Slant/Fin Liberty II LD-20 Installation And Operating Instructions Manual

Page 1
LIBE RTY II
®
OIL-FIRED WATER AND STEAM KNOCKED DOWN BOILERS AND BOILER/BURNER UNITS/NO. 2 OIL
See publication LD-41K for assembly and parts and publication LD-42KB for approved oil burners.
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO ABOVE SAFETY WARN­ING, MAY RESULT IN PERSONAL INJURY OR
DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Assembly . . . . . . . . . . . . . . . . . . . . . . .see pub. #LD-41K
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . .3
Controls and Accessories . . . . . . . . . . . . . . . . . . . . .4
Piping for Steam Boilers . . . . . . . . . . . . . . . . . . . . . .4
Blowing Off a Steam Boiler . . . . . . . . . . . . . . . . . . . .4
Cleaning Piping System . . . . . . . . . . . . . . . . . . . . . .5
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . .5
Piping for Tankless Heater . . . . . . . . . . . . . . . . . . . .5
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . .6
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . .6
Start up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning and Filling New
Water Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Steam Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Low Water Cut-off check-out . . . . . . . . . . . . . . . . . . .8
Pressure Control check-out . . . . . . . . . . . . . . . . . . . .8
Replacement of Steam Boiler . . . . . . . . . . . . . . . . . .8
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-12
Burner Data . . . . . . . . . . . . . . . . . . .see pub. # LD-42KB
Care and Maintenance:
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . .13
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . .13
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
General Maintenance . . . . . . . . . . . . . . . . . . . . . . .13
IMPORTANT: The installation of this equipment must
conform to the requirements of the authority having ju­risdiction or, in the absence of such requirements, to the installation of Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to the National Electrical Code ANSI-NFPA 70, latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Manual. Where there is any dif­ference, the more stringent requirement shall govern.
IMPORTANT: This boiler must be installed by a
trained, experienced, service technician, licensed for the installation and servicing of oil burning equipment or otherwise qualified by the authorities having jurisdiction over the installation.
In addition, where required by the authority having ju­risdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1, latest edition.
THIS MANUAL MUST BE LEFT WITH OWNER
AND SHOULD BE HUNG ON OR ADJACENT TO
THE BOILER FOR REFERENCE.
Printed in U.S.A. 0402 Publication No. LD-43K Part No. 43-0268
Page 2
2 LIBERTY
3
TAPPINGS AND OPENINGS
Tapping Loc. Steam Boiler
1 A* 2” supply onn rear section *
1
3 4 8 9
0 1/2” low limit for tankless
1
1A 1/2” tankless inlet
1
1B 1/2” tankless outlet
1
2 1/2” steam gauge glass & 67 LWCO
1
3 1-1/2” bushed to 3/4” for drain cock
1 14 1-1/2” condensate return
Flue Collector
Front Section
4
3” supply
3/4” steam safety valve 1/4” siphon, pressure gauge & pressure cut-out 3/4” alternate electronic low water cut-off 1-1/2” skimmer tapping
Tapping Loc. Water Boiler
1 1-1/2” supply 2 3/4” air vent or expansion tank
3 3/4” water relief valve 5A 1/2” tankless inlet 5B 1/2” tankless outlet
6 1/4” pressure temp. gauge
7 1/2” high limit, hi/lo or combination control 13 1-1/2” return & 3/4” drain cock 14 1-1/2” alternate return
2
T
OP VIEW
FRONT
Figure 1
RONT VIEW WATER
F
6
1
3
1
REAR 14
5A
B
5
7
FRONT
1
3
FRONT VIEW STEAM
11A
11B
0
1
REAR 14
* Rear section LD-50, LD-60, LD-70
steam boilers only.
12
1A*
DIMENSIONS
9
8
8
Figure 2
RATINGS
I=B=R Chimney Size
Nom. Rect.
I.D. Round
x Height §
(in x in x ft)
x Height
(in x ft)
A.F.U.E.
%
Water Steam
Boiler
Model
No.*
I=B=R Burner
Capacity Oil Input
GPH† BTUH
D.O.E.
Heating
Capacity
MBH
Water Steam
Water
MBH *
I=B=R
Net Ratings
Steam MBH *
Steam Sq. Ft.
LD-20 0.75 105,000 90 79 8 x 8 x 15 5 x 15 83.50 111⁄2 89⁄326 11⁄4 241⁄4 2 2.20
LD-20 BK 0.95 133,000 110 96 8 x 8 x 15 5 x 15 81.76 11
LD-30H 1.00 140,000 121 105 8 x 8 x 15 6 x 15 86.00 14
LD-30
1.10 154,000 134 134 117 101 421 8 x 8 x 15 6 x 15 84.85 84.15 14
1.25 175,000 151 131 8 x 8 x 15 6 x 15 83.50 14
LD-40H 1.50 210,000 182 179 158 134 558 8 x 8 x 15 7 x 15 86.00 84.00 18
LD-40
1.60 224,000 195 195 170 146 608 8 x 8 x 15 7 x 15 84.45 83.80 18
1.80 252,000 218 190 8 x 8 x 15 7 x 15 83.33 18
LD-50H 2.00 280,000 243 239 211 179 746 8 x 8 x 15 8 x 15 86.00 84.00 21
LD-50
LD-60
LD-70
*
2.10 294,000 256 255 223 191 796 8 x 8 x 15 8 x 15 84.06 83.45 21
2.35 329,000 272§ 237 8 x 12 x 15 8 x 15 21
2.60 364,000 298§ 298§ 259 224 933 8 x 12 x 15 10 x 15 25 15
2.85 399,000 327§ 284 8 x 12 x 15 10 x 15 25 15
3.10 434,000 352§ 354§ 306 266 1108 8 x 12 x 15 10 x 15 28
3.35 469,000 381§ 331 8 x 12 x 15 10 x 15 28
Ratings are based on light oil at 140,000 Btu per gallon, and apply only when burner
Standard working pressure 30 PSI water, 15 PSI steam. All boilers hydrostatically tested - A.S.M.E. For forced hot water heating systems where the boiler and all piping are located within the area to be heated, the boiler may be selected on the basis of gross D.O.E. capacity output. The net I=B=R output ratings shown are based on an allowance for piping and pickup of 1.15 (water) or 1.33 (steam). D.O.E. capacity gross output is divided by the allowance to obtain net rating. The manufacturer should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system opera­tion extensive piping, etc.
models listed in publication no. LD-42KB are used, and are properly adjusted to produce 13% CO
† ‡
§
2. Nominal clay tile liner dimensions. Tankless heater rating based on intermittent draw. I.B.R. gross output. Collar is oblong, will fit 6” diameter nominal connector. NOTE: All boilers under 300,000 Btuh input are tested and rated for capacity under the U.S. Department of Energy (D.O.E.) Test Procedures for Boilers
Dimensions (inches)
Return
Front to
Boiler
Length
“A”
1
2 89⁄32 6 11⁄4 241⁄4 2 2.40
7
8 101⁄32611⁄4 275⁄8 3 3.10
7
8 101⁄32 611⁄4 275⁄8 3 3.20 3.00
7
8 101⁄32 611⁄4 275⁄8 3 3.40
1
4 1123⁄32 711⁄4 31 4 3.80 3.40
1
4 1123⁄32 711⁄4 31 4 3.90 3.50
1
4 1123⁄32 711⁄4 31 4 4.15
5
8 1313⁄32 811⁄2 343⁄8 5 4.30 3.90
5
8 1313⁄32 811⁄2 343⁄8 5 4.40 4.00
5
8 1313⁄32 811⁄2 343⁄8 5 4.70
3
8 1625⁄32 9 411⁄8 7 5.45 5.00
3
8 1625⁄32 9 411⁄8 7 5.70
Flue
Flue ¢
“B”
Circulator
Dia.
“C”
3
32 811⁄2 373⁄4 6 4.90 4.50
3
32 811⁄2 373⁄4 6 5.20
Flange
‘D”
Overall Length
“E”
Boiler
Sect.
Tankless
Heater
GPM * *
Water Steam
Page 3
LIBERTY
BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be near the chimney so that the Flue Pipe Connector or Breeching to the chimney is short and direct.
A. The foundation must be capable of supporting the weight of the
boiler when filled with water:
Boiler
Size
Approximate Total Weight of Boiler
Assembly, filled with water
LD-20 440
D-30 550
L LD-40 660 LD-50 785 LD-60 895 LD-70 1000
B. The Liberty Boiler has full wet base sections which surround
fire-box for maximum heat absorbtion of burning fuel, and low floor temperature.
C. If boiler is to be located over buried conduit containing electric
wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
MINIMUM CLEARANCE
Provide accessibility clearance of 24” from surfaces requiring servicing (top and front) and 18” on any side requiring passage. The boiler shall be installed with the following MINIMUM clearances from combustible materials: A. CHIMNEY CONNECTOR -18” B. BACK AND SIDES - 6” EXCEPT as limited by 18” clearance
from chimney connector. NOTE: Except in closets and alcoves, clearances above in (A) and (B) may be reduced by providing forms of protection as specified in NFPA31, latest edition.
CHIMNEY REQUIREMENTS
A. The chimney must be constructed in accordance with all local
applicable codes and the National Board of Fire Underwriters.
See boiler models and rating table shown on page 2 for
chimney sizes. B. Check chimney condition.
Existing chimneys and stacks may have deteriorated; without re-
3
pairs their use would be hazardous. Before connecting to an old chimney or stack.
1. Clean it.
2. Inspect it thoroughly.
3. Remove obstructions.
4. Replace worn secctions of metal stacks.
5. Seal bad masonry joints.
6. Repair damaged linings.
C. Where more than one appliance vents into a common chimney,
the area of teh common breeching should at least equal the area of the largest appliance flue plus 50% of the additonal flue areas.
D. Breeching area must not be reduced at connection into chim-
ney. Breeching must be inserted into, but not beyond, inside of chimney liner.
E. Chimney height shall extend at least 3 feet above where it
passes through the roof of the building, and at least 2 feet above any ridge within 10 feet of the chimney.
F. The use of a vent cap, where permitted by code, gives addition-
al protection against adverse wind conditions and precipitation.
G. Flue Connection: Connect flue pipe between top of boiler and
chimney. Horizontal sections of flue pipe must be pitched up­ward to the chimney at least 1/4” per foot. Flue must be inserted into, but not extend beyond, the inside wall of the chimney flue. Install draft regulator in flue pipe, as shown in figure 3.
AIR SUPPLY AND VENTING
Sufficient air for combustion and ventilation in the boiler room must be provided. Failure to do this will result in poor combustion, heavy spptomg and health hazards. Any oil-fired boiler must have a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney draft* is unreliable, CO2and overfire draft* will change unpredictably.
DO NOT vent this boiler to the same chimney flue used by a fireplace or coal or wood burning furnace or boiler. The draft* produced by solid fueled devices varies tremendously between high fire and low fire:
In modern, weatherstripped, energy-saving buildings, natural infiltra­tion may not supply enough air for combustion, particularly if other fuel-burning appliances, exhaust fans or draft inducers are competing for the same air supply. Fireplaces and other solid fuel burning appli­ances consume great quantities of air while at high
BAROMETRIC DRAFT REGULATOR
INSTALLED ON HORIZONTAL CONNECTOR
BAROMETRIC DRAFT REGULATOR
INSTALLED ON VERTICAL RISE
Figure 3. Barometric Draft Regulator
Page 4
4 LIBERTY
fire; if air supply is not ample, such an appliance will creat a down­draft in the oil fired boiler flue: DO NOT operate this boiler and a solid fuel burning appliance at the same time, unless the solid fuel burner is provided with it’s own outside air supply.
FOR THIS BOILER ONLY, a grilled opening within 12” of the floor near the boiler, direct to or ducted to outside, sized to 140 sq. inch per GPH nozzle size, is recommended for air supply. If such a direct outside air supply is not provided, CO2and overfire draft must be checked (refer to STARTUP) after closing all doors and windows that will be closed on the coldest day, and operating all fuel burning appliances including this boiler for at least 30 minutes of cotinuous operation.
If fly screen must be used over air supply openings, areas calculated should be doubled; the screen should be inspected and cleaned fre­quently to maintain free air flow.
Protect air openings against closure by snow, debris, etc. Openings such as doors or windows, if used, must be locked open.
The opening size recommendation just given is for guidance only. It is an installation responsibility to provide air for combustion and ventilation to all appliances, under all operating conditions, for each installation.
*Draft is negative or suction pressure.
INSTALLING CONTROLS AND ACCESSORIES ON BOILER UNITS
Notes: Jacket must be installed on boiler units prior to installation
of trim.
I. STEAM BOILER TRIM, see page 2 for tapping locations, and fig-
ure 5 for illustration of steam boiler.
Figure 4.
A. Steam pressure gauge and pressure cut-out, install in tapping
no.4, figure 4. B. Gauge glass set - use tapping no. 12. C. Pop safety valve - use tapping no. 3, piped full size to boiler; or
pipe full size into a valveless steam header. D. Combustion safety control - mounted on burner.
II. WATER BOILER TRIM, see page 2 for tapping locations, and
figures 1 and 2 for illustration of water boiler. A. Pressure-temperature-Altitude gauge - use tapping no.6. B. High temperature limit - use tapping no. 7. C. Operating control (if used) - use tapping no. 7. D. Water relief valve - use tapping no. 3, piped full size to boiler. E. Automatic air vent or compression tank tappings - if used, install
in tapping no. 2. F. Combustion safety control - mounted on burner.
PIPING FOR STEAM BOILERS
Provide Header and Hartford Loop as suggested. Local codes apply.
BLOWING OFF A LOW PRESSURE STEAM BOILER
A. A 1-1/2” NPT is provided in the front of the boiler (tapping no. 9,
figure 1) for use as a surface blow down to provide rapid skimming of oil and grease which accumulate on the surface of the water. The boiler should be blown down as outlined below.
B. Turn off electrical power supply to boiler. Allow boiler to cool down
and steam pressure to reduce to zero before removing skimmer tapping plug. Check for steam pressure by testing the pop safety valve. Keep your hands and all parts of your body away from the discharge and of the safety valve. Drain boiler down one to two inches below skimmer tapping. The water might be hot. Remove skimmer plug slowly and carefully install a 150 psi malleable iron 1-1/2” NPT street elbow, a 1-1/2” NPT skimmer valve and length of pipe an dplace a bucket underneath the open end of the pipe. Cover bucked with a piece of cloth. (See figure 6).
C. Fil boiler slowly until water level is two inches from top of gauge
glass. (This is the starting water level for skimming only). Fire boiler to produce steam. If the system is heavily laden with oil, it may be difficult to obtain much more than a pound or so of pressure. Set the pressure control at about 7 psi. The higher the steam pressure you can use, the better and faster the cleaning.
D. As steam develops, open the SKIMMER drain valve with caution to
skim the oil and film from the top of the water. DO NOT open the boiler drain valve. Close the skimmer drain valve when the water level drops to about 5” from the top of the gauge glass. The water may stop before the level drops to 5” below the top of the glass. Refill boiler until water level is again two inches from the top of the gauge glass.
E. Repeat (D) above until all film is skimmed off the water settles to
Boiler A. Size Dim.
LD-50 15 27⁄32
LD-60 19 7⁄32
LD-70 22 19⁄32
Models LD-50 thru LD-70
Figure 5. Recommended Steam Piping at Boiler
Models LD-30 thru LD-40
Page 5
LIBERTY
a normal movement. Add make up fresh water to the boiler as described in (D) above, during the blow-off operation, to maintain the proper skimming water level in the vessel. Empty bucket fre quently in order to see the difference in water cleanliness.
F. When surging has stopped and water is clean, and no film can be
seen floating in the bucket, shut off boiler, drain down to level of skimmer tapping, remove valve, plug skimmer tapping and refill the boiler to 24-1/2” water lever. After 15 minute operation, readjust level to normal operating level of 25-1/2” from bottom of boiler (see figure 6). Check the pop safety valve for proper operation. Check for low water cut-off operation. See section on page 7 for check-out.
G. The entire process may have to be repeated over a period of a
few days on extremely fouled system.
CLEANING PIPING SYSTEM
A. To clean piping system, open all valves at the heating elements.
After getting up a good head of steam, shut the boiler down and allow the condensate to return to the boiler. The condensate will carry the oil film with it. Again blow-off the boiler. On extremely fouled systems, it may require several visits over a few days to clean the system.
B. When steam only (no water) is released through the hand valve,
the boiler will not surge or flood.
PIPING FOR WATER UNITSS
NOTE: On knock down boiler only, jacket may be installed after sup­ply and return piping connection, but must be installed prior to adding trim.
5
Figure 8. Air Collecting System
Figure 6.
Figure 7. Air Eliminating System
Figure 9. Recommended Piping to Tankless Heater
I. CIRCULATING SYSTEM
A. FORCED CIRCULATION hot water heating system:
top tapping as supply tapping, and use the front or rear bot­tom tappings for the return.
B. A FLOW CONTROL VALVE (See figure 7) will prevent gravity
circulation and usually is required when tankless heater is installed.
II. AIR CONTROL SYSTEMSS
A. DIAPHRAGM - TYPE COMPRESSION TANKS are used to
control system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the system water. See figure 7.
B. CONVENTIONAL COMPRESSION TANKSS (non-diaphragm
type) are used to control system pressure in an AIR COL­LECTING SYSTEM. Within the system, after initial start-up and venting, air is collected in the tank and acts in contact with the water to control pressure. Air is not vented from this system. If system pressure needs further control, add another tank in parallel with the original tank or install a large capacity tank. Locate the tank at the inlet end of the pump near the boiler. (See figure 8.)
Page 6
6 LIBERTY
C. HOT WATER RADIATION VENTING - Manual air vents
should be installed at the top of all “drops” (where piping goes downward). Air must be vented or purged from all zone lines to permit proper system heating.
D. PUMP LOCATION - Locating low-head pump(s) on return to
boiler is acceptable for smaller boiler sizes in residences of one or two stories. (See figure 7). The pump location shown in figure 8 is required in large, multi-story building installa­tions, especially when high-head pumps are used.
E. A conventional compression tank may be connected to the
3/4” tapping as shown in figure 8.
IPING TANKLESS HEATER (if used)
P
I. Heater capacities are listed on Page 2. II. Pipe the built-in tankless heater using the inlet and outlet tap-
pings indicated on the heater (figure 9) A. Tempering valve (illustrated, but not furnished) is suggested
to provide more volume of temperate water to kitchen and
bath.
B. High temperature water, for dishwasher and laundry, may be
piped direct.
INSTALLING THE BURNER
See Liberty Knocked Down Assembly and Parts Instructions, pub. no. LD-41K, number 8 for the installation of burner mounting studs. Mount burner to boiler, placing flange over mounting studs. Use gasket between flange and boiler. Distance between flange and nose of burner must be as shown in Liberty KD Approved Oil Burners pub. no. LD-42KB. Check to see that nozzle and settings are as given in burner data tables, pub. no. LD-42KB.
OIL SUPPLY PIPING
Install the oil tank or tanks and piping from tank to burner. Follow local codes and practices, NFPA No. 31, INSTALLATION OF OIL BURNING EQUIPMENT and the instruction sheet attached to the oil burner pump. A one-pipe system should be used for gravity fed fuel systems and for lift systems, where the total lift is less than 8 feet. where the total lift is greater than 8 feet, a two-pipe system must be used. In some instances, local codes may require a two­pipe system for below grade fuel oil tanks. Be sure to set-up the fuel oil pump for the piping system used; follow the instructions attached to the pump. Be sure to include a good quality, low pres­sure drop fuel oil filter in the supply line from the tank. This is nec­essary, especially at low fuel oil flow rates (small nozzle sizes), to prevent nozzle plugging. See Slant/Fin publication on one-pipe and two-pipe fuel oil systems.
WIRING THE BOILER
A. The wiring diagrams for the burner and boiler may be found on
pages 8-10.
B. 24 volt control wiring should be approved Safety Circuit wire,
protected as needed.
C. Power supply wiring to the burner must be 14 gauge or heavier,
as required, and should have a properly fused disconnect switch. 120 volt wiring to pumps and safety controls must also be 14 gauge or heavier. Wire must be enclosed in approved conduit.
D. All wiring must be installed in compliance with the National
Electric Code, or any local or insurance codes having jurisdic­tion.
VENT PIPING AND DRAFT REGULATOR
A. Vent pipes must be installed having the same diameter as the
boiler outlet. (See page 2).
B. Vent pipes and breeching must be pitched upward a minimum of
1/4” per foot.
C. Connect vent pipe to the chimney using as few elbows as
possible.
D. Horizontal vent connector into the chimney should not be
inserted beyond the inside wall of the chimney.
E. Install barometric draft regulator on horizontal breeching, near
chimney, with hinge horizontal and face vertical. See manufac turer’s instructions packed in carton with barometric draft regulator.
F. If two or more appliances are used on the same chimney, see
CHIMNEY, page 3.
G. Make up all joints with minimum air leaks, secure with sheet
metal screws.
RECAUTIONS BEFORE STARTING OIL BURNER
P
Make a positive check of A through F before starting burner: A. Boiler and system are full of water. All air is vented from system.
See below. B. All wiring is completed. See pages 8-10. C. Oil supply is connected to the burner; nozzle is installed
correctly, oil valve is open at tank. D. Smokepipe is connected to chimney. E. All combustible materials are cleared away. F. Combustion air supply is provided. See page 3.
WARNING: NEVER OPERATE any natural draft* boiler (Liberty
boiler is a natural draft boiler) with zero draft or overfire pres
sure: early failure of the burner, nozzle and chamber is inevita-
ble if you do. Use a draft auge, and make sure that overfire
draft* is .02”, minimum, during all operating conditions.
* Draft is negative or suction pressure.
STARTUP (COMBUSTION TEST INSTRUMENTS MUST BE USED)
A. Make sure the boiler is installed and wired properly and is full of
water. B. Open the observation door (on the front, above the burner). C. Start the oil burner (see burner instructions for bleeding air from
oil, etc.) IMMEDIATELY, set burner air bands to obtain a bright
fire without smoke or oil stain. Set the DRAFT REGULATOR to
obtain .02” overfire draft*. Take draft reading through slot in
observation door. D. Close the observation door. Allow the burner to fire for at least
one hour total firing time, to bake out the volatile binders in the
combustion chamber before taking final combustion readings. E. By alternate adjustment of the barometric draft regulator, the
burner air regulation and head reulation devices (whichever
apply) an additional 1/8”. This should result in zero smoke with
NO raw oil on the smoke paper and a smooth light-off. DO NOT
ATTEMPT TO SET FIRE BY EYE. Flame retention burners may
appear efficient and smoke free from an inefficient 7% up to an
overly high 14% CO2. However, a very low CO2 can also result in
poor ignition and raw (unburned) oil entering the fire box. At very
high CO2, any slight decrease in air flow for any reason will
cause incomplete combustion, with high smoke and dry soot for-
mation in the fire box. F. If smoke reading is satisfactory, but CO2 can not be increased to
a satisfactory level (12% or better) or overfire draft of 0.02” W.C.
can not be obtained, check for proper sealing between sections,
between burner mounting plate and front section, seal is not
satisfactory, reseal with furnace putty or silicone with a tempera-
ture rating of at least 400˚ F. (All safety precautions indicated on
material package must be followed.) G. Once burner and draft have been set-up, then smoke, CO2
and stack temperature should be checked and recorded. If
smoke is greater than trace, review the burner instructions;
replace the nozzle if necessary. Normal smoke to be expected at
approximately 13% CO2 is zero to a trace.
CLEANING AND FILLING A NEW WATER BOILER
I. BEFORE FILLING WATER BOILER.
A. Check burner to be certain it is ready for firing. DO NOT FIRE
into an empty boiler.
B. Be prepared to heat raw water to at least 180˚F, as soon as it
is introduced into the boiler. This procedure will remove dis­solved, corrosive gases.
C. Provide drain line, with valve, from boiler. Use a bottom tap-
ping. Line and drain must be suitable for handling caustic solution.
Page 7
LIBERTY
7
lution.
II. CLEANING WATER BOILER SYSTEM
A. Prepare a boil-out solution of sodium hydroxide (caustic soda)
or tri-sodium phosphate. NOTE: Use caution in handling chemicals. Caustic soda is harmful to skin, eyes and clothing.
1. Proportions: 1lb. of either chemical per 50 gallons of system water.
2. Stir chemical in whater until dissolved and pour into the boiler through a top tapping. Replace plug.
B. Fill the entire system with water. C. Start the burner, using the start-up procedure. D. Circulate the water through the entire system. E. Vent the system, including the radiation. F. Allow boiler water to reach operating temperature, if possible. G. Continue to circulate the water for a few hours. H. Shut off the burner. I. With CAUTION, drain the boiler solution to a safe location. DO
NOT LEAVE SOLUTIONN SITTING IN SYSTEM OVER 2 HOURS.
J. Wash the water side of the boiler thoroughly using a high
pressure water stream. Fill and drain the boiler several times.
III.TREATING WATER FOR CORROSION CONTROL
(This is not Scale Control) A. Prepare a solution of sodium chromate.
Proportions: 6 oz. per 50 gallons of system water.
B. Stir chemical into water until dissolved and pour into the boiler
through a top tapping. Replace plug.
IV.FILLING AND VENTING THE WATER BOILER.
A. Refill the system with fresh water. B. Bring water temperature to at least 180˚ F promptly. C. Circulate water through entire system. D. Vent the system, including the radiation. E. The boiler is now ready to be put into service or on standby. F. If brand-name air-control devicces are used, venting instruc-
tions furnished with the devices should be followed.
V. SAFETY CHECK FOR CONTROL SYSTEM
High limit control test: Set thermostat high enough for boiler water temperature to reach high limit control setting. When this temper­ature is reached, the high limit switch should open, and the burn­er should shut off automatically. If the high limit does not operate to shut off the burner, the high limit or the wiring is faulty. Repair or replace immediately.
CLEANING AND FILLING A NEW STEAM BOILER
I. BEFORE USING STEAM BOILER.
ATER CONTENT OF BOILER (GALLONS)
W
LD-20 LD-30 LD-40 LD-50 LD-60 LD-70
ater Boiler 8.3 10.7 13.1 15.5 17.8 22.6
W Steam Boiler 6.9 8.8 10.7 12.6 14.5
VOLUME OF WATER IN STANDARD PIPE OR TUBE
Nominal
Pipe Size
Inches
Standard Steel Pipe
Schedule
No.
Inside
Diameter
Inches
Gallons
per
Lin. Ft.
Type L Copper Tube
Inside
Dia.
Inches
Gallons
per
Lin. Ft.
3/8 0.430 0.0075 1/2 40 0.622 0.0157 0.545 0.0121 5/8 0.666 0.0181 3/4 40 0.824 0.0277 0.785 0.0251 1 40 1.049 0.0449 1.025 0.0429 1 1/4 40 1.380 0.0779 1.265 0.0653 1 1/2 40 1.610 0.106 1.505 0.0924 2 40 2.067 0.174 1.985 0.161 2 1/2 40 2.469 0.249 2.465 0.248 3 40 3.068 0.384 2.945 0.354
A. Check burner to be certain it is ready for firing. DO NOT FIRE into
an empty boiler.
B. Be prepared to heat raw water to at least 180˚F as soon as it is
introduced into the boiler. This procedure will remove dissolved, corrosive gases.
C. Provide drain line, with valve, from boiler. Use a bottom tapping.
Line and drain must be suitable for handling caustic solution.
D. Check for low water cut-off operation, see section below for check
out.
II. CLEAN STEAM BOILER SYSTEM.
A. Fill the boiler to water line indicated on the boiler. B. Follow start-up procedure for burner and operate the boiler with
steam in the entire system for 2 or 3 days to bring oil and dirt from the system to the boiler. While system is in operation, maintain the
proper water level in the boiler by slowly adding wate to the boiler C. Shut down burner, cool down boiler and drain system. D. Procedure to dissolve oil and grease in boiler:
1. Fill boiler to proper water line.
2. Prepare a boil-out solution of sodium hydroxide (caustic soda) a and tri-sodium phosphate: NOTE: Use caution in handling chemicals. Caustic soda is harmful to skin, eyes and clothing.
STEAM CONTROL ASSEMBLY
Installed McDonnell & Miller 67 low water cut-off and water level gauge.
SPECIAL FLUSHING INSTRUCTIONS
Installation of new boiler may break loose a heavy accu­mulation of sediment and scale from old piping and radia­tors. It is extremely important to blow down your McDonnell Cut-off more frequently the first week.
First week - 3 times
Thereafter - at least once a week
See “CARE & MAINTENANCE” section for instructions.
Page 8
8 LIBERTY
(a) Proportions: 1lb. of each chemical per 50 gallons of
system water.
(b) Stir chemicals into water until dissolved and pour into
the boiler through a top tapping. Replace plug.
3. Start the burner; boil the water for at least 5 hours; shut off the burner.
E. With CAUTION, drain the boiler solution to a safe location.
DO NOT LEAVE SOLUTION SITTING IN SYSTEM OVER 2 HOURS.
F. Wash the water side of the boiler thoroughly using a high
pressure water stream. Fill and drain the boiler several times.
III.TREATING WATER FOR CORROSION CONTROL
(This is not scale control). A. Prepare a solution of sodium chromate.
Proportions: 1lb. per 50 gallons of boiler water.
B. Stir chemical in water until dissolved and pour into boiler
through a top tapping. Replace plug.
IV. FILLING AND VENTING THE STEAM BOILER.
A. Refill the boiler to the indicated water line. B. Bring water to boiling temperature, promptly. C. The boiler is now ready to be put into service or on standby.
LOW WATER CUT-OFF CHECK OUT
I. Electronic probe type low water cut-off. If this boiler is factory
equipped with an electronic probe type low water cut-off, operation of cut-off should be checked at least twice a year as follows: A. While boiler is running, drain down boiler water slowly through
Boiler Drain Cock shown on page 5, just until light goes on. Boiler should shut down 10 seconds after light goes on.
B. Be sure that it is the low water cut-off and not the room ther-
mostat, pressure cut-out, or other control that has shut-off the
burner. C. Refill the boiler and repeat test. D. Refill the boiler and reset controls for normal operation.
II. Float type low water cut-off
If this boiler is factory equipped with a McDonnell & Miller float type low water cut-off, the low water cut-off must be blown down (flushed), at least once a week. CAUTION: When flushing float type low water cut-off control, hot water and steam will flow out the blow down valve. Blow down valve is illustrated below. A. SPECIAL FLUSHING INSTRUCTIONS
For new boiler installed in old system.
Installation of new boiler may break loose a heavy accumula-
tion of sediment and scale from old piping and radiators. If is
extremely important to blow down your McDonnell cut-off
more frequently the first week.
First week - 3 times Thereafter - at least once a week.
B. As boiler water circulates through the float chamber, dirt or
other sediment may be deposited. This chamber is extra deep. But the only sure way to keep any accumulation from interfering with float action is to “blow down”, or flush out, the control once a week. Do it while boiler is in operation. First not water level in gauge glass. Open blow-off valve at bottom of control; water will pour out, flushing away sediment. Drain until water is clear - about a pail - then close valve. If level in gauge glass has dropped, add water to boiler to restore level.
C. NOTE: Opening blow-off valve checks cut-off operation too. as
float drops with falling water level, burner will stop. After burn­er is off and normal operating conditions restored, burner will resume firing.
D. Be sure that it is the low water cut-off and not the room ther-
mostat, pressure cut-out, or other control that has shut off the burner.
PRESSURE CONTROL CHECK-OUT
A. Check burner to be certain it is ready for firing. DO NOT FIRE
into an empty boiler.
B. Set thermostat high enough for boiler to make steam. Set the
pressure control down to its lowest setting. As the boiler starts to produce steam, the steam pressure will start to build. The burner will shut-off when the steam pressure exceeds the pressure set­ting (plus differential if control has this feature).
C. Adjust the pressure control to a higher setting. The higher setting
should be above the steam pressure in the boiler. This should turn the burner back on.
D. Reset the pressure control as needed for the system. The pres-
sure control should be checked at least twice a year.
REPLACEMENT OF STEAM BOILERS
Anytime an older steam boiler is removed from the heating system and replaced with a new boiler, there are certain conditions that have to be examined on the heating system. A. Steam systems have a tendency to develop scale inside the wet
return lines and the boiler. The older the system the greater the accumulation of scale that can exist inside the piping. Therefore, it is necessary when replacing a steam boiler to check the piping for blockage or restrictions. Clean or replace the piping as
required. (See special flushing instructions above.) B. Replace all buried wet return lines. C. All equipment (air vents, radiation equipment, etc.) in the steam
heating system should be checked for proper operation. All pip-
ing should be checked for proper pitch. D. It is good engineering practice to repack or tighten the packing.
Page 9
LIBERTY
See page 10 for other primaries.
EE: “Adjusting Settings”
S
“Error Codes” for
&
L7224C & L7248L
on page 10
9
Page 10
10 LIBERTY
a
Warni ngs are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and maintaining boile r temperature. I n the instance where an Outdoor Reset Module is us ed, the warnings may indicate a rese t curve s etting er ror one o r more fea tures is not run ning optimally, a nd the Aqua stat is reverting to defa ult settin gs or has stopped running the Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.
b
To clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition clears and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and will normally only occur near en d of life for the control. If Err 8 condition has occurred early in the co ntrols life, be sure to check for voltage feedback to B1 when B1 should be o and check current draw on b t erminal to be sure oil burner is not draw­ing excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.
A
quastat
noitcA/esuaCedoC rorrE
E
nviraCOM
Alarm
81.rosnes retaw kcehc ;tluaf rosnes tatsauqA1rrE
81.gniriw ™MOCarivnE kcehc ;tluaf MOCE2rrE
Err3Excessive electrical noise or frequency out of range. Hardware fault; replace controller. 18, 58
46.egatlov/gniriw 1B kcehc ;tluaf 1B4rrE
95.caV 011 ,2L-1L kcehc ;eniL woL5rrE
Err6
a
29.esuf ecalper ,seriw MOCE kcehc ;esuF :gninraW
A/N.seulav tluafed ot teser ;fdL ,fdH ,LL ,LH ,MORPEE :gninraW7rrE
Err 8
b
Repeated B 1 fault ( voltage presen t at B1 w hen out put is turned o); che ck B1 wiring/voltage. 25
Err9
a
Warni ng: Outdoor Reset System failure; communication to Outdoor Reset Module lost, Outdo or Rese t Module failur e, multiple outdoor temperat ure senso rs detect ed on the bus, or outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
50, 53, 149
Err 10
a
Warni ng: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive cycles. Check Outdoor Reset curve settings.
150
Err 11
a
DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure, or temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
146, 147, 148
FOR L7224C OR L7248L
ADJUSTING SETTINGS
To discourage unauthorized changing of Aquastat settings, a proce­dure to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons simulta­neously for three seconds. Press the I button until the feature requir­ing adjustment is displayed:
. HL_ . High Limit. . LL_ . Low Limit. (L7224 only) . Ldf . Low Limit Differential. (L7224 only) . °F . °C. .ELL_ External Low Limit (L7248L only)
Then press the UP and/or DOWN buttons to move the set point to the desired value, to change between ˚F and C˚, or to enable (On) or disable (Off) the External Low Limit. After 60 seconds without any button inputs, the control will automatically return to the RUN mode.
DISPLAY
In the RUN mode, the Aquastat will flash .bt. (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I High Limit (HL) is displayed, followed by a three-digit number, i.e., 220, fol-
lowed by °F or °C. Pressing the I button again (on L7224 models) will display the Low Limit (LL) followed by a three-digit number and the corresponding degree designator.
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press any key.
DESCRIPTION
Boiler Temperature –
High Limit –
Low Limit –
Low Limit Differential –
Local Thermostat Status –
Enviracom Thermostat Status –
Error Code –
Degrees Fahrenheit –
Degrees Celsius –
BASIC WIRING DIAGRAMS L8124C or A (with tankless heater)
L8148A (without tankless heater)
NOTES
1. Recomended high limit set­ting is 200˚F. Low limit must be set at least 20˚F below high limit setting.
2. Pump zone terminals ZR, ZC furnished on L8124 controls only. See pump zoning diagram below.
† Overload protection and disconnect switch must be provided as required by local codes.
Page 11
LIBERTY
FIELD WIRING FOR STEAM KNOCKED DOWN BOILER & BOILER/ BURNER UNIT EQUIPPED WITH McDONNELL NO. 67. L.W.C.O.
Low limit (tankless model only) Recommended setting - 160˚F
11
WIRING FOR PACKAGED STEAM BOILER
For alternate option PS - 801 - 120 L. W. C. O
Page 12
12 LIBERTY
ZONE WIRING DIAGRAM, CIRCULATOR METHOD (L8124, only)
ULTIPLE ZONE WIRING DIAGRAM,
M ZONE VALVE METHOD
WIRING FOR L8148A PUMP ZONE DIAGRAM
Page 13
LIBERTY
13
CARE AND MAINTENANCE
I. EXTENDED SHUTDDOWN, OR REMOVAL OF BOILER FROM
SERVICE. A. Flush sludge from bottom of boiler. While the boiler is still hot
(180˚ to 200˚F), drain water from the bottom of the boiler until it runs clear.
B. Provide corrosion protection to water (this is not scale control):
1. For steam boilers, maintain a sodium chromate solution strength of 16 oz. per 50 gallons of water; and refill to the top of the gauge glass.
2. For water boilers, maintain a sodium chromate solution strength of 6 oz. per 50 gallons of water, and refill to normal fill-pressure with system vented.
3. Raise water temperature to at least 180˚F for one hour to release dissolved gases.
4. Shut down burner by disconnecting the main switch.
C. Clean boiler heating surfaces thoroughly, down to clean metal.
1. Remove flue and clean thoroughly.
2. Remove top flue collector to facilitate cleaning soot and scale from the heating surfaces. To remove the flue collector, the top rear jacket panel must first be removed. The flue collector is held in place by a single carriage bolt and wing nut at the rear of the boiler. Remove the wing nut and pull up firmly on the rear of the flue collector tipping it forward to break the seal between it and the boiler. Then, pull it out from under the lip in the front boiler section.
3. To gain access to the combustion chamber for cleaning, the burner must be removed. The flexible electrical con­duits from the burner to the limit controls are long enough to allow removing the burner without disconnecting them. The cast iron burner mounting plate should be removed along with the burner to completely expose the combustion chamber for thorough cleaning and for inspection of the tar­get wall.
4. Use the flue brush to clean the pined flueways between the sections. A wire brush may be used to remove any carbon accumulation that may have developed in the combustion chamber. Vacuum the loose soot and debris from the boiler.
5. Inspect the refractory target wall in the rear of the combus­tion chamber. If badly deteriorated, it should be replaced. Inspect the burner combustion head. Clean if necessary a and make sure all the adjustments are correct. (See burner data pages for the burner installed.) Replace oil nozzle with a new one. To insure proper burner operation. ONLY THE NOZZLES SPECIFIED IN THIS MANUAL OR ON THE BURNER LABEL SHOULD BE USED FOR REPLACE­MENT.
6. Protect all of the fireside surfaces by swabbing with neutral mineral oil.
7. Replace burner and flue collector. In most cases, the flue collector sealant can be reused. Smooth the sealant in the groove around the top of the boiler sections and under the lip in the front section. Be sure that there are no gaps. The head of the carriage bolt fits into the slot on the top of the rear section. Insert the front edge of the flue collector under the lip on the front section. Push forward and down on the flue collector, guiding the bolt into the bracket on the flue collector. Add the washer and wing nut and tighten until a proper seal is obtained.
D. If boiler room is damp, provide ventilation.
II. PROVIDING PROTECTION FOR FREEZING
Anti-freeze is sometimes used in hydronic heating systems to protect against freeze-up in the event of power failure, or safety control shutdown when the building is unoccupied. It should be recognized that unless the building is kept above freezing temper­ature by some means, the plumbing system is not protected.
Two types of anti-freeze may be used: ETHYLENE GLYCOL, used in automobiles, has desirable properties, but is toxic. Its use may be prohibited when system water/glycol solution is in contact with a potable water vessel (as with a tankless heater). PROPY­LENE GLYCOL is used in the quick-freeze food industry; it is practically non-toxic. It use may be permitted when tankless heaters are used. When anti-freeze must be used, inhibited propylene glycol is recommended. Useful information on the char­acteristics, mixing proportions, etc. of glycol in heating systems is given in Technical Topics No 2A, available from the Hydronics Institute, 35 Russo Place, Berkeley Heights, N.J. 07922. Consult glycol manufacturers for sources of propylene glycol.
III.OIL BURNER
Inspect and clean annually and following any period of improper operation. Redcheck and adjust settings as specified for burner model and nozzle size. Set burner air and draft regulator, using test instruments to obtain recommended CO2 and draft without smoke. Refer to page 6.
IV.GENERAL MAINTENANCE
These operations are recommended to be performed at regular intervals: A. BOILER HEATING SURFACES: clean off all coatings found.
Reseal covers.
B. BOILER CONTROLS: check contacts, settings, correct func-
tioning. C. PIPING: check piping and accessories for leaks. D. CHIMNEY or STUB VENT and BREECHING: check for
obstructions and leaks. E. COMBUSTION AIR TO BURNER: check for continued POS-
ITIVE supply of air as required. Air needs are greatest in cold-
est weather. Refer to AIR SUPPLY, page 3. F. WATER SYSTEM: check
1. System to be full of water and pressure to remain stable (between 12 psi and 25 psi).
2. Air-control system: noise and air binding in radiation should not occur.
3. Water lines: slightest leaks should be corrected.
4. Low water cutoff, for operation (see instructions furnished with unit). See page 8
G. STEAM SYSTEM: check
1. Low water cutoff, for operation (see instructions furnished with unit). See page 8.
2. Check pressure cut-off for operation. See page 8.
3. Any unusual water conditions. Obtain water analysis and treat water.
H. BOILER ROOM AIR SUPPLY: air vents should be open and
free of obstruction. See page 3.
† A flue brush (2-1/4” dia.) is supplied with boiler.
Replacements are available from dealer or hardware stores.
Page 14
14 LIBERTY
Page 15
LIBERTY
15
Page 16
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Loading...