CM2N3204E / 05.2001 Siemens Building Technologies
2/20 Landis & Staefa Division
• Supervise
– the air flow in air ducts
– overloads of circulators, fans and chillers
– overtemperatures of electric air heater batteries
– risk of fire or smoke
– risk of frost
– efficiency of the heat recovery equipment
Name Type reference Remarks
FLN communication card AZI65.1
1)
see data sheet 3206
LON/BACnet communication card AZI65.2
1)
see data sheet 3207
LPB communication card AZI65.3
1)
see data sheet 3208
Instructions (de, fr, it) ARG65.43
2)
included, if ordered
Instructions (en, sv, fi, no) ARG65.44
2)
included, if ordered
Instructions (nl, es, da) ARG65.45
2)
included, if ordered
Instructions (sk, hu) ARG65.47
2)
included, if ordered
1) Optional
2) Consists of operating card 2, operating instructions, and m ounting instructions
• When ordering the controller, please indicate the type reference RWI65.02. To ensure
the unit is supplied with the correct language version of the instructions, indicate the
type reference of the instructions required, e.g., ARG65.44 (for English, Swedish,
Finnish, Norwegian).
• Communication cards must be ordered separately, e.g., AZI65.1.
• Controllers and poss. communication cards are packed and supplied separately.
Name Type reference Data sheet
Temperature sensor QAA24, QAA26 1721
QAM22..., QAE21.9..., 1771, 1792
QAE22… 1771, 1792, 1791
QAD22..., QAC22, 1801, 1811
QAA64 1722
QAF63.2, QAF63.6 1821
CO
2
/VOC sensor QPA63... 1958
Processor for ventilation demand AQP63.1 1959
Remote setpoint transmitter QAA26 1721
FZA21.21, FZA61.11 3470, 3471
Signal source RVL55, 2602
PTM1.2Y10 8161
Actuator GDB161.1E; GDB163.1E 4634
GDB161.2E; GDB163.2E 4664
Automatic sensor identification (ASD logic), including type of sensor (active or passive).
Automatic activation of optimum controller configuration through ACC logic which, via
ASC, identifies the intended use of the control function. As a result, the control is
optimally matched to the plant. P-band and integral action time (TN) are separately
adjustable so that P-control (with integral action time TN = 0) or PI control can be
selected.
The controller is supplied as a PI controller. The setpoints of both heating and cooling
can be adjusted separately. Overlapping of heating/cooling sequences is not possible.
For controlling mixed air dampers or HR equipment, both the operating action and the
operating mode can be selected.
The actual values of the various outputs are permanently displayed.
Accessories
Ordering
Equipment
combinations
Technical design
Control