Siemens REP-1 Installation Instructions Manual

Page 1
Installation Instructions
Model REP-1 Network Repeater Module
INTRODUCTION
The Model REP-1 from Siemens Industry, Inc., is an MXL module that permits the user to extend the distance of the MXL RS-485 network as well as the distance of the NIM-1R RS-485 network. The REP-1 also supports both Style 4 and Style 7 wiring.
The MXL network uses an RS-485 inter­face for its network wiring. The RS-485 supports up to 32 nodes on each pair of wires (See Note below).
Note: A node is any location where
the network wires are con­nected to the screw terminals of an MXL System module.
The REP-1 module reproduces the RS-485 signal on a new pair of wires. The new signal makes it possible to add more nodes to the system.
OPERATION
An REP-1 Repeater module may be used to:
1. Add nodes to the end of a system network by providing a repeated network,
2. Add a Style 4 or Style 7 tap to a system, or
3. Add a Style 4 tap to a Style 7 network.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-092686-8
Figure 1
REP-1 Repeater PC Board
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
Basic Repeater Operation
(Refer to Figures 2A and 2B)
The REP-1 has two independent 2-wire RS-485 repeaters that permit the addition of another 80 ohms of wire to a Style 4 circuit by using the REP-1 at the end of the network. When an REP-1 Repeater is in place, there can be up to 64 nodes on that network; however, two of the nodes are used for the repeater module itself.
An REP-1 module uses one node on each network pair to which it is connected. Al­though this decreases the 32 available nodes on a network run, the REP-1 module adds 31 new nodes on the repeated net­work.
CSG-M Control of System Size
Even though the REP-1 supplies an increased node count in a system, the total system size is still controlled by the CSG-M. This limit guarantees that the MXL System can support the number of modules installed.
PROGRAMMING
(See Figure 1)
There is one switch (S1) and one jumper (JP1) on the REP-1 that must be set before installing the REP-1 in the MOM-4 module.
Setting the Switch on REP-1
The S1 switch on the REP-1 has two positions available.
The REP-1 module occupies one node on the original network and one node on the repeated network in both Style 4 and Style 7 wiring.
Adding a T-Tap to a System
(See Figures 2C and 2D)
If an REP-1 module is connected along a
Style 4 or a Style 7 network, the repeated network can run in a new direction. This type of setup makes it possible to have a star configuration on the network.
Converting Style 7 to Style 4 in a System
(See Figure 2E)
A Style 4 tap can be added to a Style 7 network by using an REP-1 module. This is helpful when installing RCC-1s and MOI-1s/7s in a Style 7 system if Style 7 is not required for those modules.
When an REP-1 is used to add Style 4 to a Style 7 network, REP-1 connects to two nodes, thus adding 30 new nodes.
The left-side position (7 to 4) of the switch enables conversion from Style 7 to Style 4.
Select the right-side position (NORM) of the switch if the REP-1 is used as a repeater.
Selecting the Correct Position for the JP1 Jumper
The REP-1 provides electrical isolation between the local power supply and the RS-485 lines. The JP1 jumper on the REP-1 has two positions relating to this feature—PSR and MMB.
Select the left-side position (PSR) for the jumper if the REP-1 is installed in an enclosure with a PSR-1. This set­ting protects ground fault isolation for the system. (See CAUTION on the next page.)
Select the right-side position (MMB) for the jumper if the REP-1 is installed in an enclosure with an MMB so as
to protect ground fault isolation circuits
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual,
P/N 315-092036.
.
2
Page 3
CAUTION
For NIM-1R Network
If a REP-1 is used on a NIM-1R
network, place the JP1 jumper in the
PSR position, no matter in which type
of cabinet the REP-1 is installed.
A—Basic Repeater--Style 4
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm0
tnerruCeludoMCDV42evitcAAm04
tnerruCeludoMCDV42ybdnatSAm04
B—Basic Repeater--Style 7
C—T-Tap Running in One
Direction with Style 4
* Place a 120-ohm resistor,
P/N 140-820150, where indicated.
Figure 2
REP-1 Basic Wiring (Including
placement of EOL resistors)
D—T-Tap Running in Two
Directions with Style 4
E—Conversion from Style 7
to Style 4
3
Page 4
INSTALLATION
(See Figure 3)
bottom of the card guide is in the hole on the MOM-4.
Remove all system power before installa­tion, first battery and then AC. (To power
up, first connect the AC and then the battery.)
Install the REP-1 in the MXL card cage Model MOM-4 by inserting the REP-1 board in the desired position.
The MOM-4 is shipped with a card guide in place for TB1, TB2, TB3, and TB4 on the MOM-4 board. In addition, an extra card guide is shipped with the REP-1. Place the new card guide at the end of the terminal block chosen for the REP-1 module. To install the card guide:
1. Loosen the appropriate screw in the center of the MOM-4.
2. Set the card guide in place, mak­ing sure the locating pin on the
3. Tighten the screw on the MOM-4 to secure the card guide.
4. Install the REP-1 by sliding it into the card guides and firmly seat­ing it in the card edge connector.
Checking Limits
Do not connect more than two REP-1s in series for proper operation of the network.
To be sure there are no more than two REP-1s in series, check that:
1) There are no more than two REP-1s between any MXL module and the MMB,
or
2) In an NIM-1R network, there are no more than two REP-1s between any pair of NIM-1Rs in the network.
Notes:
1. Use 18 AWG minimum wire.
2. Limit maximum resistance per pair to 80 ohms.
3. Use shielded twisted pair.
4. Terminate the shield ONLY at the MMB enclosure.
5. The wiring is power limited according to NFPA 70 per NEC 760.
6. Maximum voltage is 8V P-P.
Basic Repeater—Style 4
7. Maximum current is 150mA.
8. Use the end of line resistor P/N 140-820150 (120
9. Refer to Wiring Specification for MXL, MXL-IQ
FIGURE 2
Figure 3
4
1
/4W). See Figure 2A for further information.
ohms,
and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.
Page 5
ELECTRICAL CONNECTIONS
Basic Repeater
(See Figures 3 and 4)
A basic repeater connects to the network at the end of the run. A repeater can ex­tend the distance of the network or can add more nodes to the system. If a basic repeater is in place, the original network ends at the REP-1 and is terminated with a 120-ohm resistor.
The new repeated network begins at the REP-1 and also has an end of line resis­tor. Figure 3 shows the connection for a Style 4 network. The second half of the REP-1 is not used in this configuration, so it has both sides terminated as shown. For Style 7 networks (Figure 4) use both halves of the REP-1.
Notes:
1. Use 18 AWG minimum wire.
2. Limit maximum resistance per pair to 80 ohms.
3. Use shielded twisted pair.
4. Terminate the shield ONLY at the MMB enclosure.
5. The wiring is power limited according to NFPA 70 per NEC 760.
6. Maximum voltage is 8V P-P.
Basic Repeater—Style 7
Figure 4
5
7. Maximum current is 150mA.
8. Use the end of line resistor P/N 140-820150 (120
9. Refer to Wiring Specification for MXL, MXL-IQ
1
/4W). See Figure 2B for further information.
ohms,
and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.
Page 6
T-Tapping
(See Figure 5)
The REP-1 can be connected anywhere along a network run to provide a T-tap. Locate the REP-1 between the two ends of the primary network and do not use an EOL device where the primary network connects to the REP-1.
If, however, the tapped side runs in two directions from the REP-1, do not use an end of line resistor. Instead, place the end of line resistors at the two ends of the tapped network. For Style 7 networks use the second half of the REP-1 for the B side of the network. Repeat this method when connecting the end of line resistors on the B side of a Style 7 network.
Converting from Style 7 to Style 4
(See Figure 6)
The REP-1 can be used to provide a Style 4 tap on a Style 7 network. Figure 6 shows a Style 4 tap that begins at the REP-1. This tap can also be run in two directions if the end of line resistors are connected to the ends of the Style 4 tap. A typical use of this connection to either an RCC-1/1F or MOI-7 would be for a group of annunciators where Style 7 wiring is not required for the annun­ciators, but the rest of the system must be Style 7. Do not connect the Style 4 tap to
PSR-1s.
Notes:
1. Use 18 AWG minimum wire.
2. Limit maximum resistance per pair to 80 ohms.
3. Use shielded twisted pair.
4. Terminate the shield ONLY at the MMB enclosure.
5. The wiring is power limited according to NFPA 70 per NEC 760.
6. Maximum voltage is 8V P-P.
T-Tapping in One Direction (Style 4)
Figure 5
6
7. Maximum current is 150mA.
8. Use the end of line resistor P/N 140-820150 (120
9. Refer to Wiring Specification for MXL, MXL-IQ
1
/4W). See Figure 2D for further information.
ohms,
and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.
Page 7
Notes:
1. Use 18 AWG minimum wire.
2. Limit maximum resistance per pair to 80 ohms.
3. Use shielded twisted pair.
4. Terminate the shield ONLY at the MMB enclosure.
5. The wiring is power limited according to NFPA 70 per NEC
760.
6. Maximum voltage is 8V P-P.
7. Maximum current is 150mA.
8. Use the end of line resistor P/N 140-820150 (120 ohms, See Figure 2E for further information.
9. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.
1
/4W).
Figure 6
Conversion from Style 7 to Style 4
CONNECT ONLY TO RCC-1/1F OR MOI-7
7
Page 8
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-092686-8
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Loading...