Siemens SIPROTEC 4,SIPROTEC 7RW80 User Manual

Preface
Table of Contents
SIPROTEC 4 Voltage and Frequency
Protection 7RW80
V4.6
Manual
Functions
Mounting and Commissioning
Technical Data
Ordering Information and Accessories
Terminal Assignments
Connection Examples Default Settings and Protocol-dependent
Functions
Functions, Settings, Information
1 2 3 4
A
B
C
D
E
C53000-G1140-C233-4
Literature
Glossary
Index
i
i
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
We have checked the contents of this manual against the hardware and software described. However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any errors or omissions contained in the information given.
The information given in this document is reviewed regu­larly and any necessary corrections will be included in subsequent editions. We appreciate any suggested improvements.
We reserve the right to make technical improvements without notice.
Document version V04.03.00 Release date 07.2018
Copyright
Copyright © Siemens AG 2018. All rights reserved. Dissemination or reproduction of this document, or evalua-
tion and communication of its contents, is not authorized except where expressly permitted. Violations are liable for damages. All rights reserved, particularly for the purposes of patent application or trademark registration.
Registered Trademarks
SIPROTEC, SINAUT, SICAM and DIGSI are registered trade­marks of Siemens AG. Other designations in this manual might be trademarks whose use by third parties for their own purposes would infringe the rights of the owner.

Preface

Purpose of the Manual
This manual describes the functions, operation, installation, and commissioning of devices 7RW80. In partic­ular, one will find:
Information regarding the configuration of the scope of the device and a description of the device func-
tions and settings → Chapter 2;
Instructions for Installation and Commissioning → Chapter 3;
Compilation of the Technical Data → Chapter 4;
As well as a compilation of the most significant data for advanced users → Appendix.
General information with regard to design, configuration, and operation of SIPROTEC 4 devices are set out in the SIPROTEC 4 System Description /1/ SIPROTEC 4 System Description.
Target Audience
Protection-system engineers, commissioning engineers, persons entrusted with the setting, testing and main­tenance of selective protection, automation and control equipment, and operating personnel in electrical installations and power plants.
Scope
This manual applies to: SIPROTEC 4 Voltage and Frequency Protection 7RW80; Firmware-Version V4.6.
Indication of Conformity
Additional Standards IEEE Std C37.90 (see Chapter 4 "Technical Data")
This product is UL-certified according to the Technical Data. file E194016
[ul-schutz-7sx80-100310, 1, --_--]
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage Directive 2006/95 EC).
This conformity is proved by tests conducted by Siemens AG in accordance with the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for EMC directive, and with the standard EN 60255-27 for the low-voltage directive.
The device has been designed and produced for industrial use. The product conforms with the international standards of the series IEC 60255 and the
German standard VDE 0435.
SIPROTEC 4, 7RW80, Manual C53000-G1140-C233-4, Edition 07.2018
3
!
!
!
Preface
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000 Fax: +49 (180) 524-2471 E-Mail: support.energy@siemens.com
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG Siemens Power Academy TD
Humboldtstraße 59 90459 Nürnberg Germany
Phone: +49 (911) 433-7415 Fax: +49 (911) 433-7929 E-Mail: poweracademy@siemens.com Internet: www.siemens.com/poweracademy
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module or device). However, it comprises important information that must be followed for personal safety, as well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger:
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
²
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
²
CAUTION
Comply with all instructions, in order to avoid death or severe injuries.
Comply with all instructions, in order to avoid death or severe injuries.
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
²
4 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
NOTICE
i
i
NOTICE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
²
NOTE
Important information about the product, product handling or a certain section of the documentation which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
Proper storage, setup and installation
Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper action is not taken, death, severe injury or property damage can result:
The equipment must be grounded at the grounding terminal before any connections are made.
All circuit components connected to the power supply may be subject to dangerous voltage.
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
Preface
Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
Typographic and Symbol Conventions
The following text formats are used when literal information from the device or to the device appear in the text flow:
Parameter Names
Designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are marked in bold letters in monospace type style. The same applies to titles of menus.
1234A
Parameter addresses have the same character style as parameter names. Parameter addresses contain the suffix A in the overview tables if the parameter can only be set in DIGSI via the option Display additional settings.
Parameter Options
Possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are additionally written in italics. The same applies to the options of the menus.
SIPROTEC 4, 7RW80, Manual 5 C53000-G1140-C233-4, Edition 07.2018
Preface
Indications
Designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks.
Deviations may be permitted in drawings and tables when the type of designator can be obviously derived from the illustration.
The following symbols are used in drawings:
Device-internal logical input signal
Device-internal logical output signal
Internal input signal of an analog quantity
External binary input signal with number (binary input, input indication) External binary output signal with number (example of a value indication)
External binary output signal with number (device indication) used as input signal
Example of a parameter switch designated FUNCTION with address 1234 and the possible settings ON and OFF
Besides these, graphical symbols are used in accordance with IEC 60617-12 and IEC 60617-13 or similar. Some of the most frequently used are listed below:
Analog input variable
AND-gate operation of input values
OR-gate operation of input values
Exclusive OR gate (antivalence): output is active, if only one of the inputs is active
Coincidence gate: output is active, if both inputs are active or inactive at the same time
Dynamic inputs (edge-triggered) above with positive, below with negative edge
Formation of one analog output signal from a number of analog input signals
Limit stage with setting address and parameter designator (name)
Timer (pickup delay T, example adjustable) with setting address and parameter designator (name)
6 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Timer (dropout delay T, example non-adjustable)
Dynamic triggered pulse timer T (monoflop)
Static memory (SR flipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q), setting input dominant
Static memory (RS-flipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q), resetting input dominant
Preface
SIPROTEC 4, 7RW80, Manual 7 C53000-G1140-C233-4, Edition 07.2018
8 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018

Table of Contents

Preface..........................................................................................................................................................3
1 Introduction................................................................................................................................................15
1.1 Overall Operation..............................................................................................................16
1.2 Application Scope............................................................................................................. 18
1.3 Characteristics.................................................................................................................. 20
2 Functions.................................................................................................................................................... 23
2.1 General.............................................................................................................................24
2.1.1 Functional Scope......................................................................................................... 24
2.1.1.1 Functional Description........................................................................................... 24
2.1.1.2 Setting Notes......................................................................................................... 24
2.1.1.3 Settings................................................................................................................. 25
2.1.2 Device, General Settings.............................................................................................. 26
2.1.2.1 Functional Description........................................................................................... 26
2.1.2.2 Setting Notes......................................................................................................... 27
2.1.2.3 Settings................................................................................................................. 27
2.1.2.4 Information List..................................................................................................... 27
2.1.3 Power System Data 1...................................................................................................28
2.1.3.1 Functional Description........................................................................................... 28
2.1.3.2 Setting Notes......................................................................................................... 29
2.1.3.3 Settings................................................................................................................. 31
2.1.3.4 Information List..................................................................................................... 32
2.1.4 Oscillographic Fault Records........................................................................................ 32
2.1.4.1 Functional Description........................................................................................... 32
2.1.4.2 Setting Notes......................................................................................................... 33
2.1.4.3 Settings................................................................................................................. 34
2.1.4.4 Information List..................................................................................................... 34
2.1.5 Settings Groups........................................................................................................... 34
2.1.5.1 Functional Description........................................................................................... 34
2.1.5.2 Setting Notes......................................................................................................... 34
2.1.5.3 Settings................................................................................................................. 35
2.1.5.4 Information List..................................................................................................... 35
2.1.6 Power System Data 2...................................................................................................35
2.1.6.1 Functional Description........................................................................................... 35
2.1.6.2 Setting Notes......................................................................................................... 35
2.1.6.3 Settings................................................................................................................. 35
2.1.6.4 Information List..................................................................................................... 35
2.1.7 EN100-Module............................................................................................................ 36
2.1.7.1 Functional Description........................................................................................... 36
2.1.7.2 Setting Notes......................................................................................................... 36
2.1.7.3 Information List..................................................................................................... 36
2.2 Voltage Protection 27, 59..................................................................................................37
2.2.1 Measurement Principle................................................................................................ 37
SIPROTEC 4, 7RW80, Manual 9 C53000-G1140-C233-4, Edition 07.2018
Table of Contents
2.2.2 Overvoltage Protection 59........................................................................................... 38
2.2.3 Undervoltage Protection 27......................................................................................... 39
2.2.4 Setting Notes...............................................................................................................41
2.2.5 Settings.......................................................................................................................44
2.2.6 Information List...........................................................................................................45
2.3 Frequency Protection 81 O/U.............................................................................................46
2.3.1 Functional Description.................................................................................................46
2.3.2 Setting Notes...............................................................................................................47
2.3.3 Settings.......................................................................................................................48
2.3.4 Information List...........................................................................................................49
2.4 Load Restoration............................................................................................................... 50
2.4.1 Functional Description.................................................................................................50
2.4.2 Setting Notes...............................................................................................................54
2.4.3 Settings.......................................................................................................................57
2.4.4 Information List...........................................................................................................60
2.5 Supervision Functions....................................................................................................... 61
2.5.1 Measurement Supervision........................................................................................... 61
2.5.1.1 General..................................................................................................................61
2.5.1.2 Hardware Monitoring ............................................................................................ 61
2.5.1.3 Software Monitoring ............................................................................................. 61
2.5.1.4 Monitoring of the Transformer Circuits................................................................... 62
2.5.1.5 Broken Wire Monitoring of Voltage Transformer Circuits......................................... 63
2.5.1.6 Setting Notes......................................................................................................... 64
2.5.1.7 Settings................................................................................................................. 64
2.5.1.8 Information List..................................................................................................... 65
2.5.2 Trip Circuit Supervision 74TC....................................................................................... 65
2.5.2.1 Functional Description........................................................................................... 65
2.5.2.2 Setting Notes......................................................................................................... 68
2.5.2.3 Settings................................................................................................................. 68
2.5.2.4 Information List..................................................................................................... 69
2.5.3 Malfunction Responses of the Monitoring Functions.................................................... 69
2.5.3.1 Functional Description........................................................................................... 69
2.6 Flexible Protection Functions.............................................................................................71
2.6.1 Functional Description.................................................................................................71
2.6.2 Setting Notes...............................................................................................................74
2.6.3 Settings.......................................................................................................................77
2.6.4 Information List...........................................................................................................78
2.7 Synchrocheck................................................................................................................... 80
2.7.1 Allgemeines................................................................................................................ 80
2.7.2 Functional Sequence................................................................................................... 81
2.7.3 De-energized Switching...............................................................................................82
2.7.4 Direct Command / Blocking..........................................................................................83
2.7.5 Interaction with Control and External Control...............................................................84
2.7.6 Setting Notes...............................................................................................................84
2.7.7 Settings.......................................................................................................................88
2.7.8 Information List...........................................................................................................89
2.8 24 Overexcit. Protection (Volt/Hertz)................................................................................. 91
2.8.1 Functional Description.................................................................................................91
2.8.2 Setting Notes...............................................................................................................93
10 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Table of Contents
2.8.3 Settings.......................................................................................................................95
2.8.4 Information List...........................................................................................................95
2.9 Jump of Voltage Vector..................................................................................................... 96
2.9.1 Functional Description.................................................................................................96
2.9.2 Setting Notes...............................................................................................................98
2.9.3 Settings.......................................................................................................................99
2.9.4 Information List...........................................................................................................99
2.10 Phase Rotation................................................................................................................ 100
2.10.1 Functional Description...............................................................................................100
2.10.2 Setting Notes.............................................................................................................100
2.11 Function Logic................................................................................................................ 101
2.11.1 Pickup Logic of the Entire Device................................................................................101
2.11.2 Tripping Logic of the Entire Device.............................................................................101
2.11.3 Setting Notes.............................................................................................................102
2.12 Auxiliary Functions..........................................................................................................103
2.12.1 Message Processing...................................................................................................103
2.12.1.1 LED Displays and Binary Outputs (Output Relays)..................................................103
2.12.1.2 Information on the Integrated Display (LCD) or Personal Computer....................... 103
2.12.1.3 Information to a Control Center............................................................................105
2.12.2 Statistics....................................................................................................................105
2.12.2.1 Functional Description......................................................................................... 105
2.12.2.2 Setting Notes....................................................................................................... 105
2.12.2.3 Information List................................................................................................... 105
2.12.3 Measurement............................................................................................................105
2.12.3.1 Display of Measured Values.................................................................................. 106
2.12.3.2 Transfer of Measured Values................................................................................ 107
2.12.3.3 Information List................................................................................................... 107
2.12.4 Min/Max Measurement Setup.................................................................................... 108
2.12.4.1 Functional Description......................................................................................... 108
2.12.4.2 Setting Notes....................................................................................................... 108
2.12.4.3 Settings............................................................................................................... 108
2.12.4.4 Information List................................................................................................... 108
2.12.5 Set Points for Measured Values.................................................................................. 109
2.12.5.1 Setting Notes....................................................................................................... 109
2.12.6 Set Points for Statistic................................................................................................ 109
2.12.6.1 Functional Description......................................................................................... 109
2.12.6.2 Setting Notes....................................................................................................... 109
2.12.6.3 Information List................................................................................................... 110
2.12.7 Energy Metering........................................................................................................110
2.12.7.1 Setting Notes....................................................................................................... 110
2.12.7.2 Settings............................................................................................................... 110
2.12.7.3 Information List................................................................................................... 110
2.12.8 Commissioning Aids.................................................................................................. 110
2.12.8.1 Functional Description......................................................................................... 110
2.13 Breaker Control...............................................................................................................112
2.13.1 Control Device...........................................................................................................112
2.13.1.1 Functional Description......................................................................................... 112
2.13.1.2 Informationsübersicht..........................................................................................113
2.13.2 Types of Commands.................................................................................................. 113
2.13.2.1 Functional Description......................................................................................... 113
SIPROTEC 4, 7RW80, Manual 11 C53000-G1140-C233-4, Edition 07.2018
Table of Contents
2.13.3 Command Sequence..................................................................................................113
2.13.3.1 Functional Description......................................................................................... 114
2.13.4 Switchgear Interlocking............................................................................................. 114
2.13.4.1 Functional Description......................................................................................... 114
2.13.5 Command Logging.................................................................................................... 118
2.13.5.1 Functional Description......................................................................................... 119
2.14 Notes on Device Operation..............................................................................................120
2.14.1 Different operation....................................................................................................120
3 Mounting and Commissioning................................................................................................................. 123
3.1 Mounting and Connections............................................................................................. 124
3.1.1 Configuration Information......................................................................................... 124
3.1.2 Hardware Modifications.............................................................................................127
3.1.2.1 Disassembly.........................................................................................................127
3.1.2.2 Connections of the Voltage Terminals...................................................................131
3.1.2.3 Interface Modules................................................................................................ 132
3.1.2.4 Reassembly..........................................................................................................134
3.1.3 Installation................................................................................................................ 135
3.1.3.1 General................................................................................................................135
3.1.3.2 Panel Flush Mounting...........................................................................................136
3.1.3.3 Cubicle Mounting.................................................................................................137
3.1.3.4 Panel Surface Mounting....................................................................................... 138
3.2 Checking Connections.....................................................................................................140
3.2.1 Checking the Data Connections of the Interfaces........................................................140
3.2.2 Checking the System Connections............................................................................. 142
3.3 Commissioning............................................................................................................... 144
3.3.1 Test Mode and Transmission Block.............................................................................145
3.3.2 Testing the System Interface .....................................................................................145
3.3.3 Configuring Communication Modules........................................................................146
3.3.4 Checking the Status of Binary Inputs and Outputs...................................................... 150
3.3.5 Testing User-Defined Functions..................................................................................152
3.3.6 Voltage and Phase Rotation Testing........................................................................... 152
3.3.7 Polarity Check for Voltage Input V3.............................................................................153
3.3.8 Trip/Close Tests for the Configured Operating Devices................................................ 155
3.3.9 Creating Oscillographic Recordings for Tests.............................................................. 156
3.4 Final Preparation of the Device........................................................................................157
4 Technical Data.......................................................................................................................................... 159
4.1 General Device Data........................................................................................................160
4.1.1 Analog Inputs............................................................................................................160
4.1.2 Auxiliary voltage........................................................................................................160
4.1.3 Binary Inputs and Outputs......................................................................................... 160
4.1.4 Communication Interfaces.........................................................................................161
4.1.5 Electrical Tests...........................................................................................................164
4.1.6 Mechanical Tests....................................................................................................... 165
4.1.7 Climatic Stress Tests.................................................................................................. 166
4.1.8 Service Conditions..................................................................................................... 167
4.1.9 Constructive Design...................................................................................................167
4.1.10 UL certification conditions......................................................................................... 167
12 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Table of Contents
4.2 Voltage Protection.......................................................................................................... 169
4.3 Frequency Protection 81 O/U...........................................................................................171
4.4 Load Restoration............................................................................................................. 172
4.5 Flexible Protection Functions ..........................................................................................173
4.6 Synchrocheck 25 ............................................................................................................175
4.7 Overecxitation Protection 24...........................................................................................177
4.8 Jump of Voltage Vector................................................................................................... 179
4.9 User-defined Functions (CFC).......................................................................................... 180
4.10 Auxiliary Functions..........................................................................................................185
4.11 Switching Device Control................................................................................................ 188
4.12 Dimensions.....................................................................................................................189
4.12.1 Panel Flush and Cubicle Mounting (Housing Size 1/6) ................................................189
4.12.2 Panel Surface Mounting (Housing Size 1/6) ............................................................... 190
4.12.3 Bottom view..............................................................................................................190
A Ordering Information and Accessories.....................................................................................................191
A.1 Ordering Information 7RW80 V4.6 ................................................................................. 192
A.2 Accessories.....................................................................................................................195
B Terminal Assignments..............................................................................................................................197
B.1 7RW80 — Housing for Panel Flush Mounting or Cubicle Mounting...................................198
B.2 7RW80 — Housing for panel surface mounting................................................................199
C Connection Examples............................................................................................................................... 201
C.1 Connection Examples for Voltage Transformers...............................................................202
D Default Settings and Protocol-dependent Functions............................................................................... 207
D.1 LEDs............................................................................................................................... 208
D.2 Binary Input.................................................................................................................... 209
D.3 Binary Output................................................................................................................. 210
D.4 Function Keys................................................................................................................. 211
D.5 Default Display................................................................................................................212
D.6 Protocol-dependent Functions.........................................................................................213
E Functions, Settings, Information..............................................................................................................215
E.1 Functional Scope............................................................................................................ 216
E.2 Settings.......................................................................................................................... 217
E.3 Information List.............................................................................................................. 226
E.4 Group Indications............................................................................................................246
E.5 Measured Values.............................................................................................................247
Literature.................................................................................................................................................. 249
Glossary.................................................................................................................................................... 251
Index.........................................................................................................................................................261
SIPROTEC 4, 7RW80, Manual 13 C53000-G1140-C233-4, Edition 07.2018
14 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
1

Introduction

The device family SIPROTEC 7RW80 devices is introduced in this section. An overview of the devices is presented in their application, characteristics, and scope of functions.
1.1 Overall Operation 16
1.2 Application Scope 18
1.3 Characteristics 20
SIPROTEC 4, 7RW80, Manual 15 C53000-G1140-C233-4, Edition 07.2018
Introduction

1.1 Overall Operation

1.1
Analog Inputs
Overall Operation
The Voltage and Frequency protection SIPROTEC 7RW80 is equipped with a high performance microprocessor. This provides numerical processing of all functions in the device, from the acquisition of the measured values up to the output of commands to the circuit breakers. Figure 1-1 shows the basic structure of the device 7RW80.
The measuring inputs MI transform the voltages derived from the instrument transformers and match them to the internal signal levels for processing in the device. Three voltage inputs are available in the MI section.
[hw-struktur-7rw80-100519, 1, en_US]
Figure 1-1
Voltage inputs can either be used to measure the three phase-to-ground voltages, or two phase-to-phase voltages and the displacement voltage (e–n voltage) or for any other voltage. It is also possible to connect two phase-to-phase voltages in open-delta connection.
The analog input quantities are passed on to the input amplifiers (IA). The input amplifier IA element provides a high-resistance termination for the input quantities. It consists of filters that are optimized for measured­value processing with regard to bandwidth and processing speed.
The analog-to-digital (AD) transformer group consists of a an analog-to-digital converter and memory compo­nents for the transmission of data to the microcomputer.
Microcomputer System
Apart from processing the measured values, the microcomputer system (μC) also executes the actual protec­tion and control functions. They especially include:
16 SIPROTEC 4, 7RW80, Manual
Hardware structure of the numerical Voltage and Frequency Protection Device 7RW80
C53000-G1140-C233-4, Edition 07.2018
Filtering and preparation of the measured quantities
Continuous monitoring of the measured quantities
Monitoring of the pickup conditions for the individual protective functions
Interrogation of limit values and sequences in time
Control of signals for the logic functions
Output of control commands for switching devices
Recording of messages, fault data and fault values for analysis
Management of the operating system and the associated functions such as data recording, real-time
clock, communication, interfaces, etc.
The information is distributed via output amplifiers (OA).
Binary Inputs and Outputs
The computer system obtains external information through the binary input/output boards (inputs and outputs). The computer system obtains information from the system (e.g remote resetting) or from external equipment (e.g. blocking commands). These outputs include, in particular, trip commands to circuit breakers and signals for the remote indication of important events and conditions.
Front Panel
Introduction
1.1 Overall Operation
Information such as messages related to events, states, measured values and the functional status of the device are visualized by light-emitting diodes (LEDs) and a display screen (LCD) on the front panel.
Integrated control and numeric keys in conjunction with the LCD enable interaction with the remote device. These elements can be used to access the device for information such as configuration and setting parame­ters. Similarly, setting parameters can be accessed and changed if needed.
In addition, control of circuit breakers and other equipment is possible from the front panel of the device.
Interfaces
Communication with a PC can be implemented via the USB DIGSI interface using the DIGSI software, allowing all device functions to be easily executed.
Communication with a PC is also possible via port A (Ethernet interface) and port B (System/Service interface) using DIGSI.
In addition to the device communication via DIGSI, port B can also be used to transmit all device data to a central evaluator or a control center. This interface may be provided with various protocols and physical trans­mission schemes to suit the particular application.
Power Supply
A power supply unit (Vaux or PS) delivers power to the functional units using the different voltage levels. Voltage dips may occur if the voltage supply system (substation battery) becomes short-circuited. Usually, they are bridged by a capacitor (see also Technical Data).
A buffer battery is located under the flap at the lower end of the front cover.
SIPROTEC 4, 7RW80, Manual 17 C53000-G1140-C233-4, Edition 07.2018
Introduction

1.2 Application Scope

1.2
Protection Functions
Control Functions
Application Scope
The digital voltage and frequency protection SIPROTEC 4 7RW80 is a versatile device designed for protection, control, and monitoring of transformers, electrical machines and distribution systems.
The device can be used for
System decoupling or for load shedding if ever there is a risk of a system collapse as a result of inadmis-
sibly large frequency drops
Monitoring voltage and frequency thresholds
Voltage, frequency and overexcitation protection can be used to protect generators and transformers in the event of
Defective voltage control or defective frequency control
Full load rejection
Islanding generation systems.
Multilevel voltage and frequency protection is the basic function of the device. Further protection functions included are load restoration, synchrocheck, overexcitation protection, vector
jump and flexible protective functions.
The device provides a control function which can be accomplished for activating and deactivating the switch­gear via operator buttons, port B, binary inputs and - using a PC and the DIGSI software - via the front inter­face.
The status of the primary equipment can be transmitted to the device via auxiliary contacts connected to binary inputs. The present status (or position) of the primary equipment can be displayed on the device, and used for interlocking or alarm condition monitoring. The number of operating equipments to be switched is limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for the switch position indications. Depending on the primary equipment being controlled, one binary input (single point indication) or two binary inputs (double point indication) may be used for this process.
The capability of switching primary equipment can be restricted by a setting associated with switching authority (Remote or Local), and by the operating mode (interlocked/non-interlocked, with or without pass­word request).
Processing of interlocking conditions for switching (e.g. switchgear interlocking) can be established with the aid of integrated, user-configurable logic functions.
Messages and Measured Values; Recording of Event and Fault Data
The operational indications provide information about conditions in the power system and the device. Meas­urement quantities and values that are calculated can be displayed locally and communicated via the serial interfaces.
Device messages can be assigned to a number of LEDs on the front cover (allocatable), can be externally processed via output contacts (allocatable), linked with user-definable logic functions and/or issued via serial interfaces.
During a fault (system fault) important events and changes in conditions are saved in fault protocols (Event Log or Trip Log). Instantaneous fault values are also saved in the device and may be analyzed subsequently.
Communication
The following interfaces are available for communication with external operating, control and memory systems.
The USB DIGSI interface on the front cover serves for local communication with a PC. By means of the SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this operator interface, such as specifying and modifying configuration parameters and settings, configuring user-specific
18 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Introduction
1.2 Application Scope
logic functions, retrieving operational messages and measured values, inquiring device conditions and meas­ured values, issuing control commands.
Depending on the ordered variant, additional interfaces are located at the bottom of the device. They serve for establishing extensive communication with other digital operating, control and memory components:
Port A serves for DIGSI communication directly on the device or via network. Port B serves for central communication between the device and a control center. It can be operated via data
lines or fiber optic cables. For the data transfer, there are standard protocols in accordance with IEC 60870-5­103 available. The integration of the devices into the SINAUT LSA and SICAM automation systems can also be implemented with this profile.
Alternatively, additional connection options are available with PROFIBUS DP and the DNP3.0 and MODBUS protocols. If an EN100 module is available, you can use the protocol IEC 61850.
SIPROTEC 4, 7RW80, Manual 19 C53000-G1140-C233-4, Edition 07.2018
Introduction

1.3 Characteristics

1.3
General Characteristics
Characteristics
Powerful 32-bit microprocessor system
Complete digital processing and control of measured values, from the sampling of the analog input quan-
tities to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear devices
Total electrical separation between the internal processing stages of the device and the external trans-
former, control, and DC supply circuits of the system because of the design of the binary inputs, outputs, and the DC or AC converters
Easy device operation through an integrated operator panel or by means of a connected personal
computer running DIGSI
Continuous calculation and display of measured and metered values on the front of the device
Storage of min./max. measured values (slave pointer function) and storage of long-term mean values
Recording of event and fault data for the last 8 system faults (fault in a network) with real-time informa-
tion as well as instantaneous values for fault recording for a maximum time range of 20 s
Constant monitoring of the measured quantities, as well as continuous self-diagnostics covering the
hardware and software
Communication with SCADA or substation controller equipment via serial interfaces through the choice
of data cable, modem, or optical fibers
Battery-buffered clock which can be synchronized via a synchronization signal at the binary input or via a
protocol
Statistics: Recording of the number of trip signals instigated by the device.
Commissioning aids such as connection and direction check, status indication of all binary inputs and
outputs, easy testing of port B, and influencing of information at port B during test operation.
Voltage Protection 27, 59
Three-element undervoltage detection via the positive sequence system of the voltages, phase-to-phase
or phase-ground voltages
Separate overvoltage detection of the voltages applied or detection of the positive or negative sequence
component of the voltages
Settable dropout ratio for all elements of the undervoltage and overvoltage protection
User-defined characteristic
Frequency Protection 81 O/U
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are
independently adjustable
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold.
Load Restoration
4 separately adjustable load restoration stages
Individually assignable low frequency stages, which start the load restoration stage (1 to 4 for each load
restoration element)
Settable dropout ratio for all stages of the load restoration
Monitoring of the settable restoration cycles (no ON/OFF chattering)
20 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Monitoring Functions
Increased reliability due to monitoring of the internal measurement circuits as well as the hardware and
software
Monitoring of the current transformer and voltage transformer secondary circuits using sum and
symmetry supervision with optional protection function blocking
Broken-wire Monitoring of Voltage Transformer Circuits
Trip circuit monitoring possible
Phase rotation check.
Flexible Protective Functions
Up to 20 customizable protection functions with three-phase or single-phase operation
Any calculated or directly measured quantity can be evaluated on principle
Standard protection logic with definite time characteristic
Internal and configurable pickup and dropout delay
Modifiable message texts.
Synchrocheck
Introduction
1.3 Characteristics
Check of the synchronism conditions or de-energized state before manual closing of the circuit breaker
Fast measurement of the voltage difference ΔV, the phase angle difference Δϕ and the frequency differ-
ence Δf
Setable minimum and maximum voltage
Measurement also possible via transformer without external intermediate matching transformer
Measuring voltages optionally phase–to–phase or phase–to–ground.
Overecxitation Protection
Calculation of the V/f ratio V/f
Adjustable warning and tripping stage
Standard characteristic or arbitrary trip characteristic selectable for calculation of the thermal stress.
Jump of Voltage Vector
Sensitive phase jump detection to be used for network disconnection.
Phase Rotation
Selectable ABC or ACB by setting (static) or binary input (dynamic).
User Defined Functions
Freely programmable linking of internal and external signals in order to implement user-defined logic
functions
All standard logic functions (AND, OR, NOT, EXCLUSIVE-OR, etc.)
Time delays and limit value interrogations
Processing of measured values, including zero suppression, adding a knee curve for a transducer input,
and live-zero monitoring.
Linking of multiple devices for load restoration with prioritization of the stages
SIPROTEC 4, 7RW80, Manual 21 C53000-G1140-C233-4, Edition 07.2018
Introduction
1.3 Characteristics
Breaker Control
Switching devices can be opened and closed manually using control keys, programmable function keys, via port B (e.g. of SICAM or LSA), or via the user interface (using a personal computer and the DIGSI oper­ating software)
22 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
2

Functions

This chapter describes the numerous functions available on the SIPROTEC 4 device 7RW80. It shows the setting possibilities for each function in maximum configuration. Information with regard to the determina­tion of setting values as well as formulas, if required, are also provided.
Based on the following information, it can also be determined which of the provided functions should be used.
2.1 General 24
2.2 Voltage Protection 27, 59 37
2.3 Frequency Protection 81 O/U 46
2.4 Load Restoration 50
2.5 Supervision Functions 61
2.6 Flexible Protection Functions 71
2.7 Synchrocheck 80
2.8 24 Overexcit. Protection (Volt/Hertz) 91
2.9 Jump of Voltage Vector 96
2.10 Phase Rotation 100
2.11 Function Logic 101
2.12 Auxiliary Functions 103
2.13 Breaker Control 112
2.14 Notes on Device Operation 120
SIPROTEC 4, 7RW80, Manual 23 C53000-G1140-C233-4, Edition 07.2018
i
i
Functions

2.1 General

2.1
2.1.1
2.1.1.1
Setting the Functional Scope
General
The settings associated with the various device functions can be modified using the operating or service inter­face in DIGSI in conjunction with a personal computer. Some parameters can also be changed using the controls on the front panel of the device. The procedure is described in detail in the SIPROTEC System Descrip­tion /1/ SIPROTEC 4 System Description.

Functional Scope

The 7RW80 relay contains protection functions as well as auxiliary functions. The hardware and firmware is designed for this scope of functions. Additionally, the control functions can be matched to the system require­ments. Individual functions can be enabled or disabled during the configuration procedure. The interaction of functions may also be modified.
Functional Description
The available protection and additional functions can be configured as Enabled or Disabled. For individual functions, a choice between several alternatives may be possible, as described below.
Functions configured as Disabled are not processed by the 7RW80. There are no messages and corre­sponding settings (functions, limit values) queried during configuration.
NOTE
Available functions and default settings are depending on the order variant of the relay (see A Ordering
Information and Accessories).
2.1.1.2
Setting the Functional Scope
Special Features
Setting Notes
Your protection device is configured using the DIGSI software. Connect your personal computer either to the USB port on the device front or to port A or port B on the bottom side of the device depending on the device version (ordering code). The operation via DIGSI is explained in the SIPROTEC 4 System Description.
The Device Configuration dialog box allows you to adjust your device to the specific system conditions. Password no. 7 is required (for parameter set) for changing configuration parameters in the device. Without
the password the settings can only be read but not edited and transmitted to the device.
Most settings are self-explanatory. The special cases are described in the following. If you want to use the setting group change function, set address 103 Grp Chge OPTION to Enabled. In
this case, you can select up to four different groups of function parameters between which you can switch quickly and conveniently during operation. Only one setting group can be used when selecting the option Disabled.
The synchronization function is activated in address 161 25 Function 1 by the setting SYNCHROCHECK or it is set to Disabled.
Under address 182 74 Trip Ct Supv it can be selected whether the trip-circuit supervision works with two (2 Binary Inputs) or only one binary input (1 Binary Input), or whether the function is configured Disabled.
In address 617 ServiProt (CM) you can specify for which purpose port B is used. T103 means that the device is connected to a control and protection facility via serial port, DIGSI means that you are using the port to connect DIGSI or you are not using port B (Disabled).
The flexible protection functions can be configured via parameter FLEXIBLE FUNC.. You can create up to 20 flexible functions by setting a checkmark in front of the desired function. If the checkmark of a function is
24 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Functions
2.1 General
removed, all settings and configurations made previously will be lost. After re-selecting the function, all settings and configurations are in default setting. Setting of the flexible function is done in DIGSI under “Parameters”, “Additional Functions” and “Settings”. The configuration is done, as usual, under “Parameters” and “Configuration”.
2.1.1.3
Settings
Addr. Parameter Setting Options Default Setting Comments
103 Grp Chge OPTION Disabled
Disabled Setting Group Change Option
Enabled
104 OSC. FAULT REC. Disabled
Enabled Oscillographic Fault Records
Enabled
143 24 V/f Disabled
Enabled
146 VECTOR JUMP Disabled
Disabled 24 Overexcit. Protection (Volt/
Hertz)
Disabled Jump of Voltage Vector
Enabled
150 27/59 Disabled
Enabled
152 VT BROKEN WIRE Disabled
Enabled 27, 59 Under/Overvoltage Protec-
tion
Enabled VT broken wire supervision
Enabled
154 81 O/U Disabled
Enabled
155 Load Restore Disabled
Enabled 81 Over/Underfrequency Protec-
tion
Disabled Load Restoration
Enabled
161 25 Function 1 Disabled
Disabled 25 Function group 1
SYNCHROCHECK
182 74 Trip Ct Supv Disabled
Disabled 74TC Trip Circuit Supervision 2 Binary Inputs 1 Binary Input
617 ServiProt (CM) Disabled
T103 Port B usage T103 DIGSI
SIPROTEC 4, 7RW80, Manual 25 C53000-G1140-C233-4, Edition 07.2018
Functions
2.1 General
Addr. Parameter Setting Options Default Setting Comments
- FLEXIBLE FCT. 1...20 Flexible Function 01
Please select Flexible Functions 1...20 Flexible Function 02 Flexible Function 03 Flexible Function 04 Flexible Function 05 Flexible Function 06 Flexible Function 07 Flexible Function 08 Flexible Function 09 Flexible Function 10 Flexible Function 11 Flexible Function 12 Flexible Function 13 Flexible Function 14 Flexible Function 15 Flexible Function 16 Flexible Function 17 Flexible Function 18 Flexible Function 19 Flexible Function 20
2.1.2

Device, General Settings

The device requires some general information. This may be, for example, the type of annunciation to be issued in the event of an occurrence of a power system fault.
2.1.2.1
Functional Description
Command-Dependent Messages "No Trip – No Flag"
The storage of indications assigned to local LEDs and the availability of spontaneous indications can be made dependent on whether the device has issued a trip command. This information is then not issued if during a system disturbance one or more protection functions have picked up but the 7RW80 did not trip because the fault was cleared by another device (e.g. on another line). These messages are then limited to faults in the line to be protected.
The following figure illustrates the generation of the reset command for stored indications. The instant the device drops out, the presetting of parameter 610 FltDisp.LED/LCD decides whether the new fault remains stored or is reset.
[dw_ruecksetzbefehl-fuer-n-speicher-led-lcd-meld, 1, en_US]
Figure 2-1 Creation of the reset command for the latched LED and LCD messages
26 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Spontaneous Messages on the Display
You can determine whether or not the most important data of a fault event is displayed automatically after the fault has occurred (see also Subsection "Fault Messages" in Section "Auxiliary Functions").
Functions
2.1 General
2.1.2.2
Setting Notes
Fault Messages
A new pickup of a protection function generally turns off any previously set light displays so that only the latest fault is displayed at any one time. It can be selected whether the stored LED displays and the sponta­neous messages on the display appear after the new pickup or only after a new trip signal is issued. In order to select the desired mode of display, select the Device submenu in the SETTINGS menu. Under address 610 FltDisp.LED/LCD the two options Target on PU and Target on TRIP ("No trip – no flag") can be selected.
For devices with graphic display, use parameter 611 Spont. FltDisp. to specify whether a spontaneous fault message should appear automatically on the display (YES) or not (NO). For devices with text display such indications will appear after a system fault in any case.
Selection of Default Display
The start page of the default display appearing after startup of the device can be selected in the device data via parameter640 Start image DD. The pages available for each device version are listed in the Appendix
D Default Settings and Protocol-dependent Functions.
2.1.2.3
Addr.
Settings
Parameter Setting Options Default Setting Comments
610 FltDisp.LED/LCD Target on PU
Target on TRIP
611 Spont. FltDisp. YES
NO
640 Start image DD image 1
image 2 image 3
Target on PU Fault Display on LED / LCD
NO Spontaneous display of flt.annun-
ciations
image 1 Start image Default Display
2.1.2.4
No.
Information List
Information Type of
Comments Informa­tion
- >Light on SP >Back Light on
- Reset LED IntSP Reset LED
- DataStop IntSP Stop data transmission
- Test mode IntSP Test mode
- Feeder gnd IntSP Feeder GROUNDED
- Brk OPENED IntSP Breaker OPENED
- HWTestMod IntSP Hardware Test Mode
- SynchClock IntSP_Ev Clock Synchronization
- Distur.CFC OUT Disturbance CFC 1 Not configured SP No Function configured 2 Non Existent SP Function Not Available 3 >Time Synch SP_Ev >Synchronize Internal Real Time Clock 5 >Reset LED SP >Reset LED 15 >Test mode SP >Test mode
SIPROTEC 4, 7RW80, Manual 27 C53000-G1140-C233-4, Edition 07.2018
Functions
2.1 General
No. Information Type of
Informa­tion
16 >DataStop SP >Stop data transmission 51 Device OK OUT Device is Operational and Protecting 52 ProtActive IntSP At Least 1 Protection Funct. is Active 55 Reset Device OUT Reset Device 56 Initial Start OUT Initial Start of Device 67 Resume OUT Resume 68 Clock SyncError OUT Clock Synchronization Error 69 DayLightSavTime OUT Daylight Saving Time 70 Settings Calc. OUT Setting calculation is running 71 Settings Check OUT Settings Check 72 Level-2 change OUT Level-2 change 73 Local change OUT Local setting change 110 Event Lost OUT_Ev Event lost 113 Flag Lost OUT Flag Lost 125 Chatter ON OUT Chatter ON 140 Error Sum Alarm OUT Error with a summary alarm 160 Alarm Sum Event OUT Alarm Summary Event 177 Fail Battery OUT Failure: Battery empty 178 I/O-Board error OUT I/O-Board Error 181 Error A/D-conv. OUT Error: A/D converter 191 Error Offset OUT Error: Offset 193 Alarm NO calibr OUT Alarm: NO calibration data available
236.2127 BLK. Flex.Fct. IntSP BLOCK Flexible Function 301 Pow.Sys.Flt. OUT Power System fault 302 Fault Event OUT Fault Event 303 sens Gnd flt OUT sensitive Ground fault 320 Warn Mem. Data OUT Warn: Limit of Memory Data exceeded 321 Warn Mem. Para. OUT Warn: Limit of Memory Parameter exceeded 322 Warn Mem. Oper. OUT Warn: Limit of Memory Operation exceeded 323 Warn Mem. New OUT Warn: Limit of Memory New exceeded 502 Relay Drop Out SP Relay Drop Out 510 Relay CLOSE SP General CLOSE of relay 545 PU Time VI Time from Pickup to drop out 546 TRIP Time VI Time from Pickup to TRIP 10080 Error Ext I/O OUT Error Extension I/O 10081 Error Ethernet OUT Error Ethernet 10083 Error Basic I/O OUT Error Basic I/O
Comments
2.1.3
2.1.3.1
28 SIPROTEC 4, 7RW80, Manual

Power System Data 1

Functional Description
The device requires certain basic data regarding the protected equipment so that the device can adapt to its desired application. These may be, for instance, nominal power system and transformer data, measured quan­tity polarities and their physical connections, breaker properties (where applicable) etc. There are also certain parameters that are common to all functions, i.e. not associated with a specific protection, control or moni­toring function. The following section discusses these parameters.
C53000-G1140-C233-4, Edition 07.2018
Functions
2.1 General
2.1.3.2
Setting Notes
General
Some P.System Data 1 can be entered directly at the device. See Section 2.14 Notes on Device Operation for more information regarding this topic.
In DIGSI double-click Settings to open the corresponding dialog box. In doing so, a dialog box with tabs will open under P.System Data 1 where individual parameters can be configured. The following descriptions are therefore structured according to these tabs.
Rated Frequency (Power System)
The nominal frequency of the system is set under the Address 214 Rated Frequency. The factory pre­setting in accordance with the model need only be changed if the device will be employed for a purpose other than that which was planned when ordering.
In the US device versions (ordering data position 10= C), parameter 214 is preset to 60 Hz. 214.
Voltage Connection (Power System)
Address 213 specifies how the voltage transformers are connected. VT Connect. 3ph = Van, Vbn, Vcn means that the three phase voltages are wye connected, i.e. the
three phase-to-ground voltages are measured.ground. VT Connect. 3ph = Vab, Vbc, VGnd means that two phase-to-phase voltages (open delta voltage) and
the displacement voltage V VT Connect. 3ph = Vab, Vbc means that two phase-to-phase voltages (open delta voltage) are
connected. The third voltage transformer of the device is not used. VT Connect. 3ph = Vab, Vbc, Vx means that two phase-to-phase voltages (open delta voltage) are
connected. Furthermore, any third voltage Vx is connected that is used exclusively for the flexible protection functions. The transformer nominal voltages for Vx are set at address 232 and 233.
VT Connect. 3ph = Vab, Vbc, VSyn means that two phase-to-phase voltages (open delta voltage) and the reference voltage for V
device is used. VT Connect. 3ph = Vph-g, VSyn is used if the synchronization function of the device is used and only
phase-to-ground voltages are available for the protected object to be synchronized. One of these voltages is connected to the first voltage transformer; the reference voltage V
former. The selection of the voltage transformer connection affects the operation of all device functions that require
voltage input. The settings Vab, Vbc or Vab, Vbc, Vx or Vab, Vbc, VSyn or Vph-g, VSyn do not allow determining
the zero sequence voltage. The associated protection functions are inactive in this case. The table gives an overview of the functions that can be activated for the corresponding connection type
(depends also on the ordering number). The functions which are not shown are available for all connection types.
are connected.
GND
are connected. This setting is enabled if the synchronization function of the
SYN
is connected to the third voltage trans-
SYN
Table 2-1
Connection Types of the Voltage Transformers
Connection type Synchronization
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc
Vab, Vbc, Vx
Vab, Vbc, VSyn
Vph-g, VSyn
no no no
no yes yes
Measured values, which due to the chosen voltage connection cannot be calculated, will be displayed as dots.
SIPROTEC 4, 7RW80, Manual 29 C53000-G1140-C233-4, Edition 07.2018
Functions
2.1 General
The Appendix provides some connection examples for all connection types atC Connection Examples.
Nominal Values of Voltage Transformers (VTs)
At addresses 202 Vnom PRIMARY and 203 Vnom SECONDARY, information is entered regarding the primary nominal voltage and secondary nominal voltage (phase-to-phase) of the connected voltage transformers.
Transformation Ratio of Voltage Transformers (VTs)
Address 206 Vph / Vdelta informs the device of the adjustment factor between the phase voltage and the displacement voltage. This information is relevant for the processing of ground faults (in grounded systems and ungrounded systems), for the operational measured value VN and measured-variable monitoring.
If the voltage transformer set provides open delta windings and if these windings are connected to the device, this must be specified accordingly in address 213 (see above margin heading “Voltage Connection”). Since the voltage transformer ratio is normally as follows:
[uebersetzung-spannungswandler-020313-kn, 1, en_US]
the factor V
(secondary voltage, address 206 Vph / Vdelta) must be set to 3/ √3 = √3 = 1.73 which
ph/VN
must be used if the VN voltage is connected. For other transformation ratios, i.e. the formation of the displacement voltage via an interconnected transformer set, the factor must be corrected accordingly.
Please take into consideration that also the calculated secondary V0-voltage is divided by the value set in address 206. Thus, even if the V0-voltage is not connected, address 206 has an impact on the secondary operational measured value VN.
If Vab, Vbc, VGnd is selected as voltage connection type, parameter Vph / Vdelta is used to calculate the phase-to-ground voltages and is therefore important for the protection function. With voltage connection type Van, Vbn, Vcn, this parameter is used only to calculate the operational measured value of the secon­dary voltage VN.
Trip and Close Command Duration (Breaker)
In address 210 the minimum trip command duration TMin TRIP CMD is set. This setting applies to all protec­tion functions that can initiate tripping.
In address 211 the maximum close command duration TMax CLOSE CMD is set. It applies to the integrated reclosing function. It must be set long enough to ensure that the circuit breaker has securely closed. An exces­sive duration causes no problem since the closing command is interrupted in the event another trip is initiated by a protection function.
Pickup Thresholds of the Binary Inputs (Thresholds BI)
At address 220 Threshold BI 1 to 226 Threshold BI 7 you can set the pickup thresholds of the binary inputs of the device. The settings Thresh. BI 176V, Thresh. BI 88V or Thresh. BI 19V are possible.
Voltage Protection (Protection Operating Quantities)
In a three-phase connection, the fundamental harmonic of the three phase-to-phase voltages (Vphph) or phase-ground voltages (Vph-n) or the positive sequence voltage (V1) or the negative sequence voltage (V2) is supplied to the overvoltage protection elements.
In three-phase connection, undervoltage protection relies either on the positive sequence voltage (V1) or the phase-to-phase voltages (Vphph) or the phase-to-ground voltages (Vph-n).
This is configured by setting the parameter value in address 614 OP. QUANTITY 59 and 615 OP. QUAN- TITY 27.
Via Parameter 5009 59 Phases and 5109 27 Phases you may configure which measured quantity is to be evaluated (All phases or Largest phase or Smallest phase).
30 SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Loading...
+ 234 hidden pages