Siemens TYPE VBII Series, Type 1, Type 3R, Type 4/4X, Type 9 Application Manual

...
Page 1
VBII Selection and Application Guide
Type VBII
safety
Page 2
You Asked for It. Siemens Listened.
Contents
Features 4-5
Enclosure Ratings and Types 6-10
General Duty Switches Features 12
General Duty Types 13
Heavy Duty Switches Features 14-15
Heavy Duty Switch Types 16-18
Special Application/ Interlocked Receptacle Switches 19-21
Accessories 22-24
Hub and Lug Data 25-26
Dimensions Special Application Safety switches 27
Double Throw Switches 28-29
Detailed Dimension Drawings 30-47
Replacement Parts 48
Siemens asked contractors for everything they wanted in an enclosed safety switch. Their input helped create the toughest, most reliable, most hassle-free enclosed safety switch in the business—the Siemens Type VBII Safety Switch. It’s a switch that’s right for any commercial, industrial or special use application. The Siemens Safety Switch line offers a list of important features that gives contractors a competitive edge:
• Highly visible, easy-to-grip red handle
• Visible blade construction
• Door that opens greater than 180º
• Quick-make, quick-break mechanism
• 200% optional neutrals (100-600 Amps)
• All copper current-carrying parts on heavy duty switches (except lugs)
• Positive two- and three-point mounting
Ratings
• 30-1200 amps
• 240 and 600 volts AC
• 250 and 600 volts DC
• 100 AlC for general duty switches
• 200 AlC for heavy duty switches
• Design E horsepower rated
• Suitable for use as service equipment
• Provisions for UL Class T, R, J, L and H fuses
• 12X overload rating that exceeds industrystandard of 10X
Fuse Application & Selection 49
Fuse Application & Dimensions 50-51
Ratings & Test Requirements 52-53
Suggested Specifications 54-55
Catalog Numbering System 56
2
Page 3
One Tough Switch: Siemens Type VBII Safety Switch
closed
in operation
Siemens now offers a complete line of enclosed switches featuring unique and innovative designs that
are unparalleled in the industry.
General and Heavy Duty Switches Feature a Time-Proven Design
Like the time-proven Vacu-Break design, the Siemens VBII double-break switch­ing action breaks the arc in two places. This reduces heat generation and increases switching speed by doubling the breaking distance. The result is enhanced performance and increased longevity. We also provide the most visible blade design available today. Unlike conventional knife blade switch­es, the blades are self-aligning to ensure positive contact. In addition, they have no wear and friction point since the “electrical hinge” has been eliminated. The result is a very fast, positive and reliable switching action for even the most severe applications.
One Tough Switch: More Rugged and Durable in Demanding Applications
Siemens engineers tackled the problem of designing a switch that would stand up under the most demanding industrial conditions, such as those in steel mills and mining operations. These environments require a switch that must work reliably and safely in the midst of falling liquids, airborne fibers, dust, metal particles, coolants and other contaminants.
Tested and Retested
All Siemens safety switches have been tested not only to meet but to exceed all UL requirements. These tests include those for general purpose enclosed switches and those designed for more specialized purposes where applicable. The result is a rugged, reliable design that will provide superior performance in a wide variety of applications.
open
3
Page 4
General and Heavy Duty Features
Siemens Type VBII Safety Switch
Application General Duty Switches
General Duty Switches are intended for applications where reliable performance and continuity of service are needed, but where duty requirements are not severe and usual service conditions prevail. These switches are intended for use primarily with supply circuits rated 240V AC or less where the available fault current is less than 100,000A when used with Class R or T fuses or 10,000A max. when used with Class H fuses.
Application Heavy Duty Switches
Heavy Duty Switches are intended for use in applications where:
1. Rugged construction, reliable performance, continuity of service and ease of maintenance are emphasized
2. Available fault currents higher than 10,000A are likely to be encountered, such as in manufacturing plants, mass production industries and commercial, institutional and other large buildings served by network systems or transformers of higher capacities
3. System voltage is 600V AC or DC max
4. A Type 12 or 4 / 4X enclosure is required
Short-circuit Withstand Ratings General Duty Switches
Suitable for use on systems capable of delivering not more than 100,000 RMS symmetrical amperes of fault current when Class R fuses are installed. Also rated 100,000 AC max. in 200-600A ratings with Class J and T fuses.
Short Circuit Withstand Ratings Heavy Duty Switches
Suitable for use on systems capable of delivering not more than 200,000
➀
RMS
symmetrical amperes of fault current when Class J or R fuses are installed except the 800 and 1200A switches, which are suitable for use on circuits capable of delivering not more than 200,000 RMS symmetrical amperes of fault current when Class L fuses are installed. 100-1200A switches with Class T fuses and field adapter kit are also 200,000 RMS symmetrical rated.
Fuses
General Duty Switches Fusible switches will accept the following UL class fuses: Class H Class K Class R—Class R fuse clip rejecter kits are required. Class T—200-600A switches (200A switches require field adapter kit)
Heavy Duty Switches
Fusible switches will accept the following UL class fuses: Class H Class K Class R—Class R fuse clip rejecter kits are required Class J—240 and 600V switches 600V switches are field convertible Class L—800 and 1200A switches only Class T—100-1200A switches (100 and 200A switches require an adapter kit)
Cover Interlocks General Duty Switches
Defeatable-cover interlocks on Type 1 switches and 60-600A Type 3R switches prevent the switch door from being opened when in the ON position.
Heavy Duty Switches
Defeatable dual cover interlocks are standard on all heavy duty switches. Prevents cover from being opened when switch is in the ON position and prevents switch from being turned ON when door is opened.
Padlocks
General & Heavy Duty Switches Padlockable cover latch and multiple padlock provisions on handle.
NEMA Specifications
Meets NEMA standard KS-1-1990 for type GD and HD switches.
4
➀ 100,000 RMS for 60 A compact non-fusible switches.
Page 5
Underwriters’ Laboratories Inc.
Listed by UL under file #E4776 as enclosed switches and also suitable for use as service equipment except on 1200A switches on Y systems of more than 150V to ground.
Meets UL98 standard for enclosed switches and enclosures
Type 1 switches—general purpose enclo­sures (Type 1) Type 3R switches—rainproof enclosures (Type 3R) Type 4/4X switches—special purpose enclosures (Type 4/4X) Type 12 switches—special purpose enclosures (Type 12).
Groundable Neutrals
General & Heavy Duty Switches Switches designed for use on systems requiring neutrals to have groundable neutral blocks.
Feature Comparison
General Heavy Double
Duty Duty Throw Features / Ratings
✓✓✓30-600 Amps
✓✓800 and 1200 Amps
✓✓✓240 Volts AC
✓✓600 Volts AC
✓✓✓250 Volts DC
✓ 600 Volts DC
✓✓✓Double-break visible blade
design (30-200A)
✓✓✓ ✓✓✓Highly visible ON/OFF handle indication
✓ Handle design for hook stick operation ✓✓✓Padlockable cover latch ✓✓✓Padlockable handle
➂
✓
✓ Single voidable cover interlock
✓✓Dual voidable cover interlock ✓✓✓Type 1 enclosure ✓✓✓Type 3R enclosure
✓✓Type 12 enclosure
✓✓Type 4/4X enclosure ✓✓✓
✓✓✓Lugs suitable for copper or aluminum
✓✓✓CU/AL wire lugs that meet
✓✓Suitable for field-convertible
➅ ✓✓All plated copper current carrying parts
✓✓✓Spring reinforced Fuse Clips
✓✓Clear pivoting line terminal shield ✓✓✓Replacement parts
✓ Field addable 200% neutral
➆
✓
➆
✓
✓
✓✓➀Provisions for UL Class J and L fuses
✓✓Metal nameplate
✓✓Aux. switch kit
➃ Type 4X with stainless steel interior parts
➄
✓
✓ Rolled flange enclosure design (30-200A)
✓ UL approved HP ratings for
✓ high efficiency motors
✓✓Isolated ground kits
Quick-make, quick-break switching action
Generous wiring gutters that meet UL and NEC wire-bending space requirements
at 60˚C or 75˚C
UL 486B requirements
compression connectors
(except lugs)
(except 30A general duty)
➀
Provisions for UL Class T, R and H fuses
➀ 400 & 600A fusible, double-throw switches accept only Class J or T fuses. ➁ 30A general duty switches have fuse clips constructed of spring type copper. ➂ Not supplied on 30A outdoor & plug fuse switches. ➃ 30-200A Type VBII in stainless steel enclosures. ➄ 60-200A ➅ 200A general duty switches have aluminum neutral assemblies. ➆ 100-600A GD and 100-1200A HD switches will accept Class T fuses
5
Page 6
Type 1 Enclosure
Siemens Type VBII Safety Switch
Type 1 enclosures are intended for
indoor use primarily to provide protection against contact with the enclosed equipment in locations where unusual service conditions do not exist.
Features
• Tangential knockouts in all box surfaces (30-600A HD & 60-600 GD)
• Two- and three-point mounting with top keyhole
• Formed flange enclosure edges
• 180º plus side opening door
• Drawn cover design for increased durability and resistance to damage (30-600A)
• Rugged metal handle with a red insulating grip
• Front operable cover interlock release with positive rotating release action (30-1200A heavy duty and 60-600A general duty)
• Metal nameplates on all heavy duty switches
• 30 & 60A Heavy Duty & 60A
General Duty switches have
tangential knockouts which
are UL approved for bonding
conduits for non-service
entrance conductors.
6
Page 7
Type 3R Enclosure
Type 3R enclosures are intended
for outdoor use primarily to provide a degree of protection against falling rain and sleet, and must remain undamaged by the formation of ice on the enclosure. They are not intended to provide protection against conditions such as dust, internal condensation or internal icing.
Features
• Tangential knockouts in all box surfaces below lowest live parts (30-600A)
• Two- and three-point mounting with top keyhole
• Formed flange enclosure edges
• 180º plus side opening door
• Double overlap enclosure door top to provide superior protection against entry of rain
• Type HA hub provision 30A general duty
• Type HS hub provision (30-200A switches)
• Galvanized steel construction
• Drawn cover design for increased durability and resistance to damage (30-200A)
• Rugged metal handle with a red insulating grip
• Front operable cover interlock release with positive rotating release action (30-1200A heavy duty and 60-600A general duty)
• Metal nameplates on all heavy
duty switches
7
Page 8
Type 4/4X Enclosure
Siemens Type VBII Safety Switch
Type 4/4X enclosures are intended for
indoor or outdoor use primarily to provide a degree of protection against windblown dust, rain, splashing water and hose-directed water. They are not intended to provide protection against conditions such as internal condensation or internal icing. Also meets 4X definition by providing a high degree of protection against corrosion.
Features (Standard 4X)
• Ground lugs installed as standard
• External mounting feet with two-, three- and four-point mounting
• Formed front gasket flange with continuously welded seams
• Heavy duty front opening low-profile stainless
steel latches
• Stainless steel enclosure
• Stainless steel interior parts on 30-200A switches
• Formed out enclosure flanges that prevent liquid entry when door is open
• Rugged hinge design
• 180º-plus opening door
• Rugged metal handle with a red insulating grip
• Front operable cover interlock release with positive rotating release action (30-1200A heavy duty)
• Stainless steel nameplate
Features (Non-Metallic 4X)
• External mounting
• Ground lug installed as standard
• Fiberglass reinforced polyester enclosure
• No external metal parts
• Removable door for easy wiring
• Front operable cover interlock release with positive rotating release action
8
Page 9
Type 3R / 12 Enclosure
Type 3R / 3S enclosures are
intended to provide a degree of protection against windblown dust, and to allow operation when ice-laden. They are not intended to provide protection against conditions such as condensation or internal icing.
Type 12 enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt and dripping water. They are not intended to provide protection against conditions such as internal Command.
Features
• External mounting feet with two, three and four-point mounting
• Formed front gasket flange
• Unique heavy duty front opening low-profile latches
• Galvanized steel enclosure
• Formed out enclosure flanges that provide an added degree of protection against entry of dust
• Rugged hinge design
• 180º-plus opening door
• 3R / 3S / 12 rating as standard allows outdoor use
• Rugged metal handle with a red insulating grip
• Front operable cover interlock release with positive rotating release action (30-1200A heavy duty)
• Metal nameplates on Type 3S / 12 enclosures
9
Page 10
Type 7 and 9 Enclosure
Siemens Type VBII Safety Switch
Type 7 enclosures are intended for indoor use in locations classified as Class I, Groups A, B, C or D as defined in the National Electrical Code.
Type 9 enclosures are intended for indoor use in locations classified as Class II, Groups E, F or G as defined in the National Electrical Code.
Features
• Molded case switch available in 30-600A ratings
• Cast aluminum enclosure
• External door clamps
• External mounting feet
• Metal nameplate
10
Page 11
General Duty Switches
Plug Fuse and Special Application Types
Features ƒ
• Compact size
• Visible blade, double-break switching action
• Quick-make, quick-break operating mechanism
• Highly visible ON/OFF indicators
• Padlock-off handle feature
• Door padlock provision
• Bondable neutral (where indicated)
• Lugs suitable for copper or aluminum wire
• 30A cartridge fuse switches rated 100,000 AC with Class R fuses
Indoor-Type 1 Outdoor-Type 3R Horsepower Ratings ➅
Ampere Catalog Ship. Dwg. Catalog Ship. Dwg. 1-Phase, 2-Wire
Rating Number Wgt.*
➀
Fig. Number Wgt.*
➀
Fig.
Std. Max
120/240 Volt Fusible (Plug Fuse Type) 10,000 AIC Max
1-Pole and Solid Neutral 120 Volt - 1-Phase, 2-Wire
30 LF111N 31 1 LF111NR 35 12 1/2 2
2-Pole and No Neutral 120/240V - 1-Phase, 2-Wire
30 — — — Use 2-Pole and Solid Neutral
2-Pole and Solid Neutral 120/240V - 1-Phase, 3-Wire
30 LF211N 37 1 LF211NR 35 12 1 1/2 3
240 Volt Non-Fusible (Special Application)
2-Pole 240 Volt - 1- or 2-Pole - No Fuse 240 Volt - 1 Phase, 2 Wire
60 — — — LNF222R
➁
35 12
➁
—10
Selection Information - Fused/Non-Fused Pullouts ➁
Ampere Number Number Number Catalog Shipping Dimensions (Inches)
Rating of Poles of Blades of Fuses Number Weight* Height Width Depth
Fused Pullout - 1-Phase, 2-Wire
30 ➆ 2 2 2 WF2030 21 ➇ 9 1/8 60
➃
2 2 2 WF2060 5 9 1/8 5 5/32 3 7/16
Non-Fused Pullout - 1-Phase, 2-Wire
60 2 2 — WN2060 15 ➇7 3/8 5 5/32 3 7/16
➂
10,000 AIC Max
➃
5 5/32 3 7/16
240 Volts AC
240 Volts AC
* In pounds (lbs).
➀ Package of 10. ➁ No hub provision with this switch. ➂ Fuses - not included. ➃ Max. horsepower rating - 10. ➄ Features apply to 30A General Duty
and Plug Fuse Type Switches.
➅ Dual horsepower ratings:
Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed.
➆ Max. horsepower rating – 3 ➇ Package of 6
11
Page 12
General Duty Switches-Features (60-600A)
11
5
9
3
6
10
1
8
4
1. Cover interlock
2. Tangential knockouts through 600A for easy conduit lineup
3. Quick-make, quick-break operat­ing mechanism that ensures positive operation
4. Provisions for T, R, J, H and K class fuses (T & J 200-600A)
12
2
5. Generous wiring gutters that meet or exceed NEC wire­bending space requirements
6. Visible blade, double-break switch action
7. Positive two- or three-point mounting
8. Highly visible red handle grip
9. Informative door labeling which includes replacement parts list
7
12
10. Handle and cover padlocking provisions
11. Side-hinged door that opens
180 degrees for easier wiring
12. A unique enclosure design that
adds rigidity and strength. Its rolled edge prevents cuts and scrapes to conductors and to installers’ hands
Page 13
General Duty Switches
Indoor - Type 1 Outdoor - Type 3R
Ampere Catalog Ship. Dwg. Catalog Ship. Dwg.
System Rating Number Wgt.* Fig Number Wgt.* Fig.
Horsepower Ratings ➀
240 Volt AC
1-Phase, 2-Wire 2-Phase, 4-Wire 3-Phase, 3-Wire
Std. Max. Std. Max. Std. Max. Std.
250
Volt
DC
240 Volt Fusible
2-Pole, 2-Fuse and Solid Neutral ➁ 240 Volt AC / 250 Volt DC
30 GF221N 35 (10) 1 GF221NR 35 (10) 12 1 1/2 3 — — 3 7 1/2 5
60 GF222N 12 4 GF222NR 13 15 3 10 — — 7 1/2 15 10 100 GF223N 20 6 GF223NR 21 17 7 1/2 15 — — 15 30 20 200 GF224N 43 7 GF224NR 44 18 15 — — — 25 60 40 400 GF225NH➂128 9 GF225NRH➂130 20 15 –– –– –– 50 125 50 400 GF225N 160 9 GF225NR 163 20 15 — — — 50 125 50 600 GF226NH➂133 9 GF226NRH➂135 20 15 –– –– –– 75 200 –– 600 GF226N 161 9 GF226NR 170 20 15 — — — 75 200 —
3-Pole, 3-Fuse and Solid Neutral 240 Volt AC / 250 Volt DC
30 GF321N 24 (5) 2 GF321NR 24 (5) 13 1 1/2 3 — — 3 7 1/2 5
60 GF322N 13 4 GF322NR 13 15 3 10 — — 7 1/2 15 10 100 GF323N 21 6 GF323NR 22 17 7 1/2 15 — — 15 30 20 200 GF324N 44 7 GF324NR 45 18 15 — — — 25 60 40 400 GF325NH➂ 136 9 GF325NRH➂ 138 20 15 –– –– –– 50 125 50 400 GF325N 169 9 GF325NR 168 20 15 — — — 50 125 50 600 GF326NH➂ 138 9 GF326NRH➂ 141 20 15 –– –– –– 75 200 –– 600 GF326N 171 9 GF326NR 172 20 15 — — — 75 200 —
4-Pole, 4-Fuse Vacu-Break Type 240 Volt AC / 250 Volt DC
30 JF421 12 — — — — — — 3 10 — — —
60 JF422 13 — — — — — — 7 1/2 20 — — — 100 JF423 23 — — — — — — 15 30 — — — 200 JF424 56 — — — — — — 30 50 — — — 400 JF425 150 — — — — — — — — — — — 600 JF426 165 — — — — — — — — — — —
240 Volt Non-Fusible
2-Pole or 3-Pole 240 Volt AC / 250 Volt DC
* In pounds (lbs).
➀ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. ➁ These switches are UL-listed for application on grounded B-phase systems. ➂ Height reduced switch with 500 MCM max. wire bending space.
30 GNF321 24 (5) 2 GNF321R 24 (5) 13 3 — — — 7 1/2 — 5
60 GNF322 11 3 GNF322R 11 100 GNF323 19 6 GNF323R 20 200 GNF324 41 7 GNF324R 42 18 15 — — — 400 GNF325 125 8 Use 600V Switch - HF365R 15 — — 600 GNF326 132 8 Use 600V Switch - HF366R 15 — — —
14 17
10 — — — 15 — — —
15 30 60
— 125
200
— — — — ——
10 20 40 50
13
Page 14
Heavy Duty Switches
Features
15
18
1. Quick-make, quick-break operating mechanism that ensures positive operation
3
2
2. Visible blade, double-break switching action
3. Arc chutes dissipate heat and prolong switch life
4. Highly visible red handle grip designed for hook stick operation
5. Defeatable dual cover interlock
4
6. Center punch provided for field drilling to allow ON padlocking
7. Handle can be padlocked in the OFF position with up to three padlocks with 5/16” hasps
8. Generous top, bottom and side gutters that meet
6
or exceed NEC wire-bending space requirements
9. Informative door labeling, which includes replacement parts list
10.Tangential knockouts through 600A for easy conduit
lineup
14
10
11.Side-hinged door that opens past 180 degrees for easier
wiring
12.Unique enclosure design increases rigidity and prevents cuts and scrapes to conductors and installers’ hands
13.Spring reinforced fuse clips that assure reliable contact for cool operation
14.Door latch securely holds door closed and allows cover padlocking
7
15.Front removable mechanical lugs that are suitable for CU/AI 60˚C or 75˚C conductors
16.Lugs are field convertible to copper body and to a wide variety of compression connectors
17.Hinged clear line terminal shield with probe holes for inspecting or testing line side terminals
18.Embossed aluminum nameplate on Heavy Duty Switches provides highly visible ON/OFF indication
19.Drawn cover for increased rigidity and resistance to abuse
20.Top key hole and bottom mounting holes provide easy two- or three-point mounting
Page 15
20
11
17
16
9
1
19
5
13
8
14
12
15
Page 16
Heavy Duty Switches
Horsepower Ratings ➀
Indoor - Type 1 Outdoor - Type 3R 240 Volt AC
System Rating Number Wgt.* Fig. Number Wgt.* Fig. Std. Max. Std. Max. Std. Max. DC
Ampere Catalog Ship. Dwg. Catalog Ship. Dwg.
1-Phase, 2-Wire 2-Phase, 4-Wire 3-Phase, 3-Wire Volt
240 Volt Fusible
2-Pole, 2-Fuse and Solid Neutral
30 HF221N 13 4 HF221NR 13 15 1 1/2 3 — — 3 7 1/2 5
60 HF222N 16 5 HF222NR 17 16 3 10 — — 7 1/2 15 10 100 HF223N 21 6 HF223NR 22 17 7 1/2 15 — — 15 30 20 200 HF224N 44 7 HF224NR 48 18 15 — — — 25 60 40 400 HF225NH➂129 9 HF225NRH➂131 20 15 –– –– –– 50 125 50 400 HF225N 150 9 HF225NR 157 20 15 — — — 50 125 50 600 HF226NH➂133 9 HF226NRH➂135 20 15 –– –– –– 75 200 –– 600 HF226N 159 9 HF226NR 162 20 15 — — — 75 200 — 800 HF227N 360 11 HF227NR➀362 22 — — — — 100 250 —
1200 HF228N 362 11 HF228NR➀364 22 — — — — 100 250 —
3-Pole, 3-Fuse and Solid Neutral (Also used for 3-Pole, 3-Wire Applications) 240 Volt AC / 250 Volt DC
30 HF321N 13 4 HF321NR 14 15 1 1/2 3 — — 3 7 1/2 5
60 HF322N 17 5 HF322NR 18 16 3 10 — — 7 1/2 15 10
100 HF323N 22 6 HF323NR 22 17 7 1/2 15 — — 15 30 20 200 HF324N 49 7 HF324NR 50 18 15 — — — 25 60 40 400 HF325NH➂ 137 9 HF325NRH➂ 138 20 15 –– –– –– 50 125 50 400 HF325N 164 9 HF325NR 162 20 15 — — — 50 125 50 600 HF326NH➂ 139 9 HF326NRH➂ 142 20 15 –– –– –– 75 200 –– 600 HF326N 165 9 HF326NR 169 20 15 — — — 75 200 — 800 HF327N 380 11 HF327NR ➀ 383 22 — — — — 100 250 —
1200 HF328N 382 11 HF328NR ➀ 385 22 — — — — 100 250 —
➁
(Also used for 2-Pole, 2-Wire Applications) 240 Volt AC / 250 Volt DC
240 Volt Fusible
250
2-Pole, 2-Fuse Type 4 / 4X Stainless Type 12 Industrial 240 Volt AC / 250 Volt DC
30 HF221S 17 24 HF221J 16 24 1 1/2 3 — — 3 7 1/2 5 60 HF222S 23 25 HF222J 22 25 3 10 — — 7 1/2 15 10
100 HF223S 28 26 HF223J 26 26 7 1/2 15 — — 15 30 20 200 HF224S 52 27 HF224J 48 27 15 — — — 25 60 40
3-Pole, 3-Fuse (Also used for 2-Pole, 2-Wire Applications in 400-800A Ratings) 240 Volt AC / 250 Volt DC
30 HF321S 17 24 HF321J 16 24 — — — — 3 7 1/2 —
60 HF322S 23 25 HF322J 23 25 — — — — 7 1/2 15 10
100 HF323S 29 26 HF323J 26 26 — — — — 15 30 20 200 HF324S 56 27 HF324J 53 27 — — — — 25 60 40 400 HF325S 170 29 HF325J 165 29 — — — — 50 125 50 600 HF326S 170 29 HF326J 166 29 — — — — 75 200 — 800 HF327S 367 31 HF327J
* In pounds (lbs).
➀ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. ➁ These switches are UL-listed for application on grounded B-phase systems. ➂ Height reduced switch with 500 MCM max. wire bending space.
➀
367 31 — — — — 100 250 —
16
Page 17
Heavy Duty Switches
Horsepower Ratings ➂
Indoor - Type 1 Outdoor - Type 3R 480 Volt AC 600 Volt AC
Ampere Catalog Ship. Dwg. Catalog Ship. Dwg.
System Rating Number Wgt.* Fig. Number Wgt.* Fig.
600 Volt Fusible
2-Pole, 2-Fuse
3-Pole, 3-Fuse 480 Volt AC / 600 Volt AC / 250 Volt DC
3-Pole, 3-Fuse and Solid Neutral 480 Volt AC / 600 Volt AC / 250 Volt DC
➁
30 HF261 13 4 HF261R 13 15 3 7 1/2 – – 3 10 – – 5 15
60 HF262 16 5 HF262R 17 16 5 20 – – 10 25 – – 10 30 100 HF263 21 6 HF263R 22 17 10 30 – – 15 40 – – 20 50 400 HF265 149 9 HF265R 152 20 – 50 – – 50 – – – 40 50 600 HF266 155 9 HF266R 157 20 – 50 – – 50 – – – 50 50
30 HF361 13 4 HF361R 13 15 3 7 1/2 5 15 3 10 7 1/2 20 5 —
30 HF361L
60 HF362 19 5 HF362R 19 16 5 20 15 30 10 25 15 50 10 25
60 100 HF363 24 6 HF363R 24 17 10 30 25 60 15 40 30 75 20 25 200 HF364 44 7 HF364R 45 18 25 50 50 125 30 50 60 150 40 50 400 HF365H 400 HF365 162 9 HF365R 162 20 — — 100 250 — — 125 350 50 — 600 HF366H 600 HF366 166 9 HF366R 167 20 — — 150 400 — — 200 500 — — 800 HF367 380 11 HF367R 382 22 — — 200 500 — — 250 500 — —
1200 HF368 383 11 HF368R 385 22 — — 200 500 — — 250 500 — —
30 HF361N 13 4 HF361NR 15 15 3 7 1/2 5 15 3 10 7 1/2 20 5 —
60 HF362N 19 5 HF362NR 20 16 5 20 15 30 10 25 15 50 10 25 100 HF363N 24 6 HF363NR 26 17 10 30 25 60 15 40 30 75 20 25 200 HF364N 45 7 HF364NR 50 18 25 50 50 125 30 50 60 150 40 50 400 HF365N 171 9 HF365NR 162 20 — — 100 250 — — 125 350 50 — 600 HF366N 172 9 HF366NR 165 20 — — 150 400 — — 200 500 — — 800 HF367N 382 11 HF367NR 386 22 — — 150 400 — — 200 500 — —
1200 HF368N 385 11 HF368NR 388 22 — — 150 400 — — 200 500 — —
➄
19 5 HF361RL
———
➅
136 9 HF365RH
➅
138 9 HF366RH
HF362RL
➄
19 16 3 7 1/2 5 15 3 10 7 1/2 20 5 —
➄
24 17 5 20 15 30 10 25 15 50 10 25
➅
137 20 — — 100 250 — — 125 350 50 —
➅
141 20 — — 150 400 — — 200 500 — —
1-Ø, 2-Wire 3-Ø 3-Wire 1-Ø 2-Wire 3-Ø 3-Wire
Std. Max. Std. Max. Std. Max.
480 Volt AC / 600 Volt AC / 600 Volt DC
Std. Max.
250 Volt
DC
➀
➀
600 Volt
DC
➃ ➃ ➃ ➃
➃ ➃ ➃
600 Volt Fusible (For 2-Pole Applications use outside poles of 3-Pole Switches)
2-Pole, 2-Fuse
3-Pole, 3-Fuse
* In pounds (lbs).
➀ 60-200A 3-Pole switches are also rated 600V DC. ➄ Indicates oversized enclosure (30A switch in a 60A enclosure or a 60A switch in a 100A enclosure). ➁ Use 3-Pole switch for 200A applications. ➅ Height reduced switch with 500 MCM max. wire bending space. ➂ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. ➃ 600V DC rating and 600V DC HP rating requires two poles to be connected in series.
➁
30 HF261S –– 17 24 HF261J — 13 24
60 HF262S — 23 25 HF262J — 22 25 100 HF263S — 29 26 HF263J — 27 26 400 HF265S — 170 29 HF265J — 165 29 600 HF266S — 170 29 HF266J — 166 29
30 HF361S HF361SW 17 24 HF361J HF361JW 17 24
60 HF362S HF362SW 23 25 HF362J HF362JW 22 25 100 HF363S HF363SW 29 26 HF363J HF363JW 26 26 200 HF364S HF364SW 56 27 HF364J HF364JW 53 27 400 HF365S HF365SW 173 29 HF365J HF365JW 166 29 600 HF366S –– 175 29 HF366J HF366JW 168 29 800 HF367S –– 380 31 HF367J –– 380 31
1200 HF368S –– 384 –– HF368J –– 384 31
Type 4 / 4X Stainless Type 12 Industrial 480 Volt AC / 600 Volt AC / 600 Volt DC
Standard
Cat. No.
Window
Switch
Cat. No.
Ship
Wgt.*
Dwg.
Flg.
Standard
Cat. No.
Window
Switch
Cat. No.
Ship
Wgt.
*
Dwg.
Flg.
10 –– ––
10 25 –– –– –– ––
7 1/2
3
20
5
30 50 50
7 1/2
3
20
5
30 50 –– –– –– ––
––
––
––
––
––
––
––
––
––
––
480 Volt AC / 600 Volt AC / 250 Volt DC
5
15
15
30
25
60
50
125
100
250
150
400
200
500
200
500
10 15 50 50
–– –– –– –– –– –– –– ––
10
3
25 40 –– ––
–– –– –– –– –– –– –– ––
–– –– –– –– ––
7 1/2
15 30
60 125 200 250 250
–– –– –– –– ––
20 50
75 150 350 500 500 500
10 20 40 50
10 20 40 50 –– –– ––
5
15 30 50 50 50
➀
––
5
➃
25
➃
25
➃
50
–– –– –– ––
17
Page 18
Heavy Duty Switches
Indoor - Type 1 Outdoor - Type 3R Horsepower Ratings
System Rating Number Wgt.* Fig. Number Wgt.* Fig. 1Ø 3Ø 1Ø 3Ø 1Ø 3Ø DC DC
Ampere Catalog Ship. Dwg. Catalog Ship. Dwg.
600 Volt Non-Fusible (Also used for 240V Applications)
➁
2-Pole
30 HNF261 11 3 HNF261R 11 14 — — 7 1/2 — 10 — 5 15
60 HNF262 16 5 HNF262R 18 16 — — 20 — 25 — 10 30 100 HNF263 19 6 HNF263R 20 17 — — 30 — 40 — 20 50 400 HNF265 126 8 HNF265R 129 19 15 — 50 — 50 — 40 50 600 HNF266 127 8 HNF266R 129 19 15 — 50 — 50 — 50 50
3-Pole 480 Volt AC / 600 Volt AC / 250 Volt DC
30 HNF361 12 3 HNF361R 13 14 3 10 7 1/2 20 10 30 5 —
30
60 HNF362H
60 HNF362 18 5 HNF362R 19 16 10 20 20 50 25 60 10 25
60 100 HNF363 23 6 HNF363R 24 17 15 40 30 75 40 100 20 25 200 HNF364 42 7 HNF364R 43 18 15 60 50 125 50 150 40 50 400 HNF365 132 8 HNF365R 129 19 15 125 50 250 50 350 50 — 600 HNF366 133 8 HNF366R 130 19 15 200 50 400 50 500 — — 800 HNF367 302 10 HNF367R
1200 HNF368 305 10 HNF368R
———
➄
12 3 HNF362RH➄13 14 10 20 20 50 10 40 5 ––
———
HNF361RL
HNF362RL
➃
19 16 3 10 7 1/2 20 10 30 5 ––
➃
24 17 10 20 20 50 25 60 10 25
➁
305 21 15 250 50 500 50 500 — —
➁
307 21 15 250 50 500 50 500 — —
240 Volt 480 Volt 600 Volt 250V 600V
480 Volt AC / 600 Volt AC / 600 Volt D
➀
➂ ➂ ➂ ➂
600 Volt Non-Fusible (Also used for 240V Applications)
2-Pole ➁ Type 4 / 4X Stainless Type 12 Industrial 480 Volt AC / 600 Volt AC / 600 Volt DC
Standard
Cat. No.
30 — — 7 1/2 — 10 — 5 15
HNF261S
60 — — 20 — 25 — 10 30
HNF262S
100 — — 30 — 40 — 20 50
HNF263S
400 15 — 50 — — — 40 50
HNF265S
600 15 — 50 — — — 50 50
HNF266S
3-Pole 480 Volt AC / 600 Volt AC / 250 Volt DC
* In pounds (lbs)
➀ 60-200A Three-Pole switches are also rated 600V DC. ➃ Indicates oversized enclosure (30A switch in a 60A enclosure or a 60A switch in a 100A enclosure).
18
➁ Use Three-Pole switch for 200A application. ➄ Compact switch with 100,000 RMS Sym short circuit rating. ➂ 600V DC rating and 600V DC HP rating requires
two poles to be connected in series.
HNF361S
30 3 10 7 1/2 20 10 30 5 —
HNF362SH➄
60 10 20 20 50 10 40 5 ––
HNF362S
60 10 20 20 50 25 60 10 25
HNF363S
100 15 40 30 75 40 100 20 25
HNF364S
200 15 60 50 125 50 150 40 50
HNF365S
400 15 125 50 250 50 350 50 —
HNF366S
600 15 200 50 400 50 500 — —
HNF367S
800 15 250 50 500 50 500 — —
HNF368S
1200 15 250 50 500 50 500 –– ––
Window
Switch Cat. #
–– –– –– –– ––
HNF361SW
–– HNF362SW HNF363SW HNF364SW HNF365SW
––
––
––
Ship
Wgt.*
15 24
28 137 138
15 15 23 27
55 133 134 302 308
Dwg.
Fig.
23 25 26 28 28
23 23 25 26 27 28 28 30 ––
Standard
Cat. No.
HNF261J HNF262J HNF263J HNF265J HNF266J
HNF361J HNF362JH➄ HNF362J HNF363J HNF364J HNF365J HNF366J HNF367J HNF368J
Window
Switch Cat.
–– –– –– –– ––
HNF361JW
–– HNF362JW HNF363JW HNF364JW HNF365JW
__
__
__
#
Ship
Wgt.*
13 21
25 122 128
14 14 19 25
51 129 130 302 308
Dwg
Fig.
23 25 26 28 28
➀
23 23 25 26 27 28 28 30 30
➂ ➂ ➂
Page 19
Heavy Duty
Special Application / Interlocked Receptacle Switches
Application
Receptacle Safety Switches provide cord connection protection of heavy-duty portable equipment (welders, infrared ovens, batch feeders, portable convey­ors, assembly line fixtures and tools, refrigerator trucks, etc.) under load or fault conditions. All receptacle switches are supplied with 4 prong receptacles. (3 phase, 3W plus ground)
Description
➀ ➁
Type 12 and 4/4X Receptacle Safety Switches are available with 3­phase, 4-wire grounded type Crouse­Hinds Arktite™ 2 or Pyle-National prewired and mounted receptacles with interlock linkage to the switch mechanism. Insertion or removal of the plug is prevented by the interlock linkage while the switch is in the ON position. Receptacle prevents operation of switch if incorrect plug is inserted.
Crouse-Hinds Interlocked Receptacle Switches
➅
Ampere Catalog Catalog Weight Arktite➀Plug
➄
Rating
240V Fusible, 3-Pole, 3-Wire
30 HF321JCH HF321SCH 23 APJ3485 & NPJ3485 60 HF322JCH HF322SCH 30 APJ6485 & NPJ6485
100 HF323JCH HF323SCH 36 APJ10487 & NPJ10487
600V Fusible, 3-Pole, 3-Wire
30 HF361JCH HF361SCH 24 APJ3485 & NPJ3485 60 HF362JCH HF362SCH 30 APJ6485 & NPJ6485
100 HF363JCH HF363SCH 36 APJ10487 & NPJ10487
600V Non-Fusible, 3-Pole, 3-Wire
30 HNF361JCH HF361SCH 22 APJ3485 & NPJ3485 60 HNF362JCH HF362SCH 29 APJ6485 & NPJ6485
100 HNF363JCH HF363SCH 35 APJ10487 & NPJ10487
Type 12
Number Number Std. Pkg.
Type 4/4X
➆
Shipping Accepts Crouse-Hinds
➃
Catalog Number
600V Fusible, 3-Pole, 3-Wire with Viewing Window
30 HF361JCHW HF361SCHW 24 APJ3485 & NPJ3485 60 HF362JCHW HF362SCHW 30 APJ6485 & NPJ6485
100 HF363JCHW HF363SCHW 36 APJ10487 & NPJ10487
600V Non-Fusible, 3-Pole, 3-Wire with Viewing Window
30 HNF361JCHW HNF361SCHW 22 APJ3485 & NPJ3485 60 HNF362JCHW HNF362SCHW 29 APJ6485 & NPJ6485
100 HNF363JCHW HNF363SCHW 35 APJ10487 & NPJ10487
Pyle-National Interlocked Receptacle Switches 3 Poles Fusible and Non-Fusible
Ampere Rating
Switch Recept.
30 30 600 (F) HF361JPN HF361SPN 23 JPD-83046
60 60 600 (F) HF362JPN HF362SPN 28 JPD-116046
➀ Arktite™ is a registered trademark of the Crouse-Hinds Company. Plugs are not sold or supplied by Siemens. ➁ Indicates plug with maximum diameter cable bushing. ➂ QuelArc™ is a registered trademark of the Pyle-National Company. ➃ In pounds (lb). ➄ Ampere rating of both switch and receptacle. ➅ Also rated Type 3R/3S ➆ Enclosure is constructed of Type 304 stainless steel.
Voltage Catalog Stainless Steel Weight
Rating Number Catalog Number Std. Pkg. Plug Cat. No.
600 (N-F) HNF361JPN HNF361SPN 21
240 (F) HF322JPN –– 28
600 (N-F) HNF362JPN HNF362SPN 27
Type 12 Type 12
➆
Shipping Accepts Pyle-National
QuelArc™ ➁➂ Plugs
19
Page 20
Heavy Duty
Special Application 4 & 6 Pole Switches
Application
4 & 6 pole switches are commonly used as a disconnecting means for two­speed, two-winding motors. Fused switches provide both over current and short-circuit protection. Non-fusible switches normally provide a local disconnection means for two-speed motors, which are remote from their motor controller. 4 pole switches are also used in 3-phase, 4-wire circuits when a switching neutral is required. All 4 & 6 pole switches are service entrance rated.
Description
4 & 6 pole switches are available in 30­200A ratings and in both fusible and non-fusible versions; 4-pole switches are supplied with either Type 1 or Type 12/3R enclosures. 6-pole switches are available with either Type 12/3R or Type 4X stainless steel enclosures.
Standards
• UL & CUL listed under File#E4776
• Meets UL98 for enclosed switches
• 4 & 6 pole switches are suitable for use as service entrance
• Meets NEMA Standard KS-1 for enclosed switches
• Meets NEC wire bending space requirements
Features
• Visible blade, double break switching action
• Highly visible ON/OFF indication
• Defeatable dual cover interlock
• Padlockable in OFF position
• All copper current carrying parts¿
• Tangential knockouts (Type1, 4-pole switches)
• Type 12 & 4X switches are provided with an equipment ground kit as standard
4 Pole Type VBII Switches
Indoor Type 1 Type 12/#R Industrial Horsepower Ratings
Ampere Catalog Ship Wt. Catalog Ship Wt. 240V, 2Ø, 4W 240V, 3Ø 480V, 3Ø 600V, 3Ø 250V
Rating Number (lbs.) Number (lbs.)
Fusible 600 Volt AC, 250 Volt DC – 4-Pole, 4 Fuse
30 HF461 36 HF461J 36 3 10 3 7
60 HF462 40 HF462J 40 7 100 HF463 43 HF463J 43 15 30 15 30 25 60 30 75 20 200 HF464 88 HF464J 88 25 50 25 60 50 125 60 150 40
Non-fusible 600 Volt AC, 250 Volt DC – 4-Pole
30 HNF461 32 HNF461J 32 –– 10 –– 10 –– 20 –– 30 5
60 HNF462 34 HNF462J 34 –– 20 –– 20 –– 50 –– 60 10 100 HNF463 36 HNF463J 36 –– 30 –– 40 –– 75 –– 100 20 200 HNF464 78 HNF464J 78 –– 50 –– 60 –– 125 –– 150 40
6 Pole Type VBII Switches
Indoor Type 1 Type 12/#R Industrial Horsepower Ratings
Ampere Catalog Ship Wt. Catalog Ship Wt. 240V, 3Ø 480V, 3Ø 600V, 3Ø 250V
Rating Number (lbs.) Number (lbs.)
Fusible 600 Volt AC, 250 Volt DC – 6-Pole, 6 Fuse
30 HF661J 37 HF461J 37 3 7
60 HF662J 41 HF462J 41 7 100 HF663J 44 HF463J 44 15 30 25 60 30 75 20 200 HF664J 90 HF464J 90 25 60 50 125 60 150 40
➁
➂
Std. Max. Std. Max. Std. Max. Std. Max. DC
➃
1
2
/
1
2
/
➁
Std. Max. Std. Max. Std. Max. DC
➃
1
2
/
1
20 7
1
2
/
15 15 30 15 50 10
5157
2
/
15 15 30 15 50 10
➂
5157
1
2
/
20 5
1
2
/
20 5
20
Non-fusible 600 Volt AC, 250 Volt DC – 6-Pole
30 HNF661J 33 HNF661S 33 –– 10 –– 20 –– 30 5
60 HNF662J 35 HNF662S 35 –– 20 –– 50 –– 60 10 100 HNF663J 37 HNF663S 37 –– 30 –– 75 –– 100 20 200 HNF664J 80 HNF664S 80 –– 60 –– 125 –– 150 40
➀ Lugs are aluminum alloy as standard. Optional copper body lugs are available. ➁ All 4 & 6 pole VBII switches are suitable for use as service equipment when a neutral is installed or equipment ground kit is properly connected. ➂ Dual horsepower ratings: Std. – applies when non-time-delay fuses are installed. Max – applies when time delay fuses are installed. ➃ Fusible switches accept Class H fuses as the standard. Class R & J fuses can also be installed and increase the rating from 10,000 to 200,000 AIC.
For Class J, the load base is moved upward. For class R fuses, rejection kits are required.
Page 21
Heavy Duty
Special Application Switches / Non-Metallic
Application
operating temperatures and is supplied with a continuous memory retaining
Siemens Non-Metallic Safety Switches have fiberglass reinforced polyester enclosures, which are extremely resistant to a wide range of corrosive atmospheres that can be encountered
gasket for a superior seal against entry of water, dust and other contaminants. The excellent insulating properties of fiberglass virtually eliminate problems caused by internal condensation.
in waste-water treatment plants and certain other industrial applications.
All switches are load break rated and are provided with an equipment ground
Description
kit as standard. Class R fuse clip kits and auxiliary switch kits are also available.
30-200A, 600V Max, fusible and non­fusible switches are available in Type 4X enclosures. The fiberglass-reinforced enclosure allows a wide range of
Horsepower Rating - 3-Phase 250 600
Ampere Catalog 240 Volt AC 480 Volt AC 600 Volt AC Volts Volts
System Rating Number Std. Max. Std. Max. Std. Max. DC DC
3-Pole, 4--Wire, 240 Volts Fusible
1
30 HF321NX 3 7 60 HF322NX 7
3-Pole, 4-Wire, 600 Volts Fusible
30 HF361NX 3 7
60 HF362NX 7 100 HF363NX 15 30 25 60 30 75 20 50 200 HF364NX 25 60 50 125 60 150 40 50
➂
3-Pole, 3-Wire, 600 Volts Non-Fusible
30 HNF361X — 7
60 HNF362X — 15 — 50 — 60 10 30
100 HNF363X — 30 — 75 — 100 20 50 200 HNF364X — 60 — 125 — 150 40 50
➂
/2
1
/2
1
/2
—— — — 5—
15 — — — — 10 —
1
5157
/2
15 15 30 15 50 10 30
1
—20 — 30 515
/2
1
/2
20 5 15
Non-Metallic Features
• 30, 60, 100 and 200 amp switches
• 240 and 600 volts fusible
• 600 volts non-fusible
• Rated 10,000 AIC with Class H fuses
• Rated 200,000 AIC with Class J or R fuses
• UL-Listed, File E4776
➂
• Horsepower rated
• Suitable for use as service equipment
• Quick-make, quick-break mechanism
• Visible blade construction
• Padlock-off handle feature
• Field installable auxiliary contacts
• Field replaceable line and load bases
• Factory installed ground lug supplied as standard
• Line terminal shields
• Neutrals installed as standard on fusible switches
Type 7 and 9 Enclosed Molded Case Switches ➀➁
Molded Case of Current Catalog Wgt. lb./Ship.
Switch Type Poles Rating Number Package
ED2, ED4, ED6
HED4, HED6 2-3 70-100 EB 32 FXD6, FD6, HFD6, HFXD6, CFD6 2-3 250 EC2 85 JXD2(A), JXD6(A), JD6(A), SJD6(A) 2-3 200-350 EC4 85 HJD6(A), HJXD6(A), HHJD6, HHJXD6, SHJD6 2-3 300-400 EE 93 LXD6(A), LD6(A), SLD6(A), SLD6(A) 2-3 600 ED6 190 HLD6(A), HLXD6(A), HHLD6, HLXD6(A) 2-3 600 ED6 190 HHLD6, HHLXD6, SHLD6 2-3 600 ED6 190
➀ Neutrals not included. Order neutral kit when required. ➁ Order molded case switch and enclosure separately.
600V DC rating and 600V DC HP ratings require (2) poles to be connected in series.
➂
Number Maximum Enclosure Enclosure
15-60 EA 27
21
Page 22
General and Heavy Duty
Accessories
Copper Lug Kits
Heavy duty switches are UL approved to accept field installed copper lug kits.
Copper Lug Kits
Switch Copper Lug
Ampere Kit Catalog
Rating Number Description
30-60 HLC612 (9) Lugs / Kit #14-6 AWG (1)/Ø
100 HLC63 (9) Lugs / Kit #14-1/0AWG (1)/Ø
200 HLC64 (9) Lugs / Kit #6 Awg-300 Kcmil (1)/Ø
400-1200 HLC65678 (1) Lug / Kit # 1/0 Awg-600 Kcmil Cu
Equipment Ground Kits
Equipment Ground Lug Kits are available for all General and Heavy Duty Switches. They are field installable in Type 1 and Type 3R Switches and are factory installed as standard in Type 4/4X and Type 12 Switches.
Equipment Ground Kits
Switch
Ampere Catalog Number of Wire Range
Rating Number Terminals Per Terminal (Cu/Al)
30A GD GSGK60 2 #14-8 AWG
60-200 GD HG61234 2 #14-4 AWG
30-200 HD HG61234 2 #14-4 AWG
400 & 600 HG656 4 #6 AWG-250 Kcmil
800-1200 HG678 8 #6 AWG-250 Kcmil
HLC612
HG261234
Isolated Ground Kits
Isolated Ground Kits are available on 30-600A Heavy Duty Switches. They are normally used on circuits with a high content of computer or other electronic loading which require a ground which is isolated from the building ground and neutral circuits. The kit includes both isolated and grounded terminals as listed below.
Isolated Ground Kits
Switch
Ampere Catalog Number of Terminals Wire Range
Rating Number Isolated Grounded Per Terminal (Cu/Al)
30-200 HG261234 2 2 #14-4 AWG
400-600 HG2656 4 4 #14-2/0 AWG
22
Page 23
HA161234
HA261234
Auxiliary Contacts
Auxiliary Contacts are available only for Heavy Duty Switches. The auxiliary contacts are available in 1 normally open and 1 normally closed or 2 normally open and 2 normally closed configurations. Siemens offers a PLC Auxiliary Switch (30-200A) that has very low resistance for low voltage and current typical in PLC circuits. All auxiliary contacts make after and break before the main switch contacts.
Auxiliary Contacts
Switch Aux. Switch Kit Ampere Rating Kit Horsepower Rating
Ampere Catalog
Rating Number
125V AC 250V AC 28V DC 125V AC 250V AC 28V DC
Max. Max. Max. Max. Max. Max.
With 1 NO & 1 NC Isolated Contacts
30-200 HA161234 10 10 – 1/2 3/4 –
400-1200 HA165678 10 10 – 1/2 3/4 –
With 2 NO & 2 NC Isolated Contacts
30-200 HA261234 10 10 7 1/2 3/4 –
400-1200 HA265678 10 10 7 1/2 3/4 –
Low Current PLC Type with 1 NO & 1 NC Gold Plated Contacts
30-200 HA361234 10 10 – 1/2 3/4 –
400-1200 HA365678 10 10 – 1/2 3/4 –
HP61
Class R Fuse Clip Kits
All 30-600A General Duty and Heavy Duty Switches are field convertible to accept Class R Fuse Clip Kits. The kits
prevent the installation of Class H and
HR612
NOTE: For touch-up spray paint (16 oz. can) order catalog number XTP060.
Fuse Puller Kits
Fuse Puller Kits are field
installable in 30-100A Type
VBII Heavy Duty Switches
(one kit required per
switch).
K fuses (one kit required
per switch).
Fuse Puller Kits
Switch
Ampere Fuse Puller Kit
Rating Catalog Number
30 HP61
60 HP62
100 HP63
Class R Fuse Clip Kits
Catalog
Number Description
GSRK321 30A, 240V Kit (GD only)
HR21 30A, 240V Kit (HD only)
HR612 30A, 600V Kit / 60A, 240V Kit
HR62 60A, 600V Kit
HR63 100A Kit
HR64 200A Kit
HR656 400A / 600A Kit
23
Page 24
General and Heavy Duty
Accessories
Class J Fuse
All 100-600A General Duty, 100-600A 240V Heavy Duty and 600V, 30-600A Heavy Duty Switches are field convertible to accept Class J fuses by moving the load base to a predrilled J fuse position.
HT63
Class T Fuse Adapter Kits
(1 kit required per pole)
All 200-600A General Duty and 100­1200A Heavy Duty Switches are field convertible to accept Class T fuses. 400 & 600A switches are field convertible to accept Class T fuses by moving the load base to a predrilled T fuse position.
Neutral Kits
Standard Neutral Kits can be field installed in General and Heavy Duty Switches.
Neutral Kits
HN612
Switch Kit
Ampere Catalog
Rating Number
30 GD W410190
30 HD, 60 GD HN612
60, 100 HD, 100 GD HN623
200 HN64
400 & 600 HN656
800 & 1200 VBII HN678
Class T Fuse Adapter Kits
Catalog
Number Description
HT23 100A, 240V Kit
HT63 100A, 600V Kit
HT24 200A, 240V Kit
HT64 200A, 600V Kit
HX327TF 800A, 240V Kit
HX367TF 800A,600V Kit
HX328TF 1200A, 240V Kit
HN264
200% Neutral Kits
UL listed 200% Neutrals are available on 100-600A Heavy Duty Switches. They are typically used with nonlinear transformers or where increased neutral ampacity/ lug capacity is required.
200% Neutral Kits
Switch Kit Wire Range
Ampere Catalog Line & Load
Rating Number Lugs (Cu/Al)
100 HN263 (2) #14-1/0 AWG
200 HN264 (2) #6 AWG-300 Kcmil
400 HN656 (2) 1/0 AWG-750 Kcmil
600 HN678 (4) 1/0 AWG-600 Kcmil
24
Page 25
General and Heavy Duty
Hub and Lug Data
SL0420
ECHS200
Compression Lug Neutral Barrier Kit
All Heavy Duty Switches are field con-
ECHV300
vertible for crimp type lugs. When compression lugs are required for 30-
SSH150
100A switches, a neutral barrier kit is required for 1-Phase, 3W or 3-Phase, 4W applications. When compression
Interchangeable Hubs
Conduit hubs are available for
lugs are required on 400-1200A switches, lug mounting kits are required.
Type 3R, 12 and 4/4X applications. 30-200A Type 3R Switches are provided with a conduit hub provision and a removable hub plate on their top rainsheds.
Hubs
Conduit
Size Catalog
(inches) Number Used On
Type 3R ➀
3/4 ECHA075
1 ECHA100 30A GD Only
1 1/4 ECHA125
3/4 ECHS075
1 ECHS100 1 1/4 ECHS125 60-200A GD 1 1/2 ECHS150 30-200A HD
2 ECHS200 2 1/2 ECHS250 2 1/2 ECHV250
3 ECHV300 400-1200A 3 1/2 ECHV350
4 ECHV400
Type 4 / 4X
3/4 SSH075
1 SSH100 1 1/4 SSH125 1 1/2 SSH150 30-200A
2 SSH200
NOTE: 30-200A. Type 3R Switches have removable hub plates on rainsheds. 400A and larger Type 3R Switches have no provisions for mounting hubs. Drill or punch hole in the field to accommodate hub size desired.
➀ Hubs suitable for 3R Switches. ➁ Neutral Barrier kits are required on 30-100A switch only and only with 1-Phase, 3W or 3-Phase and 4W loads.
Compression lugs mounting kits are required on 400-1200A switches only.
➂ Provides mounting for a single line or load lug. ➃ Provides mounting for two compression lugs per phase on line or load one per pole required. ➄ Line lugs have wire-bending space and are UL approved for #14-6 conductors. ➅ Max. wire size for height reduced switches is 500 Kcmil (Cu/Al). ➆ All but 60A GD & Compact HD NF switches are also UL approved for #2 Cu/Al conductors. ➇ All 200A Heavy Duty Switches have a wire range & wire bending space for one # 6-300 Kcmil (Cu/Al).
Compression Lug Mounting➁ and Neutral Barrier Kits
Switch
Ampere Catalog
Rating Number Kit Description
30 HCL612 Neutral Barrier Kit
60 & 100 HCL623 Neutral Barrier Kit
400 ➂HCL65 1 Pole, Compression
400 HCL65678 1 Pole, Compression
➃
& 600
800 – Factor y Installed Only
➃
& 1200
Lug Mounting Kit
Lug Mounting Kit
Lugs
30-100A Switches are suitable for use with 60ºC or 75ºC wire. 100-1200A are suitable for use with 75ºC rated wire.
Wire Ranges (Line, Load and Standard Neutral)
Switch Wire Range with
Ampere Wire-Bending Space
Rating Per NEC Table 373-6 Lug Range
30GD #14-8 AWG (Cu/Al)
30HD #12-6 AWG (Al) or #14-6 AWG (Cu/Al) #14-2 AWG (Cu/Al)
30A HD #14-2 AWG(Cu/AI) #14-2 AWG (Cu/AI)
oversized
➆
60
60A HD #14-1/0 AWG (Cu/Al) #14-1/0 AWG (Cu/Al)
oversized
100 #14-1/0 AWG (Cu/Al) #14-1/0 AWG (Cu/Al)
200 400
600
800 (3) 1/0-750 kcmil (Cu/Al) Line and Load or (3) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
1200 (4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load (4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
#12-2 AWG (Al) or #14-3 AWG (Cu/Al) #14-2 AWG (Cu/Al)
➇
#6 AWG-250 Kcmil (Cu/Al) #6 AWG-300 Kcmil (Cu/Al)
➅
1/0 AWG-750 Kcmil (Cu/Al) or (1) 1/0 AWG-750 Kcmil (Cu/Al) or (2) 1/0 AWG-250 Kcmil (Cu/Al) (2) 1/0 AWG-250 Kcmil (Cu/Al)
➅
(2) 1/0 AWG-750 Kcmil (Cu/Al) or (2) 1/0 AWG-750 Kcmil (Cu/Al) or (4) 1/0-250 Kcmil (Cu/Al) (4) 1/0 AWG-250 Kcmil (Cu/Al)
(6) 1/0-250 kcmil (Cu/Al) (4) 1/0 AWG-600 Kcmil (Cu/Al) neutral (4) 1/0-250 kcmil (Cu/Al) neutral
(4) 1/0 AWG-600 Kcmil (Cu/Al) neutral (4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
➄
Multiple Padlock Accessory
A tamperproof device to provide for multiple padlocking to meet OSHA or plant requirements. Accepts up to six padlocks. Catalog number SL0420. Standard Carton-12.
Kirk-Key Interlocks
Kirk-Key Interlocks are factory installed only on Type VII Heavy Duty and Double Throw Safety Switches.
Interlocks are used to prevent the authorized operator from making an unauthorized operation. The interlock system is a simple method of applying key interlocks to safety switches so as to require operation in a predetermined sequence.
Before consulting the factory, the following information is required:
• User name and address
• Key number from lock assemblies on any existing locks to be inter­locked with
• Complete locking scheme
Consult factory for delivery.
#14-8 AWG (Cu/Al)
➅
25
Page 26
Heavy Duty
Crimp Lug Application Data
Heavy Duty Switches are UL approved to accept the following field installed compression lugs:
Heavy Duty 30 Amp ➀
Wire
Size CU ONLY CU/AL CU ONLY CU/AL CU ONLY CU/AL
#14-10 60096
#8 YA8C-L Box 54104 60101 CRA-8 ACL-8
YA8C-L1 Box 54130 60102 ACN-8
#6 61107
Heavy Duty 60 Amp ➁
Wire
Size CU ONLY CU/AL CU ONLY CU/AL CU ONLY CU/AL
#14-10 256-30695-1352 60097
#8 YA8C-L1 Box YA8CA3 54130 60102 ACL-8
YA8C-TC14 54930BE 61102
#6 YA6C-L Box YA6CA1 54105 60107 CRB-6 ACL-6
YA6C 54905BE 61107 CRB-6L
#4 54106 61112 CRB-4
Burndy Thomas-Betts Ilsco
60097
61102
Burndy Thomas-Betts Ilsco
Heavy Duty 100 Amp ➁
Wire
Size CU ONLY CU/AL CU ONLY CU/AL CU ONLY CU/AL
#6 YA6C-L Box YA6C YA6CA1 54105 54905BE 61107 60107 CRB-6 CRB-6L ACL-6 #4 YA4C-L Box YA4C YA4CA1 54106 54906BE 61112 60112 CRB-4 CRB-4L ACL-4 #2 YA2C-L2 Box YA2C YA2CA5 54107 61116 CRB-2 CRB-2L ACL-2 #1 YA1C-L2 YA1C — 54108 54947BE 61122 CRB-1-14 CRA-1L — 1/0 — — — 61130 — —
Burndy Thomas-Betts Ilsco
Heavy Duty 200 Amp
Wire
Size CU ONLY CU/AL CU ONLY CU/AL CU ONLY CU/AL
#2 YA2C-L Box YA2C YA2CA1 54142-TB 60117 CRB-2 CRB-2L IACL-2 ACN-2
#1 YA1C-L Box YA1C YA1CA1 54147 54947BE 60123 CRA-1-38 CRA-1L ACN-1 1/0 YA25-L Box YA25 YA25A1 54153-TB 54949BE 60129 61130 CRA-0 CRA-1/0L IACL-1/0 ACN-1/0 2/0 YA26-L3 YA26 YA26A6 54158 54910BE 60135 61136 CRA-2/0 CRA-2/0L ACL-2/0
3/0 YA27-L3 YA27 YA27A1 54163-TB 60141 61142 CRC-3/0 CRB-3/0L IACL-3/0 ACL-3/0 4/0 YA28-L3 YA28A1 54168 61148 CRC-4/0 CRB-4/0L IACL-4/0
YA28-TC38 256-30695-1253 60147 ACL-4/0 250 Kcmil YA29-L7 — 54173 54913BE 61156 CRA-250 CRA-250L IACL-250 300 Kcmil — — — 61162 — —
Burndy Thomas-Betts Ilsco
256-30695-1229 IACL-2/0
Heavy Duty 400 & 600 Amp ➂
Wire
Size CU ONLY CU/AL CU ONLY CU/AL CU ONLY CU/AL
2/0 YA26-N YA26-A1 54160 54951BE — — IACL-2/0 ACN-2/0 3/0 YA27-L Box YA27 YA27A3 54165-TB 54965BE — CRB-3/0 CRB-3/0L IACL-3/0 ACN-3/0
4/0 YA28-L Box YA28 YA28A3 54170 54970BE 60150 CRB-4/0 CRB-4/0L IACL-4/0 ACN-4/0 250 Kcmil YA29-L Box YA29 YA29A1 54113 54913BE 61156 60156 CRA-250 CRA-250L IACL-250 ACL-250 300 Kcmil YA30-L YA30 YA30A1 54414 54914BE 61162 60162 CRA-300 CRA-300L IACL-300 ACL-300 350 Kcmil YA31-L YA31 YA31A1 54915BE 61165 60165 CRA-350 CRA-350L IACL-350 — 400 Kcmil➃YA32-N — 54116 54916BE — — — 500 Kcmil➃YA34-L6 YA34-N — — 61171 — IACL-500
Burndy Thomas-Betts Ilsco
26
➀ If compression lugs are used for the neutral, order compression lug neutral barrier kit HCL612. ➁ If compression lugs are used for the neutral, order compression lug neutral barrier kit HCL623. ➂ Use compression lug mounting kit per table on previous page. ➃ Not applicable to height reduced switches.
Page 27
Special Application Safety Switches
Non-Metallic & Interlocked Receptacle Switch Dimension Drawings
W
4 X 0.50
(12.70)
A
H
Catalog Number H W D A B C E F G J
HF321NX 18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20 HF322NX 18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20 HF361NX HF362NX HF363NX HF364NX HNF361NX➀18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20 HNF362NX➀18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20 HNF363NX➀26.95 14.87 13.25 24.84 13.72 6.25 25.75 3.75 .46 12.15 HNF364NX➀33.41 27.47 13.19 31.31 26.31 18.50 32.25 3.91 .47 12.10
Dimensions (Inches) Non-Metallic
➀
18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20
➀
18.75 12.11 10.25 16.59 10.97 7.00 17.50 1.98 .46 9.20
➀
26.95 14.87 13.25 24.84 13.72 6.25 25.75 3.75 .46 12.15
➀
33.41 27.47 13.19 31.31 26.31 18.50 32.25 3.91 .47 12.10
C
B
F
G
E
J
D
VBII Interlocked Receptacle Switches
Ampere Rating
Cr-H Type Fusible (240 & 600V)
30 14.27 7.42 9.02 6.22 1.52 6.1 6.0 60 16.27 9.17 11.47 6.34 1.52 6.4 7.4
100 21.96 9.65 12.02 6.80 1.52 6.5 7.6
Cr-H Type Non-fusible (600V max)
30 11.12 7.42 9.02 6.22 1.52 6.1 6.0 60 16.27 9.17 11.47 6.34 1.52 6.4 7.4
100 21.96 9.65 12.02 6.80 1.52 6.5 7.6
Pyle-National Type Fusible (240 & 600V)
30 14.27 7.42 9.02 6.22 1.52 3.5 3.0 60 16.27 9.17 11.47 6.34 1.52 5.0 4.5
Pyle-National Type Non-fCommandusible (600V max)
30 11.12 7.42 9.02 60 16.27 9.17 11.47
Dimensions (Inches)
ABC DEFG
➀
6.22 1.52 3.5 3.0
➀
6.34 1.52 5.0 4.5
B
D
E
A
G
C
F
27
Page 28
Double Throw Switches
ON OFF ON
Description & Application
Double throw safety switches are intended to transfer loads from one power source to another. All two- and three pole double throw switches are
load side of the switching mechanism. A cover interlock is provided on all ampere ratings. The operating handle
may be padlocked in the OFF position. suitable for use as service equipment. All are UL listed. Switches are rated for use on systems up to 10,000A when protected with Class H fuses or 100,000A when protected with Class R or Class T fuses¡. They can also be used to connect a single source of power to either of two loads. In this application it is necessary to field modify fusible switches so that the fuses are on the
Fuse Capabilities of Fusible Switches
Amp
Rating H R T J
30 & 60A, 240V Std Yes (kit) No No
30 & 60A, 600V Std Yes (kit) No Yes
100 & 200A Std Yes (kit) Yes (kit) Yes
400 & 600A DTF No No Yes➂Std
Fuse Type
➂
➂
➃
Double Throw Switches
Number Type 1– Indoor Type 3R – Outdoor➀ Type 12/3R Industrial Type 4X – Stainless Steel
System Voltage of Poles Amps Catalog Number Catalog Number Catalog Number Catalog Number
Heavy Duty Fusible (30-200A with Class H fuse provisions)
Volt AC
ON OFF
Volt DC
ON
Volt AC,
Volt DC
Heavy Duty Non-Fusible
Volt AC
Volt DC
Volt AC
Volt DC
➀ Use HS Type hubs for 30–200A switches; 400A and larger switches do not have hub provisions.
28
➁ All Heavy Duty double throw switches with catalog numbers starting with “DT” are rated 200,000 AIC max. when protected by Class R, J or T fuses.
Fuse ampere rating must not exceed switch ampere rating.
➂ Move load base. ➃ Catalog No. F355SSDTK will accept Class T Fuse only ➄ Four pole switches are not approved for service entrance.
240
or
250
600
250
240
or
250
600
or
250
2 200 DTF224 DTF224R — —
3
3
➁
2 100 DTNF223 — — —
3 200 DTNF324 DTNF324R — —
3 100 DTNF363 DTNF363R DTNF363J DTNF363S
➄
4
30 DTF321 DTF321R — —
60 DTF322 DTF322R — — 100 DTF323 DTF323R — — 200 DTF324 DTF324R — — 400 DTF325 — — — 600 DTF326 — — —
30 DTF361 — — —
60 DTF362 — — — 100 DTF363 DTF363R — F353SSDTK 200 DTF364 DTF364R — F354SSDTK 400 DTF365 — — F355SSDTK
30 DTNF221 — — —
60 DTNF222 — — —
200 DTNF224 DTNF224R — — 400 DTNF225 DTNF225R — —
30 DTNF321 — — —
60 DTNF322 — — — 100 DTNF323 DTNF323R — —
400 DTNF325 — — — 600 DTNF326 — — — 800 DTNF327 — — —
30 DTNF361 DTNF361R DTNF361J DTNF361S
60 DTNF362 DTNF362R DTNF362J DTNF362S
200 DTNF364 DTNF364R DTNF364J DTNF364S 400 DTNF365 DTNF365R NF355HDTK NF355SSDTK 600 DTNF366 DTNF366R — — 800 DTNF367 DTNF367R — —
1200 DTNF368 DTNF368R — —
30 — NFR451DTK — —
60 — NFR452DTK — — 100 — NFR453DTK — — 200 NF454DTK NFR454DTK — NF454SSDTK 400 NF455DTK NFR455DTK — — 600 NF456DTK NFR456DTK — — 800 NF457DTK NFR457DTK — —
➁
➃
Page 29
Double Throw Switches
N
F
N
General Duty, Accessories, Lug Data and Horsepower Ratings
Double Throw Switches
Number Type 3R – Outdoor➀ Less Neutral Type 3R – Outdoor➀ With Neutral
System Voltage of Poles Amps Catalog Number Catalog Number
General Duty Non-Fusible
O
240 200 DTGNF224R DTGNF224NR
O
Volt AC
O
2
3
100 DTGNF223R DTGNF223NR
100 DTGNF323R DTGNF323NR 200 DTGNF324R DTGNF324NR
Accessories – 2 and 3 Pole Type "DT" Switches Only
Description Number
30A HNC612
Neutral 60 & 100A HN263 Kits 200A HNC264
400 & 600A HN678 800 & 1200A HND678
Equipment Ground Kit
Auxilary Contacts (HD only) (two required per switch)
Class R Fuse Clip Kits (two required per switch)
Class T Fuse Adapter Kits (two required per pole)
Type 3R Hubs (30-200A)
30-200A (2) #14-4 AWG HG61234 400& 600A (1) #14-2/0 HG656 400& 600A (8) #6-350 Kcmil HG678 30-200A with (1) NO & (1) NC Contacts HA161234 30-200A with (2) NO & (2) NC Contacts HA261234 400-1200A with (1) NO & (1) NC Contacts HA165678
➄
400-1200A with (2) NO & (2) NC Contacts HA265678 30-, 240V Kit HR21 30-, 600V Kit & 60A, 240V Kit HR612 60A-, 600V Kit HR62 100A Kit HR63 200A Kit HR64 100A, 240V Kit HT23 100A, 600V Kit HT63 200A-, 240V Kit HT24 200A-, 600V Kit HT64
3
/4 Conduit HS075
For
”
Conduit HS100
For 1
1/4”
For 1
Conduit HS125
1/2”
For 1
Conduit HS150
”
Conduit HS200
For 2
1/2”
Conduit HS250
For 2
➁
Accessories – 4 Pole and Type "F" and "NF" 3 Pole Switches Only
Description Number
Auxiliary Switch (two required per switch)
Ground Lug Kit
Hubs
Neutrals (for fusible stainless and 400A Type 12 & 4X only)
➃
30-800A
30-60-100A DSG100GK 200A DSG200GK 400-600-800A DSG468GK 30-60-100A Use Type HR Hubs –– 200-400A Use Type SSH 4, 4X Hubs –– 600-800A Use Type SSH 4, 4X Hubs –– 30-60-100A DT100NK 200A DT200NK 400A Fusible DS800NK
(1) NO, (1) NC
(2) NO, (2) NC
➄
➄
Replacement Parts – 2 and 3 Pole Type "DT" Switches Only
Description Number
Type 1, 3R & 12 Replacement Handle 30-200A HHD61234 Type 4X Replacement Handle 30-200A HHD61234S Type 4X Replacement Handle 400-1200A HHD65678
➀ Use HS Type hubs for 30-200A switches. ➁ Not for fusible stainless or 400A Type 12 & 4X switches. ➂ Also for fusible stainless & 400A Type 12 & 4X switches.
Catalog
Catalog
DS200EK1 DS200EK2
➁
Catalog
Wire Ranges (Line, Load and Neutral) per NEC requirements
30-200A – 2, 3 & 4 Pole Switches
Switch Wire Range (Cu/Al)
Ampere New VBII Design
Range Line, Load and Neutral
30 (1) #14-6
60 (1) #14-6 100 (1) #14-1/0 AWG 200 (1) #6-250
Kcmil
400-1200A – 2, 3 Pole Switches
Switch Wire Range (Cu/Al)
Ampere New VBII Design
Range Line, Load and Neutral
400
600 (2) 1/0 AWG - 500 Kcmil
800
1200
(1) 1/0 AWG - 750 Kcmil or (2) 1/0 AWG - 250 Kcmil
(2) 1/0 AWG - 750 Kcmil or (3) 1/0 AWG - 500 Kcmil
(3) 1/0 AWG - 600 Kcmil or (4) 1/0 AWG - 500 Kcmil
400-800A – 4 Pole Switches
Switch Wire Range (Cu/Al)
Ampere Line, Load and Neutral
Range
400
600 (2) 250- 500 Kcmil 600 (3) 250- 500 Kcmil
➂
(1) 1/0 AWG - 300 Kcmil or (2) 1/0 AWG - 750 Kcmil
Maximum Horsepower Ratings Fused
1-Phase AC 3-Phase AC
Ampere 250V
Rating 240V 240V 480V 600V DC
30 3 7
60 10 15 30 50 10 100 15 30 60 75 20 200 15 60 125 150 40 400 — 125 125 125 50 600 — 125 — — 50
1
/2 15 20 5
Maximum Horsepower Ratings Non-Fused
30 5 10 20 30 5
60 10 20 50 60 10 100 15 40 75 100 20 200 15 60 125 150 40
400-800 — 125 250 350 50
➃ The following ground lugs are provided as standard in 200A and
larger switches 200-(1) #14-4 Cu/Al 400-800A-(3) #6-250MCM Cu/Al.
➄ One aux. required for normal and one required for emergency switch
line base.
29
Page 30
C
L
1.13
[28.70]
1.94
[49.28]
1.94
[49.28]
.38
[9.65]
.28 [7.11] Dia. Grounding K.O. [4 Places]
B B
B
.97
[24.64]
.97
[24.64]
1.13
[28.7]
C
L
.38
[9.65]
.10
[2.54]
B
B
B
.97
[24.64]
.97
[24.64]
1.94
[49.28]
1.94
[49.28]
7.19
[30.23]
[Door]
1.00
[25.4]
1.00
[25.4]
1.13
[28.7]
3.00
[76.2]
Door
2.81
[71.37]
8.19
[208.02]
[Door]
6.13
[155.70]
7.97
[202.44]
.85
[21.59]
2.50
[63.50]
2.50
[63.50]
5.38
[136.65]
5.00
[127.00]
5.97
[151.64]
7.69
[195.33]
C
L
.50
[12.70]
[4] .25 [6.35] Dia.
Mounting Holes
B
B
A
B
B
B
1.00
[25.4]
1.13
[28.7]
2.94
[49.28]
.85
[21.59]
Detailed Dimension Drawings
1.00
[25.4]
1.00
[25.4]
1.13
[28.7]
3.00 [76.2] Door
2.81
[71.37]
8.13
[206.5]
[Door]
1.00
[25.4]
.85
[21.59]
2.94
[74.68]
6.13
[155.70]
7.97
[202.44]
.72
[18.29]
1.75
[44.45]
5.38
[136.35]
1.75
[44.45]
3.50
[88.9]
5.22
[132.59]
5.94
[150.88]
C
L
.50
[12.7]
.94
[23.88]
[4] .25 [6.35] Dia. Mounting Holes
B
B
A
A
B
B
C
L
1.13
[28.7]
1.00
[25.4]
1.00
[25.4]
.25 [6.35] Dia. Grounding K.O.
B
B
.38
[9.65]
1.38
[35.5]
1.13
[28.7]
C
L
.38
[9.65]
.10
[2.54]
.91
[23.1]
1.63
[41.40]
1.63
[41.40]
5.44
[36.58]
[Door]
A
A
B
Siemens Type VBII Safety Switches
Type 1 (Indoor)
30 Amp General Duty (2-Pole)
30 Amp General Duty (3-Pole)
KNOCKOUT CONDUIT
CODE SIZE
A (Concentric)
.50 .75
B (Concentric) .50 .75 1.00
Figure 1
Figure 2
Dimensions shown in inches and millimeters [ ].
30
Dimensions shown accurate to
+
1/8 inch.
((
Page 31
Type 1 (Indoor)
1.71 43[]
6.52 166[]
1.35 34[]
DIA.27
7[]
7.67 195[]
4.34 110[]
1.04 26[]
.94
24[]
9.12 232[]
.95
24[]
1.50 38[]
1.50 38[]
.68
17[]
SEE DETAIL
C
A
(4)
OF BOX
B
9.01 229[]
5.71 145[]
.91
23[]
6.64 169[]
1.51 38[]
1.80 46[]
1.80 46[]
.25
6[]
[] []
.25 DIA GROUND KNOCKOUT TOP & BOTTOM
B
(3)
TOP & BOTTOM
DIA.27
7[]
.75
19[]
.65
16[]
.28
7[]
DETAIL
C
.91
23[]
1.46 37[]
B
LEFT SIDE
1 [
30 Amp Heavy Duty Non-Fusible 60 Amp Compact Heavy Duty Non-Fusible 60 Amp General Duty Non-Fusible
2.31 313
➀
.32
8[]
]
➀
1.47 37[]
➀
10.17 258[]
8.25
➀
210[]
5.05 128[]
➀
.91
23[]
1.45 37[]
B
LEFT &
RIGHT SIDE
11.11 282[]
Figure 3
30 Amp Heavy Duty Fusible 60 Amp General Duty Fusible
7.67
1.04 26[]
3.21 82[]
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
.27 DIA (3) [7]
1.88 48[]
.79
20[]
195[]
4.34 110[]
2.42 62[]
OF BOX
4.84 123[]
+
1/8 inch.
SEE DETAIL
1.35 34[]
10.11 257[]
A
(4)
C
12.40 315[]
5.95
.94
24[]
.82
21[]
151[]
.91
➀
.32
8[]
15.45 393[]
4.07 103[]
.92
23[]
23[]
1.51 38[]
➀
1.90
1.80 46[]
48[]
➀
8.35 212[]
9.01
➀
229[]
6.64 169[]
➀
10.17 258[]
8.25 209[]
➀
8.35 212[]
KNOCKOUT CONDUIT
CODE SIZE A (Concentric) B (Tangential) .50 .75 1.00
.25 DIA GROUND KNOCKOUT TOP & BOTTOM
B
(3)
TOP & BOTTOM
.25
1.80
6[]
46[]
.50 .75
Figure 4
➀
5.05 128[]
1.46 37[]
14.26
B
(2) LEFT & RIGHT SIDE
1.46 37[]
.91
23[]
362[]
.65
16[]
.28
7[]
DETAIL
C
DIA.27
7[]
.75
19[]
31
Page 32
6.00 152[]
3.35 85[]
2.25 57[]
4.47 114[]
1.19 30[]
.63
16[]
10.19 259[]
1.47 37[]
1.97 50[]
5.00 127[]
13.04 331[]
13.36 339[]
2.48 63[]
SEE DETAIL
B
A
(4)
OF BOX
.27 DIA (3) [7]
.76
19[]
10.17 258[]
8.25 209[]
5.79 147[]
16.26 413[]
1.69 43[]
1.69 43[]
.87
22[]
5.05 128[]
8.35 212[]
17.46 443[]
1.89 48[]
A
(2) LEFT & RIGHT SIDE
9.15 232[]
11.53 293[]
2.07 53[]
2.50 64[]
2.50 64[]
.25
6[]
6.08 155[]
.87
22[]
.88 DIA KNOCKOUT
.25 DIA GROUND KNOCKOUT TOP & BOTTOM
A
(3)
TOP & BOTTOM
DIA.27
7[]
.65
16[]
.75
19[]
.28
7[]
DETAIL
B
5.68 144[]
DIA (3).27
7[]
1.19 30[]
1.88 48[]
4.71 120[]
1.51 38[]
10.68 271[]
1.21 31[]
3.50 89[]
2.96 75[]
7.00 178[]
18.72 475[]
19.38 492[]
1.61 41[]
SEE DETAIL
C
B (4)
OF BOX
2.42 62[]
10.17 258[]
2.68 68[]
8.76 223[]
21.95 557[]
2.45 62[]
2.43 62[]
.85
22[]
8.35 212[]
5.05 128[]
8.25 210[]
23.15 588[]
B
(2) LEFT & RIGHT SIDE
DIA.27
7[]
.65
16[]
.28
7[]
.75
19[]
DETAIL
C
9.64 245[]
1.94 49[]
2.88 73[]
2.88 73[]
.98
25[]
6.52 166[]
12.01 305[]
.25
6[]
178[]
.25 DIA GROUND KNOCKOUT TOP & BOTTOM
B
TOP & BOTTOM
A
(2)
TOP & BOTTOM
.88 DIA KNOCKOUT
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Type 1 (Indoor)
60 Amp Heavy Duty (Also 30 Amp Oversized Heavy Duty)
➀
Figure 5
➀
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) .50 .75 1.00 1.25
100 Amp General and Heavy Duty
32
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
+
1/8 inch.
Figure 6
➀
➀
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) .75 1.00 1.25 1.50
B (Tangential) 1.00 1.25 1.50 2.00
➀
Page 33
Type 1 (Indoor)
DIA (4)
.33
8[]
8.20
7.19 183[]
.81
21[]
15.39 391[]
3.10
3.68 93[]
5.10 130[]
3.81 97[]
25.22 640[]
22.43 570[]
5.50 140[]
5.50 140[]
SEE DETAIL
C
A
(4)
OF BOX
208[]79[]
9.74 247[]
4.39 112[]
10.17 258[]
12.33 313[]
12.42 315[]
29.90 759[]
2.37 60[]
2.31 59[]
31.07 789[]
.81
21[]
6.36 162[]
4.37 111[]
A
(2) LEFT & RIGHT SIDE}
16.98 431[]
8.19 208[]
.87
22[]
2.45 62[]
4.88 124[]
4.88 124[]
14.62 371[]
.20
5[]
.88 DIA KNOCKOUT
TOP & BOTTOM
.25 DIA GROUND KNOCKOUT TOP & BOTTOM
A
(3)
TOP & BOTTOM
2.50 64[]
39.00 991[]
2.07 53[]
20.50 521[]
24.65 626[]
44
1[
.43 DIA (4)
11[]
]
44.00 1118[]
9.23 234[]
44.57 1132[]
14.68 373[]
13.25 337[]
13.46 342[]
18.77 477[]
13.44 341[]
A(4)
11.00 [ 279 ]
26.70 [ 678 ]
1.56 [ 40 ]
5.50 [ 140 ]
11.00 [ 279 ]
16.50 [ 279 ]
4.07 [ 104 ]
1.80 [ 46 ]
.25 [ 6 ]
.50-.75 DIA (2) GROUND KNOCKOUT TOP & BOTTOM
.47
12[]
DIA.38
10[]
DIA1.00
25[]
1.44 37[]
DETAIL
C
200 Amp General and Heavy Duty
Figure 7
➀
➀
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) 1.25 1.50 2.00 2.50
➀
400 / 600 Amp General and Heavy Duty Non-Fusible
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
+
1/8 inch.
Figure 8
[ 419 ]
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) 2.00 2.50 3.00 3.50
33
Page 34
2.50 64[]
39.00 991[]
2.07 53[]
20.50 521[]
24.65 626[]
44.00 1118[]
9.23 234[]
44.57 1132[]
14.68 373[]
13.25 337[]
13.46 342[]
18.77 477[]
13.44 341[]
.43 DIA (4)
11[]
A(4)
11.00 [ 279 ]
26.70 [ 678 ]
1.56 [ 40 ]
5.50 [ 140 ]
11.00 [ 279 ]
16.50 [ 279 ]
4.07 [ 104 ]
1.80 [ 46 ]
.25 [ 6 ]
.50-.75 DIA (2) GROUND KNOCKOUT TOP & BOTTOM
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Type 1 (Indoor)
400 / 600 General and Heavy Duty Fusible
C
A
.43 DIA
(4)
[ 11 ]
Figure 9
E
B
SWITCH TYPE
STANDARD
HEIGHT REDUCED
D
[419 ]
DIMENSIONS
ABCDE
56.57[1437]
45.82[1164]
56.07[1424]
45.31[1151]
51.00[1295]
40.25[1022]
25.46[647]
20.99[533]
18.77[477]
12.49[317]
KNOCKOUT CONDUIT
CODE SIZE
A 2.00 2.50 3.00 3.50
800 / 1200 Amp Heavy Duty Non-Fusible
38.40 975[]
32
2.07
3.20
53[]
[ 81 ]
.56 Dia (4)
34
14[]
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
34.25
[ 813 ]
870[]
+
1/8 inch.
49.25 1251[]
2.79
2.50 64[]
[ 71 ]
24.02 610[]
55.16
54.82 1392[]
[ 1401 ]
18.46 469[]
14.68 373[]
13.42 341[]
13.25 337[]
9.24 235[]
54.25
[ 1389 ]
54.67
1378[]
Figure 10
40.00
39.96
[ 1016 ]
1015[]
No knockouts in the enclosures.
.25
6[]
Page 35
C
L
1.0 0
[ 25.4 ]
1.0 0
[ 25.4 ]
.31
(7.87)
.28 (7.11)
DIA GROUNDING KNOCKOUT (2) PLACES
B
B
1.69
[ 42.93 ]
1.69
[ 42.93 ]
1.13
[ 28.7 ]
1.3 1
[ 33.27 ]
C
L
.10
[ 2.54 ]
Type HA Outdoor Hub Provision
5.63
[ 143.0 ]
1.00
[ 25.4 ]
3.13
[ 79.50 ]
2.94
[ 74.68 ]
8.16
[ 207.26 ]
(Door)
1.13
[ 28.7 ]
6.13
[ 155.7 ]
8.07
[ 204.98 ]
.85
[ 21.59 ]
5.38
[ 136.65 ]
1.75
[ 44.5 ]
3.50
[ 88.9 ]
5.22
[ 132.59 ]
C
L
5.44
[ 138.18 ]
(Door)
.50
[ 12.7 ]
A
A
B
.85
[ 21.59 ]
5.94
[ 150.88 ]
1.13
[ 28.7 ]
2.81
[ 71.37 ]
(3) .25 (6.35) DIA MOUNTING HOLES
14.68 373[]
32
813[]
3.20 81[]
38.40 975[]
61.25 1556[]
67.16 1706[]
24.02 610[]
30.46 774[]
13.24 336[]
13.44 341[]
66.67 1693[]
9.24 236[]
.25
6[]
40.00 1016[]
2.79 71[]
.56 Dia (4)
14[]
Type 1 (Indoor)
800 / 1200 Amp Heavy Duty Fusible
Figure 11
No knockouts in the enclosures.
Type 3R (Outdoor)
30 Amp General Duty (2-Pole)
+
1/8 inch.
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
Figure 12
KNOCKOUT CONDUIT
CODE SIZE A (Concentric) B (Concentric) .50 .75 1.00
.50 .75
35
Page 36
1.0 0
[ 25.4 ]
3.13
[ 79.50 ]
2.94
[ 74.68 ]
8.16
[ 207.26 ]
(Door)
1.13
[ 28.7 ]
6.13
[ 155.7 ]
8.07
[ 204.98 ]
.85
[ 21.59 ]
5.38
[ 136.65 ]
2.50
[ 63.50 ]
2.50
[ 63.50 ]
5.00
[ 127 ]
6.97
[ 177.04 ]
C
L
7.1 9
[ 182.63 ]
(Door)
.50
[ 12.7 ]
A
A
B
.85
[ 21.59 ]
7.69
[ 195.33 ]
1.13
[ 28.7 ]
2.81
[ 71.37 ]
(3) .25 (6.35) DIA MOUNTING HOLES
C
L
1.9 4
[ 49.28 ]
1.9 4
[ 49.28 ]
.28 (7.11) DIA GROUNDING KNOCKOUT (2) PLACES
B B B
1.13
[ 28.7 ]
.97
[24.64]
.97
[24.64]
.38
[ 9.65 ]
1.31
[ 33.27 ]
C
L
.10
[ 2.54 ]
TYPE HA OUTDOOR HUB PROVISION
7.38
[ 187.45 ]
Detailed Dimension Drawings
1.60 41[]
.32
8[]
12.31 313[]
10.17 258[]
.92
23[]
11.11 282[]
5.05 128[]
8.25 210[]
8.35 212[]
.90
23[]
1.32 34[]
3.32 84[]
.64
16[]
SEE DETAIL
C
PROVISION FOR TYPE "HS" HUB
DIA.27
7[]
.65
16[]
.28
7[]
.75
19[]
DETAIL
C
9.01 229[]
5.71 145[]
.91
23[]
1.51 38[]
1.80 46[]
1.80 46[]
6.64 169[]
.25
6[]
.25 DIA GROUND KNOCKOUT
B
(3)
.91
23[]
1.46 37[]
B
LEFT SIDE
DIA (3).27
7[]
1.71 43[]
6.52 166[]
1.32 34[]
1.35 34[]
1.50 38[]
1.50 38[]
.95
24[]
.68
17[]
7.91 201[]
4.34
110[]
1.04 26[]
A
(2)
SEE DETAIL
C
OF BOX
B
Siemens Type VBII Safety Switches
Type 3R (Outdoor)
30 Amp General Duty (3-Pole)
KNOCKOUT CONDUIT
CODE SIZE A (Concentric) B (Concentric) .50 .75 1.00
.50 .75
Figure 13
1.94
1.94
[ 49.28 ]
[ 49.28 ]
C
L
B B B
.97
.97
[24.64]
[24.64]
.28 (7.11) DIA GROUNDING KNOCKOUT (2) PLACES
.38
[ 9.65 ]
1.13
[ 28.7 ]
30 Amp Heavy Duty Non-Fusible 60 Amp Compact Heavy Duty Non-Fusible 60 Amp General Duty Non-Fusible
36
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
+
1/8 inch.
➀
➀
➀
Figure 14
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE A (Concentric) B (Tangential) .50 .75 1.00
.50 .75
Page 37
4.47 114[]
1.19 30[]
3.35 85[]
2.25 57[]
33[]
10.43 265[]
1.47 37[]
6.00 152[]
.65
17[]
13.36 339[]
SEE DETAIL
B
OF BOX
.27 DIA (2) [ 7 ]
A
(2)
.76
19[]
5.05 128[]
10.17 258[]
8.35 212[]
.87
22[]
8.25 210[]
5.79 147[]
16.26 413[]
.91
23[]
1.69 43[]
1.89 48[]
.31
8[]
17.46 443[]
A
LEFT &
RIGHT SIDE
Type 3R (Outdoor)
1.32 33[]
.65
17[]
4.58 116[]
PROVISION FOR TYPE "HS" HUB
.64
16[]
3.32
84[]
1.32 34[]
PROVISION FOR TYPE "HS" HUB
1.35 34[]
4.84 123[]
.82
21[]
2.42 62[]
7.91 201[]
1.04 26[]
3.21 82[]
.79
20[]
4.34 110[]
34[]
10.11 257[]
1.88 48[]
A
(2)
OF BOX
SEE DETAIL
C
(3).27 DIA
[ 7 ]
15.45 393[]
.32
8[]
8.25 209[]
5.05 128[]
10.17 258[]
4.07 103[]
8.35 212[]
.91
23[]
1.46 37[]
1.90 48[]
14.39 365[]
.78
20[]
B
LEFT &
RIGHT SIDE
5.95 151[]
9.01 229[]
.91
23[]
1.51 38[]
1.80 46[]
1.80 46[]
6.64 169[]
.25
6[]
B
(3)
.25 DIA GROUND KNOCKOUT
DIA.27
7[]
[]
.65
16[]
.28
7[]
.75
19[]
DETAIL
C
30 Amp Heavy Duty Fusible 60 Amp General Duty Fusible
➀
➀
➀
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE A (Concentric) B (Tangential) .50 .75 1.00
Figure 15
.50 .75
60 Amp Heavy Duty (also 30A Oversized Heavy Duty)
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
+
1/8 inch.
.88 DIA KNOCKOUT
6.08 155[]
.87
22[]
2.08 53[]
2.50 64[]
11.53 293[]
9.16 233[]
.25 DIA GROUND KNOCKOUT
A
(3)
2.50 64[]
.25
6[]
Figure 16
.28
7[]
.65
16[]
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) .50 .75 1.00 1.25
DETAIL
B
DIA.27
7[]
.75
19[]
37
Page 38
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Type 3R (Outdoor)
100 Amp General and Heavy Duty (also 60A Oversized Heavy Duty)
➀
➀
➀
➀
➀
➀
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) .75 1.00 1.25 1.50
B (Tangential) 1.00 1.25 1.50 2.00
Figure 17
200 Amp General and Heavy Duty
15.94
7.19 183[]
.33
DIA (4)
8[]
3.68
38
5.50
93[]
140[]
3.10 79[]
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to ➀ Dimensions shown apply to heavy duty switches only.
405[]
OF BOX
8.20 208[]
SEE DETAIL
A
(2)
5.50 140[]
.88 DIA KNOCKOUT
8.19 208[]
+
1/8 inch.
22.43 570[]
.81
21[]
C
5.10 130[]
.87
22[]
2.45 62[]
4.88
.35
9[]
31.07 789[]
12.42
124[]
➀
4.39 112[]
➀
315[]
4.37 111[]
➀
16.99 432[]
14.61 371[]
➀
12.33 313[]
➀
10.17 258[]
6.36 162[]
.91
A
LEFT &
RIGHT SIDE
2.31
.81
21[]
➀
9.74 247[]
.25 DIA GROUND KNOCKOUT
A
(3)
.20
4.88 124[]
5[]
23[]
59[]
7.30 185[]
29.90 759[]
.65
17[]
1.32 34[]
.47
12[]
1.44 37[]
DETAIL
C
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) 1.25 1.50 2.00 2.50
Figure 18
PROVISION FOR TYPE "HS" HUB
DIA.38
10[]
DIA1.00
25[]
Page 39
14.68 373[]
13.44 341[]
18.77 477[]
13.46 342[]
13.25 337[]
44.07 1120[]
44.57 1132[]
.83
21[]
.62
16[]
9.23 234[]
2.07 53[]
20.50 521[]
26.50 673[]
2.50 64[]
39.00 991[]
.43 DIA (4)
11[]
A(4)
11.00 [ 279 ]
26.70 [ 678 ]
1.56 [ 40 ]
5.50 [ 140 ]
11.00 [ 279 ]
16.50 [ 279 ]
4.07 [ 104 ]
1.80 [ 46 ]
.25 [ 6 ]
.50-.75 DIA (2) GROUND KNOCKOUT BOTTOM ONLY
Type 3R (Outdoor)
26.00 660[]
2.07 53[]
20.50 521[]
2.50 64[]
51.00 1295[]
.43 DIA (4)
11[]
14.68 373[]
56.57 1437[]
9.23 234[]
56.07 1424[]
13.44 341[]
.83
21[]
.62
16[]
18.77 477[]
25.46 647[]
13.24 336[]
A(4)
11.00 [ 279 ]
26.70 [ 678 ]
1.56 [ 40 ]
5.50 [ 140 ]
11.00 [ 279 ]
16.50 [ 279 ]
4.07 [ 104 ]
1.80 [ 46 ]
.25 [ 6 ]
.50-.75 DIA (2) GROUND KNOCKOUT BOTTOM ONLY
400 / 600 Amp Heavy Duty Non-Fusible
Figure 19
[ 419 ]
KNOCKOUT CONDUIT
CODE SIZE
A 2.00 2.50 3.00 3.50
400 / 600 Amp General and Heavy Duty Fusible
+
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
1/8 inch.
C
E
A
D
STANDARD HEIGHT REDUCED
B
SWITCH TYPE
Figure 20
DIMENSIONS
ABCDE
56.57[1437]
45.82[1164]
56.07[1424]
45.31[1151]
51.00[1295]
40.25[1022]
[ 419 ]
KNOCKOUT CONDUIT
CODE SIZE
A (Tangential) 2.00 2.50 3.00 3.50
25.46[647]
20.99[533]
18.77[477]
12.49[317]
39
Page 40
34.25 870[]
2.07 53[]
38.40 975[]
2.50 64[]
61.25 1556[]
39.96
39.50 1003[]
14.68 373[]
66.82 1697[]
24.02 610[]
30.46 774[]
13.24 336[]
13.44 341[]
66.25 1683[]
.83
21[
]
9.24 235[]
.25
6[]
38.40 975[]
1027[]
40.45
9.24 235[]
.25
6[]
38.40 975[]
1027[]
40.45
3.20 81[]
32.00 813[]
40.25 1022[]
2.79 71[]
49.25 1251[]
.56 DIA (4)
14[]
14.68 373[]
13.44 341[]
24.02 610[]
18.46 469[]
13.25 337[]
54.67 1389[]
55.16 1401[]
.83
21[]
.54
14[]
9.57 243[]
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Type 3R (Outdoor)
800 / 1200 General and Heavy Duty Non-Fusible
Figure 21
40.49 [ 1028 ]
No knockouts in the enclosures.
800 / 1200 Amp Heavy Duty Fusible
40.25
[ 1022 ]
38.44
2.79
[ 71 ]
40
3.20
[ 81 ]
No knockouts in the enclosures.
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
32.00
[ 813 ]
[ 976 ]
+
1/8 inch.
67.16
[1706]
66.67
[1693]
9.29
[ 236 ]
40.49
[ 1028 ]
38.44
[ 976 ]
Figure 22
Page 41
Type 4X (Stainless); 12 (Industrial)
7.42 188[]
3.24 82[]
.42
11[]
13.33 338[]
2.75 70[]
2.75 70[]
DIA (4).27
8[]
.05
1[]
OF BOX
SEE DETAIL
A
6.65 169[]
6.22 158[]
9.02 229[]
.95
24[]
.35
9[]
DIA.63
16[]
DIA.27
7[]
DETAIL
A
11.12 282[]
5.56 141[]
8.59 218[]
1.81 46[]
1.86 47[]
14.14 359[]
8.46 215[]
.55
14[]
10.46 266[]
14.16 360[]
16.46 418[]
7.42 188[]
.42
11[]
2.75 70[]
2.75 70[]
3.24 82[]
SEE DETAIL
A
OF BOX
.27 DIA (4)
7[]
17.33 440[]
14.27 362[]
8.46 215[]
8.59 218[]
10.46 266[]
.55
14[]
5.32 135[]
17.31 440[]
1.98 50[]
4.98 126[]
.35
DIA.63
16[]
.95
24[]
DIA.27
7[]
.35
9[]
DETAIL
A
6.22 158[]
6.65 169[]
9.02
229[]
30 Amp Heavy Duty Non-Fusible 60 Amp Compact Heavy Duty Non-Fusible
Figure 23
No knockouts in the enclosures.
30 Amp Heavy Duty Fusible
No knockouts in the enclosures.
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
+
1/8 inch.
Figure 24
41
Page 42
18.47 469[]
.42
11[]
9.94 253[]
DIA (4)
.27
7
[]
3.62 92[]
SEE DETAIL
A
OF BOX
4.00 []
102
4.00 []
102
19.31 491[]
16.27 413[]
19.31 490[]
.83
21[]
8.45 215[]
8.59 218[]
5.33 135[]
1.99 51[]
10.46 266[]
6.69 170[]
.95
24[]
DIA.27
7[]
DIA.62
16[]
.35
9[]
DETAIL
A
11.47 291[]
6.34 161[]
9.17 233[]
10.43 265[]
24.16
[]
.42
11[]
4.74 120[]
SEE DETAIL
A
.27 DIA (4)
614
7[]
4.25 []
108
4.25 []
108
25.00 635[]
21.96 558[]
5.34 136[]
8.59 218[]
23.16 588[]
8.45 215[]
3.52 89[]
10.46 266[]
2.04 52[]
8.73 222[]
12.02 305[]
9.65 245[]
6.80 []
173
.95
24[]
DIA.67
17[]
DIA.27
7[]
.35
9[]
DETAIL
A
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Type 4X (Stainless); 12 (Industrial)
60 Amp Heavy Duty
Figure 25
No knockouts in the enclosures.
100 Amp Heavy Duty
No knockouts in the enclosures.
Dimensions shown in inches and millimeters [ ].
42
Dimensions shown accurate to
+
1/8 inch.
Figure 26
Page 43
Type 4X (Stainless); 12 (Industrial)
6.75 171[]
6.75 171[]
.42
11[]
32.17 817[]
15.39 391[]
7.22 183[]
OF BOX
SEE DETAIL
A
.33 DIA (4)
9[]
33.00 838[]
10.01 254[]
10.37 263[]
5.24 133[]
29.96 761[]
31.07 789[]
6.63 168[]
4.60 117[]
12.58 319[]
11.86 301[]
16.95 431[]
8.45 215[]
14.62 371[]
DIA.75
19[]
1.14 29[]
DIA.38
10[]
.44
11[]
DETAIL
A
16.00 406[]
4.41 112[]
24.82 630[]
.63
16[]
46.43 1179[]
SEE DETAIL
A
14.64 372[]
47.68 1211[]
44.14 1121[]
9.19 233[]
13.19 335[]
13.17 335[]
44.57 1132[]
13.36 339[]
18.54 471[]
9.19 233[]
24.82 630[]
26.44 672[]
1.40 36[]
.47
1[2
DIA.56
14[]
DIA1.00
25[]
DETAIL
A
]
200 Amp Heavy Duty
Figure 27
No knockouts in the enclosures.
400 / 600 Amp Heavy Duty Non-Fusible
No knockouts in the enclosures.
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
+
1/8 inch.
Figure 28
43
Page 44
14.68 373[]
58.56 1487[]
54.67 1389[]
9.24 235[]
13.24 336[]
18.46 469[]
55.16 1401[]
13.44 341[]
24.02 610[]
32.00 813[]
3.22 82[]
38.44 976[]
.78
20[]
57
1448[]
40
1016[]
SEE DETAIL
A
Detailed Dimension Drawings
24.82 630[]
16.00 406[]
4.41 112[]
.63
16[]
58.43 1484[]
SEE DETAIL
A
14.64 372[]
59.68 1516[]
56.14 1426[]
56.57 1437[]
25.17 639[]
13.19 335[]
9.19 233[]
13.34 337[]
18.54 471[]
DIA.56
[]
14
9.19 233[]
24.82 630[]
26.44 672[]
1.40 36[]
[]
DIA.56
[]
DIA1.00
25[]
DETAIL
A
14
.47 12
Siemens Type VBII Safety Switches
Type 4X (Stainless); 12 (Industrial)
400 / 600 Amp Heavy Duty Fusible
Figure 29
No knockouts in the enclosures.
800 / 1200 Amp Heavy Duty Non-Fusible
44
No knockouts in the enclosures.
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
+
1/8 inch.
Figure 30
40
1016[]
9.67
[ 246 ]
9.67
.29
[ 246 ]
236 ]
1.40 36[]
.47
1[2
]
DETAIL
38.44 976[]
A
DIA.56
14[]
DIA1.00
25[]
Page 45
Type 4X (Stainless); 12 (Industrial)
800 / 1200 Amp Heavy Duty Fusible
9.67
[ 246 ]
Figure 31
9.67
[ 246 ]
No knockouts in the enclosures.
K
Types 7 and 9 (Figure 2)
Breaker Catalog Mounting Inside Outside Conduit Size
Type Number A B C D E F G H K Std. Max.
ED2, ED4, ED6 EA 5 1/2 13 1/8 5 15/16 10 3/4 5 7/16 9 7/16 14 1/4 6 5/8 1 5/8 1 1/4 1 1/4
HED4, HED6 EB 6 18 6 1/2 16 15 9/16 9 7/8 19 3/8 6 11/16 2 2 2 FXD6, FD6, HFD6, HFXD6, CFD6
JXD2(A), JXD6(A), JD6, SJD6(A)
HJD6, HJXD6(A), HHJD6, EC4 10 1/4 22 5/8 11 3/4 20 6 1/2 15 3/8 23 7/8 8 1/4 2 3/4 2 1/2 3
HHJXD6, SHJD6 EE 8 1/2 27 1/8 10 3/4 24 1/8 7 3/4 13 7/8 27 1/4 9 9/16 4 3 4
LXD6(A), LD6(A), SLD6(A), HLD6(A), HLXD6(A), HHLD6, ED6 11 7/8 40 3/4 13 3/8 37 7/8 7 7/8 18 1/8 42 5/8 9 7/8 3 5/8 4 4
HHLXD6, SHLD6
Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to
+
1/8 inch.
Dimensions Command (inches) Knockouts (4)
EC2 10 1/4 22 5/8 11 3/4 20 6 1/2 15 3/8 23 7/8 8 1/4 2 3/4 2 2 1/2
45
Page 46
A
D
E
(6) “F“ Dia. mounting holes
C
L
This mounting hole omitted on 30-100A, 4 pole Non-fusible switches
Detailed Dimension Drawings
Siemens Type VBII Safety Switches
Figure 1: Type 1
C
B
Figure 1: Type 12/3R and 4X
E
D
(6) ”F“ Dia. mounting holes (30-200A)
C
C
L
B
A
4 & 6 Pole Safety Switch Dimensions – Inches (mm)
Enclosure Mounting
Catalog Number
Figure 1, 4-Pole Fusible and Non-fusible, Type 1
HNF461 24.50 (622) 9.53 (242) 6.09 (155) 19.00 (483) 6.75 (171) 0.268 (7)
HF461 29.12 (740) 9.53 (242) 6.09 (155) 23.50 (597) 6.75 (171) 0.268 (7)
HNF462 24.88 (632) 11.50 (292) 6.09 (155) 19.00 (483) 9.38 (238) 0.268 (7)
HF462 33.53 (852) 11.50 (292) 6.09 (155) 27.50 (699) 9.38 (238) 0.268 (7)
HNF463 27.62 (702) 12.18 (309) 6.09 (155) 19.36 (492) 8.00 (203) 0.268 (7)
HF463 36.44 (926) 12.18 (309) 6.09 (155) 28.11 (714) 8.00 (203) 0.268 (7)
HNF464 36.00 (914) 19.12 (486) 6.42 (163) 30.88 (784) 15.00 (381) 0.44 (11)
HF464 49.48 (1257) 19.12 (486) 6.42 (163) 45.50 (1130) 15.00 (381) 0.44 (11)
Figure 2, 4 & 6-Pole Fusible Type 12/3R and 4X
HF461J, HF661J, 29.50 (622) 9.53 (242) 6.48 (165) 31.65 (804) 5.47 (139) 0.27 (7)
HF661S
HF462J, HF662J, 33.53 (852) 11.50 (292) 6.48 (165) 35.69 (907) 8.00 (203) 0.27 (7)
HF662S
HF463J, HF663J, 36.44 (926) 12.18 (309) 6.48 (165) 38.67 (982) 8.47 (215) 0.27 (7)
HF663S
HF464J, HF664J, 49.48 (1257) 19.12 (486) 6.78 (172) 51.64 (1312) 13.44 (341) 0.33 (8)
HF664S
Figure 2, 4 & 6-Pole Non-fusible Type 12/3R and 4X
HNF461J, HNF661J, 24.50 (622) 9.53 (242) 6.48 (165) 26.65 (667) 5.47 (139) 0.27 (7)
HNF661S
HNF462J, HNF662J, 24.88 (632) 11.50 (292) 6.48 (165) 27.03 (687) 8.00 (203) 0.27 (7)
HNF662S
HNF463J, HNF663J, 27.54 (700) 12.18 (309) 6.48 (165) 29.77 (756) 8.47 (215) 0.27 (7)
HNF663S
HNF464J, HNF664J, 36.00 (914) 19.12 (486) 6.78 (172) 38.16 (969) 13.44 (341) 0.33 (8)
HNF664S
ABCDEF
46
Page 47
Figure 1: Type 1 & 3R
A
D
E
(6) ”F“ Dia. mounting holes (30-200A) (4) ”F“ Dia. mounting holes (400-1200A)
C
L
C
B
This mounting hole omitted on 30-100A Type VBII Non-Fusible switches
A
➃
Figure 2: Type 4X & 12
E
C
C
B
VBII Design Double Throw Dimensions – Inches
Catalog Number
Figure 1 (30-1200A Type 1 & 3R)
DTNF221, DTNF321, DTNF361, DTNF361R 24.50 9.53 6.09 19.00 6.75 0.268 DTF321, DTF321R, DTF361 29.12 9.53 6.09 23.50 6.75 0.268 DTNF222, DTNF322, DTNF362, DTNF362R 24.88 11.50 6.09 19.00 9.38 0.268 DTF322, DTF322R, DTF362 33.45 11.50 6.09 27.50 9.38 0.268
DTNF223, DTNF323, DTNF323R, DTNF363, DTNF363R, DTGNF223R, DTGNF223NR, DTGNF323R, DTGNF323NR
DTF323, DTF323R, DTF363, DTF363R 36.44 12.18 6.09 28.11 8.00 0.268
DTNF224, DTNF224R, DTNF324R, DTNF324, DTNF364R, DTGNF224R, DTGNF224NR, DTGNF324R, DTGNF324NR
DTF224, DTF224R, DTF324, DTF324R, DTF364, DTF364R 49.44 19.12 6.42 44.50 15.00 0.44 DTF325, DTF326, DTF365 73.54 28.22 9.44 65.50 16.00 0.56 DTNF225, DTNF225R, DTNF325, DTNF365, DTNF365R 57.71 28.22 9.44 49.75 16.00 0.56 DTNF326, DTNF366, DTNF366R 57.71 28.22 9.44 49.75 16.00 0.56 DTNF327, DTNF367, DTNF367R 71.65 41.60 9.44 63.70 32.00 0.56 DTNF368, DTNF368R 71.65 41.60 9.44 63.70 32.00 0.56 NFR451DTK➂, NFR452DTK➂, NFR453DTK NF454DTK➁➂, NFR454DTK
NF455DTK➂, NF456DTK➂, NF457DTK NFR455DTK➂, NFR456DTK➂, NFR457DTK
Figure 2 (30-200A Type 12 & 4X)
DTNF361J, DTNF361S 24.42 9.65 6.48 26.65 5.47 0.27 DTNF362J, DTNF362S 24.80 11.61 6.48 27.03 8.00 0.27 DTNF363J, DTNF363S 27.54 12.29 6.48 29.77 8.47 0.27 DTNF364J, DTNF364S 35.93 19.24 6.78 38.16 13.44 0.33 NF355HDTK➁, NF355SSDTK➁ 53.82 22.66 7.25 56.20 18.00 0.56 F353SSDTK F354SSDTK F355SSDTK
➀ (3) Mounting holes supplied (1 at top). ➁ (4) Mounting holes supplied. ➂ These switches are not Type VBII design. ➃ Drip hood not shown but provided on Type 3R enclosures.
Note: For inches/ millimeters conversion, multiply inches by 25.4.
➁➂
➁➂
➁➂
➁➂
D
(6) ”F“ Dia. mounting holes (30-200A) (4) ”F“ Dia. mounting holes (400-1200A)
Enclosure Mounting
ABC DEF
27.62 12.18 6.09 19.36 8.00 0.268
36.00 19.12 6.42 31.00 15.00 0.44
➂
➂
➂
24.63 11.63 4.78 21.50 9.25
37.25 19.19 6.32 33.50 16.00
63.31 27.00 8.88 58.50 22.25
37.00 11.62 5.50 39.50 9.00 0.26
50.90 19.16 6.48 63.27 16.12 0.50
74.50 25.00 8.92 76.69 20.25 0.56
C
L
C
B
➀
➁
➁
0.25
0.56
0.56
➀
➁
➁
47
Page 48
Replacement Parts
Siemens Type VBII Safety Switch
HFB656
HNB623
HBB612
HFB612
HM6123
HH6123
Ampere Line Load Handle/Handle Guard Mechanism
Rating Base Base General Duty Heavy Duty Assembly Lugs
30A General Duty 2- and 3-Pole Fusible and Non-fusible ➄ 240V Max
30 Fused, 2-Pole W410472A – – – – – ➀ 30 Fused, 3-Pole W410473A – – – – – ➀
30 Non-fused W410473B – – – – – ➀
Fusible 2 and 3-Pole 60-600A General Duty & 30-600A Heavy Duty ➄➇ 240V Max
30 HD 240V HFB21 ➁ HBB21 ➁ – HH6123 ➆ HM6123 ➆ HL612 ➀
60 GD HFB612 ➁ HBB612 ➁ GH223 – HM6123 HL612 ➀
60 HD 240V
➉
100 HFB63 ➁ HBB63 ➁ GH223 HH6123 ➆ HM6123 ➆ HL63 ➀ 200 HFB64 ➁ HBB64 ➁ GH24 HH64 ➆ HM64 ➆ HL64 ➀ 400 HFB65 ➂➅ HBB656 ➂➅ HH65678 HH65678 ➆ HM65 HL65678 ➃ 600 HFB66 ➂➅ HBB656➂➅ HH65678 HH65678 ➆ HM66 HL65678 ➃ 800 HFB67A ➁➅ HBB67A ➁➅ – HH65678 ➆ HM67A
1200 HFB68 ➅ HBB68 ➅ – HH68
HFB22 ➁ HBB22 ➁ – HH6123 ➆ HM6123 ➆ HL612 ➀
HL67A
➆
HM678
➈
➅➈
Fusible 3-Pole Heavy Duty ➄➇ 600V Max
30 600V HFB612 ➁ HBB612 ➁ – HH6123 ➆ HM6123 ➆ HL612 ➀ 60 600V HFB62 ➁ HBB62 ➁ – HH6123 ➆ HM6123 ➆ HL612 ➀
60A Oversized HFB623 ➁ HBB623 ➁ – HH6123 HM6123 –
100 HFB63 ➁ HBB63 ➁ – HH6123 ➆ HM6123 ➆ HL63 ➀ 200 HFB64 ➁ HBB64 ➁ – HH64 ➆ HM64 ➆ HL64 ➀ 400 HFB65 ➂➅ HBB656 ➂➅ – HH65678 ➆ HM65 HL65678 ➃ 600 HFB66 ➂➅ HBB656 ➂➅ HH65678 HH65678 ➆ HM66 HL65678 ➃ 800 HFB67A ➁➅ HBB67A ➁➅ – HH65678 ➆ HM67A
1200 HFB68 ➅ HBB68 ➅ – HH68
➆
HM678
HL67A
➈
➅➈
Non-Fusible 3-Pole 60-600A General Duty and 30-600A Heavy Duty ➄➇ 600V Max
30 HD HNB612 ➁ – – HH6123 ➆ HM6123 ➆ HL612 ➀ 60 GD HNB612 ➁ – GH223 – HM6123 HL612 ➀
➉
60 HD
11
100 HNB623 ➁ – GH223 HH6123 ➆ HM6123 ➆ HL63 ➀ 200 HNB64 ➁ – GH24 HH64 ➆ HM64 ➆ HL64 ➀ 400 HNB65 ➂➅ – HH65678 HH65678 ➆ HM65 HL65678 ➃ 600 HNB66 ➂➅ – HH65678 HH65678 ➆ HM66 HL65678 ➃ 800 HNB67A ➁➅ – – HH65678 ➆ HM67A HL67A
1200 HNB68 ➁➅ – – HH68
➀ Three lugs included in kit. ➆ For type 4 / 4X stainless steel switches add “S” to end of catalog number.
48
➁ Includes lugs. ➇ For replacement door for heavy duty switches add “DOOR” to end of switch catalog number. ➂ Lugs are not included. ➈ Lugs included with line and load bases. ➃ One lug per kit. ➉ Also for oversized 30A HD switches. ➄ One per switch required unless otherwise noted. Also for oversized switch HNF362RL. ➅ One required per pole.
HNB623 ➁ – – HH6123 ➆ HM6123 ➆ HL612 ➀
➆
11
HM678 ➈
➅➈
Page 49
Fuse Application and Selection Data
Siemens Type VBII Safety Switch
Siemens enclosed safety switches are designed for fuse versatility. Although Siemens is not a manufacturer of fuses, once the type of fuse needed for a particular application is determined, it’s easy to select an appropriate switch.
One-Time Fuses
One-time fuses are standard for use in situations calling for 1200 amperes or less with maximum voltages for 250 or 600 volts. Specially designed, current­carrying links are connected to contact pieces at the ends of the enclosure. When an overload occurs, the circuit quickly opens and the arc is quenched by granular insulating material that surrounds the current carrying links.
Available in all classes.
The proper fuse type for the application is selected using the following parameters:
• Voltage requirements
• Conductor ampacity
• Horsepower requirements
• Maximum available RMS fault-current
• UL fuse class when specified
Current Limiting Fuses
This design offers the highest degree of circuit protection among fuses. Inside, usually copper or silver alloy links are embedded in pure quartz sand between heavy copper end blocks. The special design is fast-acting and interrupts during the first half-cycle of a fault. This causes a limitation of both fault­peak current and let-through current.
Available in Classes J, L, R and T.
The compatible fusible safety switch is selected following these parameters:
• System voltage requirements
• Fuse amp ratings
• Available fault current
• UL fuse class
• Environmental conditions
• Number of poles required
Dual-element Time-delay Fuses
Dual-element fuses may have time­delay designation since these fuses employ two distinctly separate types of elements. One provides overload protection with time delay. (UL states that time delay means having a 10-second operating delay at 500 percent of fuse label rating.) The second provides short circuit protection similar to a single-element fuse. Dual-element fuses are most frequently used on motor loads.
49
Page 50
Fuse Applications and Dimensions
A
B
C
D
E
F
G
A
E
G
C
D
B
Siemens Type VBII Safety Switch
Class R and H Fuses
Class R Application: Over-current and short-circuit protection of motors and transformers, service entrance equip­ment, feeder and branch circuits. (General Purpose Protection)
Class R Rejection: A UL Class R fuse kit is required that rejects lower-rated fuses (H and K).
Ferrule Type 0-60A
Class H Fuse Dimensions
250 Volts 600 Volts
Ampere
Rating A B C D E F G A B C D E F G
0-30 2 –– –– –– 9/16 –– 1/2 5 –– –– –– 13/16 –– 17/32
35-60 3 –– –– –– 13/16 –– 21/32 5 1/2 –– –– –– 1 1/16 –– 21/32
65-100 5 7/8 –– –– –– 3/4 1/8 1 7 7/8 –– –– –– 3/4 1/8 1 110-200 7 1/8 –– –– –– 1 1/8 3/16 1 3/8 9 5/8 –– –– –– 1/8 3/16 1 3/8 225-400 8 5/8 –– –– –– 1 5/8 1/4 1 7/8 11 5/8 –– –– –– 1 5/8 1/4 1 7/8 450-600 10 3/8 –– –– –– 2 1/4 2 1/4 13 3/8 –– –– –– 2 1/42 1/4
Blade Type 61-600A
Class R Fuse Dimensions
250 Volts 600 Volts
Ampere
Rating A B C D E F G A B C D E F G
0-30 2 5/32 5/64 3/8 9/16 –– 1/2 5 3/16 3/32 5/8 13/16 –– 17/32
35-60 3 3/16 3/32 5/8 13/16 –– 21/32 5 1/2 1/4 3/32 7/8 1 1/16 –– 21/32
61-100 5 7/8 1/2 9/32 23/64 3/4 1/8 1 7 7/8 1/2 9/32 23/64 3/4 1/8 1 101/200 7 1/8 11/16 9/32 35/64 1 1/8 3/16 1 3/8 9 5/8 11/16 9/32 35/64 1 1/8 3/16 1 3/8 201-400 8 5/8 15/16 13/32 51/64 1 5/8 1/4 1 7/8 11 5/8 15/16 13/32 51/64 1 5/8 1/4 1 7/8 401-600 10 3/8 1 1/8 13/32 63/64 2 1/4 2 1/4 13 3/8 1 1/8 17/32 53/64 2 1/4 2 1/4
Class J
Application: Current limiting protection to a wide variety of applications, Panelboards, Switchboards, Busway and Feeder Circuits.
A
C
1” MIN
B
J
H
G
A
K
1” MIN
B
Rejection: Its unique dimensions prevent the substitution of another fuse
.
Class J Ferrule Type 0-60A
Class J Blade Type 61-600A
Class J Fuse Dimensions
AAmmppeerree
Rating A B C D E F G H J K
0-30 2 1/4 1/2 13/16 – – – – – – –
31-60 2 3/8 5/8 1 1/16 – – – – – – –
61-100 4 5/8 3 5/8 1 1/8 3/4 1/8 1 1/2 9/32 3/8 2 5/8 101-200 5 3/4 4 3/8 1 5/8 1 1/8 3/16 13/8 11/16 9/32 3/8 3 201-400 7 1/8 5 1/4 2 1/8 1 5/8 1/4 17/8 15/16 13/32 17/32 3 3/8
401-600 8 6 2 5/8 2 3/8 21/8 1 17/32 11/16 3 3/4
50
F
E
D
C
Page 51
Class L
Class T
Application: Current limiting protection for service entrance equipment, feeder circuits and metering centers.
Application: It combines two highly desirable features—a high degree of current limition and a small physical size. Panelboards, Switchboards and
Metering Center. Rejection: Its unique dimensions prevent the substitution of another fuse.
Rejection: Its unique dimension
prevents the substitution of another
fuse
85/8
21
313/16
/32
1
27/8
45/16
5
/8
11/8 27/16
Class L Blade Type 601-800A
5
/8
8
/2
27/16
15
/16
3
/8
5
/16
5
/8
113/32
3
/4
11/8
315/32
103/4
313/16
27/8
1
/2
13/8
315/32
53/8
Class L Blade Type 801-1200A
Fuse Ratings
Class Amperes Volts Dimensions Int. Ratings I2t, Ip Circuits
H 1-600A 250 and 600V NEC 10,000A Less than General purpose
K5* 1-600A 250 and 600V Class H 100,000A I
J 1-600A 600V or less Diff. from 200,000A I2t - Low Main & feeder
RK1 1/10-600A 600V or less Class H with 200,000A I2t - Slightly>J Main & feeder
RK5 1/10-600A 600V or less Class H with 200,000A I
(time 250V or less rejection I
delay) feature
T 1-1200A 300V AC Diff. from 200,000A I
T 1-800A 600V AC Diff. from 200,000A I2t - =J Main & feeder
L 601-6000A 600V or less Bolt type 200,000A I2t - Low Main & feeder
or less AC standards – 10,000A available circuits
or less AC without rejection I
Class H I
250V or less rejection I
feature small percent)
Class H I
Class H I
2
t - RK5 up to 100A Feeder
p
- RK5 up to 100A circuits
p
- Low circuits
p
- Slightly>J circuits(motor load
2
t - >RK-1 Motor starting
p
- RK-1 currents
2
t - <J Main & feeder
p
- <J circuits
p
- =J circuits
p
- Low circuits
I
5
13/8
/8
1
/8
3
/4
3
/8
* Class K5 fuses do not prohibit the use of Class H type fuses in a switch.
51
Page 52
Ratings and Test Requirements
Siemens Type VBII Safety Switch
Enclosed Switch Load Ratings
The primary functions of a fusible enclosed switch are to carry current continuously, to provide over current and short-circuit protection, to be capable of disconnecting the circuit, and to provide means for mounting fuses. Safety switches may also have other capabilities covered by load break ratings (in contrast with no-load dis­connect switches), such as standard and maximum horsepower ratings and the ability to withstand the maximum I2t energy let-throughs of fuses.
All Siemens safety switches are capable of continuously carrying their full-rated nameplate current at rated voltage. This capability is directly attainable in no-fuse switches and in fusible switches when the fuses are replaced with copper bars, without exceeding permissible temperature rise.
Fuses are capable of carrying their rated current in open air. Under this condition the fuses will not open and will not exceed permissible tempera­ture rise. When fuses are used in a switch or other enclosure, a higher ambient temperature is caused by the switch heat and fuse-generated heat. Since fuses are thermal acting by design, they will not carry full current rating at higher ambient temperatures.
To assist users of fusible equipment, UL requires each fusible switch to carry the statement “Continuous load current not to exceed 80% of the rating of the fuses employed.” Good electrical practice may require even further de­ratings depending on the type of fuse, load, altitude and ambient temperature of the switch location.
Load Break Ratings
All Siemens safety switches are load break rated. The load break rating is assigned by UL after the switch­ing unit has successfully performed the following tests for general use enclosed switches:
Load Break Ratings
Switch ON, OFF
Number of
Ampere Operations With Without
Rating per Minute Current Current Total
30-100 6 6000 4000 10000
200 5 6000 2000 8000 400 4 1000 5000 6000 600 3 1000 4000 5000 800 2 500 3000 3500
1200 1 500 2000 2500
Number of Operations
12X Current Rating
In addition to the required UL overload testing, all Siemens VBII Safety Switches have been tested at twelve times rated current at 600V AC to assure compliance to automotive and other heavy industry requirements.
Horsepower Ratings
All Siemens safety switches, where appropriate, are horsepower rated. The assignment of such ratings is made by UL only after the switching unit has undergone tests to determine its accept­ability. In addition, the unit must successfully perform on an overload test series which includes repeated interruption of the locked rotor current of the motor for which it is to be rated as follows:
Horsepower Ratings
Max HP ON/OFF Ops Number of Cycles
Rating per Minute of Operation
100 6 50 500 1 10
Number of
Most switches have two or more ratings for a particular voltage and current. Siemens safety switches are UL listed for design E horsepower ratings. With Siemens safety switches no de­rating is required in most cases. Depending on the switch and its
application, various ratings have been achieved. All Siemens switches include a complete list of the ratings on the inside of the cover.
Horsepower Rating Charts
The number and variety of horsepower ratings that can be applied to a switching unit makes it impractical, in most instances, to list all such ratings on the front of the unit. Siemens does, however, provide this data by means of a chart on the inside cover.
Horsepower Rating Range
UL test procedure include ratings up to 500 HP. Siemens safety switch units in appropriate sizes have successfully passed the locked rotor current inter­rupting test series for ratings through 500 horsepower at both 480 and 600 volts AC and through 50 horsepower at 600 volts DC.
Maximum Horsepower Ratings
The maximum horsepower rating is based upon the largest rating of a time delay fuse: 1) which can be incorporat­ed in the switch and 2) which will permit the motor to be started. Since the fuse has extra time delay, it can hold the starting current of a larger motor longer than a standard fuse.
Standard Horsepower Rating
This rating is assigned to a switch after it has successfully completed the locked rotor test series, on the basis of the largest standard fuse rating: 1) which can be incorporated in the switch and
2) which will permit the motor to be started. The standard fuse does not have a designed time delay to allow for motor starting currents.
52
Page 53
Siemens Type VBII Safety Switch
Multiple-Voltage Horsepower Ratings
A switch may have additional standard and maximum horse-power ratings for different voltages. A switch that is horsepower rated at 240V AC or 250V DC may also have horsepower ratings for motors on 120V AC or 125V DC circuits.
Multipole Horsepower Ratings
A switch may have horsepower ratings applicable to the same current and voltage ratings but with fewer poles if the switch is investigated and found suitable for the assigned rating.
Short-circuit Withstandability
UL test procedures for switches and fuses have been expanded to provide realistic standards of performance with respect to clearing high-level fault currents.
These revised standards deal with the control of destructive energy in the shorted circuit. Two types of potential damage are characteristic of high-level short-circuits: mechanical and thermal. Mechanical damage is caused by the electromagnetic force surrounding conductors; thermal damage is the result of excessive current during the fault-clearing time.
The UL fuse standard defines maximum instantaneous peak let-through current (lp) and maximum destructive energy let-through (I2t) for each fuse (except Class H). Applications of fuses and safety switches on systems having more than 10,000A are available. Short circuits require selections of the proper UL-listed fuses and switches capable of withstanding I2t let­throughs. See chart below for with­stand ratings on Siemens switches.
I2t Rated
Suitability tests for service with Class H, R, J, L and T fuses have been conducted. Representative switches with test fuses connected in series with each switch were subjected to I2t let-through values in excess of the capacities of the largest fuses acceptable by the switches.
To pass the test, the switch must remain operable after being closed into a high-amp available short-circuit current. The test fuse is sized so that higher levels of let-through current and energy will be reached than would ever occur during normal usage in the field. See the chart below for I2t ratings on Siemens switches.
Short-circuit Withstand Ratings
Fuse Rating Fuse Class General Duty Heavy Duty
Fusible Plug 10,000 –
Non-Fusible ➀ H or circuit breaker 10,000 10,000
➀ With fuses or circuit breaker in series with switch. Fuse or circuit breaker ampere rating cannot exceed switch ampere rating. ➁ 60A compact switches are rated 100,000 with 60A max.
Class J or R fuses in series with switch.
H or circuit breaker 10,000 10,000
K 10,000 10,000
J 100,000 200,000 R 100,000 200,000 T 100,000 200,000 L –– 200,000
K 10,000 10,000
J 100,000 200,000 R 100,000 200,000 L –– 200,000
Short Circuit Rating (RMS Symmetrical Amperes)
➁ ➁
I2t and Ip Ratings
Switch
Rating I
Ampere (Amp2 x sec.) (Amps)
30 50,000 14,000
60 200,000 26,000 100 500,000 32,000 200 2,000,000 50,000 400 6,000,000 75,000 600 12,000,000 100,000 800 10,000,000 80,000
1200 15,000,000 120,000
2
t Rating Ip Rating
53
Page 54
Siemens Type VBII Safety Switch
Suggested Specifications
A. GENERAL
1. TYPE
1.1. Switches shall be furnished as shown on the drawings and shall be of the type described and specified herein.
2. STANDARDS Switches shall comply with the following standards:
2.1 UL 98—Enclosed and Dead Front Switches
2.2 NEMA KS 1—Enclosed Switches
3. SUBMITTAL
3.1 Provide outline drawings with dimensions, conduit entry / exit locations, cable terminal sizes and equipment ratings for voltage, amperage, horsepower and short-circuit. They also must include replacement parts and accessories
B. PRODUCT REQUIREMENTS
1. Switch Mechanism/Handle
1.1 Switch operating mechanism shall be nonteasible, positive, quick-make, quick-break such that during normal operation of the switch, the operation of the contacts shall not be capable of being restrained by the operating handle after the closing or opening action of the contacts has started.
1.7 All Heavy Duty switches (Type 1, 3R, 4/4X stainless steel, 4X non-metallic, 12) shall have a dual-cover interlock mechanism to prevent unintentional opening of the switch cover when the switch is ON and prevent turning the switch ON when the cover is open. The cover interlock mechanism shall have an externally operated override but the override shall not permanently disable the interlock mechanism. The tool used to override the cover interlock mechanism shall not be required to enter the enclosure in order to override the interlock.
1.8 30-200A 4X stainless steel switches shall have stainless steel interior parts as standard.
1.9 All switches shall have provisions to accept up to three 5/16 inches hasp padlocks to lock the operating handle in the OFF position.
2. SWITCH INTERIOR
2.1 All switches shall have switch blades that are visible when the switch is OFF and the cover is open. (Type 1, 3R, 4/4X stainless steel, 4X non-metallic, 12).
2.2 Lugs shall be front removable and UL-listed for 60°C or 75°C conductors (30-100A), 75°C conductors (200­1200A) aluminum or copper conductors. Except for 30A General Duty line and load lugs shall be removable with no need to remove line shields and arc suppressors.
2.3 30-100A Heavy Duty switches shall be capable of accepting field installed fuse puller kits.
1.2 The operating handle shall be an integral part of the box and not of the cover.
1.3 The handle position, combined with large ON and OFF lettering on the nameplate, shall clearly indicate the switch position.
1.4 The operating handle must be made of steel, with no plastic parts other than the handle grip.
1.5 The operating handle shall be provided with a highly visible red plastic grip and must allow for hook stick operation.
1.6 The operating mechanism must be made of steel, with no plastic parts.
54
2.4 Optional copper body and crimp type lugs are to be UL approved for field installation in Heavy Duty 30-1200A ratings.
2.5 Heavy Duty Switches all shall have all-copper current carrying parts other than standard aluminum alloy lugs.
2.6 All current-carrying parts shall be plated to resist corrosion.
2.7 Heavy Duty switches shall have provisions for field installable auxiliary switches. There also must be low current PLC type auxiliary interlock available for 30-200A switches.
2.8 All Heavy Duty switches shall have spring reinforced fuse clips.
Page 55
Siemens Type VBII Safety Switch
Suggested Specifications Continued
3. SWITCH ENCLOSURES
3.1 Switch covers shall be attached with pin-type hinges. Except for outdoor General Duty 30A switches, top-hinged doors are not acceptable.
3.2 Enclosures for Type 3R switches through 200A shall have provisions for interchangeable bolt-on hubs in the top endwall. Hubs shall be Siemens Type HS or HA hubs sized as indicated on the plans.
3.3 Switches shall have wire-bending space and lug capacity for one size larger Al/Cu wire than NEC and UL minimum requirements.
3.4 The enclosure shall be finished with [gray baked polyester paint which is electrodeposited on cleaned, phosphate pre­treated steel (Type 1)], [gray baked polyester paint which is electrodeposited on cleaned, phosphate pre-treated galvanized steel (Type 3R & 12)], [a brush finish on type 304 stainless steel (Type 4/4X stainless steel)].
3.5 All Heavy Duty switch enclosures shall have a formed front flange to provide additional strength and rigidity.
3.6 Tangential knockouts shall be provided for switches rated 30-600A in Type 1 and 3R enclosures where permitted.
3.7 Cover latching means for Type 4/4X & 12 rated through 1200A shall be quick-release, lift-lever type.
4. SWITCH RATINGS
4.1 All switches shall be UL-listed.
4.2 30-200A Heavy Duty switches shall also be horsepower rated for AC and/or DC as indicated on the plans.
4.3 Switches shall be horsepower rated for design E motors on internal labeling.
4.4 The Heavy Duty switch UL-listed short-circuit current rating shall be: [10,000 RMS symmetrical amperes when used with orprotected by Class H or K fuses (30-600 amperes)] [200,000 RMS symmetrical amperes when used with or protected by Class R or Class J fuses (30-600 ampere switches employing appropriate fuse rejection schemes)]. [200,000 RMS symmetrical amperes when used with or protected by Class L fuses (800-1200 amperes)].
4.5 All switches intended for service entrance shall be UL approved for this application.
4.6 All Heavy Duty switches shall be I2t rated.
C. APPROVED MANUFACTURERS
1.1 Switches shall be manufactured by Siemens (no equal) or approved equal.
3.8 Type 12 enclosures shall be dual rated as Type 3S to allow their use in outdoor applications.
3.9 Cover viewing window shall be an available option on 30­400A NEMA 12 and 4/4X stainless steel switches. The window must allow viewing of both visible blades when the switch is OFF and viewing of indicating fuses in 30-200A ratings.
3.10 All Heavy Duty switches shall have metal nameplates, except for non-metallic switches, which must have plastic nameplates.
55
Page 56
Type VBII Safety Switch Catalog Numbering System
H F 3 6 4 N R CU
Switch Type
L = General Duty
10k AIC Max. (Plug Fused & 60A Max Non-Fused)
G = General Duty H = Heavy Duty DT = Double Throw DTG = General Duty DT
Fused or Non-Fused
F = Fused NF = Non-Fused
Number of Poles
1 =1 2 =2 3 =3 4 =4 6 =6
Voltage
1 = 120V or 120/240V 2 = 240V 6 = 600V
Special Applications With:
CH = Crouse Hines Receptacle CJ = Factory J Fuse Spacings CR = Class R Clips Installed CU = Factory Installed Copper
Wire Grips
G = Factory Installed Ground Bar H = Height or Size Reduced L = Oversized Enclosure PN = Pyle National Receptacle W = Viewing Window
Enclosure Type
Omit = Type 1, Indoor R = Type 3R, Outdoor S = Type 4/4X, Stainless Steel J = Type 12, Industrial X = Type 4/4X, Non-metallic XL = Type 4/4X, Non-metallic less lugs
With or Without Neutral
Omit = Less Neutral N = With Neutral
Amperes
1 = 30A 2 = 60A 3 = 100A 4 = 200A
5 = 400A 6 = 600A 7 = 800A 8 = 1200A
Accessories Catalog Numbering System
Switch Type
H = Heavy Duty G = General Duty
Accessory Type
A1 = Auxiliary Switch 1/NO & 1/NC A2 = Auxiliary Switch 2/NO & 2/NC A3 = Auxiliary Switch Low Current CL = Compression Lug Barrier/
Mounting Kit
G = Ground Lug Kit G2 = Insulated Ground Lug Kit
Siemens Energy & Automation, Inc.
3333 Old Milton Parkway Alpharetta, GA 30005
1-800-964-4114
www.sea.siemens.com/power
LC = Copper Lug Kit N = Neutral N2 = 200% Neutral P = Fuse Puller Kit R = Class R - Fuse Clip Kit T = Class T - Fuse Kit
H N 6 4
Amperes
1 = 30A 2 = 60A 12 = 30/60A 3 = 100A 23 = 60/100A 123 = 30/60/100A 1234 = 30/60/100/200A
Maximum Voltage
2 = 240V Max 6 = 600V Max
4 = 200A 5 = 400A 56 = 400/600A 5678 = 400/600/
800/1200A
6 = 600A 78 = 800/1200A
© 2006 Siemens Energy & Automation, Inc. All Rights Reserved