Siemens ZIC-4A Installation Instructions Manual

Page 1
Installation Instruct ions Model ZIC-4A
Zone Indicating Card
P/N 315-033050-15
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 2
CONTENTS
INTRODUCTION ............................................................................................... 3
Features............................................................................................................ 3
OPERATION ..................................................................................................... 4
Controls and Indicators..................................................................................... 4
PRE-INSTALLATION ......................................................................................... 5
Output Zones ................................................................................................... 6
ZIC-4A Switch and Jumper Settings .................................................................7
Programming Options ......................................................................................7
WIRING ............................................................................................................ 8
Using Multiple Power Supplies ......................................................................... 9
INSTALLATION ............................................................................................... 10
ELECTRICAL RATINGS................................................................................... 10
CONFIGURATIONS ........................................................................................ 11
Bell Follower ................................................................................................... 11
ZIC-4A Supervised Notification Appliance Wiring ........................................... 12
ZIC-4A Supervised Municipal Tie Wiring ......................................................... 13
ZIC-4A Leased Line Wiring ............................................................................. 13
ZIC-4A Releasing Service Wiring .................................................................... 14
ZIC-4A Releasing Service Wiring With PSC-12 Power Supply ......................... 15
ZIC-4A Bell Follower Circuit Wiring ................................................................. 16
ZIC-4A Two-Channel Audio Wiring ................................................................... 17
ZIC-4A Single-Channel Audio Wiring ............................................................... 18
ZIC-4A Two-Channel Audio and Strobe Wiring ................................................ 19
ZIC-4A Single-Channel Audio and Strobe Wiring ............................................ 20
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
Releasing Logic .............................................................................................. 21
Page 3
HNET/CAN
Installation Instruct ions Model ZIC-4A
Zone Indicating Card
INTRODUCTION The Model ZIC-4A from Siemens Industry, Inc. is a zone
indicating card that provides notification appliance circuits for the FireFinder-XLS/Desigo Fire Safety Modular/ Cerberus PRO Modular system. It has 4 outputs that can be configured for Class A or Class B and control of audible and visual notification appliances such as horns, speakers, bells, strobes etc. Its outputs can also be configured as connection to Municipal Tie, Releasing Service per NFPA 13 and 2001 or as a connection to a Leased Line remote monitoring circuit.
Each zone can be configured independently for different usages as programmed in the Zeus tool and can be controlled automatically by program logic or manually using the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular). During the initial power-up condition, each zone on the ZIC-4A is configured as a steady NAC, Class A configuration with 2A current limit. The ZIC-4A then sends a message to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) indicating that it is unconfigured.
ZIC-4A
RESET
POWER
CARD FAIL
CAN FAIL
HNET FAIL
GND FAULT
ZONE 1 ACTIVE
TRBL
ZONE 2 ACTIVE
TRBL
ZONE 3 ACTIVE
TRBL
ZONE 4 ACTIVE
TRBL
The ZIC-4A supports synchronized and non-synchronized strobes. This selection is available in the Zeus tool under the detail properties for each ZIC-4A circuit. Synchroniza­tion across multiple ZIC-4A cards is automatic as a part of the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular operating characteristics. Refer to docu­ment P/N 315-096363 for a list of strobes that support synchronization.
Features ZIC-4A features are as follows:
Class A / Class B circuit configuration
Zones can be configured independently
Can have independent input source for each output
Zone input voltage supervision
Zone output supervision
Intelligent self-restoring power limiting
Coded signal synchronization capability
Card level Ground Fault detection
Communicate H-Net protocol
Uploadable firmware update
Ability to pass through up to 3A per circuit
P/N 315-033050-15
Building
HUNDREDS
TENS
ONES
Figure 1 ZIC-4A Zone Indicating Card
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 4
OPERATION The ZIC-4A contains four Class A circuits. Each circuit is rated at 3A at 24VDC and
has an input connected to the power source and an output where the NAC devices, Municipal Tie, Releasing service and Leased Line remote monitoring device are connected. The zone inputs are isolated from one another and are supervised for the presence of power. This allows the use of different power sources with different ground references. The zone output is supervised for open and short circuit condi­tions while the zone is inactive and allows different combinations of output configura­tions (Standard NAC, Releasing, etc.) per card. Each ZIC-4A card occupies any one card slot in the CC-5 cardcage. The ZIC-4A also has the capability to detect ground fault on its zone output as indicated by a diagnostic LED.
Controls and Indicators The front panel of the ZIC-4A contains one reset switch, thirteen LEDs, and three
HNET address switches as shown in Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch re-initializes the ZIC-4A operation.
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates that power for the ZIC-4A is applied to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the card microprocessor has failed.
CAN FAIL (Yellow) Normally OFF. When illuminated, indicates
that the CAN communication with the ZIC-4A has terminated and the card goes into degrade mode (applicable only when card resides in a CAN network). NOT
USED for FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modu­lar applications.
HNET FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the HNET communication with the ZIC-4A has terminated and the card goes into degrade mode (applicable only when card resides in the HNET network).
GND FAULT (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected either a negative or positive ground fault on its field wiring.
ZONE 1 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 1 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a trouble on Zone 1 (open circuit or short circuit).
ZONE 2 ACTIVE (Red) Normally OFF. When illuminated, indi-
Siemens Industry, Inc. Building Technologies Division
cates that Zone 2 is active.
P/N 315-033050-154
Page 5
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
96 PIN DIN
PLUG CONNECTOR
S4
S1
P1
P2
P3
P4
S2
S3
On
1
4
3
2
RESET SWITCH
LEASED LINE SELECT
ZONE INPUT SUPR ENABLE
NETWORK ADDRESS
S6
S7
1
4
5
6
2
3
1
4
5
6
2
3
1
4
5
6
2
3
1
4
5
6
2
3
S5
INPUT POWER SELECT
EXT
POWER
BP
POWER
cates that the ZIC-4A has detected a trouble on Zone 2 (open circuit or short circuit).
ZONE 3 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 3 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a trouble on Zone 3 (open circuit or short circuit).
ZONE 4 ACTIVE (Red) Normally OFF. When illuminated, indi-
cates that Zone 4 is active.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a trouble on Zone 4 (open circuit or short circuit).
Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the ZIC-4A.
PRE-INSTALLATION The following components must be set prior to inserting the card to the CC-5 (refer
to Figure 2):
S1 Primary Bell Follower Select Switch:
This switch selects Zone 1 as the Primary Bell Follower. Toggle the S1 switch towards the bottom of the board if Zone 1 is configured as a Primary Bell Follower; otherwise toggle it to the top of the board for normal operation (as shown in Figure 2.)
S2, Leased Line Select Switches: These switches select the zones configured for Leased Line application. Toggle each switch to the ON position if the corre­sponding zone is configured as Leased Line. If the zone is not configured as a Leased Line application, the correspond­ing zone switch must be set to the OFF position.
During card failure, Zone 1 and Zone 2 outputs will activate if the FireFinder­XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Alarm bus is asserted, Zone 3 outputs will activate the if the FireFinder-XLS/Desigo Fire Safety
Siemens Industry, Inc. Building Technologies Division
Modular/Cerberus PRO Modular Trouble Bus is asserted. You must configure each zone to the proper Leased Line remote monitoring circuit.
Silver line on S1 and jumpers P1 and P4 indicates normal operation.
Figure 2 ZIC-4A Switch Location
P/N 315-033050-155
Page 6
HNET
S2-SW1: Set to ON if Zone 1 usage = Leased Line, Alarm Default only
S2-SW2: Set to ON if Zone 2 usage = Leased Line, Alarm Default only
S2-SW3: Set to ON if Zone 3 usage = Leased Line, Trouble Default only
S2-SW4: Set to OFF: Not Used
S3, Reset Switch: Momentarily Closed switch that when pressed will initiate a hard reset to the ZIC-4A (similar to a cold boot).
S4, S6, S7 Network Address Switch: Set the three-digit HNET network address for the ZIC-4A using the three rotary dial address switches located near the bottom of the front panel. (Refer to Figure 1 for the location of the switches.) The address for the ZIC-4A must be the same as the address selected for it in the Zeus Programming Tool. To set the address, turn the pointers on each of the three dials to the numbers for the selected address. For example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set the pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”. The range of allowable addresses is from 001 to 251 (leading zeros must be used).
S5 Input Power Select: This switch selects the source of voltage input to power the ZIC-4A. BP Power indicates that the input is derived from the backplane of the CC-2/ CC-5 and EXT Power indicates that the input is derived from E5/E11 terminal of the CC-2/CC-5, normally connected to non-power limited output of the PSC-12/PSX-12. It is important to take into account the source of the voltage during battery calculations.
P1, P2, P3, P4 Shunt Headers, NAC Input Supervision Enable: These headers select the NAC input zone supervision. If usage application is set for speaker func­tion, place the shunt jumpers of the corresponding zone between 1—2 and between 5—6, otherwise place the shunt jumpers between 1—3 and 4—6.
P1 selects NAC input supervision for Zone 1 P2 selects NAC input supervision for Zone 2 P3 selects NAC input supervision for Zone 3 P4 selects NAC input supervision for Zone 4
Output Zones The ZIC-4A can be configured for the following usages:
Standard NAC Zone - Configurable as the following NAC zones:
Steady Strobe (Synchronized or Unsynchronized) Zone Coding Temporal Code
Temporal 4, when used with Audible Base SBGA-34 March Time 120 March Time 60 March Time 30 Horn / Strobe
Releasing Zone - For release of FM-200, Halon, Pre-action & Deluge Sprinklers for Canada or USA. Releasing zone requires an REL-EOL module for proper wire supervision.
Municipal Tie - Configurable as a supervised connection to municipal tie. Municipal Tie usage application requires the LLM-1 interface module.
6
4
2
5
3
1
Leased Line - Configurable as a connection to a remote monitoring system. Leased Line usage application requires LLM-1 interface module.
Bell Follower Primary - Configurable as a Bell Follower Primary (Zone 1 only).
Bell Follower Secondary - Configurable as a Bell Follower Secondary.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-156
Page 7
SGNITTESREPMUJDNAHCTIWSA4-CIZ
EGASUENOZ1S2SNOITISOPREDAEH
CANlamroNFFO6-4,3-1
eiTlapicinuMlamroNFFO6-4,3-1
enoZgnisaeleRlamroNFFO6-4,3-1
eniLdesaeLl
yramirP-rewolloFlleB
)ylnO1enoZ(
yradnoceS-rewolloFlleBlamroNFFO6-4, gnidoCenoZlamroNFFO6-4,3-1 slleBdedoClamroNFFO6-4,3-1
enoZrekaepSlamroNFFO6-5,2-1
amroNNO-)enoZ(WS6-4,3-1
lamroNffOFFO6-4,3-1
3-1
Programming Options In order to perform its intended operation, the ZIC-4A card must be programmed
using the Zeus Programming Tool. The ZIC-4A card and its Out Ckt properties must be set prior to normal operation.
In the Zeus Programming Tool, highlight the selected ZIC-4A card in the Physical View and open the Detail View - Properties to modify and/or define the following ZIC-4A card properties:
HNET Address This address must match the address
set in the ZIC-4A hardware.
Slot Location This defines the location where the
ZIC-4A is inserted in the CC-5.
Base Language Custom Message The message associated with the ZIC-4A
card.
Alternate Language Custom Message The message associated with the ZIC-4A
card in an alternate language.
ZIC Card 24V Power Source Select back plane or screw terminals.
Each ZIC-4A card is subdivided into four output circuits that can be programmed independently of each other. In the Zeus Programming Tool, highlight the selected ZIC-4A Output Ckt in the Physical View and open the Detail View - Properties to modify and/or define the following ZIC-4A output circuit properties:
Device Address Shows preset address of ZIC card output.
Base Language Custom Message The message associated with the ZIC-4A
output circuit.
Alternate Language Custom Message The message associated with the ZIC-4A
output circuit in an alternate language.
Device Usage Signal
ZIC Circuit Usage Select usage required (see list).
ydaetSCANmrlAeniLdesaeL
dedoCCANyramirPloflleB
cnySebortSnroHyradnoceSloflleB
SV52
)ebortSnroH(ylnOnroH.liSrekaep
cnySebortSrekaepSV07
cnySnUebortSrekaepSV001
eiTlapicinuMenoZgnisaeleR
Degrade Mode Alarm Activation Determines if Degrade Alarm will activate
the ZIC-4A circuit when asserted.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-157
Page 8
WIRING
Silenceable Determines if the circuit is Silenceable or
Non-Silenceable.
Wiring Type Defines if the circuit is Class A or Class B
wiring type.
Total Current Drawn Select actual current load of output
circuit (see list).
pmA0.0pmA5.1pmA0.3 pmA5.0pmA0.2pmA5.3 pmA0.1pmA5.2pmA0.4
If the zone usage is set in the Zeus Programming tool as “Sil Horn Only (Horn Strobe)”, the Silenceable Option is always set and is specific to the Horn of the Horn Strobe device and the strobe is always Non-Silenceable.
Some restrictions apply to certain usage selections (for example, Municipal Tie can only be configured as Class B wiring type) that are enforced by the Zeus tool during Edit mode or Compile time.
Refer to the Zeus Quick Start Manual, P/N 315-033875, or the Zeus self-help index for more information.
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
All field wiring to the ZIC-4A is connected to the terminal blocks of the CC-5 card cage slot in which it is installed (Refer to Figure 3).
OUTPUTS SHOWN IN ACTIVE STATE
ZONE 1
--
+
+
+
ZONE 2
+
--
To Connect External Wiring
CLASS A
CLASS A
CLASS A
CLASS A
1. Loosen the screw of the terminal by turning it counterclockwise.
2. Insert the wire into the side of the terminal block.
12345678
910111213141516
3. Tighten the screw of the terminal block by turning it clockwise.
The top terminals (1 through 8 and 9 through 16) are connected to the notifica­tion appliance devices such as bells, horns, strobes, speakers, etc. Each zone has four
+
17 18 19 20 21 22 23 24
CLASS A
CLASS A
--
+
ZONE 3
ONE SLOT OF CC-5
CLASS A
CLASS A
+
--
+
ZONE 4
terminal connections: (+), Class A (+), (-), Class A (-). These terminals are power limited.
The bottom terminals (17 through 24) are connected to the input power source of the
+
ZONE 1
INPUT
-
+
ZONE 2
INPUT
-
+
ZONE 3
INPUT
-
+
ZONE 4
INPUT
NAC devices. Each zone has a (+) terminal and (-) terminal. These terminals are not power limited.
Figure 3
Wiring The 24VDC Power Lines To The ZIC-4A Slot In The CC-5
-
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-158
Page 9
Care must be taken when installing the zone input and zone output field wiring to prevent possible cross wiring. This can cause severe damage to the system when powered up or when zone is activated.
The screw terminals can accommodate one 12-18 AWG or two 16-18 AWG.
If the total output of all 4 zones exceeds 12 amps, a single PSC-12 cannot be used to supply the ZIC-4A. Refer to the PSC-12 Installation Instructions, P/N 315-033060 for information when the total system load exceeds 12 amps.
ONE SLOT OF CC-5
TO PSC-12, TB4 +
TO PSC-12, TB4 -
TO PSC-12, TB4 +
TO PSC-12, TB4 -
TO PSX-12, TB4 +
TO PSX-12, TB4 -
17 18 19 20 21 22 23 24
-
+
17 18 19 20 21 22 23 24
-
+
-
+
ONE SLOT OF CC-5
-
+
-
+
-
+
+
+
-
USING A SINGLE PSC-12 TO POWER A ZIC-4A
USING A PSC-12 TO
-
POWER INPUTS 1-3 AND A PSX-12 TO POWER INPUT 4
TO PSC-12, TB4 +
TO PSC-12, TB4 -
TO PSX-12, TB4 +
TO PSX-12, TB4 -
Figure 4 Using Multiple Power Supplies
Siemens Industry, Inc. Building Technologies Division
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
-
+
-
+
-
+
+
USING A PSC-12 TO
-
POWER INPUTS 1-2 AND A PSX-12 TO POWER INPUTS 3- 4
P/N 315-033050-159
Page 10
INSTALLATION The ZIC-4A plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 5.)
Insert the ZIC-4A card into the card guides right side up (lettering on the front panel is legible).
Slide the card in until the card edge connectors contact the recep­tacles on the motherboard.
Verify that the DIN connectors of the card and the card-cage aligned properly. The card can only plug in one direction to the card cage, if it does not align, DO NOT FORCE the card.
Place thumbs on the front panel adjacent to the captive screws and
gently apply even pressure on the card until the connectors seat in the
receptacles on the motherboard. Secure with the captive screws.
If the ZIC-4A is being powered from an external source, verify that E5 has the proper
Figure 5
voltage and proper terminal connections.
Installing The ZIC-4A
ELECTRICAL RATINGS
roenalPkcaBV42
tnerruCrewoPlanretxE
tnerruCV42lanimreTwercStnerruCeciveDlatoT
BV2.60
:ETON .A4-CIZehtfotkCCIZhcaefoepytgniriwdnaegasuehtnotnednepedsitnerrucV42ehT
tnerruCenalPkca
tnerruCybdnatSV42Am98
wolebETONeeS
.epytgniriwdnaegasuenozhcaerofswardtnerrucderiuqerehterawolebdetsiL
tnemeriuqeRtnerruCA4-CIZ
egasUenoZ
desUtoN00
CANAm71Am6
.cnyS-ebortSAm71Am6
tSAm71Am6
.cnysnU-ebor
ASU-eiTlapicinuMAm430
adanaC-eiTlapicinuMAm710
enoZgnisaeleRAm710
mralA-eniLdesaeLAm710
elbuorT-eniLdesaeLA
vpuS-eniLdesaeLAm710
yramirP-rewolloFlleB00
yradnoceS-rewolloFlleBAm71Am6 enoZrekaepSAm43Am6 dedoC-CANAm71Am6
tnerruCtuptuO
tnemeriuqeR
m710
Am9
8=tnerruCybdnatSA4-CIZ
tnerruCAssalC
tnemeriuqeR
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1510
Page 11
To calculate the maximum current, the following equation should be used:
ZIC-4A Total Current = ZIC-4A Standby Current + [Zone 1 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 2 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 3 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 4 Usage Req. (See Table above) + Class A current (if Class A)]
Example 1: If a ZIC-4A has the following ZICCkt setting:
ZICCkt#1 — Speaker Zone, Class A
ZICCkt#2 — Speaker Zone, Class A
ZICCkt#3 — Speaker Zone, Class A
ZICCkt#4 — Speaker Zone, Class A
By applying the equation above, the maximum current requirement for this card will be determined.
Max Current = 89 + (34 + 6) +(34 + 6) +(34 + 6) +(34 + 6) = 249mA (worst case).
Example 2: If a ZIC-4A has the following ZICCkt setting:
ZICCkt#1 — NAC, Class B
ZICCkt#2 — Strobe Sync, Class A
ZICCkt#3 — NAC-Coded, Class B
ZICCkt#4 — Not Used
Max Current = 89 + (17 + 0) +(17 + 6) +(17 + 0) +(0 + 0) = 146mA.
CONFIGURATIONS The ZIC-4A zones can be configured for the following usages (Refer to Figures 6 - 16):
Notification Applicance (NFPA 72)
Municipal Tie (NFPA 72)
Leased Line (NFPA 72)
Releasing Service (NFPA 13 and NFPA 2001)
Bell Follower
Single-Channel and Two-Channel Audio
Single-Channel and Two-Channel Audio and Strobe
Bell Follower (Refer to Figure 11) When the ZIC-4A zones are configured as a bell follower, it
follows a signal that comes from another reverse polarity source. The zones can be set as a Bell Follower-Primary or Bell Follower-Secondary.
The Bell Follower-Primary receives an input (it can be NAC output of another panel, etc), converts it to a TTL signal and then sends it to the Bell Sync Bus of the CC-5 which is monitored by the card with Bell Follower-Secondary configuration. Bell Follower-Primary can be configured on Zone 1 only. Once Zone 1 is configured as a Bell Follower-Primary, its zone output is not used. There can only be one Bell Fol­lower-Primary per enclosure. CC-5 Sync Bus transfers from card cage to card cage.
The ZIC-4A card monitors the Bell Sync Bus if any one of its zones is configured as Bell Follower-Secondary. Once a HI is detected, the card activates the Bell Follower­Secondary zone and continuously monitors this signal until it goes LO. Then the ZIC­4A card de-activates the Bell Follower-Secondary. The zone inputs of the Bell Fol­lower-Secondary are monitored for presence of input voltage (<20VDC) and its output is supervised for short and open while the zone is in supervision.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1511
Page 12
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings: Special Application
24 VDC 4mA max @ Supervisory 3A max @ Alarm
4. EOL resistor , 24k ohms , 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated. The field wiring resistance cannot exceed the maximum line resistance specified for any given NAC current draw. (See Table)
7. Sync and non-sync notification appliances permitted. Sync is provided across all four tones. Sync is not provided between ZIC-4A cards.
8. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
9. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
10. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
STYLE Z
(CLASS A)
tnerruC
warD
eniLxaM
ecnatsiseR
A0.3smho8.0 A5.2smho0.1 A0.2smho2.1 A5.1smho9.1 A0.1smho4.3 A5.0smho9.7
+
ZONE 2
24K,
*
1W 5%
NCNCNC
STYLE Y CLASS B
FOR CANADIAN APPLICATIONS,
*
USE EOL MODEL REL-EOL. OMIT THE DIODE.
-
ZONE 1
24K,
*
1W 5%
--
+
+
STYLE Z
(CLASS A)
ZONE 3
Figure 6 ZIC-4A Supervised Notification Appliance Wiring
12345678
910111213141516
24K,
*
1W 5%
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
+
ZONE 1
INPUT
-
+
ZONE 2
INPUT
-
+
ZONE 3
INPUT
NC
-
+
ZONE 4
INPUT
-
ZONE 4
STYLE Y
CLASS B
*
24K,
1W 5%
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1512
Page 13
DO NOT USE
12345678
910111213141516
+
+
+
+
+
+
+
+
-
-
+
-
+
-
+
-
17 18 19 20 21 22 23 24
ZONE 1 & 2
INPUT
ZONE 3
INPUT
ZONE 4
INPUT
ONE SLOT OF CC-5
LEASED
LINE
ZONE 1
LEASED
LINE
ZONE 3
4321
4321
LLM-1
NC
NC
NC
NC
NC
NC
NC
NC
TB1
TB2
4321
4321
LLM-1
TB1
TB2
4321
4321
LLM-1
TB1
TB2
LEASED
LINE
ZONE 2
LEASED
LINE
ZONE 4
4321
4321
LLM-1
TB1
TB2
-
----
-
24 VDC open circuit filtered
with Article 760 of NEC or local
building codes.
limited.
full wave
NOTES
1. All wiring must be in accordance
2. All output circuits are power
3. Leased Line circuit rating:
4. External circuit resistance:
2k to 5k ohms
alarm / supervisory.
5. Rated Current: 3mA to 9mA,
6. Polarity shown in active state.
7. Lease Line circuits are not
supervised.
Remote Station Receiver Unit.
8. LLM-1 module is required.
9. Load must be compatible polarity reversal labeled
-
INPUT
ZONE 4
+
-
INPUT
ZONE 3
+
10. Input voltage sources can be daisy-chained.
11. Any circuit may be used.
60 hours standby
5 minute alarm
12. Minimum Emergency Power:
compatible ratings.
tion Instructions for details on the separation of power limited and non-power limited wiring.
13. Intended for connection to a polarity reversal circuit of a remote station receiving unit having
Figure 8
14. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installa-
ZIC-4A Leased Line Wiring
4321
TB1
4321
LLM-1
NOTES
TIE
ZONE 1
MUNICIPAL
Siemens Industry, Inc. Building Technologies Division
-
5%
1W
24K,
-
+
+
TB2
accordance with
Article 760 of NEC
1. All wiring must be in
12345678
or local building codes.
not power limited.
2. All output circuits are
3. Electrical Ratings:
DO NOT USE
910111213141516
220mA to 320mA DC
1mA DC
Trip Coil: 14.5 ohms
Trip Current:
Supervisory Current:
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
Voltage: 24V nominal
1 watt, 5%, P/N 140-820405.
4. EOL resistor, 24k ohms,
5. Polarity shown in active state.
6. Supervised for open circuit only.
7. LLM-1 module is required. The total
-
INPUT
ZONE 2
+
-
INPUT
ZONE 1
+
loop resistance from the LLM-1 to
the Municipal Tie, including the
14.5 ohms in the Municipal Tie,
should not exceed 22.5 ohms.
between the positive terminals
at the output.
8. Wire jumper must be connected
9. Any circuit may be used.
10. Minimum Emergency Power:
60 hours standby
5 minute alarm
(P/N 315-033009) Installation Instructions for details on the separation of
11. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB
P/N 315-033050-1513
power limited and non-power limited wiring.
Figure 7
12. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
ZIC-4A Supervised Municipal Tie Wiring
Page 14
NOTES
U
1. All wiring must be in accordance with Article 760 of NEC or local building codes.
2. Electrical Ratings: 24VDC
2mA max @ Supervisory 3A max @ Alarm
3. All circuits are power limited to NFPA 72 per NEC 760.
4. EOL resistor, 24k ohms, 1 watt, 5%, P/N 140-820405.
5. Polarity shown in active state for UL compliant wiring only.
6. N/A
7. Releasing is wired for Class B only.
8. Any circuit may be used.
9. Input voltage sources can be daisy­chained.
10. For Compatible Solenoids, refer to table at right.
11. Refer to Zeus Quick Start Guide (P/N 315-033875) for information about programming of releasing service.
12. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/ N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
13. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
14. For FM approved Pre-Action/ Deluge: All initiating devices connected to the system must be wired CLASS A.
15. Wiring diagram shown for 24VDC solenoid.
16. Wiring diagram shown for 12VDC solenoids (2 units in series.)
17. Wiring diagram shown for 6VDC solenoids (4 units in series.)
18. The ZIC-4A circuit must be configured as “NAC Steady”. The “Releasing Zone” usage in Zeus is only to be used for legacy UL releasing applications that did not include the REL-EOL.
19. The ZIC-4A circuit must include a UL864 listed Releasing Disconnect Switch such as Siemens Model RSM-5, P/N S54339­F1-A1. The switch position must be monitored using an input module such as the HTRI-M using the second set of contacts.
RELEASING ZONE
ZONE 3
See Note 15 See Note 14 See Note 14 See Note 16
-
+
-
REL-EOL
Supervising
Module
Disconnect Circuit
24K,
1/2W
*
Disconnect
Switch
+
5%
MODULE
*
Figure 9 ZIC-4A Releasing Service Wiring
NOITACILPPARERUTCAFUNAM
31APFN
)eguleDnoitcA-erP(
1002APFN
OCSA
RENNIKS
OCSA6-235812VHGB119796-005CDV6ruoF61LU
ETITPANS
XLT
GNIKIV
EDDIK000-494798-KWA/NCDV42enO4LU SUNAJ18481,22702A
XAMINIM323988A/NCDV42enO4LU
RELEASING ZONE
ZONE 1
-
+
REL-EOL
24K,
MODULE
1/2W
5%
Disconnect
Circuit
+
NCNCNC
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
+
17 18 19 20 21 22 23 24
+
ZONE 1 & 2
INP
NC
ONE SLOT OF CC-5
-
T
RELEASING ZONE
ZONE 2
-
+
REL-EOL MODULE
24K, 1/2W
*
5%
Disconnect
+
+
+
Circuit
NCNCNC
ZONE 3
INPUT
NC
-
+
ZONE 4
INPUT
-
--
RELEASING ZONE
24K,
1/2W
*
5%
-
* The REL-EOL ships with three resistors. Use the 24K resistor (P/N 140-034677) with the ZIC-4A.
-
ZONE 4
+
REL-EOL MODULE
Disconnect
Circuit
SDIONELOSELBITAPMOC
ROLEDOMDIONELOS
REBMUNTRAP
701A0128R
701A0128TCDV42enO4LU
2C111C0N00N99NBG1237CDV42enO4LU
52XBL2VLCDV42enO4LU
5F4A-BN2-A3282GB219796-005CDV21owT8LU
A-BN2-A3282GB319296-005CDV42enO4LU
6F4 4F4A-BN2-A3282GB119796-005CDV6ruoF61LU
B495239GB176946-005CDV42enO4LU
42-2-CEY
PC/8210AP
42-2-CEYPC/7330AP 19511 29511CDV42enO4LU
59511CDV42enO4LU 10611CD 20611CDV42enO4LU 51231CDV42enO4LU 34831CDV42enO4LU 44831CDV42enO4LU
SNEMEIS
REBMUNTRAP
A/N
GB529796-005CDV42enO4LU
A/N
/NCDV42enO4LU
FOREBMUN
SDIONELOS
SEIRESNI
CDV42enO4LU
CDV42enO4LU
V42enO4LU
MUMIXAM
MUN
FOREB
SDIONELOS
DRACREP
-
+
-
+
-
+
-
LAVORPPA
Siemens Industry, Inc. Building Technologies Division
Initiating devices configured for supervisory signaling are latching by default. If non-latching behavior is required, check the self restoring supervisory checkbox in the node properties for your Zeus configuration.
P/N 315-033050-1514
Page 15
+
-
+
-
+
-
+
-
17 18 19 20 21 22 23 24
ONE SLOT OF CC-5
TO PSC-12, TB4 +
TO PSC-12, TB4 -
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings: 24 VDC
2mA max @ Supervisory 3A max @ Alarm
4. Maximum line resistance: Refer to table on pages 12 or 16.
5. Use only Pre-Action/Deluge solenoids listed in tables on page
14.
6. For FM Approved Pre-Action/ Deluge: All initiating devices conntected to the system must be wired CLASS A.
7. Refer to Figure 9 for ZIC-4A output soldenoid wiring for Releasing Service. Connect the zone ouput appropriately.
8. Inputs can be daisy-chained provided that the power supply can sustain the power require­ment of the output when activated.
9. Refer to Zeus Quick Start Guide (P/N 315-033875) for information about programming of releasing service.
10. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
11. 90 hour standby power is required to meet FM Approved installation requirements. Refer to PSC-12 Installation Instructions, P/N 315­033060 for battery calculations.
Figure 10 ZIC-4A Releasing Service Wiring With PSC-12 Power Supply
FOR FM APPROVED INSTALLATION ONLY:
Double Interlock A sprinkler system comprised of two interlocks - an interlock which opens when Pre-action Systems powered by a listed releasing panel and a second interlock which opens when a
pressure loss is experienced in the sprinkler pipes between the interlock and the system’s sprinkler heads.
Both interlocks must be open at the same time to allow for the flow of water to initiate.
A specific sequence of operation is required with all Siemens panels with listed releasing capabilities.
The FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular panel will indicate an alarm if one detector detects an alarm condition. The system will not energize the releasing circuit until an additional detector detects an alarm (any two detectors in the same protection zone covering the sprinkler system) AND the panel receives a low pressure indication from a pressure switch placed in the sprinkler piping between the second interlock and that pipe system’s sprinkler heads (indi­cates that the second interlock is in OPEN position). If this sequence is not followed precisely, the correlating system design may not properly activate the double inter­lock preaction sprinkler system, therefore, preventing the water from discharging during a true fire incident.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1515
Page 16
Y
Y
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes.
2. Only Zone 1 can be configured as Bell Follower-Primary. Any other zone can be configured as Bell Follower-Secondary. There can only be one Bell Follower-Primary per enclosure.
3. Electrical Ratings: Bell Follower-Primary: Input Alarm Current: 6mA max Input Voltage: 24 VDC nominal No end of line resistor is used.
Bell Follower-Secondary: Input Voltage: 24 VDC nominal Output Supervision Current: 4mA max Output Alarm Current: 3A max Output Voltage: 24 VDC nominal
4. Bell Follower-Primary is not supervised.
5. Bell Follower-Secondary is supervised for input voltage presence, short and open on the output and is power limited. Bell Follower­Secondary can be configured or Class A or Class B wiring.
6. The total output loop resistance must not exceed those stated in table to the right.
7. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
8. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
9. The use of sync strobes is not allowed on the secondary circuits.
BELL FOLLOWER - SECONDA R
(CLASS B)
ZONE 2
24K,
*
1W 5%
tnerruC
warD
A0.3smho8.0 A5.2smho0.1 A0.2smho2.1 A5.1smho9.1 A0.1smho4.3 A5.0smho9.7
eniLxaM
ecnatsiseR
BELL FOLLOWER - SECONDARY
(CLASS A)
ZONE 3
BELL FOLLOWER
PRIMARY INPUT
FIRE ALARM PANEL
OR
BELLEXTENDER
NCNCNCNCNC
+
1 2 3 4 5 6 7 8
+
+
9 10 11 12 13 14 15 16
24K,
*
1W
5%
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
-
+
+
+
NCNCNC
-
-
+
+
FOR CANADIANAPPLICATION S,
*
USE EOLMODELREL-EOL. OMIT THE DIODE.
-
---
-
BELL FOLLOWER - SECONDAR
(CLASS B)
ZONE 4
24K,
*
1W 5%
NAC OUTPUT SHOWN
IN ACTIVE STATE
+
-
Figure 11 ZIC-4A Bell Follower Circuit Wiring
Siemens Industry, Inc. Building Technologies Division
TO PSC-12, TB4 -
TO PSC-12, TB4 +
P/N 315-033050-1516
Page 17
Zone Wiring
STYLE Z CLASS A
ZONE 1 ZONE 2
24K,
1W 5%
STYLE Y
CLASS B
TO NEXT
ZIC-4A
STYLE Z
(CLASS A)
CHANNEL A
CHANNEL B
ZONE 3
+
-
+
-
24K,
1W 5%
+
+
12345678
+
+
910111213141516
17 18 19 20 21 22 23 24
--
24K,
1W 5%
ONE SLOT OF CC-5
+
+
NCNCNC
NC
-
---
ZONE 4
+
-
AUDIO FROM PREVIOUS ZIC-4A OR FROM ZAC-40/
+
ZAM-180 TERMINALS
-
1A AND 1B OR 2AAND 2B
STYLE Y
(CLASS B)
24K,
1W 5%
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings: Output Zone Supervisory: 4mA max Output Zone Active: 96 Watts max / zone
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
Figure 12 ZIC-4A Two-Channel Audio Wiring
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1517
Page 18
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings: Output Zone Supervisory:
4mA max
Output Zone Active:
96 Watts max / zone
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
7. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/ N 315-033009) Installation Instruc­tions for details on the separation of power limited and non-power limited wiring.
8. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
STYLE Z
(CLASS A)
STYLE Z CLASS A
ZONE 3
ZONE 1
24K,
1W 5%
24K,
1W 5%
--
+
+
12345678
+
+
910111213141516
+
+
ZONE 2
24K,
1W 5%
NCNCNC
STYLE Y CLASS B
NC
-
---
ZONE 4
STYLE Y
(CLASS B)
24K,
1W 5%
TO NEXT ZIC-4A
+
-
Figure 13 ZIC-4A Single-Channel Audio Wiring
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
AUDIO FROM PREVIOUS
+
ZIC-4A OR FROM
-
ZAM-180 TERMINALS 1A AND 1B OR 2AAND 2B
ZAC-40/
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1518
Page 19
STYLE Z CLASS A
ZONE 1
ZONE 2
24K,
1W 5%
STYLE Y
CLASS B
tnerruC
warD
A0.3smho8.0 A5.2smho0.1 A0.2smho2.1 A5.1smho9.1 A0.1smho4.3 A5.0smho9.7
eniLxaM
ecnatsiseR
AUDIO FROM PREVIOUS
ZIC-4A OR FROM ZAC-40/
ZAM-180 TERMINALS
1A AND 1B OR 2AAND 2B
TO NEXT
ZIC-4A
STYLE Z
(CLASS A)
CHANNEL A
CHANNEL B
ZONE 3
+
-
+
-
24K,
1W 5%
+
+
12345678
+
+
910111213141516
*
17 18 19 20 21 22 23 24
--
24K,
24K,
1W
1W 5%
5%
ONE SLOT OF CC-5
+
+
NCNCNC
NC
-
STYLE Y
(CLASS B)
---
FOR CANADIAN APPLICATIONS,
*
USE EOL MODEL REL-EOL. OMIT THE DIODE.
24V (-)
ZONE INPUT
24V (+)
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings For Speaker Application: Output Zone Supervisory: 4mA max @ 24VDC Output Zone Active: 96 Watts max / zone Electrical Ratings For Special Application: 24 VDC (strobe) Output Zone Supervisory: 4mA max Output Zone Alarm: 3A max
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated. The field wiring resistance cannot exceed the maximum line resistance specified for any given NAC current draw. (See Table)
11. Zone Usage pair is interchangeable. Verify proper wiring.
12. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
ZONE 4
24K,
*
1W 5%
Figure 14 ZIC-4A Two-Channel Audio And Strobe Wiring
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1519
Page 20
STYLE Z
(CLASS A)
ZONE 1
ZONE 2
24K,
*
1W 5%
STYLE Y
(CLASS B)
tnerruC
warD
A0.3smho8.0 A5.2smho0.1 A0.2smho2.1 A5.1smho9.1 A0.1smho4.3
eniLxaM
ecnatsiseR
STYLE Z
(CLASS A)
ZONE
INPUT
ZONE 3
+
-
24K,
*
1W 5%
--
+
+
+
+
12345678
+
+
910111213141516
24K,
1W 5%
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
+
--
+
+
NC NC
NC NC
-
-
---
FOR CANADIAN APPLICATIONS,
*
USE EOL MODEL REL-EOL. OMIT THE DIODE.
AUDIO FROM PREVIOUS
+
ZIC-4A OR FROM
-
ZAM-180 TERMINALS 1A AND 1B OR 2AAND 2B
ZONE 4
STYLE Y
(CLASS B)
ZAC-40/
24K,
1W 5%
TO NEXT ZIC-4A
A5.0smho9.7
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings For Speaker Application: Output Zone Supervisory: 4mA max @ 24VDC Output Zone Active: 96 Watts max / zone
Electrical Ratings For Special Application: 24 VDC (strobe)
Output Zone Supervisory: 4mA max Output Zone Alarm: 3A max
4. EOL resistor, 24k ohms,
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated. The field wiring
resistance cannot exceed the maximum line resistance specified for any given NAC current draw. (See Table)
11. Zone usage pair is interchangeable. Verify proper wiring.
12. Positive or negative ground fault detected at 40K ohms for terminals 1-16.
Figure 15 ZIC-4A Single-Channel Audio And Strobe Wiring
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1520
Page 21
ACF1
ACF2
ACF3
LED1
LED2
LED3
NACs
GENERAL ALARM
P1 UC3
FIRST ALARM /
PRE DISCHARGE NAC
P2 UC3
P1 120PPM
PRE-DISCHARGE
G2
DISCHARGED NAC
P1 SYNC STROBE
DISCHARGE
G5
M
G3
LCM LED (Yellow)
PRE DISCHARGE
G4*
M
DISCHARGED
LCM LED (Yellow)
TRUE
ENABLE
E
START
RELEASING NACs
O
TIMER
30 - 60s
T
ST2
C
PANEL
RESET
CANCEL
(Yellow)
ABORT LCM LED
ALARM
ALARM
ST1
TRUE
ENABLE
E
O
TIMER
START
T
G1
PANEL RESET
0 - 60s
PANEL
RESET
C
CLR
CLK
PANEL
RESET
CANCEL
Q
L1
D
TRUE
HZM+AW-1
ABORT
AT THE NODE LEVEL IN ZEUS IF YOU WANT
ABORT EVENTS TO SELF-RESTORE.
NOTE: SELECT SELF RESTORING SUPERVISORIES
ELIMINATE G4, CONNECT M TO M FOR DIRECT MANUAL RELEASE
*OPTIONAL: ABORT OVER-RIDES MANUAL RELEASE
MANUAL
RELEASE
SUPERVISORY
HZM+MH501
NOTE: THE USE OF ALARM VERIFICATION IS NOT ALLOWED FOR DEVICES IN A CROSS ZONED INITIATING CIRCUIT.
ALARM
Siemens Industry, Inc. Building Technologies Division
DISPLAY CAT. = ABORT SWITCH
Figure 16
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Releasing Logic
P/N 315-033050-1521
Page 22
Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1522
Page 23
This page has been left intentionally blank.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033050-1523
Page 24
This page has been left intentionally blank.
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
Siemens Gebäudesicherheit GmbH & Co. oHG D-80930 München
P/N 315-033050-15
Document ID A6V10239104
Loading...