Slant/Fin LX-150 User Manual

The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
WARNING
The venting system of this boiler is under positive pres­sure. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addition to the recommendations within this manual and the User’s Information Manual, the venting system, from the flue col­lector to the outdoor discharge, must be carefully checked annually by a qualified service agency.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
LYNX
INSTALLATION AND OPERATING INSTRUCTIONS
Printed in U.S.A. 1214 Part No. 81-5001000 Publication No. LX1-40 Rev. F
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODEL LX-90, LX-120 & LX-150
GAS-FIRED BOILERS FOR NATURAL AND L.P. PROPANE GASES
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes ........................................2
Identification of Parts ........................................................................3
Installation Requirements .................................................................4
Contamination Prevention.................................................................5
Mounting the boiler on a wall............................................................6
Venting Application...........................................................................6
Boiler Room Air Supply and Ventilation............................................6
Flue Gas Venting Requirements.......................................................7
Additional Installation Requirements for Massachusetts..................7
Vent and Air Intake Material .............................................................8
PVC/CPVC Pipe General Assembly Method....................................8
Vent and Air Intake Restrictions .......................................................8
Sidewall Venting, Non-Direct Vent ..................................................10
Vent Termination Location and Clearance......................................10
Non-Direct Vent Installation ............................................................10
Direct Vent Installation....................................................................10
Sidewall Venting, Direct Vent ..........................................................10
Vent/Air Intake Termination Installation...........................................16
Direct Vent, Venting and Air Intake through a Roof........................17
Venting and Air Intake Regular Inspection .....................................18
Condensate Removal System ........................................................18
Gas Piping ......................................................................................18
Electrical Wiring ..............................................................................19
Wiring Diagram...............................................................................20
Single and Multi Zoning..................................................................22
Water Piping ...................................................................................24
Operating Instructions.....................................................................30
Boiler Control and Display..............................................................30
Boiler Operating Status ..................................................................31
Viewing and changing temperature................................................32
Viewing and changing system setting ............................................33
Initial start and operating instruction ..............................................35
Sequence of Operation...................................................................36
Combustion check and fuel input rate............................................37
Safety Check .................................................................................37
Diagnostic error codes ...................................................................38
Care and Maintenance ...................................................................41
General Troubleshooting Guide ......................................................42
WARNING
SEE “WARNING” ON PAGE 4 FOR LIQUEFIED
PETROLEUM (L.P.) PROPANE GAS-FIRED BOILERS
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS
AND STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
Lynx
2
RATINGS AND DIMENSIONS
Figure 1. Dimensions data
SPECIFICATIONS
BOILER MODEL
LX-90 LX-120 LX-150
Input Rate, Btu/Hr
Max.
Min.
90,000 25,000
120,000
30,000
150,000
37,500
Water Piping Connection 1" NPT (Male)
Gas Piping Connection 1/2" NPT (Female)
Vent Connection
3" Nominal ID Pipe PVC, CPVC, Polypropylene
(solid or flexible) or SS. SEE WARNING
Air Intake Connection 3" Nominal ID PVC or CPVC
Gas Orifice Size for Natural Gas No Orifice Used
Gas Orifice Size for Propane
0.1900"
Code # C
0.2025"
Code # A
0.2200"
Code # E
Boiler Water Volume Gal. 0.4 0.6 1.1
Weight of Boiler (Uncrated) Lbs. 118 125 140
WARNING:
1. Use of cellular core PVC and CPVC or Radel for venting system is NOT allowed
2. Thermal insulation on non-metallic vent pipe and fittings is NOT allowed.
35
"C"
33
5
LEFT SIDE FRONT RIGHT SIDE
BOILER "A" "B" "C" "D" MODEL
BOILER "A" "B" "C" "D" LX-90 6 3/4 3 3/8 2 3/4 16 1/4
MODEL LX-120 6 5/8 3 3/8 2 16 1/4
LX-90 6 3/4 3 3/8 2 3/4 16 1/4
LX-150 6 3/8 3 3/4 2 3/4 19
LX-120 6 5/8 3 3/8 2 16 1/4
"B"
"A"
22
"D"
Lynx
3
LOCATION AND IDENTIFICATION OF PARTS
Figure 2. Location and identification of parts (front and side panels are removed) model LX-150 is shown
GAS SUPPLY VALVE
MODE DISPLAY
AIR INTAKE
HOSE
GAS VALVE
AIR INTAKE
VENT
BOILER SUPPLY WATER
BOILER RETURN WATER
BOILER CONTROL UNDER THE COVER
TURN BLACK SCREW 1/4 TURN THEN LIFT CONTROL COVER TO REMOVE
PRESSURE GAUGE
POWER SWITCH
TEMPERATURE DISPLAY
WATER SUPPLY SENSOR
WATER HIGH LIMIT
SPARK ELECRODES
COMBUSTION BLOWER
TEST PORT
CONDENSATE DRAIN
CONDENSATION TRAP/REMOVAL
(IGNITER)
HEAT EXCHANGER
WATER RETURN SENSOR
BOILER DRAIN VALVE
Lynx
4
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
This installation must also conform to the additional require­ments in this Slant/Fin Instruction Book.
BOILER LOCATION
Provide a level, solid foundation or vertical wall for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See paragraph heading “Vent Termination Location and Clear­ance” on page 9.) The location should also be such that all boiler components are protected from water (dripping, spray­ing, rain, etc.) during appliance operation and service (circu­lator replacement, control replacement, etc.).
WARNING
SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM
(L.P.) PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance with applicable provisions of NFPA 58 ( Liquefied Petroleum Gas Code) latest for installations in US and CAN/CGA B149.1 latest edition for installations in Canada.
Liquefied Petroleum (LP) propane gas is heavier than air therefore Propane gas accumulate at floor level. If you sus­pect a leak, do not attempt to operate boiler. A spark or flame from the appliance (boiler) or other sources may ignite the accumulated propane gas causing an explosion or fire. It is recommended that inspections for gas leaks be per­formed periodically by licensed professional and that leak detection devices be installed as a further safety measure.
BOILER FOUNDATION
A. Provide a solid, level foundation or vertical wall capable of
supporting the weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers, page 2. See also figure 4a & 4b for mounting the boiler on the wall.
B. Boiler can be installed on both combustible and
non-combustible floors, but must NOT be installed on or above carpeting.
C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Figure 3. Lynx boiler min. clearances for combustible construction.
INSTALLATION REQUIREMENTS
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler
shall be as follows: MINIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended
Surface
Construction for Service Front 6" 18" Rear 0" 0" Left Side 0" 8" Right Side 0" 8" Top 5" 18" Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling,
the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contami­nation sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause corrosion or other damage to the heat exchanger and compo­nents of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
• Spray cans containing chloro/fluorocarbons
• Permanent wave solutions
• Chlorinated waxes/cleaners
• Chlorine-based swimming pool chemicals
• Calcium chloride used for thawing
• Sodium chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid/muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and other similar products
AREAS LIKELY TO HAVE CONTAMINANTS
• Dry cleaning/laundry areas and establishments
• Swimming pools
• Metal fabrication plants
• Beauty shops
• Refrigeration repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture refinishing areas and establishments
• New building construction
• Remodeling areas
• Garages with workshops
Lynx
5
Figure 4a. Wall bracket securement
Figure 4b. Mounting boiler on the wall
Lynx
6
MOUNTING THE BOILER ON A WALL
Be sure that the wall is vertically plumb and capable of carrying the weight of the boiler and the system piping, when full of water. See page 2 for the boiler weight.
Be sure that there are studs available in the proper locations, for securing the boiler wall bracket and back panel. (See Figures 4a and 4b).
For wood stud walls, use lag screws or wood screws with a coarse thread and a minimum of 3” in length.
For metal stud walls, use toggle-style bolts that are specifically designed for such and maximum capacity exceeds the weight of the boiler and the system piping when full of water.
DO NOT use anchors driven into sheetrock to hold the boiler up on the wall. If mounting the boiler on a cement wall, use anchors that are specifically designed for such, and maximum capacity exceeds the weight of the boiler and the system piping, when full of water.
A. INSTALL THE WALL BRACKET. SEE FIGURE 4a.
1. Remove the wall bracket from the boiler jacket rear panel, by unfastening the single screw that holds it in place, for shipping purposes only.
2. Select the location on the wall where the boiler will be mounted. The upward facing tabs of the wall bracket will align with the top surface of the boiler jacket, and 3 feet of open wall space will be needed to accommodate the boiler jacket rear panel below this.
3. For sheetrock and stud construction, locate the studs and determine which set of holes in the wall bracket best align with the center of the studs. For cement walls, determine a location for the wall bracket to mount where the anchors will be secure, devoid of seams or cracks.
4. Place the bracket in the selected location, with the 2 tabs positioned up and facing outward, level it out, and mark the holes to be used. A minimum of 4 of these holes must be utilized, regardless of wall material.
5. Drill the appropriate diameter and depth holes for the fasteners used in the wall, where marked.
6. Fasten the wall bracket to the wall, being sure that the tabs face upward and outward, and the fasteners have engaged the wall properly.
B. INSTALL THE BOILER ON THE WALL. SEE FIGURE 4b.
1. Remove the boiler jacket front cover, by turning the 2 black screws 1/4 turn to the open position, then lifting off.
2. Remove both the boiler jacket side panels, by removing the 2 sheetmetal screws in the top and bottom front edge, then lift off.
3. To aid in lifting the boiler, a 3 foot long, 1/2” inside diameter steel pipe can be slid through the holes in the sides of the boiler rear panel. Let the pipe extend out each side of the jacket evenly, for hand-holds, and pick up the boiler without letting it tilt, for safety.
4. Lift the boiler up against the wall, with the top edge of the jacket slightly above the wall bracket tabs. There are 2 holes in the upper corners of the jacket rear panel, that can visually be aligned with the 2 larger diameter holes in the wall bracket, to ensure that the wall bracket tabs line up and engage with the boiler jacket near top lip notches properly.
5. There are 2 fastener holes in the lower area of the boiler rear panel, just below the flue collector, for insuring the boiler does not move off the wall bracket. Mark these 2 holes, with the boiler in place, then lift the boiler off the wall bracket.
6. Determine which fastener type will best engage with the wall construction at the location of the 2 market holes. Drill out the appropriate diameter and depth holes for the fasteners, where marked.
7. Lift the boiler up onto the wall bracket again, as described in Step 4. Secure the boiler to the wall, with the 2 fasteners in the lower rear panel area.
8. If able to, the 1/2” diameter lifting pipe should be removed from the boiler rear panel.
9. The 4 boiler legs may be removed at this time, if desired. 2 screws hold each leg in place, from inside the jacket panel.
10. The boiler side panels can be replaced at this time, but the front panel should be left off, for the startup procedure later in the installation.
VENTING APPLICATION
Lynx boilers are sealed combustion type boilers, it may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from outside or as a non­direct vent boiler which air for combustion is taken from inside the boiler room.
Lynx boilers must be vented by 3" diameter PVC/CPVC sched­ule 40 pipe, 3” nominal ID polypropylene pipe or the proper 3” diameter stainless steel venting system (see “vent material” on page 8) through the roof or sidewall.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventila­tion. When buildings are insulated, caulked and weather­stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventila­tion, of the National Fuel Gas Code, ANSI Z223.1-latest edi­tion, or applicable provisions of the local building codes. The following recommendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM:
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through an outside wall; one louvered opening near the floor and
one louvered opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. Openings for passage of air into the boiler room for direct-vent installation must be at least
1
2 of the openings required for the non-direct vent as mentioned above.
If additional non-direct vent appliances are installed in the same space and adequate air openings are provided for them, there are no additional air openings required for the Lynx boiler.
For both direct and non-direct installation, the following must be considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be
used in or near the boiler area.
- Boiler area must never be under negative pressure. The
flow of combustion and ventilating air to the boiler must not be obstructed.
FLUE GAS VENTING REQUIREMENTS
The Lynx boiler is a high efficiency, mechanically forced draft boiler and, therefore, require different venting arrangements than natural draft, lower efficiency boilers.
THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply. The use of a vent damper is NOT permitted on this boiler series.
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
When the Bobcat is installed and used in the Commonwealth of Massa­chusetts, the following additional
requirements pursuant to Massachusetts
code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each addi­tional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adja­cent floor level.
b. In th event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thir­ty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the hori­zontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equip­ment installed in a room or structure separate from the dwelling, build­ing or structure used in whole or part for residential purposes.
Lynx
7
Lynx
8
VENT AND AIR INTAKE MATERIALS
The vent and air intake system for direct or non-direct vent instal­lation must be 3” diameter PVC/CPVC schedule. 40 pipe, 3” nominal polypropylene (solid or flexible) or UL listed single wall 3” diameter AL29-4C* stainless steel material. The following manu­facturers’ systems are approved for use within a specified mini­mum and maximum equivalent vent length in this manual.
When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing. Use sealant specified by vent system manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions provided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materials other than specified above.
The integral flue adapter on the boiler is designed to accom­modate either PVC/CPVC Schedule 40 pipe, polypropylene or the listed stainless steel vent systems. This adapter has built-in sealing rings, so no additional sealant is required. Make sure the pipes are round and burr-free, and push down into the appropriate step of the adapter, until snug. (See Figure 5). Apply liquid soap to the outer end of the vent pipe and air intake pipe for easy insertion.
The integral air intake adapter on the boiler is designed to take PVC/CPVC pipe.
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting, cleaning and connecting PVC and CPVC pipe, for both the vent and air intake piping system:
1. When laying out the piping system, work from the boiler vent and air intake adapter to the point of outside termination.
2. Cut the PVC/CPVC pipe to the required lengths, and pre-assemble the entire system, before sealing. Disassembly after sealing, to make any corrections, will not be possible.
3. Once the pre-assembled PVC/CPVC pipe vent and air intake system is verified to be of the proper length pipe and fitting orientation, begin disassembling and preparing the pipes and fittings for the sealing process. This can be done section by section, or the complete vent and air intake system can be disassembled. It is recommended to mark the various parts, before complete disassembly, to eliminate the possibility of errors during re-assembly.
4. De-burr the inside and outside of every PVC/CPVC pipe, to ensure that they engage fully into the fittings, and flow is not compromised. A small chamfer on the outside of each pipe can particularly aid in the final assembly process.
5. Wipe or knock out any debris from inside the PVC or CPVC pipe, which may have accumulated there from the cutting process or storage. Debris can cause operational problems with the boiler combustion components.
6. Thoroughly clean the outside ends of each pipe, and the inside of each fitting. The surfaces must be dry for the sealing agents to work properly. Handle the prepared pipe lengths away from the cleaned ends, and handle the cleaned fittings, from the outside, to avoid contamination.
7. Re-assembly of the PVC or CPVC pipe should be done in sections, to avoid the primer and cement drying before the parts are engaged.
8. For each joint, first apply a coat of primer to the outside sealing surface of the pipe and the inside sealing surface of each fitting. Use only the primer type that is specified for either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A second coat of cement can be applied, if necessary, but must be done quickly and in a manner that avoids unnecessary build-up that would cause obstruction inside the system. Use only the cement type that is specified for either the PVC or CPVC pipe that is being utilized.
10. Before the cement dries, insert the pipe into the fitting. A slight twisting motion while pushing the pipe into the fitting will aid in distributing the cement evenly and ensuring the parts fully engage.
11. Quickly wipe the excess cement from the outside areas of the joint. Discard any rags used to avoid later getting the cement on hands, clothes and equipment.
Note: Polypropylene pipe, follow manufacturers instructions.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100 feet.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows as shown in the table on page 9.
*AL29-4C is a registered Trademark of Allegheny Ludlum Corp
Figure 5. Vent Pipe installation into Boiler Adapter.
Manufacturer Type/System Sealant
Heat-Fab. Inc.
Saf-T Vent
EZ Seal
Not Required
ProTech Sys-
tem, Inc.
FasNSeal Not Required
Flex-L Interna-
tional, Inc.
StaR-34 GE-IS806
N/A
PVC pipe,
Schedule 40
PVC primer and
cement
N/A
CPVC pipe,
Schedule 40
CPVC primer
and cement
Centrotherm
Eco System
Polypropylene Not required
WARNING: 1. Use of cellular core PVC and CPVC or Radel
for venting system is NOT allowed 2. Thermal insulation on non-metallic vent pipe and fittings is NOT allowed.
VENT PIPE (PVC SHOWN)
INSTALL PVC/CPVC PIPE DOWN TO THIS LIP
INSTALL STAINLESS STEEL PIPE OR POLYPROPYLENE PIPE DOWN TO THIS LIP
BOILER UPPER VENT PIPE
CHECK EDGES FOR BURRS
SEALING RINGS
TOP OF BOILER JACKET
Lynx
9
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow that is required.
5. Vent length restriction is for both direct and non-direct vent installations.
EXAMPLE: The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows.
In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100' - (4 x 5') = 80'. Since the air intake pipe also is PVC and requires the use of 4 elbows, the maximum straight pipe air intake length that can be utilized is also 80 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 80 feet.
6. The Lynx boiler is equipped with a built-in condensation drain and trap. The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensa­tion drain and trap is required on the vent piping system itself.
7. The horizontal vent pipe must be sloped upward from the boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8. The horizontal vent and air intake pipes must be supported
with pipe straps, at intervals no greater than 5 feet, when polypropylene, PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible
constructions must be maintained (see Page 4). No clearance is required between the vent and air intake pipes of this boiler.
10. Common venting with other appliances or another Lynx
boiler is not allowed.
11. DO NOT install a vent damper or similar devices in vent
system or on the boiler.
12. DO NOT insulate venting system.
Figure 6.
Heat-Fab, Inc. Saf-T Standard 3
elbow
Heat-Fab, Inc. Saf-T, tight radius elbow 6 ProTech System, Inc. FasNseal 6 Flex-L International, Inc. StaR-34 6
N/A PVC, Schedule 40 5 N/A CPVC, Schedule 40 5 Centrotherm Eco Systems
Polypropylene 5
Manufacturer
Type/System
Equivalant length (Ft.)
Equivalent Length of Various 90-Degree Elbows
Lynx
10
VENTING INSTALLATION
Only the PVC/CPVC, polypropylene and approved stainless steel materials listed on page 8 may be used for the venting system installation. If stainless steel vent systems are used, fol­low the manufacturer’s instructions, in conjunction with these instructions.
I. Non-Direct Vent Installation
The air for combustion is taken from the ambient air surrounding the boiler; therefore, ample supply of air is required for combustion and ventilation (see page 7.)
DO NOT use this installation method if the surrounding of the boiler is contaminated. See page 5 for the list of harmful contaminants and their sources, to avoid.
A. SIDEWALL VENTING - NON-DIRECT VENT
Figures 7 and 8 show typical horizontal sidewall venting. For combustible wall passage of vent piping, a UL listed thimble or flashing and sealing boot must be used, providing the wall thickness from 3" minimum up to 12" maximum. The vent piping must terminate with a screened tee or elbow termination facing down.
CAUTION: Flue gasses exiting from the vent terminal will condense. Building materials in the area of the vent terminal should be protected from discoloration and degradation.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 12 inches below, or 12 inches horizontally from, any door, window or gravity air inlet into any building. The bottom of the vent terminal or air intake terminal shall be at least 12 inches above grade or the normal snow level whichever is greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip­ment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. Vent termination must not be located in any confined space (i.e. window wells, alcoves, narrow alleys) or under any overhang or deck. Vent termination should not allow flue gas discharge towards neighbor’s windows or where personal injury or property damages can occur.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 9 shows typical venting through the roof. The vent pipe must pass through the ceiling, floor and the roof vertically through a 6" minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage, an appropriate UL listed roof flashing must be used.
An existing chimney (see Figure 10) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe within the chimney.
The vertical vent piping must terminate with a screened tee, combination of 45˚ elbow and a 90˚ screened elbow termina­tion or a rain cap termination.
II. Direct Vent Installation
Air intake piping from outside to the boiler air intake adapter provides the air for combustion. The boiler surrounding may be contaminated (See page 5). Piping the air intake to the outside can prevent contaminants from the boiler surrounding from entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 11 and 12 show typical sidewall direct venting, using a Slant/Fin vent/air intake termination. There are 2 different mod­els of vent/air intake termination available. One is designed specifically for PVC/CPVC or polypropylene venting, and the other is designed specifically for stainless steel venting sys­tems. Only these 2 models of vent/air intake termination are approved for this method of installation. Refer to the Slant/Fin boilers Parts List (publication number LXA-10PL) for the appro­priate model for the vent material to be used.
CAUTION: Flue gasses existing from the vent terminal will con­dense. Building materials in the area of the terminal should be protected from discoloration and degradation.
Vent termination location and clearances for non-direct vent stated on Paragraph I, also applies to sidewall direct venting.
Alternate Sidewall venting for direct or non-direct venting:
Vent and/or air intake piping may be installed per figure 12a in order to provide enough clearance from snow line. The total vent/air intake equivalent length must not exceed 100 ft.
In cold climates, install an insolated enclosure around the vent piping to protect from freezing.
Lynx
11
NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylene pipe
or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7).
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC or polypropylene pipe for venting.
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials for venting.
*
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
Lynx
12
NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal polypropylene pipe
or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7).
Figure 9. Lynx - non-direct vent, venting through the roof
*
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
POLYPROPYLENE
,
Lynx
13
NON - DIRECT VENT, UTILIZING AN EXISTING
CHIMNEY AS A CHASE
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” ID polypropylene or U/L listed single wall
3" dia. AL29-4C S.S.*. venting materials (See page 7).
Figure 10. Lynx - non-direct vent, utilizing an existing chimney as a chase.
*
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
POLYPROPYLENE
,
Lynx
14
DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylene or U/L listed single wall
3" dia. AL29-4C S.S.*. venting materials (See page 7).
Figure 11. Direct vent, sidewall venting illustration; utilizing PVC/CPVC or polypropylene pipe for venting
Figure 12. Direct vent, sidewall venting illustration; utilizing stainless steel vent materials for venting.
*
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
OR POLYPROPYLENE
OR POLYPROPYLENE
Loading...
+ 30 hidden pages