Siemens VRD40.040, VGD40.050/L, VGD40.065/L, VRD40.050, VRD40.065 Operation Manual And Mounting Instructions

...
Page 1
CC1U7643en
14.03.2018
Building Technologies
Operation Manual and Mounting Instructions for a VGD4/VRD4 double gas valve with 2 SKPx5 actuators
Note! The combination of a VGD4/VRD4 double gas valve with a QPLx5 pressure switch and SKPx5 actuator does not require any maintenance.
Caution! This document is intended for end users. All legal, safety, warning, and technical notes contained in the data sheets for the SKPx5 actuator (N7643), VGD4 double gas valve (N7631), VRD4 double gas valve for biogases and recycling gases (N7649), and the QPLx5 pressure switch (N7221) are also applicable!
Page 2
2/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
1 Use
The combination of the SKPx5 actuator and VGD4/VRD4 double gas valve takes on the functions of a
Safety shutoff valve (SKP15) Safety shutoff valve with specific pressure control (SKP25)
1.1 SKP15 actuator
The electrohydraulically operated SKP15 gas fittings together with VGD4/VRD4 work exclusively as a safety shutoff valve (OPEN/CLOSED) and are used primarily on gas­fired combustion plant. They open slowly and close rapidly. The SKP15 actuator can be supplied with end switches including a valve stroke display or without an end switch or valve stroke display.
1.2 SKP25 actuator
The electrohydraulically operated SKP25 gas fittings together with VGD4/VRD4 work as a safety shutoff valve (OPEN/CLOSED) and are also used as a gas pressure governor. This controls the gas pressure on the outlet side according to the setpoint value established by means of a setpoint spring. The SKP25 actuator can be supplied with or without an end switch. The valve stroke display is generally provided.
Page 3
3/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
1.3 Application example
1 x VGD40/VRD40 + 1 x SKP15 and 1 x SKP25
7643z80en/0718
OPEN/CLOSED
W
ith valve stroke display
With end switch
SKP15.001
OPEN/CLOSED
SKP15.000
Without valve stroke display
Without end switch
SKP15.001 SKP25.003
OPEN/CLOSED
With valve stroke display
With end switch
OPEN
/CL
OSE
D
With v
alvestrokedisplay
Withou
tendswitc
h
With c
onstantpressuregove
rno
r
A
I
R
TheSKP15/SKP2
5actuator
s
c
a
nbe
c
o
mbineda
twillwiththeVGD4/VRD4doublegasvalves.
1 x VGD40/VRD40 + 2 x SKP15
Page 4
4/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2 Description of the SKPx5 actuators
Operating mode display
Valve stroke display
7
6
43z81en/101
7
The valve stroke display indicates the relative valve stroke. Depending on the tolerance limits, the fully closed position of the valve may vary. The maximum achievable valve stroke with a fully open valve seat varies according to the type and size of the valve: From 12 mm to 25 mm. During normal operation of an SKP25 actuator, it is also possible to observe the stability and oscillation tendency in addition to the opening of the valve seat.
Note! SKP15.000Ex actuators do not have a valve stroke display!
Page 5
5/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.1 Electrical connection
120 V~/230 V~ activation of the SKPx5 actuator
7643z43/070
6
N L 1 2
3
1
2
3
Potential-free end switch (indicating the fully closed position) only with the SKPx5.xx1xx actuator
123
123NL
Closed valve
7643z76en/1017
7643z77en/1017
For all types
Page 6
6/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.2 SKP15 actuator
7643z73/0 817
1
2
3
4
Valve stroke dis play
Indication of operating state (LED)
ƒ
Power supply
End switch (valve CLOSED)
Service note!
No spare parts are available for the SKP15 actuator (security regulating unit). The entire actuator can only be replaced by contacting the burner manufacturer.
Page 7
7/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.3 SKP25 actuator
7643z79/0817
1
2
3
4
5
7
6
AIR
GAS
Valve stroke dis play
Indication of operating state (LED)
ƒ
Power supply
End switch (valve CLOSED)
Setpoint spring setting
Vent opening / Assembly of the AGA25.2 damping throttle
Gas connection
Key
po Control pressure
Service note!
No spare parts are available for the SKP25 actuator (security regulating unit). The entire actuator can only be replaced by contacting the burner manufacturer.
Note! The vent opening must not be closed or clogged as a result of contamination.
Page 8
8/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.4 Description of the VGD4/VRD4 double gas valve
Work on the VGD4/VRD4 double gas valve may only be carried out by qualified personnel.
mbar
Maximum operating pressure Pmax = 100 kPa DN 40/50 Pmax = 70 kPa DN 65…150
Ambient temperature
-15...+60°C
Valve 1 + Valve 2, Class A, Group 2 according to EN 161
Gas Gaz
<60°C air Family 1 + 2 + 3
7643z83/0817
Built-in filter, mesh size 0.9 mm
2.5 Mounting position
7643z
84/03
1
8
AGA66
Β
Note! The AGA66 gasket set increases the degree of protection for the valve combination from IP54 to IP65!
2.6 Torques
Max. torques / flange connection and stud screws according to DIN 939 Tighten locking and connect ing screws in the
appropriate manner
Note the material pairing of aluminum/steel!
DN 40...100 M16 x 65 50 Nm DN 125 M16 x 75 50 Nm DN 150 M20 x 80 90 Nm
Max. torque of the pressure connections
M4 G1/8 G1/4 G3/4
3 Nm 8 Nm 15 Nm 35 Nm
Page 9
9/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.7 Installation dimensions for the VGD4 double
gas valve with SKPx5 actuator
7643z 70/0318
Type DN A B C D E F G H
SKP15
SKP25
H1 H2 H1 H2
VGD40.040 / L
VRD40.040
40 240 195 168 115 58 88 110 194 382 267 415 300
VGD40.050 / L
VRD40.050
50 240 202 175 115 58 88 125 194 382 267 415 300
VGD40.065 / L
VRD40.065
65 290 214 195 118 60 102 145 200 388 270 421 303
VGD40.080 / L
VRD40.080
80 310 236 204 132 54 107 160 224 412 280 445 313
VGD40.100 / L
VRD40.100
100 350 259 228 145 43 131 180 255 443 298 476 331
VGD40.125 / L
VRD40.125
125 400 305 256 175 31 150 210 303 491 316 524 349
VGD40.150
/ L
VRD40.150
150 480 335 294 188 20 168 240 333 521 333 554 366
VGD41.040
40 240 195 149 115 58 88 110 194 382 267 415 300
VGD41.050
50 240 202 160 115 58 88 125 194 382 267 415 300
VGD41.065
65 290 214 178 118 60 102 145 200 388 270 421 303
VGD41.080
80 310 236 192 132 54 107 160 224 412 280 445 313
VGD41.100
100 350 259 208 145 43 131 180 255 443 298 476 331
VGD41.125
125 400 305 236 175 31 150 210 303 491 316 524 349
VGD41.150
150 480 335 276 188 20 168 240 333 521 333 554 366
Β
Note! VGD40.xxxL double gas valves are supplied with reverse-mounted connecting plates.
Page 10
10/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
2.8 Pressure connections
7643z71/0318
VGD40/VRD40
VGD40/VRD40
Pressure switch connecting
plate
AGA40.40
7643z
71/0418
Pilot gas connecting plate
AGA40.41
Pressure switch connecting plate (mounted on both sides)
7643z71 /0418
VGD41
VGD41
Key
Mounting s urface of the QPLx5 pressure switch
+
Pressure connection for the QP Lx5 pressure
switch
Β
Not e!
Remove M4 locking screws as required.
(G 1/4") (G 1/8") (G 1/4") (G 3/4") (G 1/8") (G 1/4")
Strainer
1 9 3
452
7
6
8
V1 V2
7643z72en/0718
10
Key
pi Inlet pressure
pm Pressur e between valve
V1/V2
po Outlet pressure for valve V2
Page 11
11/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
3 Description of the mountable QPLx5
pressure switches
The QPLx5 pressure switch is designed to monitor the gas pressure. When the pressure falls below or exceeds the adjusted switching point, the respective electrical circuit will be opened or changes over.
Caution! Service note! The QPLx5 also has to be replaced when replacing a valve. It is recommended to replace the QPLx5 after over 50,000 cycles or a service life of 10 years due to the designed lifetime for gas pressure switches according to AFECOR. It is not recommended to reinstall these, even if the seals on the valve have been replaced.
¼'' double nipple required
7
631z5
4en/0
318
pipop (p)
m vps
QPL25
QPL25
p
i
QPL15
QPL15
QPL15
Page 12
12/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
Attachment options
7
643z85/0318
QPL15
pm
QPL15
pm
QPL15
pi
7643z86/0318
7
643z87/0318
3x pressure switches (2x pm, pi) Example (not binding)
Valve proving control "A"
Example (not binding)
Valve proving control "B" and
pressure switch QPL15 (pi) below
Key
pi Inlet pressure
pm (pvps) Pressure between valve V1/V2
po Outlet pressure for val ve V2
Page 13
13/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
4 Connection diagram
4.1 Function as a minimum/maximum pressure
switch
Minimum pressure switch
When the pressure falls below the set
value, NO opens and NC closes
Maximum pressure switch
When the pressure exceeds the set value,
NC opens and NO closes
4.2 Connection via connector AGA65 according to
DIN 43650
Page 14
14/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
5 Technical data
5.1 SKPx5 actuator
Operation DIN EN 60721-3-3
Climatic condit ions Class 3K3 Mechanical conditions Class 3M3 Temperature range -10…+60°C
(longer opening times below 0°C)
-20…+60°C (with heating element AGA63.5A27)
SKP25.2 -10…+50°C
(restricted operating conditions Humidity <95% r.h. Installation altitude Max. 2,000 m above sea level
5.2 VGD4/VRD4 double gas valve
Operation DIN EN 60721-3-3
Climatic condit ions Class 3K5 Mechanical conditions Class 3M2 Temperature range -10…60°C Humidity <95% r.h. Installation altitude Max. 2,000 m above sea level
Note! For the model number of the VGD4/VRD4 double gas valve, see the nameplate on the SKPx5 actuator!
5.3 QPLx5 pressure switch
Operation DIN EN 60721-3-3
Climatic condit ions Class 3K5 Mechanical conditions Class 3M2 Temperature range -15…+60°C Humidity <95% r.h.
Caution! Condensation, formation of ice, and ingress of water are not permitted.
Environmental conditions
Environmental conditions
Environmental conditions
Page 15
15/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
6 Spare parts and accessories
Please note the different article numbers for the VGD4/VRD4 double gas valves and the SKPx5 actuator when ordering spare parts.
Article no Type
Adapter plug
For powering both SKPx5 actuators on the VGD4/VRD4 double gas valve with an AGA64 connector.
BPZ:AGA62.000A000 AGA62.000A000
Contact box for valve actuator (power supply)
Plug-in connector conforming to DIN EN
175301-803-A
3-pole + protective ground Ø 6…9 mm / max. 1.5 mm²
BPZ:AG A64 AGA64
Contact box for end switch
Plug-in connector conforming to DIN EN
175301-803-A
3-pole + protective ground Ø 4.5…11 mm / max. 1.5 mm²
BPZ:AG A65 AGA65
Heating element
For use at low ambient temperatures
(-10…< -20°C)
Refer to data sheet N7923
BPZ:AGA63.5A27 AGA63.5A27
Gasket set
For mounting between SKPx5 actuator and
VGD4/VRD4 double gas valve
Increases degree of protection from IP54 to IP65 Take note of data sheet N7631 when using
VGD4/VRD4 double gas valves
Refer to Mounting Instruction M7643.2
(74 319 0421 0)
BPZ:AG A66 AGA66
Damping throttle for the SKP25 actuator
Optional
BPZ:AGA25.2 AGA25.2
Page 16
16/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
Article no Type
Setpoint spring (yellow/gold) for SKP25 actuator
Optional for built-in standard spring AGA29 1.5…12 kPa for SKP25.0 actuator 7…70 kPa for SKP25.4 actuator
(optionally for AGA23 setpoint spring)
Ø 1.6 mm
BPZ:AG A22 AGA22
Setpoint spring (red) for SKP25 actuator
Optional for built-in standard spring AGA29 10…25 kPa for SKP25.0 actuator 15…150 kPa as a standard spring for SKP25.4
actuator
Ø 1.8 mm
BPZ:AG A23 AGA23
Setpoint spring (unpainted) for SKP25.0 actuator
Equivalent built-in standard spring 0.05…2.2 kPa Ø 1 mm
BPZ:AG A29 AGA29
AGA30.x setpoint fine adjustment for SKP25
actuator
Packaging version with one setpoint spring each Refer to Mounting Instruction M7643
(74 319 0926 0)
Setpoint spring (gold)
1.5…12 kPa Ø 1.6 mm
BPZ:AGA30.0 AGA30.0
Setpoint spring (red)
10…25 kPa Ø 1.8 mm
BPZ:AGA30.1 AGA30.1
Setpoint spring (unpainted)
10…36 kPa Ø 2 mm
BPZ:AGA30.2 AGA30.2
Page 17
17/17
Building Technologies Operation Manu al and Mounting Instruc tions VGD4 / VRD4 / SKPx5 CC1U7643en
14.03.2018
7 Lifetime
The combination of VGD4/VRD4 double gas valve and SKPx5 actuator has a design lifetime* of
Nominal size Burner startup cycles
DN 25 200,000
DN 25...80 100,000
DN 80...150 50,000
when using gases according to EN 437 (or DVGW specification G260).
This is based on the endurance tests specified in the standard EN 161. A summary of the conditions has been published by the European Control Manufacturers Association (Afecor) (www.afecor.org).
The designed lifetime is based on the use of a VGD4/VRD4 double gas valve and an SKPx5 actuator according to the manufacturer’s data sheet. After reaching the designed lifetime in terms of the number of burner startup cycles, or after the corresponding usage time, the VGD4/VRD4 double gas valve and SKPx5 actuator must be checked and/or replaced by authorized personnel.
The criteria set out in EN 161 / EN 13611 are applicable when testing the tightness. This test can be omitted if a valve proving system is in place.
* The designed lifetime is not the warranty time specified in the Terms of Delivery.
Safety components
Structural lifetime
CEN standard
Number of cycles Time (years)
Gas pressure monitor 50,000 10 EN 1854
Double gas valve (with valve proving system)
After detecting a fault EN 1643
Double gas valve (without valve proving system)
50,000…200,000 10
EN 126 EN 161
Siemens AG Building Technologies Berliner Ring 23 76437 Rastatt, Germany Tel. +49 7222 598 279 Fax +49 7222 598 269 www.siemens.com
© 2018 Siemens AG Building Technologies
Subject to change!