SINAMICS V60 Controlled Power Module (CPM60.1) Getting Started EN-9
Technical data for transformer
Recommended transformer type 380 V/220 V SG series 3AC isolating transformer
V022/083CA3egatlovylppuS
50/60 Hz
Connection group Y/Y-12
Impedance voltage (Uk%) 4
No-load current (%) For a transformer =< 1.0 kVA, the no-load current < 18%;
For a transformer > 1.0 kVA, the no-load current < 14%.
Possible motor combination Transformer power (apparent power)
AVk0.1mN4
AVk5.1mN6
AVk0.2mN7.7
AVk5.2mN01
AVk5.1mN4+mN4
AVk5.1mN6+mN4
AVk5.1mN7.7+mN4
AVk0.2mN01+mN4
AVk0.2mN6+mN6
AVk0.2mN7.7+mN6
AVk5.2mN01+mN6
AVk0.2mN7.7+mN7.7
AVk5.2mN01+mN7.7
AVk0.3mN01+mN01
4 Nm + 4 Nm + 4 Nm 1.5 kVA
4 Nm + 4 Nm + 6 Nm 1.5 kVA
4 Nm + 4 Nm + 7.7 Nm 2.1 kVA
4 Nm + 4 Nm + 10 Nm 2.0 kVA
4 Nm + 6 Nm + 6 Nm 2.0 kVA
4 Nm + 6 Nm + 7.7 Nm 2.0 kVA
4 Nm + 6 Nm + 10 Nm 2.5 kVA
4 Nm + 7.7 Nm + 7.7 Nm 2.5 kVA
4 Nm + 7.7 Nm + 10 Nm 2.5 kVA
4 Nm + 10 Nm + 10 Nm 3.0 kVA
6 Nm + 6 Nm + 6 Nm 2.0 kVA
6 Nm + 6 Nm + 7.7 Nm 2.0 kVA
6 Nm + 6 Nm + 10 Nm 2.5 kVA
6 Nm + 7.7 Nm + 7.7 Nm 2.5 kVA
6 Nm + 7.7 Nm + 10 Nm 2.5 kVA
7.7 Nm + 7.7 Nm + 7.7 Nm 2.5 kVA
Power selection (for standard
turning/milling machines)
7.7 Nm + 7.7 Nm + 10 Nm 3.0 kVA
6 Nm + 10 Nm + 10 Nm 3.0 kVA
7.7 Nm + 10 Nm + 10 Nm 3.0 kVA
10 Nm + 10 Nm + 10 Nm 3.5 kVA
CAUTION
To reduce the risk of electric shock, interference from power supply and electromagnetic
field, an isolating transformer is necessary for the 3AC 380V mains system.
The customer may select the right transformer with reference to the table above
(Determine the right transformer power based on desired motor combinations)