
RDU20U, RDU50U and
RDU50.2U
Technical Instructions
Document No. 155-735
November 1, 2006
Room Temperature Controllers
with LCD for Heating and
Cooling Systems
The RDU Series Room Controller with LCD is designed for heating and cooling
systems.
• Modulating Proportional + Integral (P+I) control
• Control depending on room or remote air temperature
• Output for a 0 to 10 Vdc actuator (RDU50U and RDU50.2U)
• Output for a floating (3-position) or on/off output actuator (RDU20U)
• Adjustable actuator run time (RDU20U)
• Automatic heating/cooling changeover (RDU20U and RDU50U)
• Manual heating/cooling changeover (RDU50.2U)
• Operating modes: Normal, Energy Saving and Off
• Operating mode changeover input for remote control
• Selectable installation and control parameters
• Adjustable minimum limitation for cooling output
• Optional selectable Direct Acting or Reverse Acting output
• Selectable display of room temperature or setpoint
• Fahrenheit or Celsius selectable
• Minimum and maximum setpoint limitation
• Operating voltage, 24 Vac
• Individual room temperature control in heating or cooling HVAC applications.
• Control of that are heated or cooled.
Automatic heating/cooling changeover
Automatic heating/cooling changeover
Manual heating/cooling changeover switch

Technical Instructions RDU20U, RDU50U and RDU50.2U Room Temperature Controllers
Document Number 155-735 with LCD for Heating and Cooling Systems
November 1, 2006
Page 2 Siemens Industry, Inc.
ARG70 Adapter Plate for 4-inch × 4-inch conduit boxes
QAH11.1 Changeover/Remote Temperature Sensor
141-570 Lockable Thermostat Guard
The temperature sensor, valves, and damper actuators must be ordered separately.
Table 2. Equipment Combinations.
0 to 10 Vdc valve actuators
44 lb-in NSR air damper actuators
88 lb-in NSR air damper actuators
Floating control valve actuators
44 lb-in NSR air damper actuators
88 lb-in NSR air damper actuators
Two-way globe zone valves
Three-way globe zone valves
Two-way globe zone valves
Three-way globe zone valves
The controller measures the room temperature with its integrated sensor or via a
remote return air temperature sensor (QAH11.1) and maintains the setpoint by
delivering continuous control commands to the actuators (0 to 10 Vdc [RDU50U and
RDU50.2U] or 24 Vac on/off, or three-position [RDU20U]). The controller provides P+I
control. The factory setting for the proportional band in heating mode is 3.6°F (2°C),
and in cooling mode 1.8°F (1°C) (adjustable). The integral action time is five minutes
(adjustable). Motor run time for the RDU20U is adjustable from 50 to 150 seconds in
10-second increments.
Figure 1. Heating/Cooling Modes.
C/O Changeover
P-band Proportional band
T Room temperature
W Room temperature setpoint
Y Y output percentage
NOTE: Diagram only shows
P-characteristic

RDU20U, RDU50U and RDU50.2U Room Temperature Controllers Technical Instructions
with LCD for Heating and Cooling Systems Document Number 155-735
November 1, 2006
Siemens Industry, Inc. Page 3
Function, Continued
RDU50U and RDU50.2U
Figure 2. Heating Mode, RA.
(DIP Switch 2 in ON Position)
Figure 3. Cooling Mode, RA.
(DIP Switch 2 in ON Position)
Figure 4. Heating Mode, DA.
(DIP Switch 2 in OFF Position)
Figure 5. Cooling Mode, DA.
(DIP Switch 2 in OFF Position)
T Room temperature
XpH Proportional band heating
XpK Proportional band cooling
W Room temperature setpoint
YOut Output percentage
NOTE: The diagrams only show the proportional part of the P+I controller.
Automatic Changeover
RDU50U and RDU20U
The water temperature measured by the changeover sensor (QAH11.1) is used by the
controller to switch from heating to cooling mode, or vice versa. When the water
temperature is above 82°F (28°C), the controller switches to Heating mode; below
61°F (16°C), it switches to Cooling mode.
If immediately after switching on, the temperature is between the two changeover
points, the controller will start in Heating mode. The medium temperature is measured
at half-minute intervals and the operational status updated. The value of the current
temperature reading and the mode can be visualized temporarily by selecting
parameter P14.
In systems without automatic changeover, the temperature sensor can be replaced by
an external switch for manual changeover. In systems with continuous heating mode,
no sensor will be connected to the controller’s input. With continuous cooling mode, the
controller changeover input must be bridged.
CM Cooling mode
HM Heating mode
M Operating mode
TW Water temperature
Figure 6. Automatic Changeover Mode.