Slant/Fin SC-3 User Manual

FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS
SC-3 Controller
MODULAR BOILER CONTROLLER SERIES
INSTALLATION AND OPERATING INSTRUCTIONS
SC-3 Applications
• Space Heat Systems With Outdoor Reset
• Constant Temperature Setpoint Control
CONTENTS
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
a) Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
b) Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
c) View of Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
d) System Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Select System Type . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
A. Space Heating Only with Outdoor Reset . . . . . . .12
a) Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . .12
b) Functions and Defaults . . . . . . . . . . . . . . . . . . . .13
c) Adjusting the Settings . . . . . . . . . . . . . . . . . . . . .13
B. Space Heating Only w/Setpoint Control . . . . . . . .17
a) Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . .17
b) Functions and Defaults . . . . . . . . . . . . . . . . . . . . . .18
c) Adjusting the Settings . . . . . . . . . . . . . . . . . . . . . . .20
Viewing the Performance . . . . . . . . . . . . . . . . . . . . . . . . .22
Useful Hints and Reloading Factory Defaults . . . . . . . .23
Testing the Contol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Factory Default Listings . . . . . . . . . . . . . . . . . . . . . . . . . .28
If your system is different than the above, call the Slant/Fin
determine the proper control.
The SC-3 is a microprocessor control which will sequence up to three heating stages based on outdoor air temperature and supply water temperature. Designed to handle a Caravan gas-fired, oil-fired or *dual fuel-fired hot water heating plant for space heating or “Setpoint” operation. A large easy to read display provides current system temperatures and operating status.
ADDITIONAL FUNCTIONS INCLUDE: Pump exercising. Pump purging. Boiler demand for space heating loads. Set point demands for set point loads. Test sequence to ensure proper component operation. CSA C US certified. Setback input for energy savings.
SPACE HEATING OPERATION: When the outdoor air tempera­ture drops below a preset value, the heating system is energized. The SC-3 Controller determines the number of stages required to meet the space heating needs and fires them. During operation, the Controller scans system temperatures, adding or deleting stages as necessary to satisfy heating load.
Controller Packing List
1- SC-3 Modular Controller P/N 435081 1- Outdoor sensor with enclosure P/N 339070 1- Universal sensor P/N 339071
SETPOINT OPERATION: The SC-3 adds and deletes stages to minimize the difference between the desired Setpoint temperature and the actual measured Supply Water Temperature.
Dual-Fuel * Not available in Canada
Printed in U.S.A. 605 PUBLICATION SC-3-40 Part No. 435083000
3 SC-3 Controller
INSTALLATION
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for uses as a primary limit control. Other controls that are intended and certified as safety limit must be placed into the control circuit. Do not open the control. Refer to qualified personnel for servicing. Opening voids warranty and could result in damage to the equipment and possibly even personal injury.
CONTROL PANEL MOUNTING
The control panel is to be mounted in an indoor area where the ambient temperature range will be 30 to 120˚F (0 to 50˚C) and less that 95% RH. Power Supply is to be 115 V (ac) +/- 10% 50/60 Hz 600 VA.
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference­Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is deter­mined by turning the control on and off, the user is encouraged to try and correct the interference by re-orienting or relocating the receiving antenna, relocating the receiver with respect to the control, and/or connecting the control to a different circuit from that to which the receiver is connected.
WARNING: The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and jumper wires as needed.
Press down at the fingertip grips on top of the front cover and pull out and down.
Remove the safety dividers from the wiring chamber by pulling them straight out of their grooves.
The control can be mounted on a standard DIN rail. First remove the control from its base and then, using the hooks and spring clip on the back of the control, mount it onto the DIN rail. This will be a popular option for those who prefer to mount the control inside a larg­er electrical panel.
Lift the front cover up and away from the control.
Press the control release clip on the base inside the wiring chamber and slide the control upwards.
Loosen the screws at the front of the wiring cover.
The control lifts up and away from the base.
The wiring can enter the bottom or the back of the enclosure. Knock­outs provided in the base allow the wiring to be run in conduit up to the enclosure. The base also has holes that line up with the mounting holes of most common electrical boxes.
The wiring cover pulls straight out from the wiring chamber.
The base is ready for mounting.
SC-3 Controller 4
INSTALLING THE SENSORS OUTDOOR SENSOR SF P/N 339070
MOUNTING THE SENSOR
Note: The temperature sensor (thermistor) is built into the enclosure.
• Remove the screw and pull the front cover ff the sensor enclosure.
o
• The enclosure can either be mounted directly
onto a wall or a 2” x 4” electrical box. When it is wall mounted, the wiring should enter through the back or bottom of the enclosure. Do not mount the enclosure with the conduit knockout facing upwards as rain could enter the enclosure and damage the sensor.
• In order to prevent heat transmitted through the wall from affecting the sensor reading, it may be necessary to install and insulating
barrier behind the enclosure.
• The sensor should be mounted on a northern wall of the building. It should not be exposed to heat sources such as ventilation or
window openings. Caution temperatures that are not high enough to meet the demand.
: If sunlight strikes the sensor enclosure or the surface area surrounding it, the system will provide water
• It should be installed at an elevation above the ground that will prevent accidental damage or tampering.
WIRING AND TESTING THE SENSOR
• Connect 18 AWG or similar wire to the two terminals provided in the enclosure and
run the wires from the sensor to the control. Do not run the wires close to and parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com Sen terminal on the control and not to earth ground.
• Follow the sensor testing instruction that follows and connect the wires to the control.
• Replace the front cover of the sensor enclosure.
UNIVERSAL SENSORS
MOUNTING THE SENSOR SF P/N 339071
Note: These sensors are designed to mount in an immersion well or on a pipe.
For example - If a Sensor is mounted onto a 1” type L copper pipe, there is approximately an 8 second delay between a sudden change in water temperature and the time the sensor measures the change. This delay increases considerably when steel pipe is used.
It is strongly recommended that an immersion well be used, especially when steel pipe of greater than 1-1/4” is used and also when large diameter pipes are used and fluid stratification is probable.
Sensor Mounted In Immersion Well SF P/N 410569
5 SC-3 Controller
The Universal Sensor can be strapped directly to the pipe using the cable tie provided. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement. The flat
ortion of the sensor should be mounted
p against the pipe.
The Universal Sensor should be placed downstream of a pump or after an elbow or similar fitting. This is especially impor­tant if large diameter pipes are used as the thermal stratification within the pipe can result in erroneous sensor readings. Proper sensor location requires that the
luid is thoroughly mixed within the pipe
f before it reaches the sensor.
WIRING AND TESTING THE SENSOR
WARNING: Do not run sensor wires close to and parallel to telephone or power cables. If the sensor wires are located in an area with
strong sources of electromagnetic interference, shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com Sen terminal on the control and not to earth ground.
• It is necessary to connect 18 AWG wire to the two sensor wires. Wire nuts can be used to hold the wires together.
• Follow the sensor testing instructions that follow and then connect the wires to the control.
SENSOR TESTING INSTRUCTIONS
A good quality test meter capable of measuring up to 5,000 kΩ (1 k = 1000 ) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor must not be connected to the control while the test is performed. Using the chart below, estimate the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
˚F ˚C ˚F ˚C ˚F ˚C ˚F ˚C
-50 -46 490,813 20 -7 46,218 90 32 7,334 160 71 1,689
-45 -43 405,710 25 -4 39,913 95 35 6,532 165 74 1,538
-40 -40 336,606 30 -1 34,558 100 38 5,828 170 77 1,403
-35 -37 280,279 35 2 29,996 105 41 5,210 175 79 1,281
-30 -34 234,196 40 4 26,099 110 43 4,665 180 82 1,172
-25 -32 196,358 45 7 22,763 115 46 4,184 185 85 1,073
-20 -29 165,180 50 10 19,900 120 49 3,760 190 88 983
-15 -26 139,402 55 13 17,436 125 52 3,383 195 91 903
-10 -23 118,018 60 16 15,311 130 54 3,050 200 93 829
-5 -21 100,221 65 18 13,474 135 57 2,754 205 96 763 0 -18 85,362 70 21 11,883 140 60 2,490 210 99 703 5 -15 72,918 75 24 10,501 145 63 2,255 215 102 648
10 -12 62,465 80 27 9,299 150 66 2,045 220 104 598 15 -9 53,658 85 29 8,250 155 68 1,857 225 107 553
SC-3 Controller 6
7 SC-3 Controller
WIRING THE SYSTEM
Use one of the following wiring diagrams to wire your system, along with the appropriate diagram on page 9.
1. Gas fired - Space Heating only
. Oil fired - Space Heating only
3
If using MM 750P-MT120 L.W.C.O. use Figure C6
on page 9 to wire the control
1. Gas fired - Space Heating only
NOTE: For boiler termination wiring at modules, see page 9
SC-3 Controller 8
2. Oil fired - Space Heating only
NOTE: For boiler termination wiring at modules, see page 9
9 SC-3 Controller
SC-3 Controller 10
DISPLAY:
Symbol Description
Stage
Displays which stage relays are turned on.
Pump
Displays when the primary pump relay is turned on.
˚F, ˚C, min, hr
Units of measurement.
Occupied Schedule
Displays when the control is in Occupied Mode.
UnOccupied Schedule
Displays when the control is in UnOccupied Mode.
Installer Access Level
Displays when the Installer/Advanced Dip switch is set to Installer
Pointer
Displays the control operation as indicated by the text.
Warning/Alarm
Displays when an error exists or the alarm relay is turned on.
Loading...
+ 18 hidden pages