Installation Instructions
OpenAir™ Electronic Fusible Link
Used with Siemens Fire and Smoke
WARNING:
CAUTION:
Damper Actuators
Docume nt No. A6V1 1200850
May 1, 2018
Product Description
The Electronic Fusible Link (EFL) is a heat responsive device used with the Siemens OpenAir™ UL listed fire and smoke control damper actuator.
Upon approaching the temperature rating of the EF L model ordered and i nstalled, the EFL cuts power to the electronic damper actuator and the actuator’s spring return mechanism closes the damper.
NOTE: The EFL must be factory-installed. The UL
rating carri ed by the specif ic damper and actuator is assigned as an assembly and cannot be added in the field.
Replacement EFLs may be field-installed wit h l ocal authority approval.
Contents
Electronic Fusible Link
Two 1.5-inch (38.1 mm) No. 8 pan head self -drilling
screws
Product Numbers
ASK791.165 165°F (74°C) ASK791.212 212°F (100°C) ASK791.250 250°F (121°C) ASK791.350 350°F (177°C)
Requir ed Tools
1-3/8-inch (35 mm) drill or hole punch
No. 2 Phillips bit
Expected Installation Time
15 minutes
Prerequisites
Appropriate OpenAir GJD, GRD, GKD, or GVD series damper actuator.
Operation
When the EFL detects that its temperature rating is being approached, t he power to the electronic damper actuator is shut off and the spring mechanism closes the damper.
NOTE: Depending on the application envi ronment, the
EFL may trip before the listed temperature rating.
The manual override reset button (see Figure 1) on the EFL can be pressed when the temperature has cool ed below the EFL setpoi nt. The EFL device will again be operational .
NOTE: The EFL is compati ble only with OpenAir GJD,
GRD, GKD, or GVD fire and smoke damper
actuators.
Warning/Caution Notations
Personal injury or l oss of life may occur if you do not follow the procedu res as specified. Equipm ent damage m ay oc cur if you do not follow the procedures as specified.
Figure 1. Parts Description.
Document No. A6V1120085 0
CAUTION:
Installation Instructions May 1, 2018
Operation, Continued
CAUTION:
Before resetting any sensor, carefully inspect the damper, damper actuator, and sensor. Verify whether or not local authorities or building managers must be contacted.
Damage to the temperature sensor will result in loss of damper control.
WARNING:
Before attempting to reset the EFL by pressing the Override/reset button, take the precaution to protect exposed skin as the EFL will be extremely hot to the touch.
Installation
NOTE: Notice the position of the top clip before
attempting to couple the actuator with the EFL sensor.
Figure 3. Proper Clip Positioning.
Internal Mounting
For internal mounting, the reset button must protrude through a 3/8-inch (9.5 mm) diameter relief hole providing operator access for resetting t he EF L.
Figure 2. The EFL and OpenAir Fire and Smoke Damper
Actuator.
WARNING:
The internal/external mounting orientation or position in the duct will affect the time and/or temperature the EFL requires to switch.
Failure to provide a relief hole will keep the reset button pressed against the duct wall or damper sleeve, and the EFL will fail to operate as intended.
Page 2 of 4 Siemens Industry, Inc.