This g uide de scribes the ins tallat ion and com missio ning of the Ambient Temperature Sensor. Store this
guide where it will be accessible at all times.
1.1 Area of Validity
This guide applies to the TEMPSENSOR-AMBIENT upgrade kit.
1.2 Target Group
This guide is for electrically skilled persons.
1.3 Symbols Used
The following types of safety precautions and general information appear in this document:
DANGER!
"DANGER" indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING!
"WARNING" indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION!
"CAUTION" indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
NOTICE!
"NOTICE" indicates a situation that can result in property damage, if not avoided.
Information
Information provides tips that are valuable for the optimal installation and operation of
your product.
4TempsensorAmb-IEN110610Installation Guide
SMA Solar Technology AGSafety
2 Safety
2.1 Appropriate usage
The TEMPSENSOR-AMBIENT Ambient Temperature Sensor consists of a PT100 measuring resistor
that is accommodated in an lP65 plastic enclosure. The TEMPSENSOR-AMBIENT Ambient
Temperature Sensor enables measurements in a 4-wire system. The measurement range of the
Ambient Temperature Sensor is between –30 °C and +80 °C. Connect the sensor to Sunny
SensorBox for further processing of the ambient data.
The Ambient Temperature Sensor is suitable for use only with original SMA accessories or with
accessories recommended by SMA Solar Technology AG.
Appropriate usage also includes observing all further documentation relating to this device and its
components.
2.2 Safety Precautions
NOTICE!
Destruction of the PV plant by a lightning strike.
All devices installed on a rooftop must be integrated into the existing lightning protection
of the PV plant.
Installation GuideTempsensorAmb-IEN1106105
Scope of SupplySMA Solar Technology AG
3 Scope of Supply
PositionQuantity Description
A1TEMPSENSOR-AMBIENT (Ambient Temperature Sensor)
B2Screw
C2Screw anchor
6TempsensorAmb-IEN110610Installation Guide
SMA Solar Technology AGAssembly
4 Assembly
4.1 Selecting the Mounting Location
• The Ambient Temperature Sensor must be assembled
with the cable gland pointing downwards in order to
pr eve nt w ate r fr om a ccu mul ati ng o n th e ca ble gla nd.
• Protect the Ambient Temperature Sensor from severe
contamination and spray.
• See adjacent image for recommended alignment of
the Ambient Temperature Sensor.
• Select an installation location which is in shade
throughout the entire day.
• Make sure that heat cannot accumulate at the
installation site.
• Please observe the maximum cable length of 30 m.
4.2 Assembling the Ambient Temperature Sensor
1. Undo four bolts on the Ambient Temperature Sensor enclosure and remove the lid.
2. Determine the mounting location and mark it. In the process, observe the mounting area
(see image).
3. Fasten the Ambient Temperature Sensor enclosure using the screws supplied.
☑ The Ambient Temperature Sensor has been assembled.
Installation GuideTempsensorAmb-IEN1106107
Electrical ConnectionSMA Solar Technology AG
5 Electrical Connection
4-wire system
To offset measuring errors that occur due to
cable resistance, connect the temperature
sensor via a 4-wire system. This type of
conne ction ensures th e curr ent fee d and v oltage
measurement are performed by separate pair cables. The length of the cable must not
exceed 30 m.
Cabling Recommendations
NOTICE
Damage to Ambient Temperature Sensor due to ingress of fluids
Use only cables with a minimum diameter of 4.5 mm
Sensor. This prevents the Ambient Temperature Sensor from being damaged by any ingress
of fluids (e.g. by rain or snow).
The cable length and quality have an effect on the signal quality. To achieve a good quality signal,
observe the following instructions regarding cabling:
Outdoors
For the outdoors, use a cable with the following key properties:
• Cross-section: at minimum 4 x 0.25 mm
2
, at minimum 4 x AWG 24
• Outer cable diameter: at minimum 4.5 mm, at maximum 7 mm
• UV-resistant
SMA Solar Technology AG recommends the following cable types:
• Lappkabel: UNITRONIC S-LifY11Y 4 x 0.34 mm
• Lappkabel UL-listed: UNITRONIC S-LifY11Y 4 x 0.34 mm
Indoors
It is permitted to use non-UV-resistant cables outdoors that are protected by a UV-resistant cable
channel if the cables comply with aforementioned specifications.
SMA Solar Technology AG recommends the following cable types:
• Lappkabel: Unitronic LiYY 4 x 0.5 mm
2
• Lappkabel UL-listed: UNITRONIC LiYY UL/CSA 4 x AWG22/7
• Helukabel: TRONIC LiYY 4 x 0.5 mm
2
2
to connect the Ambient Temperature
2
2
8TempsensorAmb-IEN110610Installation Guide
SMA Solar Technology AGElectrical Connection
5.1 Connecting Cables to the Ambient Temperature Sensor
1. Undo the screws on the Ambient Temperature Sensor enclosure and
remove the lid.
2. Remove the cable glands on the Ambient Temperature Sensor.
3. Remove the small interior protection plates. Make sure that the interior
seal does not fall out.
4. Screw the cable gland halfway onto the enclosure.
5. Introduce the cables through the cable glands of the Ambient
Temperature Sensor.
6. Connect wires to the screw terminals in 4-wire technology, see image on
the right.
7. Note the color of the wires:
I+__________________________
V+__________________________
V-__________________________
I-__________________________
8. Fasten the cable gland of the Ambient Temperature Sensor to the Ambient Temperature Sensor
enclosure by hand (torque: 0.8 Nm).
9. Connect the plug from the lid of the Ambient
Temperature Sensor with the screw terminals, see
image on the right. The polarity of the cables is userdefined.
10. Fasten the lid of the Ambient Temperature Sensor to
the enclosures using the screws.
☑ The cable is connected to the Ambient Temperature
Sensor.
Installation GuideTempsensorAmb-IEN1106109
Electrical ConnectionSMA Solar Technology AG
5.2 Connecting the Ambient Temperature Sensor to the
Sunny SensorBox
The Ambient Temperature Sensor is connected to the "F6: TmpAmp" terminal of the Sunny SensorBox.
Proceed as follows:
NOTICE!
Damage to the Sunny SensorBox due to ingress of fluids
• When working outdoors, make sure that no fluids (e.g. rain or snow) enter the open
Sunny SensorBox.
• When inserting and removing the cable
through the cable gland, make sure that
the grommet fits correctly into the cable
gland.
NOTICE!
Damage to the Sunny SensorBox due to porous rubber seals
The rubber seal in the Sunny SensorBox lid becomes porous over the course of time, and
will no longer provide a tight seal if the Sunny SensorBox is then opened. If you open the
Sunny SensorBox after an operating lifetime of more than 5 years, e.g. for upgrading the
device, the rubber seal in the Sunny SensorBox lid must be replaced with a new one. In this
event, order a replacement seal prior to maintenance work.
1. Open the lateral flaps of the Sunny SensorBox using the recesses.
2. Undo the screws in the corners of the Sunny SensorBox and open the enclosure lid towards the
left. The lid is connected to the lower shell by hooks.
3. Unscrew the cable gland sleeve nut on the bottom
center of the Sunny SensorBox and remove the
filler-plugs.
4. Route the Ambient Temperature Sensor cable
through the sleeve nut and fasten the cable glands
of the Sunny SensorBox.
10TempsensorAmb-IEN110610Installation Guide
SMA Solar Technology AGElectrical Connection
5. Remove resistance and bridge at the "F6: TmpAmb"
terminal in the Sunny SensorBox.
6. Connect the Ambient Temperature Sensor to the
"F6: TmpAmb" terminal of the Sunny SensorBox.
Please note the indicated wire colors (see page 9).
7. Check that the cable gland grommet is correctly in
place.
8. Fasten the lock nut onto the cable gland manually
to affix the cable (torque: 0.8 Nm).
9. Lay the cable using suitable fixing material.
10. Place the Sunny SensorBox enclosure lid on the
lower enclosure shell.
11. Fasten screws manually (torque: 1 Nm) into the
lower enclosure shell.
☑ The Ambient Temperature Sensor has been
connected to the Sunny SensorBox.
Installation GuideTempsensorAmb-IEN11061011
DecommissioningSMA Solar Technology AG
6 Decommissioning
6.1 Disassembling the Ambient Temperature Sensor
1. Remove the Ambient Temperature Sensor cable from the Sunny SensorBox.
2. Insert resistance (100 Ohm) and the bridge to
terminal "F6: TmpAmb" in the Sunny SensorBox.
3. Undo screws on the Ambient Temperature Sensor enclosure and remove the lid.
4. Remove the enclosure from the wall.
☑ The Ambient Temperature Sensor has been disassembled.
6.2 Disposing of the Ambient Temperature Sensor
At the end of its life cycle, dispose of the Ambient Temperature Sensor in accordance with the
applicable disposal regulations for electronic waste at the installation location at the time.
Alternatively, return it labeled as "ZUR ENTSORGUNG" ("for disposal") to SMA Solar Technology
AG, at your own expense.
12TempsensorAmb-IEN110610Installation Guide
SMA Solar Technology AGTechnical Data
7 Technical Data
General Data
Width x height x depth100 mm x 52 mm x 67 mm
Measuring shuntPT100
Mounting locationoutdoors
Environmental Conditions
Ambient temperature− 30 °C … +80 °C
Protection ratingIP65
Connection cable
Maximum cable length30 m
Measurement Range and Tolerances
Toleranceat maximum ± 0.7 °C (class B)
Measurement range− 30 °C … +80 °C
*)
*)
not included in SMA scope of supply.
Installation GuideTempsensorAmb-IEN11061013
ContactSMA Solar Technology AG
8 Contact
If you have technical problems concerning our products, contact the SMA Serviceline. We need the
following information in order to provide you with the necessary assistance:
• Ambient temperature sensor model
• Sunny SensorBox firmware version
• Sunny WebBox firmware version
• Measured values of the Ambient Temperature Sensor
The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or
in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the
purposes of evaluating the product or its correct implementation is allowed and does not require permission.
Exclusion of liability
The general terms and conditions of delivery of SMA Solar Technology AG shall apply.
The content of these documents is continually checked and amended, where necessary. However, discrepancies cannot be
excluded. No guarantee is made for the completeness of these documents. The latest version is available online at www.SMA.de
or from the usual sales channels.
Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the following:
• Damages during transportation
• Improper or inappropriate use of the product
• Operating the product in an unintended environment
• Operating the product whilst ignoring relevant, statutory safety regulations in the deployment location
• Ignoring safety warnings and instructions contained in all documents relevant to the product
• Operating the product under incorrect safety or protection conditions
• Altering the product or supplied software without authority
• The product malfunctions due to operating attached or neighboring devices beyond statutory limit values
• In case of unforeseen calamity or force majeure
The use of supplied software produced by SMA Solar Technology AG is subject to the following conditions:
• SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by
SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.
• Supplied software not developed by SMA Solar Technology AG is subject to the respective licensing and liability agreements
of the manufacturer.
SMA Factory Warranty
The current guarantee conditions come enclosed with your device. These are also available online at www.SMA.de and can be
downloaded or are available on paper from the usual sales channels if required.
Trademarks
All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand
is not a registered trademark.
The Bluetooth
Solar Technology AG is under license.