Siemens RLA162.5U Installation Instructions Manual

Page 1
Installation Instructions
procedures as specified.
CAUTION:
specified.
Document No. 129-450
October 5, 2009
Controller
Product Description
Room temperature controller for basic ventilation, air conditioning and heating systems. Compact design with two analog, 0 to 10 Vdc control outputs for heating and/or cooling.
Product Numbers
RLA162.5U Automatic Heat/Cool Changeover
Warning/Caution Notations
WARNING:
Required Tools
Small, flat-blade screwdriver
Wire strippers
6-inch level
Personal injury/loss of life may occur if you do not follow the
Equipment damage, or loss of data may occur if you do not follow the procedures as
Prerequisites
Provide 24 Vac power source to thermostat wall mounting location.
Run wires from damper/valve actuator to thermostat wall mounting location.
Installation
Figure 1. Acceptable Mounting Height in Inches.
Mounting Accessories
ARG70 wall plate
141-570 lockable thermostat guard
QAP22 Changeover sensor
Expected Installation Time
35 minutes
Item Number 129-450, Rev. AA Page 1 of 4
Figure 2. Airflow Requirements in Inches.
Page 2
Document No. 129-450 Installation Instructions October 5, 2009
1 2 3
4 5 6
Page 2 of 4 Siemens Industry, Inc.
Page 3
Wiring Terminals
Function
1 2 3 4 5
Action
Operating mode
Heating and cooling in sequence
Two-stage heatin g
Single-stage cooling
Single-stage heating
P (XP1)
Heating output control 10 Vdc at setpoint conditions
0 Vdc at setpoint conditions
1 Operating voltage, 24 Vac positiv e 2 Operating voltage, 24 Vac negati ve D1 Day/night changeover 5 Limitation input 0 to 10 Vdc GND Ground for day/night changeover 10 Measuring Neutral 11 Heat/cool changeover sensor 13 Fan or auxiliary relay, positive 18 Control signal, 0 to 10 Vdc, Heat 1 19 Control signal, 0 to 10 Vdc, Cool or Heat 2 20 Fan or auxiliary relay, negative
Figure 3. RLA162.5U Wiring Terminals.
Wiring Diagrams
Document No. 129-450
Installation Instructions
October 5, 2009
Figure 5. RLA162.5U Room Temperature Control with
Minimum Limitation of the Supply Air Temperature.
B2 Heat/cool changeover sensor E1 Fan or auxiliary unit F2 Freeze stat M Neutral N1 Room temperature controller (RLA162.5U) N2 Air duct temperature controller (RLM162U) as a
limiter R Resistive input S1 Time clock or switch for day/night setpoint
changeover U 0 to 10 Vdc output feedback Y 0 to 10 Vdc input signal Y1 Heating valve actuator Y2 Cooling valve actuator Z9 Limit thermostat
Figure 4. RLA162.5U Room Temperature Control with
Setpoint Changeover.
Commissioning
Control mode
Action (18) Cooling/Second stage
output Control Action (19)
The factory default setting for all five switches is OFF. Siemens Industry, Inc. Page 3 of 4
Table 1. DIP Switch Settings.
PI (integral action time 600 seconds)
0 Vdc at setpoint conditions 10 Vdc at setpoint conditions
Page 4
Document No. 129-450
Siemens Indus try, Inc.
+ 1 847-215-1000
Your feedback is important to us. If you have
Document No. 129-450
Response
Possible Causes
Valve does not
Valve travels in the
Control responds too slowly
Control is unstable
Installation Instructions October 5, 2009
Commissioning, Continued
Proportional band adjustment (XP1): Potentiometer setting should correspond to the required 0°F to 90°F (0 K to 50 K) range of the controller’s output signal.
Energy saving adjustment (ECO): Potentiometer setting should correspond to the required 0°F to 18°F (0 K to 10 K) offset of normal setpoint. Energy Saving = Normal setpoint +/- offset.
NOTE: XP1 and ECO adjustments must be made by the user; factory settings are zero or “random”.
Troubleshooting
Valve not connected
respond
wrong direction
No power supply
Selection of operating action is
wrong. DIP Switches 4 (Y1) and 5 (Y2) should match control action of the valve actuator.
Wrong controller terminal used
Reduce P-band (XP1)
Dimensions
Increase P-band (XP1)
Figure 6. Dimensions in Inches (Millimeters).
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Teflon is a registered trademark of DuPont. Product or company names mentioned herein may be the trademarks of their respective owners. © 2009 Siemens Building Technologies, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089
comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com
Printed in the USA
Page 4 of 4
Loading...