Siemens Siprotec 5 7SS85 Techical Data

SIPROTEC 5 V7.30 and higher Low-Impedance Busbar Protection 7SS85
Technical Data
Extract from manual C53000-G5040-C019-6, chapter 11
Energy Automation
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
This document has been subjected to rigorous technical review before being published. It is revised at regular inter­vals, and any modifications and amendments are included in the subsequent issues. The content of this document has been compiled for information purposes only. Although Siemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects and damage which result through use of the information contained herein.
This content does not form part of a contract or of business relations; nor does it change these. All obligations of Siemens AG are stated in the relevant contractual agree­ments.
Siemens AG reserves the right to revise this document from time to time.
Document version: C53000-G5040-C019-6.01 Edition: 06.2016 Version of the product described: V07.30
Copyright
Copyright © Siemens AG 2016. All rights reserved. The disclosure, duplication, distribution and editing of this
document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights created by patent grant or registration of a utility model or a design, are reserved.
Registered Trademarks
SIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM® are registered trademarks of Siemens AG. Any unauthorized use is illegal. All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner.
Preface
Purpose of the Manual
This manual describes the protection, automation, control, and monitoring functions of the SIPROTEC 5 devices.
Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main­tenance of automation, selective protection and control equipment, and operational crew in electrical installa­tions and power plants.
Scope
This manual applies to the SIPROTEC 5 device family.
Further Documentation
[dwprefdm-221012-01.tif, 3, en_US]
Device manuals Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.
Hardware manual The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.
Operating manual The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
3
C53000-G5040-C019-6, Edition 06.2016
Communication protocol manual The Communication protocol manual contains a description of the protocols for communication within
the SIPROTEC 5 device family and to higher-level network control centers.
Product information The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is provided with each SIPROTEC 5 device.
Engineering Guide The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the functionality of the SIPROTEC 5 device.
DIGSI 5 online help The DIGSI 5 online help contains a help package for DIGSI 5 and CFC. The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-
ples and editors. The help package for CFC includes an introduction to CFC programming, basic examples of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5 range.
SIPROTEC 5/DIGSI 5 Tutorial The tutorial on the DVD contains brief information about important product features, more detailed infor-
mation about the individual technical areas, as well as operating sequences with tasks based on practical operation and a brief explanation.
SIPROTEC 5 catalog The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.
Selection guide for SIPROTEC and Reyrolle The selection guide offers an overview of the device series of the Siemens protection devices, and a
device selection table.
Indication of Conformity
This product complies with the directive of the Council of the European Communities on harmonization of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low Voltage Directive 2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive in accordance with the product standard EN 60255-26 (for EMC directive) and with the product standard EN 60255-27 (for Low Voltage Directive) by Siemens AG.
The device is designed and manufactured for application in an industrial environment. The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.
Other Standards
IEEE Std C 37.90 The technical data of the product is approved in accordance with UL. For more information about the UL database, see www.ul.com Select Online Certifications Directory and enter E194016 as UL File Number.
IND. CONT. EQ.
69CA
[ul_listed_c_us, 1, --_--]
Preface
4 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000 Fax: +49 (180) 524-2471 E-Mail: support.energy@siemens.com
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG Siemens Power Academy TD
Humboldtstraße 59 90459 Nürnberg Germany
Phone: +49 (911) 433-7415 Fax: +49 (911) 433-7929 E-Mail: poweracademy@siemens.com Internet: www.siemens.com/poweracademy
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module or device). However, it comprises important information that must be followed for personal safety, as well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger:
!
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
²
Comply with all instructions, in order to avoid death or severe injuries.
!
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
²
Comply with all instructions, in order to avoid death or severe injuries.
!
CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
²
Comply with all instructions, in order to avoid moderate or minor injuries.
Preface
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 5 C53000-G5040-C019-6, Edition 06.2016
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
²
Comply with all instructions, in order to avoid property damage.
NOTE
Important information about the product, product handling or a certain section of the documentation which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
Proper storage, setup and installation
Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper action is not taken, death, severe injury or property damage can result:
The equipment must be grounded at the grounding terminal before any connections are made.
All circuit components connected to the power supply may be subject to dangerous voltage.
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected (capacitors can still be charged).
Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the equipment, ensure that the current-transformer circuits are short-circuited.
The limiting values stated in the document must not be exceeded. This must also be considered during testing and commissioning.
Preface
6 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Open Source Software
The product contains, among other things, Open Source Software developed by third parties. The Open Source Software used in the product and the license agreements concerning this software can be found in the Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the event of conflicts between Siemens license conditions and the Open Source Software license conditions, the Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft­ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects resulting from modifications to the Open Source Software by you or third parties is excluded. We do not provide any technical support for the Product if it has been modified.
When using DIGSI 5 in online mode, you are provided with the option to go to the main menu Show Open source information and read and display the Readme_OSS file containing the original license text and copy­right information.
To do this, the following steps are necessary:
Switch to online mode.
Select the device.
Select online in the menu bar.
Click Show Open source information.
NOTE
To read the Readme_OSS file, a PDF viewer must be installed on the computer. In order to operate SIPROTEC 5 devices, a valid DIGSI 5 license is required.
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
7
C53000-G5040-C019-6, Edition 06.2016
8 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Technical Data
11.1 General Device Data 555
11.2 Date and Time Synchronization 563
11.3 Busbar Differential Protection 564
11.4 Circuit-Breaker Failure Protection 1-Pole/3-Pole 565
11.5 Circuit-Breaker Failure Protection 3-Pole 567
11.6 Inherent Circuit-Breaker Failure Protection 569
11.7 End-Fault Protection 570
11.8 External Tripping Busbar Section (Direct) 571
11.9 External Tripping Busbar Section (from Bay) 572
11.10 Bus Coupler Differential Protection 573
11.11 Differential Current Supervision 574
11.12 Zero-Crossing Supervision 575
11.13 Disconnector Supervision 576
11.14 Circuit-Breaker Supervision 577
11.15 Stage with Definite-Time Characteristic Curve 578
11.16 Stage with Inverse-Time Characteristic Curve 580
11.17 Stage with Definite-Time Characteristic Curve 588
11.18 Stage with Inverse-Time Characteristic Curve 590
11.19 Overvoltage Protection with 3-Phase Voltage 598
11.20 Overvoltage Protection with Positive-Sequence Voltage 600
11.21 Overvoltage Protection with Negative-Sequence Voltage 601
11.22 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage 602
11.23 Overvoltage Protection with Any Voltage 603
11.24 Undervoltage Protection with 3-Phase Voltage 604
11.25 Undervoltage Protection with Positive-Sequence Voltage 606
11.26 Undervoltage Protection with Any Voltage 607
11.27 Overfrequency Protection 608
11.28 Underfrequency Protection 609
11.29 Rate of Frequency Change Protection 610
11.30 Inrush-Current Detection 611
11.31 Voltage-Jump Detection 612
11.32 Trip-Circuit Supervision 613
11.33 Analog Channel Supervision via Fast Current Sum 614
11.34 Operational Measured Values and Statistical Values 615
11
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 553 C53000-G5040-C019-6, Edition 06.2016
11.35 Analog-Units Function Group 617
11.36 Temperature Supervision 618
11.37 Protection Interface and Protection Topology 619
11.38 CFC 621
Technical Data
554 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
General Device Data
Analog Inputs
Current Inputs
All current, voltage, and power data are specified as RMS values. Rated frequency f
rated
50 Hz, 60 Hz
Protection-class current trans­formers
Rated current I
rated
Measuring range
5 A 1 A
0 A to 500 A 0 A to 100 A
Power consumption per current circuit at rated current
Approx. 0.1 VA
Thermal rating (protection-class current trans-
formers)
500 A for 1 s 150 A for 10 s 20 A continuously 25 A for 3 min 30 A for 2 min
Dynamic load-carrying capacity 1250 A one half wave
Voltage Input
All current, voltage, and power data are specified as RMS values. Rated frequency f
rated
50 Hz, 60 Hz
Input and output modules IO202/IO208/IO211/IO214 IO215 Measuring range 0 V to 200 V 0 V to 7.07 V Input impedance < 0.1 VA < 0.01 VA Thermal rating 230 V continuously 20 V continuously
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Connector type
8-pin multiple contact strip Differential current input channels 4 Measuring range DC -24 mA to +24 mA Fault < 0.5 % of measuring range Input impedance 140 Ω Conversion principle Delta-sigma (16 bit) Permissible potential difference
between channels
DC 20 V
Galvanic separation from ground/ housing
DC 700 V
Permissible overload DC 100 mA continuously Measurement repetition 200 ms
Measuring-Transducer Inputs (via Module ARC-CD-3FO)
Connector type
AVAGO AFBR-4526Z Number of transceivers 3 Fiber type Polymer Optical Fiber (POF) 1 mm
Receiver
Maximum -10 dBm ± 2 dBm
11.1
11.1.1
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 555 C53000-G5040-C019-6, Edition 06.2016
Minimum -40 dBm ± 2 dBm Spectrum 400 nm to 1100 nm Attenuation In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m Additional attenuation comes from the plug and sensor head.
Optical budget
1
Minimal 25 dB Analog sampling rate 16 kHz ADC type 10-bit successive approximation
Transmitter
Type LED Wavelength λ = 650 nm Transmit power Minimum 0 dBm
Maximum 2 dBm Numerical aperture
0.5
2
Signal rate connection test 1 pulse per second Pulse duration connection test 11 μs Comment:
1
All values in combination with sensors approved by Siemens.
2
Numerical aperture (NA = sin θ (launch angle))
High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212)
NOTE
Current and voltage may not be connected to a measuring-transducer input at the same time; only either current or voltage may be connected. Due to EMC, no line may be connected to an input that is not used (current or voltage).
Use shielded cables.
Table 11-1 High-Speed Measuring-Transducer Inputs, Voltage
Differential voltage input channels
8
9
Measuring range DC -10 V to +10 V Fault < 0.5 % of the measuring range Input impedance
48 kΩ Conversion principle Delta-sigma (16 bit) Permissible potential difference
between channels
DC 3.5 kV
Galvanic separation from ground/ housing
DC 3.5 kV
Permissible overload DC 20 V continuously
DC 60 V continuously (IO210 MT3 terminal point C9) Measurement repetition 62.5 μs
Table 11-2 High-Speed Measuring-Transducer Inputs, Current
Differential current input channels
8
10
Measuring range DC -20 mA to +20 mA Fault < 0.5 % of the measuring range Input impedance, current
12 Ω
9
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as a current input.
10
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as a current input.
Technical Data
11.1 General Device Data
556 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Conversion principle Delta-sigma (16 bit) Permissible potential difference
between channels
DC 3.5 kV
Galvanic separation from ground/ housing
DC 3.5 kV
Permissible current overload DC 100 mA continuously Measurement repetition 62.5 μs
Supply Voltage
Integrated Power Supply
For modular devices, the following printed circuit-board assemblies have a power supply: PS201 – Power supply of the base module and of the 1st device row PS203 – Voltage supply of 2nd device row CB202 – Plug in module assembly with integrated power supply, for example, to accommodate communica-
tion modules Permissible voltage
ranges (PS201, PS203, CB202)
DC 19 V to DC 60 V DC 48 V to DC 300 V
AC 80 V to AC 265 V, 50 Hz/60 Hz
Auxiliary rated voltage V
H
(PS201, PS203, CB202)
DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/DC 220 V/
DC 250 V or AC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz
Permissible voltage ranges (PS101)
DC 19 V to DC 60 V DC 48 V to 150 V DC 88 V to DC 300 V
AC 80 V to AC 265 V, 50 Hz/60 Hz
Auxiliary rated voltage V
H
(PS101)
DC 24 V/DC 48 V DC 60 V/DC 110 V/
DC 125 V
DC 110 V/ DC 125 V/ DC 220 V/DC 250 V or AC 100 V/AC 115 V/ AC 230 V, 50 Hz/60 Hz
Superimposed alternating voltage, peak-to-peak, IEC 60255-11
≤ 15% of the DC auxiliary rated voltage (applies only
to direct voltage) Inrush current ≤ 18 A Recommended external protection Miniature circuit breaker 6 A, characteristic C
according to IEC 60898
Internal fuse
DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101 4 A intert, AC 250 V,
DC 150 V, UL recognized SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
DC AC 230 V/50 Hz AC 115 V/50 Hz 1/3 base module, non-
modular Without plug-in modules
7.0 W 16 VA 12.5 VA
11.1.2
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 557 C53000-G5040-C019-6, Edition 06.2016
Integrated Power Supply
1/3 base module, modular Without plug-in modules
13 W 33 VA 24 VA
1/6 expansion module 3 W 6 VA 6 VA 1/6 plug-in module
assembly without plug-in modules (modules CB202)
3.5 W 14 VA 7 VA
Plug-in module for base module or plug-in module assembly (for example, communication module)
< 5 W < 6 VA < 6 VA
Stored-energy time for auxiliary voltage outage or short circuit, modular devices
For V ≥ DC 24 V ≥ 50 ms For V ≥ DC 110 V ≥ 50 ms For V ≥ AC 115 V ≥ 50 ms
Stored-energy time for auxiliary voltage outage or short circuit, non-modular devices
For V ≥ DC 24 V ≥ 20 ms For V ≥ DC 60 V/DC 110 V ≥ 50 ms For V ≥ AC 115 V ≥ 200 ms
Binary Inputs
Rated voltage range DC 24 V to 250 V
The binary inputs of SIPROTEC 5 are bipolar with the exception of the
binary inputs on the IO230 and on the IO231. Current consumption, excited Approx. DC 0.6 mA to 1.8 mA (independent of the operating voltage) Power consumption, max. 0.6 VA Pickup time Approx. 3 ms Dropout time Approx. 4 ms Switching thresholds Adjustable with DIGSI 5
Range 1 for 24 V, 48 V, and 60 V
Operating voltage
V
low
≤ DC 10 V
V
high
≥ DC 19 V
Range 2 for 110 V and 125 V
Operating voltage
V
low
≤ DC 44 V
V
high
≥ DC 88 V
Range 3 for 220 V and 250 V
Operating voltage
V
low
≤ DC 88 V
V
high
≥ DC 176 V
Maximum permitted voltage DC 300 V The binary inputs contain interference suppression capacitors. In order to ensure EMC, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.
Relay Outputs
Standard Relay (Type S)
Switching capacity
On: 1000 W/VA Off: 30 VA; 40 W ohmic;
30 W/VA at L/R ≤ 40 ms AC and DC contact voltage 250 V Permissible current per contact (continuous) 5 A Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
11.1.3
11.1.4
Technical Data
11.1 General Device Data
558 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Short-time current across closed contact 250 A for 30 ms Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time) Additional delay of the output medium used
≤ 10 ms, typically 8 ms
Max. rated data of the output contacts in accordance with UL certification
DC 24 V, 8 A, General Purpose DC 48 V, 0.8 A, General Purpose DC 240 V, 0.1 A, General Purpose AC 240 V, 5 A, General Purpose AC 120 V, 1/3 hp AC 250 V, 1/2 hp B300 R300
Interference suppression capacitors across the contacts
4.7 nF, ± 20 %, AC 250 V
Fast Relay (Type F)
Switching capacity On: 1000 W/VA
Off: 30 VA; 40 W ohmic;
30 W/VA at L/R ≤ 40 ms AC and DC contact voltage 250 V Permissible current per contact (continuous) 5 A Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time) Additional delay of the output medium used
Closing time, typical: 4 ms
Opening time, typical: 2 ms
≤ 5 ms Rated data of the output contacts in accordance with
UL certification
AC 120 V, 8.5 A, General Purpose
AC 277 V, 6 A, General Purpose
AC 277 V, 0.7 hp
AC 347 V, 4.5 A, General Purpose
B300
R300 Interference suppression capacitors across the
contacts
4.7 nF, ± 20 %, AC 250 V
Supervision 2-channel activation with cyclic testing (only for make
contact)
High-Speed Relay with Semiconductor Acceleration (Type HS)
Switching capacity
On/Off: 1000 W/VA Contact voltage AC 200 V, DC 250 V Permissible current per contact (continuous) 5 A Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 559 C53000-G5040-C019-6, Edition 06.2016
Total permissible current for contacts connected to common potential
5 A
Switching time OOT (Output Operating Time) Additional delay of the output medium used
Closing time, typical: 0.2 ms Opening time, typical: 6 ms Maximum: ≤ 9 ms
Rated data of the output contacts in accordance with UL certification
B150 Q300
Design Data
Masses
Device Size Weight of the Modular Devices
Type of construction 1/3 1/2 2/3 5/6 1/1 Flush-mounting device 4.8 kg 8.1 kg 11.4 kg 14.7 kg 18.0 kg Surface-mounted device with inte-
grated on-site operation panel
7.8 kg 12.6 kg 17.4 kg 22.2 kg 27.0 kg
Surface-mounted device with detached on-site operation panel
5.1 kg 8.7 kg 12.3 kg 15.9 kg 19.5 kg
Size Weight
Detached on-site operation panel 1/3 1.9 kg Detached on-site operation panel 1/6 1.1 kg
Dimensions of the Basic and 1/3 Modules
Type of Construction (Maximum Dimensions)
Width over all x Height over all x Depth 11(in Inches)
Flush-mounting device 150 mm x 268 mm x 229 mm (5.91 x 10.55 x 9.02) Surface-mounted device with integrated on-site oper-
ation panel
150 mm x 314 mm x 337 mm (5.91 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera­tion panel
150 mm x 314 mm x 230 mm (5.91 x 12.36 x 9.06)
Dimensions of Device Rows
Type of Construction
(Maximum Dimensions)
Width over all x Height over all x Depth 12(in Inches)
Type of construc­tion
1/3 1/2 2/3 5/6 1/1
Flush-mounting device
150 mm x 268 mm x 229 mm (5.91 x
10.55 x 9.02)
225 mm x 268 mm x 229 mm (8.86 x
10.55 x 9.02)
300 mm x 268 mm x 229 mm(11.81 x
10.55 x 9.02)
375 mm x 268 mm x 229 mm (14.76 x 10.55 x 9.02)
450 mm x 268 mm x 229 mm (17.72 x 10.55 x 9.02)
11.1.5
11
Width and depth rounded to whole numbers in mm
12
Width and depth rounded to whole numbers in mm
Technical Data
11.1 General Device Data
560 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Type of Construction
(Maximum Dimensions)
Width over all x Height over all x Depth 12(in Inches)
Surface­mounted device with integrated on-site operation panel
150 mm x 314 mm x 337 mm (5.91 x
12.36 x 13.27)
225 mm x 314 mm x 337 mm (8.86 x
12.36 x 13.27)
300 mm x
314 mm x
337 mm (11.81
x 12.36 x 13.27)
375 mm x 314 mm x 337 mm (14.76 x 12.36 x 13.27)
450 mm x 314 mm x 337 mm (17.72 x 12.36 x 13.27)
Surface­mounted device with detached on-site operation panel
150 mm x 314 mm x 230 mm (5.91 x
12.36 x 9.06)
225 mm x 314 mm x 230 mm (8.86 x
12.36 x 9.06)
300 mm x
314 mm x
230 mm (11.81
x 12.36 x 9.06)
375 mm x 314 mm x 230 mm (14.76 x 12.36 x 9.06)
450 mm x 314 mm x 230 mm (17.72 x 12.36 x 9.06)
Expansion Module Dimensions
Type of Construction (Maximum Dimensions)
Width x Height x Depth 13 (in Inches)
Flush-mounting device 75 mm x 268 mm x 229 mm (2.95 x 10.55 x 9.02) Surface-mounted device with integrated on-site oper-
ation panel
75 mm x 314 mm x 337 mm (2.95 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera­tion panel
75 mm x 314 mm x 230 mm (2.95 x 12.36 x 9.06)
Plug-In Module Dimensions
Type of Construction (Maximum Dimensions)
Width x Height x Depth (in Inches)
USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 120.5 mm (2.4 x 1.77 x 4.74) USART-Ax-xFO, ETH-Bx-xFO (without protection
cover)
61 mm x 45 mm x 132.5 mm (2.4 x 1.77 x 5.22)
ANAI-CA-4EL 61 mm x 45 mm x 119.5 mm (2.4 x 1.77 x 4.7) ARC-CD-3FO 61 mm x 45 mm x 120.5 mm (2.4 x 1.77 x 4.74)
Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module
Fiber-optic cable
R = 50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations. D-Sub cable R = 50 mm (minimum bending radius)
Degree of Protection to IEC 60529
For equipment in the surface-mounting housing
IP50 For equipment in the flush-mounting housing Front IP51
Back side of the modular devices IP50
Back side of the non-modular devices IP40 For operator protection IP2x for current terminal (installed removed)
IP1x for voltage terminal (removed/without cover)
IP2x for voltage terminal (removed/with cover)
IP2x for voltage terminal (installed) Degree of pollution, IEC 60255-27 2
12
Width and depth rounded to whole numbers in mm
13
Width and depth rounded to whole numbers in mm
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 561 C53000-G5040-C019-6, Edition 06.2016
Maximum altitude above sea level 2000 m (6561.68 ft)
UL Note
Type 1 if mounted into a door or front cover of an enclosure. When expanding the device with the 2nd device row, then they must be mounted completely inside an
enclosure.
Tightening Torques for Terminal Screws
Type of Line Current Terminal Voltage Terminal with
Spring-Loaded Terminals
Voltage Terminal with Screw Connection
Litz wire with ring-type lug
2.7 Nm No ring-type lug No ring-type lug
Stranded wires with boot­lace ferrules or pin-type lugs
2.7 Nm 1.0 Nm 0.6 Nm
Solid conductor, bare (2 mm2)
2.0 Nm 1.0 Nm
NOTE
Use copper cables only.
Torques for Other Screw Types
Screw Type
Torque
M4 x 20 1.2 Nm M4 x 8 1.2 Nm M2.5 x 6 0.39 Nm Countersunk screw, M2.5 x 6 0.39 Nm Countersunk screw, M2.5 x 8 0.39 Nm Collar screw, M4 x 20 0.7 Nm
Technical Data
11.1 General Device Data
562 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Date and Time Synchronization
Date format DD.MM.YYYY (Europe)
MM/DD/YYYY (USA)
YYYY-MM-DD (China) Time source 1, time source 2 None
IRIG-B 002(003)
IRIG-B 006(007)
IRIG-B 005(004) with extension according to
IEEE C37.118-2005
DCF77
PI (protection interface)
14
SNTP
IEC 60870-5-103
DNP3
IEEE 1588 Time zone 1, time zone 2 Local
UTC Failure indication after 0 s to 3600 s Time zone and daylight saving time Transfer of PC settings
Manually setting the time zones Time zone offset with respect to GMT -720 min to 840 min Switching over to daylight saving time Active
Inactive Beginning of daylight saving time Input: day and time End of daylight saving time Input: day and time Offset daylight saving time -120 to 120 [steps of 15]
11.2
14
If provided
Technical Data
11.2 Date and Time Synchronization
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 563 C53000-G5040-C019-6, Edition 06.2016
Busbar Differential Protection
General Differential Protection Setting Values
Rated object current I
rated obj.
100 A to 50 000 A Increments of 1
Check Zone Setting Values
Threshold value I
diff
0.20 to 4.00 Increments of 0.01
Threshold value I
diff
(sensitive characteristic curve) 0.05 to 4.00 Increments of 0.01
Threshold value I
rest
(sensitive characteristic curve) 0.00 to 25.00 Increments of 0.01
Threshold value I
rest
(sensitive characteristic curve/
CBFP)
0.00 to 25.00 Increments of 0.01
Stabilization factor k 0.10 to 0.80 Increments of 0.01
General Busbar Section Setting Values
Threshold value I
diff
0.20 to 4.00 Increments of 0.01
Threshold value I
diff
(sensitive characteristic curve) 0.05 to 4.00 Increments of 0.01
Threshold value I
rest
(sensitive characteristic curve) 0.00 to 25.00 Increments of 0.01
Threshold value I
rest
(sensitive characteristic curve/
CBFP)
0.00 to 25.00 Increments of 0.01
Stabilization factor k 0.10 to 0.80 Increments of 0.01
Setting Values for Differential Current Supervision
Limiting value of current I/I
rated, obj
(I
rated, obj
= Rated object current)
0.05 to 0.80 Increments of 0.01
Time delay for check zone and busbar-selective protection
1.00 s to 10.00 s Increments of 0.01
Setting Values for Cross-Stabilization
Restraint current ratio, selective zones
0.00 to 1.00 Increments of 0.01
Restraint current ratio, check zone 0.00 to 1.00 Increments of 0.01
Operate Time
Minimum operate time
High-speed relay (type HS) approx. 3 ms Fast relay (type F) approx. 7 ms
Frequency
Frequency range
50 Hz or 60 Hz
Tolerances
Current
5 % of the setting value or 50 mA k factor 5 % of the setting value Times 5 % of the setting value or 50 ms Frequency - 10 %, + 5 %
11.3
Technical Data
11.3 Busbar Differential Protection
564 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Circuit-Breaker Failure Protection 1-Pole/3-Pole
Starting Conditions
For circuit-breaker failure protection
1-pole tripping internal or external
15
3-pole tripping internal or external
16
Setting Values
Phase-current threshold values
1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A 5 A @ 100 Irated 0.150 A to 175.000 A Increments of 0.010 A
Threshold value sensitive 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 100 Irated 0.150 A to 175.000 A Increments of 0.010 A Supervision time of release signal 0.06 s to 1.00 s Increments of 0.01 s Time delays 0.05 s to 60.00 s Increments of 0.001 s Supervision time of binary inputs 0.05 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur­rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Circuit-Breaker Supervision
Supervision of circuit-breaker auxiliary-contact position For 3-pole CB tripping 1 input each for make contact and break contact For 1-pole CB tripping 1 input each for auxiliary contact per pole or
1 input for each series connection make contact and break contact
NOTE
The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated. Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
Pickup time, in the case of an internal start Pickup time, in the case of an external start
< 1 ms
< 5 ms Dropout time for Unbalancing operating mode Approx. 2 ms Typical dropout time < 15 ms
11.4
15
Via binary inputs
16
Via binary inputs
Technical Data
11.4 Circuit-Breaker Failure Protection 1-Pole/3-Pole
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 565 C53000-G5040-C019-6, Edition 06.2016
Dropout time, via circuit-breaker auxiliary-contact criterion
< 5 ms
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz f > 80 Hz
Active
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current Times 1 % of the setting value or 10 ms
Technical Data
11.4 Circuit-Breaker Failure Protection 1-Pole/3-Pole
566 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Circuit-Breaker Failure Protection 3-Pole
Starting Conditions
For circuit-breaker failure protection
3-pole tripping internal or external
17
Setting Values
Phase-current threshold values
1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A 5 A @ 100 Irated 0.150 A to 175.000 A Increments of 0.01 A
Sensitive threshold value 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 100 Irated 0.150 A to 175.000 A Increments of 0.01 A Supervision time of release signal 0.06 s to 1.00 s Increments of 0.01 s Time delays 0.05 s to 60.00 s Increments of 0.001 s Supervision time of binary inputs 0.05 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur­rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Circuit-Breaker Supervision
Position supervision via circuit-breaker auxiliary contacts For 3-pole CB tripping 1 input each for make contact and break contact
NOTE
The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated. Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
Pickup time, in the case of an internal start Pickup time, in the case of an external start
< 1 ms
< 5 ms Dropout time for unbalancing operating mode Approx. 2 ms Typical dropout time < 15 ms Dropout time via circuit-breaker auxiliary-contact
criterion
< 5 ms
11.5
17
Via binary inputs
Technical Data
11.5 Circuit-Breaker Failure Protection 3-Pole
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 567 C53000-G5040-C019-6, Edition 06.2016
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz f > 80 Hz
Active
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current Times 1 % of the setting value or 10 ms
Technical Data
11.5 Circuit-Breaker Failure Protection 3-Pole
568 SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Loading...
+ 56 hidden pages