Sierra Max-Trak 180+ Compod Series Instruction Manual

Model 180 + Compod™
Programmable Control Module For
180 Series Digital Mass Flow Meters & Controllers
Instruction Manual
IM- 180 COMPOD
CORPORATE HEADQUARTERS
5 Harris Court, Building L, Monterey, CA 93940 USA
Phone (831) 373-0200 (800)-866-0200 Fax (831) 373-4402
www.sierrainstruments.com
EUROPEAN HEADQUARTERS
Bijlmansweid 2 1934RE Egmond aan den Hoef
The Netherlands
Phone +31 72 507 1400 Fax +31 72 507 1401
ASIA HEADQUARTERS
Rm. 618, Tomson Centre, Building A, 188 Zhang Yang Road
Pu Dong New District, Shanghai, P. R. China
Phone: +86 21 5879 8521 Fax +8621 5879 8586
Compod™ Instruction Manual IM-COMPOD Rev. C 1
IMPORTANT CUSTOMER NOTICE
Sierra Instruments, Inc. is not liable for any damage or personal injury, whatsoever, resulting from the use of Sierra Instruments standard mass flow meters or controllers for oxygen gas. You are responsible for determining if this mass flow meter or controller is appropriate for your oxygen application. You are responsible for cleaning the mass flow meter or controller to the degree required for your oxygen flow application.
© COPYRIGHT SIERRA INSTRUMENTS 2010
No part of this publication may be copied or distributed, transmitted, transcribed, stored in a retrieval system, or translated into any human or computer language, in any form or by any means, electronic, mechanical, manual, or otherwise, or disclosed to third parties without the express written permission of Sierra Instruments. The information contained in this
manual is subject to change without notice
.
TRADEMARKS
Compod™, Smart-Trak®, and Dial-A-Gas™ are trademarks of Sierra Instruments, Inc. Other product and company names listed in this manual are trademarks or trade names of their respective manufacturers
.
Compod™ Instruction Manual IM-COMPOD Rev. C 2
INTRODUCTION
The Model 180 + Compod™ is a Modbus add-on module for the Sierra Instruments’ Smart-Trak® Model 180 gas flow measurement and control instruments.
A variety of features enable the integration of the Smart-Trak® into a Modbus network environment. Among these features:
Access to all vital data
Totalizer
Alarm output
Analog inputs
Smart-Trak® functionality monitor
SAFETY INFORMATION
Caution and warning statements are used throughout this manual to draw your attention to important information.
Caution!
This statement appears with information that is important for protecting your equipment and performance. Read and follow all cautions that apply to your application
!
!
TIP
TO FULLY UNDERSTAND THE MODEL 180 + COMPOD™ AND ITS FUNCTIONS IT IS ADVISED TO ALSO READ
THE SMART-TRAK® SERIES 180 INSTRUCTION MANUAL
Warning!
This statement appears with information that is important to protect people and equipment from damage. Pay very close attention to all warnings that apply to your application
a
Compod™ Instruction Manual IM-COMPOD Rev. C 3
ELECTRICAL CONNECTIONS
All electrical connections are made on the terminal board. There are two screw terminals which give access to input power, network interface and other options.
PIN CONFIGURATION
Terminal board overview:
Pin layout:
Pin Function Pin Function
1 +24V Power 9 Note 1 2 Ground 10 Note 1 3 Earth 11 RS232-RX (in) 4 Set point input 12 RS232-TX (out) 5 4-20mA output 13 Ground 6 Alarm output 14 RS485 7 Analog channel 1 15 RS485 –B 8 Analog channel 2 16 RS485 Shield
During power-up or reset the Modbus ID pins are scanned. These pins set the Modbus ID code.
ID3 ID2 ID1 ID0 Modbus ID
open open open open Internal ID open open open closed 1 open open closed open 2 open open closed closed 3
- - - -
closed closed closed closed 15
(Place jumper to enable)
P1
A
Closed
Open
Compod™ Instruction Manual IM-COMPOD Rev. C 4
Note 1: The terminal connections are used for optional interfaces (HART) which can be added. Please contact Sierra Instruments for more information.
RS485 CONNECTION
CONNECTION
Pin 14 = RS485 – A
Pin 15 = RS485 – B
Pin 16 = RS485 – Shield
THE MODEL 180 + COMPOD™ IS EQUIPPED WITH AN OPTICAL ISOLATED RS485 INTERFACE. DON’T CONNECT THE RS485 SHIELD TO THE GROUND OF THE POWER SUPPLY UNLESS THE ISOLATED BARRIER
!
ISN’T REQUIRED
GENERAL 2-WIRE TOPOLOGY RS485 NETWORK
The “RS485 – A” (also referred as ‘-‘) is connected with the D0 line. The “RS485 – B” (also referred as ‘+‘) is connected with the D1 line. The shield is connected to the common line of the network.
Compod™ Instruction Manual IM-COMPOD Rev. C 5
A maximum of 32 devices is authorized on an RS485 system without the need of a repeater.
Cable
It is recommended to use a twisted pair type of cable (reduces radiated and received EMI). Category 5 cables may be used to a maximum length of 600 meters. To operate at cable lengths of 1000 meter it is advised to use AWG 26 or lower.
Terminator
Reflections in a transmission line can cause communication errors. To minimize the reflection it is required to place terminator resistors at both ends of the cable. Never place a terminator resistor somewhere along the cable. The use of line terminators depends on cable lengths and should be determined on site. Typical values for terminator resistors are 120 ohm (0.5 W).
Line Polarization
In noise environments it may be necessary to polarize the lines to ensure that the receivers stay in a constant state when no signal is present. The polarization must be implemented at one location for the whole bus. The value for the pull up and pull down resistors is between 450 and 650 ohms (a higher value permits more devices to be connected to the bus).
ANALOG INPUTS
The analog inputs can be used to connect various transducers (temperature, pressure etc.). Maximum input range is 0-10 Vdc or 0-40 mA. Various options can be set through the Modbus control register (40025).
CONNECTION
Pin 2 = Ground
Pin 7 = Analog input 1
Pin 8 = Analog input 2
V1
V2
Compod™ Instruction Manual IM-COMPOD Rev. C 6
COMMUNICATING
Once the Model 180 + Compod™ is wired to the network and powered up it is time to communicate with it. The settings for the Modbus interface are as following:
ID code = 255 (or 1 – 15 depending on the ID pin settings)
Baud rate = 19200
Parity = Even
Number of bits = 8
Stop bit = 1
Delay between receiving and transmitting = 2 ms
The above settings are factory defaults and can be changed. Changing the settings can be done through the boot loader or special registers.
POWER UP
When powering up the red LED (labeled: Net) will light up after 2 seconds indicating the initialization phase. During this time data is retrieved from the Smart-Trak® and stored into the Model 180 + Compod™ memory. There is no communication through Modbus possible at this stage.
Once all data is retrieved the red LED goes off and the green LED (labeled: Active) will start blinking as it receives data from the instrument. Communication through Modbus is possible now.
If the communication with the instrument is lost for some reason, the Compod™ will try to establish it again. During this phase the Modbus interface will not be active.
The red LED will light up every time a network message is received with the correct ID code.
DATA FORMAT VARIOUS REGISTERS
32 bit real: IEEE 754 floating point, low word first
BCD encoded: hex encoded decimal values f.i. 0x89 = decimal 89
8 & 16 bits int: unsigned integer values
16 bits ASCII: ASCII encoded characters, high word = 1
Compod™ Instruction Manual IM-COMPOD Rev. C 7
st
character. 0x4944 = “ID”
Loading...
+ 16 hidden pages