Siemens Sinteso Cerberus PRO FDA221, Sinteso Cerberus PRO FDA241 User Manual

2019-01-24
Sinteso™ Cerberus™ PRO
FDA241, FDA221
Siemens aspirating smoke detector (ASD) for the addressed FDnet/C
-
NET
ASD Aspirating smoke detector
detector line or for standalone operation
Patented technology
Early detection of a wider spectrum of particle sizes in the air
Configuration using the USB interface or the control panel via FDCC221S
(optional)
'ASD Asyst-Tool' software to assist with pipe configuration
Unique dust-resistant detection chamber
Intuitive front indicator for airflow and smoke value
Access to service functions
Different event protocols
Offline/online configuration supported
Cleaning function (FDA241)
4…20 mA output
A6V10331032_j_en_-- Building Technologies
2
Building Technologies
A6V10331032_j_en_
--
Properties
The '
FXS2056
ASD Asyst Tool V2
' software is replacing the '
FXS2055
ASD Asyst Tool
'
Use
Extended optical detection thanks to dual wavelengths (blue and infrared): The aspirating smoke detectors FDA241 and FDA221 use dual-wavelength technology to trigger an alarm at the earliest possible moment. They are designed to protect small and medium-sized business-critical environments for monitoring areas of up to 800 m
2
(FDA241) or 500 m2 (FDA221). The detectors continually suck in air through a pipe system via their aspirating holes. The air is fed into a uniquely designed detection chamber, in which tiny smoke particles are detected by scattered light.
Lower mounting and service costs: The aspirating smoke detectors FDA241 and FDA221 can be used on an FDnet/C-NET detector line. For this purpose, communication transponder FDCC221S is required.
Configuration using the USB interface or the control panel via FDCC221S (optional): All detector configurations, maintenance work, and alarm and fault management processes can be carried out at a central location – the fire control panel. This ensures better control while also reducing the costs of the overall solution.
'Out-of-the-box' mounting and commissioning: Installation is simple thanks to combined functions for normalizing smoke values and airflow, as well as appropriate presettings for alarm and fault thresholds.
ASD filter box FDAZ292 available as an accessory: Dust and other dirt is filtered out of the aspirated air and does not get into the aspirating smoke detector. The filters in the ASD filter box are easy to replace.
Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms and equipment. They are especially suited to applications in which point detectors are pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a connected pipe system with defined aspirating holes. The air is supplied to the detection chamber and is analyzed for smoke particles using the detector installed there. The sensitivity of the detector can be adjusted.
The position and size of the aspirating holes are calculated with the 'FXS2056 ASD Asyst Tool V2' software. The calculation ensures that the air passes from the aspirating hole to the detector in the time specified and with the required calculated sensitivity.
software.
Examples of application
Cavities such as false ceilings or false floors
Clean rooms
Rooms the height of which is greater than that permitted for point detectors
Rooms with electromagnetic fields which influence the function of point detectors
Large rooms up to 800 m²
Separate monitoring of control cabinets and electronics cabinets
Data centers
Telecommunication centers
Mounting lines
Cable tunnels
Conveyor belts
Fire Safety 2019-01-24
3
Building Technologies
A6V10331032_j_en_
--
Functions
Applications with a filter box
Rooms with polluted air, in which the pollution has impaired the performance of optical point detectors
Mounting lines
Recycling facilities
Cement factories
Mining industry
Subway stations
Agricultural operations
All other applications with visible dust load
Indication
The display contains clear, comprehensible bar graphs for smoke and airflow, as well as an alarm indicator, an error indicator, and a dust indicator (FDA241).
When the housing cover is open, the operator has access to the 'Reset', 'Normalize Smoke', and 'Normalize Flow' functions, as well as the mini USB connector.
Front indicator FDA241
Front indicator FDA221
Fire Safety 2019-01-24
4
Building Technologies
A6V10331032_j_en_
--
Legend for the response indicators
Damage to the
connection cable
2
Operation Flow warnings Smoke alarm Info alarm
High flow
out
Blowing
Error Fire 1
Normal flow
Low flow
Fire 2
Pre-alarm
No smoke
Fault/test
Dust
Opening the detector
CAUTION
In order to prevent damage to the connection cable when positioning the housing cover, make sure that the connection cable has been routed correctly.
The service area for the detector can be accessed in two ways.
Partial access: – Remove the two screws on the top of the detector. – Slide the housing cover up until you hear it snap into place.
Full access: – Remove the two screws on the top of the detector. – Slide the housing cover up until you hear it snap into place. – Pull the housing cover out slightly at the sides and lift it up. – Remove the housing cover.
Fire Safety 2019-01-24