Siemens SIPART PS2 Series, SIPART PS2, SIPART PS2 PA, SIPART PS2 EEx-d, SIPART PS2 FF Technical Description

...
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
6/2 Product overview
6/3 SIPART PS2
6/3 Technical description 6/8 Technical specifications 6/8 - all versions 6/9 - SIPART PS2 6/11 - SIPART PS2 PA 6/13 - SIPART PS2 FF 6/15 - Option modules 6/18 Ordering data 6/18 - SIPART PS2, PS2 PA, PS2 FF 6/19 - SIPART PS2 EEx-d, PS2 EEx-d PA,
6/20 - Accessories 6/22 Dimensionsal drawings 6/23 Schematics 6/24 Mounting kits
Software
Sec. 9 SIMATIC PDM, for parameterize
HART and PROFIBUS P
PS2 EEx-d FF
A devices
You can download all instructions, cata­logs and certificates for SIPART PS2 free of charge at the following Internet address:
www.siemens.com/sipartps2
Siemens FI 01 · 2009
Electropneumatic positioners
6
© Siemens AG 2008

Product overview

Overview
Electropneumatic positioners SIPART PS2
Application Device description Catalog
Position control Pneumatic linear or part­turn actuators, also for intrinsically-safe opera­tion
As above, but in flame­proof casing for explo­sion-proof application
SIPART PS2
Universal device for positioning pneumatic actuators
• Connection: 4 to 20 mA
• HART, PROFIBUS PA or Foundation Fieldbus
• Local manual operation
• Binary inputs and outputs
• Diagnosis functions
• Blocking function
• Automatic startup
SIPART PS2
As above, but in flameproof aluminium casing
page
6/3 SIMATIC PDM
6/3 SIMATIC PDM
Software for parameterization
6/2
Siemens FI 01 · 2009
© Siemens AG 2008
Overview
SIPART PS2 electropneumatic positioner
Electropneumatic positioners

SIPART PS2

Technical description

Benefits
SIPART PS2 positioners offer decisive advantages:
• Simple installation and automatic commissioning (self-adjust­ment of zero and span)
• Simple operation with
- Local operation and configuration of the device using three
input keys and a user-friendly two-line LCD
- Programming through SIMATIC PDM
• Very high-quality control thanks to an online adaptation proce­dure
• Negligible air consumption in stationary operation
• "Tight shut-off" function (ensures maximum positioning pres­sure on the valve seat)
• Numerous functions can be activated by simple configuring (e.g. characteristics and limits)
• Extensive diagnosis functions for valve and actuator
• Only one device version for linear and part-turn actuators
• Few moving parts, hence insensitive to vibrations
• External non-contacting position sensor as option for extreme ambient conditions
• "Intelligent solenoid valve": Partial Stroke Test and solenoid valve function in a single device
• Partial Stroke Test e.g. for safety valves
• SIL (Safety Integrity Level) 2
• Can also be operated with natural gas
SIPART PS2 EEx d electropneumatic positioner in flameproof casing
SIPART PS2 in stainless steel casing
The SIPART PS2 electropneumatic positioner is used to control the final control element of pneumatic linear or part-turn actua­tors. The electropneumatic positioner moves the actuator to a valve position corresponding to the setpoint. Additional function inputs can be used to block the valve or to set a safety position. A binary input is present as standard in the basic device for this purpose.
Application
The SIPART PS2 positioner is used, for example, in the following industries:
• Chemical/petrochemical
• Power stations
• Paper and glass
• Water, waste water
• Food and pharmaceuticals
• Offshore plants
The SIPART PS2 positioner is available:
• For single-action actuators: in plastic, stainless steel or alumi­num casings, as well as flameproof aluminium casing (EEx d)
• For double-action actuators: in plastic and stainless steel cas­ing, as well as flameproof aluminum casing (EEx d)
• For non-hazardous applications
• For hazardous applications in the designs
- as intrinsically-safe device (EEx ia/ib) or
- in flameproof aluminum casing (EEx d) or
- in EEx n design (non sparking)
and in the versions:
• 0/4 to 20 mA control communication without/with communica­tion through HART signal
• With PROFIBUS PA communication interface
• With FOUNDATION Fieldbus (FF) communications interface.
Explosion-proof versions
The basic version of the device is available in an intrinsically­safe design with degr with approval for zone 2/zone 22 (dust).
Operation in zone 1 is permitted when enclosed in the flame­proof casing version SIPART PS2 EEx d. (see "Technical Data"). It is then permissible to use all option modules (except external actuator travel detection systems, SIA module, limit value con­tact module and NCS).
otection EEx ia/ib or in a design
ee of pr
6
Siemens FI 01 · 2009
6/3
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical description
6
Stainless steel casing for extreme ambient conditions
The SIPART PS2 is available in a stainless steel casing (without window in the lid) for use in particularly aggr (e.g. offshore operation, chlorine plants etc.). The device func­tions are the same as those of the basic versions.
Design
The SIPART PS2 positioner is a digital field device with a highly­integrated microcontroller.
The positioner consists of the following components:
• Casing and cover
• PCB with corresponding electronics with or without communi­cation through HART or with electronics for communication in accordance with
- PROFIBUS PA specification, IEC 61158-2; bus-supplied de-
vice, or
- FOUNDATION Fieldbus (FF) specification, IEC 61158-2,
bus-supplied device
• Actuator travel detection system
• Terminal housing with screw terminals
• Pneumatic valve manifold with piezoelectric valve precontrol.
The valve manifold is located in the housing, the pneumatic con­nections for the inlet air and the positioning pressure on the right­hand side. A pressure gauge block and/or a safety solenoid valve can be connected there as options. The SIPART PS2 posi­tioner is fitted to the linear or part-turn actuator using an appro­priate mounting assembly. The circuit board container in the casing provides slots for separately ordered boards with the following functions:
module:
I
y
• Position feedback as a two-wire signal 4 to 20 mA.
Alarm module (3 outputs, 1 input):
• Signaling of two limits of the travel or angle by binary signals. The two limits can be set independently as maximum or mini­mum values.
O
utput of an alarm if the setpoint position of the final control
• element is not reached in automatic mode or if a device/fitting fault occurs.
• Second binary input for alarm signals of for triggering safety reactions e. g. for blocking function or safety position.
Limit signaling through slot-type initiators (SIA module)
Two limits can be signaled redundantly as NAMUR signals (EN 60947-5-6) by slot-type initiators. The module also contains
m output (see Alarm module).
an alar
Limit value signal via mechanical contacts (Limit value con­tact module)
Two limits can be signaled redundantly by switching contacts. A fault message output is also integrated in the module (see alarm module).
alid for all modules described above:
V All signals are electrically isolated from one another and from the
basic unit. The outputs indicate self-signaling faults. The mod­ules are easy to retrofit.
Separate mounting of actuator travel detection system and
oller unit
contr
The actuator travel detection system and contr connected separately for all casing versions of the SIPAR (except flameproof design). Measurement of the travel or angle is carried out directly on the actuator. The controller unit can then be fitted a certain distance away, e.g. on a mounting pipe or sim­ilar, and is connected to the travel detection system by an elec­tric cable and to the actuator by one or two pneumatic lines. Such a split design is frequently advantageous if the ambient
essive environments
oller unit can be
T PS2
conditions at the fitting exceed the specified values for the posi­tioner (e.g. strong vibrations).
The following can be used for measuring the travel or angle:
• NCS sensor
• External position detection system C73451-A430-D78
• A commercially available potentiometer (10 kΩ resistance) (e.g. for higher application temperatures or customer-specific applications)
The use of linear potentiometers is recommended for very small ac­tuators with a short valve travel since, on the one hand, the space required by the linear potentiometer is very small and, on the other, the transmission characteristic is optimum for a small travel.
Separate connection of actuator travel detection system and controller unit
Separate connection of actuator travel detection system and controller unit
Non-contacting position sensor (NCS)
Contact and non-contacting positioning sensor (NCS) for part-turn actu­ator (left) and for linear actuator 14 mm (0.55 inch) (right)
NCS for travels >14 mm (0.55 inch)
6/4
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical description
The NCS sensor consists of a non-contacting position sensor. All coupling elements are omitted such as coupling wheel and driver pin with part-turn actuators or lever and pick-up bracket with linear actuators up to 14 mm travel.
This results in:
• Even greater resistance to vibration and shock
• No wear of sensor
• Problem-free mounting on very small actuators
• Negligible hysteresis with very small travels.
The sensor does not require an additional power supply, i.e. SIPART PS2 (not for EEx d version) can be operated in a 2-wire system. The NCS (N potted sensor housing which must be mounted permanently and a magnet which is mounted on the spindle of linear actuators or on the shaft butt of part-turn actuators. For the version for travels >14 mm (0.55 inch), the magnet and the NCS are premounted on a stainless steel frame and offer the same interface mechan­ically as the positioner itself, i.e. they can be mounted using the standard mounting kits 6DR4004-8V, -8VK and -8VL.
The installation of a EMC filter module in the positioner (controller unit) is necessary in order to ensure a connection level with EMC according to EN 61326/A1 and NAMUR NE21 when using exter­nal sensors (see Ordering data for "EMC filter module")
Function
The SIPART PS2 electropneumatic positioner works in a com­pletely different way to normal positioners.
Mode of operation
Comparison of the setpoint and the actual value takes place
onically in a micr
electr deviation, it uses a 5-way switch procedure to control the piezo­electric valves, which regulates the flow of air into and from the chambers of the pneumatic actuator or blows it in the opposite direction.
The microcontroller then outputs an electric control command to the piezoelectric valve in accordance with the size and direction of the deviation (deviation between setpoint w and control output x). The piezoelectric valve converts the command into a pneumatic positional increment.
The positioner outputs a continuous signal in the area where there is a large control deviation (high-speed zone); in areas of moderate control deviation (slow-speed zone) it outputs a se­quence of pulses. No positioning signals are output in the case of a small control deviation (adaptive or variable dead zone).
The linear or rotary motion of the actuator is detected by the mounting assembly and transferred to a high-quality potentio­meter made of plastic conductive material over a shaft and a non-floating gear transmission.
The angular error of the pick-up in cases where the assembly is mounted on a linear actuator is corrected automatically.
When connected in a 2-wire system, the SIPART PS2 draws its power exclusively from the 4 to 20 mA setpoint signal. The elec­tric power is also connected through the 2-wire bus signal with PROFIBUS operation (SIPART PS2 PA). The same applies for the FOUNDATION Fieldbus version.
Pneumatic valve manifold with piezoelectric valve precontrol
The piezoelectric valve can release very short control pulses. This helps achieve a high positioning accuracy ment is a piezoelectric bending conver pneumatic main control unit. The valve manifold is characterized by an extremely long service life.
Local operation
Local operation is performed using the built-in LCD and the
ee input keys. Switching between the operating levels Auto-
thr matic, Manual, Configuring and Diagnosis is possible at the
ess of a button.
pr
on Contacting Position Sensor) consists of a
ocontroller. If the microcontroller detects a
. The pilot ele-
ter which switches the
In Manual mode the drive can be adjusted over the entire range without interrupting the circuit.
Operation and monitoring with the SIMATIC PDM communi­cations pr
The SIMA through the HAR pling.
The SIMATIC PDM communications software permits easy re­mote operation and monitoring using a PC or laptop. The posi­tioner can also be configured using this program. Parameters which provide important information for maintenance and fault diagnosis of the complete unit can also be determined using process data and comparison data.
When operating the SIPART PS2 through the HART interface, the connection is made directly to the 2-wire cable to the SIPART PS2 positioner through a HART modem that can be con­nected to the RS 232 or USB interface. The signals needed for communication in conformity with the HART protocol are super­imposed on the current signal in accordance with the F
hift Keying (FSK) method.
S
Automatic commissioning
With a simple configuration menu the SIPART PS2 can be quickly adapted to the fitting and adjusted by means of an automatic star
During initialization, the micr point, full-scale value, the direction of action and the positioning speed of the fitting. From this data it establishes the minimum pulse time and the dead zone, thus optimizing the control.
Low air consumption
A hallmark of the SIPART PS2 is its own extremely low consump­tion of air. Nor costly. Thanks to the use of modern piezoelectric technology, the SIPART PS2 consumes air only when it is needed, which means that it pays for itself within a very short time
Comprehensive monitoring functions
The SIPART PS2 has various monitoring functions with which changes on the actuator and valve can be detected and sig­naled if applicable when a sele This infor or valve. The measured values to be determined and monitored, some of whose limits can be adjusted, include:
• Travel integral
• Number of changes in direction
• Alarm counter
• Self-adjusting dead zone
• Valve end limit position (e.g. for detection of valve seat wear or deposits)
• Operating hours (also according to temperature and position­ing ranges) as well as min./max. temperature
• Operating cycles of piezoelectric valves
• Valve positioning time
• Actuator leakages
ogram
TIC PDM program is available for communication
T interface and also for the PROFIBUS PA cou-
requency
tup function.
ocontroller determines the zero
mal air losses on conventional positioners are very
ctable limit has been exceeded.
mation may be important for diagnosis of the actuator
6
Siemens FI 01 · 2009
6/5
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Technical description
Status monitoring with 3-stage alarm concept
The intelligent electropneumatic SIPART PS2 positioner is equipped with additional monitoring functions. The status indi­cations derived fr faults of the unit. The severity of these faults ar "traffic light signaling", symbolized by a wrench in the colors green, yellow and red (with SIMATIC PDM and Maintenance Sta­tion):
• Need for maintenance (green wrench)
• Urgent need for maintenance (yellow wrench)
• Imminent danger of unit failure or general failure (red wrench)
This allows users to put early measures into action in the run-up to a serious valve or actuator fault, which can prevent an immi­nent system shutdown. The fact that a fault indication is sig­naled, such as the onset of a diaphragm break in the actuator or the progressive sluggishness of a unit, enables the user to en­sure system reliability at any time by means of suitable mainte­nance strategies.
This three-stage alarm hierarchy also allows early detection and signaling of other faults, such as the static friction of a packing box, the wearing of a valve plug/seating, or precipitations or in­crustations on the fittings.
These fault indications can be output either line-conducted over the alarm outputs (see above) of the positioner (max. 3), or via communication over the HART or fieldbus interfaces. In this case, the HART, PROFIBUS and FF versions of SIPART PS2 per­mit a differentiation of the various fault indications, as well as a trend representation and histogram function of all key process variables with regard to the fittings.
The LCD of the device also displays the graded maintenance re­quirements, complete with identification of the source of the fault.
Functional safety acc. to SIL 2
The SIPART PS2 positioners are also suitable for control of fit­tings, which meet the special r safety up to SIL 2 to IEC 61508 or IEC 61511-1.
This is a single-action, venting positioner with an input of 4 to 20 mA, PROFIBUS PA and FOUNDATION Fieldbus (FF) for mounting on pneumatic actuators with spring return.
The positioner vents the valve actuator on demand or in the event of a fault and puts the valve in the preset safety position.
This positioner meets the following requirements:
• Functional safety up to SIL 2 to IEC 61508 or IEC 61511-1, from firmware version C4 or higher for safe venting
• Explosion protection for the versions 6DR5...-.E...
• Electromagnetic compatibility to EN 61326/A1, Appendix A.1
SIPART PS 2 as "intelligent solenoid valve"
Open / Close valves, safety fittings in particular, are generally pneumatically contr
ART PS2 instead of this type of solenoid valve, the positioner
P performs two tasks in a single device (without extra wiring)
• Firstly, it switches the fitting off on demand by venting the ac­tuator (functional safety acc. to SIL 2 (see above)
• Secondly, it can perform a Partial Stroke Test at regular inter­vals (1 - 365 days), which prevents the blocking of the fitting, e.g. due to corrosion or furring.
As in this case SIPART PS2 is constantly working in normal op­eration (e.g. 99 % position), it also acts as a permanent test func­tion for the pneumatic output circuit, which is not usually possi­ble when using a solenoid valve.
Solenoid valves on control valves can also not normally be tested during operation. They are therefore not necessary when using SIPART PS 2 with a 4-wire connection system as the vent­ing is carried out on demand by SIPART PS2. This means that on control valves, both the control function and the shut-off function can be carried out by a single device.
om these monitoring functions signal active
ements of the functional
equir
olled over a solenoid valve. If you use SI-
e graded using
Configuring
The following settings, for example, can be configured in config­uring mode as r
• Input current range 0 to 20 mA or 4 to 20 mA
• Rising or falling characteristic at the setpoint input
• Positioning speed limit (setpoint ramp)
• Split-range operation; adjustable start-of-scale and full-scale values
• Response threshold (dead zone); self-adjusting or fixed
• Direction of action; rising or falling output pressure with rising setpoint
• Limits (start-of-scale and full-scale values) of positioning range
• Limits (alarms) of the final control element position; minimum and maximum values
• Automatic "tight shut-off" (with adjustable response threshold)
• The travel can be corrected in accordance with the valve char­acteristic.
• Function of binary inputs
• Function of alarm output etc.
The key aspects of configuring the different SIPART PS2 ver­sions are largely identical.
ed with the SIPART PS2 positioner:
equir
6/6
Siemens FI 01 · 2009
Electropneumatic positioners
A
D
A
D
1
BE1
I
W+
I
W-
W
y
0
x
0
+
_
W
x
+U
BE2
A1 A2
6
+5 V
+24 V
2
_
y
+
y
U
U
I
5
4
3
p
Z
p
2
p
1
8
9
p
2
p
1
p
1
_
+
p
2
p
1
A1 A2
7
II
1 Motherboard with microcontroller and input circuit 2 Control panel with LCD and pushbuttons 3 Piezoelectric valve unit, always present 4 Valve unit, present as accessory in double-action positioner 5 Iy module for SIPART PS2 controller 6 Alarm module for 3 alarm outputs and one binay input
Travel
Travel
Exhaust
Exhaust
Inlet air
HART
Micro-
controller
7 SIA module (slot initiator alarm module, fig.) or limit value contact module 8 Spring loaded pneumatic actuator (single-action) 9 Springless pneumatic actuator (double-action)
Note:
Alarm module (6) and SIA module (7) can only be inserted as alternatives.
© Siemens AG 2008
SIPART PS2
Technical description
SIPART PS2, electropneumatic positioner, function diagram
6
Siemens FI 01 · 2009
6/7
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Technical specifications all versions

Technical specifications

SIPART PS2 (all versions)
General data
Travel range (linear actuators) 3 ... 130 mm (0.12 ... 5.12 inch)
Angle of rotation (part-turn actuators)
Installation
• On linear actuators Using attachment set
• On part-turn actuators Using attachment set
Controller
• Five-point switch Self-adjusting
• Dead zone
- dEbA = Auto Self-adjusting or can be set as
- dEbA = 0.1 ... 10% Self-adjusting or can be set as
A/D converter
• Scan time 10 ms
• Resolution 0.05%
• Transmission error 0.2%
• Temperature effect 0.1%/10 K ( 0.1%/18 °F)
Cycle time
• 20 mA/HART device 20 ms
• PA device 60 ms
• FF device 60 ms (min. loop time)
Binary input BE1 (terminals 9/10; electrically connected to the basic device)
Degree of protection IP66 to EN 60 529/NEMA 4x
CE marking Conformity as regards EMC Direc-
EMC requirements EN 61326/A1 Appendix A.1 and
Material
• Housing
- 6DR5..0-... (plastic) Glass-fiber-reinforced Macrolon
- 6DR5..1-... (metal) GD AISi12
- 6DR5..2-... (stainless steel) Austenitic stainless steel mat.
- 6DR5..5-... (metal, pressure­proof)
• Pressure gauge block Aluminium AIMgSi, anodized
Vibration resistance
• Harmonic oscillations (sine-wave) according to DIN EN 60062-2-6/05.96
• Bumping (half-sine) to DIN EN 60068-2-29/03.95
(angle of feedback shaft 16 ... 90°)
30 ... 100°
6DR4004-8V and where necessary with an additional lever arm 6DR4004-8L on actuators accord­ing to IEC 534-6 (NAMUR) with ribs, bars or flat face
6DR4004-8D on actuators with mounting plane according to VDI/VDE 3845 and DIN 3337: The required mounting console has to be provided on the actuator side; shaft with groove and female thread M6
fixed value
fixed value
Suitable only for floating contact; max. contact load < 5 mA with 3 V
tive 89/336 EC in accordance with the following standards
NAMUR NE21 August 98
No. 1.4581
GK AISi12
3.5 mm (0.14 inch), 2 ... 27 Hz 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axis
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axis
• Noise (digitally controlled) to DIN EN 60068-2-64/08.95
• Recommended continuous duty range of the complete fitting
Weight, basic device
• Plastic casing Approx. 0.9 kg (1.98 lb)
• Metal casing, aluminium Approx. 1.3 kg (2.86 lb)
• Metal casing, stainless steel Approx. 3.9 kg (8.58 lb)
• Metal casing EEx d version Approx. 5.2 kg (11.46 lb)
Dimensions See "Dimensional drawings"
Climate class 4 To DIN EN 60721-3-4
• Storage
•Transport
• Operation
Certificate and approvals
Classification according to pres­sure equipment directive (DRGL 97/23/EC)
Pneumatic data
Power supply Compressed air, nitrogen or
• Pressure 1.4 ... 7 bar (20.3 ... 101.5 psi):
Air quality to ISO 8573-1
• Solid particle size and density Class 2
• Pressure dew point Class 2 (min. 20 K (36 °F) below
• Oil content Class 2
Unthrottled flow
• Inlet air valve
• Outlet air valve
Valve leakage < 6⋅10
Throttle ratio Adjustable up to : 1
Power consumption in the controlled state
Types of actuators
• In casing Single-action and double-action
• In aluminium casing Single-action
• In flameproof casing Single-action and double-action
• In stainless steel casing Single-action and double-action
1)
2)
3)
4)
1)
1)
2)
(ventilate actuator)
- 2 bar (29 psi) 4.1 Nm³/h (18.1 USgpm)
- 4 bar (58 psi) 7.1 Nm³/h (31.3 USgpm)
- 6 bar (87 psi) 9.8 Nm³/h (43.1 USgpm)
(exhaust actuator)
- 2 bar (29 psi) 8.2 Nm³/h (36.1 USgpm)
- 4 bar (58 psi) 13.7 Nm³/h (60.3 USgpm)
- 6 bar (87 psi) 19.2 Nm³/h (84.5 USgpm)
During commissioning at 0 °C ( 32 °F) make sure that the valves are flushed long enough with the dry medium.
At -10 °C (14 °F) the display refresh rate of the LCD is limited. Only T4 is permissible when using I
-25 ... +75 °C (-13 ... +167 °F) for 6DR55..-0G..., 6DR56..-0G..., 6DR55..-0D... and 6DR56..-0D...
With EEx d version (6DR5..5-...) the values are reduced by approx. 20%.
4)
4)
module.
y
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axis
30 m/s² ( 98.4 ft/s²) without res­onance sharpness
1K5, but -40 ... +80 °C (1K5, but -40 ... +176 °F)
2K4, but -40 ... +80 °C (2K4, but -40 ... +176 °F)
4K3, but -30 ... +80 °C (4K3, but -22 ... +176 °F)
For gases of fluid group 1, com­plies with requirements of article 3, paragraph 3 (sound engineering practice SEP)
cleaned natural gas
Sufficiently greater than max. drive pressure (actuating pressure)
ambient temperature)
-4
Nm³/h (0.0026 USgpm)
-2
< 3.6⋅10
Nm³/h (0.158 USgpm)
3)
6/8
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical specifications
Technical specifications
SIPART PS2 Basic device
Explosion protection to ATEX Without Ex d
Mounting location Zone 1 Zone 1 Zone 2/22
Permissible ambient temperature for operation
At -10 °C (+14 °F) the display refresh rate of the LCD is limited.
(for basic devices with EEX ia/ib and EEx n protection the following applies: Only T4 is permissible when using I module.)
Electrical data
Input
2-wire connection (terminals 6/8)
Rated signal range 4 ... 20 mA 4 ... 20 mA 4 ... 20 mA 4 ... 20 mA
Current to maintain the power supply 3.6 mA 3.6 mA 3.6 mA 3.6 mA
Required load voltage U
(corresponds to Ω at 20 mA)
B
• Without HART (6DR50..)
- Typical 6.36 V (corresponds to
- Max. 6.48 V (corresponds to
• Without HART (6DR53..)
- Typical 7.9 V (corresponds to
- Max. 8.4 V (corresponds to
• With HART (6DR51..)
- Typical 6.6 V (corresponds to
- Max. 6.72 V (corresponds to
• With HART (6DR52..)
- Typical 8.4 V (corresponds to
- Max. 8.8 V (corresponds to
• Static destruction limit ± 40 mA
Internal capacitance C
• Without HART 22 nF 22 nF (at "nL")
• With HART 7 nF 7 nF (at "nL")
Internal inductance L
• Without HART 0.12 mH 0.12 mH (at "nL")
i
i
without Ex protection
-30 ... +80 °C (-22 ... +176 °F)
y
318 Ω)
324 Ω)
395 Ω)
420 Ω)
330 Ω)
336 Ω)
Basic device with Ex d protection (flameproof casing)
II 2 G Ex d II C T6
6.36 V (corresponds to 318 Ω)
6.48 V (corresponds to 324 Ω)
–––
–––
6.6 V (corresponds to 330 Ω)
6.72 V (corresponds to 336 Ω)
420 Ω)
440 Ω)
Basic device with Ex ia/ib protection
Ex ia/ib II 2 G Ex ia/ib II C T6
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
7.8 V (corresponds to 390 Ω)
8.3 V (corresponds to 415 Ω)
––
––
8.4 V (corresponds to 420 Ω)
8.8 V (corresponds to 440 Ω)
Basic device with Ex n/dust protec­tion
Ex n II 3 G Ex nA nL[nL] IIC T6 Dust II 3 D Ex tD A22 IP66 T100°C
7.8 V (corresponds to 390 Ω)
8.3 V (corresponds to 415 Ω)
8.4 V (corresponds to 420 Ω)
8.8 V (corresponds to 440 Ω)
SIPART PS2
6
• With HART = 0.24 mH 0.24 mH (at "nL")
For connection to power circuits with the following max. ratings
intrinsically safe
= 30 V DC
U
i
= 100 mA
I
i
= 1 W
P
i
at "nA" and "tD":
= 30 V DC
U
n
= 100 mA
I
n
at "nL":
= 30 V DC
U
i
= 100 mA
I
i
Siemens FI 01 · 2009
6/9
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Technical specifications SIPART PS2
SIPART PS2 Basic device
3-/4-wire device (terminals 2/4 and 6/8) (6DR52.. and 6DR53..)
• Power supply U
• Current consumption I
• Internal capacitance C
• Internal inductance L
For connection to power circuits with the following max. ratings
Current input I
Rated signal range 0/4 ... 20 mA 0/4 ... 20 mA 0/4 ... 20 mA 0/4 ... 20 mA
Load voltage at 20 mA 0.2 V (corresponds to
Internal capacitance C
Internal inductance (L
For connection to power circuits with the following max. ratings
Electrical isolation between U
Test voltage 840 V DC (1 s) 840 V DC (1 s) 840 V DC (1 s) 840 V DC (1 s)
Connections
• Electric Screw terminals 2.5
• Pneumatic Female thread G¼ DIN
External position sensor (potentiometer or NCS; as option) with the following max. ratings
•U
o
• Io (static) 75 mA 75 mA
•I
(short-time) 160 mA -
s
•P
o
Maximum permissible external capaci­tance C
o
Maximum permissible external induc­tance L
o
H
H
i
i
W
i
) 0.12 mH 0.12 mH (at "nL")
i
without Ex protection
18 ... 35 V DC 18 ... 35 V DC 18 ... 30 V DC 18 ... 30 V DC
(UH - 7.5 V)/2.4 kΩ [mA] (UH - 7.5 V)/2.4 kΩ [mA] (UH - 7.5 V)/2.4 kΩ [mA] (UH - 7.5 V)/2.4 kΩ [mA]
–– 22 nF
–– 0.12 mH
intrinsically safe
10 Ω)
22 nF 22 nF (at "nL")
intrinsically safe
and I
H
W
AWG28-12 Cable gland M20 x 1.5 or
½-14 NPT
EN ISO 228-1 or ¼-18 NPT
––5V5V
120 mW 120 mW
––1 μF1 μF
1 mH 1 mH
Basic device with Ex d protection (flameproof casing)
0.2 V (corresponds to 10 Ω)
between UH and I
Screw terminals 2.5 AWG28-12
EEx d certified cable gland M20 x 1.5, ½-14 NPT or M25 x 1.5
Female thread G¼ DIN EN ISO 228-1 or ¼-18 NPT
W
Basic device with Ex ia/ib protection
Ui = 30 V DC Ii = 100 mA Pi = 1 W
1 V (corresponds to 50 Ω)
Ui = 30 V DC Ii = 100 mA Pi = 1 W
between UH and I (2 intrinsically safe cir­cuits)
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 or ¼-18 NPT
W
Basic device with Ex n/dust protec­tion
Un = 30 V DC In = 100 mA at "nL": Ui = 30 V DC Ii = 100 mA
1 V (corresponds to 50 Ω)
at "nA" and "tD": Un = 30 V DC In = 100 mA at "nL": Ui = 30 V DC Ii = 100 mA
between U
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 or ¼-18 NPT
and I
H
W
6/10
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical specifications
SIPART PS2 PA
Technical specifications
SIPART PS2 PA Basic device
Explosion protection to AT EX
Mounting location Zone 1 Zone 1 Zone 2/22
Permissible ambient temperature for operation
At -10 °C (+14 °F) the display refresh rate of the LCD is limited.
(for basic devices with Ex protection the following applies: Only T4 is per­missible when using I
Electrical data
Input
Power supply (terminals 6/7) Bus-supplied Bus-supplied Bus-supplied Bus-supplied
Bus voltage 9 ... 32 V 9 ... 32 V 9 ... 24 V 9 ... 32 V
• Bus connection with supply unit Intrinsically safe
- Max. supply voltage U
- Max. short-circuit current I
- Max. power P
• Bus connection with barrier intrinsically safe at "nL"
- Max. supply voltage (U
- Max. short-circuit current (I
- Max. power P
Current consumption 11.5 mA ± 10% 11.5 mA ± 10% 11.5 mA ± 10% 11.5 mA ± 10%
Additional fault current 0 mA 0 mA 0 mA 0 mA
Effective internal inductance L
Effective internal capacitance C
Safety shutdown can be activated with coding bridge (terminals 81/82; elec­trically isolated from the basic device)
• Input resistance > 20 kΩ > 20 kΩ > 20 kΩ > 20 kΩ
• Signal status "0" (shutdown active) 0 ... 4.5 V or unused 0 ... 4.5 V or unused 0 ... 4.5 V or unused 0 ... 4.5 V or unused
• Signal status "1" (shutdown not ac­tive)
• Effective Internal capacitance C
• Effective internal inductance L
• For connection to power supply with – Intrinsically safe At "nA", "nL" and "tD"
- Max. supply voltage U
- Max. short-circuit current I
- Maximum power P
Electrical isolation Between basic device
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
o
o
module.)
y
o
o
) 24 V 32 V
o
o
i
i
i
i
without Ex protection
Without Ex d
-30 ... +80 °C (-22 ... +176 °F)
17.5 V 17.5 V
380 mA 570 mA
5.32 W
) 250 mA
––1.2 W
8 μH 8 μH (at "nL")
Negligible Negligible
i
13 ... 30 V 13 ... 30 V 13 ... 30 V 13 ... 30 V
Negligible Negligible
i
Negligible Negligible
i
––30V30V
100 mA 100 mA
––1 W–
and the input for safety shutdown, as well as the outputs of the option modules
Basic device with Ex d protection (flameproof casing)
II 2 G Ex d II C T4/T5/T6
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
Between basic device and the input for safety shutdown, as well as the outputs of the option modules
Basic device with Ex ia/ib protection
Ex ia/ib II 2 G Ex ia/ib II C T6
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
FISCO
The basic device and the input to the safety shut­down, as well as the out­puts of the option modules, are individual, intrinsically-safe circuits
Basic device with Ex n/dust protec­tion
Ex n II 3 G Ex nA nL[nL] IIC T6 Dust II 3 D Ex tD A22 IP66 T100°C
T4: -20 ... +75 °C (-4 ... +167 °F)
T5: -20 ... +65 °C (-4 ... +149 °F)
T6: -20 ... +50 °C (-4 ... +122 °F)
at "nA" and "tD": Un = 32 V DC at "nL": FNICO
Between basic device and the input for safety shutdown, as well as the outputs of the option modules
6
Siemens FI 01 · 2009
6/11
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Technical specifications SIPART PS2 PA
SIPART PS2 PA Basic device
Communication Layers 1 and 2 according to PROFIBUS PA, transmission technique according to IEC 1158-2;
C2 connections Four connections to master class 2 are supported,
Device profile PROFIBUS PA profile B, version 3.0, more than 150 objects
Response time to master message Typical 10 ms
Device address 126 (when delivered)
PC parameterizing software SIMATIC PDM; supports all device objects. The software is not included in the scope of delivery.
Connections
• Electric Screw terminals 2.5
• Pneumatic Female thread G¼ DIN
External position sensor (potentiometer or NCS; as option) with the following max. ratings
•U
o
• Io (static) 75 mA 75 mA
•I
(short-time) 160 mA -
s
•P
o
• Maximum permissible external ca­pacitance C
• Maximum permissible external in­ductance L
o
o
without Ex protection
(all data acyclic, manipulated variable, feedbacks and status also cyclic)
AWG28-12 Cable gland M20 x 1.5 or
½-14 NPT
EN ISO 228-1 (¼-18 NPT)
––5V5V
120 mW 120 mW
––1 μF1 μF
1 mH 1 mH
Basic device with Ex d protection (flameproof casing)
slave function; layer 7 (protocol layer) according to PROFIBUS DP,
EN 50170 standard with the extended PROFIBUS functions
automatic connection setup 60 s after break in communication
Screw terminals 2.5 AWG28-12
EEx d certified cable gland M20 x 1.5, ½-14 NPT or M25 x 1.5
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
Basic device with Ex ia/ib protection
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
Basic device with Ex n/dust protec­tion
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
6/12
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical specifications
SIPART PS2 FF
Technical specifications
SIPART PS2 FF Basic device
Explosion protection to AT EX
Mounting location Zone 1 Zone 1 Zone 2/22
Permissible ambient temperature for operation
At -10 °C (+14 °F) the display refresh rate of the LCD is limited.
(for basic devices with Ex protection the following applies: Only T4 is per­missible when using I
Electrical data
Input
Power supply (terminals 6/7) Bus-supplied Bus-supplied Bus-supplied Bus-supplied
Bus voltage 9 ... 32 V 9 ... 32 V 9 ... 24 V 9 ... 32 V
• Bus connection with supply unit Intrinsically safe
- Max. supply voltage U
- Max. short-circuit current I
- Max. power P
• Bus connection with barrier intrinsically safe at "nL"
- Max. supply voltage (U
- Max. short-circuit current (I
- Max. power P
Current consumption 11.5 mA ± 10% 11.5 mA ± 10% 11.5 mA ± 10% 11.5 mA ± 10%
Additional fault current 0 mA 0 mA 0 mA 0 mA
Effective internal inductance L
Effective internal capacitance C
Safety shutdown can be activated with coding bridge (terminals 81/82; elec­trically isolated from the basic device)
• Input resistance > 20 kΩ > 20 kΩ > 20 kΩ > 20 kΩ
• Signal status "0" (shutdown active) 0 ... 4.5 V or unused 0 ... 4.5 V or unused 0 ... 4.5 V or unused 0 ... 4.5 V or unused
• Signal status "1" (shutdown not ac­tive)
• Effective Internal capacitance C
• Effective internal inductance L
• For connection to power supply with – Intrinsically safe At "nA", "nL" and "tD"
- Max. supply voltage U
- Max. short-circuit current I
- Maximum power P
Electrical isolation Between basic device
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
o
o
module.)
y
o
o
) 24 V 32 V
o
o
i
i
i
i
without Ex protection
Without Ex d
-30 ... +80 °C (-22 ... +176 °F)
17.5 V 17.5 V
380 mA 570 mA
5.32 W
) 250 mA
––1.2 W
8 μH 8 μH (at "nL")
Negligible Negligible
i
13 ... 30 V 13 ... 30 V 13 ... 30 V 13 ... 30 V
Negligible Negligible
i
Negligible Negligible
i
––30V30V
100 mA 100 mA
––1 W–
and the input for safety shutdown, as well as the outputs of the option modules
Basic device with Ex d protection (flameproof casing)
II 2 G Ex d II C T4/T5/T6
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
Between basic device and the input for safety shutdown, as well as the outputs of the option modules
Basic device with Ex ia/ib protection
Ex ia/ib II 2 G Ex ia/ib II C T6
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
FISCO
The basic device and the input to the safety shut­down, as well as the out­puts of the option modules, are individual, intrinsically-safe circuits
Basic device with Ex n/dust protec­tion
Ex n II 3 G Ex nA nL[nL] IIC T6 Dust II 3 D Ex tD A22 IP66 T100°C
T4: -20 ... +75 °C (-4 ... +167 °F)
T5: -20 ... +65 °C (-4 ... +149 °F)
T6: -20 ... +50 °C (-4 ... +122 °F)
at "nA" and "tD": Un = 32 V DC at "nL": FNICO
Between basic device and the input for safety shutdown, as well as the outputs of the option modules
6
Siemens FI 01 · 2009
6/13
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Technical specifications SIPART PS2 FF
SIPART PS2 FF Basic device
Communication
Communications group and class According to technical specification of the Fieldbus Foundation for H1 communication
Function blocks Group 3, Class 31PS (publisher, subscriber)
Execution times of the blocks AO: 50 ms
Physical layer profile 123, 511
FF registration Tested with ITK 5.0
Device address 22 (when delivered)
Connections
Electric Screw terminals 2.5
Pneumatic Female thread G¼ DIN
External position sensor (potentiometer or NCS; as option)
•U
o
•I
o
•I
s
•P
o
Maximum permissible external capaci­tance C
o
Maximum permissible external induc­tance L
o
without Ex protection
AWG28-12 Cable gland M20 x 1.5 or
½-14 NPT
EN ISO 228-1 (¼-18 NPT)
––< 5V<5V
––<75mA<75mA
––<160mA<160mA
< 120 mW < 120 mW
––< 1 μF< 1 μF
< 1 mH < 1 mH
Basic device with Ex d protection (flameproof casing)
1 resource block (RB2)
1 analog output function block (AO)
1 PID function block (PID)
1 transducer block (standard advanced positioner valve)
Screw terminals 2.5 AWG28-12
EEx d certified cable gland M20 x 1.5, ½-14 NPT or M25 x 1.5
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
Basic device with Ex ia/ib protection
PID: 80 ms
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
Basic device with Ex n/dust protec­tion
Screw terminals 2.5 AWG28-12
Cable gland M20 x 1.5 or ½-14 NPT
Female thread G¼ DIN EN ISO 228-1 (¼-18 NPT)
6/14
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical specifications
Option modules
Technical specifications
Option modules Without Ex protection
Ex protection to ATEX II 2G Ex ia/ib II C T4/T5/T6 (only
Mounting location Zone 1 Zone 2/22
Permissible ambient temperature for opera­tion (For devices with Ex protection: Only in con-
junction with the basic device 6DR5... -.E....
Only T4 is permissible when using I
Alarm module 6DR4004-8A (without Ex protec-
Binary alarm outputs A1, A2 and alarm output
Signal status High (not responded) Signal status Low* (responded) (* Low is also the status when the basic device is faulty or has not electric power sup­ply)
Internal capacitance C
Internal inductance L
Power supply U
Connection to power circuits with with the fol­lowing max. ratings
Binary input BE2
• Electrically connected to the basic device
- Signal status 0 Floating contact, open Floating contact, open Floating contact, open
- Signal status 1 Floating contact, closed Floating contact, closed Floating contact, closed
- Contact load 3 V, 5 μA3 V, 5 μA3 V, 5 μA
• Electrically isolated from the basic device
- Signal status 0 4.5 V or open 4.5 V or open 4.5 V or open
- Signal status 1 13 V 13 V 13 V
- Natural resistance ≥ 25 kΩ≥25 kΩ≥25 kΩ
Static destruction limit ± 35 V
Internal inductance and capacitance Negligible Negligible
Connection to power circuits with the follow­ing max. ratings
Electrical isolation The 3 outputs, the input BE2 and the basic device are electrically isolated from each other.
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
1)
Only in conjunction with the basic device 6DR5...-E..... With Iy module only T4 permitted.
i
i
H
module)
y
(EEx d also)
-30 ... +80 °C (-22 ... +176 °F) T4: -30 ... +80 °C (-22 ... +176 °F)
tion)
Active, R = 1 kΩ, +3/-1%* Disabled, I
(* When used in the flameproof casing the current consumption is limited to 10 mA per output.)
5.2 nF 5.2 nF (at "nL")
Negligible Negligible
≤ 35 V
intrinsically safe switching
Intrinsically safe Ui = 25.2 V at "nA" and "tD":
< 60 μA
R
With Ex protection Ex ia/ib With Ex n/dust protection
in conjunction with)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
6DR4004-6A (with Ex protection) 6DR4004-6A (with Ex protection)
2.1 mA 1.2 mA
(Switching threshold with sup­ply to EN 60947-5-6: U
= 1kΩ)
R
i
amplifier EN 60947-5-6 U
=15.5 V DC
o
= 25 mA, P = 64 mW
I
k
= 8.2 V,
H
Ex n II 3 G Ex nA nL[nL] IIC T6 Dust II 3 D Ex tD A22 IP66 T100°C
2.1 mA 1.2 mA
(Switching threshold with sup­ply to EN 60947-5-6: U
= 1kΩ)
R
i
at "nA" and "tD": Un = 15.5 V DC at "nL": Ui = 15.5 V DC Ii = 25 mA
Un = 25.2 V DC at "nL": Ui = 25.2 V DC
1)
1)
1)
= 8.2 V,
H
6
Siemens FI 01 · 2009
6/15
6
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical specifications Option modules
Option modules Without Ex protection With Ex protection EEx ia/ib With Ex n/dust protection
SIA module Limit switches with slot-type initiators and alarm output
Limit switches A1, A2
Ex protection Without II 2 G EEx ia/ib IIC T6 II 3 G EEx nA L [L] IIC T6
Connection 2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
2 slot-type initiators Type SJ2-SN Type SJ2-SN Type SJ2-SN
Function NC (normally closed) NC (normally closed) NC (normally closed)
Connection to power circuits with the fol­lowing max. ratings
Internal capacitance 41 nF 41 nF (at "nL")
Internal inductance 100 mH 100 mH (at "nL")
Electrical isolation The 3 outputs are electrically isolated from the basic device.
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
Alarm output
Connection 2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
Signal status High (not active) R = 1.1 kΩ≥ 2.1 mA 2.1 mA
Signal status Low (active) R
Internal capacitance C
Internal Inductance L
Power supply U
For connection to power with the following max. ratings
Limit value contact module Limit switches with mechanical ground contact and alarm output
Limit switches A1, A2
Ex protection without II 2 G Ex ia/ib IIC T6 II 3 G Ex nL [nL] IIC T6
Max. switching current AC/DC 4 A Connection to intrinsically safe
Max. switching voltage AC/DC 250 V / 24 V 30 V DC
Internal capacitance C
Internal inductance L
Electrical isolation The 3 outputs are electrically isolated from the basic device.
Test voltage 3150 V DC, 2s 3150 V DC, 2 s 3150 V DC, 2 s
Alarm output
Connection 2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
Signal status High (not active) R = 1.1 kΩ≥ 2.1 mA 2.1 mA
Signal status Low (active) R
Internal capacitance C
Internal Inductance L
Power supply U
For conncetion to power with the following max. ratings
i
i
H
i
i
i
i
H
6DR4004-8G (without Ex protec­tion) (not for Ex-d version)
2-wire connection 2-wire connection 2-wire connection
nominal voltage 8 V Current consumption: 3 mA (limit value not responded) 1 mA (limit value responded)
= 10 kΩ≤ 1.2 mA 1.2 mA
i
5.2 nF 5.2 nF (bei „nL“)
Negligible Negligible
UH 35 V DC, I 20 mA
intrinsically safe switching ampli-
6DR4004-8K (not for EEx d version)
Negligible Negligible
Negligible Negligible
= 10 kΩ≤ 1.2 mA 1.2 mA
i
5.2 nF 5.2 nF (bei „nL“)
Negligible Negligible
UH 35 V DC, I 20 mA
Intrinsically safe switching ampli-
6DR4004-6G (with Ex protection) 6DR4004-6G (with Ex protection)
intrinsically safe switching amplifier EN 60947-5-6
Ui = 15.5 V DC Ii = 25 mA, P i = 64 mW
U
= 8.2 V, Ri = 1 kΩ
H
fier EN 60947-5-6 U
= 15.5 V DC
i
= 25 mA
I
i
= 64 mW
P
i
6DR4004-6K 6DR4004-6K
circuit with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW
U
= 8.2 V, Ri = 1 kΩ
H
fier EN 60947-5-6
= 15.5 V DC
U
i
I
= 25 mA
i
= 64 mW
P
i
at "nA" and "tD": Un = 15.5 V DC Pn = 64 mW at "nL": Ui = 15.5 V DC Ii = 25 mA
at „nA“ and „tD“: U
= 15.5 V DC
n
at „nL“:
= DC 15.5 V
U
i
= 25 mA
I
i
(in progress)
Connection to circuits with maxi­mum values: at "nL": Ui = 30 V Ii = 100 mA,
at „nL“: U
= 15.5 V DC
i
= 25 mA
I
i
6/16
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Technical specifications
Option modules
Option modules Without Ex protection With Ex protection EEx ia/ib With Ex n/dust protection
Iy module
DC output for position feedback 2-wire connection 2-wire connection 2-wire connection
Nominal signal range 4 ... 20 mA, short-circuit-proof 4 ... 20 mA, short-circuit-proof 4 ... 20 mA, short-circuit-proof
Total operating range 3.6 ... 20.5 mA 3.6 ... 20.5 mA 3.6 ... 20.5 mA
Power supply U
External load R
Transmission error 0.3% 0.3% 0.3%
Temperature effect ≤ 0.1%/10 K (≤ 0.1%/18 °F) 0.1%/10 K ( 0.1%/18 °F) 0.1%/10 K ( 0.1%/18 °F)
Resolution 0.1% 0.1% 0.1%
Residual ripple 1% 1% 1%
Internal capacitance C
Internal inductance L
For connection to power circuits with the following max. ratings
Electrical isolation Electrically isolated from the
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
NCS sensor
(not for EEx d version)
Position range
• Linear actuator 3 ... 130 mm (0.12 ... 5.12 inch),
• Part-turn actuator 30° ... 100° 30° ... 100°
Linearity (after correction by SIPART PS2)
• Linear actuator ± 1% ± 1%
• Part-turn actuator ± 1% ± 1%
Hysteresis ± 0.2% ± 0.2%
Continuous working temperature -40 ... +85 °C (-40 ... +185 °F),
For connection to power circuits with the following max. ratings
Internal capacitance Ci - 10 nF 10 nF (at "nL")
Internal inductance Li - 240 mH 240 mH (at "nL")
Degree of protection of casing IP68/NEMA 4X IP68/NEMA 4X
H
[kΩ] (UH [V] - 12 V) /i [mA] (UH [V] - 12 V) /i [mA] (UH [V] - 12 V) /i [mA]
B
i
i
6DR4004-8J (without Ex protection)
+12...+35V +12...+30V +12...+30V
11 nF 11 nF (at "nL")
Negligible Negligible
basic device
to 200 mm (7.87 inch) on request
extended temperature range on request
6DR4004-6J (with Ex protection) 6DR4004-6J (with Ex protection)
Intrinsically safe: Ui = 30 V DC Ii = 100 mA Pi = 1 W (only T4)
Electrically isolated from the basic device
3 ... 130 mm (0.12 ... 5.12 inch), to 200 mm (7.87 inch) on request
-40 ... +85 °C (-40 ... +185 °F), extended temperature range on request
Intrinsically safe Ui = 5 V DC
at "nA" and "tD" Un = 30 V DC In = 100 mA Pn = 1 W (only T4) at "nL": Ui = 30 V DC Ii = 100 mA
Electrically isolated from the basic device
at "nL": Ui = 5 V DC
6
Siemens FI 01 · 2009
6/17
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Ordering data SIPART PS2, PS2 PA, PS2 FF
Selection and Ordering data
Electropneumatic positioner SIPART PS2, Ex protection without, EEx ia/ib and EEx n
Version
2-wire (4 to 20 mA)
• Without HART } 0
•With HART, not explosion-protected } 1 2-, 3-, 4-wire (0/4 to 20 mA)
•With HART, explosion-protected } 2
• Without HART, not explosion­protected
PROFIBUS PA connection } 5 FOUNDATION Fieldbus connection } 6
For actuator
Single-action } 1 Double-action } 2
Casing
Plastic } 0 Aluminum; only single-action } 1 1 Stainless steel (without window) } 2
Explosion protection
Without } N With explosion protection EEx ia/ib
(CENELEC/ATEX/FM/CSA) With explosion protection EEx n,
(CENELEC/ATEX)
• For zone 2 and zone 22 (dust), casing: aluminium or stainless steel; each with no window in the cover
• For zone 2 casing: aluminium or plastic; each with window in the cover
Connection thread electrical/pneumatic
M20 x 1.5 / G¼ } G ½-14 NPT / ¼-18 NPT } N M20 x 1.5 / ¼-18 NPT M ½-14 NPT / G¼ P
With plug M12 / G¼
With plug M12 / ¼-18 NPT
Limit monitor
Installed, incl. 2nd cable gland Without } 0 Alarm module; electronic
(6DR4004-.A) SIA module; slot-type initiators
(6DR4004-.G) Limit value contact module (mechani-
cal switching contacts (6DR4004-.K)
1)2)
Order No.
777
6 D R 5
} 3
} E
- 0
7 777-77A7
D
G
R
S
Selection and Ordering data
Electropneumatic positioner SIPART PS2, Ex protection without, EEx ia/ib and EEx n
Optional modules
Installed, incl. 2nd cable gland Without } 0 Iy module for position feedback
signal (4 ... 20 mA) (6DR4004-.J) EMC filter module for external
position sensor (C73451-A430-D23) Iy module and EMC filter module for
external position sensor
Customer-specific design
Without } 0
Brief instructions
German/English } A French/Spanish/Italian B
Mounted pressure gauge block
Without } 0 Single-action G¼, scaling MPA and
bar Double-action G¼, scaling MPA and
bar Single-action ¼-18 NPT, scaling
MPA and psi Double-action ¼-18 NPT, scaling
MPA and psi
Further designs Order code
Add "-Z" to Order No. and specify Order code.
Version with stainless steel sound absorbers
standard with stainless steel enclo­sures
Measuring point number (TAG No.)
HART tag max. 8 characters, max. 32 characters for PROFIBUS PA, FOUNDATION Field­bus and 4 ... 20 mA version,
specify in plain text: Y17: ........
Measuring point description
HART tag max. 16 characters, max. 32 characters for PROFIBUS PA, FOUNDATION Field-
1
2
3
bus and 4 ... 20 mA version,
specify in plain text: Y15: ........
Measuring point text
HART tag max. 24 characters, max. 32 characters for PROFIBUS PA, FOUNDATION Field­bus and 4 ... 20 mA version,
specify in plain text: Y16: ........
TAG plate made of stainless steel, 3-line
Text line 1: Plain text from Y17 Text line 2: Plain text from Y15 Text line 3: Plain text from Y16
Preset bus address
Specify in plain text: Y25: ........
} Available ex stock
1)
Maximum impact energy to the casing: 1 Joule.
2)
For device versions in plastic casing: it is essential to prevent electrostatic charging. Maximum torque of the cable gland: 67 Nm.
3)
Only for plastic casing, for other casings on request.
Order No.
777
6 D R 5
A40
3)
Y17
3)
Y15
3)
Y16
3)
A20
3)
Y25
7 777-77A7
- 0
1
2
3
1
2
3
4
6/18
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Ordering data
SIPART PS2 EEx-d, PS2 EEx-d PA, PS2 EEx-d FF
Selection and Ordering data
Electropneumatic positioner SIPART PS2, Ex protection EEx-d, aluminium housing, without cable gland
Version
2-wire (4 to 20 mA)
• Without HART } 0
•With HART, not explosion-protected 1
2-, 3-, 4-wire (0/4 to 20 mA)
•With HART } 2
• Without HART, not explosion­protected
PROFIBUS PA connection 5 FOUNDATION Fieldbus connection 6
For actuator
Single-action } 1 Double-action } 2
Connection thread electrical/pneumatic
M20 x 1.5 / G¼ } G ½-14 NPT / ¼-18 NPT } N M20 x 1.5 / ¼-18 NPT M ½-14 NPT / G¼ P M25 x 1.5 / G¼ Q
Limit monitor
Installed Without } 0 Alarm module; electronic
(6DR4004-.A)
Optional modules
Installed Without } 0 Iy module for position feedback
signal (4 ... 20 mA) (6DR4004-.J)
Customer-specific design
Without } 0
Brief instructions
German/English } A French/Spanish/Italian B
Mounted pressure gauge block
Without } 0 Single-action G¼, scaling MPa and
bar Double-action G¼, scaling MPa and
bar Single-action ¼-18 NPT, scaling
MPa and psi Double-action ¼-18 NPT, scaling
MPa and psi
Order No.
6 D R 5775 - 0 E
D)
3
777-77A7
1
1
Selection and Ordering data
Electropneumatic positioner SIPART PS2, Ex protection EEx-d, aluminium housing, without cable gland
Further designs Order code
Add "-Z" to Order No. and specify Order Code.
Measuring point number (TAG No.)
HART tag max. 8 characters, max. 32 characters for PROFIBUS PA and FOUNDATION Fieldbus version,
specify in plain text: Y17: ........
Measuring point description
HART tag max. 16 characters, max. 32 characters for PROFIBUS PA and FOUNDATION Fieldbus version,
specify in plain text: Y15: ........
Measuring point text
HART tag max. 24 characters, max. 32 characters for PROFIBUS PA and FOUNDATION Fieldbus version,
specify in plain text: Y16: ........
TAG plate made of stainless steel, 3-line
Text line 1: Plain text from Y17 Text line 2: Plain text from Y15 Text line 3: Plain text from Y16
Preset bus address
Specify in plain text: Y25: ........
} Available ex stock
D) Subject to export regulations AL: N, ECCN: EAR99H
1
2
3
4
Order No.
6 D R 5775 - 0 E
Y17
Y15
Y16
A20
Y25
777-77A7
6
Siemens FI 01 · 2009
6/19
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2
Ordering data Accessories
Selection and Ordering data Order No.
Accessories
NCS sensor
for non-contacting detection of position (not for EEx d version), cable length 6 m (19.68 ft)
Non explosion-proof 8
Explosion-protected, EEx ia/ib 6
For part-turn actuators, without mounting console
For linear actuators up to 14 mm (0.55 inch), without mounting bracket
For linear actuators >14 mm (0.55 inch), to 130 mm (5.12 inch); Mounting kit same as for SIPART PS2 (separate ordering item)
The EMC filter module is additionally required for the controller unit. (separate order item, see below)
Selection and Ordering data Order No.
Accessories
Alarm module for 3 alarm outputs and 1 binary input (functionality: 2 limit monitors, 1 fault alarm, 1 binary input)
• Without explosion protection } 6DR4004-8A
• With explosion protection
CENELEC/ATEX
• With explosion protection FM/CSA
SIA module (slot-type initiator alarm module, not for EEx d version)
• Without explosion protection 6DR4004-8G
• With explosion protection
CENELEC/ATEX and FM/CSA
Limit value contact module
(with mechanical ground contacts, not for EEx d version)
• without explosion protection 6DR4004-8K
• with explosion protection
I
module for position feedback signal
y
(4 to 20 mA)
• Without explosion protection } 6DR4004-8J
• With explosion protection
CENELEC/ATEX
• With explosion protection FM/CSA
HART modem for connecting to PC or laptop
• with RS232 interface }D)7MF4997-1DA
• with USB interface
EMC filter module for connection of exter­nal position sensor (10 kΩ) or NCS sensor (not for EEx d version)
1)
1)
1)
6 D R 4 0 0 4 -7N N70
6DR4004-6A
}
6DR4004-7A
6DR4004-6G
6DR4004-6K
6DR4004-6J
}
6DR4004-7J
}
7MF4997-1DB
D)
C73451-A430-D23
Mounting kit for NAMUR part-turn actuators
(VDI/VDE 3845, without mounting plate) } 6DR4004-8D
The following mounting plates can be used with the NAMUR part-turn actuator mounting kit 6DR4004-8D. Size W x L x H (H = height of shaft butt)
• 30 x 80 x 20 mm }C)TGX:16152-105
1
2
3
• 30 x 80 x 30 mm }
• 30 x 130 x 30 mm }
• 30 x 130 x 50 mm }
Mounting kit for other part-turn actuators
The following mounting plates can be used together with the NAMUR part-turn actuator mounting kit 6DR4004-8D.
• SPX (DEZURIK) Power Rac, sizes R1, R1A, R2 and R2A
• Masoneilan Camflex II }
• Fisher 1051/1052/1061, sizes 30, 40, 60 to 70
• Fisher 1051/1052, size 1033 }
Mounting kit for NAMUR linear actuators
• NAMUR linear actuator mounting kit with short lever arm (2 to 35 mm)
• Lever arm for travels from 35 mm to 130 mm (1.38 inch to 5.12 inch)
• Reduced mounting kit for linear actuator (without fixing angle and U-bracket), with short lever with up to 35 mm travel (1.38 inch)
• Reduced mounting kit for linear actuator (without fixing angle and U-bracket), with long lever with >35 mm travel (1.38 inch)
Mounting kit for other linear actuators
• Retrofitting kit for Moore series 72 and 750 valve positioners
• Fisher type 657/667, size 30 to 80 }
• SAMSON actuator type 3277 (yoke dimension (H5) = 101 mm connection without tube), not for EEx d
Pipe mounting
Mounting bracket for pipe mounting of the SIPART PS2 position (e.g. when using the NCS sensor)
Additional actuator items can be found at the following Internet address:
www.siemens.com/sipartps2
Customer-specific actuators available on request.
} Available ex stock
1)
U.S. certification by FM institute
2)
With a yoke dimension H5 = 95 mm, only the SIPART PS2 in a metal casing can be used.
C) Subject to export regulations AL: N, ECCN: EAR99
D) Subject to export regulations AL: N, ECCN: EAR99H
2)
(integrated
TGX:16300-147
C)
TGX:16300-149
C)
TGX:16300-151
C)
}C)TGX:16152-328
TGX:16152-350
C)
TGX:16152-364
}
C)
TGX:16152-348
C)
} 6DR4004-8V
6DR4004-8L
}
6DR4004-8VK
}
}
6DR4004-8VL
}C)TGX:16152-117
TGX:16152-110
C)
6DR4004-8S
}
}C)TGX:16152-336
6/20
Siemens FI 01 · 2009
Electropneumatic positioners
© Siemens AG 2008
SIPART PS2
Ordering data
Accessories
Manometer block including pressure gauge
• For single-action SIPART PS2 positioner with G thread (2 manometers, scaled in MPa and bar)
• For double-action SIPART PS2 positioner with G thread (3 manometers, scaled in MPa and bar)
• For single-action SIPART PS2 positioner with NPT thread (2 manometers, scaled in MPa and psi)
• For double-action SIPART PS2 positioner with NPT thread (3 manometers, scaled in MPa and psi)
Connection block, for safety solenoid valve with extended mounting flange to NAMUR
• For mounting to IEC 534-6 6DR4004-1B
• For SAMSON actuator (integrated mount­ing) see above
External position detection system
(with explosion protection to CENELEC/ATEX, EEx ia/ib) for separate mounting of position sensor and controller (for for EEx d version), comprising SIPART PS2 plastic casing with integral potentiome­ter and sliding clutch (without electronics and valve block)
The EMC filter module is additionally required for the controller unit. (separate ordering item below)
Documentation (see notes below)
Instruction Manual SIPART PS2
• German/English A5E00074600
• French/Italian/Spanish
Instruction Manual SIPART PS2 PROFIBUS PA
• German/English A5E00120716
• French/Italian/Spanish
Instruction Manual NCS Sensor
• German/English/French/Spanish/Italian A5E00097485
SIPART PS2 device documentation
• CD-ROM with complete documentation for all device versions
Device manual for SIPART PS2 (not PA and FF)
•German A5E00074630
• English
Manual for SIPART PS2 PROFIBUS PA
•German A5E00127924
• English
SITRANS I outgoing isolator HART (see „SITRANS I supply units and isolation amplifiers“) with
• 24 V DC power supply 7NG4130-1AA11
• 230 V AC power supply
} Available ex stock
1)
Only together with 6DR4004-8S and 6DR4004-1M.
} 6DR4004-1M
}
6DR4004-2M
}
6DR4004-1MN
}
6DR4004-2MN
6DR4004-1C
C73451-A430-D78
A5E00074601
A5E00120717
A5E00214567
A5E00074631
A5E00127926
7NG4130-1BA11
1)
Note
All the above mentioned manuals are included on CD-ROM or can be downloaded from the Inter
net under:
www.siemens.com/sipartps2
Following manuals are available in addition as downloads from the Internet or are included on CD-ROM:
• Instruction Manual Compact SIPART PS2 FF, Electropneu­matic Positioner (6DR56xx) with FOUNDATION Fieldbus
- German/English: A5E00214570
• Instruction Manual SIPART PS2 FF, Electropneumatic Posi­tioner (6DR56xx) with FOUNDATION Fieldbus
- German: A5E00214568
- English: A5E00214569
Scope of delivery:
• 1 SIPART PS2 positioner as ordered 1 CD-ROM with the complete documentation for all versions
• and accessories
Manual "SIPART PS2 - Configuration At a Glance"
More infomation
Special versions
On request
6
Siemens FI 01 · 2009
6/21
Electropneumatic positioners
6
59 (2.32)
M20 x 1.5
29.5
(1.16)
72 (2.83)
11.2 (0.44)
185 (7.28)
50 x 4 (1.97 x 0.16) x M6
29.5
(1.16)
50 x 4 (1.97 x 0.16) x M6
185 (7.28)
29.5
(1.16)
11.2 (0.44)
84 (3.31)
96.6 (3.80)
98 (3.86)
1)
1) For stainless steel version only
95 (3.74)
99 (3.89)
1)
74 (2.91)
1)
connections
All air
G 1/4 or 1/4 NPT
G 1/4 or 1/4 NPT
connections
All air
© Siemens AG 2008
SIPART PS2

Dimensional drawings

Dimensional drawings
Plastic and stainless steel casing (top), aluminium casing (center), plas­tic and metal casing (bottom), dimensions in mm (inch)
0GHHS[

0GHHS[
Flameproof casing left, dimensions in mm (inch)
6/22

<

Siemens FI 01 · 2009





Ø

Ø
h9




Ø

DOODLUFRQQHFWLRQV *RU137



 
0GHHS[
0[0[RU 137[
(



&RQQHFWLRQ<RQO\IRUGRXEOHDFWLRQYHUVLRQ









Electropneumatic positioners
M6
4
+0,1
(0.16
+0.04
)
4
(0,16)
12
(0.47)
25 (0,98)
35 (1.38)
6,
5
F05-Lkr.- 50 (1.97)
>4 mm
(0.16)
Mounting level of positioner
Part-turn actuator
Mounting plate
6
7
+
-
81 82
9
10
PROFIBUS PA and FOUNDATION Fieldbus connection
*) Input for safety shutdown (activated using coding jumper)
*)
+
-
£ 30 V
£ 24 V
BE1
2 3
4 5
6
7 8
i
y
20 mA
I
H+
I
W
-
I
+
-
*) R
250
W
³
if req.
= 4 to
HART modem
*) Only required with current sources not conforming to HART
PC/Laptop
+
2 3 4 5
6 7 8 9
10
BE1
18 ... 30 V
0/4 ...
J
+
_
_
*)
2 3 4 5
6 7 8 9
10
BE1
4 ... 20 mA
J
+
_
20 mA
Two-wire system
Three-/Four-wire system
*) Jumper between 5 and 7 only for three-wire system
© Siemens AG 2008
SIPART PS2

Schematics

Electric connection of 2-, 3- and 4-wire device (6DR52.. and 6DR53..)
Devices of types 6DR52.. and 6DR53.. can be operated in a 2-, 3- and 4-wir
SIPART PS2 electropneumatic positioner, example of connection for com­munication through HART for 6DR52..
e system.
Mounting onto part-turn actuators; mounting plate (scope of delivery of actuator manufacturer), extract from VDI/VDE 3845, dimensions in mm (inch)
Schematics
Electric connection of 2-wire devices (6DR50.. and 6DR51..)
Devices of types 6DR50.. and 6DR51.. are operated in a 2-wire system.
Two-wire system
SIPART PS2 electropneumatic positioner, input circuit for 6DR50.. and 6DR51..
Electric connection of PROFIBUS PA device (6DR55..) and FOUNDATION Fieldbus devices (6DR56..)
SIPART PS2 PA and SIPART PS2 FF electropneumatic positioner, input circuit for 6DR55.. and 6DR56..
J
4 ... 20 mA
6
+
6
_
7 8 9
BE1
10
SIPART PS2 electropneumatic positioner, input circuits for 6DR52..
Siemens FI 01 · 2009
6/23
Electropneumatic positioners
6
© Siemens AG 2008
SIPART PS2

Mounting kits

Mounting kit for NAMUR linear actuators
• 1 mounting bracket
• 2 mounting prisms 1 U-bracket
• 1 lever arm with adjustable pick-up roll
• 2 U-bolts
• Various screws and lock washers
Mounting of SIPART PS2 on linear actuators
6/24
Siemens FI 01 · 2009
Mounting of SIPART PS2 EEx d on linear actuators
Mounting kit for NAMUR part-turn actuators
© Siemens AG 2008
• 1 coupling wheel
• 1 driver pin 8 scales
• 1 pointer
• Various screws and lock washers
Caution: The mounting consoles and the screws for mounting onto the part-turn actuator are not included in the scope of de­livery and must be provided by the customer (see Technical specifications).
Electropneumatic positioners
SIPART PS2
Mounting kits
Mounting of SIPART PS2 on part-turn actuators
6
Mounting of SIPART PS2 EEx d on part-turn actuators
7
Siemens FI 01 · 2009
6/25
Electropneumatic positioners
6
© Siemens AG 2008
6/26
Siemens FI 01 · 2009