Siemens PSU300B, PSU300M User Manual

Page 1
SITOP PSU300M/300B
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SITOP power supply

SITOP PSU300M/300B

Manual
SITOP PSU300M 24 V/20 A 6EP1436 SITOP PSU300M 48 V/10 A 6EP1456 SITOP PSU300B 12 V/20 A 6EP1424 SITOP PSU300B 24 V/17 A 6EP1436 SITOP PSU300B 24 V/30 A 6EP1437-3BA20
11.2014
C98130
Overview
Safety notes
1
Description, device design, dimension drawing
2
Mounting/disassembly
3
Mounting position, mounting clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
-3BA10
-3BA00
-3BA00
-3BA20
-A7574-A2-2-7629
Page 2
Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY
C98130-A7574-A2-2-7629
Copyright © Siemens AG 2014. All rights reserved
Legal information
Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
12/2014 Subject to change
Page 3

Overview

The 3-phase power supply from the SITOP PSU300M/300B is a powerful, stabilized technology power supply for automated machines and systems.
The key benefits of the product include:
3-phase 320 to 575 VAC wide-range input
Power boost during operation 300% for 25 ms (only PSU300M and PSU300B 12 V/20 A)
No lateral mounting clearances are required
150% extra power when loads with high input current are switched on (PSU300M and
PSU300B 12 V/20 A only)
Ambient temperature -25 (-10)...+70 °C
48 V / 10 A permits small cable cross-sections
Selectable short-circuit behavior
Soft characteristic curve for parallel switching or battery charging can be selected
Display of the operating state using 3 LEDs
Integrated signaling contact "DC 12 V O.K." / "DC 24 V O.K." / "DC 48 V O.K."
The properties of the PSU300B power supplies makes them ideal for battery charging
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
To increase the system availability, some reliable power supplies can be expanded using SITOP supplementary modules (redundancy module, selectivity module, buffer module), as well as SITOP DC-UPS modules.
3
Page 4
Overview
Ordering data
Regulated SITOP PSU300M/300B power supply
Type
Order number
Output 24 V DC / 20 A
Output 48 V DC / 10 A
Output 12 V DC / 20 A
Output 24 V DC / 17 A
Output 24 V DC / 30 A
Accessories
Type
Order number
Device identification labels 20 mm × 7 mm, pastel turquoise
3RT1900-1SB20
The following device versions are available:
3-phase 400-500 V AC input,
3-phase 400-500 V AC input,
3-phase 400-500 V AC input,
3-phase 400-500 V AC input,
3-phase 400-500 V AC input,
6EP1436-3BA10
6EP1456-3BA00
6EP1424-3BA00
6EP1436-3BA20
6EP1437-3BA20
SITOP PSU300M/300B
4 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 5

Table of contents

Overview................................................................................................................................................. 3
1 Safety notes ............................................................................................................................................ 7
2 Description, device design, dimension drawing........................................................................................ 9
3 Mounting/disassembly ........................................................................................................................... 19
4 Mounting position, mounting clearances ................................................................................................ 21
5 Installation ............................................................................................................................................ 35
6 Technical data ...................................................................................................................................... 39
2.1 Device description ..................................................................................................................... 9
2.2 Connections and terminal designation.................................................................................... 10
2.3 Potentiometer .......................................................................................................................... 11
2.4 Status displays and signaling ................................................................................................. 12
2.5 Change-over switch ................................................................................................................ 15
2.6 Block diagram ......................................................................................................................... 16
2.7 Dimensions and weight ........................................................................................................... 17
4.1 Standard mounting position .................................................................................................... 21
4.2 Other mounting positions ........................................................................................................ 24
4.2.1 6EP1436-3BA10 ..................................................................................................................... 24
4.2.2 6EP1456-3BA00 ..................................................................................................................... 26
4.2.3 6EP1424-3BA00 ..................................................................................................................... 28
4.2.4 6EP1436-3BA20 ..................................................................................................................... 30
4.2.5 6EP1437-3BA20 ..................................................................................................................... 32
5.1 Line-side connection ............................................................................................................... 35
5.2 Output-side connection ........................................................................................................... 37
6.1 Input ........................................................................................................................................ 39
6.2 Output ..................................................................................................................................... 41
6.3 Efficiency ................................................................................................................................. 50
6.4 Closed-loop control ................................................................................................................. 53
6.5 Protection and monitoring ....................................................................................................... 54
6.6 MTBF ...................................................................................................................................... 55
6.7 Mechanical system ................................................................................................................. 55
6.8 Accessories ............................................................................................................................. 57
6.9 Dimension drawing ................................................................................................................. 57
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
5
Page 6
Table of contents
7 Safety, approvals, EMC ........................................................................................................................ 59
8 Ambient conditions ................................................................................................................................ 63
9 Applications .......................................................................................................................................... 65
10 Environment ......................................................................................................................................... 77
11 Service & Support ................................................................................................................................. 79
7.1 Safety ..................................................................................................................................... 59
7.2 Test voltage ............................................................................................................................ 60
7.3 Approvals ............................................................................................................................... 61
7.4 EMC ....................................................................................................................................... 61
9.1 Parallel connection to increase power rating ......................................................................... 65
9.2 Parallel connection for redundancy ....................................................................................... 67
9.3 Series connection for increased voltage ................................................................................ 69
9.4 Overload protection in the 24 V output circuit ........................................................................ 70
9.5 Protection against short-time voltage dips ............................................................................. 71
9.6 Protecting against longer power failures ................................................................................ 72
9.7 Battery charging with SITOP PSU300B ................................................................................. 74
SITOP PSU300M/300B
6 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 7
1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
7
Page 8
Safety notes
SITOP PSU300M/300B
8 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 9
2
2.1

Device description

Line input
DC output
Signaling contacts
Potentiometer 12 ... 14 V, 24 ... 28.8 V, 42 ... 56 V
Pilot lamps (12/24/48 V OK, OVERLOAD, SHUT DOWN)
Selector switch
DIN rail slider
Convection
Clearance above/below
SITOP PSU300M/300B is a primary-clocked power supply for connection to a 3-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LED displays indicate the operating state. The operating state of the device can be processed via the signaling contact. The PSU300B devices are optimized to charge batteries.
Figure 2-1 Design
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
9
Page 10
Description, device design, dimension drawing
2.2
Connections and terminal designation
Connections and terminal designations
Do not subject the end stop to higher loads
Do not subject the end stop to higher loads

2.2 Connections and terminal designation

The line input terminals can be used to establish the connection to the supply voltage. The output terminals
are used to connect to the loads to be supplied (see also Section
Installation (Page 35)).
Line input L1, L2, L3, PE
output "+"
output "–"
signaling contacts 13, 14
*1)
Figure 2-2 Terminal data for 6EP1436-3BA10, 6EP1456-3BA00, 6EP1424-3BA00, 6EP1436-3BA20
One screw terminal each
2 screw terminals
2 screw terminals
One screw terminal each
*1)
Figure 2-3 Terminal data for 6EP1437-3BA20
SITOP PSU300M/300B
10 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 11
Description, device design, dimension drawing
2.3
Potentiometer
NOTICE
Thermal overload possible
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.

2.3 Potentiometer

The potentiometer on the front of the device is used to adjust the output voltage. The output voltage is set to 12 V, 24 V or 48 V in the factory, and can be adjusted in the range 12 ... 14 V, 24 ... 28.8 V or 42 ... 56 V; for example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-4 Potentiometer (example 6EP1456-3BA00 / 6EP1437-3BA20)
When adjusting the output voltage to >24 V (>48 V), the output current must be derated by 4 %/V or the permissible ambient temperature must be taken into account with 3 K/V (applies to PSU300M devices).
For notes on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data for 6EP1436-3BA10, 6EP1456-3BA00, 6EP1424-3BA00, 6EP1436-3BA20 (Page 10) and Figure 2-3 Terminal data for 6EP1437-3BA20 (Page 10).
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
11
Page 12
Description, device design, dimension drawing
2.4
Status displays and signaling
6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V/10 A)
60 V DC / 0.3 A) for "24 V O.K."
60 V DC / 0.3 A) for "48 V O.K."
6EP1424-3BA00 (12 V/20 A)
6EP1436-3BA20 (24 V/17 A) 6EP1437-3BA20 (24 V / 30 A)
Red LED for "latching shutdown"
Red LED for "latching shutdown"
60 V DC / 0.3 A) for "12 V O.K."
60 V DC / 0.3 A) for "24 V O.K."
Signaling
6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V/10 A) contacts 13-14 closed
(quiescent position)

2.4 Status displays and signaling

Operating display LED green for "24 V O.K."
Yellow LED for "overload" Red LED for "latching shutdown"
Signaling contact Relay contact (NO contact, rating
Operating display LED green for "12 V O.K."
Yellow LED for "overload"
Signaling contact Relay contact (NO contact, rating
LED green for "48 V O.K." Yellow LED for "overload" Red LED for "latching shutdown" Relay contact (NO contact, rating
LED green for "24 V O.K." Yellow LED for "overload"
Relay contact (NO contact, rating
Figure 2-5 Operating display and signaling (example 6EP1456-3BA00 / 6EP1437-3BA20)
Green LED ⑤ lit Signaling contact ,
LED ⑤ off Signaling contact ,
contacts 13-14 open
SITOP PSU300M/300B
12 Manual, 11.2014, C98130-A7574-A2-2-7629
Normal operation, output voltage > 20.5 V
No supply voltage No supply voltage
Normal operation, output voltage > 41 V
Page 13
Description, device design, dimension drawing
Signaling
6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V/10 A) (quiescent position)
contacts 13-14 closed
(quiescent position)
(quiescent position)
Signaling
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
contacts 13-14 closed
(quiescent position)
(quiescent position)
2.4 Status displays and signaling
Yellow LED ⑤ lit Signaling contact ,
contacts 13-14 open
Yellow and green LED lights Signaling contact ③,
Red LED ④ lit Signaling contact ,
contacts 13-14 open
Red LED ④ flashes Signaling contact ,
contacts 13-14 open
Green LED ⑤ lit Signaling contact ,
Overload, output voltage < 20.5 V (only in "constant current" mode)
Phase failure, output voltage O.K. Phase failure, output voltage O.K.
Latching shutdown (only in "Shutdown" mode)
Overtemperature → power OFF/ON after
3 min
Normal operation Output voltage > 10.0 V
Normal operation, output voltage > 20.5 V
Overload, output voltage < 41 V (only in "constant current" mode)
Latching shutdown (only in "Shutdown" mode)
Overtemperature → power OFF/ON after
3 min
Normal operation, output voltage > 20.5 V
LED ⑤ off Signaling contact ,
contacts 13-14 open
Yellow LED ⑤ lit
Signaling contact contacts 13-14 open
Yellow and green LED lights
Signaling contact contacts 13-14 open
(quiescent position)
③,
③,
No supply voltage No supply voltage No supply voltage
Overload, output voltage < 10.0 V (only in "constant current")
Phase failure, output voltage O.K.
Overload, output voltage < 20.5 V (only in "constant current" mode)
Phase failure, output voltage O.K.
Overload, output voltage < 20.5 V (only in "constant current" mode)
-
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
13
Page 14
Description, device design, dimension drawing
Signaling
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
(quiescent position)
contacts 13-14 closed
2.4 Status displays and signaling
Red LED ④ lit Signaling contact ,
contacts 13-14 open
Red LED flashes
Signaling contact
③,
Latching shutdown (only in "Shutdown" mode)
Overtemperature → power
OFF/ON after 3 minutes
Latching shutdown (only in "Shutdown" mode)
Overtemperature → power
OFF/ON after 3 minutes
Latching shutdown (only in "Shutdown" mode)
Overtemperature → power
OFF/ON after 3 minutes
SITOP PSU300M/300B
14 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 15
Description, device design, dimension drawing
2.5
Change-over switch
Switch
ON
OFF
A
Parallel operation:
attained.
Single operation:
B
Latching shutdown:
Constant current:

2.5 Change-over switch

Figure 2-6 Selector switch (example 6EP1456-3BA00 / 6EP1437-3BA20)
The two switches A and B are used to influence the output characteristic curve:
influences the output characteristic in the load range
influences the output characteristic in the overload range
'Soft' characteristic curve (see, e.g. Figure 6-8 6EP1436-3BA10 parallel operation output char­acteristic curve (Page 46)) for the parallel oper­ation of two or more devices: The output voltage falls with increasing output current (namely, also for the overcurrent pulse!). This means that for full output current the high­est output voltage can normally no longer be
If the output current rises above the rated value and above the current limit, the device reduces the output voltage (see, e.g. Figure 6-13 6EP1436-3BA10 latching shutdown output characteristic curve (Page 48)). If the output voltage falls below (10 V), (20 V), (40 V), the device shuts down latching, the red LED lights. This limit voltage of (10 V), (20 V), (40 V) is independent of the set output voltage. The 'Short-time overload current' feature is not available in this operating mode. In order to also be able to charge large capacitances in this operating mode at the output, non-latching shutdown is performed during the first ten sec­onds after power on. During these first 10 s, the device responds for overload as if the switch is OFF.
Delivery state
'Hard' characteristic curve (see, e.g. Figure 6-3 6EP1436-3BA10 single operation output char­acteristic curve (Page 44)) for normal operation (single operation): The output voltage is inde­pendent of the output current.
Delivery state
If the output current rises above the rated value and above the current limit, the device reduces the output voltage. The yellow LED lights if the output voltage falls below (10 V), (20 V), (40 V).
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
Delivery state: A-OFF; B-OFF
15
Page 16
Description, device design, dimension drawing
2.6
Block diagram

2.6 Block diagram

Figure 2-7 Block diagram
SITOP PSU300M/300B
16 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 17
Description, device design, dimension drawing
2.7
Dimensions and weight
6EP1424-3BA00 (12 V / 20 A) 6EP1436-3BA20 (24 V / 17 A) 6EP1436-3BA10 (24 V / 20 A) 6EP1456-3BA00 (48 V / 10 A)
6EP1437-3BA20 (24 V / 30 A)
Dimensions (W × H × D) in mm
70 × 125 × 125
150 × 125 × 150
Weight
approx. 1.2 kg
approx. 3.4 kg

2.7 Dimensions and weight

Figure 2-8 6EP1424-3BA00, 6EP1436-3BA20, 6EP1436-3BA10, 6EP1456-3BA00 dimensioned
drawing
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
Figure 2-9 Dimension drawing 6EP1437-3BA20
17
Page 18
Description, device design, dimension drawing
2.7 Dimensions and weight
SITOP PSU300M/300B
18 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 19
3
WARNING
Installing the device in a housing or a control cabinet
Mounting
Removal
The SITOP PSU300M/300B power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails according to EN 60715.
To mount the device, position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place. If this is too difficult, press slider
at the same time, as described under "Removal".
To remove, pull up the slider using a screwdriver and disengage the device at the bottom edge of the standard mounting rail. Then you can remove the device from the upper edge of the standard mounting rail.
Figure 3-1 Mounting/removal (example 6EP1456-3BA00)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
19
Page 20
Mounting/disassembly
WARNING
Use in hazardous zones
If the devices are to be used in hazardous zones (Ex II 3G Ex nA nC IIC T4) they must be installed in a distribution box with degree of protection IP54 or higher.
SITOP PSU300M/300B
20 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 21
4
4.1

Standard mounting position

Output current as a function of the ambient temperature and mounting height
The device is mounted on standard mounting rails according to EN 60715. The device must be mounted vertically in such a way that the input terminals and the output terminals are at the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm).
No space is required at the side.
Figure 4-1 6EP1436-3BA10: Output current in the standard mounting position
Figure 4-2 6EP1456-3BA00: Output current in the standard mounting position
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
21
Page 22
Mounting position, mounting clearances
4.1 Standard mounting position
Figure 4-3 6EP1424-3BA00: Output current in the standard mounting position
Figure 4-4 6EP1436-3BA20: Output current in the standard mounting position
Figure 4-5 6EP1437-3BA20: Output current in the standard mounting position
SITOP PSU300M/300B
22 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 23
Mounting position, mounting clearances
4.1 Standard mounting position
Figure 4-6 Mounting height derating
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
23
Page 24
Mounting position, mounting clearances
4.2
Other mounting positions
Note
In the case of mounting positions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fas measures may be required, e.g. to prevent the device from slipping on the standard mounting rail.
4.2.1

6EP1436-3BA10

4.2 Other mounting positions

For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams.
tened standard mounting rail, additional
Figure 4-7 6EP1436-3BA10 mounting position (1)
Figure 4-8 6EP1436-3BA10 mounting position (2)
SITOP PSU300M/300B
24 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 25
Mounting position, mounting clearances
4.2 Other mounting positions
Figure 4-9 6EP1436-3BA10 mounting position (3)
Figure 4-10 6EP1436-3BA10 mounting position (4)
Figure 4-11 6EP1436-3BA10 mounting position (5)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
25
Page 26
Mounting position, mounting clearances
4.2.2

6EP1456-3BA00

4.2 Other mounting positions
Figure 4-12 6EP1456-3BA00 mounting position (1)
Figure 4-13 6EP1456-3BA00 mounting position (2)
Figure 4-14 6EP1456-3BA00 mounting position (3)
SITOP PSU300M/300B
26 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 27
Mounting position, mounting clearances
4.2 Other mounting positions
Figure 4-15 6EP1456-3BA00 mounting position (4)
Figure 4-16 6EP1456-3BA00 mounting position (5)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
27
Page 28
Mounting position, mounting clearances
4.2.3

6EP1424-3BA00

4.2 Other mounting positions
Figure 4-17 6EP1424-3BA00 mounting position (1)
Figure 4-18 6EP1424-3BA00 mounting position (2)
Figure 4-19 6EP1424-3BA00 mounting position (3)
SITOP PSU300M/300B
28 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 29
Mounting position, mounting clearances
4.2 Other mounting positions
Figure 4-20 6EP1424-3BA00 mounting position (4)
Figure 4-21 6EP1424-3BA00 mounting position (5)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
29
Page 30
Mounting position, mounting clearances
4.2.4

6EP1436-3BA20

4.2 Other mounting positions
Figure 4-22 6EP1436-3BA20 mounting position (1)
Figure 4-23 6EP1436-3BA20 mounting position (2)
Figure 4-24 6EP1436-3BA20 mounting position (3)
SITOP PSU300M/300B
30 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 31
Mounting position, mounting clearances
4.2 Other mounting positions
Figure 4-25 6EP1436-3BA20 mounting position (4)
Figure 4-26 6EP1436-3BA20 mounting position (5)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
31
Page 32
Mounting position, mounting clearances
4.2.5

6EP1437-3BA20

4.2 Other mounting positions
Figure 4-27 6EP1437-3BA20 mounting position (1)
Figure 4-28 6EP1437-3BA20 mounting position (2)
SITOP PSU300M/300B
32 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 33
Mounting position, mounting clearances
4.2 Other mounting positions
Figure 4-29 6EP1437-3BA20 mounting position (3)
Figure 4-30 6EP1437-3BA20 mounting position (4)
Figure 4-31 6EP1437-3BA20 mounting position (5)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
33
Page 34
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU300M/300B
34 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 35
5
WARNING
Hazard due to electric shock
5.1

Line-side connection

Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury.
The SITOP PSU300M/300B power supply is designed for connection to a 3-phase AC line supply (TN or TT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of 3-phase 400-500 V AC, 50/-60 Hz, IT system with rated voltages 3-phase 400-480 V AC.
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
Figure 5-1 Line connection (example: 6EP1456-3BA00)
The line supply is connected using terminals L1, L2, L3 and PE (see Figure 5-1 Line connection (example: 6EP1456-3BA00) (Page 35)), and must be implemented according to IEC 60364 and EN 50178 . A protective device (miniature circuit breaker or circuit breaker) and a disconnection unit for the power supply must be provided. A ground-fault circuit interrupter is not permissible against indirect contact as the only protective measure. This applies for the complete line supply protected by the ground-fault circuit interrupter.
35
Page 36
Installation
Protection
SITOP PSU300M/300B
Recommended line-side protection
or 3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
or 3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
or 3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
or 3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
5.1 Line-side connection
6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V / 10 A)
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
3-pole coupled miniature circuit breaker (IEC 898), characteristic C, 6-16 A or 3RV2011-1EA10 circuit breaker, setting of the thermal overcurrent trip: 3 A or 3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
3-pole coupled miniature circuit breaker (IEC 898), characteristic C, 6-16 A or 3RV2011-1EA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
3-pole coupled miniature circuit breaker (IEC 898), characteristic C, 6-10 A or 3RV2011-1EA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
3-pole coupled miniature circuit breaker (IEC 898), characteristic C, 6-16 A or 3RV2011-1EA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
3-pole coupled miniature circuit breaker (IEC 898), characteristic C, 10-16 A or 3RV2011-1EA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.
SITOP PSU300M/300B
36 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 37
Installation
5.2
Output-side connection
Note
If the safety concept of the plant or system specifies that the DC output circuit should be grounded (PELV), then it is permissible that the output voltage of the SITOP power s grounded. In this case, ideally, the grounding at the output should be directly connected from terminal " system (PE) of the plant or system.

5.2 Output-side connection

At its output, the SITOP PSU300M/300B power supply provides an isolated (= non­grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 39)).
Figure 5-2 Output connection (example 6EP1456-3BA00 / 6EP1437-3BA20)
The output voltage is connected via the + and - terminals at the output of the power supply (see Figure 5-2 Output connection (example 6EP1456-3BA00 / 6EP1437-3BA20) (Page 37)). Ensure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly.
upply is
-" of the power supply to a suitable connection point of the protective conductor
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
37
Page 38
Installation
5.2 Output-side connection
SITOP PSU300M/300B
38 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 39
6
Note
Technical data is applicable for a rated input voltage, rated load and +25° C ambient temperature (if nothing else is specified).
6.1

Input

6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V / 10 A)
Input
3-phase, AC
3-phase, AC
Rated voltage value Ue rated
400-500 V
400-500 V
Wide-range input
Yes
Yes
Overvoltage strength
2.3 × Ue rated, 1.3 ms
2.3 × Ue rated, 1.3 ms
Rated line frequency
50-60 Hz
50-60 Hz
Line frequency range
47 ... 63 Hz
47 ... 63 Hz
voltage 400 V
I²t, max
0.8 A2s
0.8 A2s
Integrated input fuse
None
None
(IEC 898)
or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
Voltage range
Remark
Power failure buffering at Ia rated, min
Remark: at Ue = 400 V
Input current / at rated value of input
Input current / at rated value of input voltage 500 V
Inrush current limiting (+25° C), max.
Protection in the line feeder cable
320 ... 575 V Derating at Ue < 340 V: 10% [Ia]
15 ms
1.2 A 1.2 A
1 A
18 A
Required: 3-pole, coupled miniature circuit breaker 6 ... 16 A characteristic C
320 ... 575 V No derating
15 ms
1 A
18 A
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
39
Page 40
Technical data
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
Voltage range
320 ... 575 V
320 ... 575 V
320 ... 575 V
Overvoltage strength
2.3 × Ue rated, 1.3 ms
2.3 × Ue rated, 1.3 ms
2.3 × Ue rated, 1.3 ms
Rated line frequency
50-60 Hz
50-60 Hz
50-60 Hz
Line frequency range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
input voltage 400 V
input voltage 500 V
(+25° C), max.
I²t, max
0.8 A2s
0.8 A2s
2.24 A2s
Integrated input fuse
None
None
None
1DD10 (UL 489)
6.1 Input
Input 3-phase, AC 3-phase, AC 3-phase, AC Rated voltage value Ue rated 400-500 V 400-500 V 400-500 V
Wide-range input Yes Yes Yes
Power failure buffering at Ia rated, min
Remark: at Ue = 400 V
Input current / at rated value of
Input current / at rated value of
Inrush current limiting
Protection in the line feeder cable (IEC 898)
20 ms 20 ms 20 ms
0.7 A 1.2 A 1.6 A
0.6 A 1 A 1.3 A
18 A 18 A 56 A
Required: 3-pole, coupled miniature circuit breaker 6 ... 10 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
Required: 3-pole, coupled miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-
SITOP PSU300M/300B
40 Manual, 11.2014, C98130-A7574-A2-2-7629
Figure 6-1 Power failure buffering
Page 41
Technical data
6.2
Output
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
Total tolerance, static ±
3 %
3 %
Static line regulation, approx.
0,1 %
0,1 %
peak-peak, max.
(bandwidth, approx. 20 MHz)
(Page 11)
(Page 11)
be adjusted
Operating display
LED green for "24 V O.K."
LED green for "48 V O.K."
60 V DC / 0.3 A) for "24 V O.K."
60 V DC / 0.3 A) for "48 V O.K."
Response when switching on/off
No overshoot of Ua (Soft-Start)
No overshoot of Ua (Soft-Start)
Starting delay, max.
2.5 s
2.5 s
Voltage rise, typ.
150 ms
150 ms
maximum
Rated current value Ia rated
20 A
10 A
Output active power / typical
480 W
480 W
circuit when powering up / typical
circuit during operation, typical
tion
(Page 15))
(Page 15))

6.2 Output

Output Regulated, isolated DC voltage Regulated, isolated DC voltage Rated voltage value Ua rated DC 24 V 48 V
Static load regulation, approx. 0,2 % 0,2 % Residual ripple in the load range
100 mV 100 mV
Spikes peak-peak, max.
Adjustment range
Remark
Product function / output voltage can
Output voltage setting
Remark
Signaling Relay contact (NO contact, rating
Voltage rise time of the output voltage,
Current range
Remark
200 mV 200 mV
24 … 28.8 V Derating, see Section Potentiometer
Yes Yes
Via potentiometer Max. 480 W
500 ms 500 ms
0 … 20 A 14 A to +70° C
42 … 56 V Derating, see Section Potentiometer
Via potentiometer Max. 480 W
Relay contact (NO contact, rating
0 … 10 A 7 A to +70° C
Constant overload current / for a short
Short-time overload current / for a short
Duration of the current overload capa­bility / for a short circuit during opera-
Can be connected in parallel to increase the power rating
Remark
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
23 A 11 A
60 A 23 A
25 ms 25 ms
Yes
Switchable characteristic curve (see Figure 2-6 Selector switch (example 6EP1456-3BA00 / 6EP1437-3BA20)
Yes
Switchable characteristic curve (see Figure 2-6 Selector switch (example 6EP1456-3BA00 / 6EP1437-3BA20)
41
Page 42
Technical data
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
to increase the power rating, units
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
voltage
voltage
voltage
DC
Total tolerance, static ±
3 %
3 %
3 %
Static line regulation, approx.
2 %
0,1 %
0,1 %
approx.
range peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
12 ... 14 V
24 … 28.8 V
24 … 28.8 V
voltage can be adjusted
Operating display
LED green for "12 V O.K."
LED green for "24 V O.K."
LED green for "24 V O.K."
on/off
(Soft-Start)
(Soft-Start)
(Soft-Start)
Starting delay, max.
2.5 s
2.5 s
2.5 s
Voltage rise, typ.
20 ms
40 ms
20 ms
output voltage, maximum
Rated current value Ia rated
20 A
20 A
30 A
typical
powering up, typical
6.2 Output
Number of units connected in parallel
2 2
Output characteristic See Figure 6-3 6EP1436-3BA10 single
operation output characteristic curve (Page 44)
Output Regulated, isolated DC
Rated voltage value Ua rated
Static load regulation,
Residual ripple in the load
Spikes peak-peak, max.
12 V 24 V 24 V
4 % 0,2 % 0,1 %
100 mV 100 mV 100 mV
200 mV 200 mV 200 mV
Regulated, isolated DC
See Figure 6-4 6EP1456-3BA00 single operation output characteristic curve (Page 44)
Regulated, isolated DC
Product function / output
Output voltage setting
Remark
Yes Yes Yes
Via potentiometer
-
Signaling Relay contact (NO contact,
rating 60 V DC / 0.3 A) for "12 V O.K."
Response when switching
Voltage rise time of the
Current range
Remark
Output active power /
Constant overload current
No overshoot of Ua
500 ms 500 ms 500 ms
0 … 20 A 20 A to +70° C
240 W 408 W 720 W
22 A 19 A 32 A
for a short-circuit when
Via potentiometer
Max. 480 W
Via potentiometer
-
Relay contact (NO contact, rating 60 V DC / 0.3 A) for "24 V O.K."
No overshoot of Ua
0 … 17 A 14 A to +70 °C
No overshoot of Ua
0 … 30 A 25 A to +70° C
SITOP PSU300M/300B
42 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 43
Technical data
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
3BA20) (Page 15))
3BA20) (Page 15))
3BA20) (Page 15))
units
(Page 44)
(Page 45)
(Page 45)
6.2 Output
Short-time overload current for a short-circuit during operation, typical
Duration of the current overload capability for a short-circuit during operation
Can be connected in parallel to increase the power rating
Remark
Number of devices that can be connected in parallel to increase the power rating,
Output characteristic See Figure 6-5 6EP1424-
60 A - -
25 ms
Yes
Switchable characteristic curve (see Figure 2-6 Selec­tor switch (example 6EP1456-3BA00 / 6EP1437-
2 2 2
3BA00 single operation out­put characteristic curve
-
Yes
Switchable characteristic curve (see Figure 2-6 Selec­tor switch (example 6EP1456-3BA00 / 6EP1437-
See Figure 6-6 6EP1436­3BA20 single operation out­put characteristic curve
-
Yes
Switchable characteristic curve (see Figure 2-6 Selec­tor switch (example 6EP1456-3BA00 / 6EP1437-
See Figure 6-7 6EP1437­3BA20 single operation out­put characteristic curve
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
Figure 6-2 Starting delay/voltage rise
43
Page 44
Technical data
6.2 Output
Figure 6-3 6EP1436-3BA10 single operation output characteristic curve
Figure 6-4 6EP1456-3BA00 single operation output characteristic curve
Figure 6-5 6EP1424-3BA00 single operation output characteristic curve
SITOP PSU300M/300B
44 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 45
Technical data
6.2 Output
Figure 6-6 6EP1436-3BA20 single operation output characteristic curve
Figure 6-7 6EP1437-3BA20 single operation output characteristic curve
The device supplies a constant output voltage until the current limit is reached. If overload occurs, the output current is limited and the output voltage lowered.
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
45
Page 46
Technical data
Selector switch A closed (parallel operation):
6.2 Output
The output voltage decreases with increasing output current.
Figure 6-8 6EP1436-3BA10 parallel operation output characteristic curve
Figure 6-9 6EP1456-3BA00 parallel operation output characteristic curve
Figure 6-10 6EP1424-3BA00 parallel operation output characteristic curve
SITOP PSU300M/300B
46 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 47
Technical data
6.2 Output
Figure 6-11 6EP1436-3BA20 parallel operation output characteristic curve
Figure 6-12 6EP1437-3BA20 parallel operation output characteristic curve
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
47
Page 48
Technical data
Selector switch B closed (latching shutdown):
6.2 Output
The device will be shut down if the overload continues for longer than 100 ms. A reset is performed by switching the power supply OFF for at least 5 seconds.
Figure 6-13 6EP1436-3BA10 latching shutdown output characteristic curve
Figure 6-14 6EP1456-3BA00 latching shutdown output characteristic curve
Figure 6-15 6EP1424-3BA00 latching shutdown output characteristic curve
SITOP PSU300M/300B
48 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 49
Technical data
6.2 Output
Figure 6-16 6EP1436-3BA20 latching shutdown output characteristic curve
Figure 6-17 6EP1437-3BA20 latching shutdown output characteristic curve
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
49
Page 50
Technical data
6.3
Efficiency
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
rated, approx.
rated, approx.

6.3 Efficiency

Efficiency at Ua rated, Ia rated, approx. 93 % 93 % Power loss at Ua rated, Ia rated, approx. 36 W 36 W
Efficiency at Ua rated, Ia
Power loss at Ua rated, Ia
Figure 6-18 6EP1436-3BA10 efficiency
88 % 93 % 93 %
20 W 31 W 50 W
SITOP PSU300M/300B
50 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 51
Technical data
6.3 Efficiency
Figure 6-19 6EP1456-3BA00 efficiency
Figure 6-20 6EP1424-3BA00 efficiency
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
51
Page 52
Technical data
6.3 Efficiency
Figure 6-21 6EP1436-3BA20 efficiency
Figure 6-22 6EP1437-3BA20 efficiency
SITOP PSU300M/300B
52 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 53
Technical data
6.4
Closed-loop control
6EP1436-3BA10 (24 V/20 A)
6EP1456-1BA00 (48 V/10 A)
(Ue rated ±15 %), max.
50 to 100 %, typ.
100 to 50 %, typ.
Regulation time / maximum
10 ms
10 ms
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
(Ue rated ±15 %), max.
(Ia: 50/100/50%), Ua ± typ.
50 to 100 %, typ.
100 to 50 %, typ.
Regulation time / maximum
10 ms
10 ms
10 ms

6.4 Closed-loop control

Dyn. line regulation
Dyn. load regulation (Ia: 50/100/50%), Ua ± typ.
Load step regulation time
Load step regulation time
Dyn. line regulation
Dyn. load regulation
Load step regulation time
Load step regulation time
1 % 1 %
2 % 2 %
2 ms 2 ms
2 ms 2 ms
2 % 1 % 1 %
4 % 2 % 3 %
2 ms 2 ms -
2 ms 2 ms -
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
53
Page 54
Technical data
6.5
Protection and monitoring
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
approx. 23 A or "latching shutdown"
approx. 11 A or "latching shutdown"
5 s/min
5 s/min
"latching shutdown"
"latching shutdown"
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
tion
Current limitation, typ.
22 A
19 A
32 A
short-circuit proof
or "latching shutdown"
or "latching shutdown"
or "latching shutdown"
up to 5 s/min
down"
down"
down"

6.5 Protection and monitoring

Output overvoltage protection < 35 V Yes, according to EN 60950 Current limitation, typ. 23 A 11 A Property of the output / short-circuit
proof Short-circuit protection Optional constant current characteristic
Yes Yes
Optional constant current characteristic
Continuous short-circuit current / rms value / typical
Remark
Overload/short-circuit indicator Yellow LED for "overload", red LED for
Output overvoltage protec-
Property of the output /
Short-circuit protection Optional constant current
Continuous short-circuit current / rms value / typical
Remark
< 35 V < 35 V < 35 V
Yes Yes Yes
characteristic approx. 22 A
22 A
Overload capability 150% Ia rated
23 A
Overload capability 150% Ia rated up to
Optional constant current characteristic approx. 19 A
19 A
-
11 A
Overload capability 150% Ia rated up to
Yellow LED for "overload", red LED for
Optional constant current characteristic approx. 32 A
32 A
-
Overload / short-circuit dis­play
SITOP PSU300M/300B
54 Manual, 11.2014, C98130-A7574-A2-2-7629
Yellow LED for "overload", red LED for "latching shut-
Yellow LED for "overload", red LED for "latching shut-
Yellow LED for "overload", red LED for "latching shut-
Page 55
Technical data
6.6
MTBF
6EP1436-3BA10 (24 V/20 A) 6EP1456-3BA00 (48 V/10 A) 6EP1424-3BA00 (12 V/20 A) 6EP1436-3BA20 (24 V/17 A) 6EP1437-3BA20 (24 V / 30 A)
tion
6.7

Mechanical system

6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
Connection system
Screw-type terminal
Screw-type terminal
solid (finely stranded)
solid (finely stranded)
0.2 ... 6 (4) mm² solid (finely stranded)
0.2 ... 6 (4) mm² solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
Width of the housing
70 mm
70 mm
Height of the housing
125 mm
125 mm
Depth of the housing
125 mm
125 mm
Mounting width
70 mm
70 mm
Mounting height
225 mm
225 mm
Weight, approx.
1.2 kg
1.2 kg
one another
ing
EN 60715 35x7,5/15 mounting rails
EN 60715 35x7,5/15 mounting rails

6.6 MTBF

Mean Time Between Failures SN29500: > 500,000 hours (typ. 700,000 hours) at 40 °C, rated load, 24-hour opera-
Connections / line supply L1, L2, L3, PE: 1 screw terminal each
for 0.2 ... 6 (4) mm²
Connections / output +, -: 2 screw terminals each for
Connections / auxiliary contacts 13, 14 (signaling contact): 1 screw
terminal each for 0.14 ... 1.5 mm²
Product feature of the housing / housing that can be lined up next to
Type of mounting / panel mounting No No Type of mounting / rail mounting Yes Yes Type of mounting / S7-300 rail mount-
Mounting Can be snapped onto standard
Yes Yes
No No
L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 6 (4) mm²
+, -: 2 screw terminals each for
13, 14 (signaling contact): 1 screw terminal each for 0.14 ... 1.5 mm²
Can be snapped onto standard
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
55
Page 56
Technical data
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
tact)
solid (finely stranded)
solid (finely stranded)
solid (finely stranded)
Width of the housing
70 mm
70 mm
150 mm
Height of the housing
125 mm
125 mm
125 mm
Depth of the housing
125 mm
125 mm
150 mm
Mounting width
70 mm
70 mm
150 mm
Mounting height
225 mm
225 mm
225 mm
Weight, approx.
1.2 kg
1.2 kg
3.4 kg
lined up next to one another
mounting
mounting
rail mounting
6.7 Mechanical system
Connection system Screw-type terminal Screw-type terminal Screw-type terminal Connections / line supply L1, L2, L3, PE:
1 screw terminal each for
0.2 ... 6 (4) mm²
L1, L2, L3, PE: 1 screw terminal each for
0.2 ... 6 (4) mm²
L1, L2, L3, PE: 1 screw terminal each for
0.2 ... 6 (4) mm²
Connections / output +, -: 2 screw terminals each
for 0.2 ... 6 (4) mm²
Connections/auxiliary con­tacts 13, 14 (signaling con-
Product feature of the hous­ing / housing that can be
Type of mounting / panel
Type of mounting / rail
Type of mounting / S7-300
Mounting Can be snapped onto standard EN 60715 35x7,5/15 mount-
1 screw terminal each for
0.14 ... 1.5 mm²
Yes Yes Yes
No No No
Yes Yes Yes
No No No
ing rails
+, -: 2 screw terminals each for 0.2 ... 6 (4) mm²
1 screw terminal each for
0.14 ... 1.5 mm²
+, -: 2 screw terminals each for 0.5 ... 16 (10) mm²
1 screw terminal each for
0.14 ... 4 (2.5) mm²
Can be snapped onto stand­ard EN 60715 35x15 mount­ing rails
SITOP PSU300M/300B
56 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 57
Technical data
6.8
Accessories
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
module
module
Mechanical accessories
Device identification labels 20 mm × 7 mm, pastel turquoise 3RT1900-1SB20
6.9

Dimension drawing

6.8 Accessories

Electrical accessories Buffer module, redundancy module ­Mechanical accessories Device identification labels 20 mm × 7 mm, pastel turquoise 3RT1900-1SB20
Electrical accessories - Buffer module, redundancy
See Section Dimensions and weight (Page 17)
CAD data that can be downloaded from the Internet:
6EP1436-3BA10 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00459)
6EP1456-3BA00 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00568)
6EP1424-3BA00 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00680)
6EP1436-3BA20 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00724)
6EP1437-3BA20 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00683)
Buffer module, redundancy
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
57
Page 58
Technical data
6.9 Dimension drawing
SITOP PSU300M/300B
58 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 59
7
7.1

Safety

6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A) Primary/secondary galvanic isolation
Yes
Yes
EN 60950-1 and EN 50178
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Degree of protection (EN 60529)
IP 20
IP 20
Leakage current, typ.
0.9 mA
0.9 mA
Leakage current, max.
3.5 mA
3.5 mA
Test voltage
See Table 7-1 Test voltage (Page 60)
See Table 7-1 Test voltage (Page 60)
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
Primary/secondary galvanic isolation
Yes
Yes
Yes
and EN 50178
and EN 50178
and EN 50178
Protection class
Class I
Class I
Class I
Degree of protection (EN 60529)
IP20
IP20
IP20
Leakage current, typ.
0.9 mA
0.9 mA
0.4 mA
Leakage current, max.
3.5 mA
3.5 mA
3.5 mA
voltage (Page 60)
voltage (Page 60)
voltage (Page 60)
Electrical isolation SELV output voltage Ua according to
Electrical isolation SELV output voltage Ua
according to EN 60950-1
Test voltage See Table 7-1 Test
SELV output voltage Ua according to EN 60950-1
See Table 7-1 Test
SELV output voltage Ua according to
SELV output voltage Ua according to EN 60950-1
See Table 7-1 Test
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
59
Page 60
Safety, approvals, EMC
7.2
Test voltage
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
60 s
3000 VAC
1500 VAC
500 VAC
1 s
1500 VAC
1500 VAC
350 VAC
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark: Tripping current for DC measurement: 0 Tripping current for AC measurement: < 100 mA

7.2 Test voltage

Figure 7-1 Test voltage without auxiliary contact diagram
Only the manufacturer can perform the type test and production test; users can also perform the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another
Connect the output terminals and PE together
Test (C)
Connect the output terminals with one another and measure with respect to PE
Table 7- 1 Test voltage
Type test 60 s 4200 VDC 2200 VDC 700 VDC
Production test 1 s 2200 VDC 2200 VDC 500 VDC
Field test
mA
SITOP PSU300M/300B
60 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 61
Safety, approvals, EMC
7.3
Approvals
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01-2007)
CB approval
Yes
Yes
SEMI F47 compliance
Fulfilled
-
Marine approvals
GL, ABS
GL, ABS
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
2006/95/EG)
2006/95/EG)
2006/95/EG)
File E197259
File E197259
File E197259
Marine approvals
-
GL
-
7.4

EMC

6EP1436-3BA10 (24 V / 20 A) 6EP1456-3BA00 (48 V / 10 A) 6EP1424-3BA00 (12 V / 20 A) 6EP1436-3BA20 (24 V / 17 A) 6EP1437-3BA20 (24 V / 30 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
80 … 1000 MHz 25 V/m 1000 … 2700 MHz 10 V/m
turbances (burst)
500 V symmetrical/unsymmetrical at DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 … 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Emitted interference
EN 55022
Class B

7.3 Approvals

CE marking Yes, (2004/108/EG and 2006/95/EG) Yes, (2004/108/EG and 2006/95/EG) UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection EPS 12 ATEX 1 442 X
IECEx EPS 14.0062X II 3G Ex nA nC IIC T4 Gc
CE marking Yes, (2004/108/EG and
UL/cUL (CSA) approval cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
High-speed transient dis-
Surge voltages EN 61000-4-5 3 kV symmetrical at the line connections
EN 61000-4-4 4 kV at line supply connections, 2 kV at the DC output
6 kV unsymmetrical at the line connections
Yes, (2004/108/EG and
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
Yes, (2004/108/EG and
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
61
Page 62
Safety, approvals, EMC
6EP1436-3BA10 (24 V / 20 A) 6EP1456-3BA00 (48 V / 10 A) 6EP1424-3BA00 (12 V / 20 A) 6EP1436-3BA20 (24 V / 17 A) 6EP1437-3BA20 (24 V / 30 A)
EN61000-6-3
Emission for residential areas
7.4 EMC
Line harmonics limit EN 61000-3-2 Class A Generic standards EN61000-6-2 Noise immunity for industrial environments
SITOP PSU300M/300B
62 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 63
8
6EP1436-3BA10 (24 V/20 A) 6EP1424-3BA00 (12 V/20 A) 6EP1436-3BA20 (24 V/17 A) 6EP1437-3BA20 (24 V/30 A)
6EP1456-3BA00 (48 V/10 A)
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Ambient temperature -25°...+70° C with natural convection -10 ...+70° C with natural convection
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage temperature -40 ...+85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Mechanical stressing during operation
Tested according to:
EN 60068-2-6 vibration, test Fc:
0.075 mm deflection in the range 10 ... 58 Hz 1 g acceleration in the range 58 ... 150 Hz
EN 60068-2-27 shock, test Ea: Acceleration 150 m/s2, test duration 11 ms
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
63
Page 64
Ambient conditions
6EP1436-3BA10 (24 V/20 A) 6EP1424-3BA00 (12 V/20 A) 6EP1436-3BA20 (24 V/17 A) 6EP1437-3BA20 (24 V/30 A)
6EP1456-3BA00 (48 V/10 A)
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 ... 795 hPa (-1000 ... +2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5 % / 1000 m or the ambient temperature must be reduced by 5 K / 1000 m (see Figure 4-6 Mounting height derating (Page 23))
Overvoltage category: III to 2000 m (EN 50178) II from 2000 m to 6000 m (EN 50178) II to 2000 m (EN 60950-1) I from 2000 m to 6000 m (EN 60950-1)
Storage:
1080 ... 660 hPa (-1000 ...+3500 m)
SITOP PSU300M/300B
64 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 65
9
9.1

Parallel connection to increase power rating

To increase the power rating, SITOP PSU300M/300B power supplies of the same type can be directly connected in parallel.
The following must be observed:
The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external connection point (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a common switch in the line feeder cable (e.g. with the main switch available in control cabinets).
The output voltages measured in no-load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 50 mV. This usually corresponds to the factory setting. If the output voltage is changed, you should connect the "-" terminals and then, in no-load operation, measure the voltage difference between the "+" terminals that have not yet been connected. The voltage difference should not exceed 50 mV.
Place selector switch A at "ON" (see Section Change-over switch (Page 15))
Figure 9-1 Parallel connection, correct and incorrect
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
65
Page 66
Applications
NOTICE
Protective circuit for the parallel connection of more than two power supplies
9.1 Parallel connection to increase power rating
When connecting more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault. For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-conform circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point.
SITOP PSU300M/300B
66 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 67
Applications
9.2
Parallel connection for redundancy
Note
For a high reliability of the supply, it is recommended that the redundant switched power supplies are fused separately on the li power supply networks.

9.2 Parallel connection for redundancy

Connecting several SITOP PSU300M/300B power supplies in parallel for redundancy purposes is required if especially high demands are placed regarding the availability of a reliable 24 V power supply. Using the SITOP PSE202U redundancy module, two 24 V power supplies of the same type up to 20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies and one SITOP PSE202U redundancy module (Page 67)). When one of the devices fails, then the other automatically takes over the power supply. If one of the power supplies fails, then this is signaled using an LED on the redundancy module as well as an isolated relay contact. For higher output current, each power supply must be connected to a redundancy module (Figure 9-3 Redundant configuration with two power supplies and two SITOP PSE202U redundancy modules (Page 68)).
When dimensioning the system, it must be ensured that n+1 redundant connected power supplies can handle the total power requirement of the remaining n power supplies.
ne-side and, if possible, be connected to different
Figure 9-2 Redundant configuration with two power supplies and one SITOP PSE202U redundancy
module
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
67
Page 68
Applications
9.2 Parallel connection for redundancy
Figure 9-3 Redundant configuration with two power supplies and two SITOP PSE202U redundancy
modules
You can find additional information at:
SITOP PSE202U manual (http://support.automation.siemens.com/WW/view/en/42248598)
SITOP PSU300M/300B
68 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 69
Applications
9.3
Series connection for increased voltage
WARNING
SELV is not guaranteed in the case of a fault

9.3 Series connection for increased voltage

To achieve an output voltage of 48 V DC, two 24 V SITOP PSU300M/300M power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+" terminal of the second power supply. The "+" terminal of the first power supply and the "-" terminal of the second power supply are routed to the load.
Depending on the grounding point of the secondary output voltages, voltages of +48 V, ±24 V or -48 V can be realized.
In the case of an asymmetric load distribution, it is not possible to guarantee correct functionality.
When connecting two power supplies in series, the continuous, permissible SELV voltage of a maximum of 60 V DC according to EN 60950 cannot be guaranteed in the case of a fault.
Figure 9-4 Series connection for increased voltage
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
69
Page 70
Applications
9.4
Overload protection in the 24 V output circuit

9.4 Overload protection in the 24 V output circuit

If an overload occurs, the electronic current limiting function limits the SITOP PSU300M/300B output current to a maximum value (see Section Technical data (Page 39)). The output cables are protected against a thermal overload if they are dimensioned corresponding to the maximum rms output current, or protected using additional components (for example, miniature circuit breaker, fuses).
However, a load circuit that fails as a result of overload, for instance, should frequently be reliably and quickly identified and specifically switched off before the power supply goes into current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for all of the remaining 24 V loads).
The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output current range for each output from 0.5 ... 3 A and 3 ... 10 A) is available; this monitors the 24 V branches for overload and short circuits (Figure 9-5 Selectivity module (Page 70)). Brief current peaks, e.g. as a result of a high inrush current, are permitted, and branches with a longer overload are switched into a no-current condition. This is also ensured for cables in a high-ohmic condition and for short-circuits that slowly develop over time.
When an output fails, the fault is signaled using a group signal contact or as a single channel signal, and the branch of the module involved is displayed using an LED.
For variants with single channel signaling, function blocks for evaluation purposes are available for SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no charge.
You can find additional information at:
SITOP PSE200U selectivity module manuals (http://support.automation.siemens.com/WW/view/en/10807226/130000)
Figure 9-5 Selectivity module
SITOP PSU300M/300B
70 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 71
Applications
9.5
Protection against short-time voltage dips

9.5 Protection against short-time voltage dips

For a drop in the line-side supply voltage, the SITOP PSU300M/300B power supply still maintains the output voltage for a short time in the millisecond range (see Chapter Technical data (Page 39)).
For line supplies that manifest frequent brief voltage dips, in order to increase the power supply reliability, it may make sense to increase the line buffering time in the device using an additional SITOP PSE201U buffer module.
The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in parallel to the 24 V power supply output (Figure 9-6 Buffer module (Page 71)). The buffer time is 200 ms at 40 A up to 1.6 s for a load current of 5 A. This time can be increased a multiple number of times by connecting buffer modules in parallel; the maximum buffer time is 10 s.
You can find additional information at:
SITOP PSE201U manual (http://support.automation.siemens.com/WW/view/en/41129219)
Figure 9-6 Buffer module
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
71
Page 72
Applications
9.6
Protecting against longer power failures

9.6 Protecting against longer power failures

Sudden and longer failures of the line supply voltage can result in undefined states and significant danger as a result of the associated failure of the plant or system control. The SITOP power supply product portfolio includes various DC-UPS solutions to prevent the failure of the 24 V power supply voltage.
Power supply failures up into the minutes range can be buffered using the maintenance-free SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-7 24 V buffering to allow the saving of process data and controlled shutdown of PCs (Page 72)).
Figure 9-7 24 V buffering to allow the saving of process data and controlled shutdown of PCs
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply integrated into PC-based automation solutions. This supports further processing of the status signals and safely running down the PC.
You can find additional information at:
Manual, DC UPS with capacitors (http://support.automation.siemens.com/WW/view/en/48932766/133300)
SITOP PSU300M/300B
72 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 73
Applications
9.6 Protecting against longer power failures
Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the range of hours can be implemented. Intelligent battery management using Energy Storage Link automatically detects the UPS1100 energy storage device, and ensures optimum temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly integrated into the widest range of automation applications with its digital inputs/outputs as well as optional USB interface or Ethernet/PROFINET port.
Figure 9-8 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions,
sensor measured values and position values
For open, PC-based automation systems, configuration and monitoring is realized using the SITOP UPS Manager PC software, which is available at no charge. This allows PC responses to the operating states of the DC UPS to be freely selected – and offers comprehensive diagnostic functions.
For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal. Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 – available at no charge – make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge.
You can find additional information at:
DC UPS SITOP UPS1600/UPS1100 Manual (http://support.automation.siemens.com/WW/view/en/84977415)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
73
Page 74
Applications
9.7
Battery charging with SITOP PSU300B
Note
The value recommended by the battery manufacturer (dependent on the accumulator temperature) must be set as end to 30° C is ideal; in this
13.5 or 27
Note
As protection against back e.m.f. and as polarity reversal protection, we recommend that a suitable diode for at least 1.2 × rated current of the power supply with a voltage is connected in series to the "+" output (connect the anode with "+" output of the SITOP PSU300B and the cathode with the plus pole of the accumulator). The output voltage of the power supply under no load must be set to the e drop at the diode. For an end
VDC (usual for 20° C to 30° C accumulator temperature, although the specifications of the accumulator manufacturer must always be observed!) and 0.8 load should be set to 27.8

9.7 Battery charging with SITOP PSU300B

The SITOP PSU300B power supplies are optimized for charging lead accumulators. For a U­I characteristic curve set to parallel operation (DIP switch "A" at "ON", see Section Figure 2-6 Selector switch (example 6EP1456-3BA00 / 6EP1437-3BA20) (Page 15)), the battery to be charged is charged with a constant current until approximately 95% of the set SITOP output voltage is reached (set using a potentiometer, see Section Figure 2-4 Potentiometer (example 6EP1456-3BA00 / 6EP1437-3BA20) (Page 11)). The charging current then decreases continuously from 1.2 × rated current at 95% of the set voltage to approx. 0 A or the self-discharging current of the accumulator at 100% of the set output voltage, i.e. the resistance characteristic curve in this range (see Figure 6-10 6EP1424-3BA00 parallel operation output characteristic curve (Page 46), Figure 6-11 6EP1436-3BA20 parallel operation output characteristic curve (Page 47), Figure 6-12 6EP1437-3BA20 parallel operation output characteristic curve (Page 47)).
-of-charge voltage. A lead accumulator temperature of +20°
case, the recommended end-of-charge voltage is normally approx.
V.
t least 40 V blocking
nd-of-charge voltage plus the voltage
-of-charge voltage of, for example, 27.0
V voltage drop at the diode, the power supply without
V.
SITOP PSU300M/300B
74 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 75
Applications
Signaling contact 13-14 closed
Signaling contact 13-14 open
WARNING
9.7 Battery charging with SITOP PSU300B
LEDs and a potential-free signaling contact indicate the associated charge state of the battery (see Section Figure 2-5 Operating display and signaling (example 6EP1456­3BA00 / 6EP1437-3BA20) (Page 12)):
Green LED (12 V OK, 24 V OK) lights
Battery voltage > approx. 10 V or > approx. 20 V
Yellow LED (overload) lights
Battery voltage < approx. 10 V or < approx. 20 V
Figure 9-9 Battery charging with SITOP PSU300B
The SITOP PSU300B power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access.
If SITOP is used as the battery charging device, the VDE 0510 regulations or the appropriate national regulations must be observed and an adequate ventilation of the battery location ensured.
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
75
Page 76
Applications
9.7 Battery charging with SITOP PSU300B
SITOP PSU300M/300B
76 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 77
10
Disposal guidelines
The devices are in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse.
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
77
Page 78
Environment
SITOP PSU300M/300B
78 Manual, 11.2014, C98130-A7574-A2-2-7629
Page 79
11
Technical support
Technical documentation on the Internet
SITOP power supply homepage
Information material
CAx data
SITOP Selection Tool
Online catalog and ordering system
Technical support for all IA/DT products can be accessed through the following communication channels:
Phone: + 49 (0) 911 895 7222
E-Mail (mailto:support.automation@siemens.com)
Internet:
Online support request form (http://www.siemens.de/automation/support-request)
Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals)
General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop)
SITOP information can be downloaded from the Internet: Information and download center (http://www.siemens.de/sitop-infomaterial)
2D/3D data and circuit diagram macros can be downloaded from the Internet: Siemens image database (http://www.siemens.de/sitop-cax)
Request all CAx data via the CAx download manager: CAx shopping cart (http://www.siemens.de/cax)
Simply and quickly select the optimum the power supply or DC-UPS: SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool)
The online catalog and the online ordering system are available through the Industry Mall homepage: Industry Mall (http://www.siemens.com/industrymall/de)
SITOP PSU300M/300B Manual, 11.2014, C98130-A7574-A2-2-7629
79
Page 80
Service & Support