Siemens SDV7 Instruction Manual

Instruction manual
Type SDV7 non-arc-resistant distribution circuit breaker
Installation operation maintenance E50001-F710-K377-V6-4A00
www.usa.siemens.com/sdv7
Arc flash hazard and hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before maintenance. Read and understand this instruction manual before using equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.
Important
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligation. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence.
Qualified person
For the purpose of this instruction manual a qualified person is one who has demonstrated skills and knowledge related to the installation, construction and operation of the equipment and the hazards involved. In addition, this person has the following qualifications:
Is trained and authorized to
de-energize, clear, ground and tag circuits and equipment in accordance with established safety procedures.
Is trained in the proper care and use of protective equipment,
such as: rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.
Is trained in rendering first aid.
Further, a qualified person shall also be familiar with the proper use of special precautionary techniques, personal protective equipment, insulation and shielding materials, and insulated tools and test equipment. Such persons are permitted to work within limited approach of exposed live parts operative at 50 volts or more, and shall, at a minimum, be additionally trained in all of the following:
The skills and techniques necessary to distinguish exposed
energized parts from other parts of electric equipment
The skills and techniques necessary to determine the nominal
voltage of exposed live parts
The approach distances specified in NFPA 70E® and the
corresponding voltages to which the qualified person will be exposed
The decision-making process necessary to determine the degree
and extent of the hazard and the personal protective equipment and job planning necessary to perform the task safely.
Note:
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local sales office.
Table of contents
Introduction 04 – 05
General description 06 – 07
Receiving, handling and storage 08 – 10
Installation 11 – 13
Electrical connections 14
Instrument transformers 15 – 16
The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Industry, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Industry, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
Installation of type SDV7-SE distribution circuit breaker with stored-energy operator 17 – 24
Installation of type SDV7-MA distribution circuit breaker with magnetic-actuator operator 25 – 34
Maintenance 35 – 42
Maintenance and troubleshooting 43 – 47
Appendix 48 – 55
Introduction
Arc flash hazard and hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before maintenance. Read and understand this instruction manual before using equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.
Arc flash hazard, hazardous voltages and high-speed moving parts.
Will cause death, serious injury or property damage.
To avoid arc flash burns, electrical shock and entanglement in moving parts, only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all danger or warning notices, and procedures contained herein. Personnel must observe all applicable regulations (e.g., OSHA), follow all requirements of NFPA 70E and adhere to specific operating procedures applicable to the installation. Use appropriate personal protective equipment (PPE) for the voltage and arc flash incident energy exposure.
4
Introduction
The type SDV7 distribution circuit breaker is designed to meet all applicable ANSI, NEMA and IEEE standards. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the proper design and fabrication by Siemens.
The purpose of this instruction manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment.
This instruction manual applies to the type SDV7 distribution circuit breaker enclosure, including the type SDV7-SE model with stored-energy operator and the type SDV7­MA model with magnetic-actuator operator.
Refer to instruction manual E50001-F710­K376-X-XXXX for instructions applicable to the type 3AH35-SE stored-energy operator used in the type SDV7-SE circuit breaker.
Refer to instruction manual E50001-F710­K378-X-XXXX for instructions applicable to the type 3AH35-MA magnetic-actuator operator used in the type SDV7-MA circuit breaker.
Field service operation and warranty issues
Siemens can provide competent, well-trained field service representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and systems. Contact regional service centers, sales offices or the factory for details, or telephone Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
For medium-voltage customer service issues, contact Siemens at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
Contact the nearest Siemens representative if any additional information is desired.
Signal words
The signal words “danger,” “warning” and “caution” used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as:
Danger - Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.
Warning - Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
Caution - Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury.
Notice - Indicates a potentially hazardous situation that, if not avoided, may result in property damage.
5
General description
The instructions included in this instruction manual are provided to aid you in obtaining longer and more economical service from your Siemens type SDV7 distribution circuit breaker. For proper installation and operation, this information should be distributed to your operators and engineers.
By carefully following these instructions, difficulties should be avoided. However, these instructions are not intended to cover all details of variations that may be encountered in connection with the installation, operation and maintenance of this equipment.
Should additional information be desired, including replacement instruction manuals, contact your local Siemens representative.
Scope
These instructions cover the installation, operation and maintenance of Siemens type SDV7 distribution circuit breaker using vacuum interrupters. The equipment designs
Figure 1: Typical type SDV7 distribution circuit breaker
Introduction
Siemens type SDV7 distribution circuit breaker is precision built equipment designed to function efficiently under normal operating conditions. It is designed and manufactured to operate within the parameters established in ANSI/IEEE C37 and NEMA standards for distribution circuit breakers. Performance requirements of these standards have been met or exceeded by these designs. Specific standards which apply include:
ANSI/IEEE C37.04-1999 rating structure
for ac high-voltage circuit breakers
ANSI/IEEE C37.06-2009 preferred ratings
ac high-voltage circuit breakers
ANSI/IEEE C37.09-1999 test procedure for
ac high-voltage circuit breakers
NEMA SG4-2009 ac high-voltage circuit
breakers.
described in this instruction manual consists of free-standing outdoor distribution circuit breakers for application up to 38 kV. A typical type SDV7 distribution circuit breaker is shown in Figure 1: Typical type SDV7 distribution circuit breaker. All diagrams, descriptions and instructions apply to all of the above classes and designs unless noted otherwise.
Standard construction details of the circuit breaker enclosure are given in appropriate sections of this instruction manual.
Standard construction details of the stored­energy operating mechanism of the circuit breaker are detailed in the type 3AH35-SE stored-energy operator instruction manual E50001-F710-K376-X-XXXX.
Standard construction details of the magnetic-actuator operating mechanism of the circuit breaker are detailed in the type 3AH35-MA magnetic-actuator operator instruction manual E50001-F710-K378-X­XXXX.
6
Special mechanical and electrical devices, furnished in accordance with purchase order requirements, are covered by supplementary instructions submitted with this instruction manual.
The equipment furnished has been designed to operate in a system having the circuit capacity specified by the purchaser. If for any reason the equipment is used in a different system or if the short-circuit capacity of the system is increased, the ratings of the equipment, including the momentary rating and the interrupting capacity of the type SDV7 distribution circuit breaker must be checked. Failure on the part of the user to receive approval of intended changes from Siemens may cause the warranty to be void.
This instruction manual applies to the type SDV7 distribution circuit breaker enclosure structure.
Refer to instruction manual E50001-F710­K376-X-XXXX for instructions applicable to the type 3AH35-SE stored-energy operator.
Refer to instruction manual E50001-F710­K378-X-XXXX for instructions applicable to the type 3AH35-MA magnetic-actuator operator.
General description
The distribution circuit breaker described in this instruction manual is of the ac high­voltage outdoor circuit breaker type, as defined in ANSI/IEEE C37 and NEMA SG4 standards. All high-voltage parts excluding roof bushings are completely enclosed within grounded barriers. The secondary control devices and primary circuits are isolated from each other by barriers.
Siemens type SDV7 distribution circuit breakers carry a type designation, as shown in Table 1: Type SDV7 distribution circuit breaker designations. This designation may appear on drawings and familiarity with them will simplify communications with the factory.
In this instruction manual, reference to type SDV7 distribution circuit breaker is used when the text applies to the circuit breaker with either type of operating mechanism. When relevant to the type of operator, the type SDV7-SE (stored-energy) or type SDV7-MA (magnetic-actuator) designations are used.
Operator Type
Stored energy SDV7-SE
Magnetic actuator SDV7-MA
Table 1: Type SDV7 distribution circuit breaker designations
7
Receiving, handling and storage
Receiving
Each type SDV7 distribution circuit breaker is securely blocked and braced for shipment. It is crated, boxed or covered as required by shipping conditions. If special handling is required, it is so indicated. Relatively delicate instruments, protective relays and other devices are included, and the type SDV7 distribution circuit breaker must be handled carefully when unloading.
Inspection and unpacking
Inspect the equipment as soon as possible after receipt for any damage that may have occurred in transit. Before unpacking, examine the package itself, as a damaged package may indicate damage to the contents of the package. Be careful when unpacking equipment. The use of sledge hammers and crowbars may damage the finish, or the equipment itself. Use nail pullers. After unpacking, examine equipment for any possible damage. Check the shipping manifest to be certain that all items have been received.
Note: If there is a shortage, make certain it is noted on the freight bill and contact the carrier immediately. Notify Siemens medium­voltage customer service at +1 (800) 347­6659 (+1 (919) 365-2200 outside the U.S.) of any shortage or damage.
1. When shipment arrives, note whether equipment is properly protected from the elements. Note trailer number on which the equipment arrived. Note blocking of equipment. During unloading, make sure to count the actual items unloaded to verify the contents as shown on the delivery receipt.
2. Make immediate inspection for visible damage upon arrival and prior to disturbing or removing packaging or wrapping material. This should be done prior to unloading when possible. When total inspection cannot be made on vehicle prior to unloading, close inspection during unloading must be performed and visible damage noted on the delivery receipt. Take pictures if possible.
3. Any visible damage must be noted on the delivery receipt and acknowledged with the driver’s signature. The damage should be detailed as much as possible. It is essential that a notation “possible internal damage, subject to inspection” be included on delivery receipt. If the driver will not sign the delivery receipt with damage noted, the shipment should not be signed for by the consignee or their agent.
Shipping damage claims
Important: The manner in which visible
shipping damage is identified by consignee prior to signing the delivery receipt can determine the outcome of any damage claim to be filed.
Notification to carrier within 15 days for concealed damage is essential if loss resulting from unsettled claims is to be eliminated or minimized.
8
4. Notify Siemens immediately of any damage, at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
5. Arrange for a carrier inspection of damage immediately.
Important: Do not move equipment from the place it was set when unloading. Also, do not remove or disturb packaging or wrapping material prior to carrier damage inspection. Equipment must be inspected by carrier prior to handling after receipt. This eliminates loss due to claims by carrier that equipment was damaged or further damaged on site after unloading.
6. Be sure equipment is properly
protected from any further damage by covering it properly after unloading.
7. If practical, make further inspection for possible concealed damage while the carrier’s inspector is on site. If inspection for concealed damage is not practical at the time the carrier’s inspector is present, it must be done within 15 days of receipt of equipment. If concealed damage is found, the carrier must again be notified and inspection made prior to taking any corrective action to repair. Also notify Siemens immediately at +1 (800) 347­6659 or +1 (919) 365-2200 outside the U.S.
Note: Shipments are not released from the factory without a clear bill of lading. Approved methods are employed for preparation, loading, blocking and tarping of the equipment before it leaves the Siemens factory. Any determination as to whether the equipment was properly loaded or properly prepared by shipper for over-the­road travel cannot be made at the destination. If the equipment is received in a damaged condition, this damage to the equipment has to have occurred while en route due to conditions beyond Siemens control. If the procedure outlined above is not followed by the consignee, purchaser or their agent, Siemens cannot be held liable for repairs. Siemens will not be held liable for repairs in any case where repair work was performed prior to authorization from Siemens.
8. Obtain the original of the carrier inspection report and forward it along with a copy of the noted delivery receipt to Siemens at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. Approval must be obtained by Siemens from the carrier before any repair work can be performed. Before approval can be obtained, Siemens must have the above referenced documents. The carrier inspection report and/or driver’s signature on the delivery receipt does not constitute approval to repair.
9
Lifting and moving
There are a number of methods that can be used in handling the type SDV7 distribution circuit breaker that, when properly employed, will not damage the type SDV7 distribution circuit breaker. The handling method used will be determined by conditions and available equipment at the installation site. Lifting with a crane by the use of a sling and lifting lugs is the preferred method of handling; however, overhead obstructions often dictate that other methods must be used. Forklift trucks may
A
~60°
be used prior to removal of wooden skids. Verify the forklift blades pass completely through the wooden skid under the circuit breaker.
Each type SDV7 distribution circuit breaker has provisions for attaching lifting cables. Lifting lugs are provided on two sides of the circuit breaker, which are designed for use with a lift sling or hooks of the proper size and a crane of adequate height and capacity. Refer to the type SDV7 distribution circuit breaker nameplate for the weight.
Lifting type SDV7 distribution circuit breaker with crane
Recommended lifting of type SDV7 distribution circuit breakers is by means of cables connected to an overhead crane. The cables are connected to the lifting lugs on the top of the type SDV7 distribution circuit breaker as illustrated in Figure 2: Lifting type SDV7 distribution circuit breaker with crane. A crane with sufficient height should be used so the load angle on the lifting cable will be approximately 60° when viewed from the front or rear.
Storage
When it is necessary to store a type SDV7 distribution circuit breaker in an area exposed to the weather or under humid conditions, energize the space heaters provided and make certain that any vents are uncovered to allow air to circulate. If at all possible, install the type SDV7 distribution circuit breaker at the permanent location even though it may be some time before the equipment is used. It is also recommended that the type SDV7 distribution circuit breaker receive periodic inspection during storage.
dimensions in inches (mm)
15.5 kV, 1,200 A­2,000 A
41
(1,040)
distribution circuit breaker with
Value A
15.5 kV
3,000 A
and
27.6 kV
1,200 A-
2,000 A
48
(1,220)
Figure 2: Lifting type SDV7
38.0 kV, 1,200 A­2,500 A
(1,550)
61
crane
Access to the heater circuit is gained by opening the door to the relay and control compartment. Refer to the wiring diagram drawing for space heater circuit connections. Lubricate hinges and other moving parts.
Heavy weight.
Can result in death, serious injury or property damage.
Observe all handling instructions in this instruction manual to prevent tipping or dropping of equipment.
10
Installation
Preparation for installation
Prior to installation of the type SDV7 distribution circuit breaker, careful design, planning and construction of the foundation or base on which the circuit breaker will rest must be made. A thorough analysis and careful construction may alleviate many problems at the time of installation, and during operation. It is important that a relatively level surface be provided capable of supporting the weight of the type SDV7 distribution circuit breaker, and 0.75 inch diameter anchor bolts are recommended.
Figure 4: Anchoring type SDV7 distribution circuit breaker on page 13 illustrates typical locations for anchor bolts. No special leveling procedures are required.
Prior to installation of a type SDV7 distribution circuit breaker, study this instruction book and the circuit breaker drawings, such as general arrangement/ outline drawing, schematic diagram, connection diagrams, current transformer connection diagram, electrical bill of material and nameplate engraving.
Special attention should be given to the foundation information contained in this instruction manual as well as the information provided on the equipment drawings. Verify the foundation conforms to the requirements described in this instruction manual and the general arrangement/outline drawing.
The type SDV7 distribution circuit breaker is shipped with the legs attached. The legs must be set to the desired height.
Setting leg height
The type SDV7 distribution circuit breaker is shipped with the legs set to a low level (and on some units, turned outward). The legs must be removed and installed correctly.
Remove the legs from the enclosure. Raise the enclosure, and install the legs at the desired height.
The legs must be installed and turned inward, so that the two sides of the each leg are adjacent to the enclosure sides and the hole at the bottom of the leg is inside the perimeter of the enclosure, as in Figure 3: Outline drawing on page 12.
Use anti-seize compound (Loctite* 77164 or 77124 nickel anti-seize) on the stainless steel cap screws used to secure the legs to facilitate removal of the legs should it be required in the future.
The height (as installed) between the mounting surface (foundation) and the bottom of the enclosure must be at least 4” (102 mm) and no higher than 28” (711 mm).
High-seismic installations
Figure 3: Outline drawing on page 12 shows optional cross-braces installed for high­seismic requirements.
Cross braces can be installed if the bottom of the enclosure is at least 12” (330 mm) above the foundation.
The cross braces consist of steel links that are adaptable for all installation heights (from 13” (330 mm) to 28” (711 mm). Install the cross braces as shown in the illustration. The end of the link with a single hole is bolted to the lowest hole on the leg. The opposite link is bolted with the single­hole end bolted to one of the two highest exposed holes in the leg below the enclosure. The highest hole or second highest hole is used, as necessary to allow alignment. Then, bolt the two links together towards the middle, using whichever set of holes align.
When optional cross braces are furnished, install all eight cross braces (four sets) to obtain the required seismic performance.
Location
The circuit breaker should be located so that it is readily accessible for manual operation and inspection. Ample clearance should be provided for doors and panels to swing open, or to be removed for servicing the circuit breaker.
1
/2-13 SAE
* Loctite is a registered trademark of Henkel Corporation.
11
Figure 3: Outline drawing
1
Note 1: Shown with optional cross-bracing for high-seismic loading, and with legs installed at maximum height 28" (711 mm).
Dimensions in inches (mm)
A
B
C
E E
2-4-6 1-3-5
H
G
I
J
D
K
L
High-voltage
compartment
TU
Operator compartment
M
N
Relay and
control
compartment
O
Ground pads on diagonally opposite corners
S
P
Note 1
Q
R
27.6 kV
1,200 A-
2,000 A
38.0 kV
1,200 A-
2,500 A
Item
15.5 kV
1,200 A-
2,000 A
15.5 kV 3,000 A
Note 1
27.6 kV
1,200 A-
2,000 A
F
38.0 kV
1,200 A-
2,500 A
Item
15.5 kV
1,200 A-
2,000 A
15.5 kV 3,000 A
A 47.1 (1,196) 56.3 (1,430) 56.3 (1,430) 65.7 (1,669) L 3.0° 3.0° 3.0° 3.0°
B 10.6 (269) 12.1 (307) 12.1 (307) 13.4 (340) M 35.8 (909) 44.2 (1,123) 44.0 (1,118) 55.6 (1,412)
C 13.0 (330) 16.0 (406) 16.0 (406) 19.5 (495) N 7.6 (193) 7.7 (196) 7.6 (193) 9.5 (241)
D 2.0 (51) 2.0 (51) 2.0 (51) 2.0 (51) O 28.4 (721) 36.5 (927) 36.4 (925) 46.1 (1,171)
E 8.0 (203) 8.0 (203) 8.0 (203) 8.0 (203) P 3.0 (76) 3.0 (76) 3.0 (76) 3.0 (76)
F 42.7 (1,085) 52.0 (1,321) 52.0 (1,321) 63.1 (1,603) Q 31.3 (795) 39.4 (1,001) 39.4 (1,001) 50.9 (1,293)
G 44.5 (1,130) 57.8 (1,468) 49.6 (1,260) 63.2 (1,605) R 38.8 (986) 47.0 (1,194) 46.8 (1,189) 58.4 (1,483)
H 8.0 (203) 18.4 (467) 11.5 (292) 20.4 (518) S
4.0 (102)-
28.0 (711)
4.0 (102)-
28.0 (711)
4.0 (102)-
28.0 (711)
4.0 (102)-
28.0 (711)
I 19.8 (503) 21.0 (307) 21.0 (307) 22.2 (564) T 73.5 (1,867) 77.2 (1,961) 77.6 (1,971) 93.5 (2,375)
J 8.0 (203) 18.4 (467) 11.5 (292) 20.4 (518)
K 3.0° 3.0° 3.0° 3.0°
U
92.0 (2,337)-
116.0 (2,945)
96.0 (2,337)-
120.0 (3,048)
96.0 (2,337)-
120.0 (3,048
120.5 (3,061)-
144.5 (3,670)
12
Figure 4: Anchoring type SDV7 distribution circuit breaker
A
B
GH
C
F
E
Dimensions in inches (mm)
Item
A 47.1 (1,196) 56.5 (1,435) 56.5 (1,435) 67.8 (1,722)
B 42.7 (1,085) 52.0 (1,321) 52.0 (1,321) 63.1 (1,603)
C 6.0 (152) 6.0 (152) 6.0 (152) 6.0 (152)
D 12.0 (305) 12.0 (305) 12.0 (305) 12.0 (305)
E 21.3 (541) 26.0 (660) 26.0 (660) 31.5 (800)
F 4.9 (124) 3.9 (99) 4.9 (124) 5.1 (130)
G 31.3 (795) 39.4 (1,001) 39.4 (1,001) 50.7 (1,288)
H 36.1 (917) 44.2 (1,123) 44.2 (1,123) 55.6 (1,412)
I (Outer
door)
J (Inner
relay
panel,
when
supplied)
15.5 kV
1,200 A-
2,000 A
40.0 (1,016) 46.5 (1,181) 46.5 (1,181) 46.8 (1,189)
36.0 (914) 42.8 (1,087) 42.8 (1,087) 41.3 (1,049)
15.5 kV 3,000 A
27.6 kV
1,200 A-
2,000 A
D
38.0 kV
1,200 A-
2,500 A
I
I
J
J
I
I
13
Electrical connections
Hazardous voltages and high speed moving parts.
Will cause death, serious injury or property damage.
Do not work on energized equipment. Always de-energize and ground high­voltage conductors before working on or near them. The user must adjust the circuit breaker height to ensure compliance with safety codes for electrical clearance.
14
Primary lead connections
The primary leads must be routed to the bushing terminals so as to maintain adequate dielectric clearance between different phase conductors and to ground. Conductors must be supported so that the circuit breaker bushings are not subjected to excessive strains, both during normal service and in the event of a short-circuit condition. The leads should be sized to have a capacity at least equal to the maximum operating current of the circuit and within the rating of the type SDV7 distribution circuit breaker. Connections are to be made to the bolted terminals of the bushings and must be securely tightened to a clean, bright surface to assure good contact.
Ground connections
Grounding pads on diagonally opposite corners of the enclosure are provided for connecting the cabinet to ground. The grounding conductors should be at least 4/0 AWG conductor on each ground pad. A good low-resistance ground is essential for adequate protection and for proper functioning of electronic components such as protective relays. Connections to ground pads must be made in such a manner that a reliable ground connection is obtained. Consult latest National Electrical Code® or National Electric Safety Code® for ground connection standards.
Secondary control wiring
All secondary control wiring installed by the factory is neatly routed and secured in place. Complete all field connections in a similar manner. Check that the protective relay panel (if so equipped) clears any additional wiring installed.
A conduit panel opening is provided in the bottom of the relay and control compartment for the connection of control circuits. The control wires should be run separately from high-voltage wiring to prevent inductive coupling between them and should be sized for full operating current to avoid a drop in voltage below that specified on the nameplate. All conduits should be sealed off at their entrance to the relay and control compartment.
Terminal blocks are provided inside the relay and control compartment for the connections necessary for the control wiring and protective relay panel (if so equipped). Terminal blocks for current transformer wiring are located in the operator compartment and wires can easily be routed from the conduit panel opening in the relay and control compartment to the current transformer circuit terminal blocks in the operator compartment. Consult the connection diagrams for the location of connection terminal points for each circuit.
Connection diagrams are provided with each type SDV7 distribution circuit breaker and will be found in the pocket inside the relay and control compartment door.
Instrument transformers
Hazardous voltages.
Will cause death, serious injury or property damage.
Do not operate current transformers with the secondary open circuited. Current transformers must be either connected to a load or short circuited. Current transformer secondary circuits also must be grounded.
Current transformers (CTs)
Figure 5: Type SDV7 distribution circuit breaker with interphase barriers and bushing current transformers installed in primary compartment on page 16 illustrates bushing (toroidal) CTs installed in the primary compartment of a type SDV7 distribution circuit breaker. The roof bushings pass through the CTs. Up to two CTs may be mounted around each roof bushing. The bushing CT connections are wired to separate terminal blocks located in the low-voltage operator compartment.
Phase barriers
Phase barriers are provided on all 27.6 kV and 38 kV class type SDV7 distribution circuit breakers as shown in Type SDV7 distribution circuit breaker with interphase barriers and bushing current transformers installed in primary compartment on page
16. These plates of insulating material are attached to the circuit breaker housing and provide suitable electrical insulation between the vacuum interrupter primary circuits.
15
Figure 5: Type SDV7 distribution circuit breaker with interphase barriers and bushing current transformers installed in primary compartment
2-4-6 1-3-5
A
E
Bushings 2-4-6
B
B
B
D C
Vacuum interrupter
X1 X2 X3 X4 X5 X1 X2 X3 X4 X5 X5 X4 X3 X2 X1 X5 X4 X3 X2 X1
X XY Y
Current transformer positions Current transformer positions
Bushings 1-3-5
Item Description
A Bushing current transformer (one per bushing shown)
B Phase barriers apply only in 27.6 kV and 38 kV
C Relay and control compartment
D Operator compartment
E High-voltage compartment
16
Note: Arrangement shown with four sets of multi-ratio current transformers (five-lead type). Consult drawings for the specific quantity and location of current transformers on your circuit breaker.
Installation of type SDV7-SE circuit breaker with stored­energy operator
Hazardous voltages and high speed moving parts.
Will cause death, serious injury or property damage.
Read instruction manuals, observe safety instructions and use qualified personnel.
Introduction
This section provides a description of the inspections, checks and tests to perform on the type SDV7-SE distribution circuit breaker prior to operation.
Inspections, checks and tests without control power
Type SDV7-SE vacuum circuit breakers are normally shipped with the primary contacts open and the springs discharged. However, prior to starting the inspection process, it is critical to first verify that the control power is de-energized, the spring-loaded mechanisms are in the discharged condition and the circuit breaker main contacts are open.
De-energizing control power in a power circuit breaker
To de-energize the control power, open the disconnect device in the relay and control compartment. Figure 6: Relay and control and operator compartments for type SDV7-SE circuit breaker with stored-energy operator on page 19 presents the location of this disconnect in a standard type SDV7-SE distribution circuit breaker.
The disconnect means shown in the photo are knife switches with fuses. Molded-case circuit breakers or pullout type fuse holders can be furnished instead when specified.
The control power disconnect device is located on the control panel in the relay and control compartment.
17
Loading...
+ 39 hidden pages