SITOP PSU8600 24 V DC/20 A
6EP3436
SITOP PSU8600 24 V DC/40 A
6EP3437
SITOP CNX8600 4 x 5 A
6EP4436
SITOP CNX8600 4 x 10 A
6EP4437
SITOP BUF8600 100 ms/40 A
6EP4297
SITOP BUF8600 300 ms/40 A
6EP4297
SITOP BUF8600 4 s/40 A
6EP4293
SITOP BUF8600 10 s/40 A
6EP4295
05.2017
A5E36758446
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Operator control at the
device
3
Installation and maintenance
4
Mounting position, mounting
clearances
5
Installation
6
Engineering and remote
access
7
Troubleshooting
8
Technical data
9
Safety, approvals, EMC
10
Environmental conditions
11
Applications
12
Environment
13
Service & support
14
-8SB00-2AY0
-8SB00-2AY0
-8XB00-0CY0
-8XB00-0CY0
-8HB00-0XY0
-8HB10-0XY0
-8HB00-0XY0
-8HB00-0XY0
-3-76
Page 2
Siemens AG
Division Process Industries and Drives
Postfach 48 48
90026 NÜRNBERG
GERMANY
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
The product/system described in this documentation may be operated only by
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
for the specific
05/2017 Subject to change
Page 3
Overview
The SITOP PSU8600 power supply system is the high-performance, regulated technology
power supply system for automated plants and machines.
The key benefits of the product include:
● Wide-range input, which allows them to be connected to almost all 3-phase line supplies
around the world
● Number of outputs can be expanded using up to four expansion modules SITOP
CNX8600
● The output voltage of each output can be adjusted in the range 4 - 28 V
● Electronic overload shutdown for each output, the response threshold can be adjusted;
alternatively: electronic current limiting (constant current), current can be adjusted
● integrated Ethernet/PROFINET interfaces (2 port switch)
● Diagnostics data and alarm messages available via Ethernet/PROFINET
● Outputs can be switched – controlled from a program – and parameterized via
Ethernet/PROFINET
● Completely integrated in TIA: user-friendly engineering in SIMATIC STEP 7 and
SIMATIC STEP 7 in the TIA Portal,
S7 function blocks for integration in user programs and WinCC faceplates
● OPC UA interface for non-proprietary communication in automation systems
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
● Remote monitoring via the integrated web server
● Brief overload capability of 150% for 5 s/min (extra power)
7.8.6.19 User management ............................................................................................................... 260
7.8.6.20 Web server ........................................................................................................................... 261
7.8.6.21 Other .................................................................................................................................... 261
7.8.7 OPC UA - performance ........................................................................................................ 261
7.8.8 Recommissioning after a basic device has been replaced - or after restoring the
7.10 Parameter write behavior of the SITOP PSU8600 .............................................................. 263
7.10.1 writing data in the STOP or RUN mode via PROFINET ...................................................... 263
7.10.2 Retentively saved PROFINET data sets in the RUN mode ................................................. 266
7.10.3 OPC UA data sets that are always retentively saved .......................................................... 269
7.11 Identification data for PROFINET IO.................................................................................... 270
8.1 Troubleshooting based on the LED signal sequence .......................................................... 271
8.2 PROFINET alarm list ........................................................................................................... 271
8.3 Alarm list web server ............................................................................................................ 276
Power supply system PSU8600
10Manual, 05.2017, A5E36758446-3-76
Page 11
Table of contents
9 Technical data .................................................................................................................................... 285
14 Service & support ................................................................................................................................ 313
9.1 Input data .............................................................................................................................. 285
9.2 Output data ........................................................................................................................... 286
12.1 Protection against brief power failures .................................................................................. 305
12.2 Protecting against longer power failures ............................................................................... 306
12.3 Parallel connection to increase power rating ........................................................................ 307
12.4 Parallel connection for redundancy ...................................................................................... 308
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
11
Page 12
Table of contents
Power supply system PSU8600
12Manual, 05.2017, A5E36758446-3-76
Page 13
1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines, and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions only form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems, machines
and networks. Systems, machines and components should only be connected to the
enterprise network or the internet if and to the extent necessary and with appropriate security
measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into
account. For more information about industrial security, please visit:
http://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and to
always use the latest product versions. Use of product versions that are no longer supported,
and failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
http://www.siemens.com/industrialsecurity.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
13
Page 14
Safety instructions
1.1
Safety instructions for explosive environments/zones
1.1.1
Basic SITOP PSU8600 device
WARNING
1.1.2
Expansion modules SITOP CNX8600
WARNING
1.1 Safety instructions for explosive environments/zones
The devices comply with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-15.
OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!
OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!
Power supply system PSU8600
14Manual, 05.2017, A5E36758446-3-76
Page 15
2
2.1
Description of the basic devices
Designation
Number of outputs
Maximum
current at the output
Article No.
24 V DC/20 A 1 20 A
6EP3436-8SB00-2AY0
24 V DC/40 A 1 40 A
6EP3437-8SB00-2AY0
The basic devices SITOP PSU8600 are primary-clocked power supplies for connection to 3phase AC line supplies. An electronically regulated DC voltage that can be set via a
potentiometer is available at the output of the devices. The device output is isolated, no-load
and short-circuit proof and has an electronic overload trip - or alternatively overload current
limiting (constant current), which can be set using an additional potentiometer. The device
output can be switched-on and switched-off using a button.
LEDs signal the operating state of the device as well as the output. The electronic overload
shutdown is reset using the reset input and the button of the output. Additional, special
functions of the devices can be activated using selector switches (DIP).
The device output can be controlled, operating and diagnostics data transferred and
externally visualized or processed via the two integrated industrial Ethernet/PROFINET
ports. An integrated web server allows authorized users to read and write data remotely via a
web browser. Further, an OPC UA server is integrated in the devices (Open Platform
Communications Unified Architecture). This facilitates non-proprietary communication in
automation systems.
The functionality of the basic devices can be expanded using supplementary modules. There
are expansion modules to increase the number of outputs, and buffer modules to extend the
internal device power failure buffer time.
Table 2- 1 Versions of the basic units
Power supply
Power supply
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
15
Page 16
Description, device design, dimension drawing
①
AC
②
DC output
0
④
Signaling contact, remote reset
⑤
Ethernet/PROFINET interface
⑥
LED displays (OK, MAN, SF, RUN, P1/P2)
⑦
DIN rail slider
⑧
Convection
⑨
Clearance above/below
Socket at the upper side of the device for the plug connection to
optional expansion modules
⑪
Buttons of the outputs
⑫
Voltage potentiometer
⑬
Current potentiometer
from ⑭
Selector switch, special functions
2.1 Description of the basic devices
input
③
Volt terminal
⑩
with LED display "ON/OFF/RST"
Power supply system PSU8600
16Manual, 05.2017, A5E36758446-3-76
Page 17
Description, device design, dimension drawing
2.2
Description of the expansion modules
Expansion module versions
Designation
Number of outputs
Max. current per output
Article No.
4 × 5 A expansion module
4
5 A
6EP4436-8XB00-0CY0
①
Connecting plug to connect to the basic device or additional supplementary modules
②
Socket to connect to additional supplementary modules
③
DC outputs
④
GND terminal for optional ground connection to the basic device
⑤
"O.K LED."
⑥
DIN rail slider
⑦
Convection
⑧
Clearance above/below
⑨
LED buttons ON/OFF/RST
⑩
Voltage potentiometer U (V)
⑪
Current potentiometer I (A)
2.2 Description of the expansion modules
Using a SITOP CNX8600 expansion module, the number of system outputs can be
increased, however, not the maximum output power of the basic device. The expansion
modules have, just like the basic device, a potentiometer for setting, and buttons to switchon and switch-off the relevant output. LEDs signal the operating states of the expansion
module as well as the individual outputs. A maximum of four expansion modules can be
used for each basic device. The connection to the basic device or to the adjacent module is
established using an integrated connecting plug.
4 × 10 A expansion module 4 10 A 6EP4437-8XB00-0CY0
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
17
Page 18
Description, device design, dimension drawing
2.3
Description of the buffer modules
Buffer module versions
Designation
Buffer time
Typical charge
time for a rated
input voltage of
400 V
Article No.
100 ms/40 A
2.3 Description of the buffer modules
A buffer module SITOP BUF8600 allows the buffer time to be extended when the power
fails. An LED is used to signal the operating state of the buffer module. A maximum of two
buffer modules can be used for each basic unit. The connection to the basic unit or to the
adjacent module is established using an integrated connecting plug.
For brief power failures, the outputs of the power supply system are supplied without
interruption using the energy stored in the buffer module.
There are two BUF8600 buffer module versions available: Buffer modules with electrolytic
capacitors and buffer modules with double-layer capacitors.
Table 2- 2 BUF8600 buffer modules with electrolytic capacitors
Buffer module
Buffer module
300 ms/40 A
100 ms at 40 A 20 s 6EP4297-8HB00-0XY0
300 ms at 40 A 60 s 6EP4297-8HB10-0XY0
Power supply system PSU8600
18Manual, 05.2017, A5E36758446-3-76
Page 19
Description, device design, dimension drawing
①
additional modules
②
Socket at the upper side of the device for the plug connection to additional modules
③
"O.K." LED
④
DIN rail slider
⑤
Convection
⑥
Clearance above/below
2.3 Description of the buffer modules
Connecting plug at the upper side of the device for plug connection to the basic device or to
When the buffer module with electrolytic capacitors is completely charged (LED "O.K." lights
green) power failures of 100 ms or 300 ms can be buffered with a load current of 40 A. The
buffer time is correspondingly increased for lower load currents.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
19
Page 20
Description, device design, dimension drawing
Designation
Buffer time
Charge time for a rated
input voltage of 400 V
Article number
charged)
charged)
①
to additional modules
②
Socket at the upper side of the device for the plug connection to additional modules
③
"O.K." LED
④…⑥
Remote ON/OFF and signaling contacts
⑦
DIN rail slider
⑧
Convection
⑨
Clearance above/below
2.3 Description of the buffer modules
Table 2- 3 BUF8600 buffer modules with double-layer capacitors
4 s/40 A buffer module 4 s at 40 A typ. 5 min;
max. 8 min
(when completely dis-
10 s/40 A buffer module 10 s at 40 A typ. 10 min;
max. 18 min
(when completely dis-
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
Connecting plug at the upper side of the device for plug connection to the basic device or
When the buffer module with double-layer capacitors is completely charged (LED "OK" lights
green) power failures of 4 s or 10 s can be buffered with a load current of 40 A. The buffer
time is correspondingly increased for lower load currents.
Power supply system PSU8600
20Manual, 05.2017, A5E36758446-3-76
Page 21
Description, device design, dimension drawing
Note
Restriction when using a SITOP BUF8600 4 s/40 A buffer module in a 40 A- power supply
system
When using a SITOP BUF8600 4
150
not
The buffer mode is immediately exited if, during the buffer mode, a system overload > 100 %
occurs.
Brief interruption of the voltage at output 1
2.3 Description of the buffer modules
Figure 2-1 Typical buffer time as a function of the load current
s/40 A buffer module in a 40 A power supply system, the
% overload capability for 5 s/min (Extra-Power) and 300% for 25 ms (Power Boost) are
supported.
When using a buffer module with double-layer capacitors, the following additional functions
are available:
If a PC is operated on the PSU8600 power supply system, when the power fails, then this
must be run down in plenty of time before the buffer time expires in order to avoid data being
lost. If the supply voltage returns after the shutdown has already started, the buffer mode is
exited and the power supply resumes normal operation. However, the PC is run down
completely. If the PC does not have an ON/OFF-switch, then it can only be rebooted by
switching off the power supply and switching it on again.
When using a buffer module with double-layer capacitors, the "Enable short-time interruption
at output 1" function is used to activate the brief interruption of the voltage at output 1 when
the supply voltage returns. However, selection and parameterization are only possible when
appropriately configured (STEP 7, OPC UA server, web server).
You can find additional information in Chapter Engineering and remote access (Page 121)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
21
Page 22
Description, device design, dimension drawing
"Longlife" mode
2.3 Description of the buffer modules
In order to increase the service life of the buffer modules with a double-layer capacitors,
these can be operated in the "Longlife" mode with reduced buffer capacity. When the buffer
module is completely charged (LED " lights green) power failures of 3 s up to a maximum of
8 s can be buffered with a load current of 40 A. However, the "Longlife" mode is only
possible when appropriately configured (STEP 7, OPC UA server, web server).
You can find additional information in Chapter Engineering and remote access (Page 121)
Power supply system PSU8600
22Manual, 05.2017, A5E36758446-3-76
Page 23
Description, device design, dimension drawing
2.4
Connections and terminal designations
2.4.1
Basic devices
Connections and terminal designations
①
L1, L2, L3, PE
②
③
0 V
(11, 12, 14);
RST
⑤
Terminal data 6EP3436-8SB00-2AY0:
*1) Do not subject the end stop to high loads
*2) Derating 18 A/60 °C or 20 A/50 °C
2.4 Connections and terminal designations
The line input terminals ① are used to establish the connection to the supply voltage. The
output terminals
to other supplementary modules can be established using the 0 Volt terminal
The operating state of the device can be interrogated using signaling contact
terminal
Ethernet/PROFINET cable (RJ plug-in connection 8P8C) are connected at the
Ethernet/PROFINET interface
④ is used for a remote reset of the electronic overload shutdown.
② and the 0 V terminal ③ are the load connections. A ground connection
③.
④. The reset
⑤ for PROFINET operation.
Line input
Output 1
0 Volt terminal
④ Signaling contact
PROFINET (2-port switch)
See the diagram under Description of the basic devices (Page 15)
remote reset
Plug-in terminal with a screw connection
Plug-in terminal with two screw connections
Plug-in terminal with three screw connections
Common plug-in terminal with a screw connection
RJ plug connection 8P8C
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
23
Page 24
Description, device design, dimension drawing
Terminal data 6EP3437-8SB00-2AY0:
*1) Do not subject the end stop to high loads
*2) Derating 35 A/60 °C or 40 A/50 °C
Note
The Ethernet/PROFINET connection to the basic devices of the PSU8600 power supply is
optimized for use of the "Industrial Ethernet FastConnect RJ45 plugs 2x2" in an industrial
design
Commercially available RJ45 plug connectors can be used to connect to
Ethernet/PROFINET. However, when withdrawing the cable, a suitable tool must be used
(e.g. a small slotted screwdriver) in order to release
2.4 Connections and terminal designations
PROFINET/Ethernet connection
Maximum length of the Ethernet/PROFINET cable: 100 m (90 m BASIC link plus 2 x 5 m
CHANNEL link)
The interface corresponds to the standard full duplex up to 100 Mbit/s electrical (100BASETX) according to IEEE 802.3.
Properties of the interface:
● Transmission rate 10/100 Mbit/s
● Two RJ45 sockets, i.e. integrated switch, for RJ45 connector, cable type 100Base-TX
(CAT5)
● Auto negotiation
● Auto crossover communication via TCP/IP and PROFINET
The physics of the Ethernet/PROFINET interface is implemented so that PROFINET IO
according to standards IEC 61158 and IEC 61784-2 are possible. As a minimum, conformity
Class B is maintained for PROFINET.
that is insensitive to noise and interference.
the RJ45 plug connector latch.
Power supply system PSU8600
24Manual, 05.2017, A5E36758446-3-76
Page 25
Description, device design, dimension drawing
2.4.2
Expansion modules
Connections and terminal designations
1, 2, 3, 4
each output
④
GND
Terminal data 6EP4436-8XB00-0CY0, 6EP4437-8XB00-0CY0:
*1) Do not subject the end stop to high loads
2.4 Connections and terminal designations
The loads to be supplied are connected at output terminals ③. When required, a ground
connection to the basic device and to additional supplementary modules can be established
using ground terminal
④.
③ Outputs
Ground terminal
Two plug-in terminals with screw connection for
Plug-in terminal with three screw connections
See the diagram under Description of the expansion modules (Page 17)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
25
Page 26
Description, device design, dimension drawing
2.4.3
Buffer modules
Note
Terminals, only for buffer modules with double-layer capacitors
The subsequently described terminals are only available for buffer modules with double layer
capacitors (BUF8600 4
Connections and terminal designations
④
⑤
READY 13, 14
⑥
Terminal data 6EP4293-8HB00-0XY0, 6EP4295-8HB00-0XY0:
2.4 Connections and terminal designations
s / 40 A and 10 s / 40 A).
Using control contact (ON), the buffer readiness of the buffer module can be activated and
deactivated and/or buffer mode exited.
Using signaling contact "Sufficient buffer readiness" (READY) it can be interrogated as to
whether the buffer module has reached an adequate charge state. Using signaling contact
"Buffer mode" (OK) the system signals that it is currently in the buffer mode.
Control contact ON X1, X2
Signaling contact "Sufficient buffer readiness"
Signaling contact "Buffering" OK 23, 24
Common plug-in terminal, each with a screw
connection
See the diagram under Description of the buffer modules (Page 18)
Power supply system PSU8600
26Manual, 05.2017, A5E36758446-3-76
Page 27
Description, device design, dimension drawing
2.5
Operator controls
2.5.1
Basic devices
No. Designation /
labeling
Function
①
the output current (Page 56).
②
potentiometer "U (V)"
on and off (Page 57).
③
potentiometer "I (A)"
shutdown and carrying out a reset (Page 58).
④
ating modes (Page 61).
2.5 Operator controls
There are two main operating areas at the SITOP PSU8600 basic devices.
● LED buttons
The potentiometers are used to set the output voltage and response threshold of the
output current. The output can be switched-on and switched-off using the buttons; further,
a manual reset can be initiated after an electronic overload shutdown.
● The selector switch allows additional special functions to be activated via the position of
the DIP switches (
① and potentiometers (② and ③):
④ to ⑪).
LED buttons
Voltage
Current
DIP switch "REN" Switches over between the MANUAL mode – with setting and
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
"ON/OFF/RST"
Switches in and switches out the output, or resets the output
after an electronic shutdown; see Chapter Setting the output
voltage (Page 55) and Setting the response threshold value of
Sets the voltage of the relevant output; see Switching an output
Sets the response threshold of the output current; see Overload
operation at the device – and REMOTE mode with remote control via PROFINET; see Chapter MANUAL and REMOTE oper-
27
Page 28
Description, device design, dimension drawing
⑤
see Chapter Prioritization when the power fails (Page 64).
⑥
CURRENT operating modes (Page 66).
⑦, ⑧
see Chapter Setting the on delay (Page 68).
⑨
see Chapter Setting the output characteristic (Page 71).
⑩
DIP switch "FUNC"
No function
⑪
the module (Page 73)
Protection and sealing
2.5 Operator controls
DIP switch "PRY1" Prioritizes output 1 in the case of a buffering (function is only
available when a CNX8600 expansion module is being used);
DIP switch "UI-1" Defines the response of the output when an overload occurs;
see Chapter
ELECTRONIC SHUTDOWN and CONSTANT
DIP switch "STDA",
"STDB"
DIP switch "SOC1" Switchover between the regular and soft output characteristic,
DIP switch "WEN" Activates and deactivates the integrated web server, see Chap-
Defines the switch-on sequence of the outputs (function is only
available when a CNX8600 expansion module is being used);
Activate the web server for the MANUAL operating mode on
ter
The operating elements, with the exception of the button, are protected against unauthorized
operation by a transparent plastic cover. When required, this plastic cover can be sealed to
prevent the operating elements being actuated by unauthorized personnel. For sealing, the
sealing wire can be routed through an opening in the plastic cover and housing, as shown in
the diagram below.
Power supply system PSU8600
28Manual, 05.2017, A5E36758446-3-76
Page 29
Description, device design, dimension drawing
See also
2.5 Operator controls
Setting the output voltage (Page 55)
Setting the response threshold value of the output current (Page 56)
Switching an output on and off (Page 57)
Overload shutdown and carrying out a reset (Page 58)
MANUAL and REMOTE operating modes (Page 61)
Prioritization when the power fails (Page 64)
ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating modes (Page 66)
Setting the on delay (Page 68)
Setting the output characteristic (Page 71)
Activate the web server for the MANUAL operating mode on the module (Page 73)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
29
Page 30
Description, device design, dimension drawing
2.5.2
Expansion modules
No. Designation /
labeling
Function
①
potentiometer "U (V)"
(Page 55).
②
(Page 56).
③
reset (Page 58).
2.5 Operator controls
The SITOP CNX8600 expansion modules have a main operating area with potentiometers
① and ②) and an LED button ③.
(
The potentiometers are used to set the output voltage and response threshold of the output
current. The potentiometers can be individually adjusted for each output. The individual
outputs can be switched-on and switched-off using the buttons; further, each output can be
manually reset after an electronic shutdown.
Power supply system PSU8600
30Manual, 05.2017, A5E36758446-3-76
Voltage
Current
potentiometer "I (A)"
LED buttons
"ON/OFF/RST"
Sets the voltage of the relevant output; see Setting the output voltage
Sets the response threshold of the output current of the relevant output;
see Setting the response threshold value of the output current
Switches in and switches out the various outputs, or resets the particular outputs after an electronic shutdown; see Switching an output on
and off (Page 57) as well as
Overload shutdown and carrying out a
Page 31
Description, device design, dimension drawing
Protection and sealing
See also
2.5 Operator controls
The operating elements, with the exception of the buttons, are protected against
unauthorized operation by a transparent plastic cover. When required, this plastic cover can
be sealed to prevent the operating elements being actuated by unauthorized personnel. For
sealing, the sealing wire can be routed through an opening in the plastic cover and housing,
as shown in the diagram below.
Overload shutdown and carrying out a reset (Page 58)
Setting the output voltage and response threshold value of the output current (Page 55)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
31
Page 32
Description, device design, dimension drawing
2.6
Displays
Meaning of the LEDs
Signaling
LED is off.
LED is continuously on
x /y
LED flashes in the interval x s on and y s off
2.6.1
Basic devices
No. Labeling
Signal type
Signaling
①
OK
LED
Device status
②
MAN
LED
Mode
③
SF
LED
Group error
④
RUN
LED
RUN/STOP
⑤
P1/P2
LED
Receive/transmit, port 1 and port 2
⑥
ON/OFF/RST
LED buttons
Operating mode of the output
2.6 Displays
The operating state of the device and the operating state of the various outputs are
displayed using multi-color LEDs.
Symbols indicate the significance of each LED, which are listed in the following table.
Power supply system PSU8600
32Manual, 05.2017, A5E36758446-3-76
Page 33
Description, device design, dimension drawing
States of the individual LEDs
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation
Operation with rated load is permissible for approx. 10 min.
Operation is permissible for 5 s/min
Yellow
Power failure, buffer operation active
101 … 150 % (operation is permissible for 5 s/min)
(0.25/0.25)
MAN
Signaling
Green
MANUAL mode, i.e. setting directly at the device
the device do not necessarily correspond to the active reference parameters.
2.6 Displays
Table 2- 4 "OK" LED ①
Flashing green (1/1) Phase asymmetry or phase failure
Flashing green (0.25/0.25) System overload in normal operation:
Red
Detection from:
• approx. 50 % rated load for 6EP3437-8MB00-2CY0
• approx. 75 % rated load for 6EP3436-8MB00-2CY0
Total output power in the range 101 - 150 %
• ERROR OFF: Device has automatically shut down as a result of device over-
temperature, phase dissymmetry, system overload
• Internal device fault
Flashing red (0.25/0.25)
Flashing yellow (0.25/0.25)
Alternating, green/red
Table 2- 5 LED "
Off
Flashing green (1/1)
• Device ready for the automatic ERROR OFF shutdown to be reset – or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
Overload at the output: Output current 101…150 % of the response threshold
(up to 149 %: operation permissible for 5 s, 150 %: operation permissible for
For overload, the output current is limited to the response threshold value
•
mode)
• Output 1 prioritized for buffer mode
• System overload
• Overtemperature of the output (in pairs)
Flashing red (0.25/0.25)
After automatic shutdown due to overload, system overload or overtemperature,
Power supply system PSU8600
38Manual, 05.2017, A5E36758446-3-76
Page 39
Description, device design, dimension drawing
2.6.3
Buffer modules
No. Labeling
Signal type
Signaling
①
OK
LED
Device status
2.6 Displays
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
39
Page 40
Description, device design, dimension drawing
States of the individual LEDs
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation, module charged, complete buffer readiness
Flashing green (1/1)
Module is being charged, buffer readiness partially available.
Flashing green (0.25/0.25)
Module is being charged, buffer readiness not available
the power fails)
Yellow
Power failure, buffer mode active
(0.25/0.25)
2.6 Displays
Table 2- 11 LED "OK" ①
Red
• ERROR OFF: Module automatically shut down due to overtemperature basic
device, phase dissymmetry
• Fault in the device or communication error to the basic device
flashing red (1/1)
Flashing red (0.25/0.25)
Alternating, green/red
Module deactivated via ON/OFF contact or remote command (no buffering when
• Device ready for the automatic ERROR OFF shutdown to be reset – or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
• Charge is still available after power supply voltage OFF
• Device shut down due to firmware update of another system component
• Incorrect hardware configuration (REMOTE mode)
Firmware being updated
Power supply system PSU8600
40Manual, 05.2017, A5E36758446-3-76
Page 41
Description, device design, dimension drawing
2.7
Signaling contact/control contact
2.7.1
Basic devices
Contacts
Explanation
11-14 closed
.
2.7 Signaling contact/control contact
The signaling contact is a changeover contact (NC contact terminals "11" and "12", NO
contact terminals "11" and "14") and facilitates processing of information about the operating
state of the power supply system and the output.
11-12 open
11-12 closed (= quiescent state)
11-14 open (= quiescent state)
Device ready, the output is switched on or
shut down either manually or via control command
In the ELECTRONIC SHUTDOWN operating mode:
• Output switched off to due overload
Other possible causes:
• No output voltage (e.g. as there is no supply voltage)
• Basic unit and supplementary modules shut down due
to overtemperature
• Basic unit and supplementary modules shut down due
to phase dissymmetry or failure
• Basic unit has limited power output and expansion mod-
ule shut down due to system overload
• Output shut down due to overtemperature
• Communication error between the basic unit and sup-
plementary module
• Expansion module failure
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
41
Page 42
Description, device design, dimension drawing
2.7.2
Buffer modules
Note
Contacts only available for SITOP BUF8600 buffer modules with double-layer capacitors
The control contact ON and the signaling contact READY and OK are only available for
buffer
and 10
Control contact
Explanation
jumper)
fails, the system is not buffered.
2.7 Signaling contact/control contact
modules SITOP BUF8600 with double layer capacitors (SITOP BUF8600 4 s / 40 A
s / 40 A).
Buffer mode of the SITOP BUF8600 buffer module with double-layer capacitors can be
prevented using control contact ON (terminals "X1" and "X2"), if a scheduled shutdown of
the power supply is planned (e.g. for maintenance, period of no operation, end of work/shift).
This avoids unnecessarily discharging the buffer module.
Deactivation via the control contact is effective for all of the SITOP BUF8600 buffer modules
in the system.
X1-X2 closed
(delivery state: via wire
X1-X2 open All of the buffer modules in the system deactivated; when the power
Buffer active, system is buffered when the power fails.
The signaling contact "Sufficient buffer readiness" "READY" is in the form of a relay contact
(NO contact, terminals "13" and "14"), and signals that the buffer module is charged to x %
(factory setting: 85 %) and is therefore ready for buffering. The threshold value can be freely
parameterized via Industrial Ethernet/PROFINET interface.
For two BUF8600 buffer modules with double-layer capacitors in the system, the threshold
that is set refers to the sum of the charged energy storage devices in both buffer modules.
The signal "Sufficient buffer readiness" refers exclusively to the SITOP BUF8600 buffer
modules with double-layer capacitors in the system.
Power supply system PSU8600
42Manual, 05.2017, A5E36758446-3-76
Page 43
Description, device design, dimension drawing
Signaling contact
Explanation
(quiescent state)
module fault
Signaling contact
Explanation
(quiescent state)
23-24 closed
Normal operation, buffer module is charged (if required).
2.7 Signaling contact/control contact
SITOP BUF8600 buffer modules with electrolytic capacitors in the system are not taken into
account.
13-14 open
13-14 closed Charge state of the buffer module or two buffer modules ≥ x %
Charge state of the buffer module or two buffer modules < x % - or
The signaling contact "Buffer mode" OK is in the form of a relay contact (NO contact,
terminals "23" and "24") and signals that the system is in buffer mode. This means that
critical processes can be immediately brought into a safe state, avoiding loss of data and
additional damage.
For two SITOP BUF8600 buffer modules with double-layer capacitors in the system, both
modules simultaneously signal buffer mode using the signaling contact. As a consequence, it
is sufficient to wire one of the two contacts. The signal "Buffer mode" refers exclusively to the
SITOP BUF8600 buffer modules with double-layer capacitors in the system.
SITOP BUF8600 buffer modules with electrolytic capacitors in the system are not taken into
account.
23-24 open
Power failure, system is buffered by the buffer module.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
43
Page 44
Description, device design, dimension drawing
2.8
Block diagrams
Basic SITOP PSU8600 device
Expansion modules SITOP CNX8600
2.8 Block diagrams
Power supply system PSU8600
44Manual, 05.2017, A5E36758446-3-76
Page 45
Description, device design, dimension drawing
SITOP BUF8600 100 ms/40 A and SITOP BUF8600 300 ms/40 A buffer modules
SITOP BUF8600 4 s/40 A and SITOP BUF8600 10 s/40 A buffer modules
2.8 Block diagrams
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
45
Page 46
Description, device design, dimension drawing
2.9
Dimensions and weights
SITOP PSU8600 basic devices
2.9 Dimensions and weights
Figure 2-2 Dimension drawing 6EP3436-8SB00-2AY0 front and left views
Figure 2-3 Dimension drawing 6EP3436-8SB00-2AY0 view from below
Power supply system PSU8600
46Manual, 05.2017, A5E36758446-3-76
Page 47
Description, device design, dimension drawing
2.9 Dimensions and weights
Figure 2-4 Dimension drawing 6EP3437-8SB00-2AY0 front and left views
Figure 2-5 Dimension drawing 6EP3437-8SB00-2AY0 view from below
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
47
Page 48
Description, device design, dimension drawing
Expansion modules SITOP CNX8600
2.9 Dimensions and weights
The dimensions are identical for both versions.
Figure 2-6 Dimension drawing for 6EP4436-8XB00-0CY0 and 6EP4437-8XB00-0CY0
Power supply system PSU8600
48Manual, 05.2017, A5E36758446-3-76
Page 49
Description, device design, dimension drawing
Buffer modules SITOP BUF8600
2.9 Dimensions and weights
Figure 2-7 Dimension drawing 6EP4297-8HB00-0XY0
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
49
Page 50
Description, device design, dimension drawing
2.9 Dimensions and weights
Figure 2-8 Dimension drawing 6EP4297-8HB10-0XY0
Power supply system PSU8600
50Manual, 05.2017, A5E36758446-3-76
Page 51
Description, device design, dimension drawing
2.9 Dimensions and weights
Figure 2-9 Dimension drawing 6EP4293-8HB00-0XY0
Figure 2-10 Dimension drawing 6EP4295-8HB00-0XY0
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
51
Page 52
Description, device design, dimension drawing
Dimensions and weights
SITOP PSU8600 basic devices
6EP3436-8SS00-2AY0
6EP3437-8SB00-2AY0
(W × H × D) in mm
Weight
Approx. 1.78 kg
2.63 kg
Expansion modules SITOP CNX8600
6EP4436-8XB00-0CY0
4 x 5 A
6EP4437-8XB00-0CY0
4 x 10 A
(W × H × D) in mm
Weight
Approx. 1.15 kg
Approx. 1.15 kg
Buffer modules SITOP BUF8600
6EP42978HB00-0XY0
100 ms at 40 A
6EP42978HB10-0XY0
300 ms at 40 A
6EP42938HB00-0XY0
4 s at 40 A
6EP42958HB00-0XY0
10 s at 40 A
(W × H × D) in mm
Weight
Approx. 1.33 kg
Approx. 2.26 kg
Approx. 1.25 kg
Approx. 1.95 kg
2.9 Dimensions and weights
Dimensions
Dimensions
Dimensions
80 × 125 × 150 125 x 125 x 150
60 × 125 × 150 60 × 125 × 150
60 × 125 × 150 125 × 125 × 150 60 x 125 x 150 125 x 125 x 150
Power supply system PSU8600
52Manual, 05.2017, A5E36758446-3-76
Page 53
3
Operating the basic devices
Note
Settings made at the basic device using the voltage potentiometer
③
REMOTE operating modes
REMOTE operating mode.
The output can be switched
Various settings can be made using the following operator controls - button ①,
potentiometers
at the front.
② and ③, and selector switches ④ to ⑪. All operator controls are located
and DIP switches ⑤ to ⑪ are only made in the MANUAL mode (see MANUAL and
(Page 61)). These operator controls are deactivated in the
-on/switched-off and reset in any mode using button ①.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
②, current potentiometer
53
Page 54
Operator control at the device
Operating the expansion modules
Note
Settings made at the expansion module using voltage potentiometer
potentiometer
operating modes
operating mode.
The outputs can be switched
Various settings can be made using the following operator controls - button ① and
potentiometers
② and ③. All operator controls are located at the front.
② and current
③ are only made in the MANUAL mode (see MANUAL and REMOTE
(Page 61)). These operator controls are deactivated in the REMOTE
-on/switched-off and reset in any mode using button ①.
Power supply system PSU8600
54Manual, 05.2017, A5E36758446-3-76
Page 55
Operator control at the device
3.1
Setting the output voltage and response threshold value of the
output current
Note
When the REMOTE operating mode is activated (see
modes
and response threshold value of the output current have no effect.
②
Voltage potentiometer for the output
③
Current potentiometer for the output
3.1.1
Setting the output voltage
3.1 Setting the output voltage and response threshold value of the output current
The potentiometer of the output is used to set the output voltage and the response threshold
value of the output current.
MANUAL and REMOTE operating
(Page 61)) changes made to the settings of the potentiometer for the output voltage
1. Using the appropriate screwdriver, rotate the voltage potentiometer for the output so that
the notch in the inner ring points to the required value (the following diagram shows a
setting for 15 V).
Values between 4 and 28 Volt can be set.
When supplied, the output voltage is set to 24 Volt.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
55
Page 56
Operator control at the device
3.1.2
Setting the response threshold value of the output current
3.1 Setting the output voltage and response threshold value of the output current
1. Using the appropriate screwdriver, rotate the current potentiometer for the output so that
the notch in the inner ring points to the required value (the following diagram shows a
setting for 2 A).
Depending on the type, at the basic devices and expansion modules, values of 2 to 20 A or
from 4 to 40 A can be set.
For the expansion modules, depending on the type, values from 0.5 up to 5 A – or from 0.5
up to 10 A can be set.
When delivered, the output current is set to the maximum possible value.
Power supply system PSU8600
56Manual, 05.2017, A5E36758446-3-76
Page 57
Operator control at the device
3.2
Switching an output on and off
①
Button (illuminated with an LED)
Shutting down an output
Note
An output that has been manually switched
manually switched
switch
nor using a
control command in the REMOTE operating mode.
The output that has been manually switched
saved when switching
device powers up.
Switch on output
3.2 Switching an output on and off
The output can be switched-on and switched-off using the button.
The output is manually shutdown when the device is supplied.
When the output is switched-on, the LED in the button is lit green.
1. You can switch off the output by pressing the button.
LED is lit yellow (output manually shutdown).
-on the output that has been manually switched-off using remote RESET –
-off (LED in the button is lit yellow) can only be
-on again by manually pressing the button again. It is neither possible to
-off (LED in the button is lit yellow) also remains
-off the device, and is manually switched-off the next time that the
The LED in the button is lit yellow when the output is manually shutdown.
1. You can switch off the output by pressing the button.
The LED is lit green (output is switched on).
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
57
Page 58
Operator control at the device
3.3
Overload shutdown and carrying out a reset
Shutdown characteristic
3.3 Overload shutdown and carrying out a reset
For the device output, in the ELECTRONIC SHUTDOWN mode, overload is permitted for a
defined time. The output is electronically shut down after the limit value has been exceeded
(see the following diagram).
An output current up to the value set using the current potentiometer is continuously
permissible (LED "ON/OFF/RST" of the output is lit green).
In the range 101...149 % of the setting value of the current potentiometer, an overload
current is permissible for 5 seconds (LED "ON/OFF/RST" of the output flashes green), then
the output is electronically shut down (LED "ON/OFF/RST" of the output is lit red).
In the range > 149 % of the setting value of the current potentiometer, the current is limited
to 150 %, after approx. 200 ms the output is electronically shut down (LED "ON/OFF/RST" of
the output is lit red).
Using a reset, the output that has been automatically shut down can be switched-on again
after a wait time of 5 seconds (LED "ON/OFF/RST" of the output flashes red).
Power supply system PSU8600
58Manual, 05.2017, A5E36758446-3-76
Page 59
Operator control at the device
Carrying out a reset with the button at the device
①
Button (illuminated with an LED)
LED in the button
Meaning/handling
overload; wait time until a reset is possible:
5 seconds.
Flashes red
Output ready for a reset; press the button to switch-on the output again.
Lit green
The reset was carried out, the output was switched-on again.
Procedure
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically shut down according to the shutdown characteristics described previously.
Before
3.3 Overload shutdown and carrying out a reset
The output can be reset using the button. This resets the electronic shutdown of the output,
caused by an overload condition.
The initial situation is an electronic shutdown as a result of an overload condition. This is
signaled using LED "ON/OFF/RST" in button
Lit red Electronic shutdown as a result of an
①:
1. After an electronic shutdown (LED "ON/OFF/RST" of the output is lit red), allow a wait
time of 5 seconds to elapse.
2. Press the button of the output if this is ready for a reset (LED "ON/OFF/RST" of the
output flashes red).
Electronic shutdown was reset, and the output has been switched-on again (LED
"ON/OFF/RST" of the output is lit green).
carrying out a reset, remove the cause of the overload to prevent a new shutdown.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
59
Page 60
Operator control at the device
Remote reset via terminal RST
Procedure
Note
If a switch
together with a CNX8600 expansion module) when switching on, this is not taken into
account for a reset initiated using a remote reset signal.
Note
The rising edge of the reset signal is evaluated;
voltage level must first drop down to below 13
3.3 Overload shutdown and carrying out a reset
The reset can be alternatively carried out using a remote reset signal. The non-isolated 24 V
input (referred to terminal "0V" of the device) at terminal "RST" can be used. A reset is
carried out for an input level of > 15 V for at least 100 ms.
Connect a voltage of > 15 V for at least 100 ms to terminal "RST".
The reset is carried out.
-on delay of the output is defined (this function is only available when operated
this means for an additional reset signal, the
V.
Power supply system PSU8600
60Manual, 05.2017, A5E36758446-3-76
Page 61
Operator control at the device
3.4
MANUAL and REMOTE operating modes
Note
In the REMOTE mode, in some instances, extended special functions can be selected for all
outputs via the
operating mode You can find more information on this at
(Page
Note
In order to ensure that in the MANUAL and REMOTE operating modes, the device operates
with the required
should only be switched over when the power supply system is in a no
3.4 MANUAL and REMOTE operating modes
When the device powers up in the MANUAL operating mode, the settings, which were made
directly at the device with the potentiometers and selector switches, apply. For an
unchanged system configuration, the output is activated with the last operating status before
shutdown.
When the device powers up in the REMOTE operating mode, the configuration parameter
set, assigned to the device by the associated control, applies. For an unchanged system
configuration, the output is activated with the parameters and operating states saved in the
configuration.
Was the last operating state of an output before shutdown
● "Manual shutdown" (LED "ON/OFF/RST" of the output is lit yellow),
● "Automatic shutdown due to overload" (LED "ON/OFF/RST" of the output is lit red)
or
● "Ready for reset" (LED "ON/OFF/RST" of the output flashes red),
then these operating states are assumed again when the system starts.
In the REMOTE operating mode, the operating state and parameters of the output can be
changed in operation, controlled by the program.
configuration. These special functions are not available in the MANUAL
Engineering and remote access
121).
device settings and/or reference parameter sets, the operating modes
-voltage state.
The switchover is made at the selector switch (see operator controls) with the
designation "REN"
④.
When delivered, DIP switch "REN" is in position "OFF" (operating mode MANUAL).
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
61
Page 62
Operator control at the device
Activating the MANUAL operating mode
Note
When switching
maintains its particular state. Initially, the reference parameters for remote operation remain
active. The voltage and current values can be changed by actuating the potentiometers at
the
DIP switches only become active after they have been actuated.
Activating the REMOTE operating mode
3.4 MANUAL and REMOTE operating modes
With the power supply system shut down, bring DIP switch "REN" into position "OFF" (left),
to activate the MANUAL operating mode.
over from the REMOTE into the MANUAL mode in operation, the output
device, or as the case may be, once the remote setpoints have been fallen below. The
With the power supply system shut down, bring DIP switch "REN" into position "ON" (right),
to activate the REMOTE operating mode.
Power supply system PSU8600
62Manual, 05.2017, A5E36758446-3-76
Page 63
Operator control at the device
NOTICE
Suddenly changing the operating state of the device.
3.4 MANUAL and REMOTE operating modes
When switching over from the MANUAL into the REMOTE mode in operation, the output
initially maintains its particular state. The settings of the potentiometers and DIP switches at
the device remain active until the new reference parameters can be loaded into the device
from an associated control system. This can happen undesirably as a result of a lost
connection or when establishing a connection to the control for the first time – and can
cause a sudden change of the device operating state (e.g. another output voltage)!
Only switch over the operating mode when the power supply system is shut down, or
before switching over in operation, ensure that the remote configuration corresponds to the
actual device settings.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
63
Page 64
Operator control at the device
3.5
Prioritization when the power fails
Note
Function is only available when operated with a CNX8600 expansion module
Note
The prioritization when the power fails may only be switched over when the power supply
system is in a no
3.5 Prioritization when the power fails
When the power fails, output 1 of the basic unit can be prioritized so that it is still supplied.
Prioritizing output 1 means that the longest possible buffer time is ensured at this output. If
output 1 is prioritized, all of the remaining outputs are shut down at approximately half of the
nominally available buffer time for the remaining duration of the power failure. LEDs
"ON/OFF/RST" of the outputs that have been shut down are lit red. When the line supply
returns, the outputs that have been shut down are automatically switched-on again.
For the basic device type, the nominal buffer time is typically 15 ms; the buffer time can be
extended using additional buffer modules.
-voltage condition.
The switchover is made at selector switch (see operating controls) with the designation
"PRY 1"
⑤.
When delivered, DIP switch "PRY 1" is in position "OFF" (prioritization deactivated).
Power supply system PSU8600
64Manual, 05.2017, A5E36758446-3-76
Page 65
Operator control at the device
All outputs have the same priority during buffering
Prioritizing output 1 during buffering
Note
Outputs 2...n, which are shut down when the power fails as output 1 has priority, are
automatically switched
3.5 Prioritization when the power fails
With the power supply system shut down, bring DIP switch "PRY 1" into position "OFF" (left),
so that all outputs have the same priority when buffering is required.
With the power supply system shut down, bring DIP switch "PRY 1" into position ON (right),
so that output 1 of the basic unit has priority when buffering is required.
-on again when the line supply returns.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
65
Page 66
Operator control at the device
3.6
ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating
modes
Note
How the system responds to overload may only be switched over when th
system is in a no
3.6 ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating modes
Two overload responses can be defined for output 1:
● In the ELECTRONIC SHUTDOWN operating mode, overload is permitted for a defined
time. The output is electronically shut down after the limit value has been exceeded (see
Overload shutdown and carrying out a reset (Page 58)).
● In the CONSTANT CURRENT operating mode, an overload current is continually
permissible (U/I curve) according to a defined characteristic. The overload current is
limited to a maximum of 150 % of the setting value of the current potentiometer for a
duration of 5 seconds (LED "ON/OFF/RST" of output 1 quickly flashes green); the current
is then limited to 100 % of the setting value (LED "ON/OFF/RST" of the output slowly
flashes green) as long as there is an overload condition.
In addition, in this operating mode, if a CNX8600 expansion module is not being used, a
brief Power Boost (300 % for 25 ms) is provided so that the downstream circuit breaker
can trip when an overload condition occurs.
e power supply
-voltage state.
The switchover is made at the selector switch (see operator controls) with the designation
⑥.
"UI-1"
When delivered, DIP switch "UI-1" is in position "OFF" (mode ELECTRONIC SHUTDOWN).
Power supply system PSU8600
66Manual, 05.2017, A5E36758446-3-76
Page 67
Operator control at the device
Electronic shutdown
Constant current
3.6 ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating modes
With the power supply system shut down, bring DIP switch "UI-1" into position "OFF" (left), to
activate the ELECTRONIC SHUTDOWN mode.
With the power supply system shut down, bring DIP switch "UI-1" into position "ON" (right),
to activate the CONSTANT CURRENT mode.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
67
Page 68
Operator control at the device
3.7
Setting the on delay
Note
The on delay time may only be switched over when the power supply system is in a no
vo
Note
The switch
and is then applicable for all outputs of the power supply system.
When the switch
on in the following sequence
-
3.7 Setting the on delay
In order to reduce the load on the overall SITOP PSU8600 power supply system as a result
of simultaneous switch-on current peaks of the loads at the output of the basic device and at
the outputs of the expansion modules, a switch on delay between the outputs can be
selected when switching on.
When the on delay is activated, the outputs are sequentially switched-on with a 25 ms or
100 ms delay time between the outputs, or "load optimized". For a load-optimized on delay,
after 100 ms, for the previous output n it is additionally checked as to whether the output
current lies below the selected response threshold value. Output n+1 is switched-on as soon
as this is the case. Outputs that have been shut down are not taken into account and are
skipped.
-
ltage state.
-on delay is only possible when operating with an CNX8600 expansion module -
-on delay is activated, the outputs are switched-
output of the basic device → outputs of expansion modules 1 → 2 → 3 → 4 → … → n.
The switchover is realized at the selector switch (see operator controls) with the designations
"STDA"
When delivered, DIP switches "STDA" and "STDB" are in the "OFF" position (no switch on
delay).
⑦ and "STDB" ⑧.
Power supply system PSU8600
68Manual, 05.2017, A5E36758446-3-76
Page 69
Operator control at the device
No on delay
STDA
STDB
25 ms on delay
STDA
STDB
3.7 Setting the on delay
With the power supply system shut down, bring both DIP switches "STDA" and "STDB" into
position "OFF" (left), to deactivate on delay.
With the power supply system shut down, bring DIP switch "STDA" into position "ON" (right)
and "STDB" into position "OFF" (left) in order to set the on delay to 25 ms.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
69
Page 70
Operator control at the device
100 ms on delay
STDA
STDB
Load-optimized on delay
STDA
STDB
3.7 Setting the on delay
With the power supply system shut down, bring DIP switch "STDA" into position "OFF" (left)
and "STDB" into position "ON" (right) in order to set the on delay to 100 ms.
With the power supply system shut down, bring both DIP switches "STDA" and "STDB" into
position "ON" (right) to activate load-optimized on delay.
Power supply system PSU8600
70Manual, 05.2017, A5E36758446-3-76
Page 71
Operator control at the device
3.8
Setting the output characteristic
Selecting the standard output characteristic
Selecting the soft output characteristic
3.8 Setting the output characteristic
For the standard output characteristic of the basic SITOP PSU8600 device, the output
voltage is regulated to obtain a constant value independent of the output current. If the "soft"
output characteristic is selected, then the output voltage slightly decreases as the output
current increases. This output response can be used so that when two basic devices are
connected in parallel to increase the power rating, the basic devices are more uniformly
utilized.
The switchover is made at the "SOC1" DIP switch
When delivered, the "SOC1" DIP switch is in the "OFF" position (standard output
characteristic).
⑨.
Bring DIP switch "SOC1" into the "OFF" position (left) to select the standard output
characteristic for the output.
Bring DIP switch "SOC1" into the "ON" position (right) to select the "soft" output
characteristic for the output.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
71
Page 72
Operator control at the device
Note
When the "soft" output characteristic is selected, at the full, rated output current, the highest
output voltage can no longer be reached. With increasing output current, in the range from
no
approximately 1.2
3.8 Setting the output characteristic
-load operation to rated output current, the output voltage linearly decreases by a value of
V.
Power supply system PSU8600
72Manual, 05.2017, A5E36758446-3-76
Page 73
Operator control at the device
3.9
Activate the web server for the MANUAL operating mode on the
module
Deactivating the web server
Activating the web server
3.9 Activate the web server for the MANUAL operating mode on the module
The basic SITOP PSU8600 device has an integrated web server. This facilitates remote
monitoring and diagnostics, for example to interrogate actual currents and
messages/signals. Further, the actual module configuration can be viewed, if necessary
changed and externally saved to a file and archived. In addition, it is possible to read the
"MANUAL configuration", and to transfer this into the "Remote configuration".
The switchover is made at the DIP switch (see operator controls), designated "WEN"
When delivered, DIP switch "WEN" is in the "OFF" position (web server deactivated).
⑪.
Bring DIP switch "WEN" into the "OFF" position (left) to deactivate the web server integrated
in the module.
Bring DIP switch "WEN" into the "ON" position (right) to activate the web server integrated in
the module.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
73
Page 74
Operator control at the device
Note
To activate the web server in the REMOTE operating mode, it must be enabled via
SIMATIC
(Page
Note
No write access when the connection is active
If the SITOP PSU8600 has an active connection to a control system (relation application),
then the parameters can only be rea
and save and delete the alarm list. If there is no active connection, then parameters can also
be write accessed via the web server.
Note
After the system is switched on for the first time with
system generates an SSL certificate to access the web server.
Wait for approximately two minutes until the SSL certificate has been generated and access
to the web server has been activated.
3.9 Activate the web server for the MANUAL operating mode on the module
STEP 7 (Page 149), SIMATIC STEP 7 in the TIA Portal (Page 122), OPC UA
230) or via the web server (Page 199) in the MANUAL.
d-accessed. It is still possible to update the firmware -
activated web server, the power supply
You can find additional information about the integrated web server in ChapterWeb server
(Page 199).
Power supply system PSU8600
74Manual, 05.2017, A5E36758446-3-76
Page 75
Operator control at the device
3.10
Monitoring functions
3.10.1
Overtemperature monitoring functions
Identifying a shutdown due to an inadmissible temperature
Basic unit
Outputs
3.10 Monitoring functions
SITOP PSU8600 basic units and SITOP CNX8600 expansion modules have integrated
overtemperature monitoring functions. The outputs are shut down if the internal temperature
is inadmissibly high.
Take the following steps after a shutdown as a result of an inadmissibly high internal
temperature:
1. Check the mounting clearances of the devices, see Standard mounting position
(Page 99) and Other mounting positions (Page 101).
Excessively low mounting clearances cause overheating.
2. Measure whether the ambient temperature is permissible, see Environmental conditions
(Page 303).
If an inadmissibly high temperature is detected inside the basic device, the output of the
basic device and the expansion modules being used are switched off.
A shutdown as a result of an inadmissibly high temperature inside the basic units is signaled
by:
● Red LED "OK"
① at the basic unit and at the supplementary modules
● LEDs "ON/OFF/RST"
● Signaling contact at the basic unit
If an inadmissibly high temperature is detected at an output, then the outputs at the
expansion modules are shut down in pairs (1 and 2 or 3 and 4). The remaining outputs
remain switched on.
② go dark
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
75
Page 76
Operator control at the device
①
LED "OK"
②
LED "ON/OFF/RST"
Reset of a shutdown due to an inadmissible temperature
Basic unit
Note
The time that it takes for the component involved to cool down depends on the ambient
temperature.
3.10 Monitoring functions
A shutdown as a result of an inadmissibly high temperature at an output is signaled by:
● Green LED "OK"
● Red LEDs "ON/OFF/RST"
expansion module
● Signaling contact at the basic unit
① at the basic device or at the expansion module
② of the output at the basic device or the output pair at the
1. Allow the components involved to cool down.
After the basic unit has cooled down, LED "OK"
2. Switch-off the power supply for the SITOP PSU8600 for at least 10 seconds.
3. Switch on the supply voltage again.
The complete system, including the state of the individual outputs, is brought into the
operating state before the temperature shutdown.
① at the basic unit flashes red.
Power supply system PSU8600
76Manual, 05.2017, A5E36758446-3-76
Page 77
Operator control at the device
Output
Note
The time that it takes for the output pair involved to cool down depends on the ambient
temperature.
3.10.2
Phase dissymmetry monitoring
Identifying a shutdown due to phase dissymmetry
Note
The reason for an unsymmetrical supply can be line supply dissymmetry
complete phase failure. This state is identified and signaled from an output power of
approximately
device.
When a phase fails, the power supply system can be continually operated up to a maximum
output current of 10
3.10 Monitoring functions
1. Allow the output pair involved to cool down.
After cooling down, LEDs "ON/OFF/RST"
2. Press the buttons of the outputs involved.
The temperature shutdown was reset, and the output has been switched-on again.
The basic unit has an integrated phase dissymmetry monitoring function. This prevents an
inadmissibly high load on the components in the input circuit of the basic unit as a result of
dissymmetry of the supply voltage.
If the power supply is operated with an unsymmetrical supply, then this is signaled by a
green flashing LED "OK"
approx. 10 min. for an unsymmetrical supply is exceeded, all of the outputs of the basic unit
and the expansion modules being used are switched off.
240 W for the 20 A basic device - or approximately 480 W for the 40 A basic
① at the basic device. If, at rated load, the permissible duration of
② of the output pair, flash red.
– as well as a
A or 20 A without any restrictions.
The following signals indicate a shutdown due to phase asymmetry:
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
77
Page 78
Operator control at the device
①
LED "OK"
②
LED "ON/OFF/RST"
Reset of a shutdown due to phase dissymmetry
3.10 Monitoring functions
A shutdown due to phase dissymmetry is signaled by:
● Red LED "OK"
● LEDs "ON/OFF/RST"
● Signaling contact at the basic unit
① at the basic unit and at the supplementary modules
② of all outputs go dark
1. Switch off the supply voltage of the SITOP PSU8600 for at least 10 seconds, and remove
the cause of the phase dissymmetry.
2. Switch on the supply voltage again.
The complete system, including the state of the individual outputs, is brought into the
operating state before the phase dissymmetry shutdown.
Power supply system PSU8600
78Manual, 05.2017, A5E36758446-3-76
Page 79
Operator control at the device
3.10.3
System overload monitoring
Note
A shutdown as a result of a system overload can only occur when using expansion modules.
When operating the basic device without expansion modules, the dynamic overload
capability of the system cannot be exceeded as a result of the coordinated shutdown
cha
When expanding the system using expansion modules (additional outputs), ensure that the
sum of the set response threshold values of the output currents does not exceed the total
power rating (current rating) of the system. Alternatively, by suitably configuring the load duty
cycle of the individual outputs, you can prevent the total power from being exceeded.
Identifying a shutdown due to system overload
3.10 Monitoring functions
In order to permit brief, higher switch-on currents of the loads to be supplied, the system has
a dynamic overload capability of 150 % of the rated power for a permissible duration of
5 s/min.
If the system is briefly operated in the range of the dynamic overload capability
(101 …150 % of the rated power), LED "OK"
racteristics of the output at the basic device.
When exceeding the permissible duration of the dynamic overload capability of 5 s/min, the
power of the output of the basic device is automatically limited for a duration of 60 s; this
means that in the case of an overload, the output current is limited to the maximum rated
output current.
① at the basic unit flashes green.
The outputs of the expansion modules are simultaneously shutdown.
This operating state is signaled by:
● Green (in buffer operation, yellow) flashing LED "OK"
● Red LED "OK"
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
① of the expansion modules
① at the basic unit
79
Page 80
Operator control at the device
①
LED "OK"
②
LED "ON/OFF/RST"
Reset of a shutdown due to system overload
Procedure
3.10 Monitoring functions
● Red LEDs "ON/OFF/RST" ② of the outputs of the expansion modules
● The signaling contact at the basic unit
After 60 s, the basic unit automatically returns to the normal operating state, the expansion
modules return to operational readiness. This state is signaled by:
● Green (in buffer operation, yellow) LED "OK"
● Green (in buffer operation, yellow) LED "OK"
● Red flashing LEDs "ON/OFF/RST"
1. Press the LED buttons of the outputs at the expansion modules.
The LEDs in the buttons light up green. The outputs are switched-on again.
2. Alternatively, using a remote reset at terminal "RST", all outputs that have been shut
down can be simultaneously switched-on again.
① at the basic unit
① of the expansion modules
② of the outputs of the expansion modules
Power supply system PSU8600
80Manual, 05.2017, A5E36758446-3-76
Page 81
Operator control at the device
3.11
Activating and deactivating buffer operation
Activating buffer operation
Deactivating buffer operation
Note
Response for two buffer components in the system
If the system has two buffer modules, opening the connection between terminals "X1" and
"X2" of one
also applies to buffer modules with electrolytic capacitors, without
Note
The external circuit must meet the requirements relating to SELV circuits according to
EN
3.11 Activating and deactivating buffer operation
Using control contact ON (terminals "X1" and "X2") at SITOP BUF8600 buffer modules with
double-layer capacitors, buffer operation can be activated, deactivated or exited when the
power fails. Preventing or exiting buffer operation is especially interesting for non-operational
periods, to prevent buffer components from being unnecessarily discharged. This then
facilitates the fastest possible buffer readiness after switching on again.
Buffer operation is only possible if terminals "X1" and "X2" are connected at the buffer
module. When delivered, this is implemented using a wire jumper. As a consequence, buffer
operation can be enabled, prevented or exited using a floating contact (e.g. a contact in the
plant or system). Instead of the wire jumper, the contact is closed, and this must have
< 10 Ohm in the closed state. The buffer components are charged irrespective of whether
contacts "X1" and "X2" are connected - or not.
1. Close the connection between terminals "X1" and "X2".
When the power fails, the power supply system is automatically buffered using the buffer
components.
1. Open the connection between terminals "X1" and "X2".
When the power fails, the power supply system is not buffered using the buffer
components.
Buffer operation is immediately exited if the connection between terminals "X1" and "X2"
is opened during buffer operation.
buffer module means that also the second buffer module is deactivated. This
control contact!
60950-1.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
81
Page 82
Operator control at the device
3.12
Restore factory settings
Note
The firmware cannot be reset.
Note
If you keep the button for output 1 pressed
canceled (LED "MAN" goes dark).
Note
If, within 5
reset procedure is canceled (LED "MAN" goes dark).
Note
The reset procedure is canceled in the following cases:
•
not
•
All LEDs return to their original state.
3.12 Restore factory settings
A reset to the factory settings deletes all hardware and software configurations stored in the
SITOP PSU8600 and restores the factory settings.
This affects, for example:
● IP address
● Device name
● Parameter values for the SITOP PSU8600 and assigned supplementary modules.
Proceed as follows to reset the SITOP PSU8600 factory settings:
1. While the SITOP PSU8600 is operational, at the basic device, press the button for output
1 Keep the button pressed for approximately 5 s until the "MAN" LED at the device
flashes green.
for another 5 s, then the reset procedure is
2. Release the button for output 1 to continue the reset procedure.
LED "MAN" flashes green for another 5 s and then goes dark.
s while LED "MAN" flashes green, you press the button for output 1, then the
3. If the LED "MAN" has gone dark, within 5 s again press the button for output 1 at the
basic device. Keep the button pressed for approximately 5 s until all of the LEDs at all of
the modules have gone dark.
All data (parameter settings, fault messages) in the basic device and the expansion
modules are reset. Settings for the potentiometers and DIP switches are kept.
The power supply system is run down.
If you have
pressed the button for output 1 within 5 s after LED "MAN" goes dark.
If you release the button for output 1 after less than 5 s.
4. Release the button for output 1 to restart the SITOP PSU8600.
Power supply system PSU8600
82Manual, 05.2017, A5E36758446-3-76
The SITOP PSU8600 automatically starts with the factory settings.
Page 83
4
WARNING
Use in hazardous zones
NOTICE
Basic device and expansion modules should be installed in a housing or a control cabinet.
4.1
Connecting plug
When the SITOP PSU8600 power supply system is installed in a hazardous zone (Ex II 3G
Ex nA nC IIC T4 Gc, Ex II 3G Ex nA IIC T4 Gc, Ex II 3G Ex nA IIC T5 Gc), then it must be
accommodated in a distribution box with IP54 degree of protection or higher.
The SITOP PSU8600 power supply system is a built-in device. It must be installed in a
housing or control cabinet, to which only qualified personnel have access.
The basic device and the system components are connected with one another using the
connecting plug
is described in Section Rail mounting (Page 84).
Before you remove the basic device or supplementary modules, you must first release the
corresponding connecting plugs. The procedure to release a connecting plug is described in
Section Removal (Page 87).
① at the upper side of the devices. The procedure to establish a connection
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
83
Page 84
Installation and maintenance
4.2
Rail mounting
Basic unit
WARNING
Risk of electric shock
4.2 Rail mounting
Before starting installation work of any kind, the main switch of the system must be opened
and measures taken to prevent it from being reclosed. If this instruction is not observed,
touching live parts can result in death or serious injury.
When installing in a control cabinet, basic devices can be snapped onto standard mounting
rails (see Chapter Mechanical system (Page 295)).
1. Position the device with the mounting rail guide at the upper edge of the standard
mounting rail and press down to lock it into place.
2. If it is difficult to snap it into place, simultaneously press the slider using a screwdriver.
Power supply system PSU8600
84Manual, 05.2017, A5E36758446-3-76
Page 85
Installation and maintenance
Supplementary modules
WARNING
Risk of electric shock
as close as possible to the
4.2 Rail mounting
Before starting installation work of any kind, the main switch of the system must be opened
and measures taken to prevent it from being reclosed. If this instruction is not observed,
touching live parts can result in death or serious injury.
The supplementary modules can be mounted in a control cabinet on standard mounting rails
(see Chapter Mechanical system (Page 295)). The electrical connection to the adjacent
basic unit or module is established using the connecting plug, integrated at the upper side of
the module housing.
1. Position the supplementary module with the mounting rail guide at the upper edge of the
standard mounting rail
2. to lock it into place.
3. If it is difficult to snap it into place, simultaneously press the slider as described for
mounting the basic device.
basic device, and press down
4. Move the supplementary module so that it is in physical contact with the basic unit.
5. Remove the plastic cover of the connection socket at the basic unit.
6. Connect the supplementary module to the basic unit using the connecting plug:
– Insert the connecting plug into the socket provided at the basic unit.
– Ensure that latch
① snaps into place.
All additional supplementary modules can be connected in the same way to the
supplementary module to the left.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
85
Page 86
Installation and maintenance
4.3
Permissible hardware configurations
Expansion modules, maximum number and compatibility
Note
Also when using four expansion
960
Expansion modules, PSU8600 power supply system
Type
Article No.
SITOP CNX8600 4x 5 A
6EP4436-8XB00-0CY0
SITOP CNX8600 4x 10 A
6EP4437-8XB00-0CY0
Buffer modules, maximum number and compatibility
Note
It is possible to use different buffer modules in one system. This means that a buffer time of
400
Buffer modules, PSU8600 power supply system
Type
Article No.
SITOP BUF8600 100 ms/40 A
6EP4297-8HB00-0XY0
SITOP BUF8600 300 ms/40 A
6EP4297-8HB10-0XY0
SITOP BUF8600 10 s/40 A
6EP4295-8HB00-0XY0
4.3 Permissible hardware configurations
The various supplementary modules can be arranged in the system as required.
A maximum of four expansion modules can be used with a basic device.
modules, the maximum power of the system is 480 W or
W - and the maximum output current is 20 A or 40 A.
A maximum of two buffer modules can be used with a basic device.
ms (100 ms + 300 ms) can be realized, for example.
SITOP BUF8600 4 s/40 A 6EP4293-8HB00-0XY0
Power supply system PSU8600
86Manual, 05.2017, A5E36758446-3-76
Page 87
Installation and maintenance
4.4
Removal
WARNING
Risk of electric shock
NOTICE
Risk of damage by breaking off the connecting plug
Note
For a hardware configuration with one or several buffer modules, after bringing the basic
device into a no
buffer components.
outputs are shutdown).
4.4 Removal
Before starting removal work of any kind, the main switch of the system must be opened
and measures taken to prevent it from being reclosed. If this instruction is not observed,
touching live parts can result in death or serious injury.
The components can only be safely and reliably removed when the connecting plugs have
been released. Release the connecting plugs, before removing or replacing the basic unit
and supplementary modules.
1. Switch the basic unit into a no-voltage condition.
-voltage condition, the first step is to discharge the energy saved in the
This can take several minutes under no load conditions (all of the
2. Release all of the connections at the plug-in terminals, and if necessary, the PROFINET
connection.
3. Release all of the connecting plugs at the basic unit and the supplementary modules
being used.
To do this, press latch
① and withdraw the connecting plug.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
87
Page 88
Installation and maintenance
The following applies to BUF8600 buffer modules:
WARNING
4.4 Removal
4. Lift the slider using a screwdriver.
5. Detach the basic unit from the lower edge of the standard mounting rail.
6. Remove the basic unit from the lower edge of the standard mounting rail.
7. If required, repeat steps 4 to 6 for each supplementary module.
After disconnecting from the supply, the device takes 30 minutes before it is safely
discharged.
Power supply system PSU8600
88Manual, 05.2017, A5E36758446-3-76
Page 89
Installation and maintenance
4.5
Replacing individual components
WARNING
Risk of electric shock
NOTICE
Risk of damage by breaking off the connecting plug
NOTICE
Risk of damage as a result of jamming when withdrawing
Removing installed components
Note
For a hardware configuration with one or several buffer modules,
device into a no
buffer components. This can take several minutes under no load conditions (all of the
outputs are shutdown).
4.5 Replacing individual components
It is only permissible to replace individual components when they are in the no-voltage state.
Before starting removal work of any kind, the main switch of the system must be opened
and measures taken to prevent it from being reclosed. If this instruction is not observed,
touching live parts can result in death or serious injury.
The components can only be safely and reliably removed when the connecting plugs have
been released. Release the connecting plugs, before removing or replacing the basic unit
and supplementary modules.
Withdrawing individual components without taking the appropriate care can damage
adjacent components. Withdraw components carefully, without applying excessive force.
Replacing an expansion module ② is shown as example. The procedure is similar for all
components.
1. Switch the basic unit into a no-voltage condition.
2. Wait until all of the LEDs of the system have gone dark.
3. Release the connections at the plug-terminals of the component to be replaced.
If the basic unit is replaced: When necessary, also release the PROFINET connection.
after bringing the basic
-voltage condition, the first step is to discharge the energy saved in the
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
89
Page 90
Installation and maintenance
4.5 Replacing individual components
4. Release the connecting plug ① at the component to be replaced.
5. Release the connecting plug ③ at the component to the right (if this is available).
6. Pull-up the slider
④ using a screwdriver ⑤.
Power supply system PSU8600
90Manual, 05.2017, A5E36758446-3-76
Page 91
Installation and maintenance
Installing a new component
4.5 Replacing individual components
7. Detach the component to be released from the lower edge of the standard mounting rail.
When doing this, ensure that both connecting plugs are completely opened and in the
vertical position in order to release the interlocking between the modules.
8. Withdraw the component to be released from the upper edge of the standard mounting
rail.
1. Position the new component with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place.
If it is difficult to snap it into place, simultaneously press the slider as described for rail
mounting.
2. Remove the plastic cover of the connecting socket (if there is an additional module at the
right-hand side).
3. Connect the new component to the adjacent components using the connecting plug.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
91
Page 92
Installation and maintenance
NOTICE
Incorrect response and damage after switching on again
Note
In the REMOTE operating mode, after replacing an individual component, it is not
absolutely necessary that the new component has to be
component was used as replacement, the assigned control system identifies this and
automatically parameterizes the new component with the settings of the predecessor
component.
However, we recommend that the manual settings
component that has been replaced.
4.5 Replacing individual components
4. Connect all of the plug-in terminals at the new component and carefully check that the
wiring is correct. If the basic unit was replaced, then also connect the PROFINET
connection.
When replacing an individual component it must be ensured that the new component
used is the identical type to the one that you have removed and has the same settings.
This is to avoid any possible incorrect response and damage after you switch on again.
After replacing the component, also ensure that the wiring of the plug-in terminals is
correct.
reparameterized. If an identical
are aligned with those of the
5. Connect power to the basic unit.
The new component of the identical type is activated. When replacing an expansion
module, the outputs of the replaced module go into the "manually shutdown" operating
state (LED is lit yellow). When replacing the basic unit, all outputs of the power supply
system go into the "manually shutdown" operating state.
6. Check all of the settings at the components to ensure that the correct values are set.
7. Commission the outputs by pressing on the relevant button.
Power supply system PSU8600
92Manual, 05.2017, A5E36758446-3-76
Page 93
Installation and maintenance
4.6
System response for a modified hardware configuration
WARNING
Risk of electric shock
NOTICE
Damage caused by incorrect wiring
Comparison of the system configuration by SITOP PSU8600
MANUAL operating mode
REMOTE operating mode
4.6 System response for a modified hardware configuration
The system response of the SITOP PSU8600 after modifying the system configuration is
explained in this section.
Modifying the system configuration involves changing, adding or removing individual
components.
Before starting to make changes of any kind to the system configuration, the main switch of
the system must be opened and measures taken to prevent it from being reclosed. If this
instruction is not observed, touching live parts can result in death or serious injury.
SITOP PSU8600 does not check that the wiring is correct.
After making any changes to the system configuration, ensure that the wiring is correct in
order to avoid damage to the system.
When the system starts or a configuration is loaded, the system compares the saved system
data with the actual system configuration:
● Article numbers of the individual components installed
● Serial numbers of the installed individual components
● Positions of the individual components in the system configuration
● Firmware versions of the installed individual components
In the MANUAL operating mode, when the system starts, SITOP PSU8600 compares the
existing system configuration with the system configuration that existed at the last complete
system start.
For an unchanged system configuration, all outputs are activated with the last operating
status before the shutdown.
In the REMOTE operating mode, when the system starts, SITOP PSU8600 compares the
existing system configuration with the last hardware configuration loaded from a control
system in the REMOTE operating mode.
For an unchanged system configuration, all outputs are activated with the parameters and
operating states saved in the configuration. If, before the shutdown, the last operating state
of an output was "Manually switched off (LED is lit yellow), "Automatically switch off due to
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
93
Page 94
Installation and maintenance
4.6.1
Behavior after changing an individual component
NOTICE
Incorrect response and damage after switching on again
Note
For replacing components by an identical component type, proceed as described under
Replacing individual components
Response after making a change and powering up in the MANUAL mode
Response after making a change and powering up in the REMOTE mode
4.6 System response for a modified hardware configuration
overload" (LED is lit red) or "Ready for reset" (LED flashes red), then these operating states
are again assumed when the system starts.
A change involves replacing an individual component by an individual component with a
different order number (not the identical type).
Different settings and an incorrectly wired new component can result in an incorrect
response and subsequent damage.
When replacing an individual component, it must be ensured that the new component has
the same settings as the component that has been replaced in order to avoid an incorrect
response and damage after you switch-on again.
After replacing the component, ensure that the wiring via the plug-in terminals is correct.
(Page 89).
● Buffer modules are automatically commissioned.
● For expansion modules, after switching on again, the outputs are in the operating state
"manually shutdown" (the LEDs of the outputs are lit yellow).
The outputs are switched-on by pressing their associated buttons.
In this case, the system response depends on the specific case.
Power supply system PSU8600
94Manual, 05.2017, A5E36758446-3-76
Page 95
Installation and maintenance
Case 1
Case 2
See also
4.6 System response for a modified hardware configuration
Replacement using a module with the same function (a buffer module by buffer module,
expansion module by expansion module):
● A compatibility check is carried out for buffer modules:
– If a buffer module with electrolytic capacitors is replaced by a buffer module with
electrolytic capacitors, then the new module is automatically commissioned.
– If a buffer module with double-layer capacitors is replaced by a buffer module with
double-layer capacitors, then a more powerful module is automatically commissioned.
A module with a lower power rating is deactivated (LED "O.K." flashes red). You can
activate this module by loading a corrected configuration via the associated control
system.
– If a buffer module with electrolytic capacitors is replaced by a buffer module with
double-layer capacitors - or vice versa - then the new module is automatically
deactivated ("O.K." LED flashes red). You can activate this module by loading a
corrected configuration via the associated control system.
● For expansion modules, a compatibility check is carried out:
– For expansion modules with a higher power rating, after switching on again, the
outputs are in the operating state "manually shutdown" (the LEDs of the outputs are lit
yellow).
The outputs are switched-on by pressing their associated buttons.
– Expansion modules with a lower power rating are deactivated (LED "O.K." flashes red,
LEDs of the outputs are dark).
You can activate these modules by loading a corrected configuration via the
associated control system.
Replacement using a module with a different function (a buffer module by an expansion
module, or vice versa):
● The new module is deactivated (LED "O.K." flashes red, LEDs of the expansion module
outputs are dark).
You can activate the module by loading a correct configuration via the associated control
system.
Replacing individual components (Page 89)
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
95
Page 96
Installation and maintenance
4.6.2
Response after adding an individual component
Note
When changing the module sequence,
previously used modules are undesirably deactivated
until now are shutdown.
To avoid undesirably deactivating modules that have been used up until now
down outputs that have been used up until now, insert the new individual components at the
right
system configuration is not changed.
Response after adding a component and powering up in the MANUAL mode
Response after adding a component and powering up in the REMOTE mode
4.6.3
Response after removing an individual component
NOTICE
Incorrect response and damage after switching on again
Note
By removing modules, it is possible that the previous module position of the remaining
modules is changed. This can result in modules, whose position has changed, being
deactivated and output
4.6 System response for a modified hardware configuration
Adding involves expanding the system on the right-hand side by adding additional
components.
by checking the module position it is possible that
– and outputs that have been used up
– and shutting
-hand side of the system. As a consequence, the previous module sequence in the
● New buffer modules are automatically commissioned.
● For new expansion modules, after switching on again, the outputs are in the operating
state "manually shut down" (the LEDs of the outputs are lit yellow).
The outputs are switched-on by pressing their associated buttons.
● The new module is deactivated (LED "O.K." flashes red, LEDs of the expansion module
outputs are dark).
You can activate the module by loading a correct configuration via the associated control
system.
Different settings and incorrect wiring, that can be caused by changes made to the system
configuration, can result in an incorrect response and subsequent damage.
After making any change to the system configuration, ensure the correct settings of the
remaining components as well as the correctness of the associated wiring to avoid any
incorrect response and damage after switching on again.
s shutdown.
Power supply system PSU8600
96Manual, 05.2017, A5E36758446-3-76
Page 97
Installation and maintenance
Response after removing a component and powering up in the MANUAL mode
Response after removing a component and powering up in the REMOTE mode
Case 1
4.6 System response for a modified hardware configuration
● Buffer modules are automatically commissioned.
● Expansion modules with an unchanged module position are activated with the last
operating state of the outputs before shutdown.
● For expansion modules with changed module position, after switching on again, the
outputs are in the operating state "manually shutdown" (the LEDs of the outputs are lit
yellow).
The outputs are switched-on by pressing their associated buttons.
● Buffer modules with unchanged module position are automatically commissioned.
● Expansion modules with an unchanged module position are activated with the last
operating state of the outputs before shutdown.
● For modules with changed module position, the system response depends on the specific
case.
The function of the module is identical with the function of the previous module at the
installation location (buffer module at the installation location of a buffer module, expansion
module at the installation location of an expansion module).
● A compatibility check is carried out for buffer modules:
– If a buffer module with electrolytic capacitors is replaced by a buffer module with
electrolytic capacitors, then the new module is automatically commissioned.
– If a buffer module with double-layer capacitors is replaced by a buffer module with
double-layer capacitors, then a more powerful module is automatically commissioned.
A module with a lower power rating is deactivated (LED "O.K." flashes red). You can
activate this module by loading a corrected configuration via the associated control
system.
– If a buffer module with electrolytic capacitors is replaced by a buffer module with
double-layer capacitors - or vice versa - then the new module is automatically
deactivated ("O.K." LED flashes red). You can activate this module by loading a
corrected configuration via the associated control system.
● For expansion modules, a compatibility check is carried out:
– For identical expansion modules with a higher power rating, after switching on again,
the outputs are in the operating state "manually shutdown" (the LEDs of the outputs
are lit yellow).
The outputs are switched-on by pressing their associated buttons.
– Expansion modules with a lower power rating are deactivated (LED "O.K." flashes red,
LEDs of the outputs are dark).
You can activate these modules by loading a corrected configuration via the
associated control system.
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
97
Page 98
Installation and maintenance
Case 2
4.6 System response for a modified hardware configuration
The function of the module is not identical with the function of the previous module at the
installation location (buffer module at the installation location of an expansion module – or
vice versa).
● The module is deactivated (LED "O.K." flashes red, LEDs of the expansion module
outputs are dark).
You can activate the module by loading a correct configuration via the associated control
system.
Power supply system PSU8600
98Manual, 05.2017, A5E36758446-3-76
Page 99
5
5.1
Standard mounting position
Output current as a function of the ambient temperature
The device is mounted on standard mounting rails according to EN 60715. The power supply
system must be mounted in such a way that the input terminals and the output terminals are
at the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the power supply
system (maximum depth of the cable duct, 50 mm).
No clearance is required at the side.
Figure 5-1 Basic device SITOP PSU8600 20 A: Output current in the standard mounting position
Figure 5-2 Basic device SITOP PSU8600 20 A and supplementary modules: Output current in the
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
standard mounting position
99
Page 100
Mounting position, mounting clearances
Output current as a function of the altitude derating
5.1 Standard mounting position
Figure 5-3 Basic device SITOP PSU8600 40 A: Output current in the standard mounting position
Figure 5-4 Basic device SITOP PSU8600 40 A and supplementary modules: Output current in the
standard mounting position
Figure 5-5 Mounting height derating
Power supply system PSU8600
100Manual, 05.2017, A5E36758446-3-76
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.