Slant/Fin S-120, S-35, S-36, S-39, S-40 Installation And Operating Instructions Manual

...
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
®
This manual must be left with
wner and should be hung on or
o
SENTRY
adjacent to the boiler for reference.
HOT WATER MODELS S-34 THROUGH S-150
INSTALLATION AND OPERATING INSTRUCTIONS
CONTENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Controls and Wiring. . . . . . . . . . . . . . . . . . 6-9
Boiler Water Temperature Control. . . . . . . . . . . . . 10-11
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 12
Boiler Room Air Supply and Ventilation . . . . . . . . . . . 13
Water Piping at Boiler . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions:
Filling and Venting Water Systems. . . . . . . . . . . . . . . 13
Initial Start:
Safety Information and Lighting Instruction . . . . . . . . 14
Burner Adjustment, Checking Gas Input . . . . . . . 14-15
Care and Maintenance
General Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . 15
Water Level Check. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Annual Inspection and Cleaning . . . . . . . . . . . . . . . . 16
Safety Check for Control Systems . . . . . . . . . . . . . . . 16
Protection from Freezing/Water Treatment. . . . . . . . . 16
Keeping Area Clear . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Piping a Heating-Cooling System . . . . . . . . . . . . . . . . . . 18
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND
STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph enti­tled "LIQUEFIED PETROLEUM (L.P.) PROPANE GAS­FIRED BOILER LOCATION" on page 4 of this instruction book. The above warning does not apply to NATURAL gas-fired boilers.
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book
In addition, where required by the authority having jurisdic­tion, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1. If there is any conflict in the above requirements, then the more stringent requirement will apply.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed otherwise qualified, in compliance with the authority having jurisdiction.
.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 113 PUBLICATION S-41 rev.A Part No. 46-0602
Boiler Model Number
Boiler Serial Number
Installation Date
2
Sentry
Note: Height dimension increases by 1-3/4" when comustible floor kit is used.
* Vent damper may be installed horizontally on all models with use of a vent elbow. For more information, see figure 2, page 5.
Sentry
3
Boiler Model
S-34 28 S-60 3 11 S-90 4 14 S-120 5 17 S-150 6 20
S-60 thru S-150
Boiler Model
S-34
No. of
Sect.
A B C D E FG
1
8" 145⁄8"4 33" ——6
1
8" 175⁄8"4 37" 41⁄2" 26" 61⁄4" 250
1
8" 205⁄8"5 37" 51⁄2" 251⁄2"61⁄4" 310
1
8" 235⁄8"6 37" 71⁄2" 25" 61⁄4" 365
1
8" 265⁄8"7 37" 81⁄2" 241⁄2"81⁄4" 425
Gas
Type
Natural 47 48 48 49 49 49 50 50 51 51
Propane 56 56 56 57 57 57 58 59 59 60
Natural 50 51 51 51 51 52 52 52 53 53
Propane 57 58 59 59 60 60 61 62 63 63
Orifice
Size for
Sea
Level
Dimensions
(inches)
(max)
1
4" 190
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
2000 3000 4000 5000 6000
Approx.
Total Wt.
Full of
Water (lb.)
7000 8000 9000 10000
CHIMNEY RECOMMENDATIONS
HEIGHT:15 ft. (minimum) from draft hood skirt to top of chimney. INSIDE DIAMETER: Same as dimen­sion C (or larger). NOTE: Larger chimney may be required if two or more boilers or a boil­er and another appliance are vented to a single chimney. Slant/Fin supplies vent dampers by several manufacturers. Some are smaller than the indicated “G maxi­mum”.
Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority. See page 14 for burner input adjustment.
Base Assembly Sentry Boiler
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition.
This installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
Burners
NATURAL GAS-FIRED BOILER LOCATION
Pilot
Burner Access Door
Gas Valve
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct.
The location should also be such that the gas ignition system com­ponents are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.).
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boiler, page 2.
B. For installation on non-combustible floors only. The
Combustible Floor Kit part number printed on the boiler rating plate is the only one to be used when installing on combustible floors. The boiler must not be installed on carpeting.
C. If boiler is to be located over buried conduit containing electric
wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
4
WARNING
LIQUEFIED PETROLEUM (L.P.) PROPANE
GAS-FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION Liquefied Petroleum (L.P.) propane gas is heavier than air. Therefore, propane boilers, piping, valves should not be installed in locations where propane leaking from defective
quipment and piping will “pool” in a basement or other space
e below the leak. A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire.
rovide a level, solid foundation for the boiler. Location should
P be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE may be in effect in your geographic area
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or sim­ilar location where heavier-than-air-gas might collect. Appliances so fueled shall not be installed in an above­grade under-floor space or basement unless such loca­tion is provided with an approved means for removal of
unburned gas.” Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE for design criteria of the “approved” means for removal of unburned gas.
CHIMNEY REQUIREMENTS
A. Sentry boilers may be vented into a masonry vitreous tile-
lined chimney or type “B” venting system NOT EXPOSED to the OUTDOORS below the roof line. Venting and sizing of venting system must be in accordance with National Fuel Gas Code ANSI Z223.1, NFPA 54, -latest edition which will be referred to as the National Fuel Gas Code. Local codes apply. If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exterior chimney), ONE of the following options apply:
1. Chimney must be re-lined with a metallic liner. When this is done, the chimney will be considered NOT exposed to the outdoors and the requirements of the National Fuel Gas Code for NON-exposed chimneys and/or local codes will apply.
2. If an exposed tile-lined chimney is to be used WITHOUT a metallic liner, the boiler must first meet the require­ments of the National Fuel Gas Code.
B. If an existing boiler is removed from a common venting
system, the common venting system may be too large for proper venting of the remaining appliances connected to the common vent. Follow the test procedure shown in Appendix “A” of this manual to insure proper operation of venting system and appliances.
C. Inspect for proper and tight construction. Any restrictions or
obstructions must be removed. An existing chimney may require cleaning.
D. Chimney or vent must extend at least 3 feet above any
ridge within 10 feet of the chimney.
Sentry
INIMUM CLEARANCES FROM COMBUSTIBLE
M CONSTRUCTIONS
A. Minimum boiler clearances shall be as follows:
SENTRY SERIES
MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUC­TION. MINIMUM ALCOVE AND CLOSET CLEARANCE.
S-34 through
S-150 Front 6" Rear 6" Left Side 6" Right Side 12" Top (above boiler) 12" Flue Connector 6"
B. Provide accessibility clearance of 24” on sides requiring
servicing and 18” on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clearances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor wall or ceiling, the
learance at the opening through the finished floor, wall or ceiling boards
c
ay not be less than 1/2 inch. Each such opening shall be covered with
m a plate of non-combustible material.
SAFETY—
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
VENT PIPING—
A. Vent piping installation must be in accordance with ANSI
Z223.1-latest edition, National Fuel Gas Code, Venting of Equipment. Other local codes may also apply and must be followed.
B. Boiler vent pipe must be the full diameter of the boiler outlet.
See dimensions, page 2.
C. If more than one appliance vents into a common breeching,
the area of the breeching must be equal to the area of the largest vent plus 50% of the area of the additional vent areas. Vent connectors serving appliances vented by natur­al draft shall not be connected into any portion of mechani­cal draft systems operating under positive pressure. Horizontal breeching or vent pipe should be as high as pos­sible, consistent with codes, so that vertical vents from appli­ances will have a high rise above draft diverter openings. All horizontal runs must slope upwards not less than 1/4 inch per foot of run. Horizontal portions of the venting system must be supported to prevent sagging by securing each joint with metal screws and by providing hanger spaced no greater than 5 feet apart.
Sentry
D. Vent or breeching into chimney should not be inserted past
the inside wall of the chimney liner.
. All venting means should be inspected frequently. See Care
E
and Maintenance and separate User's Information Manual.
VENT DAMPER INSTALLATION
he vent damper referred to in the following instructions is
T the Slant/Fin Corporation vent damper.
This device is design certified by A.G.A. for use ONLY on spe-
ific Slant/Fin Corp. gas boiler models. These boilers must also
c be equipped with a plate which states that the boiler may be used with a Slant/Fin Corp. automatic vent damper device and indicates the proper vent damper model number.
A. INSTALLATION INSTRUCTIONS BEFORE YOU START TO
INSTALL
1. Read this installation manual, the "DANGER" plate attached to the top of the boiler, the "WARNING" on the wiring diagrams, vent damper carton and operator cover.
2. Perform pre-installation inspection as required by ANSI specification Z21.66. (See Vent Damper Instructions.)
3. Select a proper, convenient location for vent damper. Vent damper may be installed vertical or horizontal on all mod­els (see figures 1 and 2).
4. Carefully unpack the unit. DO NOT FORCE IT OPEN OR CLOSED. Forcing the damper may damage the gear train and void the warranty.
B. 1. This device must be installed after the boiler draft hood
(between the draft hood outlet and the connector to the out­door chimney or vent) as close to the draft hood as practi­cable, and without modification of the draft hood or the vent damper. (See figures 1, 2 and 3.)
2. The inlet size of the vent damper must be the same nomi­nal trade size as the outlet of the draft hood.
3. This device must be located in a venting system or section of a venting system so that it serves only the single appli­ance for which it is installed. (See figure 3.)
4. Clearances of not less than 6 inches (152MM) must be maintained from combustible materials, with provisions for service access.
C. AFTER INSTALLATION:
1. Operate system through two complete cycles to check for opening and closing in proper sequence, and proper burn­er operation. DAMPER MUST BE IN OPEN POSITION WHEN BOILER MAIN BURNERS ARE OPERATING.
2. Perform installation checks as required by ANSI specifica­tion Z21.66. (See Vent Damper Instructions.)
3. Check the troubleshooting section if problems arise with the installation.
5
Figure 1. Vertical Installation of Vent Damper on Sentry “S”
Boilers
Figure 2. Horizontal Installation of Vent Damper
WARNING—DANGER
Once you have begun vent damper installation procedure, DO NOT restore electric power and gas supply until installation and inspection have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness is plugged into vent damper operator. Failure to observe this warning may create a hazardous condition that could cause an explosion or carbon monoxide poisoning.
Figure 3.
6
Sentry
GAS PIPING—
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied petro­leum gases.
B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P. propane gas. See page 2 for location of union and manual main shutoff valve that may be specified locally. Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).
4. Use table A to select proper pipe size.
Example
: Boiler model S-150 is to be installed. Distance from gas meter to the boiler is 30 ft. Heating value of natur­al gas is 1020 Btu/cu. ft. Select proper pipe size.
Gas flow = 150,000 Btu/hour
= 147 cu. ft. per hour
1020 Btu/cu.ft.
At 30 ft. length of pipe, match required capacity from Table A (choose higher capacity, in this case is 152 cu. ft. per hour). Required pipe size is 3/4". Improper gas pipe sizing will result in pilot flame outages, insufficient heat and other installation difficulties. For more information and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested before
placing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and its individual shutoff valve must be disconnect­ed from the gas supply piping system during any pressure test­ing of that system at test pressures in excess of 1/2 PSIG. This boiler must be isolated from the gas supply piping sys­tem by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be pro­vided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
ELECTRICAL CONTROLS AND WIRING—
A. The electrical power to the boiler must be on a separately
fused and live circuit.
B. The boiler, when installed, must be electrically grounded in
accordance with the requirements of the authority having jurisdiction or, in absence of such requirements, with the National Electrical Code, ANSI/NFPA No. 70-latest edition.
C. See figure 5a and 5b for wiring diagram on pages 8 and 9.
Length
f Pipe
o in Feet
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670
0 50 105 195 400 610
6
0 46 96 180 370 560
7 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
At pressure drop of 0.3 in. water, specific gravity = 0.60.
Gas Flow In Piping -- cu. ft. per hr.
ron Pipe Size (IPS)—inches
I
1/2 3/4 1 1-1/4 1-1/2
ELECTRICAL WIRING
DANGER: Before wiring, always turn off electric power supply, otherwise, shock or death can result.
1. Power Supply
A separately fused circuit is recommended. Use a standard 15 amp. fuse or breaker and 14 gage conductors in BX cable or conduit. Provide disconnect means and overload protection as required. See boiler wiring diagram (Figure 4). Boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction, or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
2. Power Connection
Connect hot and neutral to L1 and L2 terminal of the boiler control (See figure 4). Connect ground wire to ground screw inside boiler control.
3. Thermostat Connections
Thermostat wire connections must be to T and TV screw terminals of boiler temperature control (See figure 4). Thermostat Heat Anticipator Adjustments If the 24V room thermostat that controls this boiler has an adjustable heat anticipator, connect entire system to thermostat and run the system while measuring the current drawn through the thermostat wires. Set the heat anticipator at the value measured. The set current should match power requirements by zone valves and relays. Add an additional 0.1 Amp to the measured current for vent dampers. Refer to the manufacturer’s instructions of zone valve, vent damper and relays. Also, see instructions with the thermostat.
4. Multi Zoning
For pump zoning system, see figure 5 and 6 for zone valve system, see figure 7. DO NOT use control transformer to power external accessories like zone valve and relay, over load and/or burned-out transformer and boiler malfunction can result.
5. Indirect External Water Heater
If the system includes indirect water heater, the indirect signal must be sepatayed from heating zone(s) system. See figure 6 and follow steps below: a. Connect end switch of the indirect water heater relay to I1
and I2 of the boiler temperature control.
b. Connect end switch of the heating zones(s) relays to T and
TV of the boiler temperature control.
c. Power DHW and heating zone(s) circulators through end
switch relays as shown on figure 6. Do not connect heating zone(s) circulators to C1 and C2 of the control.
Loading...
+ 14 hidden pages