to extract the maximum
power from the wind generator even at low DC input voltages (low wind speeds).
The ramp function will then be steeper.
Contact the manufacturer of your wind generator for the typical properties of
your generator (voltage/power characteristic).
• <T-Stop> is set to the maximum value:
Here, the Windy Boy remains connected to the mains supply, even at low DC
input voltage levels, and "waits" for the next gust of wind. This delays an early
switch-off of the Windy Boy.
• <T-Start> is set to the minimum value:
This achieves a reduction of the switch-on time (please observe the regulations of
the energy supplier responsible).
Only change the operating parameters when you know exactly what you are
doing!
Operating instructionsWB50_60-11:FE4105Page 37
Turbine operationSMA Technology AG
Page 38WB50_60-11:FE4105Operating instructions
SMA Technology AGMaintenance and care
7 Maintenance and care
Because the Windy Boy 5000 / 6000 can be used outdoors in places that are difficult
to access, the Windy Boy has been constructed for low maintenance. To guarantee
safe operation, it is usually adequate to check the device visually for damage approximately every two months. It should also be checked if the red LED is illuminated
and, if necessary, remove the fault by referring to chapter 3.3.4 "Description of the
operational status” (page 19).
In the interests of maximum yield, the operator should check, weekly if possible, under various conditions of solar irradiation, if the displays of the Windy Boy 5000 /
6000 indicate plausible normal operation (cf. chapter 3.3.4 "Description of the operational status” (page 19)). Naturally, this information can be obtained by using one
of the communications options.
Cleaning of the Windy Boy is only necessary when the heat dissipation is limited by
dirty cooling fins or a dirty space between the Windy Boy and the wall. The dirt
should be carefully removed with an appropriate soft brush or paintbrush.
If the LEDs are so dirty that they can no longer be seen, then they can be cleaned
with a damp cloth. Solvents, abrasives or corrosive liquids must not be used!
Operating instructionsWB50_60-11:FE4105Page 39
Maintenance and careSMA Technology AG
Page 40WB50_60-11:FE4105Operating instructions
SMA Technology AGExpansions
8 Expansions
As with all inverters in the Sunny Boy family, the Windy Boy 5000 / 6000 can also
be expanded with a range of communications interfaces. This provides the operator
with the possibility of requesting detailed operational data and error messages, for
subsequent analysis on a PC using (e.g.) the free software available from SMA.
The data can currently be transferred in five different ways:
• using Powerline
• using a separate RS485 cable
• using a separate RS232 cable
• using a wireless link (Sunny Beam)
• using a separate USB-Service-Interface (USBPBS)
The wind turbine can be monitored by the Windy Boy 5000 / 6000 in a number of
different ways. SMA offers a range of products for this purpose, allowing you to
install a tailor-made monitoring system for your system. If you require detailed
information about the Windy Boy products, please request the Sunny Family catalog
or visit www.SMA.de. In the following sections the currently available
communications options are schematically described.
8.1 Sunny Data
Sunny Data is a PC program for direct monitoring of
your system. The connection of the Windy Boys to a PC
is described in the following sections.
Operating instructionsWB50_60-11:FE4105Page 41
ExpansionsSMA Technology AG
8.2 Sunny Data via Powerline
"Wireless" communication via the mains power line
(up to 50 Windy Boys)
Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back and
the PC must be equipped with an SWR-COM plug modem. The connection of the PC
using SWR-COM is described in the SWR-COM documentation.
SWR-COM
socket connector
P
h
B
o
e
t
t
r
o
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
max. 50
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
ta
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
PC with
Sunny Data
Control
Powerline
8.3 Sunny Data over RS232
Communication via a cable
(a single Windy Boy 5000 / 6000)
Prerequisites: The Windy Boy must be equipped with an RS232 Piggy-Back, the
connection to the PC usually occurs directly over the COM1 or COM2 port of the PC.
The installation of the RS232 cable is described in the installation instructions of the
Windy Boy 5000 / 6000.
PC with
P
h
B
o
e
t
r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
ic
v
r
d
h
e
s
c
r
t
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Sunny Data
Page 42WB50_60-11:FE4105Operating instructions
SMA Technology AGExpansions
8.4 Sunny Data over RS485
Communication via a cable
(up to 50 Windy Boys)
Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the
connection with the PC usually occurs via an RS485/RS232 interface converter
connected to the COM1 or COM2 port or via an RS485/USB interface converter
connected to the USB port. The installation of the RS232 cable is described in the
installation instructions of the Windy Boy 5000 / 6000.
Interface
Converter
P
h
B
o
e
t
t
r
o
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
max. 50
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
(RS485/RS232
PC with
Sunny Data
RS232
RS485
8.5 Sunny Beam
Simple wireless system monitoring for up to 4 Windy Boys.
Prerequisites: The Windy Boys must be equipped with a wireless Piggy-Back and a
Sunny Beam must be present at an appropriate distance. The installation of the
wireless Piggy-Back is described in the Sunny Beam user manual.
Sunny Beam
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
o
t
o
v
o
l
P
t
a
h
i
o
k
t
-
o
W
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
i
v
c
h
e
r
t
e
t
e
r
r
max. 4
B
e
t
r
i
e
b
O
p
e
r
a
t
i
o
n
E
r
d
s
c
h
l
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Operating instructionsWB50_60-11:FE4105Page 43
ExpansionsSMA Technology AG
8.6 Sunny Data Control over Sunny Beam
Communication with a PC over Sunny Beam
(up to 4 Windy Boys)
Prerequisites: All 4 Windy Boys must be equipped with a wireless Piggy-Back and
accessible to Sunny Beam for system monitoring. The Sunny Beam is connected to the
PC via an USB cable. The installation of the wireless Piggy-Backs and the connection
to the PC is described in the Sunny Beam user manual.
Sunny Beam
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
o
t
o
v
o
l
P
t
a
h
i
o
k
t
-
o
W
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
i
v
c
h
e
r
t
e
t
e
r
r
max. 4
B
e
t
r
i
e
b
O
p
e
r
a
t
i
o
n
E
r
d
s
c
h
l
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
USB
PC with
Sunny Data
8.7 Sunny Boy Control Light
The simple data logger for systems with up to 10 Windy Boys. The connection
between the Sunny Boy Control Light and the Windy Boys occurs via Powerline.
Prerequisites: The Windy Boys must be equipped with a Powerline Piggy-Back. The
installation is described in detail in the Sunny Boy Control Light documentation.
Sunny Boy
Control
PAC
Light
1273
W
Ph
B
o
e
t
r
to
Ph
B
otovo
e
t
r
i
e
b
O
lta
Ph
p
e
r
ik-W
otovo
a
t
i
o
n
ech
lta
ic inver
selr
E
ic
r
d
hte
s
c
h
ter
l
r
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Ph
B
ot
e
t
r
i
o
e
b
vo
O
lt
P
p
a
ho
e
r
ik
a
t
t
-W
i
ov
o
n
o
e
lta
c
hs
ic
el
i
ri
nv
E
ch
r
d
e
s
r
c
te
h
te
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
max. 10
i
e
b
vo
O
l
P
ta
p
h
e
r
ik-
ot
a
t
i
ov
o
W
n
ol
e
c
ta
h
i
se
c
lr
in
E
ic
ve
r
d
hte
s
r
c
h
te
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Powerline
Page 44WB50_60-11:FE4105Operating instructions
SMA Technology AGExpansions
8.8 Sunny Boy Control
The simple data logger for systems with up to 50 Windy Boys. The connection
between the Sunny Boy Control and the Windy Boys can be achieved as follows:
Powerline - "Wireless" communication via the mains power line
Prerequisites: All the Windy Boys must be equipped with a Powerline Piggy-Back.
Sunny Boy
P
h
B
o
e
t
t
r
o
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
max. 50
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Powerline
RS485 Communication via a cable
Prerequisites: All Windy Boys must be equipped with an RS485 Piggy-Back, the
Sunny Boy Control must be equipped with an RS485 Piggy-Back on the "COM1 Sunny Boy" interface.
P
h
B
o
e
t
t
r
o
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
P
h
B
o
e
t
t
r
o
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
max. 50
i
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
v
c
r
d
h
e
s
r
t
c
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Control
PA
C
1
2
7
3
W
Sunny Boy
Control
PA
C
1
2
7
3
W
RS485
8.9 Sunny Boy Control Plus
The data logger for systems with up to 50 Windy Boys, an additional interface for
connection to PCs or large displays and additional connection possibilities for digital
and analog inputs and outputs. Prerequisites: See Sunny Boy Control.
Operating instructionsWB50_60-11:FE4105Page 45
ExpansionsSMA Technology AG
8.10 Sunny Data Control
This is a PC program for system monitoring and visualization on a PC for systems with
a Sunny Boy Control.
Prerequisites: A system with a Sunny Boy Control, Sunny Boy Control Plus or Sunny
Boy Control Light with a connection to a PC.
Connection also
possible via Modem
P
h
B
o
e
t
r
to
i
e
b
vo
O
lta
P
p
h
e
r
i
o
a
k-
t
to
i
o
W
n
vo
ec
lt
a
hse
ic
l
i
r
n
E
i
c
ve
r
d
h
s
c
r
te
h
te
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
.
.
.
P
ho
B
e
t
r
tov
i
e
b
olt
O
Ph
p
ai
e
r
oto
a
k-
t
i
o
W
n
vo
ec
lt
aic
hs
el
inv
rich
E
r
d
er
s
c
te
h
t
er
l
r
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Ph
B
o
e
t
r
t
i
o
e
b
v
olt
O
Pho
p
aik
e
r
a
t
to
-W
i
o
n
vo
ech
lta
ic i
s
elr
nve
E
ich
r
d
s
c
r
te
h
te
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
.
.
.
Data evaluation
with Excel
Visualization
with Sunny Data
Control
Remote Desktop
Internet
presentation
with
SDC-Agent
Internet
presentation
with
SMA-Portal
The connection between the PC and the Sunny Boy
Control can occur via modem if required. Large
systems with more than 50 Windy Boys can be
monitored by coupling several Sunny Boy Controls
together.
Page 46WB50_60-11:FE4105Operating instructions
SMA Technology AGExpansions
8.11 Sunny WebBox
The Sunny WebBox is a versatile inexpensive platform for system visualization
directly on a PC or via the Internet using the Sunny Portal. The Sunny WebBox will
be available from the 2nd quarter of 2005.
PC via
Telephone
P
h
B
o
e
t
r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
c
v
r
d
h
e
s
c
t
r
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
Sunny
.
.
.
RS485
(
RS232*)
Powerline*)
(
P
h
B
o
e
t
r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
c
v
r
d
h
e
s
c
t
r
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
(Radio*)
WebBox
Connection
Hub
Memory Card
External
Sensors
LAN
P
h
B
o
e
t
r
t
i
o
e
b
v
o
O
l
P
t
p
a
h
e
r
i
o
a
k
t
t
-
i
o
o
W
n
v
o
e
l
c
t
a
h
i
s
c
e
l
i
r
n
E
i
c
v
r
d
h
e
s
c
t
r
e
h
t
e
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
LAN
LAN
LAN
Modem
Sunny
Portal
(Internet)
External
Display
PC
* Communication with Sunny WebBox via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
Operating instructionsWB50_60-11:FE4105Page 47
ExpansionsSMA Technology AG
8.12 Sunny Portal
The Sunny Portal is a high performance interface from
SMA for the monitoring and presentation of your
system in the Internet. Details can be obtained from the
Sunny Family catalog or directly under www.SUNNYPORTAL.de.
8.13 Sunny TV
Sunny TV is an accessory for Windy Boy inverters, which displays the system data
and the current performance on a monitor or video projector. It is suitable for the
presentation of large systems in lobbies and entrance halls as well as in private
areas.
Video ProjectorTV Set
S
S
u
u
n
n
n
n
y
y
T
T
V
Sunny TV
Sunny TV
Pac = 7,450 W
P
h
B
o
e
t
to
r
i
e
b
vo
O
l
Ph
tai
p
e
r
o
a
k-
t
to
i
o
W
n
v
ol
e
c
ta
h
ic
se
i
lri
nv
E
ch
r
d
e
s
r
c
te
h
te
l
r
u
E
r
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
.
.
.
Pac = 7,450 W
Sunny TV
RS485
(
P
ho
B
e
t
to
r
i
e
b
vo
O
lta
P
p
hot
e
r
ik-W
a
t
i
o
o
n
vo
e
lta
ch
ic i
se
lri
nv
E
chter
r
d
e
s
r
c
h
ter
l
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
RS232*)
Powerline*)
(
(Radio*)
Video-Out
V
P
P
a
a
c
c
=
=
7
7
,4
,4
5
5
0
0
W
W
PC Monitor
S
u
n
n
y
T
V
P
a
c
=
7
,4
5
0
W
Su
nny
TV
Configuration
P
hot
B
e
t
r
ovolta
i
e
b
O
P
p
hoto
e
r
ik-W
a
t
i
o
n
volta
echs
ic inv
elri
E
ch
r
d
er
s
c
te
h
t
er
l
r
u
E
s
s
a
r
t
h
F
a
u
l
t
S
t
ö
r
u
n
g
F
a
i
l
u
r
e
* Communication with Sunny TV via RS232, Powerline or using
a wireless link will be possible at the end of 2005 or later.
with PC
Page 48WB50_60-11:FE4105Operating instructions
SMA Technology AGTechnical data
9 Technical data
9.1 Windy Boy 5000
9.1.1 DC connection data
Max. input open circuit voltageV
Input voltage, MPP rangeV
Nominal DC operating voltageV
Max. input currentI
Max. input powerP
Recommended generator power
DC 0
DC
DC nom
DC max
DC max
P
turb max
at 5,000 full-load hours / year
Recommended generator power
P
turb max
at 2,500 full-load hours / year
All-pole isolator on the DC input
side
Overvoltage protectionThermally monitored varistors
DC voltage rippleU
SS
Personal protectionInsulation monitoring (Riso > 1 MΩ)
Own consumption in standby
cos j1
(based on the current's
fundamental frequency)
Overvoltage categoryIII
Test voltage (50 Hz)2 kV (1 s routine testing / 60 s type
testing)
Test surge voltage4 kV (1.2 / 50 µs) type testing
(serial interface: 6 kV)
Own consumption in standby
0.25 W
mode
Operating instructionsWB50_60-11:FE4105Page 53
Technical dataSMA Technology AG
9.2.3 General data
For a detailed description of the device, see chapter 3 "Unit description” (page 13)
of this manual.
General data
Protection category per DIN EN 60529IP54
Dimensions (w x h x d)430 mm x 600 mm x 450 mm
Weight63 kg (approx.)
External interfaces
Data transfer (mains cable)Optional
Data transfer (separate data cable)optional, RS232 / RS485,
electrically separated
Data transfer (wireless)Optional
Efficiency
Max. efficiencyη
max
The efficiency of the Windy Boy 5000 / 6000 is heavily dependent on the DC input
voltage. The lower the input voltage, the higher the efficiency.
> 96,0 %
96
95
94
93
92
Overall Efficiency [%]
91
90
020003000400050006000
Page 54WB50_60-11:FE4105Operating instructions
250 V
300 V
400 V
500 V
Windy Boy 6000
1000
Output Power [W]
SMA Technology AGGeneral information
10 General information
10.1 Measurement channels and messages
If your Windy Boy 5000 / 6000 is equipped with a communications component, then
numerous measurement channels and messages can be consulted. These can be
useful for both performance improvement and for fault prevention.
The following abbreviations apply:
BFR: Operation control unit
SRR: Current control unit
E-TotalTotal amount of feed-in energy
FacGrid frequency
Fehler / ErrorFault type display under "Disturbance" status
h-TotalTotal hours of mains supply feed-in operation
Iac-IstMains supply current
IpvDC current
Netz-Ein /
Power on
PacMains supply performance provided
RisoInsulation resistance of the system to the mains supply connection
Seriennummer /
Serial number
Status / StateDisplay of the current operational status
Uac / VacGrid voltage
Upv-Ist / VpvDC input voltage
Upv-Soll /
Vpv-Setpoint
ZacMains supply impedance
Total number of mains supply switch-ons
Serial number of the Windy Boy
Nominal DC voltage
The measurement channels provide information in German (e.g."Fehler“), or in
English (e. g. "Error“), depending on which software you are using (Sunny
Data or Sunny Data Control).
Operating instructionsWB50_60-11:FE4105Page 55
General informationSMA Technology AG
10.1.1 Status messages
The Windy Boy 5000 / 6000 produces a range of status messages, depending on
the mode in which it is currently operating. The status messages can vary, depending
on the type of communications system you are using.
DeratingOvertemperature in inverter ("WR"). The Windy Boy 5000 /
6000 reduces its performance to avoid overheating the device. To
avoid unnecessary yield losses, the configuration and string size
should be checked. Check if the Windy Boy 5000 / 6000 can be
located in a better position with better ventilation, thus providing
better heat dissipation.
MppThe Windy Boy 5000 / 6000 is operating in MPP mode. The
Windy Boy 5000 / 6000 takes the highest possible performance
from the PV generator. MPP is the standard display when
operating with normal sunshine (PV operation only).
Island ModeThe Windy Boy 5000 / 6000 is in Island Mode. This mode is
specially conceived for operation in a stand alone power system
with a Sunny Island as network controller. More information
about this topic can be obtained from the Sunny Island operating
manual under the category "Droop Mode".
grid mon.Testing the mains supply status (mains impedance), relay tests etc.
This message appears only during the startup phase, before the
Windy Boy 5000 / 6000 is connected to the mains supply. This
message mainly appears when there is little or no wind.
OffsetOffset compensation of the measurement electronics
disturb.Fault (see table "Fault messages")
This fault occurs for reasons of safety and prevents the Windy Boy
5000 / 6000 from connecting to the mains supply. This mode can
also be manually set.
StopInterruption of operation after a fault. This status can also be
manually set.
Turbine ModeDefault setting for Windy Boy 5000 / 6000 inverters. The input
voltage is converted according to the V/I function U
U
Start and UDCWindMax. See chapter 6 "Turbine operation”
DC
(page 33).
V-ConstConstant voltage operation (the input voltage is predefined. The
Windy Boy 5000 / 6000 operates in neither MPP mode nor
Turbine mode). In some cases, this can be set as the operational
mode.
waitingThe switch-on conditions are not (yet) satisfied.
PV
Start,
Page 56WB50_60-11:FE4105Operating instructions
SMA Technology AGGeneral information
10.1.2 Windy Boy 5000 / 6000 Operating
parameters
Unauthorized changes to the operating parameters may result in:
• Injury or accidents as a result of changing the internal safety
routines in the Windy Boy 5000 / 6000,
• Voiding of the Windy Boy 5000 / 6000 operating approval
certificate
• Voiding of the Windy Boy 5000 / 6000 warranty
Never change the parameters of your Windy Boy 5000 / 6000
without explicit authorization and instructions.
Name UnitValue range
Betriebsart /
Operating
Mode
DefaultGER/ENSUsed for setting the country specific
dFac-MAXHz/s0.005 ... 4,00,25Maximum "Mains frequency change"
5000 / 6000:
MPP: Maximum Power Point
UKonst: Constant voltage mode
(Desired voltage is defined in "UsollKonst")
Stopp: Disconnection from mains
supply, no operation
Turbine: Operating mode for wind
turbines, the input voltage is converted
according to the V/I function defined by
Start, UDCWindStart and
U
PV
U
WindMax.
DC
information.
before the mains monitoring system
disconnects the device from the mains
supply.
before the mains monitoring system
disconnects the device from the mains
supply.
hours of operation (h_Total) for the
Windy Boy. This change may be
necessary when you exchange your
Windy Boy 5000 / 6000 and want to
use the data from the old device.
Delta+) and below (Fac-Delta-) the
mains frequency of 50 Hz, before the
mains monitoring system disconnects the
device from the mains supply.
Operating instructionsWB50_60-11:FE4105Page 57
General informationSMA Technology AG
Name UnitValue range
(WB 5000 /
WB 6000)
Factory
settings
(WB 5000
/WB
Description
6000)
I-NiTestmA0 ... 2500016000Activation (16000) and deactivation (0)
of the automatic leakage current
measurement. This parameter only
functions when the Windy Boy is
deactivated (disconnected on the AC
side) or in "Stop" mode.
Inst.-CodeParameters for mains supply monitoring
can only be changed after entering the
"SMA grid guard" password.
KI-Wind-Reg0 ... 0,250,005Control speed (only possible in Turbine
KP-Wind-Reg0 ... 0,250,117Control speed (only possible in Turbine
P-Wind-RampW/s10 ... 2000500 Slow startup during mains supply
mode!)
mode!)
connection (only possible in Turbine
mode!)
Speicher-funktion /
Memory
function
Default,
Parameter,
Reset
Betriebsdaten,
Reset Fehler
noneDefault parameter: Returns all
parameter values to the factory setting.
Reset Betriebsdaten: Returns all user
level parameter values to the factor y
setting.
Reset Fehler: Resets a permanent fault.
Speichern/
store
Permanent,
volatile
PermanentPermanent: Modified parameters are
stored in the EEPROM and can be used
even when the Windy Boy has been
restarted.
Volatile: Prevents the parameters from
being stored in the EEPROM, the
parameters are stored until the next
restart.
T-Startsec5 ... 30010Start timer for mains supply
synchronization. (only possible in
Turbine mode!)
T-Stopsec1 ... 36002Stop timer for stopping operation and
switching off. (only possible in Turbine
mode!)
Uac-Min /
Vac-Min
Uac-Max /
V180 ... 300198Lower (Uac-Min) and upper (Uac-Max)
limits of the acceptable AC voltage (self
V180 ... 300260
contained power system recognition).
Vac-Max
WindMaxV1 ... 800 550 UDCWindMax represents the highest
U
DC
point of the function (please read more
about this topic in chapter 6 "Turbine
operation” (page 33)). (only possible in
Turbine mode!)
Page 58WB50_60-11:FE4105Operating instructions
SMA Technology AGGeneral information
Name UnitValue range
UDCWindStartV1 ... 800330UDCWindStart represents the lowest
Usoll-Konst /
VconstSetpiont
StartV250 ... 600300UPVStart is the parameter defining the
U
PV
V250 ...600600Desired DC voltage for constant
(WB 5000 /
WB 6000)
Factory
settings
(WB 5000
/WB
6000)
Description
point of the function (please read more
about this topic in chapter 6 "Turbine
operation” (page 33)). (only possible in
Turbine mode!)
operational voltage. These parameters
are only important when the
"Betriebsart" parameter is set to UKonst.
voltage at which the Windy Boy is
capable of connecting to the system.
180 V is the recommended voltage for
the Windy Boy 5000 and the Windy
Boy 6000. Reducing this voltage
parameter can lead to numerous
unnecessary connection attempts.
Increasing this voltage parameter can
lead to energy losses since the Windy
Boy does not immediately connect to the
system.
The following parameters are displayed in the parameter list but cannot be modified:
NameUnitValue range
PlimitW5000 / 60005000 / 6000Upper limit for AC output power
SMA-SNSerial number of the Windy Boy 5000
Software-BFR /
Firmware-BFR
Software-SRR /
Firmware-SRR
(WB5000/
6000)
Factory
settings
(WB5000/
6000)
Description
/ 6000
Firmware version of the operation
control unit (BFR)
Firmware version of the current control
unit (SRR)
Operating instructionsWB50_60-11:FE4105Page 59
General informationSMA Technology AG
10.2 Fault messages
If a fault develops, the Windy Boy 5000 / 6000 generates a message, which is
dependent on the operational mode and the type of fault.
Fault codeDescription
Bfr-Srr
NUW-FAC
NUW-UAC
NUW-ZAC
dZac-Bfr
dZac-Srr
EEPROMA data transfer fault occurred during reading or writing of data from
EEPROM
dBh
EeRestoreOne of the duplicate data sets in the EEPROM is defective and has
Fac-Bfr
Fac-Srr
Internal measurement comparison fault: the Windy Boy 5000 /
6000 found a too large difference between values provided by the
BFR and SRR. Contact SMA.
The changes in mains impedance exceed the permissible range
("Bfr" or "Srr" is an internal message that has no meaning for the
user).
The Windy Boy 5000 / 6000 disconnects from the mains supply or
stand-alone grid, to avoid potential damage. If possible, check the
mains impedance and check how often major deviations occur. If
repeated variations occur and this is causing "dZac-Bfr" or "dZacSrr" faults, ask the electricity provider if they agree to a modification
of the operating parameters. Discuss the proposed parameters with
the SMA hotline.
the EEPROM. The data is not relevant for safe operation - this fault
has no effect on performance.
Data EEPROM is defective. The device has switched itself off
because the loss of important functions has disabled the Windy Boy
5000 / 6000. Contact SMA.
been reconstructed without loss of data.
The mains frequency has exceeded the permissible range ("Bfr" or
"Srr" is an internal message that has no meaning for the user). The
Windy Boy 5000 / 6000 disconnects from the mains supply or standalone grid, to avoid potential damage. Check the mains frequency
and mains connections on the Windy Boy 5000 / 6000. If the mains
frequency lies outside the permissible range because of local
conditions, ask the electricity provider if they agree to a modification
of the operating parameters.
If the mains frequency lies within an acceptable range and "Fac-Bfr"
or "Fac-Srr" faults are still being displayed, please contact the SMA
hotline.
Page 60WB50_60-11:FE4105Operating instructions
SMA Technology AGGeneral information
Fault codeDescription
ImaxOvercurrent on the AC side. This fault code is displayed if the current
in the AC network is larger that specified. Check your system
configuration and the mains supply conditions.
K1-Schliess /
K1-Close
Fault during relay test. Please contact SMA if this fault occurs often
or repeatedly.
K1-Trenn /
K1-Open
NUW-MesMeasurement difference between BFR and SRR: Fac, Uac or Zac.
OffsetFault in the acquisition of measurement data. Contact SMA if this
fault occurs frequently.
Rechner /
NuW-
Functional fault in one of the two microcontrollers. Please contact
SMA if this fault occurs often or repeatedly.
Timeout
RisoA grounding fault exists or one of the thermally monitored varistors
on the DC input is defective as a result of overvoltage. Consult
trained electrical personnel to correct the fault. You can find
Instructions on how to change the varistors in the "Installation
manual".
ROMThe Windy Boy 5000 / 6000 firmware is faulty. Contact SMA if this
fault occurs frequently.
Uac-Bfr /
Vac-Bfr
The mains voltage has exceeded the permissible range ("Bfr" or "Srr"
is an internal message that has no meaning for the user). The Uac
fault can have the following causes:
Uac-Srr /
Vac-Srr
• Mains supply disconnected (circuit breaker or fuse)
• Broken AC cable or
• AC cable has a high internal resistance
For reasons of safety, the Windy Boy 5000 / 6000 disconnects itself
from the mains supply. Check the mains voltage and mains
connections on the Windy Boy 5000 / 6000. If the mains voltage lies
outside the acceptable range because of local conditions, ask the
electricity provider if the voltage can be adjusted at the feed-in point
or if they agree to changes in the values of the monitored
operational limits.
If the mains voltage lies within an acceptable range and "Uac-Bfr" or
"Uac-Srr" faults are still being displayed, please contact the SMA
hotline.
Operating instructionsWB50_60-11:FE4105Page 61
General informationSMA Technology AG
Fault codeDescription
UpvMax /
Over voltage on DC input
Vpv-Max
Immediately disconnect the DC input of the Windy Boy 5000 /
6000. The Windy Boy 5000 / 6000 may otherwise be damaged
seriously! Check the configuration of your system and measure the
DC voltage before reconnecting the Windy Boy 5000 / 6000 to the
DC voltage.
WatchdogFault in the program code flow monitoring.
Zac-Bfr/
Zac-Srr
The mains impedance has exceeded the permissible range ("Bfr“ or
"Srr“ is an internal message that has no meaning for the user). The
Windy Boy 5000 / 6000 disconnects from the mains supply or stand-
alone grid, to avoid potential damage. The impedance is calculated
from the mains supply impedance and the impedance of the mains
connection cable (AC cable) of the Windy Boy 5000 / 6000.
Check the mains impedance and mains connections on the Windy
Boy 5000 / 6000. Use a mains connection cable with an adequate
cross section (= low impedance), and observe the advice to this
effect in the installation guide in chapter 4.3. If the mains impedance
is still too high, then ask the electricity provider if the characteristics
of the mains supply at the feed-in point can be altered.
We declare that the above specified devices are compliant with the regulations of the European
Community, in terms of the design and the version fabricated by SMA. This especially applies
for the EMC Regulation defined in 89/336/EWG and the low voltage regulation defined in
73/23/EWG.
The devices are compliant with the following standards:
EMC:
Emission:DIN EN 61000-6-3: 2002-08
Utility Interference:DIN EN 61000-3-11: 2001-04
Immunity:DIN EN 61000-6-1: 2002-08
Safety:DIN EN 50178: 1998-04
Semiconductor-Converter:DIN EN 60146-1-1: 1994-03
DIN EN 61000-6-4: 2002-08
DIN EN 55022: 2003-09, Class B
DIN EN 61000-3-12: 2004-06 (Draft)
DIN EN 61000-6-2: 2002-08
The above mentioned devices are therefore marked with a CE sign.
The Windy Boy 5000 / 6000 string inverter is equipped with the "SMA grid guard"
independent disconnection device and it is covered by the industrial trade association
"SMA grid guard" import certificate.
Page 64WB50_60-11:FE4105Operating instructions
SMA Technology AGStand-alone systems
11 Stand-alone systems
The Windy Boy 5000 / 6000 is suitable for use in stand-alone systems based on the
Sunny Island. The Windy Boy 5000 / 6000 requires extra settings for this to ensure
optimum operation and also to achieve deactivation of the standard mains supply
monitoring settings. Please obtain all further relevant information from the Sunny
Island manuals.
Sunny Island
4248
or
Sunny Boy
Windy Boy
AC
bus
Consumers
Generator
Public Utility
Mini CHP
Operating instructionsWB50_60-11:FE4105Page 65
Stand-alone systemsSMA Technology AG
Page 66WB50_60-11:FE4105Operating instructions
SMA Technology AGContact
12 Contact
If you have any questions or technical problems concerning the Windy Boy 5000 /
6000, please contact our service hotline. Please have the following information
available when you contact SMA:
• Inverter type
• Type of wind turbine and AC/DC converter
• Type of overvoltage protection
• Communication
• Serial number of the Windy Boy 5000 / 6000
Address:
SMA Technologie AG
Hannoversche Strasse 1 - 5
34266 Niestetal
Germany
International Metro Center,
Building A, City Square No. Jia 3,
Shilipu Road, Changyang District
100025 Beijing, P.R. China
Tel. +86 10 65 58 78 15
www.SMA-CHINA.com
SMA America, Inc.
12438 Loma Rica Drive, Unit C
Grass Valley, CA 95945, USA
Tel. +1 530 273 4895
www.SMA-AMERICA.com