Siemens WTT16, WTX16 Series, WTX16, WTT16.232, WTX16.232 Series Manual

874
2
Network Node
WTT16…
WTX16…
The WT…16… network node is used to receive and handle the data transmitted by consumption meters of the Siemeca™ AMR system. In small plants, one net­work node suffices as a data collector. In larger plants, or when consumption data shall be read out from a remote location, an M-bus interface for connection to an OZW10 M-bus central unit or a Siemeca™ gateway is required. The WTT16… network node is battery-powered, the mains-powered WTX16… version is available for special applications.
Use
CE1N2874en
14.07.2005
The WT…16… network node is a component of the Siemeca™ system. It has been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building. Communication between several network nodes is via radio also so that no wiring is required. All meas­ured values acquired by the consumption meters are continuously exchanged within the network, which means that every network node stores the current consumption values, the values read out at the end of the month, and the set day values of all meter­ing devices on the network. Owing to this operating principle, all network data can be read out at any of the nodes, or a Siemeca™ gateway for remote data transmission can be used with any of the nodes. The field of use of the Siemeca™ AMR system is de­scribed in data sheet N2870.
Building Technologies
HVAC Products
Functions
Network node versions
Reception and storage of the data transmitted by the Siemeca™ AMR consumption meters
Automatic creation of a network with up to 12 WT…16 (with a maximum of 500 con­sumption meters)
Passing on all relevant consumption values to all WT…16 on the network
Communication via the Siemeca™ gateway
Communication with the OZW10 M-bus central unit
The WT…16… network node is a component of the Siemeca™ system and has been designed for exclusive use with that system. It is available in a number of versions for different applications:
Application Battery-powered Mains-powered
Standard With RS-232 interface for local data readout
WTT16 WTX16 WTT16.232 WTX16.232
Network nodes with integrated gateway are used for the remote readout of Siemeca™ AMR networks. They are described in data sheet N2878.
Combinations
Technical design
Basic design
All network nodes with integrated gateway can be used along with any other network node. The maximum number of 12 network nodes in one system must not be ex­ceeded. The network nodes with gateway and integrated M-Bus master (WTX16.GSM and WTX16.IP) are able to read M-Bus meters according to EN1434/3.
The network node consists of the following subassemblies:
power supply:
mains supply WTX16..
battery WTT16...
Receiver and transmitter are used for re­ceiving consumption data and forwarding them to other network nodes of the network. The memory stores the consumption data. It is protected against temporary power drops (e.g. mains power failure or replacement of the main battery) by a backup battery. The network can be read locally via the M-Bus interface. The network nodes WT…16.232
transceiver for
Siemeca™ network
M-Bus
(Slave)
memory for 500 meters
RS232
(optional)
have an additional RS232 interface for rea-
backup battery
dout purposes.
WTT16… nodes are battery-operated, while WTX16… require a mains power supply AC 100 V…230 V.
The network node consists of 2 major sections: The base and the housing with the electronics. It is thus possible to mount the base prior to commissioning, enabling the electrical installer to connect the WTX16 to the mains network. At the time of commis­sioning, the electronics section is snapped on and the electrical connections are made.
2/8
Building Technologies Network Node WTT16…, WTX16… CE1N2874en HVAC Products 14.07.2005
Electronics section
The housing with the electronics is identical for all types of network nodes. It contains the network controls:
Wall-mounted section
1 2 3 4
5
10
6
MODE
RESET
8
7
DISPLAY
9
11
1 Connector for M-bus service connection 2 Connector for enhancements 3 Screw terminal for the fixed M-bus connection 4 Connector for power supply DC 3,6 V 5 Connector for backup battery Indication of mains supply 6 Operating mode button (red) 7 Button for switching the display (blue) 8 Reset button (recessed) 9 Display 10 Connector (not for the user) 11 Firmware memory (covered up)
The wall-mounted section of the network nodes WTT16… contains only the main battery. The wall-mounted section of the network nodes WTX16 and WTX16.232 contains the power pack and possibly an additional RS232 interface.
GND
n.c.
RTS
CTSRxTx
2
6
5
4
7
1 Mains connection L and N 2 Preinstalled mains cable (no flexible power cable!) 3 Extra insulation (shrink sleeve) 4 Connector for power supply DC 3,6 V 5 Screw terminal for the fixed M-bus connection 6 Connector for M-bus service connection 7 Indication of mains supply
1
3
3/8
Building Technologies Network Node WTT16…, WTX16… CE1N2874en HVAC Products 14.07.2005