SMA SB 5000TL User Manual

Sunny Boy 5000TL Multi-String Transformerless Solar Inverter for Three Independent Strings
Installation Guide Version 2.1 SB5000TL-12:SE2006
IME-SB5000TL
SMA Technologie AG Explanation of Symbols used in this Document
Explanation of Symbols used in this Document
This symbol indicates information that is required for the optimal operation of the product. Read these sections carefully in order to ensure an optimal ope­ration of the product and all its features.
This symbol indicates an example.
Installation Guide SB5000TL-12:SE2006 Page 3
Legal Restructions SMA Technologie AG
Liability exclusion
The information contained in this documentation are the property of SMA Technologie AG. No part of this documentation may be published without written permission from SMA Technologie AG. A reproduction for internal purposes for the evaluation of the product or an appropriate application is permitted and does not require authorization.
All information are based on our "General Terms and Conditions of Delivery of SMA Technologie AG”. The content of this documentation is reviewed continuously and adjusted, if necessar y. SMA Technologie AG provides this documentation without exclusion of deviations and without warranty of completeness. You will find the current version on the Internet at www.SMA.de or can obtain it via the usual sales channels. Warranty or liability claims for all kinds are excluded in case of damages due to:
• Inappropriate use of the product
• Operation of the product in an improper environment
• Operation of the product without considering the relevant safety regulations
• Non-fulfillment of the warnings or safety instructions described in the documentation for the product
• Operation of the product under faulty conditions concerning security and protection
• Arbitrary changing of the product or the provided software
• Failure of the product due to interference of connected or contiguous devices out of legal limit values
• Disasters and force majeure
Software Licensing
The use of the provided software by SMA Technologie AG is subject to the following conditions: The software may be reproduced for internal purposes and installed on any number of computers. Provided source codes can be changed and adjusted on the company’s own authority according to the internal purpose. Driver may be ported to other operating systems as well. No part of the source codes may be published without written permission of SMA Technologie AG. Sublicensing of the software is not acceptable.
Liability limitation: SMA Technologie AG disclaims liability for any direct or indirect consequential damages arising from the use of the software produced by SMA Technologie AG. The same applies for the provision and/or non-provision of support.
Provided software not produced by SMA Technologie AG is subject to the respective licensing and liability agreements of the manufacturer.
Trademarks
All brand and product names used herein are trademarks or registered trademarks of their respective holders, although they may not be specifically designated as such.
SMA Technologie AG Hannoversche Strasse 1-5 34266 Niestetal Germany Tel. (+49) 5 61 95 22 – 0 Fax (+49) 5 61 95 22 – 100
www.SMA.de
E-Mail: info@SMA.de
© 2005 SMA Technologie AG. All rights reserved.
Page 4 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Table of Contents
Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Device Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3.2 External Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
4 Requirements for the Installation . . . . . . . . . . . . . . . . 13
4.1 Requirements: Mounting Place . . . . . . . . . . . . . . . . . . . . . . . .13
4.2 Requirements: PV-Modules. . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.3 Requirements: Grid 230 V (AC) . . . . . . . . . . . . . . . . . . . . . . .15
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.2 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
5.3 Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
6 Opening and Closing the Sunny Boy 5000TL. . . . . . . 27
6.1 Opening the Sunny Boy 5000TL . . . . . . . . . . . . . . . . . . . . . . .27
6.2 Closing the Sunny Boy 5000TL. . . . . . . . . . . . . . . . . . . . . . . .27
7 Technical Documentation . . . . . . . . . . . . . . . . . . . . . 29
7.1 Data PV Generator Connection . . . . . . . . . . . . . . . . . . . . . . .29
7.2 Data Grid Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
7.3 Description of Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
7.4 Sunny Boy 5000TL Operating Parameters. . . . . . . . . . . . . . . .31
8 Exchanging Varistors . . . . . . . . . . . . . . . . . . . . . . . . 33
9 Sizing of a Circuit Breaker . . . . . . . . . . . . . . . . . . . . 37
10 Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Installation Guide SB5000TL-12:SE2006 Page 5
Table of Contents SMA Technologie AG
Page 6 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Introduction

1 Introduction

The installation of the Sunny Boy may only be done by qualified technicians. The installer must be approved by the utility company. Please read the installation guide carefully before you begin with the installation. The installation of utility interactive power sources must be compliant with all applicable regulations of the utility company and with all applicable regulations and standards.
The Sunny Boy 5000TL Multi-String is equipped with the SMA grid guard. This is a type of independent disconnection device. It ensures that the Sunny Boy 5000TL Multi-String complies with the VDEW (Verband der Elektrizitätswirtschaft – German Electricity Industry Association) regulations for the connection and parallel operation of electrical power units to the low­voltage grid of the electricity supply company and with DIN VDE 0126 (4.99) which is a part of these regulations.
This installation manual is intended solely for qualified electricians. Its aim is to help install and set up SMA Sunny Boy 5000TL Multi-String inverters quickly and correctly.
For detailed information on troubleshooting and on how to use the Sunny Boy 5000TL Multi-String, including information about the different communication options, please see the operating instructions.
The „Sunny Design“ tool will help to dimension and check the size of your strings with respect to the inverter you intend to use. Further information about „Sunny Design“ is available at www.SMA.de.
If your Sunny Boy is equipped with a communication interface, you will find detailed instructions for installation in the description of the communication interfaces (Piggy­Backs), which has been delivered with the device.
If you require further information, please call the Sunny Boy hotline on the following number:
+49 561 95 22 - 499
Installation Guide SB5000TL-12:SE2006 Page 7
Introduction SMA Technologie AG
Page 8 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Safety Instructions

2 Safety Instructions

Check your plant configuration and the string sizing with „Sunny Design“ (avail­able at www.SMA.de) or with the Sunny Boy Hotline before you start with the in­stallation. Exceeding the specifications
Erdschluss Earth
F ault
Art.-Nr.: 86-00
Work on the Sunny Boy with the lid removed must be carried out by a qualified electrician. Hazardous and even lethal voltages can be encountered within the enclosure. Before working on the Sunny Boy with the lid removed, the AC and DC voltages MUST be disconnected from the Sunny Boy and it must be sure that all capacitors are discharged.
The Sunny Boy must be disconnected from the mains and precautions must be taken to prevent the grid being reconnected. In addition, the connections to the PV generator must be disconnected.
with the input voltage will destroy the Sunny Boy. Overvoltage on the DC side can even cause dangerous explosions of the Sunny Boys input capacitors and ex­plosions of the electrolytes coming from the exploded capacitors.
After isolating the AC and DC voltage you must wait approx. 30 minutes for the capacitors in the Sunny Boy to discharge. Only then is it safe to open the unit by removing the lid. You must also make sure that no voltage is present in the device.
The electronics inside your Sunny Boy 5000TL Multi-String is vulnerable in terms of electrostatic discharge. Be sure to be connected to ground (e.g. the enclosure of the Sunny Boy) before handling anything within the enclosure of the Sunny Boy.
Installation Guide SB5000TL-12:SE2006 Page 9
Safety Instructions SMA Technologie AG
Page 10 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Overview
(

3 Overview

3.1 Device Description

The following figure shows the different components and connection areas of an open Sunny Boy 5000TL Multi-String inverter.
Varistors page 33
Communication socket RS485, NLM Piggy-Back, radio)
RS232,
PE connecting cable for lid
Socket for display unit (Sunny Display)
LEDs indicating operating state
Communication terminal
PV input plug (DC),
page 23
Installation Guide SB5000TL-12:SE2006 Page 11
Socket for PLC
(Powerline Communication)
power unit
Terminals (AC), page 21
Overview SMA Technologie AG

3.2 External Dimensions

225 mm
470 mm
Photovoltaik-Stringwechselrichter Photovoltaic string inverter
490 mm
Page 12 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Requirements for the Installation

4 Requirements for the Installation

Please make sure to fulfill all conditions below before installing and commissioning the Sunny Boy 5000TL Multi-String.

4.1 Requirements: Mounting Place

The Sunny Boy 5000TL Multi-String has a weight of 31 kg. Please keep this in mind when selecting the place where and how to mount the Sunny Boy 5000TL Multi-String.
The ambient temperature must be within -25 °C and +60 °C.
The Sunny Boy 5000TL Multi-String should be installed in a place
31 kg
The Sunny Boy is designed to be mounted on a vertical wall. For an optimum energy yield and the most convenient operation, vertical installation at eye-level is preferable. In case it is absolutely necessary to tilt the Sunny Boy to the back the maximum angle is 45 °. If installing the unit outdoors, make sure that it is not slanting forwards. We advise against installing the unit in a horizontal position outdoors.
where it is not exposed to direct sunlight. An increased ambient temperature can reduce the yield of the PV system.
It is not reccomended to install the Sunny Boy lying on the back side with the lid facing upwards.
max. 45°
Install the Sunny Boy vertically, or if necessary tilted slightly to the back.
Installation Guide SB5000TL-12:SE2006 Page 13
Never install the Sunny Boy
tilted to the front.
Requirements for the Installation SMA Technologie AG
Important for the selection of the location:
Unintended removal of the PV plug connectors can damage the connectors and even result in serious injuries. Install the Sunny Boy 5000TL Multi-String at a place where an unintended removal of the PV plug connectors (e. g. by children) is not possible.
Some parts of the Sunny Boy can reach temperatures over 60 °C.
Do not install the Sunny Boy on flammable construction materials, in areas where highly inflammable materials are stored or in po­tentially explosive environments!
Please make sure there is a sufficient space for heat dissipation! In a normal environ­ment the following clearances should be provided for the Sunny Boy 5000TL Multi­String:
Minimum clearances
Lateral 20 cm
Top 20 cm
Bottom 20 cm
Front 5 cm
In a living area the Sunny Boy 5000TL Multi-String should not be mounted on plaster panels etc. in order to avoid noises.
We recommend to install the inverter on a firm and sturdy surface.
The Sunny Boy 5000TL Multi-String will emit a slight noise during operation. This noise can be annoying when the Sunny Boy is installed within a living area.
20 cm
20 cm
Photovoltaik-Stringwechselrichter Photovoltaic string inverter
5
cm
20 cm
20 cm
Page 14 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Requirements for the Installation

4.2 Requirements: PV-Modules

The Sunny Boy 5000TL Multi-String is designed for the connection of up to three strings (PV modules connected in series). The three strings may be different in terms of type, module number and orientation due to the fact that each input string is pro­cessed by a separate MPP-tracker.
The „Sunny Design“ tool will help to dimension and check the size of your string with respect to the inverter you intend to use. Information about the „Sunny Design“ tool is available at www.SMA.de.
The device has six PV plug connectors (two for each string). The connecting cables of the PV panel therefore have to be equipped with such plug connectors as well.
A connection kit for the connection of loose cable ends in a string can be purchased as an accessory. In the following you find the SMA order numbers for the different PV plug connectors:
• Multi-Contact 3 mm: „SWR-MC“
• Multi-Contact 4 mm: „MC-SET“
• Tyco: „TYCO-SET“
Limits for DC input
max. voltage per string 750 V (DC)
max. input current per string 7,5 A (DC)
Caution: A parallel connection of the DC input is not possible!

4.3 Requirements: Grid 230 V (AC)

The relevant technical regulations as well as specific re­quirements defined by the local public utility have to be complied with.
The terminals of the Sunny Boy 5000TL Multi-String are suitable for cables with a cross-section of up to 10 mm². Their outer diameter should be between 9 mm and 17 mm. The Sunny Boy 5000TL Multi-String is connected with three wires (L, N, PE).
Each connection to a Sunny Boy 5000TL Multi-
Photovoltaik-Stringwechselrichter Photovoltaic string inverter
Installation Guide SB5000TL-12:SE2006 Page 15
String must be equipped with a separate auto­matic circuit breaker 25 A type B. No other con-
25A
B
sumers may be connected to the cable.
max. 10 mm²9 … 17 mm
Requirements for the Installation SMA Technologie AG
Sizing of a circuit breaker for the AC line of a photovoltaic invert­er for utility interaction
Several factors have to be considered when you define the size of the circuit breaker for your PV-plant:
• cable type (material and isolation)
• ambient temperature surrounding the cable (higher temperatures reduce the con­ducting capacity of the cable)
• type of installation for the cable (can reduce the conducting capacity of the cable)
• bundling of cables (can reduce the conducting capacity of the cable)
• loop impedance [Z] (reduces the current that flows in case of a ground fault cur­rent through a body and has influence on the tripping characteristics of the circuit breaker)
• Adequate clearance between the circuit breakers in order to avoid excessive heating (automatic circuit breakers trip earlier when they are warmer.).
• fuse selectivity
• protection class of the connected consumer (VDE 0100 Part 410 "Protection against electric shock"
The following standards have to be complied with:
1
and/or the international standard IEC 364-4-41:1992)
• DIN VDE 0298-4
• DIN VDE 0100 Part 430
1
("Types of cable installation and conducting capacity")
1
("Protection measures for protection of cables and conductors in terms of overcurrent") and/or the international stan­dard IEC 364-4-43:1977 and IEC 364-4-473:1977
1
• VDE 0100 Part 410
("Protection against electric shock") and/or the inter-
national standard IEC 60364-4-41:1992
An example for determining the rating of the AC circuit breaker is specified in detail in chapter 8 „Exchanging Varistors” (page 33).
Do not equip the AC circuit with a 30 mA GFCI (Ground Fault Current Interrup­tor) that trips when the residual failure current to the equipment ground (PE) exceeds 30 mA.
The Sunny Boy 5000TL Multi-String constantly monitors the ground currents of the PV­plant (PV-modules, cables and inverter) and disconnects from the grid when the ground fault current deviations exceed 30 mA. The inverter automatically distinguish­es between real failure currents and normal capacitive discharge currents.
1. The standards mentioned above are to be only used as a guideline for your installation. They apply for installations in Germany. Please note that other standards will apply for different countries throughout the world.
Page 16 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Requirements for the Installation
The Sunny Boy 5000TL Multi-String does not generate any extraordinary capacitive discharge currents in normal operation. In certain cases (e.g. the internal testing of the safety components within the Sunny Boy 5000TL Multi-String) discharge currents can occur that can trip a 30 mA GFCI.
Install a 100 mA GFCI in the AC distribution in case an additional GFCI is ab­solutely necessary.
The system impedance at the installation site of the Sunny Boy 5000TL Multi-String must be less than 1 Ohms for the islanding detection and the fuses to work porperly. Furthermore you should have a suitable cable cross-section in order to keep the loss­es below 1 % at nominal power. The according losses with respect to cable length and cross-section are illustrated below. It is based on a multi-conduit cable with all conduits made of copper.
1.4%
1.2%
1.0%
0.8%
0.6%
Losses
0.4%
0.2%
0.0% 5 m 10 m 20 m 30 m 40 m 50 m
0 m 15 m 25 m 35 m 45 m
Do not use cables where the losses will exceed 1.0 %
10.0 mm²
4.0 mm²
6.0 mm²
8.0 mm²
Length
The maximum cable lengths for the different cable cross-sections are as follows:
Conductor cross-section 4.0 mm² 6.0 mm² 8.0 mm² 10.0 mm²
Max. length 12 m 18 m 24 m 31 m
Installation Guide SB5000TL-12:SE2006 Page 17
Requirements for the Installation SMA Technologie AG
The Sunny Boy 5000TL Multi-String is designed for 230 V grids. The voltage should be within 198 V and 260 V and the frequency should be within 49.8 Hz and
50.2 Hz. All settings shown below are based on the German standard DIN VDE
0126. You are also able to use other settings.
Limits for AC output
Voltage range 198 V ... 260 V
Frequency range 49.8 Hz ... 50.2 Hz
Voltage range
(without anti-islanding)
Frequency range
(without anti-islanding)
180 V ... 260 V
45.5 Hz ... 54.5 Hz
Page 18 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Installation

5 Installation

5.1 Mounting

For trouble-free mounting of the Sunny Boy 5000TL Multi-String we recommend to use the bracket for wall installation included in delivery. You can mount it verti­cally in firm concrete or stone walls with e. g. stainless steel 8 mm x 50 mm hexagon screws according to DIN 571, an appertaining washer and with an 8 mm dowel.
P h otov
o lt
Pho
ai k
-
t
S
o
t
v
ri
o
ng l t a
w i c
e
chs
s
tr i ng
el
rich i nv
t
er
er
ter
Keep the weight of the Sunny Boy 5000TL Multi-String (31 kg) in mind.
1. Mount the bracket. To mark the positions for drill holes you can also use the bracket as a drilling template.
2. Hang the upper fixing straps of the Sunny Boy 5000TL Multi-String into the bracket (2) so that it cannot be shifted sideways any more.
3. Secure the Sunny Boy 5000TL Multi-String against lifting off by screwing the M6x10 screw (included in delivery) into the lower middle fixing strap (3).
4. Ensure the Sunny Boy 5000TL Multi-String has been tightly fastened.
2
1
3
Installation Guide SB5000TL-12:SE2006 Page 19
Installation SMA Technologie AG

5.2 Electrical Installation

Check the correct polarity before you connect the PV strings!
The following figure shows the complete cabling of a Sunny Boy 5000TL Multi-String:
Page 20 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Installation
Connection of AC output
Please follow the steps below:
1. Check the grid voltage. If it is above 260 V (German standard), the Sunny Boy 5000TL Multi-String stops operation. The local public utility company should solve this problem.
2. Disconnect the grid (switch off the circuit breaker), secure it against accidental reactivation and ensure that it is disconnected.
The maximum grid voltage for feeding
max. 260 V!
operation is 260 V!
+- +- +-
3. Unscrew the lid from the enclosure of the Sunny Boy 5000TL Multi-String and carefully remove the lid. Then pull the PE cable off the inside of the lid.
4. Connect the AC cable as illustrated in the figure on the side. Use the cable gland that is included in the delivery of your Sunny Boy 5000TL Multi­String. Phase (L) and Neutral (N) may not be mixed up.
String B
String C
String A
Before opening the Sunny Boy 5000TL
Multi-String check whether the AC
output is safely isolated from supply!
Photovoltaik-Stringwechselrichter Photovoltaic
s tring
i nverter
Make sure that you pull off the green yellow PE cable from the inside of the
Sunny Boy when you open it!
L
N
Connection of „L“ and „N“
Installation Guide SB5000TL-12:SE2006 Page 21
Installation SMA Technologie AG
5. Connect the earth wire (PE) of the mains lead to the top terminal of the three-terminal block on the circuit board.
Connection of PE conductor
6. Fix the PE conductor on the lid again. Fasten the lid to the enclosure of the Sunny Boy 5000TL Multi-String by tightening the four screws.
Do not switch on the circuit breaker yet! The Sunny Boy 5000TL Multi-String may only be connected to the AC grid when the PV strings have been connected and the device is tightly closed.
Page 22 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Installation
PV String (DC) Connection
Connect the PV strings as follows:
1. Check the PV generator connections on their correct polarity and compliance with the maxi­mum string voltage of 750 V DC, see chapter
4.2 „Requirements: PV-Modules” (page 15).
The voltage from the strings is very dangerous! Be very careful and pay attention to all applicable safety regulations!
2. Measure the DC voltages between each PV plug connector of a string and ground potential. Follow the safety instructions!
3. If the measured voltages are constant and their total approximately corresponds to the open­circuit voltage of the string, a ground fault has occured in this string. The ratios of voltages approximately indicate where the ground fault can be found.
PE
When you have found a ground fault in a string, only connect it to the Sunny Boy 5000TL Multi-String after you have removed the cause for the ground fault in the PV generator.
4. Repeat steps 2 and 3 for each string.
5. Connect the trouble-free PV strings to the Sunny Boy 5000TL Multi-String. Make sure to connect them with correct polarization.
+- +- +-
6. Close off the unneeded DC input sockets using the protective caps supplied in the accessories
String B
String C
kit.
Installation Guide SB5000TL-12:SE2006 Page 23
String A
When connecting the plus and minus
poles of a string make sure to choose
the correct connection!
Installation SMA Technologie AG

5.3 Activation

You can activate the Sunny Boy 5000TL Multi-String when:
• The AC (grid) cable has been correctly connected.
• All the DC (PV) strings have been connected and all unused PV plug connectors
on the underside of the inverter have been closed with the protecting caps.
• The lid has been tightly screwed on.
Proceedings for Activation
1. Switch the circuit breaker on.
2. Check whether the LEDs indicate trouble-free operation of the Sunny Boy 5000TL Multi-String based on the table on the next page. If this is the case commissioning has been successfully completed.
On!
Off
Photovoltaik-Stringwechselrichter Photovoltaic string inverter
If the lower yellow LED repeatedly blinks once a second for four times, immediately disconnect the grid voltage and the PV gener­ator from the Sunny Boy 5000TL Multi-String. The input voltage is too high. The inverter might be damaged!
Check whether string voltages comply with limiting values stated in chapter 4.2 „Re­quirements: PV-Modules” (page 15). If the values are too high, the planner / installer of the PV generator must modify the strings.
If the LED blinks again when the PV plant is reconnected to the inverter although string voltages have been checked to be ok, disconnect the PV panel again and con­tact SMA Technologie AG (see chapter 10 „Contact” (page 39)).
Page 24 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Installation
Green Red Yellow Status
off off OK (feeding)
permanently on
blinking fast
(3 x per second)
blinking slowly
(1 x per second)
shortly turns off
(approx. 1 x per
second)
off
permanently on
off off OK (Stop)
permanently on off failure
off off
permanently on permanently on failure
off off OK (derating)
permanently on off failure
off
permanently on
off failure
permanently on OK (Initialization)
OK (waiting, grid moni-
toring)
off OK (stand-by)
off / blinking failure
off failure
off / blinking failure
You will find a detailed description of failure messages and their causes in the „Op­erating Instructions“.
Installation Guide SB5000TL-12:SE2006 Page 25
Installation SMA Technologie AG
Page 26 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Opening and Closing the Sunny Boy 5000TL

6 Opening and Closing the Sunny Boy 5000TL

If the inverter has to be openend, always follow the safety instruc­tions given in chapter 2 „Safety Instructions” (page 9).

6.1 Opening the Sunny Boy 5000TL

Caution: Stick to the order specified below!
1. Switch off the AC connection.
2. Prevent accidental reconnection!
3. Disconnect the PV generator from the Sunny Boy 5000TL Multi-String by pulling off all the connectors.
4. Wait 30 minutes! (This is necessary to let the internal capacitors discharge.)
5. Remove the four screws on the lid and pull the lid slightly forward. Unlock the green-yellow PE connection and remove it from the lid and take the lid off.

6.2 Closing the Sunny Boy 5000TL

Caution: Stick to the order specified below!
1. Connect the PE conductor to the lid. Then attach the lid to the enclosure of the Sunny Boy 5000TL Multi-String by tightening the four screws.
2. Connect the PV generator. Make sure to connect each plug to the correct terminal.
3. Switch on the AC circuit breaker. This activates the Sunny Boy 5000TL Multi­String.
4. Check whether the LEDs of the Sunny Boy 5000TL Multi-String indicate trouble­free operation.
Installation Guide SB5000TL-12:SE2006 Page 27
Opening and Closing the Sunny Boy 5000TL SMA Technologie AG
Page 28 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Technical Documentation

7 Technical Documentation

7.1 Data PV Generator Connection

Max. input open-circuit voltage U Input voltage, MPP operation U Max. input current I Max. input power P
PV max
PV
Recommended generator power 6600 Wp All-pole disconnector
on DC input side Surge voltage protection thermally monitored varistors Voltage ripple U Personnel protection Ground Fault monitoring (Riso > 1 MΩ) Internal consumption in operation < 10 W (stand-by) Pole confusion prevention by short-circuit diode

7.2 Data Grid Connection

Nominal output power P Peak output power P Nominal output current I Harmonic distortion of output
(with K
)
om
< 2 %, PAC > 0,5 P
Unom
Short-circuit resistance Imax = 30 A Operating range, grid voltage U Operating range, grid frequency f All-pole disconnector on grid side independent disconnection device
Phase difference (related to basic wave of current)
Overvoltage category III Test voltage (50 Hz) 1.65 kV (5 s unit / type test) Surge voltage test 4 kV (1.2/50 ms)
Internal consumption in stand-by 0.25 W
ACNenn
THD
ACn-
AC
cos Phi 1
750 V (at -10 °C Module Temperature)
PV 0
125 V ... 750 V DC
PV
7,5 A per input port 3800 W per String
DC plug connector standard - other snap cable connectors optional
< 10 % of input voltage
PP
AC nom
ACm ax
4600 VA 5100 W 20 A < 4 %
IAC
198 ... 260 V AC
AC
49.8 ... 50.2 Hz
(MSD), (2 independant systems)
(serial interface: 6 kV)
Installation Guide SB5000TL-12:SE2006 Page 29
Technical Documentation SMA Technologie AG

7.3 Description of Device

You will find a detailed device description in the Operating Instructions.
General Data
Protection Degree according to DIN EN 60529 IP65
Dimensions (width x height x depth) approx. 470 mm x 490 mm x 225 mm Weight approx. 31 kg
External Interfaces
Data transmission via Powerline optional Data transmission via separate data cable optional,
RS232 / RS485, electrically separated
Data transmission via radio optional
Efficiency
Max. efficiency at nominal voltage η European weighted efficiency η
max
euro
The efficiency of the Sunny Boy 5000TL Multi-String depends on the input DC voltage coming from the PV modules. The higher the voltage the higher is the efficiency of the Sunny Boy 5000TL Multi-String.
95,5 % 94,5 %
Page 30 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Technical Documentation

7.4 Sunny Boy 5000TL Operating Parameters

Any unauthorized modifications of the operating parameters can
• result in serious injuries or casualties due to altered internal
safety precautions within the Sunny Boy
• void the operating permission of the Sunny Boy
• void the warranty of the Sunny Boy
Never change the operating parameters with out explicit permis­sion and instructions!
Name Unit Range Default
Betriebsart/ Operating Mode
Default GER/ENS
dFac-MAX Hz/s 0.005 ... 4.0 0.25
dZac-MAX mOhm 0 ... 2000 350
E_Total kWh 0 ... 200000
Fac-Delta- Hz 0 ... 4.5 (0.19) 0.19
Fac-Delta+ Hz 0 ... 4.5 0.19
h_Total h 0 ... 200000
Inst.-Code
NiTest/ impedance test
Riso-Min kOhm 1000 ... 30000 1000
Speicherfunktion/ Memory Function
Speicher/ Storage
Uac-Max/ Vac-Max
Uac-Min/ Vac-Min
Usoll-Konst A/ Vconst-SetpointA
Usoll-Konst B/ Vconst-SetpointB
Usoll-Konst C/ Vconst-SetpointC
V 180 ... 300 261
V 180 ... 300 198
V 0 ... 750 290
V 0 ... 750 290
V 0 ... 750 290
MPP/
Ikonst/
UKonst/
Stop
0 / 1 1
permanent/
volatile
MPP
none
permanent
Installation Guide SB5000TL-12:SE2006 Page 31
Technical Documentation SMA Technologie AG
The following parameters appear in parameter list but cannot be modified:
Name Unit Range Description
Plimit W 5100 Upper limit of AC output power
SMA-SN Serial Number of the Sunny Boy
Software-BFR/ Firmware-BFR
Software-SRR/ Firmware SRR
Hardware-DC-BFS Hardware version of the DC converter control unit (DC -
Firmware-DC-BFS Firmware version of the DC converter control unit (DC -
Firmware version of the operation control unit (BFR)
Firmware version of the current control unit (SRR)
BFR)
BFR)
Page 32 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Exchanging Varistors

8 Exchanging Varistors

The Sunny Boy 5000TL Multi-String is a very complex technical device. Therefore there are only a few possibilities to repair failures on site. Please do not try to make repairs otherwise than described in this document. Make use of our exchange service and the repair service of SMA Technologie AG.
If the red status LED is permanently on during operation please first make sure that there is no ground fault in the PV generator. Only if the green LED is permanently on at the same time, you can skip points 3 to 5 below.
1. Disconnect the grid (switch off the circuit break­er), secure it against accidental reactivation and ensure that it is disconnected.
Off!
1. 2. 3.
Ensure that the AC voltage is off before
you open the Sunny Boy 5000TL Multi-
2. Disconnect the DC plug connectors of all strings. Make sure that their allocation to the different inverter input ports can still be recognized!
String!
+- +- +-
String B
String C
String A
Disconnect the PV strings!
3. Measure voltages between one PV plug connector of each string and the ground potential. Follow all applicable safety instructions!
PE
Measure voltages between PV plug
connectors and the ground potential.
The voltage from the strings is very dangerous! Be very careful and pay attention to all applicable safety regulations!
4. If the voltages measured are constant and their total is approximately equal to the open-circuit voltage of the string, there is a ground fault in this string. Its appoximate position can be deducted from the ratios of voltages.
Installation Guide SB5000TL-12:SE2006 Page 33
Exchanging Varistors SMA Technologie AG
5. Repeat points 3 and 4 for each string. If you have found a ground fault it is probably unnecessary to exchange the varistors. Make sure to remove the ground fault instead. This should normally be done by the installer of the PV plant. In this case proceed with point 10, but with-out reconnecting the faulty string! Protect its PV plug connectors against touching (e. g. by protective caps or insulation strip with sufficient electric strength).
If you have not found any ground fault in the PV generators, probably one of the thermally monitored varistors has lost its protective function. The varistors are subject to wear and tear and their function is reduced in the course of their aging or in case of repeated strain placed on them by surge voltages. You can now check the varistors as described below while following the safety instructions given in chapter 2 „Safety Instructions” (page 9).
6. Unscrew the lid of the Sunny Boy 5000TL Multi-String and remove it. Disconnect the PE plug inside the lid. Test safe isolation from supply.
7. Test all varistors for an electric connection between terminals 2 and 3. If there is no electric connection the varistor is useless. The position of varistors in the Sunny Boy 5000TL Multi-String can be seen in chapter 3.1 „Device Description” (page 11).
8. Replace the defective varistor by a new one as shown in the figure on the left. Ensure correct orientation of the varistor! Please contact SMA if you have not received special tools to move the terminals (included in delivery of
Unlock the varistor
with the
extractor tool
replacement varistors). However, the terminal contacts can also provisionally be released one by one with a suitable screwdriver. The failure of a varistor is normally due to circumstances
Remove varistor
that apply to all varistors in a similar manner (temperature, age, induced surge voltages). We therefore strongly recommend not only to exchange the defective one, but all six. These varistors are specially manufactured for use in
123
The wire with the little dent must be inserted
into the terminal
number 1 when you
install the new varistor
the Sunny Boy 5000TL Multi-String and are not commercially available. They have to be purchased from SMA Technologie AG direct (SMA order name:“MSWR-TV-6“).
Page 34 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Exchanging Varistors
9. If no replacement varistors are available on site the Sunny Boy 5000TL Multi-String can also be operated without them for a limited period of time. To this end remove the varistors you have found to be defective and equip the terminals with a wire jumper between terminals 2 and 3 instead. The Sunny Boy 5000TL Multi-String is then not protected against surge voltages!
1 2 3
For a limited period of time a defective
varistor can be replaced by a wire
between terminal 2 and 3.
The input port thus modified is no longer protected against surge voltages! Equip the inverter with varistors again as soon as possi­ble. The Sunny Boy 5000TL Multi-String should not be operated without varistors in plants where is a high risk of surge voltages!
10. Reconnect the PE plug to the lid and close the Sunny Boy 5000TL Multi-String again.
11. Connect the faultless strings of the PV panel. Ensure correct allocation to strings.
12. Close off the unneeded DC input sockets using
+- +- +-
the protective caps supplied in the accessories kit.
String B
String C
String A
13. Switch on the circuit breaker.
14. Check whether the LEDs of the Sunny Boy
On!
5000TL Multi-String show trouble-free operation.
Off
If you have found neither a ground fault nor a defective varistor there probably is a fault in the Sunny Boy 5000TL Multi-String. Please contact the SMA hotline in this case to discuss further proceedings.
Installation Guide SB5000TL-12:SE2006 Page 35
Exchanging Varistors SMA Technologie AG
Page 36 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Sizing of a Circuit Breaker

9 Sizing of a Circuit Breaker

Example for the sizing of a circuit breaker for the AC line of a photovoltaic in­verter for utility interaction in terms of temperature.
Photovoltaic plant with 9 inverters type Sunny Boy 5000TL Multi-String with 3 inverters per phase
0 0
­6 8 : . r N
­. t r A
L1 L2 L3
0 0
­6 8 : . r N
­. t r A
0 0
­6 8 : . r N
­. t r A
...
0 0
­6 8 : . r N
­. t r A
0 0
­6 8 : . r N
­. t r A
0 0
­6 8 : . r N
­. t r A
N
Required data of the used inverters:
• max. output current: 22 A
• max. permissible rating of the circuit breaker for one inverter: 25 A
The type of cable as well as the type of cable installation and several other conditions have influence on the maximum rating of the circuit breaker for the inverter.
• In this example we assume that the cable used (6 mm²) can be used for nominal
currents up to 32.2 A in this example.
Selection of the circuit breakers:
• The maximum possible nominal current of the cable used and the maximum pos-
sible rating for the inverter now define the maximum possible nominal current of the circuit breakers.
• 25 A are possible in our example for one inverter.
The circuit breakers must also be selected according to their thermal characteristics.
Several aspects that have affect on the load must be considered when you select a circuit breaker. These aspects are specified in the data sheets of the circuit breakers.
Example for the sizing of a 25 A circuit breaker with B characteristics for the AC line of a photovoltaic inverter for utility interaction while the circuit break­ers are installed right next to each other without gap (with respect to the ther­mal conditions).
Installation Guide SB5000TL-12:SE2006 Page 37
Sizing of a Circuit Breaker SMA Technologie AG
One vendor of circuit breakers for example specifies the ratings for an ambient tem­perature of 50 °C.
Aspects that have an affect on the load specified in the data sheets:
• Reduction of the tolerable current because of continuous load > 1 h = 0.9
• Reduction of the tolerable current due to installation of 9 circuit breakers right
next to each other without gap = 0.77
• Increase of the tolerable current resulting from ambient temperatures of 40 °C in
the distribution box = 1.07
3
2
1
Result:
The nominal current of the circuit breaker is Inr = 32 A x 0.9 x 0.77 x 1.07 = 23.7 A
The circuit breaker selected for this installation is not suitable due to the fact that the maximum tolerable current of the circuit breaker is below the maximum current of the used inverter. It will trip in normal operation.
A solution for this plant would be the installation of the circuit breakers with an 8 mm gap between each unit. This would result in a reduction coefficient of 0.98 instead of
0.77. This would result in a maximum current of 23.6 A.
Beside the sizing of the circuit breakers in terms of thermal characteristics it is neces­sary to comply with all other applicable standards 4. These are especially:
• DIN VDE 0100 Part 410 and/or the international standard IEC 364-4-41:1992
• DIN VDE 0100 Part 430 and/or the international standard IEC 364-4-43:1977
and IEC 364-4-473:1977
• DIN VDE 0298 Part 4
1. In photovoltaic applications continuous loads of over 1 h are possible.
2. The coefficient is 1 in case there is only one single circuit breaker.
3. Resulting from the sizing of the circuit breakers for ambient temperatures of 50 °C.
4. The standards listed here are standards that apply in Germany. Please note that other standards apply in other countries. Beside the standards above oth­er standards may be applicable in special installations.
Page 38 SB5000TL-12:SE2006 Installation Guide
SMA Technologie AG Contact

10 Contact

If you have any questions or technical problems with the Sunny Boy 5000TL Multi­String our hotline will be glad to help you. Please keep the following data ready when calling SMA:
• Type of inverter used
• Connected modules and number of modules
• Communication
• Serial number of the Sunny Boy
Address:
SMA Technologie AG Hannoversche Strasse 1 - 5 34266 Niestetal Germany
Tel.:+49 (561) 95 22 - 499 Fax:+49 (561) 95 22 - 4699 hotline@SMA.de www.SMA.de
Installation Guide SB5000TL-12:SE2006 Page 39
Contact SMA Technologie AG
Page 40 SB5000TL-12:SE2006 Installation Guide
SMATechnologie AG
www.SMA.de
Hannoversche Straße 1–5 34266 Niestetal Germany Tel. +49 561 9522 - 0 Fax +49 561 9522 - 100 www.SMA.de
SMA America, Inc. 12438 Loma Rica Drive, Unit C Grass Valley, CA 95945 USA Tel. +1 530 273 4895 Fax +1 530 2747 271 www.SMA-AMERICA.com
SMA Solartechnology China Room 20F, InternationalMetro Center, Building A , City Square No. Jia 3, Shilipu Road, Changyang District 100025 Beijing, PR. China Tel. +86 10 65 58 78 15 Fax +86 10 65 58 78 13 www.SMA-CHINA.com
Loading...