INTRODUCTIONThe Model ZIC-4A from Siemens Industry, Inc. is a zone
indicating card that provides notification appliance circuits
for the FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular system. It has 4 outputs that can
be configured for Class A or Class B and control of audible
and visual notification appliances such as horns, speakers,
bells, strobes etc. Its outputs can also be configured as
connection to Municipal Tie, Releasing Service per NFPA
13 and 2001 or as a connection to a Leased Line remote
monitoring circuit.
Each zone can be configured independently for different
usages as programmed in the Zeus tool and can be
controlled automatically by program logic or manually
using the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo
Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular). During the initial power-up condition, each
zone on the ZIC-4A is configured as a steady NAC, Class
A configuration with 2A current limit. The ZIC-4A then
sends a message to the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) indicating that it is
unconfigured.
ZIC-4A
RESET
POWER
CARD FAIL
CAN FAIL
HNET FAIL
GND FAULT
ZONE 1 ACTIVE
TRBL
ZONE 2 ACTIVE
TRBL
ZONE 3 ACTIVE
TRBL
ZONE 4 ACTIVE
TRBL
The ZIC-4A supports synchronized and non-synchronized
strobes. This selection is available in the Zeus tool under
the detail properties for each ZIC-4A circuit. Synchronization across multiple ZIC-4A cards is automatic as a part of
the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular operating characteristics. Refer to document P/N 315-096363 for a list of strobes that support
synchronization.
FeaturesZIC-4A features are as follows:
•Class A / Class B circuit configuration
•Zones can be configured independently
•Can have independent input source for each output
•Zone input voltage supervision
•Zone output supervision
•Intelligent self-restoring power limiting
•Coded signal synchronization capability
•Card level Ground Fault detection
•Communicate H-Net protocol
•Uploadable firmware update
•Ability to pass through up to 3A per circuit
P/N 315-033050-15
Building Building
Building
Building Building
HUNDREDS
TENS
ONES
Figure 1
ZIC-4A Zone Indicating Card
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
OPERATIONThe ZIC-4A contains four Class A circuits. Each circuit is rated at 3A at 24VDC and
has an input connected to the power source and an output where the NAC devices,
Municipal Tie, Releasing service and Leased Line remote monitoring device are
connected. The zone inputs are isolated from one another and are supervised for the
presence of power. This allows the use of different power sources with different
ground references. The zone output is supervised for open and short circuit conditions while the zone is inactive and allows different combinations of output configurations (Standard NAC, Releasing, etc.) per card. Each ZIC-4A card occupies any one
card slot in the CC-5 cardcage. The ZIC-4A also has the capability to detect ground
fault on its zone output as indicated by a diagnostic LED.
Controls and IndicatorsThe front panel of the ZIC-4A contains one reset switch, thirteen LEDs, and three
HNET address switches as shown in Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch
re-initializes the ZIC-4A operation.
The LEDs follow the reset switch and their functions are defined as follows:
POWER(Green)Normally ON. When illuminated, indi-
cates that power for the ZIC-4A is
applied to the card.
CARD FAIL(Yellow)Normally OFF. When illuminated, indi-
cates that the card microprocessor has
failed.
CAN FAIL(Yellow)Normally OFF. When illuminated, indicates
that the CAN communication with the
ZIC-4A has terminated and the card goes
into degrade mode (applicable only when
card resides in a CAN network). NOT
USED for FireFinder-XLS/Desigo Fire
Safety Modular/Cerberus PRO Modular applications.
HNET FAIL(Yellow)Normally OFF. When illuminated, indi-
cates that the HNET communication with
the ZIC-4A has terminated and the card
goes into degrade mode (applicable only
when card resides in the HNET network).
GND FAULT(Yellow)Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected either
a negative or positive ground fault on its
field wiring.
ZONE 1 ACTIVE(Red)Normally OFF. When illuminated, indi-
cates that Zone 1 is active.
TROUBLE(Yellow)Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 1 (open circuit or short
circuit).
ZONE 2 ACTIVE(Red)Normally OFF. When illuminated, indi-
Siemens Industry, Inc.
Building Technologies Division
cates that Zone 2 is active.
P/N 315-033050-154
TROUBLE(Yellow)Normally OFF. When illuminated, indi-
96 PIN DIN
PLUG CONNECTOR
S4
S1
P1
P2
P3
P4
S2
S3
On
1
4
3
2
RESET
SWITCH
LEASED LINE
SELECT
ZONE INPUT
SUPR ENABLE
NETWORK
ADDRESS
S6
S7
1
4
5
6
2
3
1
4
5
6
2
3
1
4
5
6
2
3
1
4
5
6
2
3
S5
INPUT
POWER
SELECT
EXT
POWER
BP
POWER
cates that the ZIC-4A has detected a
trouble on Zone 2 (open circuit or short
circuit).
ZONE 3 ACTIVE(Red)Normally OFF. When illuminated, indi-
cates that Zone 3 is active.
TROUBLE(Yellow)Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 3 (open circuit or short
circuit).
ZONE 4 ACTIVE(Red)Normally OFF. When illuminated, indi-
cates that Zone 4 is active.
TROUBLE(Yellow)Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 4 (open circuit or short
circuit).
Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the ZIC-4A.
PRE-INSTALLATIONThe following components must be set prior to inserting the card to the CC-5 (refer
to Figure 2):
S1 Primary Bell Follower Select Switch:
This switch selects Zone 1 as the Primary
Bell Follower. Toggle the S1 switch
towards the bottom of the board if Zone
1 is configured as a Primary Bell Follower;
otherwise toggle it to the top of the
board for normal operation (as shown in
Figure 2.)
S2, Leased Line Select Switches: These
switches select the zones configured for
Leased Line application. Toggle each
switch to the ON position if the corresponding zone is configured as Leased
Line. If the zone is not configured as a
Leased Line application, the corresponding zone switch must be set to the OFF
position.
During card failure, Zone 1 and Zone 2
outputs will activate if the FireFinderXLS/Desigo Fire Safety Modular/Cerberus
PRO Modular Alarm bus is asserted,
Zone 3 outputs will activate the if the
FireFinder-XLS/Desigo Fire Safety
Siemens Industry, Inc.
Building Technologies Division
Modular/Cerberus PRO Modular Trouble
Bus is asserted. You must configure each
zone to the proper Leased Line remote
monitoring circuit.
Silver line on S1 and jumpers P1 and
P4 indicates normal operation.
Figure 2
ZIC-4A Switch Location
P/N 315-033050-155
HNET
S2-SW1: Set to ON if Zone 1 usage = Leased Line, Alarm Default only
S2-SW2: Set to ON if Zone 2 usage = Leased Line, Alarm Default only
S2-SW3: Set to ON if Zone 3 usage = Leased Line, Trouble Default only
S2-SW4: Set to OFF: Not Used
S3, Reset Switch: Momentarily Closed switch that when pressed will initiate a hard
reset to the ZIC-4A (similar to a cold boot).
S4, S6, S7 Network Address Switch: Set the three-digit HNET network address for
the ZIC-4A using the three rotary dial address switches located near the bottom of
the front panel. (Refer to Figure 1 for the location of the switches.) The address for
the ZIC-4A must be the same as the address selected for it in the Zeus Programming
Tool. To set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 123, set the pointer for the
HUNDREDS dial to “1”, set the pointer for the TENS dial to “2”, and set the pointer for
the ONES dial to “3”. The range of allowable addresses is from 001 to 251 (leading
zeros must be used).
S5 Input Power Select: This switch selects the source of voltage input to power the
ZIC-4A. BP Power indicates that the input is derived from the backplane of the CC-2/
CC-5 and EXT Power indicates that the input is derived from E5/E11 terminal of the
CC-2/CC-5, normally connected to non-power limited output of the PSC-12/PSX-12. It
is important to take into account the source of the voltage during battery calculations.
P1, P2, P3, P4 Shunt Headers, NAC Input Supervision Enable: These headers
select the NAC input zone supervision. If usage application is set for speaker function, place the shunt jumpers of the corresponding zone between 1—2 and between
5—6, otherwise place the shunt jumpers between 1—3 and 4—6.
P1 selects NAC input supervision for Zone 1
P2 selects NAC input supervision for Zone 2
P3 selects NAC input supervision for Zone 3
P4 selects NAC input supervision for Zone 4
Output ZonesThe ZIC-4A can be configured for the following usages:
Standard NAC Zone - Configurable as the following NAC zones:
SteadyStrobe (Synchronized or Unsynchronized)
Zone CodingTemporal Code
Temporal 4, when used with Audible Base SBGA-34
March Time 120March Time 60
March Time 30Horn / Strobe
Releasing Zone - For release of FM-200, Halon, Pre-action & Deluge Sprinklers for
Canada or USA. Releasing zone requires an REL-EOL module for proper wire supervision.
Municipal Tie - Configurable as a supervised connection to municipal tie. Municipal
Tie usage application requires the LLM-1 interface module.
6
4
2
5
3
1
Leased Line - Configurable as a connection to a remote monitoring system. Leased
Line usage application requires LLM-1 interface module.
Bell Follower Primary - Configurable as a Bell Follower Primary (Zone 1 only).
Bell Follower Secondary - Configurable as a Bell Follower Secondary.
Siemens Industry, Inc.
Building Technologies Division
Programming OptionsIn order to perform its intended operation, the ZIC-4A card must be programmed
using the Zeus Programming Tool. The ZIC-4A card and its Out Ckt properties must
be set prior to normal operation.
In the Zeus Programming Tool, highlight the selected ZIC-4A card in the PhysicalView and open the Detail View - Properties to modify and/or define the following
ZIC-4A card properties:
HNET AddressThis address must match the address
set in the ZIC-4A hardware.
Slot LocationThis defines the location where the
ZIC-4A is inserted in the CC-5.
Base Language Custom MessageThe message associated with the ZIC-4A
card.
Alternate Language Custom MessageThe message associated with the ZIC-4A
card in an alternate language.
ZIC Card 24V Power SourceSelect back plane or screw terminals.
Each ZIC-4A card is subdivided into four output circuits that can be programmed
independently of each other. In the Zeus Programming Tool, highlight the selected
ZIC-4A Output Ckt in the Physical View and open the Detail View - Properties to
modify and/or define the following ZIC-4A output circuit properties:
Device AddressShows preset address of ZIC card output.
Base Language Custom MessageThe message associated with the ZIC-4A
output circuit.
Alternate Language Custom MessageThe message associated with the ZIC-4A
output circuit in an alternate language.
Device UsageSignal
ZIC Circuit UsageSelect usage required (see list).
ydaetSCANmrlAeniLdesaeL
dedoCCANyramirPloflleB
cnySebortSnroHyradnoceSloflleB
SV52
)ebortSnroH(ylnOnroH.liSrekaep
cnySebortSrekaepSV07
cnySnUebortSrekaepSV001
eiTlapicinuMenoZgnisaeleR
Degrade Mode Alarm ActivationDetermines if Degrade Alarm will activate
the ZIC-4A circuit when asserted.
Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-157
WIRING
SilenceableDetermines if the circuit is Silenceable or
Non-Silenceable.
Wiring TypeDefines if the circuit is Class A or Class B
wiring type.
Total Current DrawnSelect actual current load of output
If the zone usage is set in the Zeus Programming tool as “Sil Horn Only (Horn Strobe)”,
the Silenceable Option is always set and is specific to the Horn of the Horn Strobe
device and the strobe is always Non-Silenceable.
Some restrictions apply to certain usage selections (for example, Municipal Tie can
only be configured as Class B wiring type) that are enforced by the Zeus tool during
Edit mode or Compile time.
Refer to the Zeus Quick Start Manual, P/N 315-033875, or the Zeus self-help index
for more information.
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
All field wiring to the ZIC-4A is connected to
the terminal blocks of the CC-5 card cage
slot in which it is installed (Refer to Figure 3).
OUTPUTS SHOWN IN ACTIVE STATE
ZONE 1
--
+
+
+
ZONE 2
+
--
To Connect External Wiring
CLASS A
CLASS A
CLASS A
CLASS A
1.Loosen the screw of the terminal
by turning it counterclockwise.
2.Insert the wire into the side of the
terminal block.
12345678
910111213141516
3.Tighten the screw of the terminal
block by turning it clockwise.
The top terminals (1 through 8 and 9
through 16) are connected to the notification appliance devices such as bells, horns,
strobes, speakers, etc. Each zone has four
+
1718192021222324
CLASS A
CLASS A
--
+
ZONE 3
ONE SLOT OF CC-5
CLASS A
CLASS A
+
--
+
ZONE 4
terminal connections: (+), Class A (+), (-),
Class A (-). These terminals are power
limited.
The bottom terminals (17 through 24) are
connected to the input power source of the
+
ZONE 1
INPUT
-
+
ZONE 2
INPUT
-
+
ZONE 3
INPUT
-
+
ZONE 4
INPUT
NAC devices. Each zone has a (+) terminal
and (-) terminal. These terminals are not
power limited.
Figure 3
Wiring The 24VDC Power Lines To The
ZIC-4A Slot In The CC-5
-
Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-158
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.