Siemens SDV-4A Instruction Manual

15.5kV, 25.8kV and 27.6kV Power Circuit Breaker
Type SDV-4A
Instructions
Installation Operation Maintenance
SGIM-3788F
Hazardous voltages and high-speed moving parts.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before maintenance. Read and understand this instruction manual before using equipment.
Maintenance should be performed only by qualified personnel. Use only Siemens parts in the repair of the equipment. Do not allow tampering with the equip­ment. Follow all safety instructions contained herein.
IMPORTANT
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and mainte­nance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of draw­ings or supplementary material or both, the latter shall take precedence.
For the purpose of this manual a qualified person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: (a) is trained and authorized to de-energize, clear, ground, and tag cir-
cuits and equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as
rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.
(c) is trained in rendering first aid.
NOTE
These instructions do not purport to cover all details or variations in equip­ment, nor to provide for every possible contingency to be met in connec­tion with installation, operation, or maintenance. Should further informa­tion be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local sales office. The contents of this instruction manual shall not be­come part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Power Transmission & Distribution Inc. The warranty contained in the con­tract between the parties is the sole warranty of Siemens Power Transmis­sion & Distribution Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
15.5kV, 25.8kV and 27.6kV Power Circuit Breaker
Table of Contents
Introduction and Safety ....................................................... 2
Introduction ............................................................................. 2
Qualified Person ...................................................................... 2
Signal Words ........................................................................... 2
Hazardous Procedures ............................................................ 2
Field Service Operation ........................................................... 2
General Description .............................................................. 3
Introduction ............................................................................. 3
Scope ...................................................................................... 3
General Description ................................................................ 3
Receiving, Handling & Storage ............................................ 4
Receiving ................................................................................ 4
Inspection ............................................................................... 4
Shipping Damage Claims ........................................................ 4
Lifting and Moving .................................................................. 5
Lifting Power Circuit Breaker with Crane ................................ 5
Storage .................................................................................... 5
Installation ............................................................................. 6
Location .................................................................................. 6
Preparation for Installation ...................................................... 6
“X” Bracing Installation Instructions
(for High Seismic Applications Only) ............................... 6
Foundation-General Requirements ......................................... 7
Electrical Connections .......................................................... 8
Primary Lead Connections ...................................................... 8
Ground Connections ............................................................... 8
Secondary Control Wiring ....................................................... 8
Instrument Transformers ..................................................... 9
Current Transformers .............................................................. 9
Installation Checks and Initial Functional Tests ............... 10
Introduction ........................................................................... 10
Inspections, Checks, And Tests Without Control Power ...... 10
Spring Discharge Check ........................................................ 10
Physical Inspections .............................................................. 11
Manual Spring Charging Check ............................................. 11
As-Found and Vacuum Check Tests ...................................... 11
Automatic Spring Charging Check ........................................ 11
Final Mechanical Inspection and
Testing Without Control Power ..................................... 11
Inspection ............................................................................. 11
Testing ................................................................................... 12
Interrupter/Operator Description ...................................... 13
Introduction ........................................................................... 13
Vacuum Interrupters ............................................................. 13
Stored Energy Operating Mechanism ................................... 13
Modes Of Operation - Discussion ......................................... 14
Spring Charging Mode .......................................................... 14
Closing Mode ........................................................................ 15
Trip Free Mode ...................................................................... 15
Opening Mode ...................................................................... 15
Rapid Auto-Reclosing Mode ................................................. 15
Closing And Tripping Springs ................................................ 15
Trip Free Operation ............................................................... 16
Damper ................................................................................. 16
Manual Spring Charging ........................................................ 16
Spring Charging Motor .......................................................... 17
Close Solenoid, Trip Solenoid and Anti-Pump Relay ............. 17
Auxiliary Switch ..................................................................... 17
Limit Switches ...................................................................... 17
Standard Schematic Diagrams .............................................. 17
Capacitor Trip Device (Optional) ............................................ 18
Maintenance ........................................................................ 21
Inspection and Maintenance Intervals .................................. 21
Recommended Hand Tools ................................................... 21
Recommended Maintenance and Lubrication ...................... 21
De-energize the Circuit Breaker ............................................ 22
Checks Of Primary Power Path ............................................ 22
Cleanliness Check ................................................................. 22
Checks of the Stored Energy Operator Mechanism ............. 23
Maintenance and Lubrication ................................................ 23
Fastener Check ..................................................................... 23
Manual Spring Charging And Contact Erosion Checks ......... 23
Vacuum Interrupter Stroke Check ......................................... 24
Damper Assembly Check ..................................................... 25
Electrical Control Checks ...................................................... 25
Check Of The Wiring And Terminals ..................................... 25
Automatic Spring Charging Check —
Control Power Required................................................ 25
Electrical Close And Trip Check —
Control Power Required................................................ 26
Checks Of Spring Charging Motor ........................................ 26
High Potential Tests .............................................................. 26
Vacuum Integrity Check ........................................................ 26
High Potential Test Voltages ................................................. 26
Vacuum Integrity Test Procedure .......................................... 27
As-Found Insulation and Contact Resistance Tests .............. 27
Insulation and Contact Resistance Test Equipment .............. 27
Insulation and Contact Resistance Test Procedure ............... 27
Inspection And Cleaning Of Breaker Insulation .................... 28
Functional Tests .................................................................... 28
Relays and Instruments ........................................................ 28
Equipment Surfaces .............................................................. 28
Operator Adjustments ........................................................ 29
Spring Charging Adjustment ................................................. 29
Spring Release Latch “Bite” Adjustment ............................. 30
Overhaul .............................................................................. 31
Introduction ........................................................................... 31
Circuit Breaker Overhaul ....................................................... 31
Replacement At Overhaul ..................................................... 31
Replacement Of Closing Springs .......................................... 31
Replacement Of Opening Spring .......................................... 32
Replacement Of Closing and Tripping Solenoids
(Devices 52SRC and 52T) ............................................. 32
Replacement of Anti-Pump Relay (Device 52Y) .................... 32
Replacement of the Auxiliary Switch .................................... 32
Replacement of Motor Cutoff Switch (Device LS1)
and Spring Charged Switch (LS2) ................................. 33
Replacement of Trip Latch Reset Check Switch
(Device LS3) .................................................................. 33
Replacement of Damper Assembly ...................................... 34
Replacement of Spring Charging Motor (Device 88) ............ 34
Replacement of Vacuum Interrupters ................................... 34
Index of Figures and Tables .................................................. 34
Recommended Hand Tools ................................................... 34
Preparation ............................................................................ 35
Vacuum Interrupter Removal ................................................ 35
Vacuum Interrupter Replacement ......................................... 35
Periodic Maintenance and Lubrication Tasks ................... 39
Troubleshooting .................................................................. 40
Ordering Replacement Parts ................................................. 42
Appendix .............................................................................. 43
Cover 2074-98
1
Introduction and Safety
Introduction
The SDV (generic family name for SDV-4A) vacuum break­ers are designed to meet all applicable ANSI, NEMA, and IEEE standards. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the careful design and fabrication by Siemens.
The purpose of this instruction manual is to assist the user in developing safe and efficient procedures for the instal­lation, maintenance and use of the equipment.
Contact the nearest Siemens representative if any additional information is desired.
Hazardous voltages and high-speed moving parts.
Will cause death, serious injury or property damage.
To avoid electrical shock, burns and entangle­ment in moving parts this equipment must be installed, operated and maintained only by qualified persons thoroughly familiar with the equipment, instruction manuals and drawings. Read and understand this instruction manual before using equipment.
Qualified Person
For the purpose of this manual a Qualified Person is one who is familiar with the installation, construction or opera­tion of the equipment and the hazards involved. In addi­tion, this person has the following qualifications:
Caution - indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
Caution (without safety alert symbol) - indicates a poten­tially hazardous situation which, if not avoided, may re­sult in property damage.
Hazardous Procedures
In addition to other procedures described in this manual as dangerous, user personnel must adhere to the follow­ing:
1. Always work only on a de-energized breaker. The breaker should be isolated, grounded, and have all control power removed before performing any tests, maintenance or repair.
2. Always perform maintenance on the breaker after the spring-charged mechanisms are discharged (except for test of the charging mechanisms). Check to be certain that the indicator flags read OPEN and DISCHARGED.
3. Always let an interlock device or safety mechanism per­form its function without forcing or defeating the de­vice.
Field Service Operation
Siemens can provide competent, well-trained Field Service Representatives to provide technical guidance and advi­sory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and sys­tems. Contact regional service centers, sales offices or the factory for details, or telephone Siemens Field Service at 1-877-742-3309.
• Training and authorization to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices.
• Training in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shields, flash clothing, etc., in accordance with established safety procedures.
• Training in rendering first aid.
Signal Words
The signal words “Danger”, “Warning” and “Caution” used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as:
Danger - Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious in­jury.
2
General Description
The instructions included in this manual are provided to aid you in obtaining longer and more economical service from your Siemens Circuit Breakers. For proper installa­tion and operation, this information should be distributed to your operators, engineers and maintenance personnel.
By carefully following these instructions, difficulties should be avoided. However, the instructions are not intended to cover all details of variations that may be encountered in connection with the installation, operation and maintenance of this equipment.
Should additional information be desired, including replace­ment instruction books, contact your Siemens representa­tive.
Scope
These instructions cover the installation, operation and maintenance of Siemens type SDV power circuit breakers using vacuum interrupters. The equipment described in this manual consists of free standing outdoor power cir­cuit breakers for application up to 27.6kV. A typical breaker is shown in Figure 1. All diagrams, descriptions and in­structions apply to all above types and designs unless noted otherwise.
2075-98
Figure 1. Typical Power Circuit Breaker, Type SDV-4A.
Introduction
The successful performance and application of Power Cir­cuit Breakers depends as much on proper installation, maintenance and correct application as it does on good design and careful manufacture .
Siemens Type SDV outdoor power circuit breakers are pre­cision built units designed to function efficiently under normal operating conditions. They are designed and manu­factured to operate within the limits established in the ANSI C37 and NEMA standards for Power Circuit Breakers. Per­formance requirements of these standards have been met or exceeded by these designs. Specific Standards which apply include:
Standard construction details of the circuit breaker are given in the appropriate sections. Special mechanical and elec­trical devices, furnished in accordance with purchase or­der requirements, are covered by supplementary instruc­tions submitted with this instruction manual.
The equipment furnished has been designed to operate in a system having the circuit capacity specified by the pur­chaser. If for any reason the equipment is used in a differ­ent system, or if the short-circuit capacity of the system is increased, the momentary rating and interrupting capacity of the circuit breaker must be checked. Failure on the part of the user to receive approval of intended changes from Siemens may cause voiding the warranty.
General Description
The power circuit breaker described in this manual is the AC high-voltage circuit breaker type, as defined in ANSI C37 and NEMA SG 4. All high voltage parts excluding the roof bushings are completely enclosed within grounded metal barriers. Secondary control compartment and pri­mary circuits are isolated from each other by barriers.
Siemens power circuit breakers carry a type designation as shown in Table 1. This designation may appear on draw- ings and familiarity with them will simplify communica­tions with the factory.
C37.04 AC High-Voltage Circuit Breakers - Basis of Rating C37.06 AC High-Voltage Circuit Breakers - Preferred Ratings C37.09 AC High-Voltage Circuit Breakers - Test Code SG 4 Alternating-Current High-Voltage Circuit Breakers
Table 1. Power Circuit Breaker Designation
DESIGN TYPE
Bolted Cabinet SDV-4A
3
Receiving, Handling & Storage
Receiving
Each type SDV circuit breaker is securely blocked and braced for shipment. Every precaution is taken to insure its safe arrival. Relatively delicate instruments may be in­cluded and the circuit breakers must be handled carefully when unloading and moving.
Inspection
Inspect the equipment as soon as possible after receiving for any damage that may have occurred in transit. Before unloading, make a physical inspection of the circuit breaker, checking for shipment damage or indications of rough han­dling by the carrier. Check the shipping manifest to be cer­tain that all items have been received. If there is a short­age, make certain it is noted on the freight bill and contact the carrier immediately. Notify the Siemens sales office of any shortage or damage.
Shipping Damage Claims
IMPORTANT: The way visible shipping damage is
treated by consignee prior to signing the delivery receipt can determine the outcome of the damage claim to be filed.
Notification to carrier within the 15 day limit on concealed damage is essential if loss resulting from unsettled claims is to be eliminated or minimized.
1. When shipment arrives, note whether equipment is properly secured for transit. Note trailer number on which the equipment arrived. Note blocking of equipment. During unloading, make sure count agrees with delivery receipt.
2. Make immediate inspection for visible damage upon arrival, and prior to unloading. When total inspection cannot be made on vehicles prior to unloading, close inspection during unloading must be performed and visible damage noted on the delivery receipt. Take pictures if possible.
3. Any visible damage must be noted on the delivery receipt and acknowledged with the driver’s signature. The damage should be detailed as much as possible. It is essential that a notation “Possible internal damage, subject to inspection” be included on delivery receipt. If the driver will not sign the delivery receipt with damage noted, the shipment should not be signed for by the consignee or his agent.
4. Notify the Siemens sales office immediately of any damage.
5. Arrange for a carrier inspection of damage immediately.
IMPORTANT: Do not move equipment from the place it was set when unloading. Equipment must be inspected by carrier prior to handling after receipt. This eliminates loss due to claims by carrier that equipment was damaged or further damaged on site after unloading.
6. Be sure equipment is properly protected from any further damage by covering it properly after unloading.
7. If practical, make further inspection for possible concealed damage while the carrier’s inspector is on site. If inspection for concealed damage is not practical at the time the carrier’s inspector is present, it must be done within 15 days of receipt of equipment. If concealed damage is found, the carrier must again be notified and inspection made prior to taking any corrective action to repair. Also notify Siemens sales office immediately.
8. Obtain the original of the carrier inspection report and forward it along with a copy of the noted delivery receipt to the Siemens sales office. Approval must be obtained by Siemens from the carrier before any repair work can be performed. Before approval can be obtained, Siemens must have the documents. The carrier inspection report and/or driver’s signature on the delivery receipt does not constitute approval to repair.
Note: Any adverse judgment as to whether the equipment was properly loaded or properly prepared by shipper for over-the-road travel cannot be made at the destination. Shipments are not released from the factory without a clear bill of lading. Approved methods are employed for prepa­ration, loading, blocking and securing of the equipment before it leaves the Siemens factory. Therefore, if the equip­ment is received in a damaged condition, this damage to the equipment had to occur while enroute due to condi­tions beyond Siemens control. If the procedure outlined above is not followed by the consignee, purchaser, or his agent, Siemens cannot be held liable for repairs. Siemens will not be held liable for repairs in any case where the work was performed prior to authorization from Siemens.
4
Receiving, Handling & Storage
Heavy weight with a high center of gravity. Can cause death, serious injury or property
damage.
Observe all handling instructions in this instruction manual to prevent tipping or dropping of equipment.
Lifting and Moving
There are a number of methods that can be used in han­dling the breaker, which when properly employed, will not damage the breaker. The handling method used will be determined by conditions and available equipment at the installation site. Refer to the breaker nameplate for the weight. Lifting with a crane by the use of sling and lifting lugs is the preferred method of handling; however, over­head obstructions often dictate the method to be used. Fork lift trucks may be used prior to removal of wooden skids. Be sure that the forklift blades pass completely under the breaker.
60.0"
Refer to Figure 2 for lifting of the breaker using a sling.
Each power circuit breaker has provisions for attaching lift­ing cables. Lifting lugs are provided on each side of the breaker, which are designed for use with a sling or hooks of the proper size and a crane of adequate height and ca­pacity. Refer to the breaker nameplate for the weight.
Lifting Power Circuit Breaker with Crane
Recommended lifting of power circuit breakers is by means of cables connected to an overhead crane. The cables are connected to the lifting lugs on the top of the breaker as illustrated in Figure 2. A crane with sufficient height should be used so the load angle (from horizontal) on the lifting cable will be at least 63 degrees, when viewed from the front or the rear. The minimum recommended cable length to achieve proper load angle is 134 inches hook end to hook end. A lesser angle (shorter cable) could cause damage to the equipment.
Figure 2. Lifting Power Circuit Breaker - with Crane.
Storage
When it is necessary to store a power circuit breaker in an area exposed to the weather or under humid conditions, energize the space heaters provided and make certain that any vents are uncovered to allow air to circulate. If at all possible, install the breaker at the permanent location even though it may be some time before the equipment is used. It is also recommended that the breaker receive periodic inspection during storage.
Access to the heater circuit is gained by opening the door to the instrument panel compartment. Refer to wiring dia­gram drawing for space heater circuit connections. Lubri­cate hinges and other moving parts.
5
Installation
Location
The breaker should be located so that it is readily acces­sible for manual operation and inspection. Ample clear­ance should be provided for doors and panels to swing open, or to be removed for servicing the breaker.
Preparation for Installation
Prior to installation of a power circuit breaker, study this instruction book and the breaker drawings, such as out­line, CT diagram, elementary diagram, connection diagram, relay panel diagram and electrical bill of material, and nameplate engraving. Special attention should be given to the foundation information contained in this manual as well as the information provided on the equipment draw­ings. Be sure that the foundation conforms to the require­ments described in this manual and the outline drawing. SDV breakers are shipped with the legs positioned for ship­ment. The legs must be removed, turned to the proper position and set to the desired height. Directions are given in the notice decal.
“X” Bracing Installation Instructions (for High Seismic Applications Only)
Once the SDV breaker is set in place at the correct height with the legs correctly installed, “X” bracing must be added to each of the four sides. Figure 3 shows appropriate in­stallation for the breaker at its highest elevation. Other breaker heights will use a similar configuration. The brac­ing is to run from the first hole below (nearest) the cabinet on one leg to the bottom hole of the opposite leg. When both braces are installed on any side of the breaker, they form the letter “X”.
The bracing is to be attached to each leg using 1 set of 0.5 inch SAE Grade No. 5 hardware (torqued to 50-75 ft-lbs.). The “X” bracing bars have a series of overlapping holes to allow appropriate length adjustment. The two bars form­ing each brace will use 2 sets of 0.5 inch SAE Grade No. 5 hardware (torqued to 50-75 ft-lbs.) installed in the overlap­ping holes. Refer to Figure 3 for hardware requirements.
Figure 3. “X” Bracing Installation (High Seismic Applications Only).
6
Installation
Foundation-General Requirements
Prior to installation of the breaker, careful design, planning and construction of the foundation or base on which the breaker will rest must be made. A thorough analysis and careful construction may alleviate many problems at the
time of installation, and during operation. It is important that a relatively level surface be provided capable of sup­porting the weight of the breaker, and 0.75 inch diameter anchor bolts are recommended. Figures 4 illustrates typi­cal locations for anchor bolts. No special leveling proce­dures are required.
Figure 4. Anchoring SDV-4A Power Circuit Breaker.
7
Electrical Connections
Hazardous voltages. Will cause death, serious injury, and
property damage.
De-energize and properly ground high voltage conductors before working on or near them. The user must adjust the breaker height to ensure compliance with safety codes for electrical clearance.
Primary Lead Connections
The primary leads should be brought down from above the breaker if possible, with adequate clearance to other parts, and with the proper supports so that the breaker bushings are not subjected to excessive strains.
The leads should be sized to have a capacity at least equal to the maximum operating current of the circuit and within the rating of the breaker. Connections are to be made to the bolted terminals of the bushings and must be securely tightened to a clean, bright surface to assure good contact.
Ground Connections
Diagonally opposite grounding pads are provided for con­necting the cabinet to ground, using at least a 4/0 AWG conductor on each pad. A good low-resistance ground is essential for adequate protection and for proper function­ing of electronic components such as protective relays.
Provision for connecting to ground pads must be made in such a manner that a reliable ground connection is ob­tained. Consult latest National Electrical Code or National Electric Safety Code for ground connection standards.
Secondary Control Wiring
All secondary control wiring installed by the factory is neatly routed and secured in place. Make all field connections in a similar manner. Check that the relay panel (if so equipped) clears any additional wiring installed.
A conduit panel opening is provided in the bottom of the relay and control compartment for the connection of con­trol circuits. The control wires should be run separately from high voltage wiring to prevent inductive coupling between them and should be sized for full operating cur­rent to avoid a drop in voltage below that specified on the nameplate. All conduits should be sealed off at their en­trance to the relay and control compartment.
Terminal blocks are provided inside the relay and control compartment for the connections necessary for the con­trol wiring, bushing current transformers and relay panel (if so equipped). These terminal blocks are located inside the control compartment immediately behind the control compartment access door.
Connection diagrams are provided with each breaker and will be found in the pocket inside the control compartment door.
8
Instrument Transformers
Current Transformers Figure 5 illustrates bushing (toroidal) current transformers
installed in the primary compartment of a circuit breaker. The circuit breaker roof bushings pass through the trans­formers. Type BCM current transformers are of the toroi­dal type mounted in the circuit breaker primary compart­ment. Up to two current transformers may be mounted around each roof bushing. The bushing current transformer connections are wired to separate terminal blocks located in the control and relay compartment.
Hazardous voltage. Will cause death, serious injury, and
property damage.
Current Transformers must not be operated with an open circuit and must be either connected to a burden or short circuited and grounded at the terminal blocks.
2088-98
Figure 5. Type BCM CT’s Installed in primary compartment.
View shown is looking up into cabinet roof from below
9
Installation Checks and Initial Functional Tests
Introduction
This section provides a description of the inspections, checks and tests to perform on the circuit breaker prior to operation.
Inspections, Checks, And Tests Without Control Power
Vacuum breakers are normally shipped with the primary contacts open and the springs discharged. However, prior to starting the inspection process, it is critical to
first
verify that the control power is de-energized and the spring­loaded mechanisms are in the discharged condition.
De-energizing Control Power in a Power Circuit Breaker ­To de-energize the control power, open the disconnect de­vice in the secondary control compartment. Figure 6 shows the location of this disconnect in a standard breaker.
The control power disconnect device is located on the con­trol panel in the secondary control compartment. Figure 6 shows a knife switch with fuses. Opening the knife switch de-energizes control power to the circuit breaker. In some breakers pullout type fuse holders or molded case break­ers are used in lieu of knife switches. Removal of the fuse holder or opening the molded case breaker accomplishes the same result: control power is disconnected.
Spring Discharge Check (Figure 7)
Hazardous voltages and high-speed mechanical parts.
Will cause death, serious injury or property damage.
Read instruction manuals, observe safety instructions and use qualified personnel.
The spring discharge check consists of simply performing the following tasks in the order given. This check assures that both the tripping and closing springs are fully dis­charged.
1. De-energize control power.
2. Press Trip pushbutton.
3. Press Close pushbutton.
4. Again press Trip pushbutton.
5. Verify Spring Condition Indicator shows DISCHARGED.
2078-98
6. Verify Main Contact Status Indicator shows OPEN.
Manual Trip
Manual Close
2082-98
Figure 7. Operator Control Panel of Power Circuit Breaker.
Figure 6.
2089-98
Control Power Disconnects in Power Circuit Breaker.
10
Installation Checks and Initial Functional Tests
Physical Inspections
1. Verify that the rating of the circuit breaker is compatible with the system.
2. Perform a visual shipping damage check. Clean the breaker of all shipping dust, dirt and foreign material.
Manual Spring Charging Check
1. Insert the manual spring charging lever into the manual charge handle socket as shown in Figure 8. Operate the lever up and down until the spring condition indicator shows the closing springs are Charged, and remove the lever from the socket.
2. Repeat the Spring Discharge Check.
3. Verify that the springs are discharged and the breaker primary contacts are open by observing the indicator positions.
connected to the circuit breaker. (Refer to the specific wir­ing information and rating label for your circuit breaker to determine the voltage required and where the control volt­age signal should be applied.) When control power is con­nected to the breaker, the closing springs should automati­cally charge if the control power disconnect (see Figure 6) is closed.
The automatic spring charging features of the circuit breaker must be checked. Control power is required for automatic spring charging to take place.
1. Use the manual Close and Trip controls (Figure 7) to first
Close and then Open the circuit breaker contacts. Verify contact positions visually by observing the Open/Closed indicator on the circuit breaker.
2. Open control power circuit by opening knife switch
shown in Figure 6.
3. Perform the Spring Discharge Check again. Verify that the closing springs are discharged and the primary con­tacts of the circuit breaker are open.
Final Mechanical Inspection and Testing Without Control Power
Before the circuit breaker is energized, it must be thoroughly inspected and tested. Correct any deviations before energization.
2090-98
Figure 8. Manual Charging of Closing Springs.
As-Found and Vacuum Check Tests - Perform and record
the results of both the As-Found insulation test and the vacuum check high-potential test. Procedures for these tests are described in the Maintenance Section of this manual.
Automatic Spring Charging Check Note: A temporary source of control power and test leads
may be required if the control power source has not been
Inspection
Check the following points:
1. Make a final mechanical inspection of the circuit breaker.
Verify that the contacts are in the Open position, and the closing springs are Discharged.
2. Make sure the breaker is properly set up and reason-
ably level on its foundation and appropriately anchored to the foundation.
3. Check the tightness of all hardware on the cabinet, ad-
justable legs, bushings, bus bars and operator mecha­nism.
4. See that the operating mechanism has been properly
lubricated.
5. Blocking, supports and other temporary ties removed
from breakers, instruments, relays, etc.
6. Proper fuses correctly placed.
7. Temporary wiring jumpers (used on the secondaries of
current transformers wired to external devices, as shown on wiring diagrams) removed.
8. Ground connections properly made.
11
Installation Checks and Initial Functional Tests
9. Incoming primary and secondary connections properly made and checked for shorts or undesired grounds.
10. See that all covers, and bolted connectors are securely fastened.
11. Relays coordinated with other relays and protection de­vices on the system. Refer to relay instructions before making any adjustments.
12. Examine the vacuum interrupters for damage, and wipe the interrupters and other insulating parts with a clean, dry cloth.
13. All filters in vent areas are clean and free of shipping or construction material.
14. Retouch any paint that has been damaged during in­stallation.
Shipping bracing and tag between phase barriers (on units so equipped) may damage circuit breaker.
May result in damage to equipment.
Remove bracing and tag (on units so equipped) before energizing breaker high voltage.
Testing
High Potential tests employ hazardous voltages.
Will cause death or serious injury.
Follow safe procedures, exclude unnecessary personnel and use safety barriers. Keep away from the breaker during application of test voltages. After test completion, ground both ends and the middle ring (if visible) of the vacuum interrupter to dissipate any static charges.
Note: No hazardous X-radiation is produced with closed contacts, or with open contacts with rated operating volt­age applied.
Excessive test voltages. May result in damage to equipment.
Do not perform dielectric tests at test voltages exceeding the ratings of the tested equipment.
1. An insulation resistance test is advisable on the control circuit to be sure that all connections made in the field are properly insulated.
2. A dielectric test, if possible, should be made on the high voltage circuit for one minute at the following voltages corresponding to the rated voltage of the equipment. The voltage should be raised gradually and the circuit under test should sustain the voltage for one minute. When the test is performed with the breaker open, the integrity of the vacuum interrupter will also be verified. If these levels cannot be sustained and there is no other source for the failure, the interrupter must be replaced.
Rated
Maximum
Voltage
kV (rms)
15.5
25.8, 27.6
Power Frequency Withstand
kV (rms)
50 60
Field Test Voltage
kV (rms) kV (dc)
37.5 45
53
63.6
Note: The DC test voltage is given as a reference only. It represents values believed to be appropriate and approxi­mately equivalent to the corresponding power frequency withstand test values specified for each voltage rating. The presence of this column in no way implies any requirement for a DC withstand test on AC equipment or that a DC with­stand test represents an acceptable alternative to AC with­stand tests. When making DC tests, the voltage should be raised to the test value in discreet steps and held for a pe­riod of one minute.
Vacuum interrupters may emit X-radiation. Can cause serious injury.
X-rays can be produced when a high voltage is placed across two circuit elements in a vacuum.
Keep personnel more that six (6) feet away from a circuit breaker under test. All normal metallic doors and panels must be installed during tests.
Field Dielectric Tests are recommended when new units are installed, or after major field modifications. The equip­ment should be put in good condition prior to the field test. It is not expected that equipment shall be subjected to these tests after it has been stored for long periods of time or has accumulated a large amount of dust, moisture, or other contaminants without being first restored to good condi­tion.
12
Interrupter/Operator Description
Introduction
Type SDV circuit breakers include three vacuum interrupt­ers, a stored energy operating mechanism and necessary electrical controls. On some circuit breaker ratings, insulat­ing barriers are located between the vacuum interrupters.
This section describes the operation of each major subas­sembly as an aid in the operation, installation, maintenance and repair of the type SDV vacuum circuit breaker.
Vacuum Interrupters
The operating principle of the vacuum interrupter is simple. Figure 9 is a cutaway view of a typical vacuum interrupter. The entire assembly is sealed after a vacuum is established. The interrupter stationary contact is rigidly attached to the end cap which serves as one terminal of the interrupter. The interrupter movable contact is free to move in a guide, and is connected to the operating mechanism by a system of linkages. The metal bellows assembly provides a se­cure seal around the movable contact, preventing loss of vacuum while permitting movement of the contact.
Fixed Contact Current Connection
When the two contacts separate, an arc is initiated which continues conducting up to the following current zero. At current zero, the arc extinguishes and any conductive metal vapor which has been created by and supported the arc condenses on the contacts and on the surrounding vapor shield. Contact materials and configuration are optimized to achieve arc motion and to minimize switching distur­bances.
The arc drawn in the vacuum breaker is not cooled. The metal vapor plasma is highly conductive and the resulting arc voltage only attains values between 20V and 200V. For this reason and because of the short arcing times, the arc energy developed in the breaker is very small. This also accounts for the long life expectancy of the vacuum inter­rupter.
Phase barriers are provided on all 25.8kV and 27.6kV class type SDV units as shown in Figure 10. These plates of in­sulating material are attached to the circuit breaker hous­ing and provide suitable electrical insulation between the vacuum interrupter primary circuits. Phase barriers are not required in 15.5kV class type SDV units, but are available as an option.
Ceramic Insulator
Arc Shield
Fixed Contact
Moving
Contact
Ceramic
Insulator
Metal Bellows
Guide
Moving Contact Current
Connection
Figure 9. Cutaway View of SDV Vacuum Interrupter.
2097-98
Figure 10. Breaker with Interphase Barriers.
Stored Energy Operating Mechanism
The stored energy operating mechanism of the SDV circuit breaker is an integrated arrangement of springs, solenoids and mechanical devices designed to provide a number of critical functions. The energy necessary to close and open the contacts of the vacuum interrupters is stored in power­ful tripping and closing strings. These springs are normally charged automatically, but there are provisions for manual charging. The operating mechanism that controls charg­ing, closing and tripping functions is fully trip-free, i.e., spring charging does not automatically change the posi­tion of the primary contacts, and the closing function may be overridden by the tripping function at any time.
13
Loading...
+ 32 hidden pages