Siemens PSR-1 Installation Instructions Manual

Page 1
Installation Instructions
Model PSR-1 Remote Power Supply
PSR-1 Remote Power Supply
INTRODUCTION
The Model PSR-1 from Siemens Industry, Inc., (See Figure 1) is a microprocessor controlled remote power supply and battery charger used with the MXL System. It operates with an MPS-6 or MPS-12 to provide 6 or 12 amps, respectively, of power for various MXL mod­ules.
In addition, the PSR-1 acts as an interface between remote option modules and the MXL when used with a NET-4 plug-in communica­tion module (See Instructions P/N 315-090909) or NET-7 plug-in communication module (See Instructions P/N 315-091914).
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-090911-23
Figure 1
The PSR-1 can also be used to power an MOI/MOD annunciator driver set. In addition, the PSR-1 can be used as an auxiliary power supply in a standalone mode without an MXL.
The PSR-1 has LED status indicators for:
POWER ON, 5V AUX ON, 24V ON, BAT TRBL, TB3 TRBL (Class A power limited output for the CZM-1 and PS-5), GND FAULT, XMIT, ANY TRBL, and ANY ALARM. The PSR-1 has two
relays used for common alarm and common trouble. These relays also can be programmed for local alarm and local trouble using CSG-M.
For additional information on the MXL/MLV System, refer to the MXl/MXLV Manual,
P/N 315-092036.
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
ELECTRICAL CONNECTIONS
Remove all system power before installation, first battery and then AC. (To power up, first
connect the AC and then the battery.)
Primary Power
Primary power for the PSR-1 is provided by the MPS-6 or MPS-12. Both of these mount in the lower right-hand corner of the MXL enclosure. Follow the instructions below for the appropriate power supply.
MPS-6 — Install the MPS-6 (See MPS-6 Instruc- tions, P/N 315-090334). With the AC mains disconnected, connect the MPS-6 power cable to P12 of the PSR-1. Be sure that the jumper
assembly is installed in P10 of the PSR-1. If this jumper is not installed, the PSR-1 will detect a permanent AC fail or indicate auxilia­ry power voltage is low.
Change F2 to a 15A fuse, P/N 105-224090. Change F3 to a 6A fuse, P/N 105-268095.
MPS-12 — Install the MPS-12 (See MPS-12 Instructions, P/N 315-092030). Remove and discard the jumper assembly installed in P10 of the PSR-1. the MPS-12 power cable to P10 of PSR-1.
Disconnect the AC mains. Connect
For NFPA 72 Municipal Tie and 72 Remote Station systems multiply the total system current by 60 and record it at that Total AH
location.
or
For FM Appoved Deluge/PreAction systems multiply the total system current by 90 and record it at that Total AH location.
5. Multiply the AH Total by 1.3 to obtain the final battery amp hour capacity and record it opposite Battery Size.
Three battery models are UL listed for use with the MXL:
BP-61—24V, 15 AH BTX-1—a set of 12V, 31 AH BTX-2—a set of 12V, 55 AH, 65 AH, or 75 AH*
*
Although larger batteries may be used, as noted, the 55 AH capacity must be used for determining battery requirements.
Select the battery that meets or exceeds the final calculated battery amp hour rating. Use an external battery box with the BTX-2 model.
Do not connect the batteries at this time.
Battery Calculations
Battery backup is a requirement for the MXL. To determine the size battery you must use, follow the procedures listed below. The MXL can charge a battery of up to 55 amp hours. A bat­tery size calculation form is provided on page 3.
1. Record all the modules required in the form on the following page.
2. Calculate each row across and place the total in the right column: Total Standby 24 VDC
Module Current
3. Total the right-hand column and record it at the bottom of the form opposite Total
System Current.
4. For NFPA 72 Local and 72 Proprietary systems multiply the total system current by
24 and record it at that Total AH location.
or
Power Supply Load Calculations
To ensure that the power supply is not over­loaded, complete the worksheet on page 4.
1. Enter the quantity of each module in the enclosure.
2. Caclulate both the 24V and 5V loads for each row.
3. Total the Active 24V and Active 5V columns.
4. Ensure that both totals are within the power supply output ratings in the table below.
POWER SUPPLY OUTPUT RATINGS
Active 24 VDC
Module
PSR-1/MPS-6 6 amps 800 mA
PSR-1/MPS-12 12 amps 800 mA
2
Module Curre nt
Active 5 VDC
Module Curre nt
Page 3
NOTES:
1. Use this column for battery size calculations.
2. Power is supplied by a separate UPS.
3. EOL currents included.
4. The following modules draw no 24 VDC current and do not need to be included in the battery calculations:
LLM-1
OMM-1
OMM-2
MOM-4
MOM-2
MMM-1
PLC-4
TBM-2
TSW-2
eludoMytitnauQCDV42ybdnatS
1-RSPAm0900
9215/8215Am0300
1-MCAAm5500
I2-DLA
1-CSAAm2200 2-CSAAm58)3etoNeeS(0 1-CTBAm5400 M/UCCAm05100
003-IMCAm0300
4-MRC
4-MSC
6B1-/1-MZC
4-MZC
PC0032DAm0500
E1-/1-TCDAm05100
1-CMDAm500
D014LEAm00200
6B1-/1-PCIAm01Am5.20
TCADMAm02200
61-DIMAm200
4-/2-BKMAm600
C5-/5-BKMAm00300
C
6-/6-BKMAm00300
61-DOMAm200
7-IOMAm0200
4-TENAm500 7-TENAm0300
M7-TENAm0300 W1-MINAm0600 W1-MIN
M1-MINhtiw
1-CCOAm5100
1-LAP)2etoNe 1-MIPAm5100 2-MIP)2etoNeeS(00
A5-SPdaolV5fo¼+Am0100
7N5-SPdaolV5fo¼+Am5400
2-/F1-/1-CCR
1-ESR,R2-/
/C3-/3-CCR
CF3-/F3-
1-MCRAm00200
1-PERAm0400
1-MMTAm02)3etoNeeS(0
04-PSTAm0700
1-MFVAm010 DELevitcarepAm8
1-ASV
1-MLV/1-MSVAm70 DELevitcarepAm11
1-DLX
03-CAZAm06100
B8-1CZAm2)3etoNeeS(0
BA4-2CZAm2)3etoNeeS(0
B8-2CZAm2)3etoNeeS(0
BA4-3CZAm2)3etoNeeS(0
B8-TCZAm
eS(00
1-MIP
tnerruCeludoM
)1etoNeeS(
Am021
Am5
Am11
Am6
Am83
Am03100
fiAm51+Am55
desusi
Am00300
pAm11+Am7
re
DELevitca
Am022
51)3etoNeeS(0
eR,)B27(eiTlapicinuMAPFN *
SyrettaB
* **
eniLfodnE
eciveD
0
yaler
Am21
Am5
0
00
00
0
0
Am5.1
Am3
spmA24deecxeottonlatoT
spmA21tnerrucmralAmumixaM
tiucriCrePtnerruCdaoL
tnerruCeciveD42ybdn
/ecivedrepAm1.1
sIRTrofAm6.1
evitcarepAm81
ecivedrepAm1.1
tnerruCmetsySlatoT =42xHAlatoT-)D27(yrateirporP,)A27(lacoLAPFN * =06xHAlatoT-)C27(noitatSetom =09xHAlatoT-noitcAerP/eguleDdevorppAMF* =3.1x)**noitcerroCevreseRmralAhtiw(ezi
atSlatoT
tnerruC
3
eludoMCDV
Page 4
NOTES:
1. Use this column to calculate total current from 24 VDC supply to make sure it is not overloaded.
2. Use this column to calculate total current from 5 VDC supply to make sure it is not overloaded.
3. PSR-1 supplies 5V at 800mA, 24V at 6A (MPS-6), 24V at 12A (MPS-12).
4. The following modules draw no current from either the 5 VDC or 24 VDC power supplies and do not need to be included in these calculations:
OMM-1 OMM-2 MOM-2 MOM-4 MMM-1 PAL-1 PIM-2 PLC-4 TBM-2 TSW-2
eludoMytitnauQ
1-RSP
9215/8215Am0400
1-MCAAm58A
I2-DLA
1-CSAAm05Am01
2-CSAAm08Am01
1-CTBAm04Am01
M/UCCAm05100
003-IMC00Am69
4-MRC
4-MSC
6B1-/1-MZCAm0500
4-MZC
PC0032D00Am
E1-/1-TCDAm09100
1-CMD00Am02
6B1-/1-PCI
TCADMAm06200
61-DIMxamAm84Am2
4-/2-BKM00Am57
C5-/-BKMA
C6-/6-BKMAm00300
61-DOMxamAm008Am2
7-IOMAm0Am07
4-TEN00Am02
7-TEN00Am021
M7-TEN00Am021
W1-MINAm0600
htiwW1-MIN
M1-MIN
CCOAm01Am01
1-
1-MIP00Am05
A5-SPdaolV5fo¼+Am0100
7N5-SPdaolV5fo¼+Am5400
2-/F1-/1-CCR
1-ESR,R2-/
3-/3-CCR
/C
CF3-/F3-
1-MCRAm081Am08
1-PERAm0400
1-MMTAm1400
04-PSTAm0700
1-MFV
1-ASV
1-MLV/1-MSV
1-DLX
03-CAZW03taA3Am010
B8-1CZAm571Am5
BA4-2CZA
B8-2CZAm633Am5
BA4-3CZAm062Am5
B8-TCZAm09Am51
deretlifnUCDV03
deifitceRevaWlluF
Am511
)3etoNeeS(
repAm1.1+Am021
rofAm6.1/ecived
sIRT
evitcarepAm81
yaler
xamA5.1+Am07
tiucricrep
Am567
mralanisenoz4
daolecived+A01
).xamA5.1(
m00300
Am03100
Am51+Am56
desusi1-MIPfi
Am00300
repAm8+Am01
DELevitca
repAm11+Am7
ELevitca
D
repAm11+Am7
DELevitca
repAm1.1+Am022
ecived
m062Am01
LATOTLATOT
evitcAlatoT
eludoMCDV42
tnerruC
)1etoNeeS(
Am511
CDV5evitcA
eludoM
nerruC
t
0
)3etoNeeS(
m671
00
Am01
Am01
Am01
002
00
00
00
00
00
00
evitcAlatoT
eludoMCDV5
tnerruC
)2etoNeeS(
0
4
Page 5
SETTING THE OPTION DIPSWITCHES ON SWITCH S2
(See Figure 2)
To Disable the Network (S2-1)
The Disable Network Switch, located at S2-1, enables or disables the network connection.
DISABLE NETWORK SWITCH SETTINGS
S2-1 Network
Open (or OFF) Enabled
Closed (or ON)
*When not connected to the MXL network
Battery Setting (S2-2, -3, and -4)
There is only one allowable battery switch setting as shown in the table below. Be sure to set the PSR-1 battery size in the CSG-M to 31 AH, regardless of the factory battery size.
Disabled*
Figure 2
Switches S1 and S2 on the PSR-1
Security Mode-UL 1076 Operation (S2-5) To Disable the Tamper Switch
The PSR-1 does not support the use of security points from initiating circuits in its enclosure. To disable the tamper switch input of the PSR-1, set the security mode to disabled.
SGNITTESHCTIWSYRETTAB
sehctiwSPID
nepO
)FFOro(
nepO
)FFOro(
desolC
)NOro(
The following table defines the battery voltage thresholds for the listed battery trouble condi­tions. These voltages can be viewed in the TEST POWER menu on the MKB-2 annunciator.
BATTERY VOLTAGE THRESHOLDS
Battery Voltage
Battery Status Conditions
Battery Not Installed <14.0
Charger Disabled <18.3
Battery Low Fault On Battery <21.0
Battery Low Fault On AC <24.0
Battery High Fault >30.0
gnigrahC
tnerruC2-2S3-2S4-2S
spma0.2
xam
(Volts)
The Disable Security Mode switch is located at S2-5.
DISABLE SECURITY MODE SWITCH SETTINGS
S2-5 UL1076
Open (or OFF) Disabled
Input Power Specifications
MPS-6
Input Voltage: 120VAC, +10%, -15% Input Current: 2A max
MPS-12
Input Voltage: 120 VAC, +10%, -15% Input Current: 4A max
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm0
*tnerruCeludoMCDV42evitcAAm511
tnerruCeludoMCDV42ybdnatSAm09
rrucynaedulcnitonseoD*
.1-RSPehtybderewopseludom
5
rosecivedybnwardtne
Page 6
1ELBAT
GNIMMARGORPSSERDDAKROWTEN
RDDA12345678RDDA12345678RDDA12345678RDDA12345678
000
100 200 300 400 500 600 700 800 900 010
110 210 310 410 510 610 710 810 910 020
120 220 320 420 520 620 720 820 920 030
130 230 330 430 530 630 730 830 930 040
140 240 340 440 540 640 740 840 940 050
150 250
0
35 450 550 650 750 850 950 060
160 260 360
LAGELLI LAGELLI LAGELLI
XXOOOOOO OOXOOOOO XOXOOOOO OXXOOOOO XXXOOOOO OOOXOOOO X
OOXOOOO
OXOXOOOO XXOXOOOO OOXXOOOO
XOXXOOOO OXXXOOOO XXXXOOOO
OOOOXOOO
XOOOXOOO OXOOXOOO XXOOXOOO
OO
XOO
OOXOXOOO XOXOXO OXXOXOOO XXXOXOOO OOOXXOOO XOOXXOOO OXOXXOOO XXOXXOOO OOXXXOOO XOXXXOOO OXXXXOOO XXXXXOOO
OOOOOXOO
XOOOOXOO
OOXOO
OXO XXOOOXOO OOXOOXOO XOXOOXOO OXXOOXOO XXXOOXOO OOOXOXOO XOOXOXOO OXOXOXOO XXOXOXOO OOXXOXOO XOXXOXOO OXXXOXOO XXXXOXOO OOOOXXOO XOOOXXOO OXOOXXOO XXOOXXOO OOXOXXOO XOXOXXOO OXXOXXOO XXXOXXOO OOOXXXOO XOOXXXOO OXOXXXOO XXOXX OOXXXXOO XOXXXXOO
OXXXXXOO XXXXXXOO
460 560 660 760 860 960 070 170 270 370 470 570 670 770 870 970 080 180 280 380 480 580 680 780 880 980 090 190 290 390 490 590 690 790 890 990 001 101 201 301 401 501 601 701 801 901 011 111 211 311 411 511 611 711 811
1
91 021 121 221 321 421 521 621 721
XO
)NOro(DESOLC=X)FFOro(NEPO=O
OOOOOOXO XOOOOOXO OXOOOOXO XXOOOOXO OOXOOOXO
XOXOOOXO OXXOOOXO XXXOOOXO OOOXOOXO XOOX
OOXO
OXOXOOXO XXOXOOXO OOXXOOXO XOXXOOXO OXXXOOXO XXXXOOXO OOOOXOXO XOOOXOXO OXOOXOXO XXOOXOXO OOXOXOXO XOXOXOXO
XXOXOXO
O XXXOXOXO OOOXXOXO XOOXXOXO OXOXXOXO XXOXXOXO OOXXXOXO XOXXXOXO
OXXXXOXO XXXXXOXO
OOOOOXXO XOOOOXXO OXOOOX XXOOOXXO OOXOOXXO XOXOOXXO
OXXOOXXO XXXOOXXO
OOOXOXXO XOOXOXXO
OXOXOXXO XXOXOXXO OOXXOXXO XOXXOXXO OXXXOXXO
XOXXO
XXX
OOOOXXXO XOOOXXXO
OXOOXXXO XXOOXXXO OOXOXXXO XOXOXXXO OXXOXXXO XXXOXXXO OOOXXXXO XOOXXXXO OXOXXXXO XXOXXXXO OOXXXXXO XOXXXXXO OXXXXXXO XXXXXXXO
821 921 031 131 231 331 431 531 631 731
X 831 931 041 141 241 341 441 541 641 741 841 941 051 151 251 351 451 551 651 751 851 951 061 161 261 361 461 561 661 761 861 961 071 171 271 371 471 571 671 771 871 971 081 181 281 381
1
48 581 681 781 881 981 091 191
OX
OOOOOOOX XOOOOOOX OXOOOOOX XXOOOOOX OOXOOOOX
XOXOOOOX OXXOOOOX XXXOOOOX OOOXOOOX XOOXOOO OXOXOOOX XXOXOOOX OOXXOOOX XOXXOOOX OXXXOOOX XXXXOOOX OOOOXOOX XOOOXOOX OXOOXOOX XXOOXOOX OOXOXOOX XOXOXOOX
XOOX
OXXO XXXOXOOX OOOXXOOX XOOXXOOX OXOXXOOX XXOXXOOX OOXXXOOX XOXXXOOX
OXXXXOOX XXXXXOOX
OOOOOXOX XOOOOXOX OXOOOXOX
XOOOXOX
X OOXOOXOX XOXOOXOX OXXOOXOX XXXOOXOX OOOXOXOX XOOXOXOX OXOXOXOX XXOXOXOX OOXXOXOX XOXXOXOX
OXXXOXOX XXXXOX
OOOOXXOX XOOOXXOX OXOOXXOX XXOOXXOX OOXOXXOX XOXOXXOX
OXXOXXOX XXXOXXOX
OOOXXXOX XOOXXXOX
OXOXXXOX XXOXXXOX
XXXOX
OOX
XOXXXXOX OXXXXXOX XXXXXXOX
2
291 391 491 591 691 791 891 991 002 102 202 302 402 502 602 702 802 902 012 112 212 312 412
X 512 612 712 812 912 022 122 222 322 422 522 622 722 822 922 032 132 232 332 432 532 632 732 832 932 042 142 242 342 442 542 642 742 842 94 052 152 252 352 452 552
ELLI
OOOOOOXX XOOOOOXX OXOOOOXX XXOOOOXX OOXOOOXX
XOXOOOXX OXXOOOXX XXXOOOXX OOOXOOXX XOOXOOXX OX
OXOOXX
XXOXOOXX OOXXOOXX XOXXOOXX OXXXOOXX XXXXOOXX OOOOXOXX XOOOXOXX OXOOXOXX XXOOXOXX OOXOXOXX XOXOXOXX OXXOXOX XXXOXOXX OOOXXOXX XOOXXOXX OXOXXOXX XXOXXOXX OOXXXOXX XOXXXOXX
OXXXXOXX XXXXXOXX
OOOOOXXX XOOOOXXX OXOOOXXX
OXXX
XXOO OOXOOXXX XOXOOXXX
OXXOOXXX XXXOOXXX
OOOXOXXX XOOXOXXX
OXOXOXXX XXOXOXXX OOXXOXXX XOXXOXXX OXXXOXXX XXXXOXXX
OOOXXXX
O XOOOXXXX
OXOOXXXX XXOOXXXX OOXOXXXX XOXOXXXX OXXOXXXX
XXXOXXXX LAGELLI LAGELLI LAGELLI LAGELLI LAGELLI LAG LAGELLI LAGELLI
6
Page 7
SETTING THE NETWORK ADDRESS (S1)
(See Figure 2)
The PSR-1 occupies one network address in the MXL System. You may have up to 31 PSR-1 power supplies in your system. Regardless of how many PSR-1 power supplies are used, you
MAY NOT exceed 3000 initiating points.
Each PSR-1 must be placed at a unique address in the system. Use the CSG-M print­out to determine the address of the PSR-1. Set the network address on S1 using Table 1.
Note that the PSR-1 network address switch is a 9-position switch. Switch position 9 is not used at this time. Set it to the OFF or Open position.
When used as a standalone power supply, the network address does not need to be set.
Figure 3
Mounting the PSR-1 on the MBR-MP
MOUNTING
Mount the PSR-1 Remote Power Supply on the MBR-MP mounting plate in the MME-3 enclosure as shown in Figure 3.
1. Place the PSR-1 over the four standoffs in the upper left portion of the mounting plate.
2.
Secure it in place using the hardware provided.
MAKING THE NETWORK CONNECTION (TB4)
For the PSR-1 to communicate with the MXL, a NET-4 or NET-7 network interface card must be installed into P7 of the PSR-1. For a NET-4, con-
SET "MMB-3 MNET STYLE 7" TO "NO" IN THE CSGM.
nect the MXL network (MMB) to terminals 1 and 2 of TB4 as indicated in Figure 4. Termi
shield at the MMB only. For a NET-7,
nate the
refer to Figure
2 of the NET-7 Installation Instructions (P/N 315-
091914) and connect the network to terminals 1, 2, 3, and 4. For a NET-7 network connected to an MMB-3, refer to Figure 5. When the PSR-1 is used as a standalone power supply, neither NET-4 nor NET-7 is needed. If an MKB-2 is installed, the NET­7 must be installed in a MOM.
WIRING
Wiring Alarm and Trouble Relays (TB1)
Two relays are provided for local control of alarm and trouble indication. the MXL through CSG-M output logic. The alarm
These relays are controlled
by
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
Figure 4
Network Connection using NET-4
7
RES EOL ASSEMBLY 120 OHMS, 1/4 W, 5% P/N 140-049099
Page 8
RES EOL ASSEMBLY 120 OHMS, 1/4W, 5%
P/N 140-049099
TB4
PSR-1
RES EOL ASSEMBLY 120 OHMS, 1/4W, 5%
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
4
3
N
2
E
1
T
-
7
P/N 140-049099
SET "MMB-3 MNET STYLE 7" TO "YES" IN THE CSGM.
NO EOLR
1
3
2
4
TB1
MOI-7
Connecting a Style 7 Network to MMB-3
relay transfers if the local alarm default signal is activated by an initiating control board (CZM-4 or ALD-2I). This occurs when the initiating board cannot communicate with the MXL. Likewise, if any local module, including the PSR-1, loses communi­cation with the MXL, the trouble relay transfers. When the system is operating normally, these relays are controlled by output logic only. See Figure 6 for ratings and wiring instruction.
Auxiliary Power for CZM-1 and PS-5A (TB3)
A Class A power limited output is provided on TB3, terminals 3-6 for use with the CZM-1 and PS-5A.
1. This power is available on TB3, terminals 3 through 6.
2. All wiring must be in accordance with Article 760 of NEC or local building codes.
3. The power for CZM-1 and PS-5A is power limited to NFPA 70 per NEC 760.
PSR-1
Figure 5
CHASSIS
NET-7
NET-7M
TB4
4
3
2
1
OR
NO EOLR
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION.
6
5
4
3
2
1
TB1
SHIELD
4
3
2
1
RES EOL ASSEMBLY 120 OHMS, 1/4W, 5%
P/N 140-049099
COMMON TROUBLE
RATINGS 2A, 30 VDC RESISTIVE
COMMON ALARM
MMB-3
TB1
Figure 6
Common Alarm and Common Trouble Relays
4. Electrical Ratings:
18-31 VDC, unfiltered full wave 2A max
5. You may connect a maximum of 40 CZM-1s to the TB3 power source. Follow the guide­lines below when wiring.
a. This power may be wired Class A, as
shown in Figure 7. Class A wiring can support a maximum of 20 CZM-1s, with
total line resistance of 4 ohms max.
T-tapping is not allowed.
b. Refer to Figure 8. Class B wiring can be
to obtain the maximum of 40 CZM-1s.
Class B wire run can support a maximum of
Each
used
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR
1
HIGHER, FOR FURTHER INFORMATION.
2
3
4
5
6
TB3
CLASS A WIRING
+
+ _
_
NO T-TAPPING ALLOWED
CZM-1
18-31 VDC 2A MAX POWER LIMITED TO NFPA 70 PER NEC 760 4 OHMS MAX (TOTAL) 18 AWG MIN
POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <30K OHMS FOR TB3, 1-6
Figure 7
CZM-1 Power, Class A Wiring
8
Page 9
20 CZM-1s, 4 ohms max. Multiple Class B power connections can be used if you do not exceed the ratings above (40 CZM-1s max and 4 ohms per run max). For example, you could have four individual Class B power runs, for a total of 40 devices (for example, 12, 8, 6, and 14 CZM-1s), with each of the four runs not exceeding 4 ohms resistance.
T-tapping is allowed, provided the total resis­tance of all wires does not exceed 4 ohms.
6. Refer to Figures 9 and 10 for wiring instruc­tions for the PS-5A.
MOI-7 Power (P9)
The PSR-1 may be used in standalone mode as the power supply for the MOI-7. In this configura­tion the MOI-7 and the PSR-1 must be in the same enclosure. A separate 5V output is provided for the MOI-7. The PSR-1 local trouble contact must also be connected as a means of reporting PSR-1 troubles to the MXL. See Figure 11 for the wiring diagram.
See Figure 12 if the MOI-7 is in a separate enclo­sure. In this configuration do not use the 5V power on P9. A separate PS-5A must be in­cluded
in the remote enclosure with the MOI-7.
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR FURTHER INFORMATION.
1
CZM-1
CLASS B WIRING
CZM-1
CZM-1
TB3
2
3
+
4
_
5
6
T-TAPPING ALLOWED
Figure 8
CZM-1 Power, Class B Wiring
PSR-1
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR
1
HIGHER, FOR FURTHER INFORMATION.
POSITIVE AND NEGATIVE GROUND FAULT
2
DETECTED AT<30K OHMS FOR TB3, 1-6
+
3
+
4
_
5
_
6
DO NOT
TB3
18-31 VDC 2A MAX POWER LIMITED TO NFPA 70 PER NEC 760 4 OHMS MAX PER PAIR (TOTAL) 18 AWG MIN
USE
4321
_
PS-5A
18-31 VDC 2A MAX POWER LIMITED TO NFPA 70 PER NEC 760 4 OHMS MAX PER PAIR (TOTAL) 18 AWG MIN
POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <30K OHMS FOR TB3, 1-6
DO NOT USE
+
seciveDelbitapmoC
6B1-MZC7-553590-513N/P
6B-PC
I8-603590-513N/P
61-DOM7-038090-513N/P
7-IOM7-997290-513N/P
A5-SP8-763290-513N/P
7N5-SP21-927290-513N/P
KM3-727840-513N/P
C5-/5-B
C6-/6-BKM4-227840-513N/P
CF3-/C-/F3-/3-CCR5-566840-513N/P
thginKtneliS
9215/8215
53-RS8-196780-513N/P
D4-/D3-/D2-HDS
D8-/D7-/D6-/D5-/
§
1-SN
§
REWOPV42YRAILIXUA SECIVEDELBITAPMOC
noitallatsnI
PS-5A Power, Class A Wiring
Figure 9
snoitcurtsnI
PSR-1
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR
1
HIGHER, FOR FURTHER INFORMATION.
POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT<30K OHMS FOR TB3, 1-6
2
3
+
4
_
5
6
DO NOT
TB3
13N/P
5-492390-5
18-31 VDC 2A MAX POWER LIMITED TO NFPA 70 PER NEC 760 4 OHMS MAX PER PAIR (TOTAL) 18 AWG MIN
USE
4321
_
+
PS-5A
DO NOT USE
3-184940-513N/P
3-904580-513N/P
noitidEht8468LUrepdetsiL
PS-5A Power, Class B Wiring
Figure 10
9
Page 10
Figure 11
MOI-7 Connection
(in Same Enclosure)
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <30K OHMS FOR TB3, 1-6
TB3
PSR-1
65
4321
CZM-1B6 AND PS-5A POWER
18 AWG MIN 4 OHMS MAX
NETWORK NETWORK
_
TB1
PS-5A
TB4
4
3
2
1
18 AWG MIN
23
14
TB1
+
P1
1234
MOI-7 MOD-16 MOD-16 MOD-16
J3
SYSTEM 3 ENCLOSURE
(OR EQUIVALENT) MOUNTING
MOM-4 Module Connection
P6 on the PSR-1 is the data and 5V connection for the MOM-4. Connect P6 on the PSR-1 to P7 on the MOM-4 using the 8 circuit ribbon cable, P/N 555-190506, provided with the MOM-4. A second auxiliary non-power limited output is provided on TB3 for the MOM-4 card cage. This output is rated at 6 amps (MPS-6) or 12 amps (MPS-12) 18-31 VDC. This capacity must be
Figure 12
MOI-7 Connection
(in Remote Enclosure using PS-5A)
TO MXL NETWORK
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL
MID-16
WIRING INFORMATION.
derated by the current drawn by the CZM-1 and PS-5A power output. If the full 2 amp capacity of the CZM-1 and PS-5A output is used, the MOM-4 power must be derated to 4 amps (MPS-6) or 10 amps (MPS-12). See Figure 13 for wiring instruc­tions.
When a PSR-1 is used with an MKB-2, use a MOM­4 for the NET-7. Connect as shown in Figure 14.
10
Page 11
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
Figure 14
Connecting a NET-7
in a MOM-4
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <30K OHMS FOR TB3, 1-6
Figure 13
MOM-4 Connection
OMM-1 Module Connection
When using the PSR with voice modules, connect TB3-1 and TB3-2 on PSR to TB1 at the top of the OMM-1 on the far left. See Figure 15. Refer to the OMM-1 Instructions, P/N 315­090267 for further information.
When using the PSR with both OMM-1s and MOM-4s, connect as shown in Figure 16.
11
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.
Figure 15
OMM-1 Connection
Page 12
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS,
P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMA-
TION.
Figure 16
Connecting OMM-1s and MOM-4s with a PSR-1
POSITIVE AND NEGATIVE GROUND FAULT
DETECTED AT <30K OHMS FOR TB3, 1-6
P/N 315-090911-23
Loading...