Siemens OpenAir GDE132.1P, OpenAir GLB, OpenAir GDE131.1P, OpenAir GDE136.1P, OpenAir GDE131.1P/B Technical Instructions

...
Technical Instructions
Document No. 155-188P25
EA GDE/GLB-2
December 26, 2007
GDE/GLB Series Non-spring Return Rotary 24 Vac Floating Control
Description
Features
Application
Product Numbers
Torque Standard
GDE131.1U GDE131.1U/B (24 pk)
GDE131.1P
GDE131.1P/B (24 pk)
44 lb-in
(5 Nm)
88 lb-in
(10 Nm)
GDE131.1Q GDE131.1Q/B (12 pk) GDE131.1N GDE131.1N/B (24 pk)
GDE131.1T GDE131.1T/B (24 pk) GLB131.1P GLB131.1Q
OpenAir direct coupled 24 Vac non-spring return rotary electric actuators are designed for floating control of dampers.
Compact, lightweight design
Manual override
Standard and plenum models available
Feedback potentiometer models available
cUL and UL listed, CE certified
Independently adjustable dual auxiliary switches available
These actuators are used in constant or variable air volume installations for control of HVAC dampers requiring up to 44 lb-in (5 Nm) or 88 lb-in (10 Nm) of torque.
Table 1.
With
Potentiometer
— — — —
GDE132.1P GDE136.1P
— — — — — — — — — —
— — — — —
GLB132.1P GLB136.1P Plenum
6 ft length
Dual Auxiliary
Switches Only
Pre-Cabled No Cables
Standard
Plenum
6 ft length
Post Header AMP
Terminal Strip
— —
— — —
— —
Siemens Building Technologies, Inc.
Technical Instructions OpenAir Non-Spring Return Rotary Electric Damper Actuator Document No. 155-188P25 December 26, 2007
24 Vac Floating Control
Specifications
Operating voltage (G–Y1 or G–Y2) 24 Vac +20%, -15% Frequency 50/60 Hz
Power supply Equipment rating
Power consumption 2.3 VA Rating Class 2 according to UL, CSA Class III per EN60730
Auxiliary features
Feedback potentiometer (GDE/GLB132.1P) Sliding contact (P2) 0 to 1000 ohm < 10 mA Load < 1W Voltage UL-Class 2 (SELV/PELV for CE) < 24 Vac/dc Dual auxiliary switch contact rating AC Rating 24 Vac/24 Vdc 4A resistive, 2A inductive DC Rating 12 to 30 Vdc DC 2A Switch Range Switch A 0° to 90° with 5° intervals Recommended range usage 0° to 45° Factory setting Switch B 0° to 90° with 5° intervals Recommended range usage 45° to 90° Factory setting 85° Switching hysteresis
Function
Torque GDE 44 lb-in (5 Nm) GLB 88 lb-in (10 Nm) Runtime for 90° opening or closing
GDE 90 sec. at 60 Hz (108 sec. at 50 Hz) GLB 125 sec. at 60 Hz (150 sec. at 50 Hz) Nominal angle of rotation 90° Maximum angular rotation 95°
Mounting
Shaft size: Minimum shaft length 3/4 inch (20 mm)
3/8 to 5/8 inch
EA1010R1
8 -16 mm
Housing
Enclosure NEMA Type 2 IP54 according to EN60529
GDE131.1N and GDE 131.1T NEMA1 Material Durable plastic Gear lubrication Silicone-free
Page 2 Siemens Building Technologies, Inc.
1/4 to 1/2 inch
6 - 12.7 mm
Figure 1. Acceptable Shaft Sizes.
9/16 inch
15 mm
OpenAir Non-Spring Return Rotary Electric Damper Actuator Technical Instructions 24 Vac Floating Control Document No. 155-188P25 December 26, 2007
Specifications, Continued
Ambient conditions
Agency certification
Conformity for Plenum Models
Miscellaneous
Accessories
Ambient temperature operation -25°F to 130°F (-32°C to 55°C)
storage and transport -40°F to 158°F (-40°C to 70°C) Ambient humidity (non-condensing) 95% RH UL listed to UL873 cUL certified to Canadian Standard
C22.2 No. 24-93 In accordance with the directive set forth by the European Union for Electromagnetic Compatibility (EMC) 89/336/EEC Emissions standards EN 50081-1 Immunity standards EN 50082-2 Pre-cabled connection 18 AWG Standard cable length 3 feet (0.9m)
Life cycle: Designed for over 60,000 full strokes and a minimum of 1.5 million repositions at rated torque and temperature
Dimensions 6.2" L × 2.8" W × 2.4" D× 2.4" D (157 mm L × 71 mm W × 61 mm D)
Weight 1.06 lb. (0.48 kg) NOTE: Neither the auxiliary switches nor feedback potentiometer can be added in
the field. Order the product number that includes these options. See Table 1.
EA0695R1
ASK71.5 Allows a direct-coupled actuator to provide an auxiliary linear drive.
Figure 2. Rotary to Linear.
Ea0696R1
Figure 3.
Rotary to Linear
with Bracket.
ASK71.6 Allows economical mounting of an OpenAir
actuator to a variety of surfaces. Should be used in applications where the actuator can be rigid-surface mounted and a linear stroke output is needed.
ASK76.1U Provides the connection between the actuator and conduit.
NOTE: GDE131.1T and GDE131.1N are not
compatible with the ASK76.1U.
Figure 4.
EA0647R1
Conduit Adapter.
Siemens Building Technologies, Inc. Page 3
Technical Instructions OpenAir Non-Spring Return Rotary Electric Damper Actuator Document No. 155-188P25
24 Vac Floating Control
December 26, 2007
Accessories, Continued
Actuator Components
EA0807R1
Figure 5.
EA1060R1
Shaft Insert.
Figure 6. Shaft Guide Insert.
EA1246R1
Figure 7.
EA1251R1
Figure 8.
EA1248R1
Figure 9.
1
11
Terminal Plug
(To TEC)
ASK78.3U Shaft insert for use with 3/8-inch (8
to 10 mm) diameter shafts. (Included in box with GDE/GLB Series). (Pkg/10)
NOTE: Factory installed 1/2-inch guide must
be removed prior to installation.
985-101P25 –Shaft guide insert, 1/2 inch 25 Pk
(Factory installed with GDE/GLB Series).
985-132: Floating input cable for use only with the
Siemens Building Technologies, Inc. Terminal Equipment Controller (TEC), 3 ft, 12 pk.
985-131: Floating input cable; 3 ft, 12 pk.
985-134: Daisy chain cable 12 ft, 12 pk. 985-135: Daisy chain cable 25 ft, 12 pk.
Legend
12
1. Base plate
2
EA0642R3
A B
80 70 60
Aux Switch Adjustment
2010
50
90
45
90
34
Figure 10. Parts of the Actuator.
10
8,9
2. Positioning scale for angle of rotation
3. Connection cables
4. Connection cables
7
6
5. Manual override
6. Coupling bushing
7. Factory installed 1/2-inch guide
5
8. Auxiliary switch A
9. Auxiliary switch B
10. Position indicator
11. Adjustment lever with locking
13
screw (4 mm hex)
12. Set screw for mechanical range stop (4 mm hex)
13. Mounting bracket
Page 4 Siemens Building Technologies, Inc.
OpenAir Non-Spring Return Rotary Electric Damper Actuator Technical Instructions 24 Vac Floating Control Document No. 155-188P25 December 26, 2007
Actuator Components, Continued
Terminal Strip
Post Header AMP
EA1094R1
GDE131.1N
EA1240R1
GDE131.1T
The GDE131.1T uses a Terminal Strip connection for connection purposes rather than the cable connection.
GDE131.1T
NOTE: Wires are supplied by the
customer.
CW
Supply 24Vac
CCW
Figure 11.
GDE131.1N
The GDE131.1N model uses a Post Header for connection purposes rather than cable connections.
The Post Header has two identical
Y1
G Y2 Y1
G Y2
Input (Output) Output (Input)
Figure 12.
sets of contacts. NOTE: Cables are purchased
separately. See Accessories.