SMA SUNNY TRIPOWER 12000TL-US, SUNNY TRIPOWER 20000TL-US, SUNNY TRIPOWER 30000TL-US, SUNNY TRIPOWER 15000TL-US, SUNNY TRIPOWER 24000TL-US Installation Manual

STPTL-US-10-IA-xx-20 | 98-109400.04 | Version 2.0
SUNNY TRIPOWER 12000TL-US / 15000TL-US / 20000TL-US / 24000TL-US / 30000TL-US
STPTL-US-10-IA-xx-202
ENGLISH Installation Manual...................................................................3
FRANÇAIS Instructions d’installation..................................................... 160
Legal Provisions
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 3
Legal Provisions
No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, be it electronic, mechanical, photographic, magnetic or otherwise, without the prior written permission of SMA Solar Technology America LLC.
Neither SMA Solar Technology America LLC nor SMA Solar Technology Canada Inc. makes representations, express or implied, with respect to this documentation or any of the equipment and/or software it may describe, including (with no limitation) any implied warranties of utility, merchantability, or fitness for any particular purpose. All such representations or warranties are expressly disclaimed. Neither SMA Solar Technology AmericaLLC nor its distributors or dealers nor SMA Solar Technology Canada Inc. nor its distributors or dealers shall be liable for any indirect, incidental, or consequential damages under any circumstances.
The exclusion of implied warranties may not apply in all cases under some statutes, and thus the above exclusion may not apply.
Specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate and up-to-date. Readers are cautioned, however, that product improvements and field usage experience may cause SMA Solar Technology America LLC and/or SMA Solar Technology Canada Inc. to make changes to these specifications without advance notice, or per contract provisions in those cases where a supply agreement requires advance notice. SMA shall not be responsible for any damages, including indirect, incidental or consequential damages, caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not mean that a product or brand is not a registered trademark.
Modbus® is a registered trademark of Schneider Electric and is licensed by the ModbusOrganization,Inc.
QRCode is a registered trademark of DENSOWAVEINCORPORATED. Phillips® and Pozidriv® are registered trademarks of PhillipsScrewCompany. Torx® is a registered trademark of AcumentGlobalTechnologies,Inc.
SMASolar TechnologyAmerica LLC
6020 West Oaks Blvd.
Suite 300 Rocklin, CA 95765 U.S.A.
SMA Solar Technology Canada Inc.
2425 Matheson Blvd. E
7th Floor
Mississauga, ON L4W 5K4
Canada
Status: 7/20/2017 Copyright©2017SMA Solar Technology America LLC. All rights reserved.
ENGLISH
Important Safety Instructions
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-204
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the following products:
• STP 12000TL-US-10 (Sunny Tripower 12000TL-US)
• STP 15000TL-US-10 (Sunny Tripower 15000TL-US)
• STP 20000TL-US-10 (Sunny Tripower 20000TL-US)
• STP 24000TL-US-10 (Sunny Tripower 24000TL-US)
• STP 30000TL-US-10 (Sunny Tripower 30000TL-US)
This manual must be followed when using this product.
The product is designed and tested in accordance with international safety requirements, but as with all electrical and electronic equipment, certain precautions must be observed when installing and/or operating the product. To reduce the risk of personal injury and to ensure the safe installation and operation of the product, you must carefully read and follow all instructions, cautions and warnings in this manual.
Warnings in this Document
A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the SMA equipment and/or other equipment connected to the SMA equipment or personal injury.
Symbol Description
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
Warnings on this Product
The following symbols are used as product markings with the following meanings.
Warning regarding dangerous voltage
The product works with high voltages. All work on the product must only be per­formed as described in the documentation of the product.
Beware of hot surface
The product can become hot during operation. Do not touch the product during operation.
ENGLISH
Important Safety Instructions
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 5
Observe the operating instructions
Read the documentation of the product before working on it. Follow all safety precautions and instructions as described in the documentation.
ENGLISH
General Warnings
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-206
General Warnings
WARNING
All electrical installations must be carried out in accordance with the local electrical standards and the National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not replace and is not intended to replace any local, state, provincial, federal or national laws, regulations or codes applicable to the installation and use of the product, including without limitation applicable electrical safety codes. All installations must conform with the laws, regulations, codes and standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the compliance or non-compliance with such laws or codes in connection with the installation of the product. The product contains no user-serviceable parts. Before installing or using the product, read all of the instructions, cautions, and warnings in this manual. Before connecting the product to the electrical utility grid, contact the local utility company. This connection must be made only by qualified personnel. Wiring of the product must be made by qualified personnel only.
ENGLISH
Table of Contents
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 7
Table of Contents
1 Information on this Document................................................. 9
1.1 Validity........................................................................................................................ 9
1.2 Target Group.............................................................................................................. 9
1.3 Additional Information ............................................................................................... 9
1.4 Symbols ...................................................................................................................... 10
1.5 Nomenclature............................................................................................................. 10
2 Safety ........................................................................................ 11
2.1 Intended Use .............................................................................................................. 11
2.2 Safety Information...................................................................................................... 12
3 Scope of Delivery..................................................................... 14
4 Product Description.................................................................. 15
4.1 Sunny Tripower .......................................................................................................... 15
4.2 Interfaces and Functions ............................................................................................ 17
5 Mounting................................................................................... 19
5.1 Requirements for Mounting ....................................................................................... 19
5.2 Mounting the Inverter................................................................................................. 22
6 Electrical Connection................................................................ 25
6.1 Safety during Electrical Connection.......................................................................... 25
6.2 Overview of the Connection Area ............................................................................ 27
6.2.1 View from Below......................................................................... 27
6.2.2 Interior View ................................................................................ 28
6.3 AC Connection........................................................................................................... 28
6.3.1 Requirements for the AC Connection......................................... 28
6.3.2 Connecting the Inverter to the Utility Grid................................. 29
6.3.3 Connecting Additional Grounding............................................. 31
6.4 DC Connection........................................................................................................... 32
6.4.1 Requirements for the DC Connection......................................... 32
6.4.2 Connecting the PV Array ............................................................ 33
6.5 Connecting the Inverter to the Network ................................................................... 35
7 Commissioning the Inverter..................................................... 37
8 Configuration............................................................................ 39
8.1 Integrating the Inverter into the Network.................................................................. 39
8.2 Changing Operating Parameters.............................................................................. 39
ENGLISH
Table of Contents
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-208
8.3 Setting the Active Power Limitation in case of PV System Control Failure .............. 40
8.4 Deactivating the Arc-Fault Circuit Interrupter (AFCI)................................................ 40
8.5 Setting SMA OptiTrac Global Peak ......................................................................... 40
8.6 Adjustable Parameters............................................................................................... 41
9 Disconnecting the Inverter from Voltage Sources................. 43
10 Troubleshooting........................................................................ 45
10.1 Cleaning the Inverter.................................................................................................. 45
10.2 Event Messages ......................................................................................................... 45
10.3 Cleaning the Fans ...................................................................................................... 56
10.3.1 Cleaning the Fan at the Bottom.................................................. 56
10.3.2 Cleaning the Fan on the Left-Hand Side of the Enclosure ........ 57
10.4 Checking the Function of the Fans ............................................................................ 59
10.5 Checking the PV System for Ground Faults.............................................................. 59
10.6 Resetting the Operation Inhibition after Detection of an Arc Fault ......................... 62
11 Recommissioning the Inverter ................................................. 63
12 Decommissioning the Inverter................................................. 65
13 Procedure for Receiving a Replacement Device.................... 67
14 Technical Data .......................................................................... 71
14.1 DC/AC ....................................................................................................................... 71
14.1.1 Sunny Tripower 12000TL-US / 15000TL-US / 20000TL-US.. 71
14.1.2 Sunny Tripower 24000TL-US / 30000TL-US ........................... 73
14.2 General Data ............................................................................................................. 75
14.3 Protective Devices ...................................................................................................... 76
14.4 Climatic Conditions.................................................................................................... 76
14.5 Equipment................................................................................................................... 76
14.6 Torques ....................................................................................................................... 76
14.7 Data Storage Capacity.............................................................................................. 77
15 Spare Parts and Accessories ................................................... 78
16 Compliance Information .......................................................... 79
17 Contact ...................................................................................... 80
ENGLISH
1 Information on this Document
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 9
1 Information on this Document
1.1 Validity
This document is valid for the following device types:
• STP 12000TL-US-10 (Sunny Tripower 12000TL-US)
• STP 15000TL-US-10 (Sunny Tripower 15000TL-US)
• STP 20000TL-US-10 (Sunny Tripower 20000TL-US)
• STP 24000TL-US-10 (Sunny Tripower 24000TL-US)
• STP 30000TL-US-10 (Sunny Tripower 30000TL-US)
1.2 Target Group
The tasks described in this document must only be performed by qualified persons. Qualified persons must have the following skills:
• Knowledge of how an inverter works and is operated
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and installations
• Training in the installation and commissioning of electrical devices and installations
• Knowledge of the applicable standards and directives
• Knowledge of and compliance with this document and all safety information
1.3 Additional Information
Links to additional information can be found at www.SMA-Solar.com:
Document title Document type
"SunnyExplorer" Software for Visualizing and Administrating a SpeedwireSystem
User Manual
"Webconnect Systems in SunnyPortal" Registration in SunnyPortal and setting or changing operating pa-
rameters of the inverter
User Manual
"Grid Support Utility Interactive Inverters" Information about how to activate and to set the grid supporting fea-
tures according to UL1741SA
Technical information
"Parameter list" Overview of all inverter operating parameters and their configura-
tion options
Technical information
"Efficiency and Derating" Efficiency and Derating Behavior of the SunnyBoy, SunnyTripower
and SunnyMiniCentral Inverters
Technical information
ENGLISH
1 Information on this Document
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2010
Document title Document type
"Leading Leakage Currents" Information on the Design of Transformerless Inverters
Technical information
"Shade Management" Efficient operation of partly shaded PV systems with Opti-
TracGlobalPeak
Technical information
"Module Technology" Use of Thin-Film and Back-Contact Modules
Technical information
1.4 Symbols
Symbol Explanation
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
1.5 Nomenclature
Complete designation Designation in this document
SMA Solar Technology America LLC SMA SMA Solar Technology Canada Inc. SMA SMA Speedwire Speedwire PV system PV system Sunny Tripower 12000TL-US / 15000TL-US / 20000TL-
US / 24000TL-US / 30000TL-US
SunnyTripower, inverter
SMA Connection Unit 1000-US Connection Unit
ENGLISH
2 Safety
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 11
2 Safety
2.1 Intended Use
The SunnyTripower is a transformerless PV inverter, with 2 MPPtrackers, that converts the direct current of the PV array to grid-compliant, three-phase current and feeds it into the utility grid.
The product is suitable for indoor and outdoor use. The product must only be operated with PV arrays (PV modules and cabling) that are approved by
the electrical standards applicable on-site and the National Electrical Code® ANSI/NFPA 70 or the CanadianElectricalCode® CSA C22.1.
SMA offers the SMAConnectionUnit which is equipped with fuse holders for string fuses for up to eight strings and with a DC load-break switch. The SMA Connection Unit combines up to four strings to each of two output circuits. These two DC electric circuits can be connected to the two MPP tracker inputs of the SunnyTripower (for further information see the installation manual of the SMAConnectionUnit-US at www.SMA-Solar.com).
No galvanic isolation
The product is not equipped with a transformer and therefore has no galvanic isolation.
• Do not operate grounded PV modules together with the product. If grounded PV modules are connected to the product, an event will occur. The event will be displayed, along with the associated message, in the event list on the communication product.
• Only ground the mounting frames of the PV modules.
• The neutral conductor of the AC output is not bonded to ground within the product.
PV modules with a high capacity to ground may only be used if their coupling capacity does not exceed 3.5μF.
To protect the PV system against excessive reverse currents under fault conditions, a DC-side overcurrent protective device must be connected in accordance with the National Electrical Code
®
to prevent any short-circuit currents that exceed the ampacity of the DC electric circuit or the maximum series fuse rating of the PV modules. Typically, this requires string fusing where more than two strings are combined in parallel. Where an overcurrent protection device is required, the
National Electrical Code® requires that both positive and negative conductors have overcurrent
protection for ungrounded PV modules. All components must remain within their permitted operating ranges and their installation
requirements at all times. The product is approved for the US and Canadian market. Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMA. Unauthorized alterations will void guarantee and warranty claims and in most cases terminate the operating license. SMA shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the intended use.
ENGLISH
2 Safety
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2012
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.
2.2 Safety Information
This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
DANGER
Danger to life due to high voltages of the PV array
When exposed to sunlight, the PV array generates dangerous DC voltage, which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
• Do not touch non-insulated cable ends.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Have the inverter mounted, installed and commissioned only by qualified persons with the appropriate skills.
• If an error occurs, have it rectified by qualified persons only.
• Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document.
DANGER
Danger to life due to electric shock in case of a ground fault
If a ground fault occurs, parts of the system may still be live. Touching live components can lead to lethal electric shocks.
• Ensure that no voltage is present and wait five minutes before touching any parts of the PV system or the inverter.
CAUTION
Risk of burns from hot surfaces
The surface of the inverter can get very hot. Touching the surface can result in burns.
• Mount the inverter in such a way that it cannot be touched inadvertently.
• Do not touch hot surfaces.
• Wait 30 minutes for the surface to cool sufficiently.
• Observe the safety messages on the inverter.
ENGLISH
2 Safety
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 13
NOTICE
Damage to seals on the enclosure lids in subfreezing conditions
If you open the enclosure lids when temperatures are below freezing, the enclosure seals can be damaged. This can lead to moisture entering the inverter.
• Only open the enclosure lids if the ambient temperature is not below -5°C (23°F)
• If a layer of ice has formed on the seal of the lid when temperatures are below freezing, remove it prior to opening the enclosure lids (e.g. by melting the ice with warm air). Observe the applicable safety regulations.
NOTICE
Damage to the inverter due to moisture and dust intrusion
Dust or moisture intrusion can damage the inverter and impair its functionality.
• Close all enclosure openings of the inverter tightly.
• Never open the inverter when it is raining or snowing, or the humidity is over 95%.
ENGLISH
3 Scope of Delivery
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2014
3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your distributor if the scope of delivery is incomplete or damaged.
Figure 1 : Components included in the scope of delivery
Position Quantity Designation
A 1 Inverter B 1 Wall mounting bracket C 1 Installation manual, production test report, supplementary
sheet with the default settings
ENGLISH
4 Product Description
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 15
4 Product Description
4.1 SunnyTripower
The SunnyTripower is a transformerless PV inverter, with 2 MPPtrackers, that converts the direct current of the PV array to grid-compliant, three-phase current and feeds it into the utility grid.
No galvanic isolation
The product is not equipped with a transformer and therefore has no galvanic isolation.
• Do not operate grounded PV modules together with the product. If grounded PV modules are connected to the product, an event will occur. The event will be displayed, along with the associated message, in the event list on the communication product.
• Only ground the mounting frames of the PV modules.
• The neutral conductor of the AC output is not bonded to ground within the product.
M
o
d
e
l
S
B
X
X
X
X
X
X
T
L
U
S
-
S
U
N
N
Y
B
OY
S/N
XXXXXXXXXX
U
n
t
i
l
i
t
y
i
n
t
e
r
a
c
t
i
v
e
1
-
p
h
a
s
e
i
n
ve
r
te
r
M
a
d
e
i
n
G
e
r
m
a
n
y
SMA
Solar T
echn
ology A
G
w
w
w
.
s
m
a
-
s
o
l
a
r
.
c
o
m
D
a
te
o
f
m
a
n
u
fa
c
t
u
r
e
M
M
/
Y
Y
Y
Y
M
a
x
.
co
n
tin
u
o
u
s
o
u
tp
u
t P
o
w
e
r
*
X
X
X
X
W
a
c
R
e
d
u
c
e
d
o
u
tp
u
t p
o
w
e
r ra
tin
g
O
p
e
ra
t
in
g
v
o
lta
g
e
ra
n
g
e
(V
a
c
)*
M
IN
N
O
M
IN
A
LM
A
X
XXX XXX
XXX XXX
XXX XXX
O
p
e
ra
t
in
g
fre
q
u
e
n
c
y
ra
n
g
e
(
H
z
)*
M
I
N
N
O
M
IN
A
LM
A
X
XX.X XX.X
XX.X
M
a
x
.
vo
n
tin
u
o
u
s
o
u
tp
u
t c
u
rre
n
t*
X
X
.
X
A
a
c
@
X
X
X
V
X
X
.
X
A
a
c
@
X
X
X
V
O
u
t
p
u
t p
o
w
e
r fa
c
to
r X
M
a
x
. o
p
e
n
circ
u
it in
p
u
t v
o
lt
a
g
e
*
X
X
X
V
d
c
R
a
n
g
e
o
f in
p
u
t o
p
e
ra
tin
g
D
C
v
o
lta
g
e
(M
P
P
T
)
*
X
X
X
- X
X
X
C
d
c
@
X
X
X
V
X
X
X
- X
X
X
C
d
c
@
X
X
X
V
Oper.temp.range*-XXX°Fto+XXX°F(-XX°Cto +XX°C)
ThisunitcontainsaResidualCurrentMonitor,Isolation MonitorandInterrupter.Thisunitcontainsalisted PhotovoltaicArc-FaultCircuit-ProtectionofType1
E
N
C
LO
S
U
R
E
T
Y
P
E
XR
(
IP
5
4
)
*Formoredetailsandfürtighteningtorque, allowablewiresizeandtypeseethe InstallationGuide.
S
e
c
tio
n
1
o
f
2
U
t
i
l
i
t
y
i
n
t
e
r
a
c
t
i
v
e
i
n
ve
r
t
e
r
L
i
s
t
e
t
U
L
1
7
4
1
3
6
A
N
U
t
i
l
i
t
y
i
n
t
e
r
a
c
t
i
v
e
1
-
P
h
a
s
e
i
n
ve
r
t
e
r
Te
s
t
e
d
To
C
o
m
p
l
y
Wi
t
h
F
C
C
S
t
a
n
d
a
r
d
s
FO
R
H
O
M
E
O
R
O
F
F
I
C
E
U
S
E
CCAN/CSAC22.2No.107.1-1UL1699B
DE34
A
G
H
E
D
F
A
B
C
F
w
w
w
.su
n
n
y
p
o
r
ta
l.c
o
m
/
r
e
g
is
te
r
P
IC
0
0
1
8
0
0
3
0
4
6
0
0
1
1
7
R
ID
:3
7
X
X
A
3
D
Figure 2 : Design of the SunnyTripower
Position Designation
A Thread for screwing in the eye bolts for transport with a crane B Upper enclosure lid
ENGLISH
4 Product Description
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2016
Position Designation
C Type label
The type label uniquely identifies the inverter. You will require the information on the type label to use the product safely and when seeking customer support from the SMAServiceLine. You will find the following information on the type label:
• Device type (Model)
• Serial number (SerialNo.)
• Date of manufacture
• Device-specific characteristics
D Additional label with details for registration in SunnyPortal:
• Internet address of the PV System Setup Assistant
• Identification key (PIC)
• Registration ID (RID) E Ventilation grid F Recessed grips G LEDs
The LEDs indicate the operating state of the inverter:
• Green LED is glowing: operation
• Green LED is flashing: the requirements for the connection to the utility grid
have not been met or the inverter has reduced its output power due to excessive temperature.
• Red LED is glowing: an error has occurred that must be rectified by a qualified
person (see Section10 "Troubleshooting", page45). You will find the detailed error message in SunnyPortal or SunnyExplorer.
• Blue LED: no function H Lower enclosure lid
Symbols on the Inverter and on the Type Label
Inverter Together with the green LED, this symbol indicates the operating state of
the inverter. Observe the documentation
Together with the red LED, this symbol indicates an error. Communication
This symbol is located next to the blue LED.
ENGLISH
4 Product Description
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 17
The product does not have a transformer.
Equipment Grounding Terminal This symbol indicates the position for the connection of an equipment
grounding conductor. Risk of burns due to hot surfaces
The product can get hot during operation. Avoid contact during opera­tion. Prior to performing any work on the product, allow the product to cool down sufficiently.
Danger to life due to electric shock The product operates at high voltages. Prior to performing any work on
the product, disconnect the product from voltage sources. All work on the product must be carried out by qualified persons only.
Observe the documentation Observe all documentation supplied with the product.
FCC designation The product complies with the requirements of the applicable FCC stan-
dards. UL1741 is the standard applied by Underwriters Laboratories to the
product to certify that it meets the requirements of the National Electrical
Code®, the Canadian Electrical Code® CSA C22.1; the IEEE929‑2000
and IEEE1547.
4.2 Interfaces and Functions
The inverter can be equipped or retrofitted with the following interfaces and functions:
SMASpeedwire/Webconnect
The inverter is equipped with SMA Speedwire/Webconnect as standard. SMA Speedwire/ Webconnect is a type of communication based on the Ethernet standard. This enables inverter­optimized 10/100 Mbit data transmission between Speedwire devices in PV systems and the software Sunny Explorer. The Webconnect function enables direct data transmission between the inverters of a small-scale system and the Internet portal Sunny Portal without any additional communication device and for a maximum of 4 inverters per SunnyPortal system. In large-scale PV power plants, data transmission to the Internet portal Sunny Portal is carried out via the SMA Cluster Controller. You can access your Sunny Portal system from any computer with an Internet connection.
Class 1 wiring methods are to be used for field wiring connection to the terminals of the communication interface.
ENGLISH
4 Product Description
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2018
RS485 Interface
The inverter can communicate via cables with special SMA communication products via the RS485 interface (information on supported SMAproducts at www.SMA-Solar.com). The RS485 interface can be retrofitted and can be used in place of the SMASpeedwire/Webconnect interface in the inverter.
Class 1 wiring methods are to be used for field wiring connection to the terminals of the communication interface.
Grid Management Services
The inverter is a grid support utility interactive inverter. The inverter has been tested and certified to be compliant with UL1741SA (2016/09/07). For connecting the inverter to the utility grid, no additional grid monitoring equipment is necessary. A description of the tested functions and instructions on the activation and setting of functions can be found in the technical information "Grid support utility interactive inverters" at www.SMA-Solar.com.
SMAOptiTracGlobalPeak
SMAOptiTracGlobalPeak is an advancement of SMAOptiTrac and allows the operating point of the inverter to follow the optimal operating point of the PV array (MPP) precisely at all times. In addition, with the aid of SMAOptiTracGlobalPeak, the inverter detects several maximum power points in the available operating range, such as may occur particularly with partially shaded strings. You can activate SMAOptiTracGlobalPeak via the operating parameters (see Section8.5 "Setting SMA OptiTrac Global Peak", page40).
Arc-Fault Circuit Interrupter (AFCI)
In accordance with the National Electrical Code®, the inverter has a system for arc fault detection and interruption.
An electric arc with a power of 300 W or greater must be interrupted by the AFCI in the time specified by UL 1699B. A detected electric arc causes the inverter to interrupt feed-in operation. In order to restart feed-in operation, the feed-in operation must be activated manually. If the installation conditions allow it, you can deactivate the arc-fault circuit interrupter.
QonDemand 24/7
The inverter can supply reactive power by means of QonDemand24/7 covering the entire unit circle around the clock (for details on the configuration refer to the Technical Information "IntegratedPlantControl and QonDemand24/7" at www.SMA-Solar.com).
IntegratedPlantControl
The inverter can display the Q(V) characteristic curve specified by the grid operator by means of Integrated Plant Control without measuring on the grid-connection point. The inverter can automatically compensate equipment installed between the inverter and the grid-connection point after having activated the function (for information on the system configuration refer to the Technical Information "IntegratedPlantControl and QonDemand24/7" at www.SMA-Solar.com).
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 19
5 Mounting
5.1 Requirements for Mounting
Requirements for the Mounting Location:
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the product in areas containing highly flammable materials or gases.
• Do not mount the product in potentially explosive atmospheres.
☐ Do not mount the inverter on a pillar. ☐ Do not install the inverter in a living area. ☐ The inverter must be mounted on a solid surface (e.g. concrete, brickwork, free-standing
constructions).
☐ The inverter can be mounted in a position that is directly exposed to solar irradiation. There is,
however, the possibility that the inverter reduces its power output to avoid overheating due to high temperatures.
☐ The mounting location must be suitable for the weight and dimensions of the inverter (see
Section14 "Technical Data", page71).
☐ To ensure optimum operation, the ambient temperature should be between -25°C (-13°F) and
60°C (140°F). ☐ Climatic conditions must be met (see Section14 "Technical Data", page71). ☐ The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2020
Dimensions for mounting:
40
(1.57)
647
(25.5)
79.2
(3.11)
Ø 11
(Ø 0.43)
87
(3.43)
20
(0.79)
11 mm
(0.43 in)
104.6 (4.11)
110
(4.33)
619
(24.36)
130
(5.12)
86
(3.39)
86
(3.39)
467
(18.39)
130
(5.12)
507
(19.96)
638
(25.1)
432 (17)
216
(8.5)
216
(8.5)
Figure 3 : Position of the anchoring points (dimensions in mm (in))
Recommended clearances:
To guarantee optimal operation and adequate heat dissipation for the inverter, the following requirements for clearances should be observed. This will prevent the inverter power output from being reduced due to excessive temperatures. However, smaller clearances are permitted without causing any risk.
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 21
Prescribed clearances in accordance with the
National Electrical Code
®
or
Canadian Electrical Code
®
CSA C22.1
Under certain conditions, the National Electrical Code® or the Canadian Electrical Code
®
CSA C22.1 specify greater clearances.
• Ensure that the prescribed clearances in accordance with the National Electrical Code
®
or Canadian Electrical Code® CSA C22.1 are adhered to.
☐ Maintain the recommended clearances to walls as well as to other inverters or objects. ☐ Ensure adequate clearance on the right-hand side of the inverter below the fan. ☐ If multiple inverters are mounted in areas with high ambient temperatures, increase the
clearances between the inverters and ensure sufficient fresh-air supply.
1382 mm
(54.41 in)
2224 mm (87.56 in)
530 mm
(20.87 in)
50 mm
(1.97 in)
400 mm
(15.45 in)
315 mm
(14.45 in)
415 mm
(16.34 in)
438 mm
(17.24 in)
415 mm
(16.34 in)
940 mm
(37.01 in)
(7.48 in)
190 mm
Permitted and prohibited mounting positions:
☐ The inverter must only be mounted in one of the permitted positions. This will ensure that no
moisture can penetrate the inverter. ☐ The inverter should be mounted in such a way that the LED signals can be read without
difficulty.
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2022
Figure 4 : Permitted and prohibited mounting positions
5.2 Mounting the Inverter
Additionally required mounting material (not included in the scope of delivery):
☐ At least two screws suitable for the support surface (diameter: 10mm at maximum) ☐ At least two washers that are suitable for the screws (diameter: 30mm (1.8in) at maximum) ☐ If necessary, two screw anchors suitable for the support surface and the screws ☐ For transporting the inverter with a crane: two eye bolts suitable for the weight of the inverter
(size: M10) ☐ To secure the inverter from being lifted off: two screws, washers and screw anchors that are
suitable for the support surface
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 23
CAUTION
Risk of injury when lifting the inverter, or if it is dropped
The inverter weighs 55kg (121lb). There is risk of injury if the inverter is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall mounting bracket.
• Carry and lift the inverter in an upright position with several people without tilting it. With one hand grasp the recessed grip, and with the other hand support the top part of the enclosure. This will prevent the inverter tipping forward.
• If the inverter is to be transported and lifted with a crane, remove the filler plugs on the top of the inverter and screw the eye bolts into the threads.
CAUTION
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation.
• Mount the inverter in such a way that it cannot be touched inadvertently during operation.
Procedure:
1.
CAUTION
Risk of injury due to damaged cables
There may be power cables or other supply lines (e.g. gas or water) routed in the wall.
• Ensure that no lines are laid in the wall which could be damaged when drilling holes.
2. Align the wall mounting bracket horizontally on the wall and use it to mark the position of the drill holes. Use at least one hole on the right-hand and left-hand side in the wall mounting bracket.
3. If the inverter is to be secured from being lifted off of the wall mounting bracket, mark the position of the drill holes for the screw that attaches the inverter to the wall mounting bracket. Observe the dimensions of the two anchoring points at the bottom of the inverter rear panel.
4. Set the wall mounting bracket aside and drill the marked holes.
ENGLISH
5 Mounting
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2024
5. Insert screw anchors into the drill holes if the support surface requires them.
6. Secure the wall mounting bracket horizontally using screws and washers.
7. Hook the inverter into the wall mounting bracket.
8. If the inverter has been transported with a crane, remove the eye bolts from the threads on the top of the inverter and reinsert the filler plugs.
9. In order to secure the inverter from being lifted off the wall accidentally, attach it to the wall with suitable mounting material. Use both of the lower drill holes on the rear panel of the inverter.
10. Ensure that the inverter is securely in place.
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 25
6 Electrical Connection
6.1 Safety during Electrical Connection
DANGER
Danger to life due to high voltages of the PV array
When exposed to sunlight, the PV array generates dangerous DC voltage, which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
• Do not touch non-insulated cable ends.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Have the inverter mounted, installed and commissioned only by qualified persons with the appropriate skills.
• If an error occurs, have it rectified by qualified persons only.
• Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document.
CAUTION
Risk of fire
• To reduce the risk of fire, connect only to a circuit provided with 50A maximum branch­circuit overcurrent protection in accordance with the National Electrical Code® (NE, ANSI/ NFPA 70).
NOTICE
Damage to seals on the enclosure lids in subfreezing conditions
If you open the enclosure lids when temperatures are below freezing, the enclosure seals can be damaged. This can lead to moisture entering the inverter.
• Only open the enclosure lids if the ambient temperature is not below -5°C (23°F)
• If a layer of ice has formed on the seal of the lid when temperatures are below freezing, remove it prior to opening the enclosure lids (e.g. by melting the ice with warm air). Observe the applicable safety regulations.
NOTICE
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic discharge.
• Ground yourself before touching any component.
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2026
NOTICE
Damage to the inverter due to moisture ingress during electrical installation
• Never open the inverter when it is raining or snowing, or the humidity is over 95%.
• For attaching the conduits to the enclosure, only use UL-listed rain-tight conduit fittings or UL­listed conduit fittings for wet locations complying with UL514B.
• Seal all unused openings tightly.
NOTICE
Ground faults, unreliable and highly resistive connections due to
Wire Nuts
®
Potential damage to or failure of the inverter.
• Do not use Wire Nuts®.
Electrical installations
All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1.
• Before connecting the inverter to the utility grid, contact your local grid operator. The electrical connection of the inverter must be carried out by qualified persons only.
• Ensure that no cables used for electrical connection are damaged.
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 27
6.2 Overview of the Connection Area
6.2.1 View from Below
Figure 5 : Enclosure openings at the bottom of the inverter
Position Designation
A Enclosure opening with filler plug for communication connection
(diameter: 27.8mm to 28.0mm (1.09in to 1.10in))
B Enclosure opening with filler plug for Ethernet connection
(diameter: 27.8mm to 28.0mm (1.09in to 1.10in))
C Enclosure opening for AC connection
(diameter: 34.5mm to 34.7mm (1.36in to 1.37in))
D Enclosure openings for DC connection
(diameter: 34.5mm to 34.7mm (1.36in to 1.37in))
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2028
6.2.2 Interior View
Figure 6 : Connection areas in the interior of the inverter
Position Designation
A Connecting terminal plate for AC connection B Switch for changing the language to English for service purposes C Screw to release and attach the communication board D Slot for the SD memory card, for service purposes only E Terminal for equipment grounding and grounding electrode conductor F Connecting terminal plate for DC connection
6.3 AC Connection
6.3.1 Requirements for the AC Connection
Additionally required material (not included in the scope of delivery):
☐ 1 metal conduit: 25.4mm (1in) ☐ 1 UL-listed rain-tight conduit fitting for wet locations: 25.4mm (1in)
Cable requirements:
☐ The AC cable must be approved for temperatures of over +90°C (+194°F). ☐ The AC cable must be designed in accordance with the local installation requirements. ☐ The AC cable must be made of solid wire or stranded wires. ☐ Conductor cross-section: 10mm² to 6mm² (8AWG to 6AWG) ☐ Conductor type: copper wire ☐ The maximum cable length subject to conductor cross-section must be observed.
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 29
Load-break switch and cable protection:
NOTICE
Damage to the inverter due to the use of screw-type fuses as load-break switch
Screw-type fuses are not load-break switches.
• Do not use screw-type fuses as load-break switches.
• Use a load-break switch or a circuit breaker for load disconnection.
☐ In PV systems with multiple inverters, protect each inverter with a separate three-phase circuit
breaker. Observe the maximum permissible fuse protection (see Section14 "Technical Data", page71). This will prevent residual voltage from being present at the corresponding cable after disconnection.
☐ The load-break switch or circuit breaker must be listed (seeNational Electrical Code®, ANSI/
NFPA 70) ☐ Loads installed between the inverter and the circuit breaker must be fused separately. ☐ The overcurrent protection for the AC output circuit is to be provided by others.
Compatible grid configurations:
Device 480V / 277V WYE 480VDelta
STP 12000TL-US-10 Yes No STP 15000TL-US-10 Yes No STP 20000TL-US-10 Yes No STP 24000TL-US-10 Yes No STP 30000TL-US-10* Yes Yes**
* A neutral conductor connection is necessary for the 480V / 277V WYE. A neutral conductor
connection is not necessary for the 480V Delta.
** For connection to 480 V Delta commercial services where co-located loads may result in recurring and
persistent line-to-ground faults (effectively resulting in a corner grounded Delta grid configuration), inverters must be protected from excessive line-to-ground voltages by isolating the PV system from the source(s) of the fault(s).
6.3.2 Connecting the Inverter to the Utility Grid
Requirements:
☐ All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. ☐ The AC and DC electric circuits are isolated from the enclosure. If required by the National
Electrical Code®, ANSI/NFPA 70, the installer is responsible for grounding the system.
☐ The connection requirements of the grid operator must be met. ☐ The grid voltage must be within the permissible range. The exact operating range of the
inverter is specified in the operating parameters.
ENGLISH
6 Electrical Connection
SMA Solar Technology America LLC
Installation ManualSTPTL-US-10-IA-xx-2030
Procedure:
1.
DANGER
Danger to life due to electric shock
• Ensure that the three-pole circuit breaker is switched off and cannot be reconnected.
2. Release all screws of the lower enclosure lid using an Allen key (AF3).
3. Lift and remove the lower enclosure lid from below.
4. Remove the adhesive tape from the enclosure opening for the AC connection.
5.
NOTICE
Damage to the inverter due to moisture and dust intrusion
Electronic components in the inverter can be destroyed or damaged as a result of dust or moisture intrusion.
• Do not enlarge the enclosure opening.
6. Insert the conduit fitting into the opening and tighten from the inside using the counter nut.
7. Attach the conduit to the enclosure opening.
8. Insert the AC cable through the conduit into the inverter.
9. Strip the cable insulation by 12mm to 13mm (0.5 in).
10. Open all locking levers of the connecting terminal plate right up to the stop.
11.
CAUTION
Risk of fire if two conductors are connected to one terminal
If you connect two conductors to a terminal, a fire can occur due to a bad electrical connection.
• Never connect more than one conductor per terminal.
12. Connect the equipment grounding conductor to the terminal .
ENGLISH