Siemens ZIC-8B Installation Instructions Manual

HNET/CAN
Installation Instruct ions Model ZIC-8B
Zone Indicating Card
INTRODUCTION The Model ZIC-8B from Siemens Industry, Inc., is a zone
indicating card that provides notification appliance circuits for the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system. It has 8 outputs that can be configured as Class B only for control of audible and visual notification appliances such as horns, speakers, bells, strobes, etc.
Each zone can be configured independently for different usages as programmed in the Zeus tool and can be controlled automatically by program logic or manually using the PMI/ PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modu­lar), FCM2041-U3 (Cerberus PRO Modular). Installation of a ZIC-2C Zone Indicating Card on the ZIC-8B gives it two channel audio capability.
The ZIC-8B supports synchronized and non-synchronized strobes. This selection is available in the Zeus tool under the detail properties for each ZIC-8B circuit. Synchronization across multiple ZIC-8B cards is automatic as a part of the FireFinder­XLS/Desigo Fire Safety Modular/Cerberus PRO Modular operating characteristics. Refer to document P/N 315-096363 for a list of strobes that support synchronization.
ZIC-8B
RESET
POWER
CARD FAIL
CAN FAIL
HNET FAIL
GND FAULT
ZONE 1 ACTIVE
TRBL
ZONE 2 ACTIVE
TRBL
ZONE 3 ACTIVE
TRBL
ZONE 4 ACTIVE
TRBL
ZONE 5 ACTIVE
TRBL
ZONE 6 ACTIVE
TRBL
ZONE 7 ACTIVE
TRBL
ZONE 8 ACTIVE
TRBL
HUNDREDS
Features ZIC-8B features are as follows:
Class B circuit configuration
Zones can be configured independently
Can have independent input source for
Zone input voltage supervision per input (DC only)
Zone output supervision
Intelligent self-restoring power limiting
Coded signal synchronization capability
Card level Ground Fault detection
Communicate H-Net protocol
Uploadable firmware update
Ability to pass through up to 2A per output circuit
P/N 315-048670-11
(See Note on Restrictions, page 2)
every 2 outputs
Building
TENS
ONES
Figure 1 ZIC-8B Zone Indicating Card
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
RESTRICTIONS
Each zone input supplies power to two adjacent zone outputs as follows:
Zone Input Zone Output
1 1 and 2 2 3 and 4 3 5 and 6 4 7 and 8
Adjacent associated output zones must have the same usage. Each output must not draw greater than 2A@24 VDC. During system test be sure to activate each zone output pair to ensure that the maximum zone input current is not exceeded.
When any of the ZIC-8B output circuits are used for speakers the following rules apply:
1. The output circuits are available in two groups, 1-4 and 5-8.
2. Either output group can be used for speakers or NACs.
3. Each output circuit in an output group must have the same usage.
4. Unused output circuits must not be configured in Zeus.
5. Zone inputs 1-2 feed output circuits 1-4.
6. Zone inputs 3-4 feed output circuits 5-8.
OPERATION The ZIC-8B contains eight Class B circuits. Each circuit is rated at 2A at 24VDC and
has an input connected to the power source and an output where the NAC devices are connected. The zone inputs are isolated from one another and are supervised for the presence of power. This allows the use of different power sources with different ground references. The zone output is supervised for open and short circuit condi­tions while the zone is inactive and allows different combinations of output configura­tions (standard NAC, speakers, etc.) per card. Each ZIC-8B card occupies any one card slot in the CC-5/CC-2 cardcage. The ZIC-8B also has the capability to detect ground fault on its zone output as indicated by a diagnostic LED. (See Note above.)
Controls and Indicators The front panel of the ZIC-8B contains one reset switch, twenty-one LEDs, and three
HNET address switches as shown in Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch re-initializes the ZIC-8B operation.
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates that power for the ZIC-8B is applied to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indicates
that the card microprocessor has failed.
CAN FAIL (Yellow) Normally OFF. When illuminated, indicates
that the CAN communication with the ZIC-8B has terminated and the card goes into degrade mode (applicable only when card resides in a CAN network). NOT USED
for FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular applications.
HNET FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the HNET communication with the ZIC-8B has terminated and the card goes into degrade mode (applicable only when card resides in the HNET network).
Siemens Industry, Inc. Building Technologies Division
P/N 315-048670-112
GND FAULT (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected either a negative or positive ground fault on its field wiring.
ZONE 1 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 1 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 1 (open circuit or short circuit) or Zone 1 is disarmed.
ZONE 2 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 2 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 2 (open circuit or short circuit) or Zone 2 is disarmed.
ZONE 3 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 3 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 3 (open circuit or short circuit) or Zone 3 is disarmed.
ZONE 4 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 4 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 4 (open circuit or short circuit) or Zone 4 is disarmed.
ZONE 5 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 5 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 5 (open circuit or short circuit) or Zone 5 is disarmed.
ZONE 6 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 6 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 6 (open circuit or short circuit) or Zone 6 is disarmed.
ZONE 7 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 7 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
Siemens Industry, Inc. Building Te chnologies Division
cates that the ZIC-8B has detected a trouble on Zone 7 (open circuit or short circuit) or Zone 7 is disarmed.
P/N 315-048670-113
ZONE 8 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 8 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-8B has detected a trouble on Zone 8 (open circuit or short circuit) or Zone 8 is disarmed.
Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the ZIC-8B.
Output Zones The ZIC-8B output zones can be configured as 25V or 70V speaker zones or for the
following standard NAC Zone usages:
Steady
Strobe (Synchronized or Unsynchronized)
Zone Coding
Temporal Code
Temporal 4, when used with Audible Base SBGA-34
March Time 120
March Time 60
March Time 30
Canadian 2 stage - 30
Canadian 2 stage - 120
Sync Horn Strobe
Programming Options In order to perform its intended operation, the ZIC-8B card must be programmed
using the Zeus Programming Tool. The ZIC-8B card and its Out Ckt properties must be set prior to normal operation.
In the Zeus Programming Tool, highlight the selected ZIC-8B card in the Physical View and open the Detail View - Properties to modify and/or define the following ZIC-8B card properties:
HNET Address This address must match the address
set in ZIC-8B hardware.
Base Language Custom Message The message associated with ZIC-8B card.
Alternate Language Custom Message The message associated with ZIC-8B
card in an alternate language.
ZIC CARD 24V Power Source Select back plane or screw termnals.
ZIC-2C Card Installed Check if ZIC-2C card is installed.
Each ZIC-8B card is subdivided into eight output circuits that can be programmed independently. In the Zeus Programming Tool, highlight the selected ZIC-8B Output Ckt in the Physical View and open the Detail View - Properties to modify and/or define the following ZIC-8B output circuit properties:
Device Address Shows preset address of ZIC card output.
Base Language Custom Message The message associated with the ZIC-8B
Siemens Industry, Inc. Building Technologies Division
output circuit.
P/N 315-048670-114
Loading...
+ 8 hidden pages