Slant/Fin Oil Hot Water User Manual

®
HOT WATER/OIL
APPLICATION GUIDE
WET-BASED CAST-IRON MODULAR BOILERS
Guidelines for the design, purchase and installation of Slant/Fin Caravan oil-fired and dual fuel hot water modular boiler systems.
CONTENTS
Ratings and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
ecommended piping and water flow . . . . . . . . . . . . . . . . .3-6
R
Optional factory supply and return headers . . . . . . . . . . . . . .7
Boiler room design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Boiler room air supply requirements . . . . . . . . . . . . . . . . . . . .8
Typical layouts for oil-fired systems . . . . . . . . . . . . . . . . . . . . .9
Venting a oil-fired system . . . . . . . . . . . . . . . . . . . . . . . . .10,11
Fuel oil storage facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Fuel oil delivery systems for single fuel burners . . . . . . .12-14
CODES AND STANDARDS
Oil-fired Caravan installations must comply to local codes or, in the absence of local codes, to the ANSI/NFPA 31, Installation of Oil Burning Equipment, latest edition.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Codes for controls and safety devices for automatically fired boilers, No. CSD-1. The installation must also conform to the additional requirements of Slant/Fin Instruction Book publication no. L-40 latest edition.
All electrical wiring is to be done in accordance with the National Electrical Code ANSI/NFPA No. 70-latest edition and all local electrical codes. The unit must be electrically grounded if an external power source is used.
In Canada, the installation must be in accordance with standards CGA B149.1 and B149.2, installation codes for oil burning appliances and equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code Part 1 and/or local codes.
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-16
Field wiring at modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
C-3 system wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
S
SC-3 ladder wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
SC-9 space heating wiring . . . . . . . . . . . . . . . . . . . . . . . . . .20
C-9 space heating ladder wiring . . . . . . . . . . . . . . . . . . . . .21
S
SC-9 space and domestic hot water wiring . . . . . . . . . . . . .22
SC-9 space and domestic hot water ladder wiring . . . . . . . .23
Caravan warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Request for Caravan rating plate . . . . . . . . . . . . . . . . . . .25-28
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can cause scaling and leave deposits in the boiler and the surrounding pipes. This will lead to inefficient boiler operation and breakdown. Fresh water will enter the system as a result of hidden leaks such as may occur in underground piping. Relief valves should be piped to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat exchangers. Any process application that results in introduction of fresh water into a boiler can cause scaling with deposits forming in the boiler and surrounding piping. This will damage the boiler. Introduction of fresh water from leaks will cause similar damage. Use of fresh water will void warranty.
In some areas it may be necessary to use a feed water treatment to control the corrosive makeup of the feed water. Check with the local authority, to determine if the feed water will need a conditioning treatment before being supplied to the boiler.
LOCAL CODE APPROVALS
New York City:
New York City Bar No. 51-58
Pennsylvania:
174-BT-S
Publication No. CG-10-HWO
Printed in the U.S.A. 1212
www.slantfin.com
INTRODUCTION
This Caravan application manual is intended to simplify the selection and application of Slant/Fin modular systems for a variety of space heating and domestic hot water requirements. Where any additional information is required, contract your local wholesaler, Slant/Fin
C. Faster, easier installation - modules are completely factory
assembled, including individual jackets to save on-site labor. Optional easy to install supply and return headers with flexible quick connect fittings are available for hot water systems.
sales representative, or the Slant/Fin factory.
D. Safety - each module contains an individual high limit control
A. Design flexibility - Caravan modular boiler systems are
vailable in virtually any size capacity simply by adding modules.
a
B. Boiler room design, size and flexibility - since Caravan
modules have the burner and controls mounted to the front, they
and a flame safeguard control. ASME relief valve is provided
eparately for mounting directly on boiler.
s
E. Fast domestic hot water recovery - Caravan offers an external
heat exchanger of the positive circulating type. can be installed with minimum clearances as per codes, thus saving a significant amount of floor space.
Table 1: Oil Caravan ratings hot water models - LDWO Series (100 psi maximum working pressure)
odel No.
M
LDWO-600-2-5 LDWO-750-2-6 LDWO-850-2-7 LDWO-900-3-5 LDWO-1100-3-6 LDWO-1300-3-7 LDWO-1700-4-7 LDWO-2100-5-7 LDWO-2500-6-7 LDWO-2900-7-7 LDWO-3400-8-7
* Light oil, 140,000 Btuh per gallon. † Net ratings are based on a piping and pick-up allowance of 1.15. Slant/Fin should
be consulted before selecting a boiler for installation having unusual piping and pick-up requirements.
No. of
eating
H
odules
M
2 2 2 3 3 3 4 5 6 7 8
Firing
ate
R
#2 Oil
GPH*
4.30
5.20
6.00
6.40
7.80
9.00
12.00
15.00
18.00
21.00
24.00
Ratings (MBH)
nput
I
602 728 840
896 1092 1260 1680 2100 2520 2940 3360
Gross
Output
500 596 711 750
903 1066 1421 1777 2132 2487 2843
‡ EDR
W
Sq. Ft.)
(
2900 3487 4120 4347 5233 6180
8240 10300 12360 14420 16480
ater
AHRI
et
N Ratings (MBH)†
435 523 618 652 785
927 1236 1545 1854 2163 2472
‡ Based on 150 Btuh per square foot E.D.R. at 170°F average water temperature.
§ Modules in excess of 8 are piped in parallel to first eight.
For larger sizes, use multiples of the above.
oiler
B
Horsepower
14.9
17.8
21.2
22.4
26.9
31.8
42.4
53.0
63.7
74.3
84.9
Water
ontent
C
gal.)
(
31.0
35.6
45.2
46.5
53.4
67.8
90.4
113.0
135.6
158.2
180.8
hip
S
Wt.
1570 1790 2000 2355 2685 3000 4000 5000 6000 7000 8000
Recommen
ed
d
Header
Size§
2" 2" 3" 3" 3" 3" 3" 3" 3" 4" 4"
Thermal
ff
E
%
82.7
82.7
84.6
82.7
82.7
84.6
84.6
84.6
84.6
84.6
84.6
2
odel No.
M
DWO-600-2-5 21
L
A B
5
8 87⁄3
LDWO-750-2-6 25 9
29
C
2
8
34
D
3
8 4
*
L
'4"
32 8 373⁄4 4'4" LDWO-850-2-7 283⁄8 1119⁄32 9 411⁄8 4'4" LDWO-900-3-5 215⁄8 87⁄32 8 343⁄8 6'7" LDWO-1100-3-6 25 9
29
32 8 373⁄4 6'7" LDWO-1300-3-7 283⁄8 1119⁄32 9 411⁄8 6'7" LDWO-1700-4-7 283⁄8 1119⁄32 9 411⁄8 8'10" LDWO-2100-5-7 28 LDWO-2500-6-7 28 LDWO-2900-7-7 283⁄8 1119⁄32 9 411⁄8 15'7" LDWO-3400-8-7 28
Note: Standard boiler unit prefix is LDWO.
3
8 1119⁄32 9 411⁄8 11'1"
3
8 1119⁄32 9 411⁄8 13'4"
3
8 1119⁄32 9 411⁄8 17'10"
Figure 1. Oil Caravan dimensions and typical piping/hot water models
* 27" spacing between modules.
Design Data
Max. ASME Working Pressure: 100 psi
Power Requirements: 120 V/60 HZ,
Amp (s) per module: For Carlin burners 6.0
RECOMMENDED PIPING AND WATER FLOW
Good system design addresses flow rates through boilers. It is possible to have too little flow and too much flow. Most boiler system designs are based on a 20˚F to 30˚F temperature rise in the boiler when it is firing at full input.
When the flow rate is too high through a module the water flow tends to short circuit from the return tapping to the supply tapping of a module. When flow rate is too high the boiler efficiency may drop and there is excess electrical consumption by the circulator.
Recommended water flows and resultant pressure drops through Caravan modules are as follows. Flow rate is for 20 rise in water temperature and pressure drop is determined at recommended flow rate and includes 1-1/2” pipe that connects module to Slant/Fin header. 7-section modules are used in LDWO-850, LDWO-1300,
Module
Flow Rate/
Module GPM
7-section 34 0.30
6-section 30 0.30
5-section 25 0.30
LDWO-1700, LDWO-2100, LDWO-2500, LDWO-2900 and LDWO-3400.
6-section modules are used in LWO-750 and LWO-1100.
5-section modules are used in LWO-600 and LWO-900.
Operating Pressures
System static pressure should be at least 15 PSI cold in modules. When circulators are operating the pressure in the modules should be at least 15 PSI when the water is cold.
Optional Piping Method - Primary/Secondary
When applying oil-fired Caravan boilers to a low temperature water system care should be taken to maintain 130˚F return water temperature inside the Caravan boiler. One way to accomplish this is to design the boiler using primary/secondary piping.
Slant/Fin recommends a minimum of 15˚F system water temperature rise across modules that are firing. If the desired temperature rise is lower than a primary/secondary arrangement should be used, either for the whole modular boiler or using a
Pressure
Drop/Module PSI
multiple boiler system as described below. The 15˚F minimum temperature rise can be maintained in the modules without affecting the system water.
1. Primary/secondary piping may be applied to a Caravan modular boiler system as demonstrated on Figure 4. In this type of application the modular boiler is contained within the primary loop. However, this is still a modular boiler, if it has no valves between the modules.
2. Primary/secondary piping may also be used on each individual “module”, please see figure 5. In this arrangement the Caravan is no longer a “modular” boiler, it is now a “multiple” boiler system. In a multiple boiler system each module is actually a standalone boiler and each boiler should be equipped with a manual reset hi limit and low water cutoff. Certain local codes also require a minimum distance between each boiler.
Please remember to always follow code requirements applicable to the building that the boilers are being installed in.
Most Caravan systems are applied as a modular boiler, not as a multiple boiler. A modular boiler system is efficient, easy to main­tain and very dependable. When a multiple boiler is used there are additional circulators, manual reset hi limits and low water cut-offs to install and maintain.
Some people believe a multiple boiler system is more efficient because water flows through only those units that are firing. They may think water flowing through modules not firing leads to energy loss in those modules. However, we must remember a boiler heat exchanger is designed to absorb heat from high temperature com­bustion and transfer it to low temperature water (certainly below 250˚F water). Boilers do not make good “convectors” and very little heat is passed through the venting of a module not firing. Oil-fired modules experience very low airflow through the heat exchanger when not firing.
In most applications we recommend a step or stage controller, that modulates system water temperature, be used on a Caravan system. These controls ensure the number of modules firing equals the actual demand for heat. Slant/Fin’s step controllers are the SC-3 and SC-9 model controls. Please see the Control section of this manual for more information on these controls.
3
Figure 2. Typical space heat piping – For primary circulation only.
Figure 3. Typical space heat and domestic piping – For primary circulation only.
4
Figure 4. Primary/Secondary piping of modular boiler.
Figure 5. Primary/Secondary piping of multiple boiler.
5
ECOMMENDED SYSTEM PIPING AND WATER FLOW
R
Minimum flow rate formula:
Minimum flow rate through modules =
Gross output (MBH)
20,000
Figure 6. Recommended boiler piping for variable volume zone circulation
Note: A water flow proving device
is recommended on all Caravan systems.
Figure 7. Supply and return piping locations for space heat with domestic hot water
SUGGESTED DOMESTIC HOT WATER PIPING
Figure 8: Instantaneous tankless coil—
two temperature with recirculation
Figure 9: Storage tank from tankless coil with recircula-
tion locations for space heat with domestic hot water
6
EQUIPMENT INCLUDED
3
'' RETURN HEADER WITH 1
1
/2'' STUBS
(3 MODULE)
* 3'' BUILDING
PIPING
(
BY OTHERS)
1
1
/2'' X 34'' SQUARE NIPPLE
1
1
/2'' X 30'' NIPPLE
CAST END CAP
WITH
3
/4'' TAPP ING.
SUPPLY OR RETURN.
FOR USE WITH LWCO.
3
'' SUPPLY HEADER WITH 1
1
/2'' STUBS
(3 MODULE)
1
1
/2'' X 4'' NIPPLE
3'' PIPE X 20'' (BY OTHERS)
1
1
/2'
' UNION
1
1
/2'' X 11/2'' X 11/2'' TE E
1
1
/2'
' X
3
/4'
' BUSHING
3
/4'' DRAIN VALVE
1
1
/2'' X CLOSE NIPPLE
1
1
/2'' ELBOW
3'' SUPPLY HEADER
W
ITH 1
1
/2'
' STUBS
(
2 MODULE)
*3
'' BUILDIING PIPE
CONNECTION
1
/2'
' PRESSURE
TEMPERATURE
GAUGE
1
/2'' WEL LS
3'' FLEX JOINT
(SEE DETAIL "A")
1
1
/2'' ELBOW
1
1
/2'' X 15'' NIPPLE
C
AST END CAP
3
'' RETURN HEADER WITH 1
1
/2'' STUBS
(2 MODULE)
3'' FLEX JOINTS
(
SEE DETAIL "A")
1
1
/2'' X 8'' SQUARE NIPPLE
1
1
/2'' FLEX JOINT
(
SEE DETAIL "A")
1
1
/2'
' X 4'' NIPPLE
CONTROL HEADER
3'' x
1
/2'' x 1/2'' x 1/2''
LDWO SERIES –– Hot Water Models
• Pre-assembled heat exchangers with built-in air separators
• Insulated baked enamel jacket.
• Flue collector.
• Draft regulator.
• Flame retention oil burner with nozzle and CAD cell.
• Primary burner control.
• Temperature limit.
• Flue brush.
• Module temperature and pressure gauge.
• System pressure and temperature gauge. (unmounted-1 per system).
• Pressure relief valve (unmounted-1 per module).
• Control header (unmounted-1 per system, up to 8 modules).
OPTIONAL EQUIPMENT
• Headers.
• Control System.
Pressure/Temp Rating for flex joint fittings
150 psi 275˚ F
*Building piping must be rigidly secured so it cannot
move where connected to headers.
NOTE: Shown reverse return (Preferred). For direct return, header assembly piping connections may be made at the same end of the boiler bank, not as shown.
Some governing agencies do not allow compression type couplings. Consult your local code requirements.
Figure 10. Oil Caravan—optional header assembly for all models LDWO and LWDF hot water Caravan systems.
7
BOILER ROOM DESIGN
Caravan modular boiler systems allow better utilization of floor space and permit future expansion with minimum cost. Caravan modules are hand truckable, fit through doorways and often may be installed around an existing inoperative boiler. They can be grouped in heating module batteries of single, multiple or angular rows. Oil-fired boiler systems consisting of 9 or more modules should be piped in parallel in two or more batteries. Illustrated below are typical boiler room layouts and dimensional data on the
ize requirements of oil-fired hot water boilers.
s
Figure 11. Correct location of combustion-air supply ducts
BOILER ROOM AIR SUPPLY
To ensure safe, efficient operation, the modular boiler system must be supplied with sufficient air to support complete combustion, replacing air entering draft dampers or draft hoods and ventilating the boiler room or areas. For additional information, not listed below, see ANSI,Z223.1, section 5.3.3.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
WO UNOBSTRUCTED OPENINGS FOR PASSAGE OF
T AIR INTO THE BOILER ROOM:
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor (below burner air inlet) and one louvered opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of 1 square inch per 4000 BTUH system input.
2. Air drawn horizontally from outdoors through HORIZONTAL DUCTS; one opening near the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of 1 square inch per 2000 BTUH of total system input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000 BTUH of total system input.
4. Air drawn from inside the building; one opening near the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of 1 square inch per 1000 BTUH of total system input.
of total
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
UNLESS PROPERLY CONTROLLED, AVOID THE USE OF FORCED VENTILATION, SINCE IT CAN CREATE AN UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN BOILER ROOM AND AIR SOURCE.
8
Figure 12. Typical layouts for oil-fired systems
* Caravan can be installed as close as 1" from the wall, local codes
permitting. However, 24" is recommended for service inspection access.
See Figure 1 dimensions A and D.
9
Loading...
+ 19 hidden pages