21.0 SPARE PARTS VGH -xx-CH ........................................ 152
22.0 SPARE PARTS VGH -xx-CO ........................................ 157
WARNING: If the information in
this manual is not followed
exactly, a fire or explosion may
result causing property damage,
personal injury or loss of life.
other flammable vapors and
liquids in the vicinity of this or
any other appliance.
- WHAT TO DO IF YOU SMELL GAS
•
Do not try to light any appliance.
•
Do not touch any electrical switch; do not use
any phone in your building.
•
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
•
If you cannot reach your gas supplier, call the
fire department.
- Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
4 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
PROGRAMMABLE IN- AND OUTPUTS ................................................................................................... 87
11 USING THE DISPLAY ............................................................................................................................... 88
DISPLAY AND BUTTONS ..................................................................................................................... 88
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 5
SYSTEM TEST......................................................................................................................................... 125
15
16 COMMISSIONING THE BOILER............................................................................................................. 126
FIRST: FLUSHING THE BOILER WITH WATER ...................................................................................... 126
SECOND: FILLING & VENTING THE BOILER AND THE SYSTEM .............................................................. 126
THIRD: CHECK THE WATER FLOW ..................................................................................................... 126
MOUNTING THE CONDENSATE TRAP ................................................................................................ 127
CHECKING GAS PRE SSU RE.............................................................................................................. 127
FIRING FOR THE FIRST TIME ............................................................................................................ 128
17 ADJUSTING AND SETTING THE BOILER ............................................................................................ 129
21 SPARE PARTS VGH-xx-CH ................................................................................................................... 152
SPARE PART LIST VGH-XX-CH ....................................................................................................... 154
22 SPARE PARTS VGH-CO ........................................................................................................................ 157
SPARE PART LIST VGH-XX-CO ....................................................................................................... 159
6 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
IMPORTANT
THE FOLLOWING WARNINGS AND STATEMENTS BEFORE READING
indicates the presence of an imminently hazardous situation that will cause
death, serious personal injury or substantial property damage.
indicates the presence of a hazardous situation which can cause death,
serious personal injury or substantial property damage.
indicates a hazardous situation which will or can
cause minor or moderate personal injury or property damage.
hazards due to electric shock.
indicates speci al instruc tions on i nstallatio n, oper ation or mai ntenance t hat ar e
important but not related to personal injury or property damage.
is void. Failure to properly install this unit may result in property damage, serious injury to
occupants, or possibly death.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
WARNING
READ ALL OF
THE INSTALLATION INSTRUCTIONS
Danger Sign:
Warning Sign:
Caution Sign plus Safety Alert Symbol:
Caution Sign plus a lightning bolt indicates the risk of electric shock and the potential of
Notice Sign:
This Boiler must be installed by a licensed a n d t r ained H e at ing T echnician or the Warranty
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 7
1 SAFETY GUIDELINES
8 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
CONSIGNES DE SÉCURITÉ.
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 9
n the event of a blocked vent the boiler w ill
operation.
only be reset by
• Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the
Read this manual entirely before setting domestic hot water setpoint(s).
•WARNING: There are no u s er s erv ic eable par ts o n th i s boi ler. Warr anty does n ot c over
recommended personal protective equipment. Installation and service must be
appliance.
WARNING: Improper installation, adjustment,
humans)
AVERTISSEMENT: Une installation, un réglage, une
pouvant l'être).
CAUTION
DANGER
NOTICE
WARNING
Avertissement
WARNING
This boiler is equi pped with a pressure s witch. I
lockout. No attempt by the user/owner should be made to put the boiler back into
A qualified service technician must be notified of the issue. The boiler should
a qualified service technician after they have diagnosed and corrected the issued that caused
the safety lockout of the boiler.
electrical supply to the circ ulator. Instead, shut of f the gas s upply at a locat ion external t o
the appliance.
• Do not use this boiler if any part has been under water. Immediately call a qualified service
technician to inspect the boiler and to r eplac e any part of the c ontrol sy stem and any gas
control which has been under water.
•Scalding
Water temperatures over 125 ºF (5 2 ºC) c an c ause sev ere burns i nstant ly, or dea th fro m
scalds. Children, the disabled and the elderly are at the highest risk of being scalded.
Feel water before bathing or showering.
We highly recommend the ins tal lat ion of a c ar b on m on ox ide (CO ) de tec tor i n the boi ler r oo m
for all installations.
defects caused by at t emp ts to s erv ice t h is bo il er by s o meon e other than a qualif ie d ga s
service technician. These attempts could cause property damage, personal injury or loss
of life.
•WARNING: Crystalline Sil ica - Certain components in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, serious injury (exposure to hazardous
materials) or death. Refer to Section 18.2
for information on handling instructi ons and
performed by a qualified installer, service agency or the gas supplier (who must read and
follow the supplied instructions be fore install ing, servic ing, or removin g this boiler. This
boiler contains materials that have been identified as carcinogenic, or possibly
carcinogenic, to humans).
•WARNING: There are no u s er ser v iceable par ts o n t h i s boi ler. Warranty does not c ov er
defects caused by at t emp ts to s erv ice t h is bo il er by s o meon e other than a qualif ie d ga s
service technician. These attempts could cause property damage, personal injury or loss
of life.
•a water heater that will be used t o supply p otable water s hall not be co nnected to a ny
heating system or component(s) previously used with a non-potable water heating
alteration, service or maintenance can cause
property damage, personal injury (exposure to
hazardous materials) * or loss of life.
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier (who must read and follow the
supplied instructions before installing,
servicing, or removing this boiler. This boiler
contains materials that have been identified as
carcinogenic, or possibly carcinogenic, to
10 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
modification, une réparation ou un entretien non
conforme aux normes peut entraîner des dommages
matériels, des blessures (exposition à des matières
dangereuses) ou la mort. L'installation et l'entretien
doivent être effectués par un installateur ou un service
d'entretien qualifié ou le fournisseur de gaz (qui doivent
avoir lu les instructions fournies avant de faire
l'installation, l'entretien ou l'enlèvement de la chaudière
et les respecter. Cette chaudière contient des matériaux
qui ont été identifiés comme étant cancérogènes ou
Avertissement
L'installation et l'entretien doivent être assurés par un installateur ou un service
AVERTISSEMENT. Assurez-vous de bien suivre les instructions données dans
AVERTISSEMEN T. Assure z-vous de b ien suivre les ins tructions d onnées d ans cette notice p our rédu ire au
minimum le risque d'incendie ou d'explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
(pour installateurs francophones)
cette notice pour réduire au minimum le risque d'incendie ou d'explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
— Ne pas entreposer ni utiliser d'essence ou ni d'autres vapeurs ou liquides
inflammables à proximité de cet appareil ou de tout autre appareil.
— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
•Ne pas tenter d’allumer d’appareils.
•Ne touchez à aucu n interrupteur. N e pas vous servir de s téléphones dans le bât iment
où vous vous trouvez.
•Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les
instructions du fournisseur.
•Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incendies.
d'entretien qualifié ou par le fournisseur de gaz.
INTRODUCTION
Ce manuel est écrit pour l’utilisateur.
Slant/Fin n'est pas responsable de tout dommage causé par ne pas suivre correctement de ces instructions. Pour
service et réparation, utiliser seulement pièces de rechange de Slant/Fin. Tout documentation produit par le
fabricant est sous réserve de la loi sur le droit d'auteur. Ce manuel est sujet à changement sans préavis.
Explications:
VGH = Chaudière à condensation
DHW = Eau Chaude Sanitaire (ECS)
CH = Chauffage central (pour objectif chauffage et/ ou eau chaude indirect)
BCU = commande (burner control unit)
PB = écran (Pixel Button)
CONSIGNES DE SÉCURITÉ
POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE
« A. Cet appareil ne comporte pas de veilleuse. Il est muni d'un dispositif d'allumage qui allume automatique-ment
le brûleur. Ne tentez pas d'allumer le brûleur manuellement.»
« B. AVANT DE FAI RE FO NCTIONNER , reniflez tout autour d e l'appar eil pour déceler une odeur de g az. Reniflez près du plancher, car certains gaz sont plus lourds que l'air et peuvent s'accumuler au niveau du sol. »
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
•Ne pas tenter d'allumer d'appareil.
•Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
•Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
•Si vous ne pouvez rejoindre le fournisseur, appelez le service des incendies.
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 11
« C. Ne poussez o u to urne z la man ette d' a dm iss ion d u gaz qu'à l a m ain ; ne j a m ais ut il iser d' out il. S i la manette
OUVRIR FERMER
reste coincée, ne pas tenter de la réparer ; appelez u n technicien qualifié. Le fait de for cer la ma nette ou de la
réparer peut déclencher une explosion ou un incendie. »
« D. N'utilisez pas cet appareil s'il a été plongé dans l'eau, même partiellement. Faites inspecter l'appareil par un
technicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans
l'eau. »
Avertissement
Une installation, un r églage, une modificat ion, une réparation ou u n entretien non con-for me aux normes peut
entraîner des dommages matériels, des blessures (exposition à des matières dange-reuses) ou la mort.
L'installation et l'entretien doivent être effectués par un installateur ou un service d'entretien qualifié ou le
fournisseur de gaz (qui doivent avoir lu les instructions fournies avant de faire l'installation, l'en-tretien ou
l'enlèvement de la chaudière et les respecter. Cette chaudière contient des matériaux qui ont été iden-tifiés
comme étant cancérogènes ou pouvant l'être).
Comment couper l'admission de gaz de L’appareil:
1. Réglez le thermostat à la température la plus basse.
2. Coupez l'alimentation électrique de l'appareil s'il faut procéder à l'entretien
3. Le robinet d'arrêt de gaz est situé dessous la chaudière dans la conduite de gaz.
4. Tourner le robinet sens horaire à "OFF" (fermé) pour arrêter l’alimentation
en gaz. Ne pas forcer.
En cas de surchauffe ou s i l'admission de g az ne peut être coupée, ne pas c ouper ni débranc her l'aliment ation
électrique de la pompe. Fermer plutôt le robinet d'admission de gaz à l'extérieur de l'appareil.
Entretien et inspection
« Inspecter de faço n v isue ll e le s y s tème d'év ac ua tio n pour d ét erm in er l a gros s eu r et l'inclinaison hor iz ont ale qui
conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement, de fuite, de corrosion et autres
défaillances qui pourraient présenter des risques. »
L'entretien et l'inspection de la chaud ière doivent être effectués aux occasions suivantes :
• Lorsqu'un certain nombre de codes d'erreur et/ou de verrouillage semblables apparaissent.
• Au moins tous les 12 mois, l'entretien doit être fait pour assurer un fonctionnement sûr et effic ace.
Les dommages causés par le manque d'entretien ne seront pas couverts par la garantie
Retrait d'une chaudière existante.
« Au moment du retrait d'une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil
toujours raccordé au système d'évacuation commun et qui fonctionne alors que d'autres appareils toujours
raccordés au système d'évacuation ne fonctionnent pas :»
« Sceller toutes les ouvertures non utilisées du système d'évacuation. »
« Inspecter de façon visuelle le système d'évacuation pour déterminer la grosseur et l'inclinaison horizontale qui
conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement, de fuite, de corrosion et autres
défaillances qui pourraient pr és enter des risqu es .
« Dans la mesure du poss ible, fermer toutes les port es et les fenêtres du bâtiment et tou tes les portes entre
l'espace où les apparei ls toujours raccordés au système d' évacuation sont installés et les autr es espaces du
bâtiment. Mettre en marc he les séc heuses, tous les appare ils non rac cordés au système d'év acuation c ommun
et tous les ventilateurs d'extraction comme les hottes de cuisinière et les ventilateurs des salles de bain. S'assurer
que ces ventilateurs fonct ionnent à la vitess e maximale. Ne pas fa ire fonctionner les ventilateurs d'été . Fermer
les registres des cheminées. » « Mettre l'appareil inspecté en marche. Suivre les instructions d'allumage. Régler
le thermostat de façon que l'appareil fonctionne de façon continue. »
« Une fois qu'il a été déterminé, selon la méthode indiquée ci-dessus, que chaque appareil raccordé au système
d'évacuation est m is à l'air libre de façon adé quate. Remettre les portes et les fenêtres, les ventilateurs, les
registres de cheminées et les appareils au gaz à leur position originale.
« Tout mauvais fonctionnement du système d'évacuation commun devrait être corrigé de façon que l'installation
soit conforme au N ational Fuel Gas Code, ANSI Z 223.1/NFPA 54 et (où) aux c odes d'installation CAN/CSAB149.1. Si la grosseur d'u ne s ection du s yst ème d'éva cuatio n doit être modifi ée, l e sys tème devrait être mo difi é
pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 et (où) les codes d'installation CAN/CSA-B149.1. »
12 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
2 INTRODUCTION
1. Combi-boiler (CH & DHW)
2. Carbon mo noxid e
This manual is the installation and service manual for the high-efficiency heating systems from the VGH-CH
(Central Heating boi lers) series and VGH-CO (Combi boilers) series. This manual is spec ifically written for the
installer.
The distributor and manufacturer ar e not ac countable for any damag e c aused by installers not correctly following
these instructions.
For service and repair purposes use only original Slant/Fin spare parts.
All documentation produced by the manufacturer is subject to copyright law.
This manual is subject to change without notice.
Terms and abbreviations
In this manual the following terms and abbreviations are used:
A (Amp) Ampère
AFUE Annual Fuel Utilization Efficiency
AHRI Air-conditioning, Heating and Refrigeration Institute
ANSI American National Standards Institute
ASME American Society of Mechanical Engineers
ASSE American Society of Sanitary Engineering
bar Unit of pressure (1 bar = 14.5 PSI)
BCU Burner Control Unit
BTU British Thermal Unit
°C Degree Celsius
CaCO3 Calcium carbonate
CH Central Heating.
CO
CO2 Carbon dioxide
Combi A boiler providing a combination of central heating and domestic hot water
CVPC Chlorinated Polyvinyl Chloride, a thermoplastic
DHW Domestic Hot Water
°F Degree Fahrenheit
Hz Hertz
LB Digit-based Liquid Crystal Display Board
LCD Liquid Crystal Display
LPG Liquefied Petroleum Gas
MBH 1000 BTUs per hour
mg Milligram
NFPA National Fire Protection Association
NOx Mono-nitrogen oxides
NPT National Pipe Thread, American standard for threaded pipes and fittings
NTC Negative Temperature Coe fficie nt, a quality of sensors and resistors
O
2
PB Graphical Display Board
Oxygen
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 13
PCB Printed Circuit Board
•ASME Boiler and Pressure Vessel Code
Section “Heating boilers”
•ASME Boiler and Pressure Vessel Code
Section “Recommended Rules for the Care and Operation of
Heating Boilers”
•ANSI Z223.1 / NFPA 54
National Fuel Gas Code
•ANSI / NFPA 70
National Electrical Code
•ANSI / NFPA 211
Chimneys, Fireplaces, Vents and Solid Fuel Burning
Appliances
PEX Cross-linked polyethylene
pH Acidity degree
PID Proportional Integral Derivative, a control concept used in automation
ppm Particles per million
psi Pounds per square inch, a unit of pressure
Pump Circulator
PVC Polyvinyl Chloride, a thermoplastic
PWM Pulse Width Modulation
RCF Refractory Ceramic Fibers
RT Room Thermostat
TDS Total Diss olv e d Solids, a characteristic used in water quality
UL Underwriters Laboratories, American testing and certification institute
VAC Volt Alternating Current
VDC Volt Direct Current
W Watt, a unit of power
W.C. Water column
Codes, standards and regulations
Installation, maintenance and repairs must be performed in strict accordance with the state and local requirements
and regulations.
In the absence of local requirements, the following standards and regulations apply:
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and
Safety Devices for Automatically Fired Boilers, ANSI, ASME CSD-1.
Maintenance and inspection
For a good, safe and long-lasting operation of the boi ler and to maintain warranty it is m andatory to carry out
inspection, maintenance and service on the boiler at least once a year.
Maintenance and inspection of the boiler must be carried out in the following situations:
• When a number of similar error codes and/or lockouts appear.
• At least once every 12 months to ensure safe and efficient operation.
Damage caused by lack of maintenance will not be covered under warranty.
Visually inspect the venting system for pro per size and horizonta l pitch and determine ther e is no blockage or
restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
More details on maintenance, inspections and repairs are cover ed in chapter 18.
14 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
For installations in the Commonwealth of Massachusetts
The following local requirements apply in addition to all other applicable NFPA requirements:
For direct-vent boilers, mec hanical-vent heat ing appliances or domestic hot water equi pment, where the bott om
of the vent termina l and the intake is installed below four feet above grade, th e following requ irements mus t be
met:
1) If not present o n each floor level wher e there are be drooms, a car bon monox ide det ector an d alarm must
be placed in a living area outside the bedrooms. The carbon monoxide detector and alarm must comply with
NFPA 720 (2005 Edition).
2) A carbon monoxide detector and alarm must be located in the room that houses the boiler and/or equipment and must:
a) be powered by the same electrical circuit as the boiler and/or equipment so that only one service switch
services both the boiler and the carbon monoxide detector;
b) have battery back-up power;
c) meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
d) have been approved and listed by a Nationally Recognized Testing Lab as recognized under 527 CMR.
3) A product-approve d vent terminal must be us ed, and if applicable, a pro duct approved air intak e must be
used. Installation must be performed in strict compliance with the manufacturer’s instructions. A copy of the
installation instructions must remain with the boiler and/or equipment at the completion of the installation.
4) A metal or plastic identification plate must be mounted at the exterior of the building, four feet directly above
the location of ve nt ter mina l. The plate must be of suffic ient size to be eas ily read from a dis tance of eigh t
feet away and read “Gas Vent Directly Below”.
For direct-vent boilers mechanical-vent heating boilers or domestic hot water equipment, where the bottom of the
vent terminal and the intake is installed higher than four feet above grade, the following requirements must be met:
1) If not present o n each floor level wher e there are be drooms, a car bon monox ide det ector an d alarm must
be placed in a living area outside the bedrooms. The carbon monoxide detector and alarm must comply with
NFPA 720 (2005 Edition).
2) A carbon monoxide detector must:
a) be located in the room where the boiler and/or equipment is located;
b) be either hard-wired or battery powered or both; and:
c) comply with NFPA 720 (2005 Edition).
3) A product-approve d vent te rminal mus t be used, a nd if applicab le, a produc t- approved air intak e must be
used. Installation must be in strict compliance with the manufacturer’s instructions. A copy of the installation
instructions must remain with the boiler and/or equipment at the completion of the installation.
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 15
3 TECHNI CAL DATA VGH RESIDENTIAL BOILERS
On/Off thermostat or modulating thermostat
Low Water Cut Off
System circulator
Alarm outputs
On/Off thermostat or modulating thermostat
Low Water Cut Off
System circulator
Alarm outputs
FUNCTIONAL INTRODUCTION
The VGH b oilers are cent ral heatin g/combi boilers w ith a maximu m high effici ency. Such a performance c an be
reached by, amongst o ther things, using a sp ecial heat exchanger m ade of stainless stee l. This allows the flue
gases to cool down below the condensation point, thus releasing extra heat. This has an immediate positive impact
on the efficiency.
The VGH boiler is factory set for Natural gas.
Fuel used must have Sulphur rates with a maximum a nnual peak over a s hort pe riod of tim e of 150 mg/m
3
ppm) and an annual average of 30 mg/m
. (22 ppm average).
Boiler control includes:
Cascade control for up to sixteen boilers
Remote operation and heat demand indication from each boiler
Weather compensation control – Outdoor reset.
Indirect tank control (On heat only boiler models)
Connections for VGH-CH boilers:
3
(110
0-10 VDC remote flow temperature (set point) control
0-10 VDC remote boiler input control
Outdoor temperature sensor
External indirect tank circulator or diverter valve
PWM control for external boiler circulator.
Connections for VGH-CO boilers:
0-10 VDC remote flow temperature (set point) control
0-10 VDC remote boiler input control
Outdoor temperature sensor
PWM control for external boiler circulator.
External flow switch or external safety device.
Modbus
External system sensor
DHW indirect sensor or aquastat.
External Ignition coil
External flow switch or external safety device.
Modbus
External system sensor
External Ignition coil
16 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Information
Software Versions
Error Log
Figure 3.1
Software Versions
Display [63EF 83BC]
Figure 3.2
Figure 3.3
Location of version numbers
Burner Controller Hardware Version
– To be found on the second line of the white sticker on the side of the burner controller.
e.g. 957MN15_3Rh4b
Burner Controller Software Versions
• Press the menu button
• Go to Information
• Go to Software Versions.
Boiler Status
Boiler History
i
Boiler [5C79 14A9]
Device Group 900MN
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 17
Minimum power consumption W 140140140
Maximum power consumption W 190220200
Standby power consumption W 666
Power supply V/Hz 120 / 60
Protection class - IPX4D5
NOTES
3
CO2 or O2 of the unit measured/set without the boiler front panel in place.
4
Maximum allowed combined resistance of flue gas and air supply piping at high fire
5
For gas appliance type B23(P) (Room Air) only class IPX4D with special air inlet, otherwise the
protection class is IP20 (see also picture at page 19)
6
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 21
TECHNICAL SPECIFICATIONS VGH-180-CH/VGH-200-CO
IV
Type boiler
VGH-180-CH
VGH-200-CO
p nom inch W.C. (mbar)
p min inch W.C. (mbar)
p max inch W.C. (mbar)
Propane
11.0 (27.4)
8.0 (19.9)
13.0 (32.4)
Table 3. 5
GENERAL
Boiler category -
Dimensions (h x w x d) Inch (mm) 28.2" x 17.4" x 16.9" (717mm x 442mm x 429mm)
Water content
Gallon
(liter)
0.83 (3.15) 0.83 (3.15)
Weight (empty) Lbs (kg) 98 (44) 101 (46)
Supply/return connection
CH
Supply/return connection
DHW
inch NPT ¾” NPT ¾”
inch
NPT ¾” NPT ½”
Gas connection inch NPT ¾” NPT ¾”
Flue connection Inch (mm) 3” (80mm) 3” (80mm)
GAS CONSUMPTION Values min-max:
Natural gas
Propane
1
Gas supply
Nat. gas
ft3/h
m3/h
ft3/h
3
/h
m
Inch W.C./
(mbar)
16.7 – 167.4
0.47 – 4.74
7.2 – 72.1
0.2 – 2.04
18.6 – 186.0
0.52 – 5.26
8.0 – 80.0
0.23 – 22.7
7.0 (17.4)
pressure
nominal 2
Propane
Inch W.C./
(mbar)
11.0 (27.4)
NOTES
1
Using propane, maximum fan speed needs to be reduced.
2Min. and max. gas supply pressures are listed in the table below.
Natural gas 7.0 (17.4) 3.5 (8.7) 10.5 (26.2)
22 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Type boiler
VGH-180-CH
VGH-200-CO
CO2 flue gas
Low Fire %
9.4 – 8.9
High Fire %
9.1 – 8.4
Low Fire %
9.8
High Fire %
10.1
Low Fire %
4.1 – 5.0
High Fire %
4.6 – 6.0
Low Fire %
6.0
High Fire %
5.5
Inch W.C.
(Pa)
INSTALLATION
T = 20 F
68.4 (20.8)
68.4 (20.8)
T = 35 F
22.6 (6.9)
22.6 (6.9)
Pressure boiler min-max.
psi (bar)
11.6 – 43.5 (0.8 – 3.0)
Max. supply temperature
°F (°C)
194 (90)
DHW PERFORMANCE
flow rate at ∆T = 77 °F
gal/min (l/min)
-
4.6 (17.4)
Pressure DHW min-max
psi (bar)
-
14.5 - 116 (1.0 -8.0)
Thermal Efficiency 6
%
95.4
ELECTRIC
Minimum power consumption
W
150
150
Maximum power consumption
W
260
290
Standby power consumption
W 6 6
Power supply
V/Hz
120 / 60
Protection class - IPX4D5
NOTES
Efficiency of DHW performance measured according to ANSI Z21.10.3-2015 • CSA 4.3-2015
Table 3. 6
O2 flue gas
3
3
Natural gas
Propane
Natural gas
Propane
Flue gas temperature at combustion air
temperature = 70 °F (20 °C)
Available pressure for the flue and inlet system 4
Resistance
boiler
3
CO2 or O2 of the unit measured/set without the boiler front panel in place
4
Maximum allowed combined resistance of flue gas and air supply piping at high fire
5
For gas appliance type B23( P) (Room Air) only class IPX4D with special air inlet, otherwise the
∆
∆
°F (°C) 86 – 153 (30 – 67)
400 490
ft.head (m.W.C.)
ft.head (m.W.C.)
protection class is IP20 (see also picture at page 19)
6
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 23
NOTICE
High altitude operation
High Altitude Operation
Elevations
2000 ft (610 m)
3000 ft (914 m)
4000 ft (1219 m)
4500 ft (1372 m)
Above 4500 ft (1372 m)
In USA
No de-rate
De-rate by 4 %
De-rate by 8 %
De-rate by 10 %
De-rate 4% per 1000 ft.
In Canada
No de-rate
De-rate by 10%
De-rate by 10 %
De-rate by 10 %
De-rate 4% per 1000 ft.
Model number
Min
Max
Combustion – At elevations above 2000 ft (610 m), the combustion of the appliance must be checked with
kits are neede d, sinc e the 1: 1 Gas /A ir ra tio o f th e gas v alv e and th e ven tu ri w ill re spo n d
instructions may result in property damage, serious injury, or death.
Table 3. 7
Table 3. 8
Boiler model
number
pressure
temperature*
capacity
surface
VGH-80-CH /
VGH-90-CO
461953
T4804.4CL
50 Psi
210 °F
91 MBH
7.99 SQTF
VGH -100-CH
461955
T4804.4CL
50 Psi
210 °F
136 MBH
9.99 SQFT
VGH -120-CH
/ VGH-150-CO
461959
T4806.4CL
50 Psi
210 °F
182 MBH
11.99
SQFT
VGH-150-CH /
VGH-200-CO
461963
T4807.4CL
50 Psi
210 °F
227 MBH
17.98
Table 3. 9
The boiler is designed to operate at its maximum listed capacity in installations at elevations less than or equal to 2000 ft
(610 m) above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity will be
de-rated for elevations above 2000 ft (610 m) in accordance with the table underneath.
In USA and Canada, de-rate by 4% extra for every 1000 ft. above 4500 ft.
a calibrated (altitude corrected) combustion analyzer to ensure safe and reliable operation. No orifices o r
high-altitude
automatically to reduced air pressure.
It is the Installers responsibility to check the combustion of the appliance. Failure to follow these
How to calculate De-rating at intermediate elevations for US:
Elevation between:
2000 and 3000 ft : (New value – 2000) x 0.004 Example: Elevation is 2600 ft. De-rating is (2600-2000)x0.004 = 2.4 %
3000 till 4000 ft : ((New value – 3000) x 0.004)+4 Example: Elevation is 3700 ft. De-rating is ((3700-3000)x0.004)+4 = 6.8 %
4000 till 4500 ft : ((New value – 4000) x 0.004)+8 Example: Elevation is 4200 ft. De-rating is ((4200-4000)x0.004)+8 = 8.8 %
Above 4500 ft : ((New value – 4500) x 0.004)+10 Example: Elevation is 4800 ft. De-rating is ((4800-4500)x0.004)+10 = 11.2 %
How to calculate De-rating at intermediate elevations for Canada:
Elevation between:
2000 till 4500 ft : All values de-rate by 10% Example: Elevation is 3600 ft. De-rating = 10 %
Above 4500 ft : ((New value – 4500) x 0.004)+10 Example: Elevation is 7600 ft. De-rating is ((7600-4500)x0.004)+10 = 22.4 %
External flow temperature sensor for behind the low header 10kOhm@77°F
81 7109 000
MagFilter Pro XL
81 7284 000
Mag Flush Pro
81 7132 000
Heating System Cleaner
81 7133 000
Heating System Protector
81 7134 000
VGH Residential Yearly Maintenance Service Kit
81 7285 000
French I&O Manual Residential Boiler
81 7282 000
French User Manual residential Boiler
81 7283 000
Qty Description
Part number
1
Startup and commissioning check list
---
1
Wall bracket with locking plate and bolts
81 7264 000
3
Spare nuts for the burner plate (in a bag attached to the front of the gas valve)
See spare part list
1
Spare fuse for the boiler control (at the burner controller)
See spare part list
1
Bottom part of the condensate drain assembly
81 7263 000
1
Pressure/temperature residential VGH control kit
81 7288 000
This kit consists of
1 ASME pressure 30 psi relief valve (packed into an additional box)
65 0550 000
1 Outdoor (air) temperature sensor: 10kOhm@25°C -B3977
81 7108 000
1 Temperature and pressure gauge
91 0373 061
1 ¾ Gas shut off ball valve
83 3803 000
1 Boiler Drain
40 0201 000
1 Warranty card
41 1189 000
1 VGH Residential Installation and Service manual
81 7286 000
1 VGH Residential User Manual
81 7287 000
Table 5. 1
Table 5. 2
Optional Accessories
Depending on the selected boiler type, the selected controlling behavior for the central heating system and/or the
optional use of an indirect tank, the following items are available as accessories. Contact your supplier for ordering.
Supplied with the boiler
The VGH boiler will be supplied with the following documents and accessories:
After delivery, always check the boiler package to see if it is complete and without any defects. Report any defects
or missing parts immediately to your supplier.
28 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
CAUTION
6 INSTALLATION LOCATION OF THE VGH
The installation of the gas appliance must conform to the requirements of this manual and your
CSD-1
The wall used for mou nting t he b oiler must be ab le to hol d the weight of th e boile r, pipin g and
a (optional cascade) stand.
NOTICE
General
The boiler must be posit ioned and installed by a qua lified installer or the gas company in acc ordance with all
applicable standards , local codes and regulat ions (see also paragrap h 2.2). Commissioning of t he b oi ler must be
done by a qualified installer or technician, who has been trained for this type of boiler.
Boiler Installation Location Requirements
The installation of the boiler must meet the following location requirements:
• The installation of this boiler when installed using room air must comply with NFPA 54.
• The flue gas pipes must be connected to the outside wall and/or the outside roof, see chapter 9.
• The installation area must be dry and frost-free.
• The boiler has a built-in fa n that will generate noise, depending on the tota l heat demand. The boiler
location must minimize any disturbance this might cause. Preferably mount the boiler on a solidly
constructed wall or stand.
• There must be sufficient lighting available in the boiler room to work safely on the boiler.
• When a boiler is position ed at the highes t point of the installation, th e supply and return pipes mus t first
protrude 20” above the top of the boiler, before these pipes go to the installation side. In other words, the
water level must always be 20” above t he top o f the b oiler an d an auto mat ic air v ent mus t be inst alled i n
the supply or return pipe. It is recommended to install a low water cut off above the boiler, when the boiler
is installed above the system or at the highest po int in the insta llatio n.
• Do not install the boiler in a location where it will be exposed to temperatures of 100 °F or higher.
• Do not install the boiler in a location where it w ill be exposed t o high levels of humi dity and moisture or
where condensation might fall onto the boiler.
•Make sure there is an open connection to the s ewer to drain the c ondensate. This conn ection must be
lower than the condensate drains level of the boiler. If not, a condensate pump will be required.
•Do not locate the boiler in an area which contains corrosive or other contaminants as outlined in section
9.8.1, especially Table 9.11 and Table 9.12.
•When considering installation locations, consideration must be given to the combustion air supply,
specifically whether to use indoor air or sealed combustion.
•Do not allow the combustion air to come from a source or area which contains corrosive or other
contaminants as outlined in section 9.8.1, especially Table 9.11 and Table 9.12.
The boiler must be positioned and installed by a qualified installer or gas company in accordance with all applicable
standards, local codes and regulations. Commissioning of the boiler must be done by a qualified installer or
technician, who has been trained for this type of boiler.
In the Commonwealth of Massachusetts this boiler must be installed by a licensed Plumber or Gas Fitter.
The installation area/room must have the following provisions:
• 120 V - 60 Hz power source socket with ground.
• Open connection to the sewer system for draining condensing water.
• A wall or stand to properly support the weight of the boiler.
• Depending on the current of the used circulator, apply a circuit break er betw e en 6 and 12 amps
local authority. Where required by the authority having jurisdiction, the installation must conform
to the standard for Controls and Safety Devices for Automatically Fired Boilers ANSI/ASME
fittings, and the we ight of the w ater. If not, it is r ec ommend ed to mount t he boi ler by means of
The boiler must NOT be installed on or near carpeting.
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO 29
Model No.
Clearances to wall, ceiling and floor
A: Front
B: Top
C: Sides
D: Back
E: Bottom
Minimum required
clearances
Recommended
service clearances
Clearances from combustible materials
2. Vent pipe – at least 1" (25 mm) from combustible materials.
* See closet / enclosure installation.
Table 6. 1
Figure 6.1
Ceiling
A
Wall
E
B
C
C
D
A
Installation Clearances
When installing the boiler, the following table shows the clearances which are required, and which clearances are
recommended considering service and maintenance. If the recommended clearances are not provided service or
maintenance on the boiler might not be possible without removing the boiler from its space.
1. Hot water pipes—at least 1/2" (12 mm) from combustible materials.
Closet / enclosure installation
If the boiler is installed in closets or small enclosures which do not provide at least the recommended clearances,
air openings must be provided to the front of the closet or enclosure.
These air openings must be maximum 12 inch from the top and maximum 12 inch from the bottom of the enclosure.
* To get enough air cir culat i on on e of t hose t w o values (Front or S ides) has t o be at least 1 inch the other can be
0”.
Note
PVC venting is not permitted within the closet, alcove, or enclosure when the boiler is installed in a closet, alcove
or small enclosure. See also chapter 9.
30 E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Loading...
+ 134 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.