Care and Maintenance .............................................................41
General Troubleshooting Guide ................................................42
Conversion to Propane.............................................................43
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
INSTALLATION INSTRUCTIONS
Installation location ONLY as permitted in paragraph
entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE
GAS-FIRED BOILER LOCATION" on page 4 of this
instruction book.
The above warning does not apply to NATURAL
gas fired boilers.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1-latest edition. The installation must also
conform to the additional requirements in this Slant/Fin
Instruction Book.
In addition where required by the authority having jurisdiction, the installation must conform to American
Society of Mechanical Engineers Safety Code for
Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-1.
IMPORTANT
BEFORE READING THE
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
WARNING
The venting system of this boiler is under positive pressure. Leakage from this system can be hazardous and if
not avoided can result in death or serious injury. In addition to the recommendations within this manual and the
User’s Information Manua
flue collector to the outdoor discharge, must be carefully
checked annually by a qualified service agency.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 1008Part No. 84-5736 Publication No. LX-40 Rev. C
l, the venting system, from the
WARNING
This boiler, gas piping and accessories must be
installed, connected, serviced and repaired by a
trained, experienced service technician, familiar with all
precautions required for gas-fired equipment and
licensed or otherwise qualified, in compliance with the
authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
Page 2
2
Lynx Model LX-85
RATINGS AND DIMENSIONS
WATER INLET (RETURN) - 1" NPT (MALE)
WATER OUTLET (SUPPLY) - 1" NPT (MALE)
5 3/8
2 1/2
23
17 3/4
REAR VIEW
Figure 1. Dimensions data
2 5/8
36 3/4
6 7/8
1 1/2
3 3/8
27 7/8
16 1/47
23 3/4
SIDE VIEW
VENT CONNECTION
AIR INTAKE
CONNECTION
12 3/8
33 7/8
GAS SHUTOFF
VALVE
1/2" NPT
(FEMALE)
4 3/4
8 5/8
41
23 5/8
FRONT VIEW
SPECIFICATIONS FOR LX-85 BOILER
Fuel Rate Input:85,000 BTUH maximum
25,000 BTUH minimum
Boiler Water Volume:.75 gallon (6.25 lbs)
Water Piping Connections: 1" NPT (male)
Gas Piping Connection:1/2" NPT (female)
Vent Connection:3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Air Intake Connection:3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Weight of Boiler (uncrated): 105 lbs.
Gas orifice size:Natural Gas - No orifice used *
Propane - 0.190" diameter **, ID Code: C
*Note: No orifice changes are required for high altitude installations.
**See page 43 for conversion procedure to propane.
Figure 2. Lynx Boiler
Page 3
Lynx Model LX-85
FIELD WIRING ENTRANCES
FIELD WIRING TERMINALS
LOCATION AND IDENTIFICATION OF PARTS
SPARK ELECTRODE
(IGNITOR)
WINDOW
(SIGHT GLASS)
GAS VALVE
FLUE SENSOR
WATER OUTLET
(SUPPLY)
3
AIR INTAKE CONNECTION
GAS SUPPLY VALVE
TEMPERATURE DISPLAY
MODE DISPLAY
POWER SWITCH
PRESSURE GAUGE
TOP (EXTERIOR)
VENT CONNECTION
VENTURI
HEAT EXCHANGER
FLUE COLLECTOR
WATER INLET
(RETURN)
COMBUSTION
BLOWER
BOILER DRAIN
VALVE
FRONT (INTERIOR)
FLUE SAMPLE PORT
BOILER CONTROL
SEDIMENT TRAP
WATER
COMBUSTION BLOWER
HEAT EXCHANGER
ENCLOSURE
FRONT COVER
CONDENSATE TRAP
RIGHT SIDE (INTERIOR)
SUPPLY SENSOR
WATER HIGH LIMIT
WATER
RETURN SENSOR
CONDENSATE
DRAIN TEE
Figure 3. Location and identification of par ts
Page 4
4
Lynx Model LX-85
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1latest edition.
This installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
NATURAL GAS-FIRED BOILER LOCATION
Provide a level, solid foundation for the boiler. Location
should be as near as possible to chimney or outside wall so
that the flue pipe from boiler is short and direct. (See Appendix A for vent terminal location restrictions.) The
location should also be such that all boiler components are
protected from water (dripping, spraying, rain, etc.) during
appliance operation and service (circulator replacement,
control replacement, etc.).
REQUIRES SPECIAL ATTENTION
Liquefied Petroleum (L.P.) propane gas is heavier than air.
Therefore, propane boilers, piping, valves should NOT be
installed in locations where propane leaking from defective
equipment and piping will "pool" in a basement or other
space below the leak.
A spark or flame from the boiler or other source may ignite
the accumulated propane gas causing an explosion or fire.
Provide a level, solid foundation for the boiler. Location
should be as near the chimney as possible so that the flue
pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE ma y be in effect in
your geographic area.
The following precautions are cited by the 1994 UNIFORM
MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-burning
appliances shall not be installed in a pit, basement or
similar location where heavier-than-air-gas might collect.
Appliances so fueled shall not be installed in an abovegrade under-floor space or basement unless such location is provided with an approved means for removal of
unburned gas."
Consult Chapter 5 of the 1994 UNIFORM MECHANICAL
CODE for design criteria of the "approved" means for
removal of unburned gas.
MINIMUM CLEARANCES FROM COMBUSTIBLE
CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler
shall be as follows:
MINIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended
Surface
Front 6"18"
Rear 0"0"
Left Side0"5"
Right Side 0"5"
Top 5"18"
Flue Connector:
Enclosed —2"6"
Uninclosed —1"6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clearances in order to maintain the minimum clearances of
others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling,
the clearance at the opening through the finished floor boards or wall
or ceiling boards may be not less than 1/2 inch. Each such opening
shall be covered with a plate of uncombustible material.
Constructionfor Service
1"*
5"
6"
BOILER FOUNDATION
A. Provide a solid, level foundation capable of supporting
the weight of the boiler filled with water, and extending at
least 2" past the jacket on all sides. See dimensions of
boilers, page 2.
B. Boiler can be installed on both combustible and
non-combustible floors, but must NOT be installed on or
above carpeting.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or
the National Board of Fire Underwriters for specific
requirements.
* 2" FOR ENCLOSED
Figure 4. Lynx boiler min. clearances for combustible
construction.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.
Page 5
Lynx Model LX-85
5
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contamination
sources, whether the combustion air comes from the interior or exterior of
the building. Contaminated air can cause corrosion or other damage to the
heat exchanger and components of the boiler, causing failure of these
parts or unsafe operation.
Below is a list of products and areas which may cause
contaminated combustion air:
PRODUCTS TO AVOID
•Spray cans containing chloro/fluorocarbons
•Permanent wave solutions
•Chlorinated waxes/cleaners
•Chlorine-based swimming pool chemicals
•Calcium chloride used for thawing
•Sodium chloride used for water softening
•Refrigerant leaks
•Paint or varnish removers
•Hydrochloric acid/muriatic acid
•Cements and glues
•Antistatic fabric softeners used in clothes dryers
•Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
•Adhesives used to fasten building products and other
similar products
AREAS LIKELY TO HAVE CONTAMINANTS
•Dry cleaning/laundry areas and establishments
•Swimming pools
•Metal fabrication plants
•Beauty shops
•Refrigeration repair shops
•Photo processing plants
•Auto body shops
•Plastic manufacturing plants
•Furniture refinishing areas and establishments
•New building construction
•Remodeling areas
•Garages with workshops
VENTING APPLICATION
The Lynx LX-85 is a sealed combustion type boiler, it may be installed
and vented either as a direct vent boiler which all air for combustion is
obtained directly from outside or as a non-direct vent boiler which air for
combustion is taken from inside the boiler room.
The Lynx LX-85 boiler must be vented by 3" diameter PVC/CPVC schedule 40 pipe, or the proper 3” diameter
stainless steel venting system (see “vent material” on page 6) through the
roof or sidewall. An optional adapter is available for connecting stainless
steel venting to the boiler vent outlet.
See the Lynx LX-85 Parts List, publication # LX-10PL.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventilation. When
buildings are insulated, caulked and weather-stripped, now or later on,
direct openings to outside may be required and should be provided. If the
boiler is not near an outside wall, air may be ducted to it from outside wall
openings.
Provisions for combustion and ventilation air must be made in accordance
with section 5.3, Air for Combustion and Ventilation, of the National Fuel
Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local
building codes. The following recommendation applies to buildings of
energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWOUNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER
ROOM.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH
OF MASSACHUSETTS
When the Lynx-85 is installed and used in the Commonwealth of Massachusetts, the following additional
code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued
when a gas conversion burner is installed, and shall be equipped with a
manual reset device that will automatically shut off gas to the burner in the
event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in
every dwelling, building or structure used in whole or part for residential
purposes, including those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less than seven (7) feet
above finsihed grade in the area of the venting, including but not limited to
decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time
of installation of the side wall horizontal vented fueled equipment, the
installing plumber or gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-up is installed on the
floor level where the gas equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed professionals
for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment
is installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back up may be installed on the next adjacent floor level.
b. In th event that the requirements of this subdivision can not be met at
the time of completion of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon
monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall
read, in print size no less that one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTR UCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless,
upon inspection, the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not
Required TO Be Vented” in the most current edition of NFPA 54 as
adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building or
structure used in whole or part for residential purposes.
requirements pursuant to Massachusetts
Page 6
6
Lynx Model LX-85
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through
an outside wall; one louvered opening near the floor and
one louvered opening near the ceiling, each opening with a
minimum FREE air passage area of 1 square inch per 4000Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one
opening near the floor and one opening near the ceiling, each
opening with a minimum FREE air passage area of 1 squareinch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICALLY from outdoors; one opening at the
floor and one opening at the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near the
floor and one opening near the ceiling, each opening with a
minimum FREE air passage area of 1 square inch per 1000Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL
BURNING EQUIPMENT, THE AREA OF FREE OPENINGS
MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE
THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of
the boiler controls and boiler room. Openings for passage of air
into the boiler room for direct-vent installation must be at least
1
⁄2 of
the openings required for the non-direct vent as
mentioned above.
If additional non-direct vent appliances are installed in the same
space and adequate air openings are provided for them, there are
no additional air openings required for the Lynx LX-85.
For both direct and non-direct installation, the following must be
considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be
locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be
used in or near the boiler area.
- Boiler area must never be under negative pressure. The
flow of combustion and ventilating air to the boiler must
not be obstructed.
VENT AND AIR INTAKE MATERIALS
The vent piping for direct or non-direct vent installation must be
3” diameter PVC/CPVC schedule 40 pipe, or UL listed single
wall 3” diameter AL29-4C* stainless steel material. The air
intake piping for direct vent installation must be 3" diameter
PVC/CPVC schedule 40 pipe. The following manufacturers’
systems are approved for use within a specified minimum and
maximum equivalent vent length in this manual.
Manufacturer
Heat-Fab. Inc.Saf-T VentNot Required
ProTech System,FasNSealNot Required
Inc.
Flex-LStaR-34GE-IS806
International, Inc.
Z-Flex, Inc.Z-VentGE, RTV 106
N/APVC pipe,PVC primer
N/ACPVC pipe,CPVC primer
*AL29-4C is a registered Trademark of Allegheny Ludlum Corp
Type/System
EZ Seal
Schedule 40and cement
Schedule 40and cement
Sealant
When joining the various components of the listed stainless
steel vent systems, the manufacturers’ instructions should be
closely followed to insure proper sealing. Use sealant specified
by vent system manufacturer for sealing of pipe and fittings, if
required. When joining the PVC/CPVC pipe and fittings, follow
the instructions provided in this manual. All connections must be
liquid and pressure tight. DO NOT use galvanized flue pipe or
any plastic-type materials other than PVC/CPVC Schedule 40.
The vent and air intake connections on the boiler are designed to
accommodate either PVC/CPVC Schedule 40 pipe or the listed
stainless steel vent systems (by inserting the optional adapter
specified in the Lynx LX-85 Parts List, publication # LX-10PL, for
stainless steel venting). Built-in sealing rings are provided, so no
additional sealant is required. The application of liquid soap to the
outer end of the vent pipe (or adapter, if used) will aid in installing
it. Make sure the pipes are round and burr-free, and push down
into the appropriate step of the connector or adapter, until snug.
(See Figure 5).
FLUE GAS VENTING REQUIREMENTS
The Lynx LX-85 series boiler is a high efficiency, mechanically
forced draft boiler and, therefore, requires different venting
arrangements than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY
READ AND FOLLOWED IN ORDER TO AVOID ANY HAZARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION
OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these
instructions and with ANSI Z223.1-latest edition NATIONAL FUEL
GAS CODE, Part 7, Venting of Equipment. Other local codes may
also apply and must be followed. Where there is a conflict
between these requirements, the more stringent case shall apply.
The use of a vent damper is NOT permitted on this boiler series.
AIR INTAKE PIPE
(PVC OR CPVC)
VENT PIPE
(PVC OR CPVC)
CHECK EDGE
FOR BURRS
FLUE AND AIR INTAKE
CONNECTOR
Figure 5. Vent and Air Intake Pipe installation into Boiler
vent and air intake connections.
Page 7
Lynx Model LX-85
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting,
cleaning and connecting PVC and CPVC pipe, for both the
vent and air intake piping system:
1. When laying out the piping system, work from the boiler
vent and air intake adapter to the point of outside
termination.
2. Cut the PVC/CPVC pipe to the required lengths, and
pre-assemble the entire system, before sealing.
Disassembly after sealing, to make any corrections, will not
be possible.
3. Once the pre-assembled PVC/CPVC pipe vent and air
intake system is verified to be of the proper length pipe and
fitting orientation, begin disassembling and preparing the
pipes and fittings for the sealing process. This can be done
section by section, or the complete vent and air intake
system can be disassembled. It is recommended to mark
the various parts, before complete disassembly, to
eliminate the possibility of errors during re-assembly.
4. De-burr the inside and outside of every PVC/CPVC pipe, to
ensure that they engage fully into the fittings, and flow is
not compromised. A small chamfer on the outside of each
pipe can particularly aid in the final assembly process.
5. Wipe or knock out any debris from inside the PVC or
CPVC pipe, which may have accumulated there from the
cutting process or storage. Debris can cause operational
problems with the boiler combustion components.
6. Thoroughly clean the outside ends of each pipe, and the
inside of each fitting. The surfaces must be dry for the
sealing agents to work properly. Handle the prepared pipe
lengths away from the cleaned ends, and handle the
cleaned fittings, from the outside, to avoid contamination.
7. Re-assembly of the PVC or CPVC pipe should be done in
sections, to avoid the primer and cement drying before the
parts are engaged.
8. For each joint, first apply a coat of primer to the outside
sealing surface of the pipe and the inside sealing surface of
each fitting. Use only the primer type that is specified for
either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A
second coat of cement can be applied, if necessary, but
must be done quickly and in a manner that avoids
unnecessary build-up that would cause obstruction inside
the system. Use only the cement type that is specified for
either the PVC or CPVC pipe that is being utilized.
10. Before the cement dries, insert the pipe into the fitting. A
slight twisting motion while pushing the pipe into the fitting
will aid in distributing the cement evenly and ensuring the
parts fully engage.
11. Quickly wipe the excess cement from the outside areas of
the joint. Discard any rags used to avoid later getting the
cement on hands, clothes and equipment.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100
equivalent feet.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows as
shown in the table on this page.
7
Figure 6.
3. The vent termination is in addition to the allowed
equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one
90˚ elbow that is required.
5. Vent length restriction is for both direct and non-direct
vent installations.
EXAMPLE: Boiler model LX-85 is to be installed. The
combustion air is provided by air intake piping directly to the
boiler (direct-vent installation). The vent piping will be PVC
and installation location will require the use of 4 elbows for
the vent to run the termination. The air intake piping will also
be PVC, and also will require the use of 4 elbows.
In this case, the maximum straight pipe vent length that can
be utilized with the 4 elbows would be: 100’ - (4’ x 5’) = 80’.
Since the air intake pipe also is PVC and requires the use of
4 elbows, the maximum straight pipe air intake length that
can be utilized is also 80 feet.
If the air for combustion were taken from the boiler room
(non-direct vent installation), still the maximum straight vent
length would be 80 feet.
Flex-L International, Inc. StaR-346
Z-Flex, Inc.Z-Vent6
N/APVC, Schedule 405
N/ACPVC, Schedule 405
Type/System
elbow
Equivalent
Length (Feet)
Page 8
8
Lynx Model LX-85
6. The LX-85 boiler is equipped with a built-in condensation
drain and trap. The trap must be filled with water. DO NOT
operate the boiler without filling the trap with water to
prevent flue gas discharge into space. The drain must
dispose of possibly large quantities of condensate, which
may require a neutralizing system. Refer to the “Condensate
Drainage” section of this manual. No additional condensation drain and trap is required on the vent piping system
itself.
7. The horizontal vent pipe must be sloped upward from the
boiler at a pitch of at least 1/4” per 1 foot of run, so that
the condensate from the vent system runs to the boiler
vent adapter pipe, then out the built-in condensation drain
and trap.
8. The horizontal vent and air intake pipes must be supported
with pipe straps, at intervals no greater than 5 feet, when
PVC/CPVC pipe is utilized. This support spacing applies
also to stainless steel vent pipe, unless the manufacturer’s
instructions permit otherwise. The vertical vent and air
intake pipes also must be supported, wherever the building
construction provides allowance for it, such as ceiling or
roof passage openings where a firestop and support or
braces can be affixed.
9. Minimum clearances of vent pipes from combustible
constructions must be maintained (see Page 4). No
clearance is required between the vent and air intake pipes
of this boiler.
10. Common venting with other appliances or another Lynx
boiler is not allowed.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above
any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 4 feet below,
4 feet horizontally from, or 1 foot above any door, window
or gravity air inlet into any building. The bottom of the vent
terminal or air intake terminal shall be at least 12 inches
above grade or the normal snow level whichever is
greater.
3. Through the wall vents shall not terminate over public
walkways or over areas where condensate or vapor could
create a nuisance or hazard or could be detrimental to
the operation of regulators, relief valves or other equipment. Minimum clearance of 4 feet horizontal distance is
maintained, from electric meters, gas meters, regulators
and relief equipment.
4. Vent termination must not be located in any confined
space (i.e. window wells, alcoves, narrow alleys) or under
any overhang or deck. Vent termination should not allow
flue gas discharge towards neighbor’s windows or where
personal injury or property damages can occur.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 9 shows typical venting through the roof. The vent pipe
must pass through the ceiling, floor and the roof vertically
through a 6" minimum diameter cutout. A fire stop is required
for each ceiling and floor penetration. For roof passage, an
appropriate UL listed roof flashing must be used.
11. DO NOT install a vent damper or similar devices in vent
system or on the boiler.
12. DO NOT insulate venting system.
VENTING INSTALLATION
Only the approved PVC/CPVC and stainless steel materials
listed on page 6 may be used for the venting system installation. If stainless steel vent systems are used, follow the manufacturer’s instructions, in conjunction with these instructions.
I. NON-DIRECT VENT INSTALLATION
The air for combustion is taken from the ambient air
surrounding the boiler; therefore, ample supply of air is required
for combustion and ventilation (see page 6.)
DO NOT use this installation method if the surrounding of the
boiler is contaminated. See page 5 for the list of harmful
contaminants and their sources, to avoid.
A. NON-DIRECT VENT SIDEWALL VENTING
Figures 7 and 8 show typical horizontal sidewall venting. For
combustible wall passage of vent piping, a UL listed thimble
or flashing and sealing boot must be used, providing the wall
thickness from 3" minimum up to 12" maximum. The vent
piping must terminate with a screened tee or elbow termination
facing down.
CAUTION: Flue gasses exiting from the vent terminal will
condense. Building materials in the area of the vent terminal
should be protected from discoloration and degradation.
An existing chimney (see Figure 10) may be used as a chase
for vertical venting. Other appliances CANNOT be vented into
the same chimney or vent pipe with in the chimney.
The vertical vent piping must terminate with a screened tee,
combination of 45˚ elbow and a 90˚ screened elbow termination or a rain cap termination.
II. DIRECT VENT INSTALLATION
Air intake piping from outside to the boiler air intake connector
provides the air for combustion. The boiler surrounding may be
contaminated (See page 5). Piping the air intake to the outside
can prevent contaminants from the boiler surrounding from
entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 11 and 12 show typical sidewall direct venting, using a
Slant/Fin vent/air intake termination. There are 2 different models of vent/air intake termination available. One is designed
specifically for PVC/CPVC venting, and the other is designed
specifically for stainless steel venting systems. Only these 2
models of vent/air intake termination are approved for this
method of installation. Refer to the Slant/Fin Lynx LX-85 Parts
List (publication number LX-10PL) for the appropriate model for
the vent material to be used.
CAUTION: Flue gasses existing from the vent terminal will condense. Building materials in the area of the terminal should be
protected from discoloration and degradation, in addition to the
requirements of the vent termination location and clearances
stated in this manual.
Page 9
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
9
AL29-4C S.S.*. venting materials (See page 6).
90˚ ELBOW
AIR INTAKE
(DO NOT BL0CK)
SLOPE UP 1/4 IN.
PER FOOT MIN.
FROM BOILER TO
VENT TERMINATION
3 IN. DIA.
PVC/CVPC
PIPE FOR
VENT
6" MIN.
9" MAX.
TERMINATION 90˚ ELBOW
WITH SCREEN
A U/L LISTED FLASHING
AND SEALING BOOT MUST
BE USED ON COMBUS TIBLE
WALLS.
OUTSIDE WALL
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe f or venting.
6" MIN.
9" MAX.
OUTSIDE VENT TERMINATION
ELBOW WITH SCREEN
A U/L LISTED WALL THIMBLE
MUST BE USED ON COMBUSTIBLE
WALLS. S/F P/N 440695
(ADJUSTABLE 5 IN. TO 8 IN.)
MAY BE USED. ABOVE THIMBLE
MUST BE USED WITH HEAT-FAB
SLIP JOINT CONNECTOR
STANDARD
90
?
ELBOW
AIR INTAKE
(DO NOT BL0CK)
SLOPE UP 1/4 IN.
PER FOOT MIN.
FROM BOILER TO
VENT TERMINATION
3 INCH. DIA.
STAINLESS
STEEL VENTING
MATERIAL FOR
VENT
ADAPTOR
SNOW LINE
(SEE DEFINITION)
12" MIN
12" MIN
S/F P/N 440695 (ADJUSTABLE
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
OUTSIDE WALL
SNOW LINE
(SEE DEFINITION)
Page 10
10
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
90° TERMINATION
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
ELBOW WITH SCREEN
RAIN CAP TERMINATION MAY BE USED
*
FIRESTOP AND
SUPPORT
90° ELBOW
AIR INTAKE
(DO NOT BLOCK)
SLOPE UP 1/4 IN.
PER FOOT MIN.
10 FT MIN.
VENT TERMINATION
TEE WITH SCREEN
1 FT MIN.
FLASHING AND
STORM COLLAR
NIM "2
2" MIN
3 IN. DIA. PVC/CPVC
PIPE OR STAINLESS STEEL
VENTING MATERIAL FOR VENT
FIRESTOP AND
SUPPORT
96044 N/P F/S
ELBATSUJDA( 5
Figure 9. Lynx model LX-85 - non-direct vent, venting through the roof
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
USE ADAPTOR IF
STAINLESS STEEL
IS USED
3 IN. DIA. PVC/CPVC
PIPE OR STAINLESS STEEL
VENTING MATERI AL FOR VENT
Page 11
Lynx Model LX-85
LYNX MODEL LX-85 NON - DIRECT VENT, UTILIZING AN EXISTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
*
CHIMNEY AS A CHASE
AL29-4C S.S.*. venting materials (See page 6).
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
RAIN CAP TERMINATION MAY BE USED
10 FT MIN.
CHIMNEY
TOP PLATE
90° TERMINATION
ELBOW WITH SCREEN
VENT TERMINATION
TEE WITH SCREEN
1 FT MIN.
11
SLOPE UP 1/4 IN.
PER FOOT MIN.
90° ELBOW
AIR INTAKE
(DO NOT BLOCK)
SEAL CHIMNEY OPENING
WITH MORTAR OR COVER PLATE
USE ADAPTOR IF
STAINLESS STEEL
IS USED
(
ELBATSUJ
596044 N/P F/S
DA
Figure 10. Lynx model LX-85 - non-direct vent, utilizing an existing chimney as a chase.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
3 INCH DIA. PVC/CPVC
PIPE OR STAINLESS STEEL
VENTING MATERIAL FOR
VENT
3 INCH DIA. PVC/CPVC
PIPE OR ST AINLESS STEEL
VENTING MATERIAL FOR
VENT
Page 12
12
Lynx Model LX-85
LYNX MODEL LX-85 - DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
3 - 16" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA PVC/CPVC PIPE FOR VENT
SLANT/FIN VENT/AIR INTAKE
TERMINATION KIT PART # 84 0802 000
12" MIN
AIR INTAKE LOUVERS
3" DIA PVC/CPVC COUPLING WTH SCREEN
SNOW LINE **
(SEE DEFINITION)
OUTSIDE WALL
Figure 11. Direct vent, sidewall venting illustration; utilizing PVC/CPVC pipe for venting
3 - 12" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA STAINLESS STEEL
PIPE FOR VENT
ADAPTOR
SLANT/FIN VENT/AIR INTAKE
TERMINATION KIT PART # 84 0804 000
12" MIN
AIR INTAKE LOUVERS
3" DIA STRAIGHT SCREENED VENT TERMINATION
SNOW LINE **
(SEE DEFINITION)
OUTSIDE WALL
Figure 12. Direct vent, sidewall venting illustration; utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
Page 13
Lynx Model LX-85
13
3" DIA PVC/CPVC PIPE FOR VENT
OUTSIDE TERMINATION PLATE
3" DIA PVC/CPVC COUPLING WITH SCREEN
INSIDE TERMINATION PLATE
3" DIA PVC/CPVC
PIPE FOR AIR INTAKE
SCREW
WALL
(3"-16" THICK)
3" DIA PVC/CPVC
PIPE FOR VENT
SCREW
STOP FOR AIR/VE NT
OUTSIDE TERMINAL
Figure 13a. Vent/Air intake termination; utilizing PVC/CPVC pipe for venting.
4" GALV. PIPE
(WALL THIMBLE - FOR
COMBUTIBLE WALLS
ONLY)
3" DIA AL29-4C S.S. VENT PIPE (SLIP JOINT CONNECTOR )
VENT/AIR INTAKE TERMINATION FOR PVC/CPVC
VENTING INSTALLATION
This termination is designed specifically for 3” diameter PVC or
CPVC Schedule 40 pipe to be used as the vent and air intake
piping material, only. It can be used on a combustible wall,
provided the 1” minimum clearance of the vent pipe to any
combustible surface is maintained.
1. Termination must be installed horizontally.
2. Refer to Figure 13a for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and
clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in
the wall.
Height: 5
Width: 12
1
⁄4”
3
⁄4”
6. From outside of the wall, install outside termination plate
using 4 screws. Make sure the louvers are at right side.
Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the out
side termination plate air intake collar, about 1/2” from the
edge. This will seal the air intake pipe to the air intake
collar, in step #9.
8. From inside, install the inside termination plate, using 4
screws. Make sure that the holes for the vent and air intake
pipe visually line up with the vent passage hole and air
intake collar on the outside termination plate.
9. Cut the PVC or CPVC air intake pipe to the proper
dimension to fit onto the air intake collar of the terminal.
Slide the air intake pipe through the inside termination
plate and onto the air intake collar, where the sealant was
pre-applied in Step #7.
10. Cut the PVC or CPVC vent pipe so that it will extend out
at least 2" from the outside termination plate and 2" from
inside termination plate.
11. Cement a 3” diameter PVC or CPVC coupling onto the
PVC or CPVC vent pipe, and install the stainless steel
screen (supplied with the boiler) into the coupling.
VENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL
VENTING INSTALLATION
This termination is designed specifically for the 3” diameter
stainless steel venting systems approved to be used as the
vent, and 3” diameter PVC or CPVC schedule 40 pipe to be
used as the air intake piping material, only. It can be used on a
combustible wall, provided a length of 4” diameter galvanized
pipe is installed as a thimble around the vent pipe, for the wall
passage.
1. Termination must be installed horizontally.
2. Refer to Figure 13b for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and
clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in
the wall.
Height: 5
Width: 12
1
⁄4”
3
⁄4”
6. From outside of the wall, install outside termination plate
using 4 screws. Make sure the louvers are at right side.
Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the
outside termination plate air intake collar, about 1/2” from
the edge. This will seal the air intake pipe to the air intake
collar, in step #11.
8. For combustible wall a 4” galvanized pipe must be used as
a wall thimble.The length of the 4” galvanized pipe should
be approximately 1” shorter than the wall thickness.
9. From inside the building, fit galvanized pipe over 4” collar of
the outside plate.
10. From inside, install inside termination plate using 4 screws.
Make sure the 4” collar on the plate, penetrated into the
galvanized pipe.
11. Cut the PVC or CPVC air intake pipe to the proper
dimension to fit onto the air intake collar of the terminal.
Slide the air intake pipe through the inside termination
plate and onto the air intake collar, where the sealant was
pre-applied in Step #7.
12. From outside the wall, insert the bare end of the PVC or
CPVC vent pipe through the outside and inside terminal
plates, until the coupling is flush with the outside wall plate.
13. From inside, proceed with the air intake and vent pipe
installation. Follow the proper PVC/CPVC assembly
practices specified on page 7 and venting system
restrictions specified on page 7 of this manual.
12. Assemble and seal straight screened termination to the slip
joint connector.
13. From outside of the building, insert vent pipe (slip joint
connector and termination assembly) through the 3” holes
of the outside and inside termination plate.
14. From inside, proceed with air intake and vent pipe
installation. Follow vent manufacturer’s instructions and
restrictions specified on page 7 of this manual.
Page 15
Lynx Model LX-85
15
B. DIRECT VENT - VENTING AND AIR INTAKE
THROUGH A ROOF
Figure 14 shows typical vertical venting. The vent pipe must
pass through the ceiling, floor and the roof vertically through a
6” minimum diameter cutout. A fire stop is required for each
ceiling and floor penetration. For roof passage an appropriate
UL listed roof flashing must be used.
The vertical vent piping must terminate with a screened
straight termination. The air intake termination should be a
screened 180˚ elbow facing down. The air intake opening must
be at least 1 foot below the vent opening.
LYNX MODEL LX-85 - DIRECT VENT, VENTING AND AIR INTAKE
THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
FLASHING AND
STORM COLLAR
AIR INTAKE
180° ELBOW
WITH SCREEN
For PVC/CPVC pipe, follow the proper assembly practices
specified on page 7, and venting system restrictions specified
on page 7 of this manual. For stainless steel venting systems,
follow the vent manufacturer’s instructions and the restrictions
specified on page 7 of this manual
STRAIGHT TERMINATION
10 FT MIN.
WITH SCREEN
1 FT MIN.
1 FT MIN.
O
N
S
E
N
I
L
W
SUPPORT
FIRESTOP AND
SUPPORT
PIPE
3" DIA. PVC/CPVC
PIPE FOR AIR INTAKE
2" MIN
FIRESTOP AND
SUPPORT
SLOPE UP 1/4 IN.
PER FOOT MIN.
3" DIA. PVC/CPVC
OR STAINLESS
STEEL VENTING
MATERIAL FOR
VENT
USE ADAPTOR IF
STAINLESS STEEL
IS USED
Figure 14. Direct vent, venting and air intake through a roof.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
Page 16
16
Lynx Model LX-85
VENTING AND AIR INTAKE SYSTEM REGULAR
INSPECTION
A. Inspect the system regularly for condensation, corrosion,
sagging and/or physical damage. A qualified professional
should service the boiler annually and include such an
inspection at that time. The homeowner should look over the
system monthly for damage, water stains, any signs of rust,
other corrosions or separation of the vent and air intake piping
(if direct-vent).
B. Should an inspection turn up signs of condensation,
corrosion, sagging or damage, the boiler should be shut down
immediately and the condition should be corrected by a
qualified professional.
CONDENSATE REMOVAL SYSTEM
The Lynx LX-85 is equipped with a built-in condensation drain
and trap. The trap must be filled with water. DO NOT operate the
boiler without filling the trap with water to prevent flue gas
discharge into space. If the trap is disassembled for inspection, it
must be reassembled and filled with water as before.
A 3/4” PVC tee, located on the left rear of the boiler jacket, is provided to run the condensate liquid from the boiler. Connect the
plastic tubing that will be run to the drain to the bottom take-off of
the tee. Leave the top take-off of the tee open, to act as a vacuum breaker. If the building drain is above the bottom portion of
the tee, a condensate removal pump will be required. This pump
must have an overflow switch, and be compatible with the acidic
condensate liquid, as must all fittings and the tubing used in this
condensate removal system. (See Figure 15).
No part of the condensate removal system can be exposed to
freezing temperatures, or any other conditions that could cause
blockage. DO NOT run drain tubing to the outside of the building.
In addition, certain jurisdictions or drain pipe materials may
require a neutralization unit to be installed in the condensate
removal system. Any piping other than plastic types will be
subject to corrosion or deterioration from the acidic condensate, which may have a pH level as low as 3.0. A condensate
filter containing lime, marble, or phosphate chips can neutralize
the condensate to a pH level above 6.5, which is safe for all
drain piping materials. (See Figure 15). The neutralizing filter
medium will require periodic changing, to ensure it’s affectiveness. Replacing the medium on an annual basis is recommended, or refer to the manufacturer’s instructions for systems
that are available for neutralizing condensate.
COMMONWEALTH OF MASSACHUSETTS SPECIAL
REQUIREMENT
When the Lynx-85 is installed and used in the Commonwealth of
Massachusetts, a neutralization unit MUST be installed in the
condensate removal system.
GAS PIPING
A. Local installation codes apply. The pipe joint compound
used on threads must be resistant to the action of liquefied
petroleum gases.
B. The gas supply line to the boiler should run directly from the
meter for natural gas or from the fuel tank for L.P. propane
gas. A manual gas supply shut-off valve is provided on the
boiler’s gas supply pipe. (See Figure 3, on page 3). Local
codes may specify a manual main gas supply shut-off valve to
be 5’ above the floor, and a disconnection union at the gas
piping entrance to the boiler. In this case, unless the boiler is
wall mounted at the right height, the gas supply shut-off valve
must be relocated to the specified location. If the gas supply
pipe must be upsized for flow considerations, then the same
size main gas supply shut-off valve must be used.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter
to the installation site.
2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow
in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
EXAMPLE: Boiler model LX-85 is to be installed. Distance
from gas meter to the boilers is 30 ft. Heating value of natural
gas is 1020 Btu/cu. Ft. Select proper pipe size.
Gas flow = 85,000 Btu/hour
1020 Btu/cu. ft.
= 83 cu. ft. per hour
DRAIN VACUUM BREAKER, LEAVE OPEN
CONDENSATE TRAP, FILL WITH WATER
NEUTRALIZING UNIT (IF REQUIRED)
CONDENSATE PUMP (IF REQUIRED)
DRAIN INSIDE BUILDING
Figure 15. Condensate disposal system
PLASTIC TUBING
Page 17
Lynx Model LX-85
17
At 30 ft. length of pipe, match required capacity from table on
this page (choose higher capacity, in this case is 152 cu. ft. per
hour). Required pipe size is
3
⁄4".
Improper gas pipe sizing will result in flame outages, insufficient heat and other installation difficulties. For more information and also if other appliances are to be attached to the
piping system, see Appendix C of National Fuel Gas Code
ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested
before replacing the boiler in operation. Use liquid soap
solution for all gas leak testing. DO NOT use open flame.
This boiler and it’s individual shutoff valve must be
disconnected from the gas supply piping system during and
pressure testing of that system at test pressures in excess
1
of
⁄2 PSIG. This boiler must be isolated from the gas supply
piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system
at test pressures equal to or less than
1
⁄2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap is integrally
provided, as illustrated on page 3.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for
the type of gas used. Gas supply pressure should never be
less than minimum or more than maximum pressure when
the boiler or any other appliance is turned on or off.
At pressure drop of 0.3 in. water, specific gravity = 0.6.
ELECTRICAL WIRING
All field wiring to the boiler is connected to the 2 sets of
terminal strips, located in a junction box behind the jacket top
panel. (See Figure 3, on page 3)
DANGER: Before wiring always turn off electric power supply.
Otherwise, shock or death can result.
Boiler must be electrically grounded in accordance with the
requirements of the authority having jurisdiction, or, in the
absence of such requirements, with the National Electrical
Code, ANSI/NFPA 70-latest edition.
Proper polarity is critical for the power supply connections.
Reversed polarity will cause system lockout. Proper grounding is critical for boiler operation, connect the ground wire to
the green ground screw next to the line voltage terminal
strip.
2. Circulator(s)
A set of terminals are provided for the boiler loop circulator.
Only wire this circulator to these terminals, additional
circulators for the space heating system loop require the
use of relays and a separate power source.
For multiple zoning, either zone valves or circulators may
be used.
For zone valve system (See Figure 17a).
For pump zoning system (See Figure 17b, c, d, e).
DO NOT use boiler transformer to power external
accessories like zone valve and relays, overload and/or
burned out transformer and boiler malfunction can result.
Use separate transformer to power such components.
A second set of terminals are provided for the domestic hot
water tank circulator (if used). The boiler loop circulator is
always de-energized when the DHW tank circulator is
energized, or vice-versa, depending on the priority feature
selected.
3. SPACE HEATING THERMOSTAT(S)
Install thermostat on an inside wall and away from any heat
sources, sunshine and drafts. A set of terminals are provided for connection of 24 volt style thermostats, relays or zone
valve end switches (isolated contacts). (See wiring diagrams
Figure 16a,17a, 17 b, 17c, 17d, 17e).
Thermostat heat anticipator: For a non-zoned system set
thermostat heat anticipator to 0.1 Amps, for zoned system
set to match power requirements of zone valves or relays.
Refer to manufacturer’s instructions and specifications. Also
see instructions with thermostat.
4. DOMESTIC HOT WATER TANK THERMOSTAT
A set of terminals are provided for connection of the DHW
tank thermostat (if used). (See wiring diagram Figure 16a).
5. OUTDOOR AIR SENSOR
A set of terminals are provided for connection of an outdoor
air sensor (if this method is used). (See wiring diagram
Figure 16a).
1. Power Supply
A separately fused circuit is recommended. Use standard
15 Amp. fuse or breaker and 14 gage conductors in BX
cable or conduit.
Provide disconnect means and overload protection as
required. See boiler wiring diagram (Figure 16a) boiler
control (Figure16b) and ladder diagram (Figure 16c).
The outdoor air sensor that is supplied with the boiler is a
12k ohm type. Mount on an outside wall, shielded from
direct sunlight or flow of heat or cooling from other sources.
See instructions provided with sensor.
6. LOW WATER CUTOFF
A set of terminals are provided for connection of a LWCO. If
this device is used, remove the factory installed jumper from
these terminals. (See wiring diagram Figure 16a).
Page 18
18
Lynx Model LX-85
Figure 16a. Schematic wiring diagram.
Page 19
Lynx Model LX-85
19
Figure 16b. Boiler Control.
Figure 16c. Ladder wiring diagram.
Page 20
20
Lynx Model LX-85
ZONE 1
THERMOSTAT
V8043E/F
END
SWITCH
TT T TTT TTTTT T TT
TH-TR
MOTOR
1 2 3 4 5 6 7 8
V8043E/F
SWITCH
FIELD WIRING
TERMINALS
ON BOILER
END
TH-TR
ZONE 2
THERMOSTAT
V8043E/F
1
END
SWITCH
2
3456
MOTOR
T
R845A
RELAY
Figure 17a. Multizoning of Lynx boiler; zone valve system.
TH-TR
JUMPER
ZONE 3
THERMOSTAT
MOTOR
T
DISCONNECT
SWITCH
LI
1
120V/24V
TRANSFORMER
SPACE
HEATING
SYSTEM
T
CIRCULATOR
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
L2
DISCONNECT
SWITCH
LI
R845A
RELAY ZONE 3
1
1
2
3456
CIRC.
ZONE 3
TT
ZONE 3
THERMOSTAT
R845A
RELAY ZONE 2
23456
1
CIRC.
ZONE 2
ZONE 2
THERMOSTAT
TTTT
L2
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1 2 3 4 5 6 7 8
Figure 17b. Multizoning of Lynx boiler; pump zoning system using R845A rela y.
R845A
RELAY ZONE 1
23456
1
CIRC.
ZONE 1
FIELD WIRING
TERMINALS
ON BOILER
ZONE 1
THERMOSTAT
Page 21
Lynx Model LX-85
ZONE 3
THERMOSTAT
R882A/B
R882A/B
ZONE 2
THERMOSTAT
R882A/B
ZONE 1
THERMOSTAT
120V/24V
TRANSFORMER
DISCONNECT
SWITCH
LI
L2
120V/60HZ
21
1
CIRC.
ZONE 1
1 2 3 4 5 6 7 8
CIRC.
ZONE 3
FIELD WIRING
TERMINALS
ON BOILER
CIRC.
ZONE 2
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Figure 17c. Multizoning of Lynx boiler; pump zoning system using R882A/B rela ys.
Page 22
22
Lynx Model LX-85
THERMOSTAT
TT
R845A
RELAY
3
2
1
4
56
DISCONNECT
SWITCH
LI
1
CIRCULATOR
L2
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1 2 3 4 5 6 7 8
FIELD WIRING
TERMINALS
ON BOILER
Figure 17d. Single zoning of Lynx boiler; pump zoning system using R845A rela y.
THERMOSTAT
120 V / 24 V
TRANSFORMER
DISCONNECT
SWITCH
LI
1
R 882A/B
L2
RELAY
CIRCULATOR
1
POWER SUPPLY, PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1 2 3 4 5 6 7 8
Figure 17e. Single zoning of Lynx boiler; pump zoning system using R882A/B relay.
FIELD WIRING
TERMINALS
ON BOILER
Page 23
Lynx Model LX-85
23
WATER PIPING
1. Connection of system to boiler:
Primary/secondary piping of the system is recommended, to
ensure the proper flow through the boiler. (See Figures 20
through 22). The boiler loop piping must be the same
diameter as the water outlet (supply) and inlet (return) piping
connections provided on the boiler, particularly on longer
loops. See page 2 for piping connection size.
2. Circulator Pumps:
The boiler loop piping must utilize the Taco 0011 circulator
that is supplied with the boiler, to ensure the proper flow
through the boiler. Refer to Figure 19 for the boiler water side
pressure drop and Table 2 for the recommended pump
models for the domestic hot water system. Install the pumps
in the orientation shown in Figures 20 through 22.
3. Relief Valve(supplied with boiler):
Tee the relief valve into the boiler water outlet (supply) piping
as close to the water outlet (supply) connection as possible.
(See Figure 18). The relief valve’s discharge piping must be
the same size or larger than the relief valve’s outlet, and must
terminate 6” minimum from floor with a plain (no threads) end.
Place a bucket under pressure relief valve discharge. Make
sure discharge is always visible. DO NOT hard-pipe to drain
piping, or any place where freezing could occur. No shut-off
valve is permitted between the relief valve and boiler, or in the
discharge line.
4. Air Control System:
An appropriately sized diaphragm-type expansion tank must
be used to control the system pressure. See boiler volume
data on page 2, and the recommended location in Figures 20
through 22. An air vent is recommended to be installed on an
air separator in close proximity to the expansion tank.
5. Cold Water Fill:
A pressure reducing (fill) valve, with a shut-off valve upstream
of it, should be installed in close proximity of the expansion
tank. (See Figures 20 through 22). Use a back flow check
valve in the cold water supply as required by local codes.
6. Low Water Cutoff:
On a hot water boiler installed above radiation level, the boiler
must be provided with a low water cutoff device at the time of
installation by the installer (see Figure 18 for piping
arrangement).
7. Water Treatment and Freeze Protection:
A good water treatment program will not only extend the
useful life of this boiler but it will also save much of the time
and expense of repairs made necessary by preventable
occurrences. A reputable water treatment company should be
consulted to evaluate and determine the best overall
treatment program for your boiler equipment.
The heat exchanger is made of aluminum, so the system
water must be maintained between 7.0 and 8.5 PH level.
Thoroughly flush the system, before connecting the boiler, to
remove any sediment or glycol.
Anti-freeze is sometimes used in hydronic systems to
protect against freeze-up in the event of power failure or
boiler shut down in the cold winter. Use RhoGard
(Propylene glycol with Pro-Tek 922 inhibitor) by Rhomar
Water Management, Inc. Follow the manufacturer’s
instructions for proper application and proper mixture for
minimum ambient temperature. Any use of anti-freeze
other than that supplied b y Slant-Fin or specifically
approved and/or recommended for use by Slant-Fin
will void the warranty.
Never use any types of automotive or standard gylcol freeze
protection fluids. Never use Ethylene Glycol as it is toxic
to humans.
8. Piping a heating - cooling system to a water boiler and
chiller:
Figure 22 illustrates a method of piping a heating-cooling
system to a water boiler and a chiller. Hand valves (shown)
or automatic valves must be installed to prevent circulation
of chilled water in the boiler or hot water in the chiller.
The air control system and pressure control system must
operate with chiller only, or the boiler only, being valved to
the piping system. Separate control devices on the boiler
and chiller may be used, or a single set of air and pressure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in
air handling units, flow control valves or other devices
must be installed to prevent gravity circulation of water in
the coils during the cooling cycle.
Page 24
24
WATER OUTLET PIPING
Lynx Model LX-85
TO REST OF SYSTEM
LOW WATER CUTOFF MANIFOLD
(IF LWCO UTILIZED)
*PIPING ORIENTATION FOR REFERENCE ONLY.
Figure 18. Relief Valve and Low Water Cutoff Installation
PROBE TYPE LOW WATER CUTOFF
(IF REQUIRED)
PRESSURE RELIEF VALVE
(SUPPLIED WITH BOILER)
RELIEF VALVE DISCHARGE PIPING
3/4" NPT STREET ELBOW
1" x 1" x 3/4" TEE
WATER OUTLET (SUPPLY) PIPE 1" MIN. DIAMETER
WATER INLET (RETURN) PIPE 1" MIN. DIAMETER
Page 25
Lynx Model LX-85
25
PRESSURE DROP
10
FLOW RATEBoiler heat loss
Head
8
(feet w.c.)
6
4
2
0
LYNX LX-85
gpmFeet w.c
7.78.553
3.81.5
2.50.7500
02468
Flow Rate (GPM)
Figure 19. Boiler water side pressure drop
Flow
Rate
(gpm)
Temp
Rise
(˚F)
Boiler
Head
Loss
(Feet w.c.)
Domestic Water
Tank Piping
Head Loss **
(Feet w.c.)
7.720˚8.5’2.5’
Available Head Capability Left for Various Model
Circulators to Overcome DHW Tank Head Loss
(Feet w.c.) ***
Taco 0012Taco 0014Taco 0011
Not Recommended7.0’14.0’
5.030˚3.0’2.0’8.0’
3.8*40˚1.5’1.5’
Table 2. Recommended pump models for domestic hot water tank piping.
Notes:
*This is the minimum flow rate recommended for the model LX-85 boiler.
**Domestic water tank piping head is based on 1” inside diameter piping and full port valves.
10.0’17.0’25.0’
14.0’22.0’
***Refer to the DHW Tank Manufacturer’s water flow rate requirements and associated pressure drop head loss, to select
the appropriate circulator.
Page 26
26
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
Lynx Model LX-85
MAKE UP
WATER
SUPPLY
Figure 20. Zoning with circulators.
HOT WATER
OUTLET
DOMESTIC
HOT WATER
TANK
COLD
INLET
WATER
*PIPING ORIENTATION FOR REFERENCE ONLY
Page 27
Lynx Model LX-85
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
MAKE UP
WATER
SUPPLY
27
Figure 21. Zoning with zone valves.
HOT WATER
OUTLET
DOMESTIC
HOT WATER
TANK
*PIPING ORIENTATION FOR REFERENCE ONLY
COLD
INLET
WATER
Page 28
28
ADDITIONAL
ZONES
SPACE HEAT
ZONE #1
WATER
CHILLER
UNIT
Lynx Model LX-85
MAKE UP
WATER
SUPPLY
* PIPING ORIENTATION FOR REFERENCE ONLY
Figure 22. Piping a heating-cooling system to the boiler and a c hiller.
DOMESTIC
HOT WATER
TANK
HOT WATER
OUTLET
COLD
INLET
WATER
Page 29
Lynx Model LX-85
29
OPERATING INSTRUCTIONS
I. FILLING AND VENTING WATER SYSTEMS
A. Fill the system with water. Vent or purge of air.
B. Fire the boiler as soon as possible (see following warning
and instructions) and bring water temperature in the
system.
C. Vent air and add water as needed to achieve operating
pressure on boiler gauge. Pressure must be between
approximately 12 psi (cold water) and 25 psi at water
temperature setting of high limit control, for boilers
equipped with 30 psi relief valves. Boilers rated for a higher
pressure and equipped with a matching relief valve may
operate at a higher pressure, but no higher than 5 psi
below the relief valve opening pressure.
D. Check for and repair any leaks before placing system in
service.
BEFORE FIRING BOILER, make these checks:
Before firing boiler, review the “Boiler Control and Display
Features” section of this manual. Understanding the features and
programming the applicable parameters is essential for setting up
the boiler to operate properly on the heating system it is installed
on.
1. System is full of water. Air is vented or purged.
2. Relief valve is installed in accordance with ASME Boiler
and Pressure Vessel Code, Section IV. Valve opening is
not closed or reduced in size.
3. Venting is installed according to instructions under “FLUE
GAS VENTING REQUIREMENTS”.
4. All wiring is completed, following applicable wiring
diagrams.
3. While “t” is blinking, DHW tank temperature may be
set to desired temperature (if tank is equipped with
sensor). The setting range is between 104˚ to 185˚F.
4. View actual boiler supply & return water temperature, domestic hot water tank temperature (if tank
equipped with sensor), flue temperature and outside
temperature (if outside sensor is used) on
“Temperature Display” by selecting 1, 2, 3, 4, or 5 on
“Mode Display”.
• These numbers are steady on display and are
not settable.
• All sensor inputs to the control must be
connected to a 12k ohm sensor.
C. Viewing and changing system setting:
A trained, experienced service technician or installer should
perform following adjustments. See table 5 for details.
1. Space heating and DHW post pump time may be
changed.
2. Space heating and DHW modes may be chosen.
3. Priority for either space heating or DHW may be chosen,
with a selectable time limit or infinite operation.
4. Weather compensation slope and set point temperature
may be changed (if outside sensor is used).
(See Figure 24 for graph).
5. Read actual blower RPM.
6. Adjust blower RPM for high and low input adjustment.
7. Read flame current in micro amp.
8. Run boiler on high, low or ignition input steady for 20
minutes for test purposes.
D. Display and push buttons:
5. Using soap solution, check for gas leaks in all gas piping
from meter to boiler gas supply pipe. DO NOT use open
flame.
II. BOILER CONTROL AND DISPLAY FEATURES
(See Figure 23)
A. Boiler Operation Status:
“Mode Display” shows status of boiler operation
(see table 3).
B. Viewing and Changing Temperatures:
Setting boiler supply water temperature and water tank
temperature (see table 4).
Press “Select” button for viewing following different modes
on “Mode Display”
1. While “c” is blinking, boiler supply water temperature
for space heating may be set to desired temperature
The setting range is between 90˚ to 185˚F.
2. While “d” is blinking, boiler supply water temperature
for DHW may be set to desired temperature. The
setting range is between 104˚ to 185˚F.
1. Reset - Used to clear a Lock out error (indicated with an
“A” in the “Mode Display”).
2. Select - Used to scroll through the modes in the “Viewing
and Changing Temperatures” and “Viewing and Changing
System Setting” menus.
3. Enter - Used to store values that are changed in the
“Viewing and Changing Temperatures” and “Viewing and
Changing System Setting” menus.
4. Up- Used to increase values in the “Viewing and Changing
Temperatures” and “Viewing and Changing System
Setting” menus.
5. Down - Used to decrease values in the “Viewing and
Changing Temperatures” and “Viewing and Changing
System Setting” menus.
Page 30
30
Lynx Model LX-85
"MODE" DISPLAY
"RESET" PUSH BUTTON
"BURNER STATUS"
STEADY DOT = BURNER ON
BLINKING DOT = BURNER OFF
Figure 23. Display Board
"TEMPERATURE" DISPLAY (3 DIGITS)
"UP" PUSH BUTTON
*
"DOWN" PUSH BUTTON
"ENTER" PUSH BUTTON
"SELECT" PUSH BUTTON
Table 3
LYNX BOILER DISPLAY BOARD
“Boiler Operation Status”
MODE
DISPLAY
Reset button must be pressed to resume normal operation.
NOTE: Blinking dot on “Mode Display” indicates active heating control, burner off.
Steady dot indicates burner is on.
*:Error must be corrected to resume boiler operation. Pressing the “Reset” button is not required.
**: The boiler loop circulator is energized, if the boiler water temperature drops below 50˚F.
***: Error must be corrected to resume DHW operation. Space heating not affected. Pressing
the “Reset” button is not required.
DESCRIPTION & TEMPERATURE DISPLAY
Boiler is on stand-by mode.
Temperature display shows supply water Temp.
Space heating mode.
Temperature display shows supply water Temp.
Domestic hot water mode.
Temperature display shows supply water Temp.
Frost protection mode. **
Temperature display shows supply water Temp.
Lockout (Alarm) condition.
Temperature Display indicates the lockout code
Error Condition. *
Temperature display indicates the error code.
Warning Condition. ***
Temperature display indicates the error code.
Page 31
Lynx Model LX-85
Press “SELECT” button for viewing different modes on “MODE DISPLAY”
31
Table 4
VIEWING AND CHANGING TEMPERATURES
MODE
DISPLAY
blinking
blinking
blinking
DESCRIPTION & TEMPERATURE DISPLAY
Space heating supply water temperature could be changed by
pressing “Up/Down” button. Settable from 90˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 1)
Domestic hot water supply temperature could be changed by
pressing”Up/Down” button. Settable from 104˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 2)
Domestic hot water tank temperature could be changed by
pressing “Up/Down” button. Settable from 104˚F to 160˚F
(steps of 1 F). The default value is 140˚F.
Press “Enter” button to store.
(see note 3)
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
NOTE:
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
(if outdoor sensor is used)
1-For space heating mode “0” (boilers not utilizing outdoor sensor))
2-For DHW mode “2” (storage tank with Aquastat)
3-For DHW mode “1” (storage tank with sensor)
Page 32
32
Lynx Model LX-85
VIEWING AND CHANGING SYSTEM SETTING -
Table 5
“To change system setting or perform system test”
The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change
system setting: Press “UP or DOWN” button, then press “ENTER”
WARNING: Only a trained, experienced service technician or installer should use this table.
MODE DISPLAY
*
*
*
*
*
Changing space heating post pump time. Settable from 10 to 900 seconds.
(steps of 10 seconds). The default value is 30 seconds.
Changing DHW post pump time. Settable from 1 to 255 seconds.
(steps of 1 seconds). The default value is 15 seconds.
Changing space heating control mode
0: Thermostat only (default) - boiler without outdoor sensor
1: Outside sensor and Thermostat
2: Outside sensor only
3: Permanent heat demand (boiler circulator always on)
Changing domestic hot water (DHW) mode
0: No DHW
1: Storage tank with sensor
2: Storage tank with thermostat (default value)
3: Plate heat exchanger
Changing DHW or space heating priority mode
0: DHW priority (no time limit)
1: Space heating priority (no time limit)
2: DHW priority for limited time (default)
3: Space heating priority for limited time
DESCRIPTION
**
**
*
*
*
*
(space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F).
*
*
Changing weather compensation set point (space heating mode 2 only).
*
*
*
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
Changing priority limited time. Settable from 20 to 80 minutes.
The default value is 30 minutes.
Boiler model selection, value is 1 for model LX-85
Boiler model confirmation, value is 1 for model LX-85
Weather compensation supply water reference temperature
The default value is 86˚F.
Changing compensation slope (space heating mode 1 or 2).
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Not Utilized
Settable from 32˚F to 122˚F (steps of 1˚F).
The default value is 68˚F.
Display shows blower RPM (mutiply reading by 10 for actual RPM)
Display shows flame current in micro amps
*
NOTE: *: Alternating **: Steady
System test – Display shows flame current
0: System test off
L: Steady low input (20 minutes)
I: Steady ignition input (20 minutes)
H: Steady high input (20 minutes)
Page 33
Lynx Model LX-85
33
Maximum
water target
temp.
185 °F
Water
Supply
Target Temp.
(°F)
200
190
180
170
160
150
140
130
120
)
.
x
a
m
(
0
0
.
5
=
e
e
p
p
o
o
l
Sl
S
0
.
.
4
=
= 3
e
p
o
l
S
0
.
8
.
2
1
=
=
e
e
p
p
o
o
l
l
S
S
5
.
1
=
e
p
o
l
S
2
.
1
=
e
p
o
l
S
=
e
p
o
l
S
e
p
o
l
S
)
t
l
u
a
f
e
d
(
0
.
1
5
.
0
=
110
Minimum
water target
temp.
100
90
Water
reference
80
temp. (default
of 86°F)
70
7060-20-10-3001020304050
6 8 °F
Outdoor Temp. (°F)
Figure 24. Space Heating mode with outside sensor water set point graph.
.)
n
i
m
(
1
.
0
=
e
p
o
l
S
-40
Page 34
34
Lynx Model LX-85
III. INITIAL START
Safe lighting and other performance criteria were met when testing various gas manifold and control assemblies used on the
Lynx LX-85 boiler under the ANSI Z21.13 - latest edition.
Instructions
Follow the lighting instructions in this manual. These instructions
are also attached to the boiler.
TURN 90˚
TO OPEN
TURN 90˚
TO CLOSE
C. Use only your hand to turn the gas supply shut-off valve.
Never use tools. If the supply shut-off valve will not turn by
hand, don’t try to repair it, call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under
water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the
control system and any gas control which has been under
water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
automatically lights the burner. D
O NOT try to light the
burner by hand.
5. Open the gas supply shut-off valve, by turning the handle to
be parallel to the gas piping (See Figure 25).
GAS SUPPLY SHUTOFF VALVE
IN "OPEN" POSITION
GAS SUPPLY SHUTOFF VALVE
IN "CLOSED" POSITION
Figure 25. Gas supply shutoff valve operation.
SAFETY INFORMATION
For Your Safety Read Before Operating
WARNING: If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, personal
injury or loss of life.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
DO NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch: DO NOT use any
phone in your building.
• Immediately call you gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
6. Wait five (5) minutes (longer for propane) to clear out any
gas, then smell for gas, including near the floor. If you then
smell gas, STOP! Follow “B” in the safety information
above on this page. If you don’t smell gas, go to next step.
7. Turn on all electric power to the appliance.
8. Set thermostat to desired setting.
If the appliance will not operate, follow the instructions
“To Turn Off Gas to Appliance” and call your service
technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Close the gas supply shut off valve, by turning the handle
to be perpendicular to the gas piping. (See Figure 25).
Page 35
Lynx Model LX-85
LYNX BOILER MODEL LX-85 SEQUENCE OF OPERATION
35
THERMOSTAT CALLS FOR HEAT
CIRCULATOR(S) ON
COMBUSTION BLOWER ON
(AT MEDIUM SPEED)
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 33”
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 03”
NO
NO
BLOWER SPEED CONFIRMED?
YES
5 SECOND PRE-PURGE PERIOD
TRIAL FOR IGNITION - 6 SECONDS
SPARK IGNITOR ENERGIZED
GAS VALVE OPENS
WATER HIGH LIMIT CLOSED?
YES
GAS VALVE REMAINS OPEN
FOR 4 SECONDS
NO
3 TRIALS FOR
IGNITION
WITH NO FLAME SENSED?
2 TIMES RETRIALS
FOR IGNITION
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 01”
YES
GAS VALVE REMAINS OPEN. CONTROL
SENSORS, BLOWER SPEED, FLAME
THERMOSTAT CALL FOR HEAT ENDS
10 SECOND BLOWER POST PURGE.
15 SECOND CIRCULATOR POST PURGE.
SPARK IGNITOR DE-ENERGIZED
NO
FLAME SIGNAL SENSED?
YES
CONTINUOUSLY MONITORS
THERMOSTAT, HIGH LIMIT, WATER
SIGNAL, AND LWCO (IF USED).
GAS VALVE CLOSES
GAS VALVE CLOSED.
BLOWER POST PURGE
10 SECONDS.
Page 36
36
Lynx Model LX-85
IV. CHECK COMBUSTION AND FUEL INPUT RATE
A. Remove the boiler jacket top panel, by removing the 2
screws near the back and lifting as the top panel is slid
toward the back. Remove the boiler jacket front panel, by
pulling forward from the top, and lifting off the pivots at the
bottom. (See Figure 26a).
B. Lift the control panel up over the jacketing, by removing the
2 screws in front, and folding at the hinge while lifting
upward from the bottom. Position the notches in the side
brackets onto the jacket side panel pivots, to secure in
place. (See Figure 26b).
C. Remove the heat exchanger enclosure front cover, by
unlatching the 2 top corners and lifting as the cover is
pulled forward from the top. (See Figure 26c).
D. Start and run the burner at the maximum firing rate, by
using the “System Test” mode in the “Viewing and changing
system setting” menu. Refer to Table 5 on page 32.
1.Measure the CO, and CO2of the flue gas. A flue
sample port is provided in the vent pipe (See
Figure 3 on page 3). The length of certain combustion
analyzer probes may require that the control panel be
lowered, in order to insert the probe into the flue
sample port. The CO should not exceed 100 ppm,
when the combustion is correct. The CO2 should be
in the range listed in Table 6.
4.If the fuel input is not at the rate specified on page 2
at the maximum firing rate, then the blower speed
should be adjusted to attain the specified input rate.
This can be done by using the “Change blower RPM
for high input” mode in the “Viewing and Changing
System Setting” menu. Refer to Table 5 on page 32.
Increasing the blower rpm will increase the fuel input
rate, and decreasing the blower rpm will decrease the
fuel input rate.
E. In the “System Test” mode in the “Viewing and Changing
System Setting” menu, use the “down” push button to
switch to the minimum firing rate. Refer to Table 5 on
page 32.
1.Measure the CO and CO2of the flue gas. The CO
should not exceed 30 ppm, when the combustion
is correct. The CO2should be in the range
listed in Table 6.
2.
If the CO2 is not within the range specified for that
gas type at the minimum firing rate, then adjust the
gas valve offset to the nominal valve shown in Table 6.
(See Figure 26d) for the location of the offset adjustment. Remove the cap that covers the offset screw
Turn the offset clockwise to increase the CO2value.
Turn the offset counter-clockwise to decrease the
CO2value. Replace the offset cap when adjustment
is complete.
.
2.If the CO2is not within the range specified for that
gas type at the maximum firing rate, then adjust the
venturi throttle to the nominal value shown in Table 6.
Turn the throttle clockwise to decrease the CO
value. Turn the throttle counter-clockwise to increase
the CO2value. See Figure 26d.
3.Once the correct combustion is confirmed at the
maximum firing rate, check the fuel input rate on the
gas meter.
BTUH INPUT = cu. ft. metered in 3 minutes x
*The higher heating value of the gas can vary for
different localities. Consult the gas supplier for this
value in BTU/cu.ft.
Fuel
Nat.
Gas
Firing
heating value of the gas* x 20
CO
2
Rate
min. nom. max.
max.8.7% 9.0% 9.3%
min.7.7% 8.0% 8.3%
2
3.Once the correct combustion is confirmed at the
minimum firing rate, check the fuel input rate of the
gas meter.
BTUH Input = cu. ft. metered in 3 minutes x
heating valve of the gas * x 20.
4.If the fuel input is not at the rate specified on page 2
at the minimum firing rate, then the blower speed
should be adjusted to attain the specified input rate.
This can be done by using the “Change blower RPM
for low input” mode in the “Viewing and Changing
System Setting” menu. Refer to Table 5 on page 32.
Increasing the blower rpm will increase the fuel input
rate, and decreasing the blower rpm will decrease the
fuel input rate.
F. Exit the “System Test” mode, once the combustion and fuel
input rate has been checked and adjusted, if necessary.
Refer to Table 5 on page 32.
G. Replace the heat exchanger enclosure front cover, and
secure the 2 latches. Lower the control panel back in place,
and secure with the 2 screws. Replace the jacket top panel,
and secure with the 2 screws. Replace the jacket front
panel, engaging the top area clips to secure..
max. 10.2% 10.5% 10.8%
Propane
min.9.2% 9.5% 9.8%
Table 6. Combustion values for
Natural Gas and Propane.
Page 37
Lynx Model LX-85
SCREWS
37
TOP COVER
FRONT COVER
Figure 26a. Remove jacket top and front covers.
PIVOT
HEAT EXCHANGER
ENCLOSURE
FRONT COVER
Figure 26b. Lift control panel.
CONTROL PANEL
HINGE
LATCH
Figure 26c. Remove heat exchanger enclosure
front cover.
VENTURI
THROTTLE
ADJUSTMENT
SCREW
Figure 26d. Gas valve and venturi adjustment.
COMBUSTION
BLOWER
OFFSET
ADJUSTMENT
SCREW
(UNDER CAP)
GAS VALVE
Page 38
38
Lynx Model LX-85
V. SAFETY CHECK
A. Check for gas leaks:
Using soap solution, check for gas leaks from meter to gas
valve including all pipes and fittings and gas valve
connections. Use liquid soap solution for all gas testing. DO
NOT use open flame.
B. Thermostat Test:
Set thermostat setting to low enough to end call for heat.
Gas valve should close and burner should stop firing.
Blower and circulator pump should go into a post purge,
then shut off.
A. LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error
and retry operation. The temperature display shows the error code.
ERROR CODEINDICATIONREMEDY
01
Ignition Failure - 3 unsuccessful
ignition attempts in a row.
C. Control Safety Shutdown test:
With the burner firing, disconnect the spark cable from the
spark ignitor. Gas valve should close and burner should
stop firing. The boiler will try for ignition three times after
this, then should lock out with an “A 01” error shown on the
display. Reconnect the spark cable to the spark ignitor, and
press the “Reset” button to return to normal operation.
VI. DIAGNOSTIC ERROR CODES
WARNING: Only a trained, experienced service technician
should perform troubleshooting. Turn off all electric power to the
boiler before service.
Check for steady sparking at electrodes. If spark not
steady - check spark gap to be .125”, clean or replace
spark ignitor, check power supply voltage and grounding.
If spark is steady - check for proper gas supply pressure.
Check combustion, if able to ignite, or replace gas valve.
02
03
04, 05, 09, 10,
12, 13, 14, 15,
16, 18, 32
19, 20
33
Flame Failure - 3 losses of flame
signal during one demand.
Water High Limit Open
Control Failure
Flame Detected at Wrong Time
Fan Failure - RPM error
Check for proper combustion, at both max. and min.
input firing rates. If combustion is within the range
specified in Table 6 on page 36, clean or replace spark
ignitor, check power supply voltage and grounding.
Check to see if the water outlet temperature reaches
220˚F. If it does, replace the water outlet 12k ohm
sensor. If it does not, replace the water high limit switch.
Replace control board. Make sure the proper boiler
model selection and confirmation code is entered.
See Table 5 on page 32.
If a flame is still observed after a call for heat is stopped,
replace the gas valve. If the burner seems to be shutting
down properly, replace the spark ignitor.
Check wire harness connections going to the blower.
Replace blower.
Page 39
Lynx Model LX-85
B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the
condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset”
button is not required.
ERROR CODEINDICATIONREMEDY
Check wire harness connections going to the
01
02
03
Water Outlet Sensor Open
Water Inlet Sensor Open
Flue Gas Sensor Open
sensor.
Replace the sensor.
Check wire harness connections going to the
sensor.
Replace the sensor.
Check wire harness connections going to the
sensor.
Replace the sensor.
39
11
12
13
19, 42, 45,
46, 47, 48
20
21
22
24
Water Outlet Sensor ShortedReplace the sensor.
Water Inlet Sensor ShortedReplace the sensor.
Flue Gas Sensor ShortedReplace the sensor.
Replace control board. Make sure the proper
Control Failure
Flame Detected at Wrong Time
Polarity ErrorReverse the hot and neutral power supply wires.
Frequency Error
Earth Connection FaultyCheck grounding of control and boiler chassis.
boiler model selection and confirmation code is
entered. See Table 5 on page 32.
If a flame is still observed after a call for heat is
stopped, replace the gas valve, If the burner
seems to be shutting down properly, replace the
spark ignitor.
Check power supply frequency to be 60 hz,
certain power supplies may not provide the
proper frequency.
continued on page 40
Page 40
40
continued from page 39
ERROR CODEINDICATIONREMEDY
Check flue gas temperature, at the maximum firing
rate and high water temperature. If the flue gas
30
31
32
Excess Flue Temperature
Low Water Cutoff Error
Excess Water Inlet Temperature
temperature reaches 212˚F, check the fuel input
rate and combustion. Check the condition of the
heat exchanger. If the flue gas temperature does
not reach 212˚F, replace the flue sensor.
If a low water cutoff is installed, check the system
water pressure and content. Check the condition of
the LWCO. If no LWCO is installed, check the
jumper is in place at the wiring terminal board.
See Figure 16a on page 18.
Check that the wire harnesses to the water inlet
and outlet sensors are not reversed. The water
inlet sensor harness should have a blue colored
connector, the water outlet sensor harness should
have a red colored connector. Check that the
pumping flow direction is correct.
Lynx Model LX-85
51
52
C. WARNING ERRORS: Indicated by an “H” in the mode display. Operation of the space heating mode is not affect-
ed, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored, once the
condition is fixed. The temperature display shows the error code. Pressing the “reset” button is not required.
04
Domestic Hot Water Tank Sensor Open
14
Reset Button Error
Boiler Model Selection Error
Domestic Hot Water Tank
Sensor Shorted
Try turning power supply off and on again. If error
returns, replace the display board.
Check that the proper boiler model selection and
confirmation code is entered in the display.
See Table 5 on page 32.
If sensor is utilized, check wire harness connections
going to the sensor, or replace the sensor. If no sensor is utilized, check the proper DHW mode is programmed. See Table 5 on page 32.
If sensor is utilized, replace the sensor. If no sensor
is utilized, check the proper DHW mode is programmed. See Table 5 on page 32.
Page 41
Lynx Model LX-85
41
CARE AND MAINTENANCE
This section must be brought to the attention of the owner by the
installer so that the owner can make the necessary arrangements with a qualified service agency for the periodic care and
maintenance of the boiler. The installer must also inform the
owner that the lack of proper care and maintenance of this boiler
and any fuel burning equipment may result in a hazardous condition. Installer should discuss contents of the User’s Information
Manual (Publication LX-UIM) with the owner.
A trained and qualified service technician should perform the
inspection listed in these instructions before each heating season
and at regular intervals.
I. GENERAL MAINTENANCE
A. Safety check, see page 38.
B. Vent and air intake system inspection
1. Check for obstruction, condensation, corrosion and
physical damage.
2. Check outside termination. Screen and louvers should be
free of any debris and must be cleaned as required.
3. Perform “Venting and Air intake System Regular
Inspection”, see page 16.
C. Piping
Check the following:
1. Water piping and accessories for leaks. Slightest leaks
should be corrected.
2. System to be full of water and pressure to remain stable at
correct setting on gauge.
II. ANNUAL MAINTENANCE
IMPORTANT: The spark ignitor must be replaced at the
beginning of each heating season.
III. INSPECTION DURING HEATING SEASON
A. Check water pressure regularly and add water slowly to
system when needed. If much water is added, venting may be
necessary. Regular loss of water from boiler system may
indicate either a system leak, or a faulty air control system, or
a faulty automatic fill valve.
B. Check venting system. See “Venting and Air Intake System
Regular Inspection” on page 16.
C. Check condensation drain trap to be full of water. Check for
deterioration of the tubing. Check that the trap is not plugged.
D. The combustion blower does not require or have provisions
for lubrication.
E. If required, lubricate the circulator as per the manufacturer’s
instruction.
IV. CLEANING
A. Heat Exchanger: In the unlikely event of flue passage or
water passage blockage, service to remedy situation must be
performed only by an authorized Slant/FIn representative.
B. Burner: In the unlikely event of blockage or deterioration,
service to remedy situation must be performed only by an
authorized Slant/Fin representative.
IF REPLACEMENT PARTS ARE NEEDED
3. Air-control system. Noise and air binding in radiation
should not occur.
4. Low water cutoff for operation (see instruction furnished
with unit).
D. Boiler Room Air Supply
Check air vents for continuous positive supply of air as
required. Air needs are greatest in cold weather if boiler
installation is non-direct vent method. Air vents must open and
free of obstruction.
WARNING: The flow of combustion and ventilating air to the
boiler should not be obstructed.
When parts are needed, refer to boiler model and serial number
shown on the boiler name/rating plate. Refer to publication
number LX-10PL replacement parts for part numbers. Whenever
possible refer to the original order by number and date.
Control identification and replacement should not be attempted
by unskilled personnel. Only, simple easily - identified controls
and parts may be obtained locally. All other control and parts
should be identified by and ordered from Slant/Fin. Relief/Safety
valves must be ASME rater for the pressure and gross output of
the boiler.
For replacement parts, heating contractors should contact their
Slant/Fin boiler distributor.
Page 42
42
Lynx Model LX-85
GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNEL
WARNING:Only a trained, experienced service technician should perform troubleshooting.
Turn off all electrical power to the boiler before servicing.
A. BURNER FAILS TO OPERATE - NO HEAT
CAUSE
1. No power, display off, power switch off. Main electric 1. Close switch. Check or replace fuse.
switch open. Blown or defective line fuse.
2. Gas supply valve shut off.2. Open gas supply valve. Check gas pressure.
3. Harnesses plug-in connectors are not securely connected.3. Check connectors on boiler control.
4. Operational problem, detected by control.4. Error code on display can be correlated to
REMEDY
specific problems and remedy. Refer to page
38-40 for error codes.
B. NOT ENOUGH HEAT
1. Thermostat setting is too low.1. Set thermostat at higher setting.
2. Boiler water maintained at too low temperature.2. Increase space heating set point temperature.
Refer to Table 4 on page 31.
3. Circulator not running.3. With thermostat calling for heat, check for power
to circulator. If power is O.K. but circulator is not
running, replace circulator.
4. Boiler water level too low.4. Carefully snap open relief valve handle to
determine if boiler is full of water, if not full of
water, check for system leaks and check water
pressure regulator. Repair any system leaks.
Adjust or replace water pressure reducing valve.
5. Fuel input rate too low.5. Check the maximum fuel input firing rate.
C. FUMES AND GAS ODORS
1. Leaks in gas piping or accessories.1. Locate leaks and repair.
2. Gas leaks in service line or meter connections.2. Close service supply valve - shut down boiler
3. Condensation trap is not full of water.3. Check and fill with water.
4. Venting system is physically damaged.4. Check carefully and repair. Also, see “Venting
5. Over - firing or poor combustion.5. Check the maximum fuel input firing rate and
Refer to page 36 for the procedure.
and notify utility.
System Regular Inspection”.
combustion. Refer to page 36 for procedure.
Page 43
Lynx Model LX-85
SCREWS
VENTURI
GAS PIPE
PROPANE ORIFICE
RUBBER GROMMET
DISCONNECT GAS PIPE
GAS VALVE
Figure 27. Propane orifice installation.
VENTURI GASKET
COMBUSTION BLOWER
GAS VALVE CABLE
SCREW
DISCONNECT GAS VALVE CABLE
43
WARNING:
Only a trained, experienced Service
Technician or Installer should per-
form the conversion procedure.
CONVERTING TO PROPANE
A conversion kit, complete with the appropriate orifice disk and
conversion label, is available for performing this procedure.
Refer to the Lynx model LX-85’s boiler’s parts list publication
LX-10PL for the kit part number. This conversion kit can only be
used for the LX-85 boiler. The following procedure for performing the conversion to Propane is intended for a Lynx boiler that
is not yet installed. If the boiler is already installed, be sure to
turn the gas and power supply off, before proceeding. Once the
boiler is installed, the combustion should be checked, as per the
instructions and specifications on page 36. The fuel input rate
for Propane will be approximately as specified on page 2, when
the supply pressure is in the range of 10” to 14” w.c.
1. Remove the boiler jacket top panel, by removing the 2
screws near the back and lifting as the top panel is slid
toward the back. Remove the boiler jacket front panel,
by pulling forward from the top, and lifting off the pivots
at the bottom. (See Figure 26a).
2. Lift the control panel up over the jacketing by removing
the 2 screws in front, and folding at the hinge while
lifting upward from the bottom. Position the notches in
the side brackets onto the jacket side panel pivots, to
secure in place. (See Figure 26b).
3. Remove the heat exchanger enclosure front cover, by
unlatching the 2 top corners and lifting as the cover is
pulled forward from the top. (See Figure 26c).
4. Remove the gas valve cable, by turning the single
screws on the plug end counter-clockwise until free.
(See Figure 27).
5. Disconnect the gas valve supply pipe, by turning the
nut at the valve inlet counter-clockwise until free.
(See Figure 27).
6. Remove the 2 Torx or Phillips screws securing the
venturi to the blower.
7. Remove the venturi/gas valve assembly, taking note of
the position of the gasket behind the venturi, for
reassembly purposes.
8. Remove the 3 Torx or Phillips screws securing the gas
valve to the venturi. (See Figure 27).
9. Remove the black rubber grommet from the gas valve,
by where the venturi was attached.
10. Place the Propane orifice disk into the black rubber
grommet, confirm the stamp on the orifice disk
matches the number specified on page 2 of this
manual for the boiler model being converted.
11. Replace the black rubber grommet, with the Propane
orifice disk, into the gas valve pocket from which it was
removed.
12. Reassemble the venturi to the gas valve, being careful
that the grommet and orifice disk are kept in the proper
positions until the screws are secured.
13. Reinstall and tighten the 2 Torx or Phillips screws that
secure the venturi/gas valve assembly to the blower.
14. Re-connect the gas valve supply pipe, by aligning
properly with the rubber gasket in place, and turning
the nut at the valve inlet clockwise until tight.
15. Replace the gas valve cable and secure with the
single screws.
16. Affix the Propane conversion label next to the boiler
rating plate.
17. If the boiler is in the process of being installed, it is
best to check the combustion and make any necessary
adjustments before replacing the heat exchanger cover
and jacket panels. See page 36 of this manual. If the
boiler installation is to occur at a future time, the heat
exchanger cover and jacket panels can now be reinstalled, and the combustion check should be performed
after the boiler is installed.