Slant/Fin LYNX LX-85 Installation And Operating Instructions Manual

This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
LYNX
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODEL LX-85
GAS-FIRED BOILER FOR NATURAL AND L.P. PROPANE GASES
INSTALLATION AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes........................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Additional Installation Requirements for Massachusetts............5
Contamination Prevention...........................................................5
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation......................................5
Flue gas Venting Requirements..................................................6
Vent Material ..............................................................................6
Air Intake Material ......................................................................6
Vent and Air Intake Restrictions .................................................7
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance ..................................8
Non-Direct Vent Vertical Venting.................................................8
Direct Vent Installation................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.....................................14
Direct Vent, Venting and Air Intake through a Roof ..................15
Venting and Air Intake Regular Inspection ...............................16
Condensate Removal System..................................................16
Gas Piping ................................................................................16
Electrical Wiring ........................................................................17
Wiring Diagram.........................................................................18
Multi Zoning ..............................................................................20
Water Piping .............................................................................23
Operating Instructions...............................................................29
Boiler Control Display...............................................................29
Boiler Control............................................................................29
Sequence of Operation.............................................................35
Gas Input Rate Adjustment ......................................................36
Safety Check ...........................................................................38
Care and Maintenance .............................................................41
General Troubleshooting Guide ................................................42
Conversion to Propane.............................................................43
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
INSTALLATION INSTRUCTIONS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
IMPORTANT
BEFORE READING THE
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
WARNING
The venting system of this boiler is under positive pres­sure. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addi­tion to the recommendations within this manual and the User’s Information Manua flue collector to the outdoor discharge, must be carefully checked annually by a qualified service agency.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 1008 Part No. 84-5736 Publication No. LX-40 Rev. C
l, the venting system, from the
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
2
Lynx Model LX-85
RATINGS AND DIMENSIONS
WATER INLET (RETURN) - 1" NPT (MALE)
WATER OUTLET (SUPPLY) - 1" NPT (MALE)
5 3/8
2 1/2
23
17 3/4
REAR VIEW
Figure 1. Dimensions data
2 5/8
36 3/4
6 7/8
1 1/2
3 3/8
27 7/8
16 1/4 7
23 3/4
SIDE VIEW
VENT CONNECTION
AIR INTAKE CONNECTION
12 3/8
33 7/8
GAS SHUTOFF VALVE 1/2" NPT (FEMALE)
4 3/4
8 5/8
41
23 5/8
FRONT VIEW
SPECIFICATIONS FOR LX-85 BOILER
Fuel Rate Input: 85,000 BTUH maximum
25,000 BTUH minimum
Boiler Water Volume: .75 gallon (6.25 lbs)
Water Piping Connections: 1" NPT (male)
Gas Piping Connection: 1/2" NPT (female)
Vent Connection: 3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Air Intake Connection: 3" nominal I.D. pipe (PVC, CPVC or stainless steel)
Weight of Boiler (uncrated): 105 lbs.
Gas orifice size: Natural Gas - No orifice used *
Propane - 0.190" diameter **, ID Code: C
*Note: No orifice changes are required for high altitude installations. **See page 43 for conversion procedure to propane.
Figure 2. Lynx Boiler
Lynx Model LX-85
FIELD WIRING ENTRANCES
FIELD WIRING TERMINALS
LOCATION AND IDENTIFICATION OF PARTS
SPARK ELECTRODE (IGNITOR)
WINDOW (SIGHT GLASS)
GAS VALVE
FLUE SENSOR
WATER OUTLET (SUPPLY)
3
AIR INTAKE CONNECTION
GAS SUPPLY VALVE
TEMPERATURE DISPLAY
MODE DISPLAY
POWER SWITCH
PRESSURE GAUGE
TOP (EXTERIOR)
VENT CONNECTION
VENTURI
HEAT EXCHANGER
FLUE COLLECTOR
WATER INLET (RETURN)
COMBUSTION BLOWER
BOILER DRAIN VALVE
FRONT (INTERIOR)
FLUE SAMPLE PORT
BOILER CONTROL
SEDIMENT TRAP
WATER
COMBUSTION BLOWER
HEAT EXCHANGER ENCLOSURE FRONT COVER
CONDENSATE TRAP
RIGHT SIDE (INTERIOR)
SUPPLY SENSOR
WATER HIGH LIMIT
WATER RETURN SENSOR
CONDENSATE DRAIN TEE
Figure 3. Location and identification of par ts
4
Lynx Model LX-85
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
This installation must also conform to the additional require­ments in this Slant/Fin Instruction Book.
NATURAL GAS-FIRED BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See Appen­dix A for vent terminal location restrictions.) The location should also be such that all boiler components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
WARNING LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION Liquefied Petroleum (L.P.) propane gas is heavier than air. Therefore, propane boilers, piping, valves should NOT be installed in locations where propane leaking from defective equipment and piping will "pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire. Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE ma y be in effect in your geographic area.
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air-gas might collect. Appliances so fueled shall not be installed in an above­grade under-floor space or basement unless such loca­tion is provided with an approved means for removal of
unburned gas." Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE for design criteria of the "approved" means for removal of unburned gas.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler
shall be as follows: MINIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended Surface Front 6" 18" Rear 0" 0" Left Side 0" 5" Right Side 0" 5" Top 5" 18" Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling,
the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
Construction for Service
1"*
5"
6"
BOILER FOUNDATION
A. Provide a solid, level foundation capable of supporting
the weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers, page 2.
B. Boiler can be installed on both combustible and
non-combustible floors, but must NOT be installed on or above carpeting.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
* 2" FOR ENCLOSED
Figure 4. Lynx boiler min. clearances for combustible construction.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Lynx Model LX-85
5
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contamination sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause corrosion or other damage to the heat exchanger and components of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
AREAS LIKELY TO HAVE CONTAMINANTS
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
VENTING APPLICATION
The Lynx LX-85 is a sealed combustion type boiler, it may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from outside or as a non-direct vent boiler which air for combustion is taken from inside the boiler room.
The Lynx LX-85 boiler must be vented by 3" diameter PVC/CPVC sched­ule 40 pipe, or the proper 3” diameter stainless steel venting system (see “vent material” on page 6) through the roof or sidewall. An optional adapter is available for connecting stainless steel venting to the boiler vent outlet. See the Lynx LX-85 Parts List, publication # LX-10PL.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventilation. When buildings are insulated, caulked and weather-stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes. The following recommendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWOUNOBSTRUCT­ED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER
ROOM.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
When the Lynx-85 is installed and used in the Commonwealth of Massa­chusetts, the following additional code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each addi­tional level of the dwelling, building or structure served by the side wall hor­izontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adja­cent floor level.
b. In th event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizon­tally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTR UCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or part for residential purposes.
requirements pursuant to Massachusetts
6
Lynx Model LX-85
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor and
one louvered opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a min­imum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. Openings for passage of air into the boiler room for direct-vent installation must be at least
1
2 of the openings required for the non-direct vent as mentioned above.
If additional non-direct vent appliances are installed in the same space and adequate air openings are provided for them, there are no additional air openings required for the Lynx LX-85.
For both direct and non-direct installation, the following must be considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be
used in or near the boiler area.
- Boiler area must never be under negative pressure. The
flow of combustion and ventilating air to the boiler must not be obstructed.
VENT AND AIR INTAKE MATERIALS
The vent piping for direct or non-direct vent installation must be 3” diameter PVC/CPVC schedule 40 pipe, or UL listed single wall 3” diameter AL29-4C* stainless steel material. The air intake piping for direct vent installation must be 3" diameter PVC/CPVC schedule 40 pipe. The following manufacturers’ systems are approved for use within a specified minimum and maximum equivalent vent length in this manual.
Manufacturer
Heat-Fab. Inc. Saf-T Vent Not Required
ProTech System, FasNSeal Not Required Inc.
Flex-L StaR-34 GE-IS806 International, Inc.
Z-Flex, Inc. Z-Vent GE, RTV 106
N/A PVC pipe, PVC primer
N/A CPVC pipe, CPVC primer
*AL29-4C is a registered Trademark of Allegheny Ludlum Corp
Type/System
EZ Seal
Schedule 40 and cement
Schedule 40 and cement
Sealant
When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing. Use sealant specified by vent system manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions provided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materials other than PVC/CPVC Schedule 40.
The vent and air intake connections on the boiler are designed to accommodate either PVC/CPVC Schedule 40 pipe or the listed stainless steel vent systems (by inserting the optional adapter specified in the Lynx LX-85 Parts List, publication # LX-10PL, for stainless steel venting). Built-in sealing rings are provided, so no additional sealant is required. The application of liquid soap to the outer end of the vent pipe (or adapter, if used) will aid in installing it. Make sure the pipes are round and burr-free, and push down into the appropriate step of the connector or adapter, until snug. (See Figure 5).
FLUE GAS VENTING REQUIREMENTS
The Lynx LX-85 series boiler is a high efficiency, mechanically forced draft boiler and, therefore, requires different venting arrangements than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply. The use of a vent damper is NOT permitted on this boiler series.
AIR INTAKE PIPE (PVC OR CPVC)
VENT PIPE (PVC OR CPVC)
CHECK EDGE FOR BURRS
FLUE AND AIR INTAKE CONNECTOR
Figure 5. Vent and Air Intake Pipe installation into Boiler vent and air intake connections.
Lynx Model LX-85
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting, cleaning and connecting PVC and CPVC pipe, for both the vent and air intake piping system:
1. When laying out the piping system, work from the boiler
vent and air intake adapter to the point of outside termination.
2. Cut the PVC/CPVC pipe to the required lengths, and
pre-assemble the entire system, before sealing. Disassembly after sealing, to make any corrections, will not be possible.
3. Once the pre-assembled PVC/CPVC pipe vent and air
intake system is verified to be of the proper length pipe and fitting orientation, begin disassembling and preparing the pipes and fittings for the sealing process. This can be done section by section, or the complete vent and air intake system can be disassembled. It is recommended to mark the various parts, before complete disassembly, to eliminate the possibility of errors during re-assembly.
4. De-burr the inside and outside of every PVC/CPVC pipe, to
ensure that they engage fully into the fittings, and flow is not compromised. A small chamfer on the outside of each pipe can particularly aid in the final assembly process.
5. Wipe or knock out any debris from inside the PVC or
CPVC pipe, which may have accumulated there from the cutting process or storage. Debris can cause operational problems with the boiler combustion components.
6. Thoroughly clean the outside ends of each pipe, and the
inside of each fitting. The surfaces must be dry for the sealing agents to work properly. Handle the prepared pipe lengths away from the cleaned ends, and handle the cleaned fittings, from the outside, to avoid contamination.
7. Re-assembly of the PVC or CPVC pipe should be done in
sections, to avoid the primer and cement drying before the parts are engaged.
8. For each joint, first apply a coat of primer to the outside
sealing surface of the pipe and the inside sealing surface of each fitting. Use only the primer type that is specified for either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A
second coat of cement can be applied, if necessary, but must be done quickly and in a manner that avoids unnecessary build-up that would cause obstruction inside the system. Use only the cement type that is specified for either the PVC or CPVC pipe that is being utilized.
10. Before the cement dries, insert the pipe into the fitting. A
slight twisting motion while pushing the pipe into the fitting will aid in distributing the cement evenly and ensuring the parts fully engage.
11. Quickly wipe the excess cement from the outside areas of
the joint. Discard any rags used to avoid later getting the cement on hands, clothes and equipment.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100 equivalent feet.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows as shown in the table on this page.
7
Figure 6.
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow that is required.
5. Vent length restriction is for both direct and non-direct vent installations.
EXAMPLE: Boiler model LX-85 is to be installed. The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows.
In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100’ - (4’ x 5’) = 80’. Since the air intake pipe also is PVC and requires the use of 4 elbows, the maximum straight pipe air intake length that can be utilized is also 80 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 80 feet.
Equivalent Length of Various 90-Degree Elbows
Manufacturer
Heat-Fab, Inc. Saf-T Standard 3
Heat-Fab, Inc. Saf-T, tight radius elbow 6 ProTech System, Inc. FasNseal 6
Flex-L International, Inc. StaR-34 6 Z-Flex, Inc. Z-Vent 6
N/A PVC, Schedule 40 5 N/A CPVC, Schedule 40 5
Type/System
elbow
Equivalent
Length (Feet)
8
Lynx Model LX-85
6. The LX-85 boiler is equipped with a built-in condensation drain and trap. The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensa­tion drain and trap is required on the vent piping system itself.
7. The horizontal vent pipe must be sloped upward from the boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8. The horizontal vent and air intake pipes must be supported
with pipe straps, at intervals no greater than 5 feet, when PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible
constructions must be maintained (see Page 4). No clearance is required between the vent and air intake pipes of this boiler.
10. Common venting with other appliances or another Lynx
boiler is not allowed.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window or gravity air inlet into any building. The bottom of the vent terminal or air intake terminal shall be at least 12 inches above grade or the normal snow level whichever is greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip­ment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. Vent termination must not be located in any confined space (i.e. window wells, alcoves, narrow alleys) or under any overhang or deck. Vent termination should not allow flue gas discharge towards neighbor’s windows or where personal injury or property damages can occur.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 9 shows typical venting through the roof. The vent pipe must pass through the ceiling, floor and the roof vertically through a 6" minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage, an appropriate UL listed roof flashing must be used.
11. DO NOT install a vent damper or similar devices in vent system or on the boiler.
12. DO NOT insulate venting system.
VENTING INSTALLATION
Only the approved PVC/CPVC and stainless steel materials listed on page 6 may be used for the venting system installa­tion. If stainless steel vent systems are used, follow the manu­facturer’s instructions, in conjunction with these instructions.
I. NON-DIRECT VENT INSTALLATION
The air for combustion is taken from the ambient air surrounding the boiler; therefore, ample supply of air is required for combustion and ventilation (see page 6.)
DO NOT use this installation method if the surrounding of the boiler is contaminated. See page 5 for the list of harmful contaminants and their sources, to avoid.
A. NON-DIRECT VENT SIDEWALL VENTING
Figures 7 and 8 show typical horizontal sidewall venting. For combustible wall passage of vent piping, a UL listed thimble or flashing and sealing boot must be used, providing the wall thickness from 3" minimum up to 12" maximum. The vent piping must terminate with a screened tee or elbow termination facing down.
CAUTION: Flue gasses exiting from the vent terminal will condense. Building materials in the area of the vent terminal should be protected from discoloration and degradation.
An existing chimney (see Figure 10) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe with in the chimney.
The vertical vent piping must terminate with a screened tee, combination of 45˚ elbow and a 90˚ screened elbow termina­tion or a rain cap termination.
II. DIRECT VENT INSTALLATION
Air intake piping from outside to the boiler air intake connector provides the air for combustion. The boiler surrounding may be contaminated (See page 5). Piping the air intake to the outside can prevent contaminants from the boiler surrounding from entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 11 and 12 show typical sidewall direct venting, using a Slant/Fin vent/air intake termination. There are 2 different mod­els of vent/air intake termination available. One is designed specifically for PVC/CPVC venting, and the other is designed specifically for stainless steel venting systems. Only these 2 models of vent/air intake termination are approved for this method of installation. Refer to the Slant/Fin Lynx LX-85 Parts List (publication number LX-10PL) for the appropriate model for the vent material to be used.
CAUTION: Flue gasses existing from the vent terminal will con­dense. Building materials in the area of the terminal should be protected from discoloration and degradation, in addition to the requirements of the vent termination location and clearances stated in this manual.
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
9
AL29-4C S.S.*. venting materials (See page 6).
90˚ ELBOW
AIR INTAKE (DO NOT BL0CK)
SLOPE UP 1/4 IN. PER FOOT MIN.
FROM BOILER TO VENT TERMINATION
3 IN. DIA. PVC/CVPC PIPE FOR VENT
6" MIN. 9" MAX.
TERMINATION 90˚ ELBOW WITH SCREEN
A U/L LISTED FLASHING AND SEALING BOOT MUST BE USED ON COMBUS TIBLE WALLS.
OUTSIDE WALL
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe f or venting.
6" MIN. 9" MAX.
OUTSIDE VENT TERMINATION ELBOW WITH SCREEN
A U/L LISTED WALL THIMBLE MUST BE USED ON COMBUSTIBLE WALLS. S/F P/N 440695 (ADJUSTABLE 5 IN. TO 8 IN.) MAY BE USED. ABOVE THIMBLE MUST BE USED WITH HEAT-FAB SLIP JOINT CONNECTOR
STANDARD 90
?
ELBOW
AIR INTAKE (DO NOT BL0CK)
SLOPE UP 1/4 IN. PER FOOT MIN.
FROM BOILER TO VENT TERMINATION
3 INCH. DIA. STAINLESS STEEL VENTING MATERIAL FOR VENT
ADAPTOR
SNOW LINE
(SEE DEFINITION)
12" MIN
12" MIN
S/F P/N 440695 (ADJUSTABLE
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
OUTSIDE WALL
SNOW LINE
(SEE DEFINITION)
10
Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
90° TERMINATION
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
ELBOW WITH SCREEN
RAIN CAP TERMINATION MAY BE USED
*
FIRESTOP AND SUPPORT
90° ELBOW
AIR INTAKE (DO NOT BLOCK)
SLOPE UP 1/4 IN.
PER FOOT MIN.
10 FT MIN.
VENT TERMINATION TEE WITH SCREEN
1 FT MIN.
FLASHING AND STORM COLLAR
NIM "2
2" MIN
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
FIRESTOP AND SUPPORT
96044 N/P F/S
ELBATSUJDA( 5
Figure 9. Lynx model LX-85 - non-direct vent, venting through the roof
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
USE ADAPTOR IF STAINLESS STEEL IS USED
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERI AL FOR VENT
Lynx Model LX-85
LYNX MODEL LX-85 NON - DIRECT VENT, UTILIZING AN EXISTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
*
CHIMNEY AS A CHASE
AL29-4C S.S.*. venting materials (See page 6).
ALTERNATE VERTICAL TERMINATION
*
45° ELBOW
RAIN CAP TERMINATION MAY BE USED
10 FT MIN.
CHIMNEY TOP PLATE
90° TERMINATION ELBOW WITH SCREEN
VENT TERMINATION TEE WITH SCREEN
1 FT MIN.
11
SLOPE UP 1/4 IN.
PER FOOT MIN.
90° ELBOW
AIR INTAKE (DO NOT BLOCK)
SEAL CHIMNEY OPENING
WITH MORTAR OR COVER PLATE
USE ADAPTOR IF STAINLESS STEEL IS USED
(
ELBATSUJ
596044 N/P F/S
DA
Figure 10. Lynx model LX-85 - non-direct vent, utilizing an existing chimney as a chase.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
3 INCH DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
3 INCH DIA. PVC/CPVC PIPE OR ST AINLESS STEEL VENTING MATERIAL FOR VENT
12
Lynx Model LX-85
LYNX MODEL LX-85 - DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 6).
3 - 16" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA PVC/CPVC PIPE FOR VENT
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 84 0802 000
12" MIN
AIR INTAKE LOUVERS
3" DIA PVC/CPVC COUPLING WTH SCREEN
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
Figure 11. Direct vent, sidewall venting illustration; utilizing PVC/CPVC pipe for venting
3 - 12" THICK WALL
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
90° ELBOW
3" DIA STAINLESS STEEL PIPE FOR VENT
ADAPTOR
SLANT/FIN VENT/AIR INTAKE TERMINATION KIT PART # 84 0804 000
12" MIN
AIR INTAKE LOUVERS
3" DIA STRAIGHT SCREENED VENT TERMINATION
SNOW LINE ** (SEE DEFINITION)
OUTSIDE WALL
Figure 12. Direct vent, sidewall venting illustration; utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
*
Lynx Model LX-85
13
3" DIA PVC/CPVC PIPE FOR VENT
OUTSIDE TERMINATION PLATE
3" DIA PVC/CPVC COUPLING WITH SCREEN
INSIDE TERMINATION PLATE
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
SCREW
WALL (3"-16" THICK)
3" DIA PVC/CPVC PIPE FOR VENT
SCREW
STOP FOR AIR/VE NT OUTSIDE TERMINAL
Figure 13a. Vent/Air intake termination; utilizing PVC/CPVC pipe for venting.
4" GALV. PIPE (WALL THIMBLE - FOR COMBUTIBLE WALLS ONLY)
3" DIA AL29-4C S.S. VENT PIPE (SLIP JOINT CONNECTOR )
INSIDE TERMINATION PLATE
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
3" DIA AL29-4C S.S.
(SLIP JOINT CONNECTOR)
WALL (3"-12" THICK)
FLUE GAS
VENT PIPE
SCREW
3" DIA PVC/CPVC PIPE FOR AIR INTAKE
INSIDE TERMINATION PLATE
AIR
SEAL HERE
OUTSIDE TERMINATION PLATE
3" DIA PVC/CPVC COUPLING WITH SCREEN
FLUE GAS
LOUVERS
3" DIA PVC/CPVC PIPE FOR A IR INTAKE
AIR
WALL (3"-16" THICK)
INSIDE TERMINATION PLATE
WALL (3"-12" THICK)
SCREW
STRAIGHT SCREENED TERMINATION
OUTSIDE TERMINATION PLATE
STRAIGHT SCREENED TERMINATION
Figure 13b. Vent/Air intake termination; utilizing stainless steel venting materials.
SEAL HERE
LOUVERS
OUTSIDE TERMINATION PLATE
14
Lynx Model LX-85
VENT/AIR INTAKE TERMINATION FOR PVC/CPVC VENTING INSTALLATION
This termination is designed specifically for 3” diameter PVC or CPVC Schedule 40 pipe to be used as the vent and air intake piping material, only. It can be used on a combustible wall, provided the 1” minimum clearance of the vent pipe to any combustible surface is maintained.
1. Termination must be installed horizontally.
2. Refer to Figure 13a for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and
clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in
the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate
using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the out
side termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #9.
8. From inside, install the inside termination plate, using 4
screws. Make sure that the holes for the vent and air intake pipe visually line up with the vent passage hole and air intake collar on the outside termination plate.
9. Cut the PVC or CPVC air intake pipe to the proper
dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
10. Cut the PVC or CPVC vent pipe so that it will extend out
at least 2" from the outside termination plate and 2" from inside termination plate.
11. Cement a 3” diameter PVC or CPVC coupling onto the
PVC or CPVC vent pipe, and install the stainless steel screen (supplied with the boiler) into the coupling.
VENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL VENTING INSTALLATION
This termination is designed specifically for the 3” diameter stainless steel venting systems approved to be used as the vent, and 3” diameter PVC or CPVC schedule 40 pipe to be used as the air intake piping material, only. It can be used on a combustible wall, provided a length of 4” diameter galvanized pipe is installed as a thimble around the vent pipe, for the wall passage.
1. Termination must be installed horizontally.
2. Refer to Figure 13b for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and clearances” explained on page 8.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate using 4 screws. Make sure the louvers are at right side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the outside termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #11.
8. For combustible wall a 4” galvanized pipe must be used as a wall thimble.The length of the 4” galvanized pipe should be approximately 1” shorter than the wall thickness.
9. From inside the building, fit galvanized pipe over 4” collar of the outside plate.
10. From inside, install inside termination plate using 4 screws. Make sure the 4” collar on the plate, penetrated into the galvanized pipe.
11. Cut the PVC or CPVC air intake pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
12. From outside the wall, insert the bare end of the PVC or CPVC vent pipe through the outside and inside terminal plates, until the coupling is flush with the outside wall plate.
13. From inside, proceed with the air intake and vent pipe installation. Follow the proper PVC/CPVC assembly practices specified on page 7 and venting system restrictions specified on page 7 of this manual.
12. Assemble and seal straight screened termination to the slip joint connector.
13. From outside of the building, insert vent pipe (slip joint connector and termination assembly) through the 3” holes of the outside and inside termination plate.
14. From inside, proceed with air intake and vent pipe installation. Follow vent manufacturer’s instructions and restrictions specified on page 7 of this manual.
Loading...
+ 30 hidden pages