Current Transformer Requirements
Default Settings and Protocol-dependent
Functions
1
2
3
4
A
B
C
D
E
E50417-G1140-C343-A8
Functions, Settings, Information
Literature
Glossary
Index
F
i
i
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
This document has been subjected to rigorous technical
review before being published. It is revised at regular intervals, and any modifications and amendments are included
in the subsequent issues. The content of this document has
been compiled for information purposes only. Although
Siemens AG has made best efforts to keep the document as
precise and up-to-date as possible, Siemens AG shall not
assume any liability for defects and damage which result
through use of the information contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of
Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from
time to time.
Document version: E50417-G1140-C343-A8.00
Edition: 12.2017
Version of the product described: V4.7
document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
Registered Trademarks
SIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM® are
registered trademarks of Siemens AG. Any unauthorized
use is illegal. All other designations in this document can
be trademarks whose use by third parties for their own
purposes can infringe the rights of the owner.
Preface
Purpose of the Manual
This manual describes the functions, operation, installation, and commissioning of devices 7SJ80. In particular, one will find:
Information regarding the configuration of the scope of the device and a description of the device func-
•
tions and settings → Chapter 2;
Instructions for Installation and Commissioning → Chapter 3;
•
Compilation of the Technical Data → Chapter 4;
•
As well as a compilation of the most significant data for advanced users → Appendix.
•
General information with regard to design, configuration, and operation of SIPROTEC 4 devices are set out in
the SIPROTEC 4 System Description /1/ SIPROTEC 4 System Description.
Target Audience
Protection-system engineers, commissioning engineers, persons entrusted with the setting, testing and maintenance of selective protection, automation and control equipment, and operating personnel in electrical
installations and power plants.
Scope
This manual applies to: SIPROTEC 4 Overcurrent Time Protection 7SJ80; Firmware-Version V4.7.
Indication of Conformity
Additional StandardsIEEE Std C37.90 (see Chapter 4 "Technical Data")
This product is UL-certified according to the Technical Data. file E194016
[ul-schutz-7sx80-100310, 1, --_--]
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within
specified voltage limits (Low-voltage Directive 2006/95 EC).
This conformity is proved by tests conducted by Siemens AG in accordance with the Council
Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for EMC
directive, and with the standard EN 60255-27 for the low-voltage directive.
The device has been designed and produced for industrial use.
The product conforms with the international standards of the series IEC 60255 and the
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
²
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
²
CAUTION
Comply with all instructions, in order to avoid death or severe injuries.
Comply with all instructions, in order to avoid death or severe injuries.
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
²
4SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
NOTICE
i
i
NOTICE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
²
NOTE
Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
•
Proper storage, setup and installation
•
Proper operation and maintenance
•
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
The equipment must be grounded at the grounding terminal before any connections are made.
•
All circuit components connected to the power supply may be subject to dangerous voltage.
•
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
•
(capacitors can still be charged).
Preface
Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
•
equipment, ensure that the current-transformer circuits are short-circuited.
The limiting values stated in the document must not be exceeded. This must also be considered during
•
testing and commissioning.
Typographic and Symbol Conventions
The following text formats are used when literal information from the device or to the device appear in the
text flow:
Parameter Names
Designators of configuration or function parameters which may appear word-for-word in the display of the
device or on the screen of a personal computer (with operation software DIGSI), are marked in bold letters in
monospace type style. The same applies to titles of menus.
1234A
Parameter addresses have the same character style as parameter names. Parameter addresses contain the
suffix A in the overview tables if the parameter can only be set in DIGSI via the option Display additionalsettings.
Parameter Options
Possible settings of text parameters, which may appear word-for-word in the display of the device or on the
screen of a personal computer (with operation software DIGSI), are additionally written in italics. The same
applies to the options of the menus.
Designators for information, which may be output by the relay or required from other devices or from the
switch gear, are marked in a monospace type style in quotation marks.
Deviations may be permitted in drawings and tables when the type of designator can be obviously derived
from the illustration.
The following symbols are used in drawings:
Device-internal logical input signal
Device-internal logical output signal
Internal input signal of an analog quantity
External binary input signal with number (binary input,
input indication)
External binary output signal with number
(example of a value indication)
External binary output signal with number (device indication) used as
input signal
Example of a parameter switch designated FUNCTION with address
1234 and the possible settings ON and OFF
Besides these, graphical symbols are used in accordance with IEC 60617-12 and IEC 60617-13 or similar.
Some of the most frequently used are listed below:
Analog input variable
AND-gate operation of input values
OR-gate operation of input values
Exclusive OR gate (antivalence): output is active, if only one of the
inputs is active
Coincidence gate: output is active, if both inputs are active or inactive
at the same time
Dynamic inputs (edge-triggered) above with positive, below with
negative edge
Formation of one analog output signal from a number of analog input
signals
Limit stage with setting address and parameter designator (name)
Timer (pickup delay T, example adjustable) with setting address and
parameter designator (name)
6SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Timer (dropout delay T, example non-adjustable)
Dynamic triggered pulse timer T (monoflop)
Static memory (SR flipflop) with setting input (S), resetting input (R),
output (Q) and inverted output (Q), setting input dominant
Static memory (RS-flipflop) with setting input (S), resetting input (R),
output (Q) and inverted output (Q), resetting input dominant
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the software. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
Open Source Software..................................................................................................................................9
The device family SIPROTEC 7SJ80 devices is introduced in this section. An overview of the devices is
presented in their application, characteristics, and scope of functions.
The digital SIPROTEC 7SJ80 overcurrent protection is equipped with a powerful microprocessor. It allows all
tasks to be processed digitally, from the acquisition of measured quantities to sending commands to circuit
breakers. Figure 1-1 shows the basic structure of the 7SJ80.
The measuring inputs (MI) convert the currents and voltages coming from the measuring transformers and
adapt them to the level appropriate for the internal processing of the device. The device provides 4 current
transformers and - depending on the model - additionally 3 voltage transformers. Three current inputs serve
for the input of the phase currents, another current input (ΙN) may be used for measuring the ground fault
current ΙN (current transformer neutral point) or for a separate ground current transformer (for sensitive
ground fault detection ΙNs and directional determination of ground faults ) - depending on the model.
[hw-struktur-7sj80-060606, 1, en_US]
Figure 1-1
The optional voltage transformers can either be used to input 3 phase-to-ground voltages or 2 phase-to-phase
voltages and the displacement voltage (open delta voltage) or any other voltages. It is also possible to connect
two phase-to-phase voltages in open delta connection.
The analog input quantities are passed on to the input amplifiers (IA). The input amplifier IA element provides
a high-resistance termination for the input quantities. It consists of filters that are optimized for measuredvalue processing with regard to bandwidth and processing speed.
The analog-to-digital (AD) transformer group consists of an analog-to-digital converter and memory components for the transmission of data to the microcomputer.
20SIPROTEC 4, 7SJ80, Manual
Hardware structure of the digital multi-functional protective relay 7SJ80
E50417-G1140-C343-A8, Edition 12.2017
Microcomputer System
Apart from processing the measured values, the microcomputer system (μC) also executes the actual protection and control functions. They especially include:
Filtering and preparation of the measured quantities
•
Continuous monitoring of the measured quantities
•
Monitoring of the pickup conditions for the individual protective functions
•
Interrogation of limit values and sequences in time
•
Control of signals for the logic functions
•
Output of control commands for switching devices
•
Recording of messages, fault data and fault values for analysis
•
Management of the operating system and the associated functions such as data recording, real-time
•
clock, communication, interfaces, etc.
The information is distributed via output amplifiers (OA).
•
Binary Inputs and Outputs
The computer system obtains external information through the binary input/output boards (inputs and
outputs). The computer system obtains information from the system (e.g remote resetting) or from external
equipment (e.g. blocking commands). These outputs include, in particular, trip commands to circuit breakers
and signals for the remote indication of important events and conditions.
Introduction
1.1 Overall Operation
Front Panel
Information such as messages related to events, states, measured values and the functional status of the
device are visualized by light-emitting diodes (LEDs) and a display screen (LCD) on the front panel.
Integrated control and numeric keys in conjunction with the LCD enable interaction with the remote device.
These elements can be used to access the device for information such as configuration and setting parameters. Similarly, setting parameters can be accessed and changed if needed.
In addition, control of circuit breakers and other equipment is possible from the front panel of the device.
Interfaces
Communication with a PC can be implemented via the USB DIGSI interface using the DIGSI software, allowing
all device functions to be easily executed.
Communication with a PC is also possible via port A (Ethernet interface) and port B (System/Service interface)
using DIGSI.
In addition to the device communication via DIGSI, port B can also be used to transmit all device data to a
central evaluator or a control center. This interface may be provided with various protocols and physical transmission schemes to suit the particular application.
Power Supply
A power supply unit (Vaux or PS) delivers power to the functional units using the different voltage levels.
Voltage dips may occur if the voltage supply system (substation battery) becomes short-circuited. Usually,
they are bridged by a capacitor (see also Technical Data).
A buffer battery is located under the flap at the lower end of the front cover.
The multi-function numerical overcurrent protection SIPROTEC 4 7SJ80 is used as protection, control and
monitoring unit for busbar feeders. For line protection, the device can be used in networks with grounded,
lowresistance grounded, isolated or a compensated neutral point structure. It is suited for networks that are
radial and supplied from a single source, open or closed looped networks and for lines with sources at both
ends.
The device includes the functions that are usually necessary for protection, monitoring of circuit breaker positions and control of circuit breakers in single and double busbars; therefore, the device can be employed
universally. The device provides excellent backup protection of differential protective schemes of any kind for
lines, transformers and busbars of all voltage levels.
Non-directional overcurrent protection (50, 50N, 51, 51N) is the basic function of the device. There are three
definite time elements and one inverse time element for the phase currents and the ground current. For the
inverse time elements, several characteristics of different standards are provided. Alternatively, a user-defined
characteristic can be used for the sensitive ground fault detection.
Further protection functions included are the negative sequence protection, overload protection, circuit
breaker failure protection and ground fault protection.
Depending on the ordered variant, further protection functions are included, such as frequency protection,
overvoltage and undervoltage protection, and ground fault protection for high-resistance ground faults (directional or non-directional).
Apart from the short circuit protection functions mentioned before, there are further protection functions
possible as order variants. The overcurrent protection can, for example, be supplemented by a directional
overcurrent protection.
The automatic reclosing function enables several different reclosing cycles for overhead lines. An external
automatic reclosing system can also be connected. To ensure quick detection of the fault location after a short
circuit, the device is equipped with a fault locator.
Before reclosing after a three-pole tripping, the device can verify the validity of the reclosure via a voltage
check and/or a synchrocheck. The synchrocheck function can also be controlled externally.
Control Functions
The device provides a control function which can be accomplished for activating and deactivating the switchgear via operator buttons, port B, binary inputs and - using a PC and the DIGSI software - via the front interface.
The status of the primary equipment can be transmitted to the device via auxiliary contacts connected to
binary inputs. The present status (or position) of the primary equipment can be displayed on the device, and
used for interlocking or alarm condition monitoring. The number of operating equipments to be switched is
limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for
the switch position indications. Depending on the primary equipment being controlled, one binary input
(single point indication) or two binary inputs (double point indication) may be used for this process.
The capability of switching primary equipment can be restricted by a setting associated with switching
authority (Remote or Local), and by the operating mode (interlocked/non-interlocked, with or without password request).
Processing of interlocking conditions for switching (e.g. switchgear interlocking) can be established with the
aid of integrated, user-configurable logic functions.
Messages and Measured Values; Recording of Event and Fault Data
The operational indications provide information about conditions in the power system and the device. Measurement quantities and values that are calculated can be displayed locally and communicated via the serial
interfaces.
Device messages can be assigned to a number of LEDs on the front cover (allocatable), can be externally
processed via output contacts (allocatable), linked with user-definable logic functions and/or issued via serial
interfaces.
22SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
During a fault (system fault) important events and changes in conditions are saved in fault protocols (Event
Log or Trip Log). Instantaneous fault values are also saved in the device and may be analyzed subsequently.
Communication
The following interfaces are available for communication with external operating, control and memory
systems.
The USB DIGSI interface on the front cover serves for local communication with a PC. By means of the
SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this operatorinterface, such as specifying and modifying configuration parameters and settings, configuring user-specific
logic functions, retrieving operational messages and measured values, inquiring device conditions and measured values, issuing control commands.
Depending on the ordered variant, additional interfaces are located at the bottom of the device. They serve for
establishing extensive communication with other digital operating, control and memory components:
Port A serves for DIGSI communication directly on the device or via network. Furthermore, 2 SICAM I/O units
7XV5673 can be connected to this port. Port A can also be used for time synchronization using the NTP
protocol.
Port B serves for central communication between the device and a control center. It can be operated via data
lines or fiber optic cables. For the data transfer, there are standard protocols in accordance with IEC 60870-5103 available. The integration of the devices into the SINAUT LSA and SICAM automation systems can also be
implemented with this profile.
Alternatively, additional connection options are available with PROFIBUS DP and the DNP3.0 and MODBUS
protocols. If an EN100 module is available, you can use the protocols IEC61850, PROFINET or DNP3 TCP.
Furthermore, connecting a SICAM I/O unit is possible via IEC651850 GOOSE.
Complete digital processing and control of measured values, from the sampling of the analog input quan-
•
tities to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear
devices
Total electrical separation between the internal processing stages of the device and the external trans-
•
former, control, and DC supply circuits of the system because of the design of the binary inputs, outputs,
and the DC or AC converters
Complete set of functions necessary for the proper protection of lines, feeders, motors, and busbars
•
Easy device operation through an integrated operator panel or by means of a connected personal
•
computer running DIGSI
Continuous calculation and display of measured and metered values on the front of the device
•
Storage of min./max. measured values (slave pointer function) and storage of long-term mean values
•
Recording of event and fault data for the last 8 system faults (fault in a network) with real-time informa-
•
tion as well as instantaneous values for fault recording for a maximum time range of 20 s
Constant monitoring of the measured quantities, as well as continuous self-diagnostics covering the
•
hardware and software
Communication with SCADA or substation controller equipment via serial interfaces through the choice
•
of data cable, modem, or optical fibers
Battery-buffered clock which can be synchronized via a synchronization signal at the binary input or via a
•
protocol
Switching statistics: Counting the number of trip commands initiated by the device, logging the currents
•
of the last switch-off operation initiated by the device, and accumulating the eliminated short-circuit
currents of each breaker pole
Operating hours counter: Counting the operating hours of the protected object under load
•
Commissioning aids such as connection and direction check, status indication of all binary inputs and
•
outputs, easy testing of port B, and influencing of information at port B during test operation.
Time Overcurrent Protection 50, 51, 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
•
for phase current and ground current ΙN or summation current 3Ι
Two-phase operation of the overcurrent protection (ΙA, ΙC) is possible
•
For inverse-time overcurrent protection, selection from various characteristics of different standards
•
possible
Blocking is possible, e.g. for reverse interlocking with any element
•
Instantaneous tripping by any element is possible when switching onto a fault
•
In-rush restraint with second harmonic current quantities.
•
Ground Fault Protection 50N, 51N
0
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
•
applicable for grounded or high-resistance grounded systems
For inverse-time overcurrent protection, selection from various characteristics of different standards
•
24SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
In-rush restraint with second harmonic current quantities
•
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
•
Directional Time Overcurrent Protection 67, 67N
Three definite time overcurrent protection elements and one inverse time overcurrent protection
•
element for the phase operate in parallel to the non-directional overcurrent elements. Their pickup values
and time delays can be set independently of these.
Direction determination with cross-polarized voltages and voltage memory and dynamically unlimited
•
direction sensitivity
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summa-
Statistical methods to help adjust maintenance intervals for CB contacts according to their actual wear
•
several independent subfunctions have been implemented(ΣΙ-procedure, ΣΙx-procedure, 2P-procedure
•
and Ι2t-procedure)
Acquisition and conditioning of measured values for all subfunctions operates phase-selective using one
•
procedure-specific threshold per subfunction.
User Defined Functions
Freely programmable linking of internal and external signals in order to implement user-defined logic
•
functions
All standard logic functions (AND, OR, NOT, EXCLUSIVE-OR, etc.)
•
Time delays and limit value interrogations
•
Processing of measured values, including zero suppression, adding a knee curve for a transducer input,
•
and live-zero monitoring.
Breaker Control
Switching devices can be opened and closed manually using control keys, programmable function keys,
•
via port B (e.g. of SICAM or LSA), or via the user interface (using a personal computer and the DIGSI operating software)
Feedback of switching states via the switch auxiliary contacts
•
Plausibility monitoring of the circuit breaker position and check of interlocking conditions.
•
28SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
2
Functions
This chapter describes the numerous functions available on the SIPROTEC 4 device 7SJ80. It shows the setting
possibilities for each function in maximum configuration. Information with regard to the determination of
setting values as well as formulas, if required, are also provided.
Based on the following information, it can also be determined which of the provided functions should be
used.
2.1General30
2.2Overcurrent Protection 50, 51, 50N, 51N56
2.3Directional Overcurrent Protection 67, 67N82
2.4Dynamic Cold Load Pickup106
2.5Single-Phase Overcurrent Protection112
2.6Voltage Protection 27, 59122
2.7Negative Sequence Protection 46132
2.8Frequency Protection 81 O/U138
2.9Undervoltage-controlled reactive power protection (27/Q)142
The settings associated with the various device functions can be modified using the operating or service interface in DIGSI in conjunction with a personal computer. Some parameters can also be changed using the
controls on the front panel of the device. The procedure is described in detail in the SIPROTEC System Description /1/ SIPROTEC 4 System Description.
Functional Scope
The 7SJ80 relay contains protection functions as well as auxiliary functions. The hardware and firmware is
designed for this scope of functions. Additionally, the control functions can be matched to the system requirements. Individual functions can be enabled or disabled during the configuration procedure. The interaction of
functions may also be modified.
Functional Description
Example for the configuration of the functional scope:
A protected system consists of overhead lines and underground cables. Since automatic reclosing is only
needed for the overhead lines, the automatic reclosing function is not configured or “disabled” for the relays
protecting the underground cables.
The available protection and additional functions can be configured as Enabled or Disabled. For individual
functions, a choice between several alternatives may be possible, as described below.
Functions configured as Disabled are not processed by the 7SJ80. There are no messages and corresponding
settings (functions, limit values) queried during configuration.
NOTE
Available functions and default settings are depending on the order variant of the relay (see A Ordering
Information and Accessories).
2.1.1.2
Setting the Functional Scope
Special Features
Setting Notes
Your protection device is configured using the DIGSI software. Connect your personal computer either to the
USB port on the device front or to port A or port B on the bottom side of the device depending on the device
version (ordering code). The operation via DIGSI is explained in the SIPROTEC 4 System Description.
The Device Configuration dialog box allows you to adjust your device to the specific system conditions.
Password no. 7 is required (for parameter set) for changing configuration parameters in the device. Without
the password the settings can only be read but not edited and transmitted to the device.
Most settings are self-explanatory. The special cases are described in the following.
If you want to use the setting group change function, set address 103 Grp Chge OPTION to Enabled. In
this case, you can select up to four different groups of function parameters between which you can switch
quickly and conveniently during operation. Only one setting group can be used when selecting the option
Disabled.
For the elements associated with non-directional overcurrent protection 50(N), 51(N) (phase and ground),
various tripping characteristics can be selected at addresses 112 Charac. Phase and 113 Charac.Ground. If only the definite time characteristic is desired, select Definite Time. Alternatively, you can
select between inverse-time curves according to IEC standard (TOC IEC) or ANSI standard (TOC ANSI). The
dropout behavior of the IEC and ANSI curves is specified at address 1210 or 1310 when configuring the time
overcurrent protection.
30SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Loading...
+ 532 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.