Siemens RDUxxx Series Operating Instructions Manual

CE1B3061en / 05.02.2003 Subject to alteration Siemens Building Technologies / HVAC Products
Operating Instructions RDU…
RDU... – the temperature controller that allows you to easily set the room temperature you want. You have 2 choices. You can either rely on the factory settings or make adjustments that suit your individual needs.
Display
Settings and operation
Normal operation
Display of current room temperature or new setpoint
Warmer / colde r
Adjustment of temperature setpoints
3061Z01en
Heating valve open
Cooling valve open
Display of actual room temperature
Buttons for setpoint adjustments
Heating mode, Off, cooling mode
Operating mode selector (RDU50.2)
Are your rooms too warm or too cold?
Normal operation
The + / - buttons allow you to increase or decrease the current room temperature setpoint in s teps of 0.5 °C. To do this, proceed as follows:
Press
or once
The setpoint display starts fl ashing
Press the buttons again to change the room temperature setpoint 10 seconds after the last press, the new tem perature setpoint will automatically be stored. The display st ops flashing.
Changing from heating to cooling mode
/
Automatic changeover
With the RDU50.2, manual changeover modes selector from heating mode, Off to cooling mode. Off = out of operation.
Display shows that the heating output is active Display shows that the cooling output is active
Changing from normal operation to energy saving mode
/
Changeover from normal operation to energy saving m ode takes place automatically via an external contact (window switch / remote operation switch, etc.).
(Exception with type RDU50.2 in Off mode) Display shows normal operation. Display shows energy saving mode.
Energy saving mode
If you want to change the factory-set tem perature setpoints (16 °C for heating and 28 °C for cooling), follow the procedure given below (“Changing the control parameters”).
Important:
The setpoint of energy saving mode can be set to Off. This means that the controller is not active in energy saving mode and the parameter display s hows Off.
Risk of frost!
CE1B3061en / 05.02.2003 Subject to alteration Siemens Building Technologies / HVAC Products
Commissioning (by qualified HVAC staff)
Para­meter
Controller’s parameter factory settings:
Setting range (all settings can be made in increments of 0.5 K)
RDU20 RDU50 RDU50.2
P01
Setpoint of heating in energy saving mode (operating mode changeover switch activated)
16 °C
0: corresponds to Off (display Off) 5…18 °C
P02
Setpoint of cooling in energy saving mode (operating mode changeover switch activated)
28 °C 0: corresponds to Off (display Off) 24…35 °C
P03 Minimum setpoint limitation in normal mode
5 °C 5…20 °C
P04 Maximum setpoint limitation in normal mode
35 °C 21…35 °C
P05 Heat-cool changeover switching point cooling
16 °C 10…25 °C
X
P06 Heat-cool changeover switching point heating
28 °C 27…40 °C
X
P07 Sensor calibration 0 K -3…+3 P08 P-band in heating mode 2 K 0.5…+4 K
P09 P-band in cooling mode 1 K 0.5…+4 K
Integral action time X
P10
Integral action time (only with modulating PI control, DIP switch no. 2 is set to ON)
5 min. 1…10 min. (increments of 1 min.)
XX
Minimum output limitation in cooling mode (normal operation) 0 % 0. ..100 % (increments of 10 %) X
P11
Actuator running time (only with modulating PI control, DIP switch no. 2 is set to ON)
150 s 50...150 s (increments of 10 s ) XX
P12 Active temperature sensor (no setting, dis play only)
-
1: room temperature sensor active 2: return air temperature sensor active
P13 Value of current room temperature reading (no setting, display only)
-
0…49 °C = current temperature value
P14
Value of current heat-cool changeover temperature reading including indicat ion of current
mode (
, ) (no setting, display only)
-
100 = input open (no sensor connected, heating mode ( )) 0…49 °C = current temp. value
00 = input bridged, cooling mode (
)
P15
Test mode for checking the actuator direction (note that this parameter can be quit only if the setting is back at “---” and by pressing buttons + and – simultaneous ly)
---
“---“ = no signal on outputs Y1 and Y2 OPE = output Y1 forced open CLO = output Y2 forced open
XX
Changing the control parameters
(To optimize the control performance, a number of control parameters can be adjusted. This can also be made during operation without opening the controller.
Do you want to change the control parameters of the heating and / or cooling setpoints in the normal or energy saving mode? Or do you want to increase / decrease the switching differential in heating and cooling mode?
Then, proceed as follows:
(For factory settings, see above under “Commissioning)
1. Normal operation mode
2. Press the + and – buttons simultaneously for a min. of 3
and a max. of 5 seconds. Release them and within 2 seconds, press the + button again for 3 seconds. The display will show “P01”.
3. Select the required parameter by repeatedly pressing
the + or – button:
P01 P02 P14 P15
+-+-+
--
+
3055z01
4. Press the + and – buttons simultaneously, the current
value of the selected parameter appears, which can be changed by repeatedly pressing the + or – button.
5. By pressing buttons + and - simultaneously again or
5 seconds after the last press of a button, t he last parameter will be displayed again.
6. If you wish to display and change additional
parameters, repeat steps 3 through 5.
7. 10 seconds after the last display or setting,
all changes will be stored.
If the room temperature displayed by the controller does not agree with the temperature effectively measured, the t emperature sensor can be recalibrated. For that purpose, parameter P07 must be changed
Proceed as described under “Changing the control parame­ters” and follow steps 1 through 3 to select parameter P07.
With step 4, the room temperature dis played can now be matched to the temperature effectiv ely measured. Each push of the + or – button changes the temperature by + or –
0.5 °C up to a maximum of + / - 3 °C. With step 7, the recalibration is autom atically stored 10 seconds after the last readjustment.
Legend to table
Adjustable:please record all changes you make
Not adjustable / display only
X
Not adjustable / no display
Loading...