Slant/Fin LYNX LX-85 Installation And Operating Instructions Manual

Page 1
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
LYNX
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODEL LX-85
GAS-FIRED BOILER FOR NATURAL AND L.P. PROPANE GASES
INSTALLATION AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes........................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Additional Installation Requirements for Massachusetts............5
Contamination Prevention...........................................................5
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation......................................5
Flue gas Venting Requirements..................................................6
Vent Material ..............................................................................6
Air Intake Material ......................................................................6
Vent and Air Intake Restrictions .................................................7
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance ..................................8
Non-Direct Vent Vertical Venting.................................................8
Direct Vent Installation................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.....................................14
Direct Vent, Venting and Air Intake through a Roof ..................15
Venting and Air Intake Regular Inspection ...............................16
Condensate Removal System..................................................16
Gas Piping ................................................................................16
Electrical Wiring ........................................................................17
Wiring Diagram.........................................................................18
Multi Zoning ..............................................................................20
Water Piping .............................................................................23
Operating Instructions...............................................................29
Boiler Control Display...............................................................29
Boiler Control............................................................................29
Sequence of Operation.............................................................35
Gas Input Rate Adjustment ......................................................36
Safety Check ...........................................................................38
Care and Maintenance .............................................................41
General Troubleshooting Guide ................................................42
Conversion to Propane.............................................................43
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
INSTALLATION INSTRUCTIONS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
IMPORTANT
BEFORE READING THE
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
WARNING
The venting system of this boiler is under positive pres­sure. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addi­tion to the recommendations within this manual and the User’s Information Manua flue collector to the outdoor discharge, must be carefully checked annually by a qualified service agency.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 1008 Part No. 84-5736 Publication No. LX-40 Rev. C
l, the venting system, from the
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
Page 2
2
Lynx Model LX-85
RATINGS AND DIMENSIONS
WATER INLET (RETURN) - 1" NPT (MALE)
WATER OUTLET (SUPPLY) - 1" NPT (MALE)
5 3/8
2 1/2
23
17 3/4
REAR VIEW
Figure 1. Dimensions data
2 5/8
36 3/4
6 7/8
1 1/2
3 3/8
27 7/8
16 1/4 7
23 3/4
SIDE VIEW
VENT CONNECTION
AIR INTAKE CONNECTION
12 3/8
33 7/8
GAS SHUTOFF VALVE 1/2" NPT (FEMALE)
4 3/4
8 5/8
41
23 5/8
FRONT VIEW
SPECIFICATIONS FOR LX-85 BOILER
Fuel Rate Input: 85,000 BTUH maximum
25,000 BTUH minimum
Boiler Water Volume: .75 gallon (6.25 lbs)
Water Piping Connections: 1" NPT (male)
Gas Piping Connection: 1/2" NPT (female)
Vent Connection: 3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Air Intake Connection: 3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Weight of Boiler (uncrated): 105 lbs.
Gas orifice size: Natural Gas - No orifice used *
Propane - 0.190" diameter **, ID Code: C
*Note: No orifice changes are required for high altitude installations. **See page 43 for conversion procedure to propane.
Figure 2. Lynx Boiler
Page 3
Lynx Model LX-85
FIELD WIRING ENTRANCES
FIELD WIRING TERMINALS
LOCATION AND IDENTIFICATION OF PARTS
SPARK ELECTRODE (IGNITOR)
WINDOW (SIGHT GLASS)
GAS VALVE
FLUE SENSOR
WATER OUTLET (SUPPLY)
3
AIR INTAKE CONNECTION
GAS SUPPLY VALVE
TEMPERATURE DISPLAY
MODE DISPLAY
POWER SWITCH
PRESSURE GAUGE
TOP (EXTERIOR)
VENT CONNECTION
VENTURI
HEAT EXCHANGER
FLUE COLLECTOR
WATER INLET (RETURN)
COMBUSTION BLOWER
BOILER DRAIN VALVE
FRONT (INTERIOR)
FLUE SAMPLE PORT
BOILER CONTROL
SEDIMENT TRAP
WATER
COMBUSTION BLOWER
HEAT EXCHANGER ENCLOSURE FRONT COVER
CONDENSATE TRAP
RIGHT SIDE (INTERIOR)
SUPPLY SENSOR
WATER HIGH LIMIT
WATER RETURN SENSOR
CONDENSATE DRAIN TEE
Figure 3. Location and identification of par ts
Page 4
4
Lynx Model LX-85
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
This installation must also conform to the additional require­ments in this Slant/Fin Instruction Book.
NATURAL GAS-FIRED BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See Appen­dix A for vent terminal location restrictions.) The location should also be such that all boiler components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
WARNING LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION Liquefied Petroleum (L.P.) propane gas is heavier than air. Therefore, propane boilers, piping, valves should NOT be installed in locations where propane leaking from defective equipment and piping will "pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire. Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE ma y be in effect in your geographic area.
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air-gas might collect. Appliances so fueled shall not be installed in an above­grade under-floor space or basement unless such loca­tion is provided with an approved means for removal of
unburned gas." Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE for design criteria of the "approved" means for removal of unburned gas.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler
shall be as follows: MINIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended Surface Front 6" 18" Rear 0" 0" Left Side 0" 5" Right Side 0" 5" Top 5" 18" Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling,
the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
Construction for Service
1"*
5"
6"
BOILER FOUNDATION
A. Provide a solid, level foundation capable of supporting
the weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers, page 2.
B. Boiler can be installed on both combustible and
non-combustible floors, but must NOT be installed on or above carpeting.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
* 2" FOR ENCLOSED
Figure 4. Lynx boiler min. clearances for combustible construction.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Page 5
Lynx Model LX-85
5
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contamination sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause corrosion or other damage to the heat exchanger and components of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
AREAS LIKELY TO HAVE CONTAMINANTS
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
VENTING APPLICATION
The Lynx LX-85 is a sealed combustion type boiler, it may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from outside or as a non-direct vent boiler which air for combustion is taken from inside the boiler room.
The Lynx LX-85 boiler must be vented by 3" diameter PVC/CPVC sched­ule 40 pipe, or the proper 3” diameter stainless steel venting system (see “vent material” on page 6) through the roof or sidewall. An optional adapter is available for connecting stainless steel venting to the boiler vent outlet. See the Lynx LX-85 Parts List, publication # LX-10PL.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventilation. When buildings are insulated, caulked and weather-stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes. The following recommendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWOUNOBSTRUCT­ED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER
ROOM.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
When the Lynx-85 is installed and used in the Commonwealth of Massa­chusetts, the following additional code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each addi­tional level of the dwelling, building or structure served by the side wall hor­izontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adja­cent floor level.
b. In th event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizon­tally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTR UCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or part for residential purposes.
requirements pursuant to Massachusetts
Page 6
6
Lynx Model LX-85
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor and
one louvered opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a min­imum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. Openings for passage of air into the boiler room for direct-vent installation must be at least
1
2 of the openings required for the non-direct vent as mentioned above.
If additional non-direct vent appliances are installed in the same space and adequate air openings are provided for them, there are no additional air openings required for the Lynx LX-85.
For both direct and non-direct installation, the following must be considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be
used in or near the boiler area.
- Boiler area must never be under negative pressure. The
flow of combustion and ventilating air to the boiler must not be obstructed.
VENT AND AIR INTAKE MATERIALS
The vent piping for direct or non-direct vent installation must be 3” diameter PVC/CPVC schedule 40 pipe, or UL listed single wall 3” diameter AL29-4C* stainless steel material. The air intake piping for direct vent installation must be 3" diameter PVC/CPVC schedule 40 pipe. The following manufacturers’ systems are approved for use within a specified minimum and maximum equivalent vent length in this manual.
Manufacturer
Heat-Fab. Inc. Saf-T Vent Not Required
ProTech System, FasNSeal Not Required Inc.
Flex-L StaR-34 GE-IS806 International, Inc.
Z-Flex, Inc. Z-Vent GE, RTV 106
N/A PVC pipe, PVC primer
N/A CPVC pipe, CPVC primer
*AL29-4C is a registered Trademark of Allegheny Ludlum Corp
Type/System
EZ Seal
Schedule 40 and cement
Schedule 40 and cement
Sealant
When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing. Use sealant specified by vent system manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions provided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materials other than PVC/CPVC Schedule 40.
The vent and air intake connections on the boiler are designed to accommodate either PVC/CPVC Schedule 40 pipe or the listed stainless steel vent systems (by inserting the optional adapter specified in the Lynx LX-85 Parts List, publication # LX-10PL, for stainless steel venting). Built-in sealing rings are provided, so no additional sealant is required. The application of liquid soap to the outer end of the vent pipe (or adapter, if used) will aid in installing it. Make sure the pipes are round and burr-free, and push down into the appropriate step of the connector or adapter, until snug. (See Figure 5).
FLUE GAS VENTING REQUIREMENTS
The Lynx LX-85 series boiler is a high efficiency, mechanically forced draft boiler and, therefore, requires different venting arrangements than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply. The use of a vent damper is NOT permitted on this boiler series.
AIR INTAKE PIPE (PVC OR CPVC)
VENT PIPE (PVC OR CPVC)
CHECK EDGE FOR BURRS
FLUE AND AIR INTAKE CONNECTOR
Figure 5. Vent and Air Intake Pipe installation into Boiler vent and air intake connections.
Page 7
Lynx Model LX-85
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting, cleaning and connecting PVC and CPVC pipe, for both the vent and air intake piping system:
1. When laying out the piping system, work from the boiler
vent and air intake adapter to the point of outside termination.
2. Cut the PVC/CPVC pipe to the required lengths, and
pre-assemble the entire system, before sealing. Disassembly after sealing, to make any corrections, will not be possible.
3. Once the pre-assembled PVC/CPVC pipe vent and air
intake system is verified to be of the proper length pipe and fitting orientation, begin disassembling and preparing the pipes and fittings for the sealing process. This can be done section by section, or the complete vent and air intake system can be disassembled. It is recommended to mark the various parts, before complete disassembly, to eliminate the possibility of errors during re-assembly.
4. De-burr the inside and outside of every PVC/CPVC pipe, to
ensure that they engage fully into the fittings, and flow is not compromised. A small chamfer on the outside of each pipe can particularly aid in the final assembly process.
5. Wipe or knock out any debris from inside the PVC or
CPVC pipe, which may have accumulated there from the cutting process or storage. Debris can cause operational problems with the boiler combustion components.
6. Thoroughly clean the outside ends of each pipe, and the
inside of each fitting. The surfaces must be dry for the sealing agents to work properly. Handle the prepared pipe lengths away from the cleaned ends, and handle the cleaned fittings, from the outside, to avoid contamination.
7. Re-assembly of the PVC or CPVC pipe should be done in
sections, to avoid the primer and cement drying before the parts are engaged.
8. For each joint, first apply a coat of primer to the outside
sealing surface of the pipe and the inside sealing surface of each fitting. Use only the primer type that is specified for either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A
second coat of cement can be applied, if necessary, but must be done quickly and in a manner that avoids unnecessary build-up that would cause obstruction inside the system. Use only the cement type that is specified for either the PVC or CPVC pipe that is being utilized.
10. Before the cement dries, insert the pipe into the fitting. A
slight twisting motion while pushing the pipe into the fitting will aid in distributing the cement evenly and ensuring the parts fully engage.
11. Quickly wipe the excess cement from the outside areas of
the joint. Discard any rags used to avoid later getting the cement on hands, clothes and equipment.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100 equivalent feet.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows as shown in the table on this page.
7
Figure 6.
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow that is required.
5. Vent length restriction is for both direct and non-direct vent installations.
EXAMPLE: Boiler model LX-85 is to be installed. The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows.
In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100’ - (4’ x 5’) = 80’. Since the air intake pipe also is PVC and requires the use of 4 elbows, the maximum straight pipe air intake length that can be utilized is also 80 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 80 feet.
Equivalent Length of Various 90-Degree Elbows
Manufacturer
Heat-Fab, Inc. Saf-T Standard 3
Heat-Fab, Inc. Saf-T, tight radius elbow 6 ProTech System, Inc. FasNseal 6
Flex-L International, Inc. StaR-34 6 Z-Flex, Inc. Z-Vent 6
N/A PVC, Schedule 40 5 N/A CPVC, Schedule 40 5
Type/System
elbow
Equivalent
Length (Feet)
Page 8
8
Lynx Model LX-85
6. The LX-85 boiler is equipped with a built-in condensation drain and trap. The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensa­tion drain and trap is required on the vent piping system itself.
7. The horizontal vent pipe must be sloped upward from the boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8. The horizontal vent and air intake pipes must be supported
with pipe straps, at intervals no greater than 5 feet, when PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible
constructions must be maintained (see Page 4). No clearance is required between the vent and air intake pipes of this boiler.
10. Common venting with other appliances or another Lynx
boiler is not allowed.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window or gravity air inlet into any building. The bottom of the vent terminal or air intake terminal shall be at least 12 inches above grade or the normal snow level whichever is greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip­ment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. Vent termination must not be located in any confined space (i.e. window wells, alcoves, narrow alleys) or under any overhang or deck. Vent termination should not allow flue gas discharge towards neighbor’s windows or where personal injury or property damages can occur.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 9 shows typical venting through the roof. The vent pipe must pass through the ceiling, floor and the roof vertically through a 6" minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage, an appropriate UL listed roof flashing must be used.
11. DO NOT install a vent damper or similar devices in vent system or on the boiler.
12. DO NOT insulate venting system.
VENTING INSTALLATION
Only the approved PVC/CPVC and stainless steel materials listed on page 6 may be used for the venting system installa­tion. If stainless steel vent systems are used, follow the manu­facturer’s instructions, in conjunction with these instructions.
I. NON-DIRECT VENT INSTALLATION
The air for combustion is taken from the ambient air surrounding the boiler; therefore, ample supply of air is required for combustion and ventilation (see page 6.)
DO NOT use this installation method if the surrounding of the boiler is contaminated. See page 5 for the list of harmful contaminants and their sources, to avoid.
A. NON-DIRECT VENT SIDEWALL VENTING
Figures 7 and 8 show typical horizontal sidewall venting. For combustible wall passage of vent piping, a UL listed thimble or flashing and sealing boot must be used, providing the wall thickness from 3" minimum up to 12" maximum. The vent piping must terminate with a screened tee or elbow termination facing down.
CAUTION: Flue gasses exiting from the vent terminal will condense. Building materials in the area of the vent terminal should be protected from discoloration and degradation.
An existing chimney (see Figure 10) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe with in the chimney.
The vertical vent piping must terminate with a screened tee, combination of 45˚ elbow and a 90˚ screened elbow termina­tion or a rain cap termination.
II. DIRECT VENT INSTALLATION
Air intake piping from outside to the boiler air intake connector provides the air for combustion. The boiler surrounding may be contaminated (See page 5). Piping the air intake to the outside can prevent contaminants from the boiler surrounding from entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 11 and 12 show typical sidewall direct venting, using a Slant/Fin vent/air intake termination. There are 2 different mod­els of vent/air intake termination available. One is designed specifically for PVC/CPVC venting, and the other is designed specifically for stainless steel venting systems. Only these 2 models of vent/air intake termination are approved for this method of installation. Refer to the Slant/Fin Lynx LX-85 Parts List (publication number LX-10PL) for the appropriate model for the vent material to be used.
CAUTION: Flue gasses existing from the vent terminal will con­dense. Building materials in the area of the terminal should be protected from discoloration and degradation, in addition to the requirements of the vent termination location and clearances stated in this manual.
Page 9
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
9
AL29-4C S.S.*. venting materials (See page 6).
90˚ ELBOW
AIR INTAKE (DO NOT BL0CK)
SLOPE UP 1/4 IN. PER FOOT MIN.
FROM BOILER TO VENT TERMINATION
3 IN. DIA. PVC/CVPC PIPE FOR VENT
6" MIN. 9" MAX.
TERMINATION 90˚ ELBOW WITH SCREEN
A U/L LISTED FLASHING AND SEALING BOOT MUST BE USED ON COMBUS TIBLE WALLS.
OUTSIDE WALL
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe f or venting.
6" MIN. 9" MAX.
OUTSIDE VENT TERMINATION ELBOW WITH SCREEN
A U/L LISTED WALL THIMBLE MUST BE USED ON COMBUSTIBLE WALLS. S/F P/N 440695 (ADJUSTABLE 5 IN. TO 8 IN.) MAY BE USED. ABOVE THIMBLE MUST BE USED WITH HEAT-FAB SLIP JOINT CONNECTOR
STANDARD 90
?
ELBOW
AIR INTAKE (DO NOT BL0CK)
SLOPE UP 1/4 IN. PER FOOT MIN.
FROM BOILER TO VENT TERMINATION
3 INCH. DIA. STAINLESS STEEL VENTING MATERIAL FOR VENT
ADAPTOR
SNOW LINE
(SEE DEFINITION)
12" MIN
12" MIN
S/F P/N 440695 (ADJUSTABLE
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
OUTSIDE WALL
SNOW LINE
(SEE DEFINITION)
Page 10
10
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
90° TERMINATION
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
ELBOW WITH SCREEN
RAIN CAP TERMINATION MAY BE USED
*
FIRESTOP AND SUPPORT
90° ELBOW
AIR INTAKE (DO NOT BLOCK)
SLOPE UP 1/4 IN.
PER FOOT MIN.
10 FT MIN.
VENT TERMINATION TEE WITH SCREEN
1 FT MIN.
FLASHING AND STORM COLLAR
NIM "2
2" MIN
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
FIRESTOP AND SUPPORT
96044 N/P F/S
ELBATSUJDA( 5
Figure 9. Lynx model LX-85 - non-direct vent, venting through the roof
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
USE ADAPTOR IF STAINLESS STEEL IS USED
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERI AL FOR VENT
Page 11
Lynx Model LX-85
LYNX MODEL LX-85 NON - DIRECT VENT, UTILIZING AN EXISTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
*
CHIMNEY AS A CHASE
AL29-4C S.S.*. venting materials (See page 6).
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
RAIN CAP TERMINATION MAY BE USED
10 FT MIN.
CHIMNEY TOP PLATE
90° TERMINATION ELBOW WITH SCREEN
VENT TERMINATION TEE WITH SCREEN
1 FT MIN.
11
SLOPE UP 1/4 IN.
PER FOOT MIN.
90° ELBOW
AIR INTAKE (DO NOT BLOCK)
SEAL CHIMNEY OPENING
WITH MORTAR OR COVER PLATE
USE ADAPTOR IF STAINLESS STEEL IS USED
(
ELBATSUJ
596044 N/P F/S
DA
Figure 10. Lynx model LX-85 - non-direct vent, utilizing an existing chimney as a chase.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
3 INCH DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
3 INCH DIA. PVC/CPVC PIPE OR ST AINLESS STEEL VENTING MATERIAL FOR VENT
Page 12
12
Lynx Model LX-85
LYNX MODEL LX-85 - DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
3 - 16" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA PVC/CPVC PIPE FOR VENT
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 84 0802 000
12" MIN
AIR INTAKE LOUVERS
3" DIA PVC/CPVC COUPLING WTH SCREEN
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
Figure 11. Direct vent, sidewall venting illustration; utilizing PVC/CPVC pipe for venting
3 - 12" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA STAINLESS STEEL PIPE FOR VENT
ADAPTOR
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 84 0804 000
12" MIN
AIR INTAKE LOUVERS
3" DIA STRAIGHT SCREENED VENT TERMINATION
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
Figure 12. Direct vent, sidewall venting illustration; utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
Page 13
Lynx Model LX-85
13
3" DIA PVC/CPVC PIPE FOR VENT
OUTSIDE TERMINATION PLATE
3" DIA PVC/CPVC COUPLING WITH SCREEN
INSIDE TERMINATION PLATE
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
SCREW
WALL (3"-16" THICK)
3" DIA PVC/CPVC PIPE FOR VENT
SCREW
STOP FOR AIR/VE NT OUTSIDE TERMINAL
Figure 13a. Vent/Air intake termination; utilizing PVC/CPVC pipe for venting.
4" GALV. PIPE (WALL THIMBLE - FOR COMBUTIBLE WALLS ONLY)
3" DIA AL29-4C S.S. VENT PIPE (SLIP JOINT CONNECTOR )
INSIDE TERMINATION PLATE
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
3" DIA AL29-4C S.S.
(SLIP JOINT CONNECTOR)
WALL (3"-12" THICK)
FLUE GAS
VENT PIPE
SCREW
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
INSIDE TERMINATION PLATE
AIR
SEAL HERE
OUTSIDE TERMINATION PLATE
3" DIA PVC/CPVC COUPLING WITH SCREEN
FLUE GAS
LOUVERS
3" DIA PVC/CPVC PIPE FOR A IR INTAKE
AIR
WALL (3"-16" THICK)
INSIDE TERMINATION PLATE
WALL (3"-12" THICK)
SCREW
STRAIGHT SCREENED TERMINATION
OUTSIDE TERMINATION PLATE
STRAIGHT SCREENED TERMINATION
Figure 13b. Vent/Air intake termination; utilizing stainless steel venting materials.
SEAL HERE
LOUVERS
OUTSIDE TERMINATION PLATE
Page 14
14
Lynx Model LX-85
VENT/AIR INTAKE TERMINATION FOR PVC/CPVC VENTING INSTALLATION
This termination is designed specifically for 3” diameter PVC or CPVC Schedule 40 pipe to be used as the vent and air intake piping material, only. It can be used on a combustible wall, provided the 1” minimum clearance of the vent pipe to any combustible surface is maintained.
1. Termination must be installed horizontally.
2. Refer to Figure 13a for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and
clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in
the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate
using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the out
side termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #9.
8. From inside, install the inside termination plate, using 4
screws. Make sure that the holes for the vent and air intake pipe visually line up with the vent passage hole and air intake collar on the outside termination plate.
9. Cut the PVC or CPVC air intake pipe to the proper
dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
10. Cut the PVC or CPVC vent pipe so that it will extend out
at least 2" from the outside termination plate and 2" from inside termination plate.
11. Cement a 3” diameter PVC or CPVC coupling onto the
PVC or CPVC vent pipe, and install the stainless steel screen (supplied with the boiler) into the coupling.
VENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL VENTING INSTALLATION
This termination is designed specifically for the 3” diameter stainless steel venting systems approved to be used as the vent, and 3” diameter PVC or CPVC schedule 40 pipe to be used as the air intake piping material, only. It can be used on a combustible wall, provided a length of 4” diameter galvanized pipe is installed as a thimble around the vent pipe, for the wall passage.
1. Termination must be installed horizontally.
2. Refer to Figure 13b for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the outside termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #11.
8. For combustible wall a 4” galvanized pipe must be used as a wall thimble.The length of the 4” galvanized pipe should be approximately 1” shorter than the wall thickness.
9. From inside the building, fit galvanized pipe over 4” collar of the outside plate.
10. From inside, install inside termination plate using 4 screws. Make sure the 4” collar on the plate, penetrated into the galvanized pipe.
11. Cut the PVC or CPVC air intake pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
12. From outside the wall, insert the bare end of the PVC or CPVC vent pipe through the outside and inside terminal plates, until the coupling is flush with the outside wall plate.
13. From inside, proceed with the air intake and vent pipe installation. Follow the proper PVC/CPVC assembly practices specified on page 7 and venting system restrictions specified on page 7 of this manual.
12. Assemble and seal straight screened termination to the slip joint connector.
13. From outside of the building, insert vent pipe (slip joint connector and termination assembly) through the 3” holes of the outside and inside termination plate.
14. From inside, proceed with air intake and vent pipe installation. Follow vent manufacturer’s instructions and restrictions specified on page 7 of this manual.
Page 15
Lynx Model LX-85
15
B. DIRECT VENT - VENTING AND AIR INTAKE
THROUGH A ROOF
Figure 14 shows typical vertical venting. The vent pipe must pass through the ceiling, floor and the roof vertically through a 6” minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage an appropriate UL listed roof flashing must be used.
The vertical vent piping must terminate with a screened straight termination. The air intake termination should be a screened 180˚ elbow facing down. The air intake opening must be at least 1 foot below the vent opening.
LYNX MODEL LX-85 - DIRECT VENT, VENTING AND AIR INTAKE
THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
FLASHING AND
STORM COLLAR
AIR INTAKE
180° ELBOW
WITH SCREEN
For PVC/CPVC pipe, follow the proper assembly practices specified on page 7, and venting system restrictions specified on page 7 of this manual. For stainless steel venting systems, follow the vent manufacturer’s instructions and the restrictions specified on page 7 of this manual
STRAIGHT TERMINATION
10 FT MIN.
WITH SCREEN
1 FT MIN.
1 FT MIN.
O
N
S
E
N
I
L
W
SUPPORT
FIRESTOP AND
SUPPORT
PIPE
3" DIA. PVC/CPVC
PIPE FOR AIR INTAKE
2" MIN
FIRESTOP AND
SUPPORT
SLOPE UP 1/4 IN.
PER FOOT MIN.
3" DIA. PVC/CPVC
OR STAINLESS
STEEL VENTING
MATERIAL FOR
VENT
USE ADAPTOR IF STAINLESS STEEL IS USED
Figure 14. Direct vent, venting and air intake through a roof.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
Page 16
16
Lynx Model LX-85
VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION
A. Inspect the system regularly for condensation, corrosion,
sagging and/or physical damage. A qualified professional should service the boiler annually and include such an inspection at that time. The homeowner should look over the system monthly for damage, water stains, any signs of rust, other corrosions or separation of the vent and air intake piping (if direct-vent).
B. Should an inspection turn up signs of condensation,
corrosion, sagging or damage, the boiler should be shut down immediately and the condition should be corrected by a qualified professional.
CONDENSATE REMOVAL SYSTEM
The Lynx LX-85 is equipped with a built-in condensation drain and trap. The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. If the trap is disassembled for inspection, it must be reassembled and filled with water as before.
A 3/4” PVC tee, located on the left rear of the boiler jacket, is pro­vided to run the condensate liquid from the boiler. Connect the plastic tubing that will be run to the drain to the bottom take-off of the tee. Leave the top take-off of the tee open, to act as a vacu­um breaker. If the building drain is above the bottom portion of the tee, a condensate removal pump will be required. This pump must have an overflow switch, and be compatible with the acidic condensate liquid, as must all fittings and the tubing used in this condensate removal system. (See Figure 15).
No part of the condensate removal system can be exposed to freezing temperatures, or any other conditions that could cause blockage. DO NOT run drain tubing to the outside of the building. In addition, certain jurisdictions or drain pipe materials may require a neutralization unit to be installed in the condensate removal system. Any piping other than plastic types will be subject to corrosion or deterioration from the acidic conden­sate, which may have a pH level as low as 3.0. A condensate filter containing lime, marble, or phosphate chips can neutralize the condensate to a pH level above 6.5, which is safe for all drain piping materials. (See Figure 15). The neutralizing filter
medium will require periodic changing, to ensure it’s affective­ness. Replacing the medium on an annual basis is recom­mended, or refer to the manufacturer’s instructions for systems that are available for neutralizing condensate.
COMMONWEALTH OF MASSACHUSETTS SPECIAL REQUIREMENT
When the Lynx-85 is installed and used in the Commonwealth of Massachusetts, a neutralization unit MUST be installed in the condensate removal system.
GAS PIPING
A. Local installation codes apply. The pipe joint compound
used on threads must be resistant to the action of liquefied petroleum gases.
B. The gas supply line to the boiler should run directly from the
meter for natural gas or from the fuel tank for L.P. propane gas. A manual gas supply shut-off valve is provided on the boiler’s gas supply pipe. (See Figure 3, on page 3). Local codes may specify a manual main gas supply shut-off valve to be 5’ above the floor, and a disconnection union at the gas piping entrance to the boiler. In this case, unless the boiler is wall mounted at the right height, the gas supply shut-off valve must be relocated to the specified location. If the gas supply pipe must be upsized for flow considerations, then the same size main gas supply shut-off valve must be used.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
EXAMPLE: Boiler model LX-85 is to be installed. Distance from gas meter to the boilers is 30 ft. Heating value of natural gas is 1020 Btu/cu. Ft. Select proper pipe size.
Gas flow = 85,000 Btu/hour
1020 Btu/cu. ft.
= 83 cu. ft. per hour
DRAIN VACUUM BREAKER, LEAVE OPEN
CONDENSATE TRAP, FILL WITH WATER
NEUTRALIZING UNIT (IF REQUIRED)
CONDENSATE PUMP (IF REQUIRED)
DRAIN INSIDE BUILDING
Figure 15. Condensate disposal system
PLASTIC TUBING
Page 17
Lynx Model LX-85
17
At 30 ft. length of pipe, match required capacity from table on this page (choose higher capacity, in this case is 152 cu. ft. per hour). Required pipe size is
3
4".
Improper gas pipe sizing will result in flame outages, insuffi­cient heat and other installation difficulties. For more informa­tion and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested
before replacing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and it’s individual shutoff valve must be disconnected from the gas supply piping system during and pressure testing of that system at test pressures in excess
1
of
2 PSIG. This boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
1
2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap is integrally provided, as illustrated on page 3.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
Length of pipe in Feet
Gas Flow In piping -- cu. ft. per hr.
Iron Pipe Size (IPS) — inches
1/2
3
/4 11
1
/4
11/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
At pressure drop of 0.3 in. water, specific gravity = 0.6.
ELECTRICAL WIRING
All field wiring to the boiler is connected to the 2 sets of terminal strips, located in a junction box behind the jacket top panel. (See Figure 3, on page 3)
DANGER: Before wiring always turn off electric power supply. Otherwise, shock or death can result.
Boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction, or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
Proper polarity is critical for the power supply connections. Reversed polarity will cause system lockout. Proper ground­ing is critical for boiler operation, connect the ground wire to the green ground screw next to the line voltage terminal strip.
2. Circulator(s)
A set of terminals are provided for the boiler loop circulator. Only wire this circulator to these terminals, additional circulators for the space heating system loop require the use of relays and a separate power source.
For multiple zoning, either zone valves or circulators may be used.
For zone valve system (See Figure 17a).
For pump zoning system (See Figure 17b, c, d, e).
DO NOT use boiler transformer to power external accessories like zone valve and relays, overload and/or burned out transformer and boiler malfunction can result. Use separate transformer to power such components.
A second set of terminals are provided for the domestic hot water tank circulator (if used). The boiler loop circulator is always de-energized when the DHW tank circulator is energized, or vice-versa, depending on the priority feature selected.
3. SPACE HEATING THERMOSTAT(S)
Install thermostat on an inside wall and away from any heat sources, sunshine and drafts. A set of terminals are provid­ed for connection of 24 volt style thermostats, relays or zone valve end switches (isolated contacts). (See wiring diagrams Figure 16a,17a, 17 b, 17c, 17d, 17e).
Thermostat heat anticipator: For a non-zoned system set thermostat heat anticipator to 0.1 Amps, for zoned system set to match power requirements of zone valves or relays. Refer to manufacturer’s instructions and specifications. Also see instructions with thermostat.
4. DOMESTIC HOT WATER TANK THERMOSTAT
A set of terminals are provided for connection of the DHW tank thermostat (if used). (See wiring diagram Figure 16a).
5. OUTDOOR AIR SENSOR
A set of terminals are provided for connection of an outdoor air sensor (if this method is used). (See wiring diagram Figure 16a).
1. Power Supply
A separately fused circuit is recommended. Use standard 15 Amp. fuse or breaker and 14 gage conductors in BX cable or conduit.
Provide disconnect means and overload protection as required. See boiler wiring diagram (Figure 16a) boiler control (Figure16b) and ladder diagram (Figure 16c).
The outdoor air sensor that is supplied with the boiler is a 12k ohm type. Mount on an outside wall, shielded from direct sunlight or flow of heat or cooling from other sources. See instructions provided with sensor.
6. LOW WATER CUTOFF
A set of terminals are provided for connection of a LWCO. If this device is used, remove the factory installed jumper from these terminals. (See wiring diagram Figure 16a).
Page 18
18
Lynx Model LX-85
Figure 16a. Schematic wiring diagram.
Page 19
Lynx Model LX-85
19
Figure 16b. Boiler Control.
Figure 16c. Ladder wiring diagram.
Page 20
20
Lynx Model LX-85
ZONE 1
THERMOSTAT
V8043E/F
END
SWITCH
TT T TT T T TT TT T TT
TH-TR
MOTOR
1 2 3 4 5 6 7 8
V8043E/F
SWITCH
FIELD WIRING TERMINALS ON BOILER
END
TH-TR
ZONE 2
THERMOSTAT
V8043E/F
1
END
SWITCH
2
3456
MOTOR
T
R845A RELAY
Figure 17a. Multizoning of Lynx boiler; zone valve system.
TH-TR
JUMPER
ZONE 3
THERMOSTAT
MOTOR
T
DISCONNECT
SWITCH
LI
1
120V/24V
TRANSFORMER
SPACE
HEATING
SYSTEM
T
CIRCULATOR
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
L2
DISCONNECT
SWITCH
LI
R845A
RELAY ZONE 3
1
1
2
3456
CIRC.
ZONE 3
TT
ZONE 3
THERMOSTAT
R845A
RELAY ZONE 2
23456
1
CIRC.
ZONE 2
ZONE 2
THERMOSTAT
TT TT
L2
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1 2 3 4 5 6 7 8
Figure 17b. Multizoning of Lynx boiler; pump zoning system using R845A rela y.
R845A
RELAY ZONE 1
23456
1
CIRC.
ZONE 1
FIELD WIRING
TERMINALS
ON BOILER
ZONE 1
THERMOSTAT
Page 21
Lynx Model LX-85
ZONE 3
THERMOSTAT
R882A/B
R882A/B
ZONE 2
THERMOSTAT
R882A/B
ZONE 1
THERMOSTAT
120V/24V
TRANSFORMER
DISCONNECT
SWITCH
LI
L2
120V/60HZ
21
1
CIRC.
ZONE 1
1 2 3 4 5 6 7 8
CIRC.
ZONE 3
FIELD WIRING
TERMINALS ON BOILER
CIRC.
ZONE 2
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Figure 17c. Multizoning of Lynx boiler; pump zoning system using R882A/B rela ys.
Page 22
22
Lynx Model LX-85
THERMOSTAT
TT
R845A RELAY
3
2
1
4
56
DISCONNECT SWITCH
LI
1
CIRCULATOR
L2
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1 2 3 4 5 6 7 8
FIELD WIRING TERMINALS ON BOILER
Figure 17d. Single zoning of Lynx boiler; pump zoning system using R845A rela y.
THERMOSTAT
120 V / 24 V TRANSFORMER
DISCONNECT SWITCH
LI
1
R 882A/B
L2
RELAY
CIRCULATOR
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1 2 3 4 5 6 7 8
Figure 17e. Single zoning of Lynx boiler; pump zoning system using R882A/B relay.
FIELD WIRING TERMINALS ON BOILER
Page 23
Lynx Model LX-85
23
WATER PIPING
1. Connection of system to boiler:
Primary/secondary piping of the system is recommended, to ensure the proper flow through the boiler. (See Figures 20 through 22). The boiler loop piping must be the same diameter as the water outlet (supply) and inlet (return) piping connections provided on the boiler, particularly on longer loops. See page 2 for piping connection size.
2. Circulator Pumps:
The boiler loop piping must utilize the Taco 0011 circulator that is supplied with the boiler, to ensure the proper flow through the boiler. Refer to Figure 19 for the boiler water side pressure drop and Table 2 for the recommended pump models for the domestic hot water system. Install the pumps in the orientation shown in Figures 20 through 22.
3. Relief Valve(supplied with boiler):
Tee the relief valve into the boiler water outlet (supply) piping as close to the water outlet (supply) connection as possible. (See Figure 18). The relief valve’s discharge piping must be the same size or larger than the relief valve’s outlet, and must terminate 6” minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping, or any place where freezing could occur. No shut-off valve is permitted between the relief valve and boiler, or in the discharge line.
4. Air Control System:
An appropriately sized diaphragm-type expansion tank must be used to control the system pressure. See boiler volume data on page 2, and the recommended location in Figures 20 through 22. An air vent is recommended to be installed on an air separator in close proximity to the expansion tank.
5. Cold Water Fill:
A pressure reducing (fill) valve, with a shut-off valve upstream of it, should be installed in close proximity of the expansion tank. (See Figures 20 through 22). Use a back flow check valve in the cold water supply as required by local codes.
6. Low Water Cutoff:
On a hot water boiler installed above radiation level, the boiler must be provided with a low water cutoff device at the time of installation by the installer (see Figure 18 for piping arrangement).
7. Water Treatment and Freeze Protection:
A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time and expense of repairs made necessary by preventable occurrences. A reputable water treatment company should be consulted to evaluate and determine the best overall treatment program for your boiler equipment.
The heat exchanger is made of aluminum, so the system water must be maintained between 7.0 and 8.5 PH level. Thoroughly flush the system, before connecting the boiler, to remove any sediment or glycol.
Anti-freeze is sometimes used in hydronic systems to protect against freeze-up in the event of power failure or boiler shut down in the cold winter. Use RhoGard
(Propylene glycol with Pro-Tek 922 inhibitor) by Rhomar Water Management, Inc. Follow the manufacturer’s
instructions for proper application and proper mixture for minimum ambient temperature. Any use of anti-freeze
other than that supplied b y Slant-Fin or specifically approved and/or recommended for use by Slant-Fin will void the warranty.
Never use any types of automotive or standard gylcol freeze protection fluids. Never use Ethylene Glycol as it is toxic to humans.
8. Piping a heating - cooling system to a water boiler and chiller:
Figure 22 illustrates a method of piping a heating-cooling system to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.
The air control system and pressure control system must operate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pres­sure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils during the cooling cycle.
Page 24
24
WATER OUTLET PIPING
Lynx Model LX-85
TO REST OF SYSTEM
LOW WATER CUTOFF MANIFOLD
(IF LWCO UTILIZED)
*PIPING ORIENTATION FOR REFERENCE ONLY.
Figure 18. Relief Valve and Low Water Cutoff Installation
PROBE TYPE LOW WATER CUTOFF (IF REQUIRED)
PRESSURE RELIEF VALVE (SUPPLIED WITH BOILER)
RELIEF VALVE DISCHARGE PIPING
3/4" NPT STREET ELBOW
1" x 1" x 3/4" TEE
WATER OUTLET (SUPPLY) PIPE 1" MIN. DIAMETER
WATER INLET (RETURN) PIPE 1" MIN. DIAMETER
Page 25
Lynx Model LX-85
25
PRESSURE DROP
10
FLOW RATE Boiler heat loss
Head
8
(feet w.c.)
6
4
2
0
LYNX LX-85
gpm Feet w.c
7.7 8.5 53
3.8 1.5
2.5 0.75 00
02468
Flow Rate (GPM)
Figure 19. Boiler water side pressure drop
Flow
Rate
(gpm)
Temp
Rise
(˚F)
Boiler
Head Loss
(Feet w.c.)
Domestic Water
Tank Piping
Head Loss **
(Feet w.c.)
7.7 20˚ 8.5’ 2.5’
Available Head Capability Left for Various Model
Circulators to Overcome DHW Tank Head Loss
(Feet w.c.) ***
Taco 0012 Taco 0014 Taco 0011
Not Recommended 7.0’ 14.0’
5.0 30˚ 3.0’ 2.0’ 8.0’
3.8* 40˚ 1.5’ 1.5’
Table 2. Recommended pump models for domestic hot water tank piping.
Notes:
* This is the minimum flow rate recommended for the model LX-85 boiler.
** Domestic water tank piping head is based on 1” inside diameter piping and full port valves.
10.0’ 17.0’ 25.0’
14.0’ 22.0’
*** Refer to the DHW Tank Manufacturer’s water flow rate requirements and associated pressure drop head loss, to select
the appropriate circulator.
Page 26
26
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
Lynx Model LX-85
MAKE UP
WATER
SUPPLY
Figure 20. Zoning with circulators.
HOT WATER
OUTLET
DOMESTIC
HOT WATER
TANK
COLD
INLET
WATER
*PIPING ORIENTATION FOR REFERENCE ONLY
Page 27
Lynx Model LX-85
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
MAKE UP
WATER
SUPPLY
27
Figure 21. Zoning with zone valves.
HOT WATER
OUTLET
DOMESTIC
HOT WATER
TANK
*PIPING ORIENTATION FOR REFERENCE ONLY
COLD
INLET
WATER
Page 28
28
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
WATER
CHILLER
UNIT
Lynx Model LX-85
MAKE UP
WATER
SUPPLY
* PIPING ORIENTATION FOR REFERENCE ONLY
Figure 22. Piping a heating-cooling system to the boiler and a c hiller.
DOMESTIC
HOT WATER
TANK
HOT WATER
OUTLET
COLD
INLET
WATER
Page 29
Lynx Model LX-85
29
OPERATING INSTRUCTIONS
I. FILLING AND VENTING WATER SYSTEMS
A. Fill the system with water. Vent or purge of air.
B. Fire the boiler as soon as possible (see following warning
and instructions) and bring water temperature in the system.
C. Vent air and add water as needed to achieve operating
pressure on boiler gauge. Pressure must be between approximately 12 psi (cold water) and 25 psi at water temperature setting of high limit control, for boilers equipped with 30 psi relief valves. Boilers rated for a higher pressure and equipped with a matching relief valve may operate at a higher pressure, but no higher than 5 psi below the relief valve opening pressure.
D. Check for and repair any leaks before placing system in
service.
BEFORE FIRING BOILER, make these checks:
Before firing boiler, review the “Boiler Control and Display Features” section of this manual. Understanding the features and programming the applicable parameters is essential for setting up the boiler to operate properly on the heating system it is installed on.
1. System is full of water. Air is vented or purged.
2. Relief valve is installed in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Valve opening is not closed or reduced in size.
3. Venting is installed according to instructions under “FLUE GAS VENTING REQUIREMENTS”.
4. All wiring is completed, following applicable wiring diagrams.
3. While “t” is blinking, DHW tank temperature may be set to desired temperature (if tank is equipped with sensor). The setting range is between 104˚ to 185˚F.
4. View actual boiler supply & return water tempera­ture, domestic hot water tank temperature (if tank equipped with sensor), flue temperature and outside temperature (if outside sensor is used) on “Temperature Display” by selecting 1, 2, 3, 4, or 5 on “Mode Display”.
• These numbers are steady on display and are
not settable.
• All sensor inputs to the control must be
connected to a 12k ohm sensor.
C. Viewing and changing system setting:
A trained, experienced service technician or installer should perform following adjustments. See table 5 for details.
1. Space heating and DHW post pump time may be changed.
2. Space heating and DHW modes may be chosen.
3. Priority for either space heating or DHW may be chosen, with a selectable time limit or infinite operation.
4. Weather compensation slope and set point temperature may be changed (if outside sensor is used). (See Figure 24 for graph).
5. Read actual blower RPM.
6. Adjust blower RPM for high and low input adjustment.
7. Read flame current in micro amp.
8. Run boiler on high, low or ignition input steady for 20 minutes for test purposes.
D. Display and push buttons:
5. Using soap solution, check for gas leaks in all gas piping from meter to boiler gas supply pipe. DO NOT use open flame.
II. BOILER CONTROL AND DISPLAY FEATURES
(See Figure 23)
A. Boiler Operation Status:
“Mode Display” shows status of boiler operation (see table 3).
B. Viewing and Changing Temperatures:
Setting boiler supply water temperature and water tank temperature (see table 4). Press “Select” button for viewing following different modes on “Mode Display”
1. While “c” is blinking, boiler supply water temperature for space heating may be set to desired temperature The setting range is between 90˚ to 185˚F.
2. While “d” is blinking, boiler supply water temperature for DHW may be set to desired temperature. The setting range is between 104˚ to 185˚F.
1. Reset - Used to clear a Lock out error (indicated with an “A” in the “Mode Display”).
2. Select - Used to scroll through the modes in the “Viewing and Changing Temperatures” and “Viewing and Changing System Setting” menus.
3. Enter - Used to store values that are changed in the “Viewing and Changing Temperatures” and “Viewing and Changing System Setting” menus.
4. Up- Used to increase values in the “Viewing and Changing Temperatures” and “Viewing and Changing System Setting” menus.
5. Down - Used to decrease values in the “Viewing and Changing Temperatures” and “Viewing and Changing System Setting” menus.
Page 30
30
Lynx Model LX-85
"MODE" DISPLAY
"RESET" PUSH BUTTON
"BURNER STATUS"
STEADY DOT = BURNER ON
BLINKING DOT = BURNER OFF
Figure 23. Display Board
"TEMPERATURE" DISPLAY (3 DIGITS)
"UP" PUSH BUTTON
*
"DOWN" PUSH BUTTON
"ENTER" PUSH BUTTON
"SELECT" PUSH BUTTON
Table 3
LYNX BOILER DISPLAY BOARD
“Boiler Operation Status”
MODE
DISPLAY
Reset button must be pressed to resume normal operation.
NOTE: Blinking dot on “Mode Display” indicates active heating control, burner off.
Steady dot indicates burner is on.
*: Error must be corrected to resume boiler operation. Pressing the “Reset” button is not required. **: The boiler loop circulator is energized, if the boiler water temperature drops below 50˚F. ***: Error must be corrected to resume DHW operation. Space heating not affected. Pressing
the “Reset” button is not required.
DESCRIPTION & TEMPERATURE DISPLAY
Boiler is on stand-by mode.
Temperature display shows supply water Temp.
Space heating mode.
Temperature display shows supply water Temp.
Domestic hot water mode.
Temperature display shows supply water Temp.
Frost protection mode. **
Temperature display shows supply water Temp.
Lockout (Alarm) condition.
Temperature Display indicates the lockout code
Error Condition. *
Temperature display indicates the error code.
Warning Condition. ***
Temperature display indicates the error code.
Page 31
Lynx Model LX-85
Press “SELECT” button for viewing different modes on “MODE DISPLAY”
31
Table 4
VIEWING AND CHANGING TEMPERATURES
MODE
DISPLAY
blinking
blinking
blinking
DESCRIPTION & TEMPERATURE DISPLAY
Space heating supply water temperature could be changed by
pressing “Up/Down” button. Settable from 90˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 1)
Domestic hot water supply temperature could be changed by
pressing”Up/Down” button. Settable from 104˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 2)
Domestic hot water tank temperature could be changed by
pressing “Up/Down” button. Settable from 104˚F to 160˚F
(steps of 1 F). The default value is 140˚F.
Press “Enter” button to store.
(see note 3)
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
NOTE:
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
(if outdoor sensor is used)
1- For space heating mode “0” (boilers not utilizing outdoor sensor)) 2- For DHW mode “2” (storage tank with Aquastat) 3- For DHW mode “1” (storage tank with sensor)
Page 32
32
Lynx Model LX-85
VIEWING AND CHANGING SYSTEM SETTING -
Table 5
“To change system setting or perform system test”
The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change
system setting: Press “UP or DOWN” button, then press “ENTER”
WARNING: Only a trained, experienced service technician or installer should use this table.
MODE DISPLAY
*
*
*
*
*
Changing space heating post pump time. Settable from 10 to 900 seconds.
(steps of 10 seconds). The default value is 30 seconds.
Changing DHW post pump time. Settable from 1 to 255 seconds.
(steps of 1 seconds). The default value is 15 seconds.
Changing space heating control mode 0: Thermostat only (default) - boiler without outdoor sensor 1: Outside sensor and Thermostat 2: Outside sensor only 3: Permanent heat demand (boiler circulator always on)
Changing domestic hot water (DHW) mode
0: No DHW 1: Storage tank with sensor 2: Storage tank with thermostat (default value) 3: Plate heat exchanger
Changing DHW or space heating priority mode
0: DHW priority (no time limit) 1: Space heating priority (no time limit) 2: DHW priority for limited time (default) 3: Space heating priority for limited time
DESCRIPTION
**
**
*
*
*
*
(space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F).
*
*
Changing weather compensation set point (space heating mode 2 only).
*
*
*
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
Changing priority limited time. Settable from 20 to 80 minutes.
The default value is 30 minutes.
Boiler model selection, value is 1 for model LX-85
Boiler model confirmation, value is 1 for model LX-85
Weather compensation supply water reference temperature
The default value is 86˚F.
Changing compensation slope (space heating mode 1 or 2).
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Not Utilized
Settable from 32˚F to 122˚F (steps of 1˚F).
The default value is 68˚F.
Display shows blower RPM (mutiply reading by 10 for actual RPM)
Display shows flame current in micro amps
*
NOTE: *: Alternating **: Steady
System test – Display shows flame current
0: System test off L: Steady low input (20 minutes) I: Steady ignition input (20 minutes) H: Steady high input (20 minutes)
Page 33
Lynx Model LX-85
33
Maximum water target temp.
185 °F
Water
Supply
Target Temp.
(°F)
200
190
180
170
160
150
140
130
120
)
.
x
a
m (
0
0
.
5
=
e
e
p
p
o
o
l
Sl
S
0
.
.
4
=
= 3
e
p
o
l
S
0
.
8
.
2
1
=
=
e
e
p
p
o
o
l
l
S
S
5
.
1
=
e
p
o
l
S
2
.
1
=
e
p
o
l
S
=
e
p
o
l
S
e
p
o
l
S
)
t
l
u
a
f
e
d
(
0
.
1
5
.
0
=
110
Minimum water target temp.
100
90
Water reference
80 temp. (default of 86°F)
70
70 60 -20-10 -3001020304050
6 8 °F
Outdoor Temp. (°F)
Figure 24. Space Heating mode with outside sensor water set point graph.
.)
n
i
m
(
1
.
0
=
e
p
o
l
S
-40
Page 34
34
Lynx Model LX-85
III. INITIAL START
Safe lighting and other performance criteria were met when test­ing various gas manifold and control assemblies used on the Lynx LX-85 boiler under the ANSI Z21.13 - latest edition.
Instructions
Follow the lighting instructions in this manual. These instructions are also attached to the boiler.
TURN 90˚ TO OPEN
TURN 90˚ TO CLOSE
C. Use only your hand to turn the gas supply shut-off valve.
Never use tools. If the supply shut-off valve will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. D
O NOT try to light the
burner by hand.
5. Open the gas supply shut-off valve, by turning the handle to be parallel to the gas piping (See Figure 25).
GAS SUPPLY SHUTOFF VALVE IN "OPEN" POSITION
GAS SUPPLY SHUTOFF VALVE IN "CLOSED" POSITION
Figure 25. Gas supply shutoff valve operation.
SAFETY INFORMATION
For Your Safety Read Before Operating
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch: DO NOT use any phone in your building.
• Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
6. Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas, STOP! Follow “B” in the safety information above on this page. If you don’t smell gas, go to next step.
7. Turn on all electric power to the appliance.
8. Set thermostat to desired setting. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close the gas supply shut off valve, by turning the handle to be perpendicular to the gas piping. (See Figure 25).
Page 35
Lynx Model LX-85
LYNX BOILER MODEL LX-85 SEQUENCE OF OPERATION
35
THERMOSTAT CALLS FOR HEAT
CIRCULATOR(S) ON
COMBUSTION BLOWER ON
(AT MEDIUM SPEED)
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 33”
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 03”
NO
NO
BLOWER SPEED CONFIRMED?
YES
5 SECOND PRE-PURGE PERIOD
TRIAL FOR IGNITION - 6 SECONDS
SPARK IGNITOR ENERGIZED
GAS VALVE OPENS
WATER HIGH LIMIT CLOSED?
YES
GAS VALVE REMAINS OPEN
FOR 4 SECONDS
NO
3 TRIALS FOR
IGNITION
WITH NO FLAME SENSED?
2 TIMES RETRIALS
FOR IGNITION
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 01”
YES
GAS VALVE REMAINS OPEN. CONTROL
SENSORS, BLOWER SPEED, FLAME
THERMOSTAT CALL FOR HEAT ENDS
10 SECOND BLOWER POST PURGE.
15 SECOND CIRCULATOR POST PURGE.
SPARK IGNITOR DE-ENERGIZED
NO
FLAME SIGNAL SENSED?
YES
CONTINUOUSLY MONITORS
THERMOSTAT, HIGH LIMIT, WATER
SIGNAL, AND LWCO (IF USED).
GAS VALVE CLOSES
GAS VALVE CLOSED.
BLOWER POST PURGE
10 SECONDS.
Page 36
36
Lynx Model LX-85
IV. CHECK COMBUSTION AND FUEL INPUT RATE
A. Remove the boiler jacket top panel, by removing the 2
screws near the back and lifting as the top panel is slid toward the back. Remove the boiler jacket front panel, by pulling forward from the top, and lifting off the pivots at the bottom. (See Figure 26a).
B. Lift the control panel up over the jacketing, by removing the
2 screws in front, and folding at the hinge while lifting upward from the bottom. Position the notches in the side brackets onto the jacket side panel pivots, to secure in place. (See Figure 26b).
C. Remove the heat exchanger enclosure front cover, by
unlatching the 2 top corners and lifting as the cover is pulled forward from the top. (See Figure 26c).
D. Start and run the burner at the maximum firing rate, by
using the “System Test” mode in the “Viewing and changing system setting” menu. Refer to Table 5 on page 32.
1. Measure the CO, and CO2of the flue gas. A flue sample port is provided in the vent pipe (See Figure 3 on page 3). The length of certain combustion analyzer probes may require that the control panel be lowered, in order to insert the probe into the flue sample port. The CO should not exceed 100 ppm, when the combustion is correct. The CO2 should be in the range listed in Table 6.
4. If the fuel input is not at the rate specified on page 2 at the maximum firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM for high input” mode in the “Viewing and Changing System Setting” menu. Refer to Table 5 on page 32. Increasing the blower rpm will increase the fuel input rate, and decreasing the blower rpm will decrease the fuel input rate.
E. In the “System Test” mode in the “Viewing and Changing
System Setting” menu, use the “down” push button to switch to the minimum firing rate. Refer to Table 5 on page 32.
1. Measure the CO and CO2of the flue gas. The CO should not exceed 30 ppm, when the combustion is correct. The CO2should be in the range listed in Table 6.
2.
If the CO2 is not within the range specified for that gas type at the minimum firing rate, then adjust the gas valve offset to the nominal valve shown in Table 6. (See Figure 26d) for the location of the offset adjust­ment. Remove the cap that covers the offset screw
Turn the offset clockwise to increase the CO2value. Turn the offset counter-clockwise to decrease the CO2value. Replace the offset cap when adjustment is complete.
.
2. If the CO2is not within the range specified for that gas type at the maximum firing rate, then adjust the venturi throttle to the nominal value shown in Table 6. Turn the throttle clockwise to decrease the CO value. Turn the throttle counter-clockwise to increase the CO2value. See Figure 26d.
3. Once the correct combustion is confirmed at the maximum firing rate, check the fuel input rate on the gas meter.
BTUH INPUT = cu. ft. metered in 3 minutes x
* The higher heating value of the gas can vary for
different localities. Consult the gas supplier for this value in BTU/cu.ft.
Fuel
Nat. Gas
Firing
heating value of the gas* x 20
CO
2
Rate
min. nom. max.
max. 8.7% 9.0% 9.3%
min. 7.7% 8.0% 8.3%
2
3. Once the correct combustion is confirmed at the minimum firing rate, check the fuel input rate of the gas meter. BTUH Input = cu. ft. metered in 3 minutes x heating valve of the gas * x 20.
4. If the fuel input is not at the rate specified on page 2 at the minimum firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM for low input” mode in the “Viewing and Changing System Setting” menu. Refer to Table 5 on page 32. Increasing the blower rpm will increase the fuel input rate, and decreasing the blower rpm will decrease the fuel input rate.
F. Exit the “System Test” mode, once the combustion and fuel
input rate has been checked and adjusted, if necessary. Refer to Table 5 on page 32.
G. Replace the heat exchanger enclosure front cover, and
secure the 2 latches. Lower the control panel back in place, and secure with the 2 screws. Replace the jacket top panel, and secure with the 2 screws. Replace the jacket front panel, engaging the top area clips to secure..
max. 10.2% 10.5% 10.8%
Propane
min. 9.2% 9.5% 9.8%
Table 6. Combustion values for Natural Gas and Propane.
Page 37
Lynx Model LX-85
SCREWS
37
TOP COVER
FRONT COVER
Figure 26a. Remove jacket top and front covers.
PIVOT
HEAT EXCHANGER ENCLOSURE FRONT COVER
Figure 26b. Lift control panel.
CONTROL PANEL
HINGE
LATCH
Figure 26c. Remove heat exchanger enclosure front cover.
VENTURI
THROTTLE ADJUSTMENT SCREW
Figure 26d. Gas valve and venturi adjustment.
COMBUSTION BLOWER
OFFSET ADJUSTMENT SCREW (UNDER CAP)
GAS VALVE
Page 38
38
Lynx Model LX-85
V. SAFETY CHECK
A. Check for gas leaks:
Using soap solution, check for gas leaks from meter to gas valve including all pipes and fittings and gas valve connections. Use liquid soap solution for all gas testing. DO NOT use open flame.
B. Thermostat Test:
Set thermostat setting to low enough to end call for heat. Gas valve should close and burner should stop firing. Blower and circulator pump should go into a post purge, then shut off.
A. LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error
and retry operation. The temperature display shows the error code.
ERROR CODE INDICATION REMEDY
01
Ignition Failure - 3 unsuccessful
ignition attempts in a row.
C. Control Safety Shutdown test:
With the burner firing, disconnect the spark cable from the spark ignitor. Gas valve should close and burner should stop firing. The boiler will try for ignition three times after this, then should lock out with an “A 01” error shown on the display. Reconnect the spark cable to the spark ignitor, and press the “Reset” button to return to normal operation.
VI. DIAGNOSTIC ERROR CODES
WARNING: Only a trained, experienced service technician
should perform troubleshooting. Turn off all electric power to the boiler before service.
Check for steady sparking at electrodes. If spark not steady - check spark gap to be .125”, clean or replace spark ignitor, check power supply voltage and grounding. If spark is steady - check for proper gas supply pressure. Check combustion, if able to ignite, or replace gas valve.
02
03
04, 05, 09, 10, 12, 13, 14, 15,
16, 18, 32
19, 20
33
Flame Failure - 3 losses of flame
signal during one demand.
Water High Limit Open
Control Failure
Flame Detected at Wrong Time
Fan Failure - RPM error
Check for proper combustion, at both max. and min. input firing rates. If combustion is within the range specified in Table 6 on page 36, clean or replace spark ignitor, check power supply voltage and grounding.
Check to see if the water outlet temperature reaches 220˚F. If it does, replace the water outlet 12k ohm sensor. If it does not, replace the water high limit switch.
Replace control board. Make sure the proper boiler model selection and confirmation code is entered. See Table 5 on page 32.
If a flame is still observed after a call for heat is stopped, replace the gas valve. If the burner seems to be shutting down properly, replace the spark ignitor.
Check wire harness connections going to the blower. Replace blower.
Page 39
Lynx Model LX-85
B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the
condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required.
ERROR CODE INDICATION REMEDY
Check wire harness connections going to the
01
02
03
Water Outlet Sensor Open
Water Inlet Sensor Open
Flue Gas Sensor Open
sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
39
11
12
13
19, 42, 45,
46, 47, 48
20
21
22
24
Water Outlet Sensor Shorted Replace the sensor.
Water Inlet Sensor Shorted Replace the sensor.
Flue Gas Sensor Shorted Replace the sensor.
Replace control board. Make sure the proper
Control Failure
Flame Detected at Wrong Time
Polarity Error Reverse the hot and neutral power supply wires.
Frequency Error
Earth Connection Faulty Check grounding of control and boiler chassis.
boiler model selection and confirmation code is entered. See Table 5 on page 32.
If a flame is still observed after a call for heat is stopped, replace the gas valve, If the burner seems to be shutting down properly, replace the spark ignitor.
Check power supply frequency to be 60 hz, certain power supplies may not provide the proper frequency.
continued on page 40
Page 40
40
continued from page 39
ERROR CODE INDICATION REMEDY
Check flue gas temperature, at the maximum firing rate and high water temperature. If the flue gas
30
31
32
Excess Flue Temperature
Low Water Cutoff Error
Excess Water Inlet Temperature
temperature reaches 212˚F, check the fuel input rate and combustion. Check the condition of the heat exchanger. If the flue gas temperature does not reach 212˚F, replace the flue sensor.
If a low water cutoff is installed, check the system water pressure and content. Check the condition of the LWCO. If no LWCO is installed, check the jumper is in place at the wiring terminal board. See Figure 16a on page 18.
Check that the wire harnesses to the water inlet and outlet sensors are not reversed. The water inlet sensor harness should have a blue colored connector, the water outlet sensor harness should have a red colored connector. Check that the pumping flow direction is correct.
Lynx Model LX-85
51
52
C. WARNING ERRORS: Indicated by an “H” in the mode display. Operation of the space heating mode is not affect-
ed, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored, once the condition is fixed. The temperature display shows the error code. Pressing the “reset” button is not required.
04
Domestic Hot Water Tank Sensor Open
14
Reset Button Error
Boiler Model Selection Error
Domestic Hot Water Tank
Sensor Shorted
Try turning power supply off and on again. If error returns, replace the display board.
Check that the proper boiler model selection and confirmation code is entered in the display. See Table 5 on page 32.
If sensor is utilized, check wire harness connections going to the sensor, or replace the sensor. If no sen­sor is utilized, check the proper DHW mode is pro­grammed. See Table 5 on page 32.
If sensor is utilized, replace the sensor. If no sensor is utilized, check the proper DHW mode is pro­grammed. See Table 5 on page 32.
Page 41
Lynx Model LX-85
41
CARE AND MAINTENANCE
This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrange­ments with a qualified service agency for the periodic care and maintenance of the boiler. The installer must also inform the owner that the lack of proper care and maintenance of this boiler and any fuel burning equipment may result in a hazardous condi­tion. Installer should discuss contents of the User’s Information Manual (Publication LX-UIM) with the owner.
A trained and qualified service technician should perform the inspection listed in these instructions before each heating season and at regular intervals.
I. GENERAL MAINTENANCE
A. Safety check, see page 38.
B. Vent and air intake system inspection
1. Check for obstruction, condensation, corrosion and physical damage.
2. Check outside termination. Screen and louvers should be free of any debris and must be cleaned as required.
3. Perform “Venting and Air intake System Regular Inspection”, see page 16.
C. Piping
Check the following:
1. Water piping and accessories for leaks. Slightest leaks should be corrected.
2. System to be full of water and pressure to remain stable at correct setting on gauge.
II. ANNUAL MAINTENANCE
IMPORTANT: The spark ignitor must be replaced at the
beginning of each heating season.
III. INSPECTION DURING HEATING SEASON
A. Check water pressure regularly and add water slowly to
system when needed. If much water is added, venting may be necessary. Regular loss of water from boiler system may indicate either a system leak, or a faulty air control system, or a faulty automatic fill valve.
B. Check venting system. See “Venting and Air Intake System
Regular Inspection” on page 16.
C. Check condensation drain trap to be full of water. Check for
deterioration of the tubing. Check that the trap is not plugged.
D. The combustion blower does not require or have provisions
for lubrication.
E. If required, lubricate the circulator as per the manufacturer’s
instruction.
IV. CLEANING
A. Heat Exchanger: In the unlikely event of flue passage or
water passage blockage, service to remedy situation must be performed only by an authorized Slant/FIn representative.
B. Burner: In the unlikely event of blockage or deterioration,
service to remedy situation must be performed only by an authorized Slant/Fin representative.
IF REPLACEMENT PARTS ARE NEEDED
3. Air-control system. Noise and air binding in radiation should not occur.
4. Low water cutoff for operation (see instruction furnished with unit).
D. Boiler Room Air Supply
Check air vents for continuous positive supply of air as required. Air needs are greatest in cold weather if boiler installation is non-direct vent method. Air vents must open and free of obstruction.
WARNING: The flow of combustion and ventilating air to the
boiler should not be obstructed.
When parts are needed, refer to boiler model and serial number shown on the boiler name/rating plate. Refer to publication number LX-10PL replacement parts for part numbers. Whenever possible refer to the original order by number and date.
Control identification and replacement should not be attempted by unskilled personnel. Only, simple easily - identified controls and parts may be obtained locally. All other control and parts should be identified by and ordered from Slant/Fin. Relief/Safety valves must be ASME rater for the pressure and gross output of the boiler.
For replacement parts, heating contractors should contact their Slant/Fin boiler distributor.
Page 42
42
Lynx Model LX-85
GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNEL
WARNING: Only a trained, experienced service technician should perform troubleshooting.
Turn off all electrical power to the boiler before servicing.
A. BURNER FAILS TO OPERATE - NO HEAT
CAUSE
1. No power, display off, power switch off. Main electric 1. Close switch. Check or replace fuse. switch open. Blown or defective line fuse.
2. Gas supply valve shut off. 2. Open gas supply valve. Check gas pressure.
3. Harnesses plug-in connectors are not securely connected. 3. Check connectors on boiler control.
4. Operational problem, detected by control. 4. Error code on display can be correlated to
REMEDY
specific problems and remedy. Refer to page 38-40 for error codes.
B. NOT ENOUGH HEAT
1. Thermostat setting is too low. 1. Set thermostat at higher setting.
2. Boiler water maintained at too low temperature. 2. Increase space heating set point temperature.
Refer to Table 4 on page 31.
3. Circulator not running. 3. With thermostat calling for heat, check for power
to circulator. If power is O.K. but circulator is not running, replace circulator.
4. Boiler water level too low. 4. Carefully snap open relief valve handle to
determine if boiler is full of water, if not full of water, check for system leaks and check water pressure regulator. Repair any system leaks. Adjust or replace water pressure reducing valve.
5. Fuel input rate too low. 5. Check the maximum fuel input firing rate.
C. FUMES AND GAS ODORS
1. Leaks in gas piping or accessories. 1. Locate leaks and repair.
2. Gas leaks in service line or meter connections. 2. Close service supply valve - shut down boiler
3. Condensation trap is not full of water. 3. Check and fill with water.
4. Venting system is physically damaged. 4. Check carefully and repair. Also, see “Venting
5. Over - firing or poor combustion. 5. Check the maximum fuel input firing rate and
Refer to page 36 for the procedure.
and notify utility.
System Regular Inspection”.
combustion. Refer to page 36 for procedure.
Page 43
Lynx Model LX-85
SCREWS
VENTURI
GAS PIPE
PROPANE ORIFICE
RUBBER GROMMET
DISCONNECT GAS PIPE
GAS VALVE
Figure 27. Propane orifice installation.
VENTURI GASKET
COMBUSTION BLOWER
GAS VALVE CABLE
SCREW
DISCONNECT GAS VALVE CABLE
43
WARNING:
Only a trained, experienced Service
Technician or Installer should per-
form the conversion procedure.
CONVERTING TO PROPANE
A conversion kit, complete with the appropriate orifice disk and conversion label, is available for performing this procedure. Refer to the Lynx model LX-85’s boiler’s parts list publication LX-10PL for the kit part number. This conversion kit can only be used for the LX-85 boiler. The following procedure for perform­ing the conversion to Propane is intended for a Lynx boiler that is not yet installed. If the boiler is already installed, be sure to turn the gas and power supply off, before proceeding. Once the boiler is installed, the combustion should be checked, as per the instructions and specifications on page 36. The fuel input rate for Propane will be approximately as specified on page 2, when the supply pressure is in the range of 10” to 14” w.c.
1. Remove the boiler jacket top panel, by removing the 2 screws near the back and lifting as the top panel is slid toward the back. Remove the boiler jacket front panel, by pulling forward from the top, and lifting off the pivots at the bottom. (See Figure 26a).
2. Lift the control panel up over the jacketing by removing the 2 screws in front, and folding at the hinge while lifting upward from the bottom. Position the notches in the side brackets onto the jacket side panel pivots, to secure in place. (See Figure 26b).
3. Remove the heat exchanger enclosure front cover, by unlatching the 2 top corners and lifting as the cover is pulled forward from the top. (See Figure 26c).
4. Remove the gas valve cable, by turning the single screws on the plug end counter-clockwise until free. (See Figure 27).
5. Disconnect the gas valve supply pipe, by turning the nut at the valve inlet counter-clockwise until free. (See Figure 27).
6. Remove the 2 Torx or Phillips screws securing the venturi to the blower.
7. Remove the venturi/gas valve assembly, taking note of
the position of the gasket behind the venturi, for reassembly purposes.
8. Remove the 3 Torx or Phillips screws securing the gas valve to the venturi. (See Figure 27).
9. Remove the black rubber grommet from the gas valve, by where the venturi was attached.
10. Place the Propane orifice disk into the black rubber grommet, confirm the stamp on the orifice disk matches the number specified on page 2 of this manual for the boiler model being converted.
11. Replace the black rubber grommet, with the Propane orifice disk, into the gas valve pocket from which it was removed.
12. Reassemble the venturi to the gas valve, being careful that the grommet and orifice disk are kept in the proper positions until the screws are secured.
13. Reinstall and tighten the 2 Torx or Phillips screws that secure the venturi/gas valve assembly to the blower.
14. Re-connect the gas valve supply pipe, by aligning properly with the rubber gasket in place, and turning the nut at the valve inlet clockwise until tight.
15. Replace the gas valve cable and secure with the single screws.
16. Affix the Propane conversion label next to the boiler rating plate.
17. If the boiler is in the process of being installed, it is best to check the combustion and make any necessary adjustments before replacing the heat exchanger cover and jacket panels. See page 36 of this manual. If the boiler installation is to occur at a future time, the heat exchanger cover and jacket panels can now be rein­stalled, and the combustion check should be performed after the boiler is installed.
Page 44
©Slant/Fin Corp. 2007.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...