Please ask skilled service persons for reliable earthing connection
Your safety is the most important thing we concerned !
| NOTE |
|---|
|
All the picture in this manual are for explanation purpose only. They may be slightly different from the heat pump water heaterr you purchased (depand on mode). The actual shaped shall prevail. |
PAGE
| PRECAUTIONS | 1 |
|---|---|
| ACCESSORIES | 2 |
| INSTALLATION LOCATION | 2 |
| INSTALLATION | 3 |
| PIPELINE CONNECTION | 4 |
| DUCT CONNECTION WAY | 5 |
| ELECTRIC CONNECTION | 6 |
| OPERATING INSTRUCTION | 8 |
| RUNNING AND CAPABILITY | 14 |
| MAINTENANCE | 16 |
| SPECIFICATIONS | 17 |
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage.
The safety precautions listed here are divided into two categories. In either case, important safety instructions are listed to which close attention must be paid
WARNING
Failure to observe a warning may result in death or serious Iniury.
Failure to observe a caution may result in injury or damage to the equipment.
The water heating unit must be earthed effectively .
1
After a long term use, check the unit stand and fittings. If damaged, the unit may fall and result in injury.
Arrange the drain hose to ensure smooth drainpipe. Improper drainpipe may cause wetting of the building, furniture etc.
Do not touch the inner parts of the controller. Do not remove the front panel. Some parts inside are dangerous to touch, and a machine malfunction may be caused.
System will stop or restart heating automatically. A continuous power supply for water heating is necessary, except service and maintenance.
Table, 2-1
| Accessory Name | Qty. | Sharp Purpose | |
|---|---|---|---|
|
Owner's & Installation
Manual |
1 |
Installation and use instruc
This manual |
|
| Y-shaped Filter | 1 | ₽ | To filtrate inlet water |
| One Way Valve | 1 | 6 -3 |
Prevent water from
flowing back |
| Adaptor | 1 | Drain condensate water | |
A
Before installing the unit, reserve the space of maintenance shown in the following figure.
Fig.3-2
Installation 8 Owner's Manua
Pipeline Connection Sketch
When install the main unit, please set a drain valve at the drain orifice of the unit by self.
Installation & Owner's Manual
NOTE
A safety valve should be installed at the water inlet of the unit. Arrange water pipes and which connected fittings as illustration of the above figure. In case of install it at a place where outside temperature below freezing point, insulation must be provided for all hydraulic components.
•The handle of PT Valve should be pulled out once per half year, to make sure that there is no jam of the valve.
Please beware of burn, because of the high temperature of water. The drainage pipe should be well installed ,in order to avoid freezing up in cold weather.
It will cause explosion and injury, if do not comply with the above instruction.
The mainboard of machine has two dedicated ports use for connecting to the solar thermal, they are CN17 ON/OFF port and CN18 Feedback port. The ports ensure heat pump and solar thermal won't work together.
■ Among them, the CN17 ON/OFF port is used for receiving the control signal of the solar energy water heating system, this signal needs to be voltage free switch signal. When the control signal is closing signal, the heat pump system will be locked and can't open to heat; when the control signal is open circuit signal, the heat pump system will be relieved its locked state, and the unit will judge to open or shut down according to the unit's own condition.
■ The CN18 Feedback port is used to send the feed backing of open/stop situation to the solar thermal, this port feeds back the high and low level signals. When both sides of the terminal is low level (0V) for outlet, means that the heat pump unit is under open state; when both sides of the terminal is high level (5V) for outlet, means that the heat pump unit is under shut down state.
Which need to be declared is that the heat pump unit only receives and provides the above two signals, the control software needs to be wrote according to the entire water heating system control while designing the project installation.
■ Be caution, as the water tank can automatic recover temperature protection switch TCO when operating temperature is 78°C, and the operating temperature for the manual recover temperature protection switch is 85°C, when the water temperature of the solar thermal which enter the water tank coil is over heated (higher than the operating temperature of the TCO), it will lead to TCO operates and every part of the machine loads, include the power of the main control board, the display screen will be cut off, so please be sure the water temperature of the solar thermal which enter the water tank coil won't be over heated.
Fig. 6-1
Air inlet and outlet no need to connect with canvas
Note: Upon connect canvas, portion airflow and capacity in heat pump system will lose in the system.
■ Air inlet without canvas, air outlet connect to canvas. A≤10m
Fia.6-3
Recommending: Use it in where with surplus heat or indoor place in the winter where with surplus heat.
■ Air inlet and outlet need to connect with canvas. A+B≤10m
■ Air inlet connect to canvas, air outlet without canvas. A≤10m
Recommending: In summer, use this connection way could charge flesh air into room.
Canvas Duct Description
| Canvas Duct | Round canvas duct | Rectangle canvas duct | Other shaped canvas duct |
|---|---|---|---|
|
Dimension
(mm) |
Dimension ⊕190
(mm) |
||
|
Straight-line
pressure drop (Pa/m) |
≤2 | ≤2 | |
|
Straight-line
length (m) |
≤10 | ≤10 | Refer to above data |
|
Bent pressure
drop(Pa) |
≤2 | ≤2 | |
| Bent's qty. | ≤5 | ≤5 | |
V
Canvas duct to be connected at air outlet better than at inlet.
NOTE
| WARNING |
|---|
| Linen connect convex nortion cirflew and |
Upon connect canvas, portion airflow and capacity in heat pump system will lose in the system.
■ Filter installing at the main unit inlet. In terms of the main unit connect with canvas, filter in there must be put forward to the air inlet of duct. ( Fig.6-7/6-8 )
To fluently drain condensate water from evaporator, please install the main unit at a horizontal floor. Otherwise, please ensuring the drain vent is at the lowest place. Recommending the inclination angle of unit to the ground should no more than 2°.
Installation & Owner's Manual
Table. 7-1
| Model Name SWH-35/300TS | |||
|---|---|---|---|
| Power Supply | 220-240V~50Hz | ||
|
Mlin. Diameter of Power
Supply Line(mm2) |
4 | ||
| Earth Wire(mm2) | 4 | ||
| Manual Switch(A) Capcity/Fuse | 32/25 | ||
| Creepage Breaker | 30 mA ≤0.1sec | ||
Just to be on the safe side, the unit must be installed an Creepage Breaker near the power supply and must be effectively earthed.
T3: Tube Temp. Sensor T4: Ambient Temp. Sensor T5U: Tank Temp. Sensor (upper) T5L: Tank Temp. Sensor (lower) TP: Discharge Temp. Sensor(upper) TH: Return air temperature sen
Before using this unit, please follow the steps below.
Water Affusion: If the unit is used for the first time or used again after emptying the tank, please make sure that the tank is full of water before turning on the power. Method: see Fia.7-1
Operation without water in water tank may result in damage of auxiliary e-heater. Due to such damage, the supplier is not responsible for the quality issue.
After powered on, the display lights up. Users can operate the unit through the buttons under the display for different modes
Over 50°C may result in serious burn or so caused death. Special care should be paid to the children, the disabled and the old in case of water burn
Emptying: If the unit needs cleaning, moving etc, the tank should be emptied. Method: See Fig.8-2 :
1 Control Panel Explanation
Fig.8-3
2 Display Explanation
| 1 | HIGH TEMP indicator: When the setting temp. exceeds 50°C, it lights up to remind you that the outlet temp. is too high for direct spray. |
|---|---|
| 2 | FILL WATER indicator: When the power supply is turned on, it lights up to remind you to re-affuse water. |
| 3 | ALARM indicator: It will flashing at the malfunction or protection time. |
| 4 |
TEMP-SET indicator: Show the setting temperature and
blank when screen protection. Codes are show at the malfunction or protection time |
| 5 | LOCK indicator: When the UI is locked, it always lights. |
| 6 | Water temp. indicator: When the actual water temp. exceeds 60°C, it lights up. |
| 7 | Water temp. indicator: When the actual water temp. exceeds 50°C, it lights up. |
When you run the unit for the first time, all the indicators on the UI will light for 3 second, and the buzzer will "didi" ring twice at the same time, and then, display the fiducial web page. After no operation for 1 minute, all indicators will go out automatically except Water fill indicator flashing and tank's temp. indicator lighting. Buzzer will "di" ring when you press it.
When the tank is full, please press the ON\OFF key, the Water fill indicator will stop flashing and you can continue to function other settings. When all settings finished, please press the ON\OFF key again and the Water fill indicator will go out. And then run the unit.
When the unit is running, if there is no operation or malfunction for 20s, the backlight of the display will go out automatically except operation model,outlet temp.lock indicator.
If there no operation for 1min, the unit will lock automatically. but the lock indicator would be right all time.
Disinfection mode- unit will automaticly run disinfection mode every Friday at 23:00PM.
Display panel indicates this mode by showing "CL"
In order to prevent wrong operation, a special lock function has been designed. If there is no operation for 1min, the unit will be locked automatically, and display the lock indicator . When the unit is locked, no keys can be operated.
Unlock
Fia.8-6
The clock is for a 24-hour system and the initial time is 00:00. To make a better use of this unit, it is recommended to set the time for accurate local time. Every time powered off, the clock will be reset to the initial time 00:00.
Method for time set
Fig.8-7
Temp. Set
Temp displayed is the water temp. in the upper part of the tank. Default is 55°C and the Economy mode setting range is 38~60°C, the Hybrid and E-heater mode setting range is 38~60°C.
Method for set
Fig.8-9
Fig.8-10
Fig.8-11
Cancel:
Timer
User can set up a running start time and a stop time on a specifically by the timer function. The least numbers of timer is ten minutes.
Time on: User can set up a start time by this. The unit will auto run one time between the set time and 24:00 on the same day. Method for set
|
Stop operation for about 10s, flashing
stops and TIME ON+TIME OFF set is finished. |
|
|---|---|
| 88:88 | |
| Fig.8-13 | |
| Cancel |
Fig.8-14
Time on and Time off can not be set to the same time. If they are the same, the stop time will delay 10 minutes automatically. For example, Time on and Time off set to 1:00 at the same time, then the stop time will adjust to 1:10 automatically.
NOTE
Time off function can not be used alone. The key can be used only after setted the on time. User can press the on\off key manual beyond the timer range.
Power On and Power Off
Press Power On/Power Off button after all the above have finished and the system will run as the setting. And simply press the same button to stop it.
Fia.8-15
• The LA code from the screen of set Temp. will appear and remind user when ambience temp. not meet the operation condition of heat pump unit(beyond -7~43°C), User can switch the economy mode to E-heating mode in sure of enough volume of hot water if need, The unit will return operation pre-status automatically in no any operation when the ambience temp. meet the operation condition of heat pump mode and the error LA will be disappear at the same time,the screen display nomally.
Installation & Owner's Manual
In case of continual 20 hours when in the season ambient temperature doesn't meet for the heat pump operation requirement (absent from the range -7~43°C), "LA" will display at Temp. Settings window and ALARM indicator flashing simultaneously alarming that the temperature doesn't suit for heat pump performance, only E-heating mode could be set at such circumstance. Please switch to E-heating mode manually for ensuring there's adequate hot water could be supplied, if that so code is going to disappear and indicator alarm stop flashing any more, all recover to be normal.
Fig.8-17
Fig.8-18
Fig.8-19
The error code from the screen of set Temp. will display when malfunction happen, the system display error code after one minute when press the key again and the screen display set temp.
Fia.8-20
When the economy mode happen malfunction, the system can keep using after switching to E-heater mode; When some error happens, though the system could be used in some circumstances, it could not reach the expected efficiency. Please contact your supplier for help.
Error Code Explanation (See table. 8-20)
The covers of the E-heater should not be opened
without guidance of professional technician, in case of electric shock or any danger.
Table 8-2
| Display | Malfunction Description | ||
|---|---|---|---|
| E0 | Error of sensor T5U | ||
| E1 | Error of sensor T5L | ||
| E2 | Tank and Wired Controller communication error | ||
| E4 | Evap. pipe temperature sensor error | ||
| E5 | Ambient temperature sensor error | ||
| E6 | Discharge pipe temp.sensor error | ||
| E7 | Heat Pump system error | ||
| E8 | Electric leakage protection | ||
| E9 | TH sensor condenser failure | ||
| P1 | System high pressure protection | ||
| P2 | Discharge pipe temperature overhigh protection | ||
| P3 | No current flowing in Compressor | ||
| P4 | Compressor overloaded protection | ||
| P8 | No current flowing in electric heater | ||
| P9 | Upper e-heater overloaded protection | ||
| LA | Ambient temp. is not fit for heat pumps, change the mode to E-heater mode | ||
If the errors happen, please contact the supplier or after-sale service.
Fig.9-1
(Water outlet temp. range 38~60 °C, running ambient -30~43 °C)
Installation & Owner's Manual
E-heater Mode: In this mode, the compressor and the fan motor will not run but the e-heater work only. (Water outlet temp. range 38~60°C, running ambient -30~43)
°C ).
| NOTE |
|---|
In the E-heat mode, only half tank of water, i.e. 150L, could be heat every time.
The system's operation temperature is within -30~43°C and below are the operation temperature for each mode.
1) Economy Mode: -7~43℃
This mode should be used at the ambient temperature maintaining at -7~43°C. While the ambient temperature below than -7°C, the energy efficient would bocome low obviously, we recommend you to using the E-heat mode at this circumstance.
2) Hybrid Mode: -30~43°C
3) E-heater Mode: -30~43°C
Mode Selection
Different mode is designed to meet different demand and the following are recommended selections.
When self-protection happens, cut the power supply manually and restart after the error resolved.
NOTE
3-min Protection
With the power supplied, an immediate restart after the shutting down will have to wait 3 min as to protect the compressor.
When it is humid and cold, the evaporate may defrost and the water-heating capacity decrease. And the system will stop heating water and start defrosting and then restart water-heating
Table. 10-1
| Malfunction | Cause | Resolutions |
|---|---|---|
|
Outlet water
is cold. The display is dark. |
|
|
|
No hot
water from the outlet. |
|
|
|
Water
leakage |
The joints on the pipeline are not sealed well. | Check and reseal all the joints. |
If the unit runs to some malfunction or error, it should be shut down and power supply cut off. And then please contact your local service center or supplier for help.
Table. 11-1
| Model | SWH-35/300TS | ||||||
|---|---|---|---|---|---|---|---|
| Mode | Economy Mode | Hybrid Mode | E-heater Mode | ||||
| W | ater-heating cap. | 3000W | 3000W | 3000W | |||
| R | ated power/AMPS | 1500W/6.5A | 4300W/18.7A | 3000W/13.0A | |||
| Power supply | 220-240V~ 50Hz | ||||||
| C | Dperation control | Auto/Man | ual startup, error alarm | ı, etc | |||
| Protection |
High-pressure Pro
Temp Controller&I |
tector, Over-load Prot
Protector, Electric Lea |
ector,
kage Protector, etc |
||||
| С | ompressor power | 850W | |||||
| E-heater power | 3000W | ||||||
| Regrigerant | R134a(1200g) | ||||||
| Outlet water temp. | Default 55°C,(38-60°Cadjustable) | ||||||
| Water side exchanger | Surface heat exchanger | ||||||
| Inlet pipe Dia. | DN20 | ||||||
| tem | Outlet pipe Dia. | DN20 | |||||
| sys | Solar water outlet | DN20 | |||||
| eline | Solar water inlet | DN20 | |||||
| ır pip | Drain pipe Dia. | DN20 | |||||
| Nate | PT valve Dia. | DN20 | |||||
| Max. pressure | 1.0MPa | ||||||
| Jer | Material | Hydrophilic aluminum fin, inner groove copper tube | e copper tube | ||||
|
chang
side |
Motor power | 80W | |||||
|
Exo
air : |
Outlet air type | , | /ertical upflow air sup | ply | |||
| Dimension | Ф650×1920mm | ||||||
| W | ater tank cap. | 300L | |||||
| Net weight | 123kg | ||||||
| Fu | sible link type | T5A 250VAC | |||||
|
The test conditions:
Test temperature 15/12℃(DB/WB), Water temperature from 15℃ up to 45℃. |
|||||||
Icon on the product or in the accompanying documentation means that used electric or electronic products must not be disposed together with domestic waste. For the correct disposal of the product hand it over to a place for take-back, where it is collected free of charge. By correct disposal of the product you can help to preserve valuable natural resources and help in preventing potential negative impacts to environment and human health, which could be consequence of incorrect disposal of waste. Ask for more details from local authorities, nearest collection point, in Waste Acts of respective country, in the Czech Republic in Act no. 185/2001 Coll., in the wording of later regulations. In case of incorrect disposal of this waste, a fine can be imposed according to national regulations.
Manufacturer: Sinclair Corporation Ltd., 1-4 Argyll Street, London W1F 7LD, UK
Supplier and technical support: Nepa, spol.s.r.o. Purkyňova 45 612 00 Brno Czech Republic www.nepa.cz
Toll-free info line: +420 800 100 285






















Loading...