Siemens ZN-31U Operation And Installation Instructions Manual

Operation and Installation Instructions
Model ZN-31U Dual Contact Zone Module
Operation
The Model ZN-31U Dual Contact Zone mod­ule is designed to provide two detector line circuits incor­porating contact type devices and a similar output for zone trouble. The contact type devices may be manual stations, waterflow switches, thermal detectors, relay contacts, etc.
The yellow LED trouble lamps (one for each circuit) will il­luminate should a break occur in the detector lines. Such a condition will initiate a system Trouble signal. The yel­low LED Trouble Indicators will be extinguished upon res­toration of circult integrity or upon receipt of any system alarm.
Note: In the event of an AC power failure and standby battery operation, the LED Trouble Indicator is not operative.
Both red and yellow LEDs can be lamp tested from the system control panel.
Installation
1. Mount the module to the horizontal mounting brackets in the control enclosure.
2. Install the Model JA-5 (5 in long) bus connector cable assembly between receptacle P2 of the module and receptacle P1 of the module or control panel immedi­ately preceding it in the bus.
3. Modules are to be bus-connected from right to left. For
4. If a module is the last module in the system, install either
5. Wire the circuit(s) as described in the CP-35 Control
6. If a supplementary relay module, annunciator, or other
Wiring Test
Refer to the CP-35 Control Panel Instruction Manual, Installa­tion and Wiring.
Troubleshooting
Refer to Troubleshooting the System, in the Instruction Manual for the Control Panel (P/N 315-085063).
1. An open or high line resistance will cause trouble.
2. Check open lines for 5.6K ohms end of line device (EL-31),
Fire Safety
Note: If the preceding module is on another row in the enclosure, a JA-24 (24 in long) bus connector cable assembly will be required.
two-row enclosures, the modules in the lower row are to be connected from left to right. Succeeding rows are to be alternately connected, right to left, left to right, etc.
a JS-30 (30 in long) or JS-64 (64 in long) bus connector assembly from the unused receptacle of the last module to terminal 41 of the CP-35 control panel. This completes the module supervision circuit.
Panel Instruction Manual, (P/N 315-085063), Installation and Wiring. Refer to the Wiring illustration.
Note: If a zone is not used, the EOL device should be connected to the alarm initiating circuit terminals 2 and 3 (Zone 1) or 4 and 5 (Zone 2) of the
module.
output module is used, then the alarm outputs, terminals 1 (Zone 1) and 6 (Zone 2), should be connected to these units.
approximately 6mA supervisory current.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-086275-3
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
P/N 315-086275-3
Loading...