Current Transformer Requirements
Default Settings and Protocol-dependent
Functions
1
2
3
4
A
B
C
D
E
E50417-G1140-C343-A8
Functions, Settings, Information
Literature
Glossary
Index
F
i
i
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
This document has been subjected to rigorous technical
review before being published. It is revised at regular intervals, and any modifications and amendments are included
in the subsequent issues. The content of this document has
been compiled for information purposes only. Although
Siemens AG has made best efforts to keep the document as
precise and up-to-date as possible, Siemens AG shall not
assume any liability for defects and damage which result
through use of the information contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of
Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from
time to time.
Document version: E50417-G1140-C343-A8.00
Edition: 12.2017
Version of the product described: V4.7
document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
Registered Trademarks
SIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM® are
registered trademarks of Siemens AG. Any unauthorized
use is illegal. All other designations in this document can
be trademarks whose use by third parties for their own
purposes can infringe the rights of the owner.
Preface
Purpose of the Manual
This manual describes the functions, operation, installation, and commissioning of devices 7SJ80. In particular, one will find:
Information regarding the configuration of the scope of the device and a description of the device func-
•
tions and settings → Chapter 2;
Instructions for Installation and Commissioning → Chapter 3;
•
Compilation of the Technical Data → Chapter 4;
•
As well as a compilation of the most significant data for advanced users → Appendix.
•
General information with regard to design, configuration, and operation of SIPROTEC 4 devices are set out in
the SIPROTEC 4 System Description /1/ SIPROTEC 4 System Description.
Target Audience
Protection-system engineers, commissioning engineers, persons entrusted with the setting, testing and maintenance of selective protection, automation and control equipment, and operating personnel in electrical
installations and power plants.
Scope
This manual applies to: SIPROTEC 4 Overcurrent Time Protection 7SJ80; Firmware-Version V4.7.
Indication of Conformity
Additional StandardsIEEE Std C37.90 (see Chapter 4 "Technical Data")
This product is UL-certified according to the Technical Data. file E194016
[ul-schutz-7sx80-100310, 1, --_--]
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within
specified voltage limits (Low-voltage Directive 2006/95 EC).
This conformity is proved by tests conducted by Siemens AG in accordance with the Council
Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for EMC
directive, and with the standard EN 60255-27 for the low-voltage directive.
The device has been designed and produced for industrial use.
The product conforms with the international standards of the series IEC 60255 and the
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
²
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
²
CAUTION
Comply with all instructions, in order to avoid death or severe injuries.
Comply with all instructions, in order to avoid death or severe injuries.
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
²
4SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
NOTICE
i
i
NOTICE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
²
NOTE
Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
•
Proper storage, setup and installation
•
Proper operation and maintenance
•
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
The equipment must be grounded at the grounding terminal before any connections are made.
•
All circuit components connected to the power supply may be subject to dangerous voltage.
•
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
•
(capacitors can still be charged).
Preface
Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
•
equipment, ensure that the current-transformer circuits are short-circuited.
The limiting values stated in the document must not be exceeded. This must also be considered during
•
testing and commissioning.
Typographic and Symbol Conventions
The following text formats are used when literal information from the device or to the device appear in the
text flow:
Parameter Names
Designators of configuration or function parameters which may appear word-for-word in the display of the
device or on the screen of a personal computer (with operation software DIGSI), are marked in bold letters in
monospace type style. The same applies to titles of menus.
1234A
Parameter addresses have the same character style as parameter names. Parameter addresses contain the
suffix A in the overview tables if the parameter can only be set in DIGSI via the option Display additionalsettings.
Parameter Options
Possible settings of text parameters, which may appear word-for-word in the display of the device or on the
screen of a personal computer (with operation software DIGSI), are additionally written in italics. The same
applies to the options of the menus.
Designators for information, which may be output by the relay or required from other devices or from the
switch gear, are marked in a monospace type style in quotation marks.
Deviations may be permitted in drawings and tables when the type of designator can be obviously derived
from the illustration.
The following symbols are used in drawings:
Device-internal logical input signal
Device-internal logical output signal
Internal input signal of an analog quantity
External binary input signal with number (binary input,
input indication)
External binary output signal with number
(example of a value indication)
External binary output signal with number (device indication) used as
input signal
Example of a parameter switch designated FUNCTION with address
1234 and the possible settings ON and OFF
Besides these, graphical symbols are used in accordance with IEC 60617-12 and IEC 60617-13 or similar.
Some of the most frequently used are listed below:
Analog input variable
AND-gate operation of input values
OR-gate operation of input values
Exclusive OR gate (antivalence): output is active, if only one of the
inputs is active
Coincidence gate: output is active, if both inputs are active or inactive
at the same time
Dynamic inputs (edge-triggered) above with positive, below with
negative edge
Formation of one analog output signal from a number of analog input
signals
Limit stage with setting address and parameter designator (name)
Timer (pickup delay T, example adjustable) with setting address and
parameter designator (name)
6SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Timer (dropout delay T, example non-adjustable)
Dynamic triggered pulse timer T (monoflop)
Static memory (SR flipflop) with setting input (S), resetting input (R),
output (Q) and inverted output (Q), setting input dominant
Static memory (RS-flipflop) with setting input (S), resetting input (R),
output (Q) and inverted output (Q), resetting input dominant
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the software. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
Open Source Software..................................................................................................................................9
The device family SIPROTEC 7SJ80 devices is introduced in this section. An overview of the devices is
presented in their application, characteristics, and scope of functions.
The digital SIPROTEC 7SJ80 overcurrent protection is equipped with a powerful microprocessor. It allows all
tasks to be processed digitally, from the acquisition of measured quantities to sending commands to circuit
breakers. Figure 1-1 shows the basic structure of the 7SJ80.
The measuring inputs (MI) convert the currents and voltages coming from the measuring transformers and
adapt them to the level appropriate for the internal processing of the device. The device provides 4 current
transformers and - depending on the model - additionally 3 voltage transformers. Three current inputs serve
for the input of the phase currents, another current input (ΙN) may be used for measuring the ground fault
current ΙN (current transformer neutral point) or for a separate ground current transformer (for sensitive
ground fault detection ΙNs and directional determination of ground faults ) - depending on the model.
[hw-struktur-7sj80-060606, 1, en_US]
Figure 1-1
The optional voltage transformers can either be used to input 3 phase-to-ground voltages or 2 phase-to-phase
voltages and the displacement voltage (open delta voltage) or any other voltages. It is also possible to connect
two phase-to-phase voltages in open delta connection.
The analog input quantities are passed on to the input amplifiers (IA). The input amplifier IA element provides
a high-resistance termination for the input quantities. It consists of filters that are optimized for measuredvalue processing with regard to bandwidth and processing speed.
The analog-to-digital (AD) transformer group consists of an analog-to-digital converter and memory components for the transmission of data to the microcomputer.
20SIPROTEC 4, 7SJ80, Manual
Hardware structure of the digital multi-functional protective relay 7SJ80
E50417-G1140-C343-A8, Edition 12.2017
Microcomputer System
Apart from processing the measured values, the microcomputer system (μC) also executes the actual protection and control functions. They especially include:
Filtering and preparation of the measured quantities
•
Continuous monitoring of the measured quantities
•
Monitoring of the pickup conditions for the individual protective functions
•
Interrogation of limit values and sequences in time
•
Control of signals for the logic functions
•
Output of control commands for switching devices
•
Recording of messages, fault data and fault values for analysis
•
Management of the operating system and the associated functions such as data recording, real-time
•
clock, communication, interfaces, etc.
The information is distributed via output amplifiers (OA).
•
Binary Inputs and Outputs
The computer system obtains external information through the binary input/output boards (inputs and
outputs). The computer system obtains information from the system (e.g remote resetting) or from external
equipment (e.g. blocking commands). These outputs include, in particular, trip commands to circuit breakers
and signals for the remote indication of important events and conditions.
Introduction
1.1 Overall Operation
Front Panel
Information such as messages related to events, states, measured values and the functional status of the
device are visualized by light-emitting diodes (LEDs) and a display screen (LCD) on the front panel.
Integrated control and numeric keys in conjunction with the LCD enable interaction with the remote device.
These elements can be used to access the device for information such as configuration and setting parameters. Similarly, setting parameters can be accessed and changed if needed.
In addition, control of circuit breakers and other equipment is possible from the front panel of the device.
Interfaces
Communication with a PC can be implemented via the USB DIGSI interface using the DIGSI software, allowing
all device functions to be easily executed.
Communication with a PC is also possible via port A (Ethernet interface) and port B (System/Service interface)
using DIGSI.
In addition to the device communication via DIGSI, port B can also be used to transmit all device data to a
central evaluator or a control center. This interface may be provided with various protocols and physical transmission schemes to suit the particular application.
Power Supply
A power supply unit (Vaux or PS) delivers power to the functional units using the different voltage levels.
Voltage dips may occur if the voltage supply system (substation battery) becomes short-circuited. Usually,
they are bridged by a capacitor (see also Technical Data).
A buffer battery is located under the flap at the lower end of the front cover.
The multi-function numerical overcurrent protection SIPROTEC 4 7SJ80 is used as protection, control and
monitoring unit for busbar feeders. For line protection, the device can be used in networks with grounded,
lowresistance grounded, isolated or a compensated neutral point structure. It is suited for networks that are
radial and supplied from a single source, open or closed looped networks and for lines with sources at both
ends.
The device includes the functions that are usually necessary for protection, monitoring of circuit breaker positions and control of circuit breakers in single and double busbars; therefore, the device can be employed
universally. The device provides excellent backup protection of differential protective schemes of any kind for
lines, transformers and busbars of all voltage levels.
Non-directional overcurrent protection (50, 50N, 51, 51N) is the basic function of the device. There are three
definite time elements and one inverse time element for the phase currents and the ground current. For the
inverse time elements, several characteristics of different standards are provided. Alternatively, a user-defined
characteristic can be used for the sensitive ground fault detection.
Further protection functions included are the negative sequence protection, overload protection, circuit
breaker failure protection and ground fault protection.
Depending on the ordered variant, further protection functions are included, such as frequency protection,
overvoltage and undervoltage protection, and ground fault protection for high-resistance ground faults (directional or non-directional).
Apart from the short circuit protection functions mentioned before, there are further protection functions
possible as order variants. The overcurrent protection can, for example, be supplemented by a directional
overcurrent protection.
The automatic reclosing function enables several different reclosing cycles for overhead lines. An external
automatic reclosing system can also be connected. To ensure quick detection of the fault location after a short
circuit, the device is equipped with a fault locator.
Before reclosing after a three-pole tripping, the device can verify the validity of the reclosure via a voltage
check and/or a synchrocheck. The synchrocheck function can also be controlled externally.
Control Functions
The device provides a control function which can be accomplished for activating and deactivating the switchgear via operator buttons, port B, binary inputs and - using a PC and the DIGSI software - via the front interface.
The status of the primary equipment can be transmitted to the device via auxiliary contacts connected to
binary inputs. The present status (or position) of the primary equipment can be displayed on the device, and
used for interlocking or alarm condition monitoring. The number of operating equipments to be switched is
limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for
the switch position indications. Depending on the primary equipment being controlled, one binary input
(single point indication) or two binary inputs (double point indication) may be used for this process.
The capability of switching primary equipment can be restricted by a setting associated with switching
authority (Remote or Local), and by the operating mode (interlocked/non-interlocked, with or without password request).
Processing of interlocking conditions for switching (e.g. switchgear interlocking) can be established with the
aid of integrated, user-configurable logic functions.
Messages and Measured Values; Recording of Event and Fault Data
The operational indications provide information about conditions in the power system and the device. Measurement quantities and values that are calculated can be displayed locally and communicated via the serial
interfaces.
Device messages can be assigned to a number of LEDs on the front cover (allocatable), can be externally
processed via output contacts (allocatable), linked with user-definable logic functions and/or issued via serial
interfaces.
22SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
During a fault (system fault) important events and changes in conditions are saved in fault protocols (Event
Log or Trip Log). Instantaneous fault values are also saved in the device and may be analyzed subsequently.
Communication
The following interfaces are available for communication with external operating, control and memory
systems.
The USB DIGSI interface on the front cover serves for local communication with a PC. By means of the
SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this operatorinterface, such as specifying and modifying configuration parameters and settings, configuring user-specific
logic functions, retrieving operational messages and measured values, inquiring device conditions and measured values, issuing control commands.
Depending on the ordered variant, additional interfaces are located at the bottom of the device. They serve for
establishing extensive communication with other digital operating, control and memory components:
Port A serves for DIGSI communication directly on the device or via network. Furthermore, 2 SICAM I/O units
7XV5673 can be connected to this port. Port A can also be used for time synchronization using the NTP
protocol.
Port B serves for central communication between the device and a control center. It can be operated via data
lines or fiber optic cables. For the data transfer, there are standard protocols in accordance with IEC 60870-5103 available. The integration of the devices into the SINAUT LSA and SICAM automation systems can also be
implemented with this profile.
Alternatively, additional connection options are available with PROFIBUS DP and the DNP3.0 and MODBUS
protocols. If an EN100 module is available, you can use the protocols IEC61850, PROFINET or DNP3 TCP.
Furthermore, connecting a SICAM I/O unit is possible via IEC651850 GOOSE.
Complete digital processing and control of measured values, from the sampling of the analog input quan-
•
tities to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear
devices
Total electrical separation between the internal processing stages of the device and the external trans-
•
former, control, and DC supply circuits of the system because of the design of the binary inputs, outputs,
and the DC or AC converters
Complete set of functions necessary for the proper protection of lines, feeders, motors, and busbars
•
Easy device operation through an integrated operator panel or by means of a connected personal
•
computer running DIGSI
Continuous calculation and display of measured and metered values on the front of the device
•
Storage of min./max. measured values (slave pointer function) and storage of long-term mean values
•
Recording of event and fault data for the last 8 system faults (fault in a network) with real-time informa-
•
tion as well as instantaneous values for fault recording for a maximum time range of 20 s
Constant monitoring of the measured quantities, as well as continuous self-diagnostics covering the
•
hardware and software
Communication with SCADA or substation controller equipment via serial interfaces through the choice
•
of data cable, modem, or optical fibers
Battery-buffered clock which can be synchronized via a synchronization signal at the binary input or via a
•
protocol
Switching statistics: Counting the number of trip commands initiated by the device, logging the currents
•
of the last switch-off operation initiated by the device, and accumulating the eliminated short-circuit
currents of each breaker pole
Operating hours counter: Counting the operating hours of the protected object under load
•
Commissioning aids such as connection and direction check, status indication of all binary inputs and
•
outputs, easy testing of port B, and influencing of information at port B during test operation.
Time Overcurrent Protection 50, 51, 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
•
for phase current and ground current ΙN or summation current 3Ι
Two-phase operation of the overcurrent protection (ΙA, ΙC) is possible
•
For inverse-time overcurrent protection, selection from various characteristics of different standards
•
possible
Blocking is possible, e.g. for reverse interlocking with any element
•
Instantaneous tripping by any element is possible when switching onto a fault
•
In-rush restraint with second harmonic current quantities.
•
Ground Fault Protection 50N, 51N
0
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
•
applicable for grounded or high-resistance grounded systems
For inverse-time overcurrent protection, selection from various characteristics of different standards
•
24SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
In-rush restraint with second harmonic current quantities
•
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
•
Directional Time Overcurrent Protection 67, 67N
Three definite time overcurrent protection elements and one inverse time overcurrent protection
•
element for the phase operate in parallel to the non-directional overcurrent elements. Their pickup values
and time delays can be set independently of these.
Direction determination with cross-polarized voltages and voltage memory and dynamically unlimited
•
direction sensitivity
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summa-
Statistical methods to help adjust maintenance intervals for CB contacts according to their actual wear
•
several independent subfunctions have been implemented(ΣΙ-procedure, ΣΙx-procedure, 2P-procedure
•
and Ι2t-procedure)
Acquisition and conditioning of measured values for all subfunctions operates phase-selective using one
•
procedure-specific threshold per subfunction.
User Defined Functions
Freely programmable linking of internal and external signals in order to implement user-defined logic
•
functions
All standard logic functions (AND, OR, NOT, EXCLUSIVE-OR, etc.)
•
Time delays and limit value interrogations
•
Processing of measured values, including zero suppression, adding a knee curve for a transducer input,
•
and live-zero monitoring.
Breaker Control
Switching devices can be opened and closed manually using control keys, programmable function keys,
•
via port B (e.g. of SICAM or LSA), or via the user interface (using a personal computer and the DIGSI operating software)
Feedback of switching states via the switch auxiliary contacts
•
Plausibility monitoring of the circuit breaker position and check of interlocking conditions.
•
28SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
2
Functions
This chapter describes the numerous functions available on the SIPROTEC 4 device 7SJ80. It shows the setting
possibilities for each function in maximum configuration. Information with regard to the determination of
setting values as well as formulas, if required, are also provided.
Based on the following information, it can also be determined which of the provided functions should be
used.
2.1General30
2.2Overcurrent Protection 50, 51, 50N, 51N56
2.3Directional Overcurrent Protection 67, 67N82
2.4Dynamic Cold Load Pickup106
2.5Single-Phase Overcurrent Protection112
2.6Voltage Protection 27, 59122
2.7Negative Sequence Protection 46132
2.8Frequency Protection 81 O/U138
2.9Undervoltage-controlled reactive power protection (27/Q)142
The settings associated with the various device functions can be modified using the operating or service interface in DIGSI in conjunction with a personal computer. Some parameters can also be changed using the
controls on the front panel of the device. The procedure is described in detail in the SIPROTEC System Description /1/ SIPROTEC 4 System Description.
Functional Scope
The 7SJ80 relay contains protection functions as well as auxiliary functions. The hardware and firmware is
designed for this scope of functions. Additionally, the control functions can be matched to the system requirements. Individual functions can be enabled or disabled during the configuration procedure. The interaction of
functions may also be modified.
Functional Description
Example for the configuration of the functional scope:
A protected system consists of overhead lines and underground cables. Since automatic reclosing is only
needed for the overhead lines, the automatic reclosing function is not configured or “disabled” for the relays
protecting the underground cables.
The available protection and additional functions can be configured as Enabled or Disabled. For individual
functions, a choice between several alternatives may be possible, as described below.
Functions configured as Disabled are not processed by the 7SJ80. There are no messages and corresponding
settings (functions, limit values) queried during configuration.
NOTE
Available functions and default settings are depending on the order variant of the relay (see A Ordering
Information and Accessories).
2.1.1.2
Setting the Functional Scope
Special Features
Setting Notes
Your protection device is configured using the DIGSI software. Connect your personal computer either to the
USB port on the device front or to port A or port B on the bottom side of the device depending on the device
version (ordering code). The operation via DIGSI is explained in the SIPROTEC 4 System Description.
The Device Configuration dialog box allows you to adjust your device to the specific system conditions.
Password no. 7 is required (for parameter set) for changing configuration parameters in the device. Without
the password the settings can only be read but not edited and transmitted to the device.
Most settings are self-explanatory. The special cases are described in the following.
If you want to use the setting group change function, set address 103 Grp Chge OPTION to Enabled. In
this case, you can select up to four different groups of function parameters between which you can switch
quickly and conveniently during operation. Only one setting group can be used when selecting the option
Disabled.
For the elements associated with non-directional overcurrent protection 50(N), 51(N) (phase and ground),
various tripping characteristics can be selected at addresses 112 Charac. Phase and 113 Charac.Ground. If only the definite time characteristic is desired, select Definite Time. Alternatively, you can
select between inverse-time curves according to IEC standard (TOC IEC) or ANSI standard (TOC ANSI). The
dropout behavior of the IEC and ANSI curves is specified at address 1210 or 1310 when configuring the time
overcurrent protection.
30SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.1 General
Set to Disabled to disable the entire time overcurrent protection.
The directional overcurrent protection 67(N) is set at address 115 67/67-TOC and 116 67N/67N-TOC. Here,
the same options are available as for non-directional overcurrent protection (except the 50-3 element).
For (sensitive) ground fault detection address 130 S.Gnd.F.Dir.Ch lets you specify the directional charac-
teristic of the sensitive ground fault detection. You can select between cos φ / sin φ and V0/I0 φ mea.
as the measurement procedure. The cos φ / sin φ procedure (via residual wattmetric current detection) is
set by default.
If the measuring method cos φ / sin φ is set, select between a definite time characteristic (Definite
Time) and an inverse time characteristic User Defined PU at address 131 Sens. Gnd Fault. V0/I0 φ
mea. provides the definite time characteristic Definite Time, inverse time characteristics TOC IEC or TOC
ANSI. When selecting the setting Disabled, the entire function is disabled.
For the intermittent ground fault protection, you can specify the measured quantity (with Ignd, with 3I0
or with Ignd,sens.) to be used by this protection function at address 133 INTERM.EF.
At address 134 Dir. Interm. EF you can set the directional intermittent ground fault protection to
Enabled or Disabled.
For unbalanced load protection, address 140 46 allows you to specify which tripping characteristics to use.
You can select between Definite Time, TOC ANSI or TOC IEC. If this function is not required, select
Disabled.
The overload protection is activated in address 142 49 by selecting the setting without ambient temperature
No ambient temp or it is set to Disabled.
At address 155 27/Q-Protection you can set the QU protection to Enabled or Disabled.
The synchronization function is activated in address 161 25 Function 1 by the setting SYNCHROCHECK or it
is set to Disabled.
In address 170 you can set the breaker failure protection to Enabled or Disabled. The setting option
enabled w/ 3I0> subjects the ground current and the negative sequence current to a plausibility check.
For the CB maintenance functions, several options are available under address 172 52 B.WEAR MONIT. Irre-
spective of this, the basic functionality of the summation current formation (ΣΙ procedure) is always active. It
requires no further configurations and adds up the tripping currents of the trips initiated by the protection
functions.
When selecting the ΣIx-Procedure, the sum of all tripping current powers is formed and output as reference
value. The 2P Procedure continuously calculates the remaining lifespan of the circuit breaker.
With the Ι2t Procedure the square fault current integrals are formed via arc time and output as a reference
value.
Further information concerning the individual procedures of the CB maintenance are given in
Section2.23.2 Statistics. You can also disable this function by setting it to Disabled.
In address 181, you can enter how many line sections (maximum of three) are taken into account by the fault
locator.
Under address 182 74 Trip Ct Supv it can be selected whether the trip-circuit supervision works with two
(2 Binary Inputs) or only one binary input (1 Binary Input), or whether the function is configured
Disabled.
In address 617 ServiProt (CM) you can specify for which purpose port B is used. T103 means that the
device is connected to a control and protection facility via serial port, DIGSI means that you are using the
port to connect DIGSI or you are not using port B (Disabled).
The flexible protection functions can be configured via parameter FLEXIBLE FUNC.. You can create up to 20
flexible functions by setting a checkmark in front of the desired function (an example is given in the Section
2.19 Reverse-Power Protection Application with Flexible Protection Function). If the checkmark of a function is
removed, all settings and configurations made previously will be lost. After re-selecting the function, all
settings and configurations are in default setting. Setting of the flexible function is done in DIGSI under
“Parameters”, “Additional Functions” and “Settings”. The configuration is done, as usual, under “Parameters”
and “Masking I/O (Configuration Matrix)”.
Please selectFlexible Functions 1...20
Flexible Function 02
Flexible Function 03
Flexible Function 04
Flexible Function 05
Flexible Function 06
Flexible Function 07
Flexible Function 08
Flexible Function 09
Flexible Function 10
Flexible Function 11
Flexible Function 12
Flexible Function 13
Flexible Function 14
Flexible Function 15
Flexible Function 16
Flexible Function 17
Flexible Function 18
Flexible Function 19
Flexible Function 20
The device requires some general information. This may be, for example, the type of annunciation to be
issued in the event of an occurrence of a power system fault.
2.1.2.1
Functional Description
Command-Dependent Messages "No Trip – No Flag"
The storage of indications assigned to local LEDs and the availability of spontaneous indications can be made
dependent on whether the device has issued a trip command. This information is then not issued if during a
system disturbance one or more protection functions have picked up but the 7SJ80 did not trip because the
fault was cleared by another device (e.g. on another line). These messages are then limited to faults in the line
to be protected.
The following figure illustrates the generation of the reset command for stored indications. The instant the
device drops out, the presetting of parameter 610 FltDisp.LED/LCD decides whether the new fault
remains stored or is reset.
Figure 2-1Creation of the reset command for the latched LED and LCD messages
Spontaneous Messages on the Display
You can determine whether or not the most important data of a fault event is displayed automatically after
the fault has occurred (see also Subsection "Fault Messages" in Section "Auxiliary Functions").
2.1.2.2
Setting Notes
Fault Messages
A new pickup of a protection function generally turns off any previously set light displays so that only the
latest fault is displayed at any one time. It can be selected whether the stored LED displays and the spontaneous messages on the display appear after the new pickup or only after a new trip signal is issued. In order to
select the desired mode of display, select the Device submenu in the SETTINGS menu. Under address 610
FltDisp.LED/LCD the two options Target on PU and Target on TRIP ("No trip – no flag") can be
selected.
Use parameter 611 Spont. FltDisp. to specify whether or not a spontaneous fault message should appear
automatically on the display (YES) or not (NO).
Selection of Default Display
The start page of the default display appearing after startup of the device can be selected in the device data
via parameter640 Start image DD. The pages available for each device version are listed in the Appendix
E Default Settings and Protocol-dependent Functions.
Time Synchronization via Port A
If you want the time synchronization of the device to be performed via port A, set the parameters required for
this purpose at the following addresses:
Address 660
IP adr[0](Prim) to 663 IP adr[3]
IP-Addresses 0 to 3, NTP primary
(Prim)
34SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.1 General
Address 664 IP adr[0] (Sec) to 667 IP adr[3]
IP-Addresses 0 to 3, NTP secondary
(Sec)
Address 668 Client activclient for primary and secondary addresses switched
on or off.
Address 669 Daylight Setdaylight saving time switched on or off.
Address 670 Offset TZ/minoffset for the time zone in minutes
Address 671 Offset DayT/minoffset for daylight saving time in minutes
Address 672 W2S month to 675 W2S hourmonth, week (of the month), day of the week, hour
of switching to daylight saving time
Address 676 S2W month to 679 S2W hourmonth, week (of the month), day of the week, hour
of switching to winter time
Access authorization for port A
At address 651 ParEN100(LC)blk you can parameterize a read access option via the EN100 module at port
A. If the parameter is set to ON, you can read out the device parameters using DIGSI or fetch fault records.
IEC 61850 GOOSE Function
At address 700 GOOSE-Stop you can set the GOOSE function of the IEC 61850 protocol to active or not. If
GOOSE-Stop is set to YES, you can release the GOOSE function again via a binary input during operation.
Sundayday of time set winter to summer
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
675W2S hour1 .. 24 2 hour of time set winter to summer
676S2W month1 .. 12 10 month of time set summer to
winter
677S2W week1 .. 5 5 week of time set summer to
winter
678S2W dayMonday
Sundayday of time set summer to winter
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
679S2W hour1 .. 24 3 hour of time set summer to winter
700GOOSE-StopYES
NOGOOSE-Stop
NO
2.1.2.4
No.
Information List
InformationType of
Comments
Information
->Light onSP>Back Light on
-Reset LEDIntSPReset LED
-DataStopIntSPStop data transmission
-Test modeIntSPTest mode
-Feeder gndIntSPFeeder GROUNDED
-Brk OPENEDIntSPBreaker OPENED
-HWTestModIntSPHardware Test Mode
-SynchClockIntSP_EvClock Synchronization
-Distur.CFCOUTDisturbance CFC
1Not configuredSPNo Function configured
2Non ExistentSPFunction Not Available
3>Time SynchSP_Ev>Synchronize Internal Real Time Clock
5>Reset LEDSP>Reset LED
15>Test modeSP>Test mode
16>DataStopSP>Stop data transmission
51Device OKOUTDevice is Operational and Protecting
52ProtActiveIntSPAt Least 1 Protection Funct. is Active
36SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.1 General
No.InformationType of
Information
55Reset DeviceOUTReset Device
56Initial StartOUTInitial Start of Device
67ResumeOUTResume
68Clock SyncErrorOUTClock Synchronization Error
69DayLightSavTimeOUTDaylight Saving Time
70Settings Calc.OUTSetting calculation is running
71Settings CheckOUTSettings Check
72Level-2 changeOUTLevel-2 change
73Local changeOUTLocal setting change
110Event LostOUT_EvEvent lost
113Flag LostOUTFlag Lost
125Chatter ONOUTChatter ON
140Error Sum AlarmOUTError with a summary alarm
160Alarm Sum EventOUTAlarm Summary Event
177Fail BatteryOUTFailure: Battery empty
178I/O-Board errorOUTI/O-Board Error
181Error A/D-conv.OUTError: A/D converter
191Error OffsetOUTError: Offset
193Alarm NO calibrOUTAlarm: NO calibration data available
194Error neutralCTOUTError: Neutral CT different from MLFB
232CT ph mismatchOUTLPCT phase Current Transf. mismatching
233CT gnd mismatchOUTLPCT ground Current Transf. mismatching
301Pow.Sys.Flt.OUTPower System fault
302Fault EventOUTFault Event
303sens Gnd fltOUTsensitive Ground fault
320Warn Mem. DataOUTWarn: Limit of Memory Data exceeded
321Warn Mem. Para.OUTWarn: Limit of Memory Parameter exceeded
322Warn Mem. Oper.OUTWarn: Limit of Memory Operation exceeded
323Warn Mem. NewOUTWarn: Limit of Memory New exceeded
335>GOOSE-StopSP>GOOSE-Stop
502Relay Drop OutSPRelay Drop Out
510Relay CLOSESPGeneral CLOSE of relay
545PU TimeVITime from Pickup to drop out
546TRIP TimeVITime from Pickup to TRIP
10080Error Ext I/OOUTError Extension I/O
10081Error EthernetOUTError Ethernet
10082Error TerminalOUTError Current Terminal
10083Error Basic I/OOUTError Basic I/O
The device requires certain basic data regarding the protected equipment so that the device can adapt to its
desired application. These may be, for instance, nominal power system and transformer data, measured quantity polarities and their physical connections, breaker properties (where applicable) etc. There are also certain
Functions
2.1 General
parameters that are common to all functions, i.e. not associated with a specific protection, control or monitoring function. The following section discusses these parameters.
2.1.3.2
Setting Notes
General
Some P.System Data 1 can be entered directly at the device. See Section 2.25 Notes on Device Operation
for more information regarding this topic.
In DIGSI double-click Settings to open the corresponding dialog box. In doing so, a dialog box with tabs will
open under P.System Data 1 where individual parameters can be configured. The following descriptions
are therefore structured according to these tabs.
Rated Frequency (Power System)
The nominal frequency of the system is set under the Address 214 Rated Frequency. The factory presetting in accordance with the model need only be changed if the device will be employed for a purpose other
than that which was planned when ordering.
In the US device versions (ordering data position 10= C), parameter 214 is preset to 60 Hz. 214.
Phase Rotation (Power System)
Address 209 PHASE SEQ. is used to change the default phase sequence (A B C for clockwise rotation) if
your power system permanently has an anti-clockwise phase sequence (A C B. A temporary reversal of rotation is also possible using binary inputs (see Section 2.21.2 Setting Notes).
Polarity of Current Transformers (Power System)
At address 201 CT Starpoint, the polarity of the wye-connected current transformers is specified (the
following figure applies accordingly to two current transformers). This setting determines the measuring
direction of the device (forward = line direction). Changing this parameter also results in a polarity reversal of
the ground current inputs ΙN or ΙNS.
[polung-stromwandler-020313-kn, 1, en_US]
Figure 2-2Polarity of current transformers
Current Connection Ι4 (Power System)
Here, it is communicated to the device whether the ground current of the current transformer neutral point is
connected to the fourth current input (Ι4). This corresponds to the Holmgreen connection, (see connection
example in C Connection Examples). In this case, parameter 280 Holmgr. for Σi is set to YES. In all other
cases, even if the ground current of the own line is measured via a separate ground current transformer, enter
the setting NO. This setting exclusively affects the function “Current Sum Monitoring” (see Section
2.11.1 Measurement Supervision).
38SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Current Connection (Power System)
Via parameter 251 CT Connect. a special connection of the current transformers can be determined.
The standard connection is A, B, C, (Gnd). It may only be changed if the device is set to measure one or
more ground currents via two current inputs. The standard connection has to be used in all other cases.
The following picture illustrates such a special connection.
Functions
2.1 General
[7sj80-mess-2erdstroeme-20070301, 1, en_US]
Figure 2-3
Measurement of two ground currents, example
The phase currents ΙA and ΙC must be connected to the first current input (terminals F1, F2) and to the third
(terminals F5, F6) The ground current ΙN or ΙNs is connected to the fourth input (terminals F7, F8) as usual, in
this case the ground current of the line. A second ground current, in this case the transformer starpoint
current, is connected to the second current input ΙN2 (terminals F3, F4).
The settings A,G2,C,G; G->B or A,G2,C,G; G2->B are used here. They both define the connection of a
ground current ΙN2 to the second current input (terminals F3, F4). The settings only differ in the calculation of
ΙB. In the case of A,G2,C,G; G2->B, the phase current ΙB is determined from the phase currents ΙA and ΙC and
from the measured ground current ΙN or ΙNs at the fourth current input. In the case of A,G2,C,G; G2->B, the
phase current ΙB is determined from the phase currents ΙA and ΙC and from the measured ground current ΙN2 at
the second current input. This setting is only possible for devices with sensitive ground current transformer.
Therefore, the current ΙN2 at the second current input is referred to ΙN in the flexible protection functions and
in the operational measured values. The sensitive ground current at the fourth current input is referred to ΙNs.
The setting must be selected according to the system requirements.
The following table gives an overview of how the protection functions are assigned to the ground current
Important! The function “Directional Time Overcurrent Protection Ground 67N” may only be enabled if the
ground current of the protected line is measured via ΙN2. This is not the case in the example shown in
Figure 2-3. Here, the ground current of the protected line is measured via ΙN. The function must be deacti-
vated. A connection in which the function can be enabled is illustrated in the Appendix C Connection Exam-
ples Figure C-11
The settings for address 251 are only possible with DIGSI at Display Additional SettingsThe Appendix provides some connection examples at C Connection Examples.
NOTE
The settings in address 2251 CT Connect. for evaluating the phase currents are only effective if address
250 50/51 2-ph prot was set to OFF.
x
x
Ι
N
Ι
N
Current
input 4
(ΙN/ ΙNs)
x
Ι
Ns
Ι
Ns
Voltage Connection (Power System)
Address 213 specifies how the voltage transformers are connected.
VT Connect. 3ph = Van, Vbn, Vcn means that the three phase voltages are wye connected, i.e. the
three phase-to-ground voltages are measured.ground.
VT Connect. 3ph = Vab, Vbc, VGnd means that two phase-to-phase voltages (open delta voltage) and
the displacement voltage V
VT Connect. 3ph = Vab, Vbc means that two phase-to-phase voltages (open delta voltage) are
connected. The third voltage transformer of the device is not used.
VT Connect. 3ph = Vab, Vbc, Vx means that two phase-to-phase voltages (open delta voltage) are
connected. Furthermore, any third voltage Vx is connected that is used exclusively for the flexible protection
functions. The transformer nominal voltages for Vx are set at address 232 and 233.
VT Connect. 3ph = Vab, Vbc, VSyn means that two phase-to-phase voltages (open delta voltage) and
the reference voltage for V
device is used.
VT Connect. 3ph = Vph-g, VSyn is used if the synchronization function of the device is used and only
phase-to-ground voltages are available for the protected object to be synchronized. One of these voltages is
connected to the first voltage transformer; the reference voltage V
former.
The selection of the voltage transformer connection affects the operation of all device functions that require
voltage input.
The settings Vab, Vbc or Vab, Vbc, Vx or Vab, Vbc, VSyn or Vph-g, VSyn do not allow determining
the zero sequence voltage. The associated protection functions are inactive in this case.
The table gives an overview of the functions that can be activated for the corresponding connection type
(depends also on the ordering number). The functions which are not shown are available for all connection
types.
are connected.
GND
are connected. This setting is enabled if the synchronization function of the
SYN
is connected to the third voltage trans-
SYN
40SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Table 2-1Connection Types of the Voltage Transformers
Functions
2.1 General
Connection
Functions
type
Van, Vbn,
Directional
definite
time/
inverse time
overcurrent
protection
phase
yesyesyesnoyesyesyesyes
Directional
definite-
time/ inver-
setime over-
current
protection
ground
Sensitive
ground fault
protection
50Ns, 51Ns,
67Ns
Synchroni-
zation
Fault
locatorQUprotec-
tion
Directional
intermit-
tent
ground
fault
Vcn
Vab, Vbc,
yesyesyesnoyesyesyesyes
VGnd
Vab, Vbc
Vab, Vbc, Vx
Vab, Vbc,
yes
yes
yes
yes
yesno
1)
1)
yes
yes
yes
2)
2)
2)
nonoyesnono
nonoyesnono
yesnoyesnono
VSyn
Vph-g, VSyn
1)
Determination of the direction is only possible by evaluating the negative sequence system (otherwise select zero
nono
yes
2)
yesnononono
sequence system or negative sequence system).
2)
With this type of voltage transformer connection the current elements operate only non-directional, the voltage
elements do not work.
With voltage connections Vab, Vbc, Vab, Vbc, Vx and Vab, Vbc, VSyn the power values are only
available if you have symmetrical voltage conditions within the network. In this case, address 207Vol.Symmetry (Power System Data 1) is set to YES. The power values are not available with setting NO.
Measured values, which due to the chosen voltage connection cannot be calculated, will be displayed as dots.
The Appendix provides some connection examples for all connection types atC Connection Examples.
Fuse
failure
monitor
Distance Unit (Power System)
Address 215 Distance Unit allows you to specify the distance unit (km or Miles) for the fault locator. In
the absence of a fault locator or if this function has been removed, this parameter is of no importance.
Changing the distance unit does not imply an automatic conversion of the setting values that are dependent
on the distance unit. These have to be re-entered at the respective addresses.
ATEX100 (Power System)
Parameter 235 ATEX100 enables meeting the requirements for protecting explosion-protected motors for
thermal replicas. Set this parameter to YES to save all thermal replicas of the 7SJ80 devices in the event of a
power supply failure. After the supply voltage is restored, the thermal replicas will resume operation using the
stored values. Set the parameter to NO, to reset the calculated overtemperature values of all thermal replicas
to zero if the power supply fails.
Nominal Values of Current Transformers (CTs)
At addresses 204 CT PRIMARY and 205 CT SECONDARY, information is entered regarding the primary and
secondary ampere ratings of the current transformers. It is important to ensure that the rated secondary
current of the current transformer matches the rated current of the device, otherwise the device will calculate
incorrect primary data. At addresses 217 Ignd-CT PRIM and 218 Ignd-CT SEC, information is entered
regarding the primary and secondary ampere rating of the current transformer. In case of a normal connection
(neutral point current connected to ΙN transformer), 217 Ignd-CT PRIM and 204 CT PRIMARY must be set
to the same value.
If the device features a sensitive ground current input, parameter 218 Ignd-CT SEC is set to 1 A by default.
For US device models (order item 10= C) parameters 205 and 218 are set by default to 5 A..
If address 251 has been set so that ground currents are measured by two inputs (setting options A,G2,C,G;
G->B or A,G2,C,G; G2->B), you have to set the primary rated current of the second ground transformer
connected to ΙN2 at address 238. secondary ampere rating must conform with the phase current transformer.
To calculated the phase current ΙB correctly, the primary rated current of the ground current transformer,
which is used to calculate ΙB (address 217 or address 238), must be smaller than the primary rated current of
the phase current transformer (address 204).
Nominal Values of Voltage Transformers (VTs)
At addresses 202 Vnom PRIMARY and 203 Vnom SECONDARY, information is entered regarding the primary
nominal voltage and secondary nominal voltage (phase-to-phase) of the connected voltage transformers.
Transformation Ratio of Voltage Transformers (VTs)
Address 206 Vph / Vdelta informs the device of the adjustment factor between the phase voltage and the
displacement voltage. This information is relevant for the processing of ground faults (in grounded systems
and ungrounded systems), for the operational measured value VN and measured-variable monitoring.
If the voltage transformer set provides open delta windings and if these windings are connected to the device,
this must be specified accordingly in address 213 (see above margin heading “Voltage Connection”). Since the
voltage transformer ratio is normally as follows:
(secondary voltage, address 206 Vph / Vdelta) must be set to 3/ √3 = √3 = 1.73 which
ph/VN
must be used if the VN voltage is connected. For other transformation ratios, i.e. the formation of the
displacement voltage via an interconnected transformer set, the factor must be corrected accordingly.
Please take into consideration that also the calculated secondary V0-voltage is divided by the value set in
address 206. Thus, even if the V0-voltage is not connected, address 206 has an impact on the secondary
operational measured value VN.
If Vab, Vbc, VGnd is selected as voltage connection type, parameter Vph / Vdelta is used to calculate
the phase-to-ground voltages and is therefore important for the protection function. With voltage connection
type Van, Vbn, Vcn, this parameter is used only to calculate the operational measured value of the secondary voltage VN.
Trip and Close Command Duration (Breaker)
In address 210 the minimum trip command duration TMin TRIP CMD is set. This setting applies to all protection functions that can initiate tripping.
In address 211 the maximum close command duration TMax CLOSE CMD is set. It applies to the integrated
reclosing function. It must be set long enough to ensure that the circuit breaker has securely closed. An excessive duration causes no problem since the closing command is interrupted in the event another trip is initiated
by a protection function.
Current Flow Monitoring (Breaker)
In address 212 BkrClosed I MIN the pickup threshold of the integrated current flow monitoring function
can be set. This parameter is used by several protection functions (e.g. voltage protection with current criterion, overload protection and circuit breaker maintenance). If the set current value is exceeded, the circuit
breaker is considered closed.
The threshold value setting applies to all three phases, and must take into consideration all used protection
functions.
The pickup threshold for the breaker failure protection is set separately (see 2.17.2 Setting Notes).
42SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Circuit-breaker Maintenance (Breaker)
i
i
i
i
Parameters 260 to 267 are assigned to CB maintenance. The parameters and the different procedures are
explained in the setting notes of this function (see Section 2.23.2 Statistics).
Pickup Thresholds of the Binary Inputs (Thresholds BI)
At address 220 Threshold BI 1 to 226 Threshold BI 7 you can set the pickup thresholds of the binary
inputs of the device. The settings Thresh. BI 176V, Thresh. BI 88V or Thresh. BI 19V are possible.
Two-phase Time Overcurrent Protection (Protection Operating Quantities)
The two-phase overcurrent protection functionality is used in grounded or compensated systems where interaction of three-phase devices with existing two-phase protection equipment is required. Via parameter 250
50/51 2-ph prot the time overcurrent protection can be configured to two or three-phase operation. If the
parameter is set to ON, the value 0 A instead of the measured value for ΙB is used permanently for the
threshold comparison so that no pickup is possible in phase B. All other functions, however, operate in three
phases.
Parameter 613 50N/51N/67N w. defines whether ground fault protection, breaker failure protection or Fuse
Failure Monitor is either to operate using measured values (Ignd (measured))) or the quantities calculated
from the three phase currents (3I0 (calcul.)). In the first case, the measured quantity at the fourth
current input is evaluated. In the latter case, the summation current is calculated from the three phase current
inputs. If the device features a sensitive ground current input (measuring range starts at 1 mA), the ground
fault protection always uses the calculated variable 3I0. In this case, parameter 613 50N/51N/67N w. is not
available.
Functions
2.1 General
Voltage Protection (Protection Operating Quantities)
In a three-phase connection, the fundamental harmonic of the largest of the three phase-to-phase voltages
(Vphph) or phase-ground voltages (Vph-n) or the positive sequence voltage (V1) or the negative sequence
voltage (V2) is supplied to the overvoltage protection elements. In three-phase connection, undervoltage
protection relies either on the positive sequence voltage (V1) or the smallest of the phase-to-phase voltages
(Vphph) or the phase-to-ground voltages (Vph-n). This is configured by setting the parameter value in
address 614 OP. QUANTITY 59 and 615 OP. QUANTITY 27.
With single-phase voltage transformers, a direct comparison of the measured quantities with the threshold
values is carried out and the parameterization of the characteristic quantity switchover is ignored.
NOTE
If parameter 213 VT Connect. 3ph is set to Vph-g, VSyn, the voltage measured by voltage transformer 1 is always used for voltage protection. Then parameters 614 and 615 are not available.
NOTE
If parameter 213 VT Connect. 3ph is set to Vab, Vbc, VSyn or Vab, Vbc or Vab, Vbc, Vx, the
setting option Vph-n for parameter 614 and 615 is not available.
2.1.3.3
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
Thresh. BI 19V
232VXnom PRIMARY0.10 .. 800.00 kV20.00 kVRated Primary Voltage X
233VXnom SECONDARY100 .. 225 V100 VRated Secondary Voltage X
235AATEX100NO
YES
YESStorage of th. Replicas w/o
Power Supply
238Ignd2-CT PRIM.1 .. 50000 A400 AIgnd2-CT rated primary c.
(conn. to I2)
239Ignd2-CT SEC.1A
5A
250A50/51 2-ph protOFF
ON
251ACT Connect.A, B, C, (Gnd)
1AIgnd2-CT rated secondary
current (I2)
OFF50, 51 Time Overcurrent
with 2ph. prot.
A, B, C, (Gnd)CT Connection
A,G2,C,G; G->B
A,G2,C,G; G2->B
252Ph LPCT pol.not reversed
reversed
not reversedPhase LPCT orientation /
polarity
260Ir-5210 .. 50000 A125 ARated Normal Current (52
Breaker)
261OP.CYCLES AT Ir100 .. 1000000 10000 Switching Cycles at Rated
Normal Current
262Isc-5210 .. 100000 A25000 ARated Short-Circuit
Breaking Current
263OP.CYCLES Isc1 .. 1000 50 Switch. Cycles at Rated
Short-Cir. Curr.
264Ix EXPONENT1.0 .. 3.0 2.0 Exponent for the Ix-
Method
265Cmd.via control(Setting options depend on
configuration)
none52 B.Wear: Open Cmd. via
Control Device
266T 52 BREAKTIME1 .. 600 ms80 msBreaktime (52 Breaker)
267T 52 OPENING1 .. 500 ms65 msOpening Time (52 Breaker)
280Holmgr. for ΣiNO
The Multifunctional Protection with Control 7SJ80 is equipped with a fault record memory. The instantaneous
values of the measured values
E50417-G1140-C343-A8, Edition 12.2017
i
i
i
i
Functions
2.1 General
iA, iB, iC, iN, iNs and vA, vB, vC, vA2, vB3, vC1, vN, vX, v
(voltages depending on connection) are sampled at intervals of 1.0 ms (at 50 Hz) and stored in a revolving
buffer (20 samples per cycle). In the event of a fault, the data are recorded for a set period of time, but not for
more than 5 seconds. A maximum of 8 faults can be recorded in this buffer. The fault record memory is automatically updated with every new fault, so no acknowledgment for previously recorded faults is required. In
addition to protection pickup, the recording of the fault data can also be started via a binary input or via the
serial interface.
2.1.4.1
v
AB
v
BC
v
CA
v
A
v
B
v
C
vyes
v
en
v
SYN
v
x
Functional Description
The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4
graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also
calculates additional information from the measured values. Currents and voltages can be presented either as
primary or as secondary values. Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
If port B of the device has been configured correspondingly, the fault record data can be imported by a central
controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation.
Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection
pickup or after a tipping.
If device parameter 651 ParEN100(LC)blk is set to ON, you can also read out fault records via port A (see
Section 2.1.2.2 Setting Notes).
Depending on the selected type of connection of the voltage transformers (address 213 VT Connect. 3ph),
the following measured values are recorded in the fault record:
Voltage connection
Van, Vbn, VcnVab, Vbc,
VGnd
yesyesyesyesyes
yesyesyesyesyes
yesyesyesyesyes
yesyes
yesyes
yesyes
yesyes
Vab, VbcVab, Vbc, VxVab, Vbc, VSynVph-g, VSyn
ph-n
, v
SYN
yesyes
yes
NOTE
The signals used for the binary tracks can be allocated in DIGSI.
NOTE
If one of the current transformer connection types A,G2,C,G; G->B or A,G2,C,G; G2->B has been
selected via parameter 251 CT Connect., the ground current ΙN2 measured with the second current trans-
former is indicated under track ΙN. The ground current detected by the fourth current transformer is indicated under track ΙNs.
Fault recording (waveform capture) will only take place if address 104 OSC. FAULT REC. is set to Enabled.
Other settings pertaining to fault recording (waveform capture) are found in the Osc. Fault Rec.
submenu of the SETTINGS menu. Waveform capture makes a distinction between the trigger instant for an
oscillographic record and the criterion to save the record (address 401 WAVEFORMTRIGGER). Normally, the
trigger is the pickup of a protection element, i.e. the time 0 is defined as the instant the first protection function picks up. The criterion for saving may be both the device pickup (Save w. Pickup) or the device trip
(Save w. TRIP). A trip command issued by the device can also be used as trigger instant (Start w.TRIP), in this case it is also the saving criterion.
A fault event starts with the pickup by any protection function and ends when the last pickup of a protection
function has dropped out. Usually this is also the extent of a fault recording (address 402 WAVEFORM DATA =
Fault event). If automatic reclosing is performed, the entire system fault — with several reclosing attempts
if necessary — can be recorded until the fault has been cleared for good (address 402 WAVEFORM DATA =
Pow.Sys.Flt.). This facilitates the representation of the entire system fault history, but also consumes
storage capacity during the automatic reclosing dead time(s).
The actual storage time begins at the pre-fault time PRE. TRIG. TIME (address 404) ahead of the reference
instant, and ends at the post-fault time POST REC. TIME (address 405) after the storage criterion has reset.
The maximum storage duration of each fault record (MAX. LENGTH) is entered at address 403. Recording per
fault must not exceed 5 seconds. In maximum 8 records can be saved altogether with a maximum total time
of 18 s .
An oscillographic record can be triggered by a status change of a binary input, or from a PC via the operator
interface. Storage is then triggered dynamically. The length of the fault recording is set in address 406 BinInCAPT.TIME (but not longer than MAX. LENGTH, address 403). Pre-fault and post-fault times will add to this.
If the binary input time is set to ∞, the length of the record equals the time that the binary input is activated
(static), but not longer than the MAX. LENGTH (address 403).
2.1.4.3
Addr.
401WAVEFORMTRIGGERSave w. Pickup
Settings
ParameterSetting OptionsDefault SettingComments
Save w. PickupWaveform Capture
Save w. TRIP
Start w. TRIP
402WAVEFORM DATAFault event
Fault eventScope of Waveform Data
Pow.Sys.Flt.
403MAX. LENGTH0.30 .. 5.00 sec2.00 secMax. length of a Waveform
Capture Record
404PRE. TRIG. TIME0.05 .. 0.50 sec0.25 secCaptured Waveform Prior to
Trigger
405POST REC. TIME0.05 .. 0.50 sec0.10 secCaptured Waveform after Event
406BinIn CAPT.TIME0.10 .. 5.00 sec; ∞0.50 secCapture Time via Binary Input
2.1.4.4
No.
Information List
InformationType of
Comments
Information
-FltRecStaIntSPFault Recording Start
4>Trig.Wave.Cap.SP>Trigger Waveform Capture
203Wave. deletedOUT_EvWaveform data deleted
30053Fault rec. run.OUTFault recording is running
48SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.1 General
2.1.5
2.1.5.1
Changing Setting Groups
2.1.5.2
General
Settings Groups
Up to four different setting groups can be created for establishing the device's function settings.
Applications
Setting groups enable the user to save the corresponding settings for each application so that they can
•
be quickly called up when required. All setting groups are stored in the device. Only one setting group
may be active at a time.
Functional Description
During operation the user can switch back and forth setting groups locally, via the operator panel, binary
inputs (if so configured), the service interface using a personal computer, or via the system interface. For
reasons of safety it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected as Enabled during
configuration (see Section 2.1.1.2 Setting Notes). In 7SJ80 relays, four independent setting groups (A to D)
are available. While setting values may vary, the selected functions of each setting group remain the same.
Setting Notes
If setting group change option is not required, Group A is the default selection. Then, the rest of this section is
not applicable.
If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled
(address 103) when the function extent is configured. For the setting of the function parameters, each of the
required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System
Description gives further information on how to copy setting groups or reset them to their status at delivery
and also how to change from one setting group to another.
Section 3.1 Mounting and Connections of this manual tells you how to change between several setting groups
externally via binary inputs.
2.1.5.3
Addr.
302CHANGEGroup A
2.1.5.4
No.
-P-GrpA actIntSPSetting Group A is active
-P-GrpB actIntSPSetting Group B is active
-P-GrpC actIntSPSetting Group C is active
-P-GrpD actIntSPSetting Group D is active
7>Set Group Bit0SP>Setting Group Select Bit 0
8>Set Group Bit1SP>Setting Group Select Bit 1
Group AChange to Another Setting Group
Group B
Group C
Group D
Binary Input
Protocol
Information List
InformationType of
Information
Comments
Functions
2.1 General
2.1.6
2.1.6.1
Power System Data 2
Functional Description
The general protection data (P.System Data 2) include settings associated with all functions rather than a
specific protection or monitoring function. In contrast to the P.System Data 1 as discussed before, they
can be changed with the setting group.
Applications
When the primary reference voltage and the primary reference current of the protected object are set, the
device is able to calculate and output the operational measured value percentage.
For purposes of fault location, a maximum of three different line sections can be considered.
2.1.6.2
Setting Notes
Definition of Nominal Rated Values
At addresses 1101 FullScaleVolt. and 1102 FullScaleCurr., the primary reference voltage (phasetophase) and reference current (phase) of the protected equipment is entered. If these reference sizes match
the primary nominal values of the VTs and CTs, they correspond to the settings in address 202 and 204
(Section 2.1.3.2 Setting Notes). They are generally used to show values referenced to full scale.
Ground Impedance Ratios (only for Fault Location)
The adjustment of the ground impedance ratio is only important for the utilization of the line fault location
function. This is done by entering the resistance ratio RE/RL and the reactance ratio XE/XL.
The values under addresses 1103 and 1104 apply if only one line section is available and to all faults that
occur outside the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, addresses 6001 and 6002
•
for line section 1, addresses 6011 and 6012
•
for line section 1, addresses 6021 and 6022.
•
Resistance ratio RE/RL and reactance ratio XE/XL are calculated formally and do not correspond to the real
and imaginary components of
ZE/ZL. No complex calculation is required! The ratios can be obtained from the
line data using the following formulas:
[formelfehlerorter-260602-kn, 1, en_US]
Where
R
0
X
0
R
1
X
1
– Zero sequence resistance of the line
– Zero sequence reactance of the line
– Positive sequence resistance of the line
– Positive sequence reactance of the line
This data can be used for the entire line or line section, or as distance-related values, since the quotients are
independent of the distance.
Calculation example:
20 kV free line 120 mm2 with the following data:
For ground impedance ratios, the following results:
[formfehl-260602-kn, 1, en_US]
Reactance per Unit Length (only for Fault Location)
The setting of the reactance per unit length is only important for the utilization of the line fault location function. The reactance setting enables the protective relay to indicate the fault location in terms of distance.
The reactance value X' is entered as a reference value x', i.e. in Ω/mile if set to distance unit Miles (address
215, see Section 2.1.3.2 Setting Notes under "Distance Unit") or in Ω/km if set to distance unit km. If, after
having entered the reactance per unit length, the distance unit is changed under address 215, the reactance
per unit length must be reconfigured in accordance with the new distance unit.
The values under address 1106 (km) or 1105 (Miles) apply if only one line section is available and to all faults
that occur outside the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, addresses 6004(km) or 6003 (Miles)
•
for line section 2, addresses 6014 (km) or 6013 (Miles),
•
for line section 3, addresses 6024 (km) or 6023 (Miles).
•
When setting the parameters in DIGSI, the values can also be entered as primary values. In that case the
following conversion to secondary values is not required.
For the conversion of primary values to secondary values the following applies in general:
Functions
2.1 General
[zsekundaer-260602-kn, 1, en_US]
Likewise, the following applies to the reactance per unit length of a line:
[xsekundaer-260602-kn, 1, en_US]
with
N
CTR
N
VTR
— Transformation ratio of the current transformer
— Transformation ratio of the voltage transformer
Calculation example:
In the following, the same line as illustrated in the example for ground impedance ratios (above) and addi-
tional data on the voltage transformers will be used:
Current Transformers
500 A/5 A
Voltage Transformers20 kV/0.1 kV
The secondary reactance per unit length is calculated as follows:
The setting of the line angle is only important for the utilization of the line fault location function. The line
angle can be derived from the line constants. The following applies:
[formel-allg-ltgdaten-1-oz-310702, 1, en_US]
with RL being the ohmic resistance and XL being the reactance of the line.
The value under address 1109 applies if only one line section is available and to all faults that occur outside
the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, address 6005
•
for line section 2, address 6015
•
for line section 3, address 6025
•
This data can be used for the entire line or line section, or as distance-related values, since the quotients are
independent of the distance. It is also irrelevant whether the quotients were derived from primary or secondary values.
Calculation Example::
110 kV free line 150 mm2 with the following data:
R'1 = 0.19 Ω/km (0.31 Ω/mile)
X'1 = 0.42 Ω/km (0.69 Ω/mile)
The line angle is calculated as follows:
[formel-allg-ltgdaten-2-oz-310702, 1, en_US]
The respective address must be set to Line angle = 66°.
Line Length (only for Fault Location)
The setting of the line length is only important for the utilization of the line fault location function. The line
length is required so that the fault location can be given as a reference value (in %). Furthermore, when using
several line sections, the respective length of the individual sections is defined.
The values under address 1110 (km) or 1111 (Miles apply if only one line section is available and to all faults
that occur outside the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, addresses 6006 (km) or 6007 (Miles)
•
for line section 2, addresses 6016 (km) or 6017 (Miles)
•
for line section 3, addresses 6026 (km) or 6027 (Miles)
•
The length set for the entire line must correspond to the sum of lengths configured for the line sections. A
deviation of 10% max. is admissible.
Operating Range of the Overload Protection
The current threshold entered in address 1107 I MOTOR START limits the operating range of the overload
protection to larger current values. The thermal replica is kept constant for as long as this threshold is
exceeded.
52SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Inverting Power Measured Values/Metered Values
The directional values (power, power factor, work and related min., max., mean and setpoint values), calculated in the operational measured values, are usually defined a positive in the direction of the protected
object. This requires that the connection polarity for the entire device was configured accordingly in the
P.System Data 1 (compare also "Polarity of the Current Transformers", address 201). But it is also possible
to make different settings for the "forward" direction" for the protection functions and the positive direction
for the power etc., e.g. to have the active power supply (from the line to the busbar) displayed positively. To
do so, set address 1108 P,Q sign to reversed. If the setting is not reversed (default), the positive
direction for the power etc. corresponds to the "forward" direction for the protection functions. Section
4 Technical Data provides a detailed list of the values in question.
Functions
2.1 General
2.1.6.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer.
1103RE/RL-0.33 .. 7.00 1.00 Zero seq. compensating
factor RE/RL
1104XE/XL-0.33 .. 7.00 1.00 Zero seq. compensating
factor XE/XL
1105x'1A0.0050 .. 15.0000 Ω/mi0.2420 Ω/mifeeder reactance per mile:
5A0.0010 .. 3.0000 Ω/mi0.0484 Ω/mi
x'
1106x'1A0.0050 .. 9.5000 Ω/km0.1500 Ω/kmfeeder reactance per km: x'
5A0.0010 .. 1.9000 Ω/km0.0300 Ω/km
1107I MOTOR START1A0.40 .. 10.00 A2.50 AMotor Start Current (Block
5A2.00 .. 50.00 A12.50 A
1108P,Q signnot reversed
reversed
not reversedP,Q operational measured
49, Start 48)
values sign
1109Line angle10 .. 89 °85 °Line angle
1110Line length0.1 .. 1000.0 km100.0 kmLine length in kilometer
1111Line length0.1 .. 650.0 Miles62.1 MilesLine length in miles
6001S1: RE/RL-0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor RE/RL
6002S1: XE/XL-0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor XE/XL
6003S1: x'1A0.0050 .. 15.0000 Ω/mi0.2420 Ω/miS1: feeder reactance per
5A0.0010 .. 3.0000 Ω/mi0.0484 Ω/mi
mile: x'
6004S1: x'1A0.0050 .. 9.5000 Ω/km0.1500 Ω/kmS1: feeder reactance per
5A0.0010 .. 1.9000 Ω/km0.0300 Ω/km
km: x'
6005S1: Line angle10 .. 89 °85 °S1: Line angle
6006S1: Line length0.1 .. 650.0 Miles62.1 MilesS1: Line length in miles
6007S1: Line length0.1 .. 1000.0 km100.0 kmS1: Line length in kilometer
6011S2: RE/RL-0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor RE/RL
6012S2: XE/XL-0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor XE/XL
6013S2: x'1A0.0050 .. 15.0000 Ω/mi0.2420 Ω/miS2: feeder reactance per
6014S2: x'1A0.0050 .. 9.5000 Ω/km0.1500 Ω/kmS2: feeder reactance per
5A0.0010 .. 1.9000 Ω/km0.0300 Ω/km
km: x'
6015S2: Line angle10 .. 89 °85 °S2: Line angle
6016S2: Line length0.1 .. 650.0 Miles62.1 MilesS2: Line length in miles
6017S2: Line length0.1 .. 1000.0 km100.0 kmS2: Line length in kilometer
6021S3: RE/RL-0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor RE/RL
6022S3: XE/XL-0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor XE/XL
6023S3: x'1A0.0050 .. 15.0000 Ω/mi0.2420 Ω/miS3: feeder reactance per
5A0.0010 .. 3.0000 Ω/mi0.0484 Ω/mi
mile: x'
6024S3: x'1A0.0050 .. 9.5000 Ω/km0.1500 Ω/kmS3: feeder reactance per
5A0.0010 .. 1.9000 Ω/km0.0300 Ω/km
km: x'
6025S3: Line angle10 .. 89 °85 °S3: Line angle
6026S3: Line length0.1 .. 650.0 Miles62.1 MilesS3: Line length in miles
6027S3: Line length0.1 .. 1000.0 km100.0 kmS3: Line length in kilometer
2.1.6.4
No.InformationType of
Information List
Comments
Information
126ProtON/OFFIntSPProtection ON/OFF (via system port)
356>Manual CloseSP>Manual close signal
466.4010 Cmd TripIntSPTrip via control command
501Relay PICKUPOUTRelay PICKUP
511Relay TRIPOUTRelay GENERAL TRIP command
533Ia =VIPrimary fault current Ia
534Ib =VIPrimary fault current Ib
535Ic =VIPrimary fault current Ic
561Man.Clos.DetectOUTManual close signal detected
2720>Enable ANSI#-2SP>Enable 50/67-(N)-2 (override 79 blk)
4601>52-aSP>52-a contact (OPEN, if bkr is open)
4602>52-bSP>52-b contact (OPEN, if bkr is closed)
16019>52 Wear startSP>52 Breaker Wear Start Criteria
1602052 WearSet.failOUT52 Wear blocked by Time Setting Failure
1602752WL.blk I PErrOUT52 Breaker Wear Logic blk Ir-CB>=Isc-CB
1602852WL.blk n PErrOUT52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
18420>Trip via BISP>Trip via Binary Input
18421Trip via GOOSEExSPTrip via GOOSE
18423Direct TripOUTDirect Trip
18424PI Trip NCOUTPI Trip NC(ON,if Device ok & No Trip)
18425>DDI OpenSP>DDI Open status
54SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.1 General
2.1.7
2.1.7.1
2.1.7.2
Interface Selection
IEC 61850 GOOSE Function
2.1.7.3
No.
009.0100 Failure ModulIntSPFailure EN100 Modul
009.0101 Fail Ch1IntSPFailure EN100 Link Channel 1 (Ch1)
009.0102 Fail Ch2IntSPFailure EN100 Link Channel 2 (Ch2)
EN100-Module
Functional Description
The Ethernet EN100-Modul enables integration of the 7SJ80 in 100-Mbit communication networks in control
and automation systems with the protocols according to IEC 61850 standard. This standard permits uniform
communication of the devices without gateways and protocol converters. Even when installed in heterogeneous environments, SIPROTEC 4 relays therefore provide for open and interoperable operation. Parallel to the
process control integration of the device, this interface can also be used for communication with DIGSI and for
inter-relay communication via GOOSE.
Setting Notes
No special settings are required for operating the Ethernet system interface module (IEC 1850, Ethernet
EN100-Modul). If the ordered version of the device is equipped with such a module, it is automatically allo-
cated to the interface available for it, namely Port B.
The GOOSE function can be disabled via a device parameter. For more information, please refer to Section
The overcurrent protection is provided with a total of four elements each for the phase currents and the
ground current. All elements are independent from each other and can be combined as desired.
If it is desired in isolated or resonant-grounded systems that three-phase devices should work together with
two-phase protection equipment, the overcurrent protection can be configured in such a way that it allows
twophase operation besides the three-phase mode (see Section 2.1.3.2 Setting Notes).
The high-set elements 50-2, 50-3, 50N-2, 50N-3 as well as the overcurrent elements 50-1 and 50N-1 always
operate with a definite tripping time (51), the elements 51 and 51N always with an inverse tripping time (50).
Applications
The non-directional overcurrent protection is applicable for networks that are radial and supplied from a
•
single source or open looped networks, for backup protection of differential protective schemes of all
types of lines, transformers, generators and busbars.
General
The overcurrent protection for the ground current can either operate with measured values ΙN or with the
quantities 3Ι0 calculated from the three phase currents. Which values are used depends on the setting of
parameter 613 Gnd O/Cprot. w. and the selected type of connection of the current transformers. Information on this can be found in Chapter 2.1.3.2 Setting Notes, connection examples in Appendix C Connection
Examples. Devices featuring a sensitive ground current input, however, generally use the calculated quantity
3Ι0.
All overcurrent elements enabled in the device may be blocked via the automatic reclosing function
(depending on the cycle) or via an external signal to the binary inputs of the device. Removal of blocking
during pickup will restart time delays. The Manual Close signal is an exception in this case. If a circuit breaker
is manually closed onto a fault, it can be re-opened immediately. For overcurrent elements or high-set
elements the delay may be bypassed via a Manual Close pulse, thus resulting in high speed tripping. This pulse
is extended up to at least 300 ms.
The automatic reclosure function 79 may also initiate immediate tripping for the overcurrent and high-set
elements depending on the cycle.
Pickup of the definite-time elements can be stabilized by setting the dropout times. This protection is used in
systems where intermittent faults occur. Combined with electromechanical relays, it allows different dropout
responses to be adjusted and a time grading of digital and electromechanical relays to be implemented.
Pickup and delay settings may be quickly adapted to system requirements via dynamic setting changeover
(see Section 2.4 Dynamic Cold Load Pickup).
Tripping by the 50-1 and 51 elements (in phases), 50N-1 and 51N elements (in ground path) may be blocked
for inrush conditions by utilizing the inrush restraint feature.
The following table gives an overview of the interconnections to other functions of the devices 7SJ80.
Definite Time, High-set Elements 50-3, 50-2, 50N-3, 50N-2
For each element, an individual pickup value 50-3 PICKUP, 50-2 PICKUP or 50N-3 PICKUP, 50N-2
PICKUP is set. For 50-3 PICKUP and 50N-3 PICKUP, it is possible to measure the Instantaneous in
addition to Fundamental and True RMS. If set to Instantaneous, the element picks up at 2 · √2 · setting
value (rms). Each phase and ground current is compared separately per element with the common pickup
values 50-3 PICKUP, 50-2 PICKUP or 50N-3 PICKUP, 50N-2 PICKUP. If the respective pickup value is
exceeded, this is signaled. After the user-defined time delays 50-3 DELAY, 50-2 DELAY or 50N-3 DELAY,
50N-2 DELAY have elapsed, trip commands are issued which are available for each element. The dropout
value is roughly equal to 95% of the pickup value for currents > 0.3 Ι
neous values has been parameterized for the 50-3 or 50N-3 element, the dropout ratio is set to 90 %.
Pickup can be stabilized by setting dropout times 1215 50 T DROP-OUT or 1315 50N T DROP-OUT. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the function does not drop out at high speed. The trip delay time 50-3 DELAY, 50-2 DELAY or 50N-3 DELAY,
50N-2 DELAY continues running in the meantime. After the dropout delay time has elapsed, the pickup is
reported OFF and the trip delay time is reset unless the threshold 50-3 PICKUP, 50-2 PICKUP or 50N-3PICKUP, 50N-2 PICKUP has been exceeded again. If the threshold is exceeded again during the dropout
delay time, the time is canceled. The trip delay time 50-3 DELAY, 50-2 DELAY or 50N-3 DELAY, 50N-2DELAY continues running in the meantime. If the threshold value is exceeded after this time has elapsed, the
trip command is issued immediately. If the threshold value is not exceeded at this time, there is no reaction. If
the threshold value is exceeded again after expiry of the trip command delay time while the dropout delay
time is still running, tripping is initiated immediately.
These elements can be blocked by the automatic reclosing function (79 AR).
The pickup values of each 50-2, 50-3 Element for phase currents and 50N-2, 50N-3 Element for the ground
current and the element-specific time delays can be set individually.
The following figures give an example of logic diagrams for the high-set elements 50-2 PICKUP or 50N-2
PICKUP. They also apply analogously to the high-set elements 50-3 PICKUP and 50N-3 PICKUP.
Logic diagram for 50-2 high-set element for phases
If parameter MANUAL CLOSE is set to 50-2 instant. or 50-3 instant. and manual close detection is
used, a pickup causes instantaneous tripping, even if the element is blocked via binary input.
The same applies to 79 AR 50-2 inst. or 79 AR 50-3 inst.
58SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
2.2.3
[7sj6x-hochstromst-ie-20061212, 1, en_US]
Figure 2-5
Logic diagram for 50N-2 high-set element
If parameter MANUAL CLOSE is set to 50N-2 instant. or 50N-3 instant. and manual close detection is
used, a pickup causes instantaneous tripping, even if the element is blocked via binary input. The same applies
to AR 50N-2 inst.
The same applies to 79 AR 50N-2 inst. or 79 AR 50N-3 inst.
Definite Time Overcurrent Elements 50-1, 50N-1
For each element an individual pickup value 50-1 PICKUP or 50N-1 PICKUP is set. Apart from Fundamental, the True RMS can also be measured. Each phase and ground current is compared separately with
the setting value 50-1 or 50N-1 for each element. If the respective value is exceeded, this is signaled. If the
inrush restraint feature (see below) is applied, either the normal pickup signals or the corresponding inrush
signals are output as long as inrush current is detected. After user-configured time delays 50-1 DELAY or
50N-1 DELAY have elapsed, a trip signal is issued if no inrush current is detected or inrush restraint is disabled. If the inrush restraint feature is enabled and an inrush condition exists, no tripping takes place but a
message is recorded and displayed indicating when the overcurrent element time delay elapses. Trip signals
and signals on the expiration of time delay are available separately for each element. The dropout value is
approximately 95% of the pickup value for currents > 0.3 INom.
Pickup can be stabilized by setting dropout times 1215 50 T DROP-OUT or1315 50N T DROP-OUT. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the function does not drop out at high speed. The trip-command delay time 50-1 DELAY or 50N-1 DELAY continues
running in the meantime. After the dropout delay time has elapsed, the pickup is reported OFF and the trip
delay time is reset unless the threshold 50-1 or 50N-1 has been exceeded again. If the threshold is exceeded
again during the dropout delay time, the time is canceled. However, the trip-command delay time 50-1
DELAY or 50N-1 DELAY continues running. If the threshold value is exceeded after its expiry, the trip
command is issued immediately. If the threshold value is not exceeded at this time, there is no reaction. If the
threshold value is exceeded again after expiry of the trip-command delay time, while the dropout delay time is
still running, tripping occurs immediately.
Pickup stabilization of the overcurrent elements 50-1 or 50N-1 by means of settable dropout time is deactivated if an inrush pickup is present since an inrush does not represent an intermittent fault.
These elements can be blocked by the automatic reclosing function (79 AR).
The pickup values of each 50-1 element for phase currents and 50N-1 element for the ground current and the
element-specific time delays can be set individually.
The following figures show the logic diagrams for the current elements 50-1 and 50N-1.
[7sj6x-ueberstromst-i-fuer-ph-20061212, 1, en_US]
Figure 2-6
Logic diagram for the 50-1 overcurrent element for phases
If parameter MANUAL CLOSE is set to 50 -1 instant. and manual close detection is used, a pickup causes
instantaneous tripping, even if blocking of the element via binary input is present.
The same applies to 79 AR 50-1 inst.
The dropout delay only operates if no inrush was detected. An incoming inrush will reset a running dropout
Figure 2-7Logic diagram of the dropout delay for 50-1
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
[7sj6x-ueberstromst-ie-20061212, 1, en_US]
Figure 2-8
Logic diagram for the 50N-1 overcurrent current element
If parameter MANUAL CLOSE is set to 50N-1 instant. and manual close detection applies, the trip is initiated as soon as the pickup conditions arrive, even if the element is blocked via a binary input.
The same applies to 79 AR 50N-1 inst.
The pickup values of each 50-1, 50-2 element for the phase currents and 50N-1, 50N-2 element for the
ground current and the valid delay times for each element can be set individually.
The dropout delay only functions if no inrush was detected. An incoming inrush will reset a running dropout
Inverse time overcurrent elements are dependent on the ordering version. They always operate with an
inverse time Curve in accordance with IEC or ANSI standards. The characteristics and associated formulas are
given in the Technical Data.
When configuring one of the inverse-time characteristics, the definite-time elements 50-3, 50-2,and 50-1 are
also active (see Section "Definite-time High-set Current Elements 50-3, 50-2, 50N-3, 50N-2 " and "Definitetime Overcurrent Elements 50-1, 50N-1 ").
A voltage restraint can optionally be set (see Section “Inverse Time Overcurrent Protection (Voltagecontrolled / Voltage-restraint”).
Pickup Behavior
For each element, an individual pickup value 51 PICKUP or 51N PICKUP is set. Apart from Fundamental,
the True RMS can also be measured. Each phase and ground current is separately compared with the setting
value 51 or 51N per element. If a current exceeds 1.1 times the setting value, the corresponding element picks
up and is signaled individually. If the inrush restraint function is used, either the normal pickup signals or the
corresponding inrush signals are issued as long as inrush current is detected. If the 51 element picks up, the
tripping time is calculated from the actual fault current flowing, using an integrating method of measurement.
The calculated tripping time depends on the selected tripping curve. Once this time has elapsed, a trip signal is
issued provided that no inrush current is detected or inrush restraint is disabled. If the inrush restraint function
is enabled and an inrush condition exists, no tripping takes place but a message is issued indicating when the
overcurrent element time delay elapses.
These elements can be blocked by the automatic reclosing feature (79 AR).
For ground current element 51N, the characteristic may be selected independently of the characteristic used
for phase currents.
Pickup values of elements 51 (phase currents) and 51N (ground current) and the relevant time multiplicators
may be set individually.
The following two figures show the logic diagrams for the inverse time overcurrent protection.
Logic diagram of the inverse-time overcurrent protection element for phases
If an ANSI characteristic is configured, parameter 1209 51 TIME DIAL is used instead of parameter 1208 51TIME DIAL.
If parameter MANUAL CLOSE is set to 51 instant. and manual close detection applies, the trip is initiated
as soon as the pickup conditions arrive, even if the element is blocked via a binary input.
If an ANSI characteristic is configured, parameter 1309 51N TIME DIAL is used instead of parameter 1308
51N TIME DIAL.
If parameter MANUAL CLOSE is set to 51N instant. and manual close detection applies, the trip is initiated
as soon as the pickup conditions arrive, even if the element is blocked via binary input.
The same applies to 79 AR 51N inst.
Dropout Behavior
For the ANSI or IEC characteristics, you can select whether an element drops out instantaneously after a
threshold has been undershot or whether dropout is performed by means of disk emulation. "Instantaneous"
means that the picked-up element drops out when 95 % of the pickup value is undershot. For a new pickup,
the time delay starts at zero.
The disk emulation evokes a dropout process (timer counter is decrementing) which begins after de-energization. This process corresponds to the reset of a Ferraris disk (explaining its denomination "disk emulation"). In
case several faults occur in succession, the "history" is taken into consideration due to the inertia of the
Ferraris disk and the time response is adapted. Reset begins as soon as 90 % of the setting value is undershot,
in accordance to the dropout curve of the selected characteristic. In the range between the dropout value
(95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes
are in idle state.
Disk emulation offers advantages when the overcurrent relay elements must be coordinated with conventional electromechanical overcurrent relays located towards the source.
Logic diagram of the inverse-time overcurrent protection element for ground
64SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
2.2.5
Inverse Time Overcurrent Protection 51V (Voltage-controlled /
Voltagerestraint)
Undervoltage Consideration
The inverse time overcurrent protection is provided with an undervoltage detection that can be disabled
(address 1223 VOLT. INFLUENCE). This function can influence overcurrent detection by means of two
different methods:
Voltage-controlled: If a set voltage threshold is undershot, the overcurrent element is released.
•
Voltage-restraint: The pickup threshold of the overcurrent element depends on the voltage magnitude.
•
A lower voltage decreases the current pickup value (see Figure 2-13). In the range between V/V
to 0.25 a linear, directly proportional dependence is realized, and therefore the following applies:
The 51 PICKUP value is decreased proportional to the voltage decrease. Consequently, for constant current Ι
the Ι/ 51 PICKUP ratio is increased and the tripping time is reduced. Compared with the standard curves represented in Section “Technical Data” the tripping curve shifts to the left side as the voltage decreases.
Switching to the lower pickup value or decreasing the pickup threshold is carried out phase-selectively. The
assignment of voltages to current-carrying phases is shown in the following table.
Table 2-3
Controlling voltages in relation to the fault currents
StromSpannung
Ι
A
Ι
B
Ι
C
VA – V
VB – V
VC – V
B
C
A
In order to avoid an unwanted operation in case of a voltage transformer fault, a function blocking is implemented via a binary input controlled by the voltage transformer protection breaker as well as via the deviceinternal measuring voltage failure detection ("Fuse Failure Monitor").
The following two figures show the logic diagrams for the inverse time overcurrent protection with undervoltage consideration.
Logic diagram of the voltage-controlled inverse time overcurrent protection
66SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
[7sjx_logic_51-phase, 1, en_US]
Logic diagram of the voltage-restraint inverse-time overcurrent protection
2.2.6
Figure 2-14
Dynamic Cold Load Pickup Function
It may be necessary to dynamically increase the pickup thresholds of the overcurrent protection if certain
system components exhibit an increased power consumption when they are switched on after a long period
of zero voltage (e.g. air-conditioning systems, heating installations, motors). Thus, a general increase of
pickup thresholds can be avoided taking into consideration such starting conditions.
This dynamic pickup value changeover fuction is common to all overcurrent elements and is described in
Section 2.4 Dynamic Cold Load Pickup. The alternative pickup values can be set individually for each element
of the time overcurrent protection.
When the multi-functional protective relay with local control 7SJ80 is installed, for instance, to protect a
power transformer, large magnetizing inrush currents will flow when the transformer is energized. These
inrush currents may be several times the nominal transformer current, and, depending on the transformer size
and design, may last from several tens of milliseconds to several seconds.
Although pickup of the relay elements is based only on the fundamental harmonic component of the measured currents, false device pickup due to inrush is still a potential problem since, depending on the transformer size and design, the inrush current also comprises a large component of the fundamental.
The 7SJ80 features an integrated inrush restraint function. It prevents the “normal” pickup of 50-1 or 51 relay
elements (not 50-2 and 50-3) in the phases and the ground path of all directional and non-directional overcurrent relay elements. The same is true for the alternative pickup thresholds of the dynamic cold load pickup
function. After detection of inrush currents above a pickup value, special inrush signals are generated. These
signals also initiate fault annunciations and start the associated trip delay time. If inrush conditions are still
present after the tripping time delay has elapsed, a corresponding message (
but the overcurrent tripping is blocked (see also logic diagrams of time overcurrent elements, Figure 2-6 to
Figure 2-11).
Inrush current contains a relatively large second harmonic component (twice the nominal frequency) which is
nearly absent during a fault current. The inrush restraint is based on the evaluation of the 2nd harmonic
present in the inrush current. For frequency analysis, digital filters are used to conduct a Fourier analysis of all
three phase currents and the ground current.
Inrush current is recognized if the following conditions are fulfilled at the same time:
The harmonic content is larger than the setting value 2202 2nd HARMONIC (minimum 0.125 * Ι
•
the currents do not exceed an upper limit value 2205 I Max;
•
an exceeding of a threshold value via an inrush restraint of the blocked element takes place.
•
In this case an inrush in the affected phase is recognized (annunciations 1840 to 1842 and 7558
Gnd Det
Since quantitative analysis of the harmonic components cannot be completed until a full line period has been
measured, pickup will generally be blocked by then. Therefore, assuming the inrush restraint feature is
enabled, a pickup message will be delayed by a full line period if no closing process is present. On the other
hand, trip delay times of the time overcurrent protection feature are started immediately even with the inrush
restraint being enabled. Time delays continue running with inrush currents present. If inrush blocking drops
out after the time delay has elapsed, tripping will occur immediately. Therefore, utilization of the inrush
restraint feature will not result in any additional tripping delays. If a relay element drops out during inrush
blocking, the associated time delay will reset.
„InRush Gnd Det“, see Figure 2-15) and its blocking being carried out.
„....Timeout.“
) is output,
Nom,sec
InRush
);
Cross Blocking
Since inrush restraint operates individually for each phase, protection is ideal where a power transformer is
energized into a single-phase fault and inrush currents are detected on a different healthy phase. However,
the protection feature can be configured to allow that not only this phase element but also the remaining
elements (including ground) are blocked (the so-called CROSS BLOCK function, address 2203) if the permissible harmonic component of the current is exceeded for only one phase.
Please take into consideration that inrush currents flowing in the ground path will
the phase elements.
Cross blocking is reset if there is no more inrush in any phase. Furthermore, the cross blocking function may
also be limited to a particular time interval (address 2204 CROSS BLK TIMER). After expiry of this time
interval, the cross blocking function will be disabled, even if inrush current is still present.
The inrush restraint has an upper limit: Above this (via adjustable parameter 2205 I Max) current blocking is
suppressed since a high-current fault is assumed in this case.
The following figure shows the inrush restraint influence on the time overcurrent elements including crossblocking.
The pickup annunciations of the individual phases (or ground) and the individual element are combined with
each other in such a way that the phase information and the element that has picked up are issued.
Table 2-4Pickup Indications of Overcurrent Protection
Internal indicationFigureOutput indicationFNo.
50-3 A PU
50-2 A PU
50-1 A PU
51 A PU
50-3 B PU
50-2 B PU
50-1 B PU
51 B PU
50-3 C PU
50-2 C PU
50-1 C PU
51 C PU
50N-3 PU
50N-2 PU
50N-1 PU
51N PU
50-3 A PU
50-3 B PU
50-3 C PU
50N-3 PU
50-2 A PU
50-2 B PU
50-2 C PU
50N-2 PUFigure 2-5
50-1 A PU
50-1 B PU
50-1 C PU
50N-1 PUFigure 2-5
51 A PU
51 B PU
51 C PU
51N PUFigure 2-11
(All pickups)
Figure 2-4
Figure 2-6
Figure 2-10
Figure 2-4
Figure 2-6
Figure 2-10
Figure 2-4
Figure 2-6
Figure 2-10
Figure 2-5
Figure 2-8
Figure 2-11
Figure 2-4
Figure 2-4
Figure 2-4
Figure 2-6
Figure 2-6
Figure 2-6
Figure 2-10
Figure 2-10
Figure 2-10
50/51 Ph A PU
50/51 Ph B PU
50/51 Ph C PU
50N/51NPickedup
50-3 picked up
50N-3 picked up
50-2 picked up
50N-2 picked up
50-1 picked up
50N-1 picked up
51 picked up
51N picked up
50(N)/51(N) PU
1762
1763
1764
1765
1767
1768
1800
1831
1810
1834
1820
1837
1761
In the trip signals, the element which initiated the tripping is also indicated.
The 2-phase overcurrent protection functionality is used in isolated or grounded systems where interaction
with existing 2-phase protection equipment is required. As an isolated or grounded system remains operational with a 1-phase ground fault, this protection serves to detect double ground faults with high ground
fault currents. The respective feeder must be switched off only in this case. A 2-phase measurement is sufficient for this purpose. In order to ensure selectivity of the protection in this section of the system, only phases
A and C are monitored.
If 250 50/51 2-ph prot (settable in P.System Data 1) is set to ON, ΙB is not used for threshold comparison. If the fault is a simple ground fault in B, the element will not pick up. A double ground fault is assumed
only after pickup on A or C, causing the element to pick up and trip after the delay time has elapsed.
E50417-G1140-C343-A8, Edition 12.2017
i
i
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
NOTE
With inrush detection activated and inrush only on B, no cross blocking will take place in the other phases.
On the other hand, if inrush with cross blocking is activated on A or C, B will also be blocked.
2.2.10
Application Example
Fast Busbar Protection Using Reverse Interlocking
Each of the current elements can be blocked via binary inputs. A setting parameter determines whether the
binary input operates in the normally open (i.e. actuated when energized) or the normally closed (i.e. actuated when de-energized) mode. This allows fast busbar protection to be applied in star systems or open ring
systems by applying "reverse interlocking". This principle is often used, for example, in distribution systems,
auxiliary systems of power plants and similar systems, where a station supply transformer supplied from the
transmission grid serves internal loads of the generation station via a medium voltage bus with multiple
feeders (Figure 2-16).
The reverse interlocking principle is based on the following: Time overcurrent protection of the busbar feeder
trips with a short time delay T 50-2 independent of the grading times of the feeders, unless the pickup of the
next load-side overcurrent protection element blocks the busbar protection (Figure 2-16). Always the protection element nearest to the fault will trip with the short time delay since this element cannot be blocked by a
protection element located behind the fault. Time elements T 50-1 or T51 are still effective as backup
element. Pickup signals output by the load-side protective relay are used as input message
a binary input at the feeder-side protective relay.
When selecting the time overcurrent protection in DIGSI, a dialog box appears with several tabs for setting the
individual parameters. Depending on the functional scope specified during configuration of the protection
functions under addresses 112 Charac. Phase and 113 Charac. Ground, the number of tabs can vary. If
address FCT 50/51 was set to Definite Time, or Charac. Ground was set to Definite Time, then
only the settings for the definite time elements are available. The selection of TOC IEC or TOC ANSI makes
available additional inverse time characteristics. The superimposed high-set elements 50-2, 50-3 or 50N-2,
50N-3 are available in all these cases.
Parameter 250 50/51 2-ph prot can also be set to activate two-phase overcurrent protection.
Under address 1201 FCT 50/51, overcurrent protection for phases and under address 1301 FCT 50N/51N,
the ground overcurrent protection can be switched ON or OFF.
Pickup values, time delays, and characteristics for ground protection are set separately from the pickup values,
time delays and characteristic curves associated with phase protection. Because of this, relay coordination for
ground faults is independent of relay coordination for phase faults, and more sensitive settings can often be
applied to directional ground protection.
Depending on the setting of parameter 251 CT Connect., the device can also be used in specific system
configuration with regard to current connections. Further information can be found under Section
2.1.3.2 Setting Notes, “Current Connections”.
The comparison values to be used for the respective element can be set in the setting sheets for the elements.
Measurement of the fundamental harmonic (standard method):
•
This measurement method processes the sampled values of the current and filters in numerical order the
fundamental harmonic so that the higher harmonics or transient peak currents remain largely unconsidered.
Measurement of the true RMS value
•
The current amplitude is derived from the sampled values in accordance with the definition equation of
the true RMS value. This measurement method should be selected when higher harmonics are to be
considered by the function (e.g. in capacitor banks).
Measurement with instantaneous values
•
This procedure compares the instantaneous values to the set threshold. The element picks up at 2 · √2 ·
setting value (rms). It does not perform a mean-value calculation and is thus sensitive with regard to
disturbances. This measurement method should only be selected if an especially short pickup time of the
element is required. In this measurement procedure, the operating time of the element is reduced
compared to the measurement of effective values or fundamental harmonics (see “Technical Data”).
The type of the comparison values can be set under the following addresses:
The pickup current of the high-set element 50-2 PICKUP or50-3 PICKUP can be set at address 1202 or
1217. The corresponding delay time 50-2 DELAY or 50-3 DELAY can be configured under address 1203 or
Address 1219 50-3 measurem.
72SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
1218. It is usually used for purposes of current grading intended for large impedances that are prevalent in
transformers or generators. It is specified in such manner that it picks up faults up to this impedance.
Example of the high-set current element 50-2 PICKUP: Transformer used for busbar supply with the
following data:
Vector groupsDy 5
Neutral pointGrounded
Fault power on 110 kV-side1 GVA
Based on the data above, the following fault currents are calculated:
Three-Phase High Voltage Side Fault Currentat 110 kV = 5250 A
Three-Phase Low Voltage Side Fault Currentat 20 kV = 3928 A
On the High Voltage Side Flowingat 110 kV = 714 A
The nominal current of the transformer is:
Ι
= 84 A (High Voltage Side)Ι
NomT, 110
= 462 A (Low Voltage
NomT, 20
Side)
Current Transformer (High Voltage Side)100 A/1 A
Current Transformer (Low Voltage Side)500 A/1 A
Due to the following definition
[hochstrom-260602-kn, 1, en_US]
the following setting applies to the protection device: The 50-2 high-set current element must be set higher
than the maximum fault current which is detected during a low side fault on the high side. To reduce fault
probability as much as possible even when fault power varies, the following setting is selected in primary
values: 50-2 /Ι
= 10, i.e. 50-2 = 1000 A. The same applies analogously when using the high-set element
Nom
50-3.
Increased inrush currents, if their fundamental component exceeds the setting value, are rendered harmless
by delay times (address 1203 50-2 DELAY or 1218 50-3 DELAY).
The principle of the "reverse interlocking" utilizes the multi-element function of the time overcurrent protec-
tion: Element 50-2 PICKUP is applied as a fast busbar protection with a shorter safety delay time 50-2DELAY (e.g. 100 ms). For faults at the outgoing feeders, element 50-2 is blocked. The elements 50-1 or 51
serve as backup protection. The pickup values of both elements (50-1 PICKUP or 51 PICKUP and 50-2 PICKUP)
are set equal. The delay time 50-1 DELAY or 51 TIME DIAL is set in such manner that it overgrades the
delay for the outgoing feeders.
The selected time is an additional delay time and does not include the operating time (measuring time,
dropout time). The delay can also be set to ∞. In this case, the element will not trip after pickup. However,
pickup, will be signaled. If the 50-2 element or the 50-3 element is not required at all, the pickup threshold
50-2 or 50-3 is set to ∞. This setting prevents tripping and the generation of a pickup message.
High-set Current Elements 50N-2, 50N-3 (ground)
The pickup current of the high-set element 50N-2 PICKUP or 50N-3 PICKUP can be set at address 1302 or
1317. The corresponding delay time 50N-2 DELAY or 50N-3 DELAY can be configured under address 1303
or 1318. The same considerations apply to these settings as they did for phase currents discussed earlier.
The selected time is an additional delay time and does not include the operating time (measuring time,
dropout time). The delay can also be set to ∞. In this case, the element will not trip after pickup. However,
pickup, will be signaled. If the 50N-2 element or 50N-3 element is not required at all, the pickup threshold
50N-2 or 50N-3 should be set to ∞. This setting prevents tripping and the generation of a pickup message.
50-1 Element (phases)
For setting the 50-1 element, it is the maximum anticipated load current that must be considered above all.
Pickup due to overload should never occur since in this mode the device operates as fault protection with
correspondingly short tripping times and not as overload protection. For this reason, a setting equal to 20% of
the expected peak load is recommended for line protection, and a setting equal to 40% is recommended for
transformers and motors.
The settable time delay (address 1205 50-1 DELAY) results from the grading coordination chart defined for
the system.
The selected time is an additional delay time and does not include the operating time (measuring time,
dropout time). The delay can also be set to ∞. In this case, the element will not trip after pickup. However,
pickup, will be signaled. If the 50-1 element is not required at all, then the pickup threshold 50-1 should be set
to ∞. This setting prevents tripping and the generation of a pickup message.
50N-1 Element (ground)
The 50N-1 element is normally set based on minimum ground fault current.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of
7SJ80 may be used for the 50N–1 relay element. It can be enabled or disabled for both the phase current and
the ground current in address 2201 INRUSH REST.. The characteristic values of the inrush restraint are listed
in Subsection "Inrush Restraint".
The settable delay time (address 1305 50N-1 DELAY) results from the time coordination chart defined for the
system. For ground currents in a grounded system a separate coordination timer with short time delays can be
applied.
The selected time is an additional delay time and does not include the operating time (measuring time,
dropout time). The delay can also be set to ∞. In this case, the element will not trip after pickup. However,
pickup, will be signaled. If the 50N-1 element is not required at all, the pickup threshold 50N-1 PICKUP should
be set to ∞. This setting prevents tripping and the generation of a pickup message.
Pickup Stabilization (Definite Time)
The configurable dropout times 1215 50 T DROP-OUT or 1315 50N T DROP-OUT can be set to implement a
uniform dropout behavior when using electromechanical relays. This is necessary for a time grading. The
dropout time of the electromechanical relay must be known to this end. Subtract the dropout time of the
device (see Technical Data) from this value and enter the result in the parameters.
51 Element (phases) with IEC or ANSI characteristics
Having set address 112 Charac. Phase = TOC IEC or TOC ANSI when configuring the protection functions (Section 2.1.1.2 Setting Notes), the parameters for the inverse time characteristics will also be available.
If address 112 Charac. Phase was set to TOC IEC, you can select the desired IEC characteristic (NormalInverse, Very Inverse, Extremely Inv. or Long Inverse) at address 1211 51 IEC CURVE. If
address 112 Charac. Phase was set to TOC ANSI, you can select the desired ANSI characteristic (Very
Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv., Extremely Inv. or Definite Inv.) at address 1212 51 ANSI CURVE.
If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already
been included between the pickup value and the setting value. This means that a pickup will only occur if a
current of about 1.1 times the setting value is present. If Disk Emulation was selected at address 1210 51Drop-out, reset will occur in accordance with the reset curve as described before.
The current value is set in address 1207 51 PICKUP. The setting is mainly determined by the maximum
anticipated operating current. Pickup due to overload should never occur since in this mode, the device operates as fault protection with correspondingly short tripping times and not as overload protection.
The corresponding time multiplier for an IEC characteristic is set at address 1208 51 TIME DIAL and in
address 1209 51 TIME DIAL for an ANSI characteristic. It must be coordinated with the time coordination
chart of the system.
74SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
The time multiplier can also be set to ∞. In this case, the element will not trip after pickup. However, pickup
will be signaled. If the 51 element is not required at all, address 112 Charac. Phase should be set to Defi-nite Time during protection function configuration (see Section 2.1.1.2 Setting Notes).
If highly sensitive settings close to the load current are required in weak power systems or transformers, the
element can be stabilized via the undervoltage as an additional criterion for the power system fault. The operating modes can be set in address 1223 VOLT. INFLUENCE. In a voltage-controlled operation, the voltage
threshold is defined via parameter 1224 51V V< below which the current element is released
51N Element (ground) with IEC or ANSI Characteristics
Having set address 113 Charac. Ground = TOC IEC when configuring the protection functions (Section
2.1.1 Functional Scope), the parameters for the inverse time characteristics will also be available. Specify in
address 113 Charac. Ground = TOC IEC the desired IEC characteristic (Normal Inverse, Very
Inverse, Extremely Inv. or Long Inverse). If address 113 Charac. Ground = TOC ANSI, you can
select the desired ANSI characteristic (Very Inverse, Inverse, Short Inverse, Long Inverse,
Moderately Inv., Extremely Inv. or Definite Inv.) in address 1312 51N ANSI CURVE.
If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already
been included between the pickup value and the setting value. This means that a pickup will only occur if a
current of about 1.1 times the setting value is present. If Disk Emulation was selected at address 1310 51Drop-out, reset will occur in accordance with the reset curve as described before.
The current value is set in address 1307 51N PICKUP. The setting is mainly determined by the minimum
anticipated ground fault current.
The corresponding time multiplier for an IEC characteristic is set at address 1308 51N TIME DIAL and at
address 1309 51N TIME DIAL for an ANSI characteristic. This has to be coordinated with the grading coordination chart of the network. For ground currents with grounded network, you can often set up a separate
grading coordination chart with shorter delay times.
The time multiplier can also be set to ∞. In this case, the element will not trip after pickup. However, pickup
will be signaled. If the 51N-TOC elementt is not required at all, address 113 Charac. Ground should be set
to Definite Time during configuration of the protection functions (see Section 2.1.1 Functional Scope).
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
Inrush Restraint
When applying the protection device to transformers where high inrush currents are to be expected, the
7SJ80 can make use of an inrush restraint function for the overcurrent elements 50-1, 51, 50N-1 and 51N.
Inrush restraint is only effective and accessible if address 122 InrushRestraint was set to Enabled. If this
function is not required, then Disabled is set. In address 2201 INRUSH REST., the function is switched ON
or OFF jointly for the overcurrent elements 50-1 PICKUP,51 PICKUP, 50N-1 PICKUP and 51N PICKUP
The inrush restraint is based on the evaluation of the 2nd harmonic present in the inrush current. Upon
delivery from the factory, a ratio Ι2f/Ιf of 15 % is set. Under normal circumstances, this setting will not need to
be changed. The setting value is identical for all phases and ground. However, the component required for
restraint may be adjusted to system conditions in address 2202 2nd HARMONIC. To provide more restraint in
exceptional cases, where energizing conditions are particularly unfavorable, a smaller value can be set in the
aforementioned address, e.g. 12 %. Irrespective of parameter 2202 2nd HARMONIC, rush blocking will only
occur if the absolute value of the 2nd harmonic is at least 0.125 * INom,sec.
The effective duration of the cross-blocking 2203 CROSS BLK TIMER can be set to a value between 0 s
(harmonic restraint active for each phase individually) and a maximum of 180 s (harmonic restraint of a phase
blocks also the other phases for the specified duration).
If the current exceeds the value set in address 2205 I Max, no further restraint will take place for the 2nd
harmonic.
Manual Close Mode (phases ground)
When a circuit breaker is closed onto a faulted line, a high-speed trip by the circuit breaker is usually desired.
For overcurrent or high-set element the delay may be bypassed via a Manual Close pulse, thus resulting in
instantaneous tripping. The internal "Manual close" signal is built from the binary input signal >Manual Close
356
(no.
). The internal "Manual close" signal remains active as long as the binary input signal >Manual Close is
active, but at least for 300 ms (see the following logic diagram). To enable the device to react properly on
occurrence of a fault in the phase element, address 1213 MANUAL CLOSE has to be set accordingly. Correspondingly, address 1313 MANUAL CLOSE is considered for the ground path address. Thus, the user determines for both elements, the phase and the ground element, what pickup value is active with what delay
when the circuit breaker is closed manually.
[lo_7sj6-hand-ein, 1, en_US]
Figure 2-17Manual close feature
External Control Command
If the manual close signal is not sent from 7SJ80 device, i.e. neither via the built-in operator interface nor via a
serial interface, but directly from a control acknowledgment switch, this signal must be passed to a 7SJ80
binary input, and configured accordingly (
CLOSE can become effective. The alternative Inactive means that all elements operate as per configuration
even with manual close and do not get special treatment.
Internal Control Function
If the manual close signal is sent via the internal control function of the device, an internal connection of
information has to be established via CFC (interlocking task level) using the CMD_Information block (see
Figure 2-18).
>Manual Close
), so that the element selected for MANUAL
[handein-260602-kn, 1, en_US]
Figure 2-18Example for the generation of a manual close signal using the internal control function
NOTE
For an interaction between the automatic reclosing function (79 AR) and the control function, an extended
CFC logic is necessary. See margin heading “Close command: Directly or via Control” in the Setting Notes of
the automatic reclosing function (Section 2.15.6 Setting Notes).
Interaction with the Automatic Reclosing Function (phases)
If reclosing follows, high-speed and simultaneous protection against faults with 50-2 or 50-3 is usually
desired. If the fault still exists after the first reclosing, the 50-1 or the 51 element will be initiated with graded
tripping times, that is, element 50-2 or 50-3 will be blocked. You can use the parameters 1214 50-2 active
or 1216 50-3 active active for this purpose to define whether or not the 50-2 or the 50-3 element is
impacted by a release signal of the internal or an external automatic reclosing system. The setting with 79active means that the 50-2 or the 50-3 element will only be released if automatic reclosing is not blocked. If
this is not desired, the setting Always is selected so that the 50-2 or the 50-3 element is always active.
The integrated automatic reclosing function of 7SJ80 also provides the option to individually determine for
each overcurrent element whether tripping or blocking is to be carried out instantaneously or unaffected by
the AR with the set time delay (see Section 2.15 Automatic Reclosing System 79).
Interaction with the Automatic Reclosing Function (ground)
When reclosing occurs, it is desirable to have high-speed protection against faults with 50N-2 or 50N-3. If the
fault still exists after the first reclosing, the 50N-1 or the 51N element will be initiated with coordinated tripping times, that is, element 50N-2 or 50N-3 will be blocked. At address 1314 50N-2 active or 1316 50N-3active active it can be specified whether the 50N-2 or the 50N-3 element should be influenced by the
76SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
release signal of an internal or external automatic reclosing system. Address with 79 active determines
that the 50N-2 or the 50N-3 element will only operate if automatic reclosing is not blocked. If not desired,
select the setting Always so that the 50N-2 or the 50N-3 element will always operate, as configured.
The integrated automatic reclosing function of 7SJ62/64 also provides the option to individually determine for
each overcurrent element whether tripping or blocking is to be carried out instantaneously or unaffected by
the AR with the set time delay (see Section 2.15 Automatic Reclosing System 79).
120851 TIME DIAL0.05 .. 3.20 sec; ∞0.50 sec51 Time Dial
120951 TIME DIAL0.50 .. 15.00 ; ∞5.00 51 Time Dial
121051 Drop-outInstantaneous
121151 IEC CURVENormal Inverse
121251 ANSI CURVEVery Inverse
1213AMANUAL CLOSE50-3 instant.
1214A50-2 activeAlways
1215A50 T DROP-OUT0.00 .. 60.00 sec0.00 sec50 Drop-Out Time Delay
1216A50-3 activeAlways
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
ON50, 51 Phase Time Overcur-
OFF
5A0.50 .. 175.00 A; ∞20.00 A
5A0.50 .. 175.00 A; ∞5.00 A
5A0.50 .. 20.00 A5.00 A
Disk EmulationDrop-out characteristic
Disk Emulation
Normal InverseIEC Curve
Very Inverse
Extremely Inv.
Long Inverse
Very InverseANSI Curve
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
176150(N)/51(N) PUOUT50(N)/51(N) O/C PICKUP
176250/51 Ph A PUOUT50/51 Phase A picked up
176350/51 Ph B PUOUT50/51 Phase B picked up
176450/51 Ph C PUOUT50/51 Phase C picked up
176550N/51NPickedupOUT50N/51N picked up
176750-3 picked upOUT50-3 picked up
176850N-3 picked upOUT50N-3 picked up
176950-3 TRIPOUT50-3 TRIP
177050N-3 TRIPOUT50N-3 TRIP
178750-3 TimeOutOUT50-3 TimeOut
178850N-3 TimeOutOUT50N-3 TimeOut
179150(N)/51(N)TRIPOUT50(N)/51(N) TRIP
180050-2 picked upOUT50-2 picked up
180450-2 TimeOutOUT50-2 Time Out
180550-2 TRIPOUT50-2 TRIP
181050-1 picked upOUT50-1 picked up
181450-1 TimeOutOUT50-1 Time Out
181550-1 TRIPOUT50-1 TRIP
182051 picked upOUT51 picked up
182451 Time OutOUT51 Time Out
182551 TRIPOUT51 TRIP
183150N-2 picked upOUT50N-2 picked up
183250N-2 TimeOutOUT50N-2 Time Out
183350N-2 TRIPOUT50N-2 TRIP
183450N-1 picked upOUT50N-1 picked up
183550N-1 TimeOutOUT50N-1 Time Out
183650N-1 TRIPOUT50N-1 TRIP
183751N picked upOUT51N picked up
183851N TimeOutOUT51N Time Out
183951N TRIPOUT51N TRIP
1840PhA InrushDetOUTPhase A inrush detection
1841PhB InrushDetOUTPhase B inrush detection
1842PhC InrushDetOUTPhase C inrush detection
1843INRUSH X-BLKOUTCross blk: PhX blocked PhY
185150-1 BLOCKEDOUT50-1 BLOCKED
185250-2 BLOCKEDOUT50-2 BLOCKED
185350N-1 BLOCKEDOUT50N-1 BLOCKED
185450N-2 BLOCKEDOUT50N-2 BLOCKED
185551 BLOCKEDOUT51 BLOCKED
185651N BLOCKEDOUT51N BLOCKED
186651 Disk PickupOUT51 Disk emulation Pickup
186751N Disk PickupOUT51N Disk emulation picked up
755150-1 InRushPUOUT50-1 InRush picked up
755250N-1 InRushPUOUT50N-1 InRush picked up
755351 InRushPUOUT51 InRush picked up
80SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
No.InformationType of
Comments
Information
755451N InRushPUOUT51N InRush picked up
7556InRush OFFOUTInRush OFF
7557InRush BLKOUTInRush BLOCKED
7558InRush Gnd DetOUTInRush Ground detected
755967-1 InRushPUOUT67-1 InRush picked up
756067N-1 InRushPUOUT67N-1 InRush picked up
756167-TOC InRushPUOUT67-TOC InRush picked up
756267N-TOCInRushPUOUT67N-TOC InRush picked up
7563>BLOCK InRushSP>BLOCK InRush
7564Gnd InRush PUOUTGround InRush picked up
7565Ia InRush PUOUTPhase A InRush picked up
7566Ib InRush PUOUTPhase B InRush picked up
7567Ic InRush PUOUTPhase C InRush picked up
1003450-3 BLOCKEDOUT50-3 BLOCKED
1003550N-3 BLOCKEDOUT50N-3 BLOCKED
The directional time overcurrent protection comprises three elements each for phase currents and the ground
current that can operate directional or non-directional. All elements are independent of each other and can be
combined as desired.
High current element 67-2 and overcurrent element 67-1 always operate with a definite tripping time, the
third element 67-TOC always operates with inverse tripping time.
Applications
The directional overcurrent protection allows the application of multifunctional protection devices 7SJ80
•
also in systems where protection coordination depends on knowing both the magnitude of the fault
current and the direction of power flow to the fault location.
The non-directional overcurrent protection described in Section 2.2 Overcurrent Protection 50, 51, 50N,
•
51N may operate as overlapping backup protection or may be disabled. Additionally, individual elements
(e.g. 67-2 and/or 67N-2) may be interconnected with the directional overcurrent protection.
For parallel lines or transformers supplied from a single source, only directional overcurrent protection
•
allows selective fault detection.
For line sections supplied from two sources or in ring-operated lines, the overcurrent protection has to be
•
supplemented by the element-specific directional criterion.
General
For parallel lines or transformers supplied from a single source (see Figure 2-19), the second feeder (II) is
opened on occurrence of a fault in the first feeder (I) if tripping of the breaker in the parallel feeder is not
prevented by a directional measuring element (at B). Therefore, where indicated with an arrow (Figure 2-19),
directional overcurrent protection is applied. Please ensure that the "forward" direction of the protection
element is in the direction of the line (or object to be protected). This is not necessarily identical with the
direction of the normal load flow, as shown in Figure 2-19.
Figure 2-19Overcurrent protection for parallel transformers
82SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.3 Directional Overcurrent Protection 67, 67N
For line sections supplied from two sources or in ring-operated lines, the overcurrent protection has to be
supplemented by the directional criterion. Figure 2-20 shows a ring system where both energy sources are
merged to one single source.
Figure 2-20Transmission lines with sources at both ends
Depending on the setting of parameter 613 50N/51N/67N w., the ground current element can operate
either with measured values IN or with the values 3I0 calculated from the three phase currents. Devices
featuring a sensitive ground current input, however, use the calculated quantity 3I0.
The directional orientation Forward, Reverse or Non-Directional can be set individually for each
element (Non-Directional from V4.7 on).
For each element the time can be blocked via binary input or automatic reclosing (cycle-dependent), thus
suppressing the trip command. Removal of blocking during pickup will restart time delays. The Manual Close
signal is an exception. If a circuit breaker is manually closed onto a fault, it can be re-opened immediately. For
overcurrent elements or high-set elements the delay may be bypassed via a Manual Close pulse, thus resulting
in high-speed tripping.
Furthermore, immediate tripping may be initiated in conjunction with the automatic reclosing function (cycle
dependant).
Pickup stabilization for the 67/67N elements of the directional overcurrent protection can be accomplished by
means of settable dropout times. This protection comes into use in systems where intermittent faults occur.
Combined with electromechanical relays, it allows different dropout responses to be adjusted and a time
grading of digital and electromechanical relays to be implemented.
Pickup and delay settings may be quickly adjusted to system requirements via dynamic setting switching (see
Section 2.4 Dynamic Cold Load Pickup).
Utilizing the inrush restraint feature tripping may be blocked by the 67-1, 67-TOC, 67N-1, and 67N-TOC
elements in phases and ground path when inrush current is detected.
The following table gives an overview of these interconnections to other functions of the 7SJ80 devices.
Definite Time Directional High-set Elements 67-2, 67N-2, 67-3, 67N-3
For each element an individual pickup value 67-2 PICKUP, 67-3 PICKUP or 67N-2 PICKUP, 67N-3
PICKUP is set which can be measured as Fundamental or True RMS. Each phase current and the ground
current is compared with the common pickup value for each element 67-2 PICKUP, 67-3 PICKUP or
67N-2 PICKUP, 67N-3 PICKUP, and it is signaled when the value is exceeded provided that the fault direc-
tion is the same as the parameterized direction. After the associated delay times 67-2 DELAY, 67-3 DELAY
or 67N-2 DELAY, 67N-3 DELAY have expired, the tripping commands are initiated which are equally available separately for each element. The dropout value is approximately 95% of the pickup value for currents >
0.3 Ι
Pickup can be stabilized by setting dropout times 1518 67 T DROP-OUT or 1618 67N T DROP-OUT. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the function does not drop out instantaneously. The trip delay times 50-2 DELAY, 67-3 DELAY or 50N-2 DELAY,
67N-3 DELAY continue during that time. After the dropout delay time has elapsed, the pickup is reported
OFF and the trip delay time is reset unless the threshold 50-2 PICKUP, 67-3 PICKUP or 50N-2 PICKUP,
67N-3 PICKUP has been exceeded again. If the threshold is exceeded again during the dropout delay time,
the time is canceled. The trip delay time 50-2 DELAY, 67-3 DELAY or 50N-2 DELAY, 67N-3 DELAY
continues. If the threshold value is exceeded after this time has elapsed, the trip command is issued immediately. If the threshold value is not exceeded at this time, there is no reaction. If the threshold value is
exceeded again after expiry of the trip command delay time, while the dropout delay time is still running, tripping is initiated immediately.
Each of these elements can be directional or non-directional (non-directional from V4.7 on).
These elements can be blocked by the automatic reclosing function (79 AR).
The following figure gives an example of the logic diagram for the high-set elements 67-2 of the phase
currents. The high-set element 67-3 is structured identically.
Logic diagram for directional high-set element 67-2 for phases
If parameter MANUAL CLOSE is set to 67-2 instant. or 67-3 instant. and manual close detection is
present, a pickup causes instantaneous tripping even if the element is blocked via binary input.
The same applies to 79 AR 67-2 or 79 AR 67-3 instantaneous.
2.3.3
Definite Time, Directional Time Overcurrent Elements 67-1, 67N-1
For each element, an individual pickup value 67-1 PICKUP or 67N-1 PICKUP is set which can be measured
as Fundamental or True RMS. Phase and ground currents are compared separately with the common
setting value 67-1 PICKUP or 67N-1 PICKUP. Currents above the setting values are recognized separately
when fault direction is equal to the configured direction. If the inrush restraint function is used, either the
normal pickup signals or the corresponding inrush signals are issued as long as inrush current is detected.
When the relevant delay times 67-1 DELAY, 67N-1 DELAY have expired, a tripping command is issued
unless an inrush has been recognized or inrush restraint is active. If the inrush restraint feature is enabled, and
an inrush condition exists, no tripping takes place, but a message is recorded and displayed indicating when
the overcurrent element time delay elapses. Trip signals and other flags for each element are issued when the
element times out. The dropout value is roughly equal to 95% of the pickup value for currents > 0.3 Ι
Pickup can be stabilized by setting dropout times 1518 67 T DROP-OUT or 1618 67N T DROP-OUT. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the function does not drop out at high speed. The trip-command delay time 50-1 DELAY or 50N-1 DELAY continues
in the meantime. After the dropout delay time has elapsed, the pickup is reported OFF and the trip delay time
is reset unless the threshold 50-1 PICKUP or 50N-1 PICKUP has been exceeded again. If the threshold is
exceeded again during the dropout delay time, the time is canceled. The trip-command delay time 50-1DELAY or 50N-1 DELAY continues in the meantime. Should the threshold value be exceeded after its expiry,
the trip command is issued immediately. If the threshold value is not exceeded at this time, there will be no
reaction. If the threshold value is exceeded again after expiry of the trip-command delay time, while the
dropout delay time is still running, tripping occurs immediately.
The inrush restraint of the overcurrent elements 50-1 PICKUP or 50N-1 PICKUP is disabled via configurable dropout times if an inrush pickup occurs, because the occurrence of an inrush does not constitute an
intermittent fault.
Each of these elements can be directional or non-directional (non-directional from V4.7 on).
These elements can be blocked by the automatic reclosure function (AR).
The following figure shows by way of an example the logic diagram for the directional overcurrent element
Logic diagram for the directional relay element 67-1 for phases
If parameter MANUAL CLOSE is set to 67-1 instant. and manual close detection is present, a pickup
causes instantaneous tripping even if the element is blocked via binary input.
The same applies to 79 AR 67-1 instantaneous.
The dropout delay does only function if no inrush was detected. An approaching inrush resets an already
Inverse Time, Directional Overcurrent Elements 67-TOC, 67N-TOC
Inverse time elements are dependent on the variant ordered. They operate either according to the IEC- or the
ANSI-standard. The characteristics and associated formulas are identical with those of the non-directional
overcurrent protection and are given in the Technical Data. When the inverse time curves are configured, the
definite time elements (67-2, 67-1) are also available.
Pickup Behavior
For each element, an individual pickup value 67-TOC PICKUP or 67N-TOC PICKUP is set which can be
measured as Fundamental or True RMS. Each phase and ground current is separately compared with the
common pickup value 67-TOC PICKUP or 67N-TOC PICKUP of each element. When a current value
exceeds the corresponding setting value by a factor of 1.1, the corresponding phase picks up and a message is
generated phase-selectively assuming that the fault direction is equal to the direction configured. If the inrush
restraint feature is used, either the normal pickup signals or the corresponding inrush signals are issued as
long as inrush current is detected. If the 67-TOC element picks up, the tripping time is calculated from the
actual fault current flowing, using an integrating method of measurement. The calculated tripping time
depends on the selected tripping curve. Once this time has elapsed, a trip signal is issued provided that no
inrush current is detected or inrush restraint is disabled. If the inrush restraint feature is enabled and an inrush
condition exists, no tripping takes place, but a message is recorded and displayed indicating when the overcurrent element time delay elapses.
For ground current element 67N-TOC PICKUP, the characteristic may be selected independently of the characteristic used for phase currents.
Pickup values of the 67-TOC (phases) and 67N-TOC (ground current) and the associated time multipliers may
be set individually.
Each of these elements can be directional or non-directional (non-directional from V4.7 on).
Dropout Behavior
When using an ANSI or IEC curve, it can be selected whether the dropout of an element is to occur instantaneously or whether dropout is to be performed by means of the disk emulation mechanism. "Instantaneously"
means that pickup drops out when the pickup value of approx. 95 % of the set pickup value is undershot. For a
new pickup, the time counter starts at zero.
The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energization. This process corresponds to the reset of a Ferraris disk (explaining its denomination "disk emulation"). In
case several faults occur in succession the "history" is taken into consideration due to the inertia of the Ferraris
disk and the time response is adapted. Reset begins as soon as 90 % of the setting value is undershot, in
accordance to the dropout curve of the selected characteristic. In the range between the dropout value (95 %
of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in
idle state.
Disk emulation offers advantages when the overcurrent relay elements must be coordinated with conventional electromechanical overcurrent relays located towards the source.
The following figure shows by way of an example the logic diagram for the 67-TOC relay element of the directional inverse time overcurrent protection of the phase currents.
Logic diagram for the directional overcurrent protection: 67-TOC relay element
2.3.5
Figure 2-24
Interaction with Fuse Failure Monitor (FFM)
False or undesired tripping can be caused by a measuring voltage that can be caused by either short-circuit or
broken wire in the voltage transformer's secondary system or an operation of the voltage transformer fuse.
Failure of the measuring voltage in one or two phases can be detected, and the directional time overcurrent
elements (Dir Phase and Dir Ground) can be blocked, see logic diagrams.
Undervoltage protection, sensitive ground fault detection and synchronization are also blocked in this case.
For additional information on the operation of the fuse failure monitor, see Section 2.11.1 Measurement
It may be necessary to dynamically increase the pickup values of the directional time overcurrent protection if,
at starting, certain elements of the system show an increased power consumption after a long period of zero
voltage (e.g. air-conditioning systems, heating installations, motors). Thus, a general raise of pickup thresholds can be avoided taking into consideration such starting conditions.
This dynamic pickup value changeover is common to all overcurrent elements and is described in Section
2.4 Dynamic Cold Load Pickup. The alternative pickup values can be set individually for each element of the
directional and non-directional time overcurrent protection.
Inrush Restraint
7SJ80 features an integrated inrush restraint function. It prevents "normal" pickup of the 67-1 or 67-TOC
elements (not 67-2 and 67-3) in the phases and in the ground path of the non-directional and directional
overcurrent protection functions. The same is true for the alternative pickup thresholds of the dynamic cold
load pickup function. If inrush currents are detected, special inrush pickup signals are generated. These signals
also initiate fault recording and start the associated trip delay time. If inrush conditions are still present after
the tripping time delay has elapsed, a corresponding message ("....TimeOut ") is output, but tripping is
blocked (for further information see "Inrush Restraint" in Section 2.2 Overcurrent Protection 50, 51, 50N,
51N).
Determination of Direction
The determination of the fault direction for the phase directional element and the ground directional element
is performed independently.
Basically, the direction determination is performed by determining the phase angle between the fault current
and a reference voltage.
Method of Directional Measurement
For the phase directional element the fault current of the corresponding phase and the unfaulted phasetophase voltage are used as reference voltage. The unfaulted voltage also allows for a correct direction determination even if the fault voltage has collapsed entirely (short-line fault). In phase-to-ground voltage connections, the phase-to-phase voltages are calculated. In a connection of two phase-to-phase voltages and VN, the
third phase-to-phase voltage is also calculated.
With three-phase short-line faults, memory voltage values are used to clearly determine the direction if the
measurement voltages are not sufficient.Upon the expiration of the storage time period (2 s), the detected
direction is saved, as long as no sufficient measuring voltage is available. When closing onto a fault, if no
memory voltage values exist in the buffer, the relay element will trip. In all other cases the voltage magnitude
will be sufficient for determining the direction.
For each directional ground element there are two possibilities of direction determination.
Direction Determination with Zero-sequence System or Ground Quantities
For the directional ground fault elements, the direction can be determined from the zero-sequence system
quantities. In the current path, the ΙN current is valid, when the transformer neutral current is connected to the
device. Otherwise, the device calculates the ground current from the sum of the three phase currents. In the
voltage path, the displacement voltage VN is used as reference voltage if connected. Otherwise the device
calculates as reference voltage the zero-sequence voltage 3 · V0 from the sum of the three phase voltages. If
the magnitude of V0 or 3 · V0 is not sufficient to determine the direction, the direction is undefined. Then the
directional ground element will not initiate a trip signal. The directional ground element cannot be applied
when only two current transformers are used.
90SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Direction Determination with Negative Sequence System
Here, the negative sequence current and as reference voltage the negative sequence voltage are used for the
direction determination. This is advantageous if the zero sequence is influenced via a parallel line or if the zero
voltage becomes very small due to unfavorable zero impedances. The negative sequence system is calculated
from the individual voltages and currents. As with the use of the zero sequence values, a direction determination is carried out if the values necessary for the direction determination have exceeded a minimum threshold.
Otherwise the direction is undetermined.
When voltage transformers are open-delta-connected, direction determination is always based on the negative- sequence quantities.
Cross-Polarized Reference Voltages for Direction Determination
The direction of a phase-directional element is detected by means of a cross-polarized voltage. In a phase-toground fault, the cross-polarized voltage (reference voltage) is 90° out of phase with the fault voltages (see
Figure 2-25). With phase-to-phase faults, the position of the reference voltages changes, depending on the
degree of collapse of the fault voltages, up to 30°.
Figure 2-25Cross-polarized voltages for direction determination
Measured Values for the Determination of Fault Direction
Each phase has its own phase measuring element. The fourth measuring element is used as ground measuring
element. If the current exceeds the pickup threshold of a phase or that of the ground path, direction determination is started by the associated measuring element. In case of a multiphase fault, all phase measuring
elements involved perform their own direction determination. If one of the calculated directions differs from
the set direction, the function picks up.
The following table shows the allocation of measured values for the determination of fault direction for
various causes of pickup.
Table 2-6
Measured Values for the Determination of Fault Direction
or 3 · V0 = |VA + VB + VC|, depending on the connection type of voltages
Ι
A
Ι
A
Ι
A
VB - V
VB - V
VB - V
VB - V
VB - V
VB - V
C
C
C
C
C
C
Ι
B
Ι
B
——
Ι
B
Ι
B
——
Ι
B
Ι
B
Direction Determination of Directional Phase Elements
As already mentioned, the direction determination is performed by determining the phase angle between the
fault current and the reference voltage. In order to satisfy different network conditions and applications, the
reference voltage can be rotated by an adjustable angle. In this way, the vector of the rotated reference
voltage can be closely adjusted to the vector of the fault current in order to provide the best possible result for
the direction determination. Figure 2-26 clearly shows the relationship for the directional phase element
based on a single-phase ground fault in Phase A. The fault current Ι
ϕsc. The reference voltage, in this case VBC for the directional phase element A, is rotated by the setting value
1519 ROTATION ANGLE, positively counter-clockwise. In this case, a rotation by +45°.
Figure 2-26Rotation of the reference voltage, directional phase element
The rotated reference voltage defines the forward and reverse area, see Figure 2-27. The forward area is a
range of ±86° around the rotated reference voltage V
If the vector of the fault current is in this area, the
ref,rot
device detects forward direction. In the mirrored area, the device detects reverse direction. In the intermediate
area, the direction result is undefined.
In a network, the vector of the fault current is usually in the forward or reverse area. If the vector moves out of
one these areas, e.g. the forward area, in direction of the undefined area, it leaves the forward area at V
ref,rot
±86° and reaches the undefined area. If the vector leaves the undefined area in direction of the forward area
92SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Functions
2.3 Directional Overcurrent Protection 67, 67N
(or reverse area), a hysteresis of 2° is added. This hysteresis prevents chattering of the directional result. The
current vector reaches the forward area at ±84° (= 86°-2° hysteresis).
Figure 2-27Forward characteristic of the directional function, directional phase element
Direction Determination of Directional Ground Element with Ground Values
Figure 2-28 shows the treatment of the reference voltage for the directional ground element, also based on a
single-phase ground fault in phase A. Contrary to the directional phase elements, which work with the
unfaulted voltage as reference voltage, the fault voltage itself is the reference voltage for the directional
ground element. Depending on the connection of the voltage transformer, this is the voltage 3V0 (as shown in
Figure 2-28) or VN. The fault current -3Ι0 is phase offset by 180° to the fault current Ι
voltage 3V0 by fault angle ϕsc. The reference voltage is rotated by the setting value 1619 ROTATION ANGLE.
In this case, a rotation by -45°.
sequence voltage is used, as current for the direction determination, the negative sequence system in which
the fault current is displayed. The fault current -3Ι2 is in phase opposition to the fault current Ι
the voltage 3V2 by the fault angle ϕsc. The reference voltage is rotated through the setting value 1619 ROTA-TION ANGLE. In this case, a rotation of -45°.
Figure 2-29Rotation of the reference voltage, directional ground element with negative sequence values
and follows
scA
The forward area is a range of ±86° around the rotated reference voltage V
sequence system current -3Ι2 is in this area, the device detects forward direction.
2.3.9
Reverse Interlocking for Double End Fed Lines
Application Example
The directionality feature of the directional overcurrent protection enables the user to perform reverse interlocking also on double end fed lines using relay element 67-1. It is designed to selectively isolate a faulty line
section (e.g. sections of rings) in high speed, i.e. no long graded times will slow down the process. This
scheme is feasible when the distance between protective relays is not too great and when pilot wires are available for signal transfer via an auxiliary voltage loop.
For each line, a separate data transfer path is required to facilitate signal transmission in each direction. When
implemented in a closed-circuit connection, disturbances in the communication line are detected and
signalled with time delay. The local system requires a local interlocking bus wire similar to the one described
in Subsection "Reverse Interlocking Bus Protection" for the directional overcurrent protection (Section
2.2 Overcurrent Protection 50, 51, 50N, 51N).
During a line fault, the device that detects faults in forward (line) direction using the directional relay element
67-1 will block one of the non-directional overcurrent elements (50-1, 50-TOC) of devices in the reverse direction (at the same busbar) since they should not trip (Figure 2-30). In addition, a message is generated
regarding the fault direction. "Forward" messages are issued when the current threshold of the directional
relay element 67-1 is exceeded and directional determination is done. Subsequently, "forward" messages are
transmitted to the device located in reverse direction.
During a busbar fault, the device that detects faults in reverse (busbar) direction using the directional relay
element 67-1 will block one of the non-directional overcurrent elements (50-1, 50-TOC) of devices at the
opposite end of the same feeder. In addition, a "Reverse" message is generated and transmitted via the auxiliary voltage loop to the relay located at the opposite end of the line.
Figure 2-30Reverse interlocking using directional elements
The directional overcurrent element providing normal time grading operates as selective backup protection.
The following figure shows the logic diagram for the generation of fault direction signals.
[7sj6x-meld-gener-fehlerricht-20060118, 1, en_US]
Figure 2-31Logic diagram for the generation of fault direction signals
2.3.10
Setting Notes
General
When selecting the directional time overcurrent protection in DIGSI, a dialog box appears with several tabs for
setting the associated parameters. Depending on the functional scope specified during configuration of the
protective functions in addresses 115 67/67-TOC and 116 67N/67N-TOC, the number of tabs can vary.
If 67/67-TOC or 67N/67N-TOC is set equal to Definite Time, only the parameters for definite time overcurrent protection are accessible here. If you select TOC IEC or TOC ANSI, the inverse time characteristics is
available, too. The superimposed directional elements 67-3, 67-2 and 67-1or 67N-3, 67N-2 and 67N-1apply in
all these cases.
At address 1501 FCT 67/67-TOC, directional phase overcurrent protection may be switched ON or OFF.
Pickup values, time delays, and characteristic are set separately for phase protection and ground protection.
Because of this, relay coordination for ground faults is independent of relay coordination for phase faults, and
more sensitive settings can often be applied to directional ground protection. Thus, at address 1601 FCT67N/67N-TOC, directional ground time overcurrent protection may be switched ON or OFF independent of
the directional phase time overcurrent protection.
Depending on the parameter 613 50N/51N/67N w., the device can either operate using measured values IN
or the quantities 3I0 calculated from the three phase currents. Devices featuring a sensitive ground current
input generally use the calculated quantity 3Ι0.
The directional orientation of the function is influenced by parameter 201 CT Starpoint (see Section
2.1.3 Power System Data 1).
Measurement Methods
The comparison values to be used for the respective element can be set in the setting sheets for the elements.
Measurement of the Fundamental Harmonic (standard method):
•
This measurement method processes the sampled values of the current and filters in numerical order the
fundamental harmonic so that the higher harmonics or transient peak currents are rejected.
Measurement of the True RMS Value
•
The current amplitude is derived from the sampled value in accordance with the definition equation of
the true RMS value. This measurement method should be selected when higher harmonics are to be
considered by the function (e.g. in capacitor bank).
The type of the comparison values can be set under the following addresses:
The direction characteristic, i.e. the position of the ranges “forward”and “reverse” is set for the phase directional elements under address 1519 ROTATION ANGLE and for the ground directional element under address
1619 ROTATION ANGLE. The short-circuit angle is generally inductive in a range of 30° to 60°. This means
that usually the default settings of +45° for the phase directional elements and -45° for the ground directional
element can be maintained for the adjustment of the reference voltage, as they guarantee a safe direction
result.
Nevertheless, the following contains some setting examples for special applications (Table 2-7). The following
must be observed: With the phase directional elements, the reference voltage (fault-free voltage) for phaseground- faults is vertical on the short-circuit voltage. For this reason, the resulting setting of the angle of rotation is (see also Section 2.3.8 Determination of Direction):
Ref. volt. angle of rotation = 90 - φ
With the ground directional element, the reference voltage is the short-circuit voltage itself. The resulting
setting of the angle of rotation is then:
Ref. volt. angle of rotation = -φ
It should also be noted for phase directional elements that with phase-to-phase faults, the reference voltage is
rotated between 0° (remote fault) and 30° (close-up fault) depending on the collapse of the faulty voltage.
This can be taken into account with a mean value of 15°:
Ref. volt. angle of rotation = 90 - φ
sc
Phase directional element (phaseto-ground fault)
sc
Directional ground element (phaseto-ground fault).
-15°Phase directional element (phase-
sc
to-phase fault)
96SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Table 2-7Setting examples
i
i
Functions
2.3 Directional Overcurrent Protection 67, 67N
Applicationφ
1)
Power flow direction
2)
With the assumption that these are cable lines
k
typical
60°Bereich 30°...0°
30°Bereich 60°...30°
30°Bereich 60°...30°
Setting
Directional Phase
Element
1519 ROTATION
ANGLE
→ 15°
→ 45°
→ 45°
Setting
Directional Ground
Element
1619 ROTATION
ANGLE
–60°
–30°
–30°
Directional Orientation
Directional overcurrent protection normally operates in the direction of the protected object (line, transformer, etc.). If the protection device is properly connected in accordance with one of the circuit diagrams in
Appendix C Connection Examples, this is the “forward” direction.
The directional orientation Forward or Reverse can be set separately for each element. Moreover, each
element can also be operated Non-Directional.
Address 1526 67-3 Direction
•
Address 1523 67-2 Direction
•
Address 1524 67-1 Direction
•
Address 1525 67-TOC Direct.
•
Address 1626 67N-3 Direction
•
Address 1623 67N-2 Direction
•
Address 1624 67N-1 Direction
•
Address 1625 67N-TOC Direct.
•
NOTE
If the threshold value of the 67-1 or 67N-1 element is exceeded, the phase-specific directional indications
“forward” or “reverse” are output (indications 2628 to 2636), independent of whether the fault direction is
the same as the configured direction.
These indications are used for directional comparison protection.
Quantity Selection for Direction Determination for the Directional Ground Element
Parameter 1617 67N POLARIZAT.can be set to specify whether direction determination is accomplished
from the zero sequence quantities or ground quantities (with VN and IN) or from the negative sequence
quantities (with V2 and I2) in the ground directional element. The first option is the preferential setting;
the latter is to be selected in case of danger that the zero voltage be too small due to unfavourable zero impedance or that a parallel line influences the zero system.
NOTE
If parameter 213 VT Connect. 3ph is set to Vab, Vbc, Vab, Vbc, VSyn or Vab, Vbc, Vx, the
direction is always determined using the negative sequence values V2/Ι2. For these voltage connection
types the zero sequence voltage (VN or 3V0) is not available.
Directional High-set Elements 67-2, 67-3 (phases)
The high-current element 67-2 PICKUP or 67-3 PICKUP is set at address 1502 or 1528. The associated
delay 67-2 DELAY or 67-3 DELAY at 1503 or 1529. For setting, the same considerations apply as did for the
non-directional time overcurrent protection in Section 2.2.11 Setting Notes.
The selected time is only an additional time delay and does not include the operating time (measuring time,
dropout time). The delay can be set to ∞. After pickup the element will then not trip. Pickup, however, will be
signaled. If the 67-2 element or 67–3 element is not required at all, the pickup value 67-2 PICKUP or 67-3PICKUP should be set to ∞. For this setting, there is neither a pickup signal generated nor a trip.
Directional High-set Elements 67-2, 67-3 (ground)
The high-current element 67N-2 PICKUP or 67N-3 PICKUP is set at address 1602 or 1628. The associated
delay 67N-2 DELAY or 67N-3 DELAY at 1603 or 1629. The same considerations apply for these settings as
for the phase currents.
The selected time is an additional delay time and does not include the operating time (measuring time,
dropout time). If the delay time is set to ∞, the element does not trip after the pickup, but the pickup condition is signaled. If the directional 67N-2 element or 67N-3 element is not required, set the pickup threshold
67N-2 PICKUP or 67N-3 PICKUP to ∞. This setting prevents tripping and the generation of a pickup indication.
Directional Overcurrent Element 67-1 (phases)
The pickup value of the 67-1 element (67-1 PICKUP) address1504 should be set above the maximum anticipated load current. Pickup due to overload should never occur since in this mode the device operates as fault
protection with correspondingly short tripping times and not as overload protection. For this reason, lines are
set to approx. 20% above the maximum expected (over)load and transformers and motors to approx. 40%.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of
7SJ80 may be used for the 67-1 element (for more information see margin heading "Inrush Restraint").
The delay for directional elements (address 1505 67-1 DELAY) is usually set shorter than the delay for
nondirectional elements (address 1205) since the non-directional elements overlap the directional elements
as backup protection. It should be based on the system coordination requirements for directional tripping.
For parallel transformers supplied from a single source (see "Applications"), the delay of element 67-1 DELAY
located on the load side of the transformers may be set to 0 without provoking negative impacts on selectivity.
The selected time is only an additional time delay and does not include the operating time (measuring time,
dropout time). The delay can be set to ∞. After pickup the element will then not trip. Pickup, however, will be
signaled. If the 67-1 element is not required at all, the pickup value 67-1 PICKUP should be set to ∞. This
setting prevents from tripping and the generation of a pickup message.
Directional Overcurrent Element 67N-1 (ground)
The pickup value of the 67N-1 overcurrent element(1604 67N-1 PICKUP)should be set below the minimum
anticipated ground fault current.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of
7SJ80 may be used for the 67N-1 relay element (67N-1 PICKUP) (for more information see margin heading
"Inrush Restraint").
98SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
The delay is set at address 1605 67N-1 DELAY and should be based on system coordination requirements for
directional tripping. For ground currents in a grounded system a separate coordination chart with short time
delay is often used.
The selected time is only an additional time delay and does not include the operating time (measuring time,
dropout time). The delay can be set to ∞. After pickup the element will then not trip. Pickup, however, will be
signaled. If the 67N-1 element is not required at all, the pickup value 67N-1 PICKUP should be set to ∞. This
setting prevents from tripping and the generation of a pickup message.
Pickup Stabilization (67/67N Directional)
The pickups can also be stabilized via parameterizable dropout times under address 1518 67 T DROP-OUT or
1618 67N T DROP-OUT.
Directional Element 67-TOC with IEC or ANSI Curves (phases)
Having set address 115 67/67-TOC = TOC IEC or TOC ANSI when configuring the protection functions
(Section 2.1.1 Functional Scope), the parameters for the inverse time characteristics will also be available.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint function of
7SJ80 may be used for the 67-TOC element (67-TOC PICKUP) (for more information see margin heading
"Inrush Restraint").
If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already
been included between the pickup value and the setting value. This means that a pickup will only occur if a
current of about 1.1 times the setting value is present. If Address 1510 67-TOC Drop-out is set to DiskEmulation, reset will occur in accordance with the reset curve as described in Section 2.2 Overcurrent
Protection 50, 51, 50N, 51N.
The current value is set in address 1507 67-TOC PICKUP. The setting is mainly determined by the maximum
operating current. Pickup due to overload should never occur, since the device in this operating mode operates as fault protection with correspondingly short tripping times and not as overload protection.
The corresponding element time multiplication factor for an IEC characteristic is set at address 1508 67 TIMEDIAL and in address 1509 67 TIME DIAL for an ANSI characteristic. It must be coordinated with the time
grading of the network.
The time multiplier can also be set to ∞. After pickup the element will then not trip. Pickup, however, will be
signaled. If the 67-TOC element is not required at all, address 115 67/67-TOC should be set to DefiniteTime during protective function configuration (see Section 2.1.1 Functional Scope).
If address 115 67/67-TOC = TOC IEC, you can specify the desired IEC–characteristic (Normal Inverse,
Very Inverse, Extremely Inv. or Long Inverse) in address 1511 67- IEC CURVE. If address 115
67/67-TOC = TOC ANSI you can specify the desired ANSI–characteristic (Very Inverse, Inverse, Short
Inverse, Long Inverse, Moderately Inv., Extremely Inv. oder Definite Inv.) in address 1512
67- ANSI CURVE.
Functions
2.3 Directional Overcurrent Protection 67, 67N
Directional Element 67N-TOC with IEC or ANSI Curves (ground)
Having set address 116 67N/67N-TOC = TOC IEC when configuring the protection functions (Section
2.1.1 Functional Scope), the parameters for the inverse time characteristics will also be available. Specify in
address 1611 67N-TOC IEC the desired IEC characteristic (Normal Inverse, Very Inverse, Extremely
Inv. or Long Inverse). If address 116 67N/67N-TOC was set to TOC ANSI, you can select the desired
ANSI characteristic (Very Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv.,
Extremely Inv. or Definite Inv.) in address 1612 67N-TOC ANSI.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of
7SJ80 may be used for the 67N-TOC element (67N-TOC PICKUP) (for more information see margin heading
"Inrush Restraint").
If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already
been included between the pickup value and the setting value 67N-TOC PICKUP. This means that a pickup
will only occur if a current of about 1.1 times the setting value is present. If Disk Emulation was selected at
address 1610 67N-TOC DropOut, reset will occur in accordance with the reset curve as for the existing
nondirectional time overcurrent protection described in Section 2.2 Overcurrent Protection 50, 51, 50N, 51N.
The current value is set at address 1607 67N-TOC PICKUP. The minimum appearing ground fault current is
most relevant for this setting.
The corresponding element time multiplication factor for an IEC characteristic is set at address 1608 67N-TOCT-DIAL and in address 1609 67N-TOC T-DIAL for an ANSI characteristic. This has to be coordinated with
the system grading coordination chart for directional tripping. For ground currents with grounded network,
you can mostly set up a separate grading coordination chart with shorter delay times.
The time multiplier can also be set to ∞. After pickup the element will then not trip. Pickup, however, will be
signaled. If the 67N-TOC element is not required at all, address 116 67N/67N-TOC should be set to Defi-nite Time during protection function configuration (see Section 2.1.1).
Inrush Restraint
When applying the protection device to transformers where high inrush currents are to be expected, the
7SJ80 can make use of an inrush restraint function for the directional overcurrent elements 67-1 PICKUP,
67-TOC PICKUP, 67N-1 PICKUP and 67N-TOC PICKUP as well as the non-directional overcurrent
elements. The inrush restraint option is enabled or disabled in 2201 INRUSH REST. (in the settings option
non-directional time overcurrent protection). The characteristic values of the inrush restraint are already listed
in the section discussing the non-directional time overcurrent (Section 2.2.11 Setting Notes).
Manual Close Mode (phases, ground)
When a circuit breaker is closed onto a faulted line, a high speed trip by the circuit breaker is often desired. For
overcurrent or high-set element the delay may be bypassed via a Manual Close pulse, thus resulting in instantaneous tripping. The internal "Manual close" signal is built from the binary input signal
356). The internal "Manual close" signal remains active as long as the binary input signal
active, but at least for 300 ms (see the following logic diagram). To enable the device to react properly on
occurrence of a fault in the phase elements after manual close, address 1513 MANUAL CLOSE has to be set
accordingly. Accordingly, address 1613 MANUAL CLOSE is considered for the ground path address. Thus, the
user determines for both elements, the phase and the ground element, what pickup value is active with what
delay when the circuit breaker is closed manually.
>Manual Close
>Manual Close
(no.
is
[lo_7sj6-hand-ein, 1, en_US]
Figure 2-32Manual close feature
External Control Switch
If the manual close signal is not from the 7SJ80 device, that is, neither sent via the built-in operator interface
nor via a serial port but directly from a control acknowledgment switch, this signal must be passed to a 7SJ80
binary input, and configured accordingly (
>Manual Close
), so that the element selected for MANUAL
CLOSE can become effective. Inactive means that all elements (phase and ground) operate with the config-
ured trip times even with manual close.
Internal Control Function
The manual closing information must be allocated via CFC (interlocking task-level) using the CMD_Information
block, if the internal control function is used.
[handein-260602-kn, 1, en_US]
Figure 2-33Example for the generation of a manual close signal using the internal control function
100SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.