Siemens OLM/P11 V4.0, OLM/G12 V4.0, OLM/G11-1300 V4.0, OLM/P12 V4.0, OLM/G12-1300 V4.0 Operating Instructions Manual

...
Preface
1
Introduction
2
Network Topologies
3
Product Characteristics
4
5
Approvals and Marks
6
References
7
Drawings
8
SIMATIC NET PROFIBUS Optical Link Module OLM / P11 V4.0 OLM / P12 V4.0 OLM / P11 V4.0 OLM / G12 V4.0 OLM / G12-EEC V4.0 OLM / G11-1300 V4.0 OLM / G12-1300 V4.0
Operating Instructions
07/2008
A2B00065774O, Edition V1.5
Copyright Siemens AG 2008. All rights reserved. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility or design, are reserved.
Disclaimer We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions.
Siemens AG Automation and Drives Postfach 4848, D-90327 Nürnberg
Siemens AG 2008 Subject to technical change
Siemens Aktiengesellschaft A2B00065774O, Edition V1.5
Safety Guidelines
These operating instructions contain notices which you should observe to ensure your own personal safety as well as to avoid property damage. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring to property damage only have no safety alert symbol. Depending on the danger level, the notices are displayed in descending order as follows.
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
with safety alert symbol indicates that minor personal injury can result if proper precautions are not taken.
Caution
without safety alert symbol indicates that property damage can result if proper precautions are not taken.
Notice
used without the safety alert symbol indicates a potential situation which, if not avoided, may result in an undesirable result or state.
When several danger levels apply, the notices of the highest level (lower number) are always displayed. If a notice refers to personal damages with the safety alert symbol, then another notice may be added warning of property damage.
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
iii
Qualified Personnel
The device/system may only be set up and operated in conjunction with this documentation. Only qualified personnel should be allowed to install and work on the equipment. Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards.
Correct Usage of Hardware Products
Please note the following:
Warning
This device may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.
Note: If PROFIBUS OLMs are supplied via long 24 V supply lines or over networks, measures must be taken to prevent interference by strong electro magnetic pulses on the supply lines. These can occur, for example, due to lightning strikes or when heavy inductive loads are switched. The robustness of the PROFIBUS OLM against electromagnetic interference was verified by the Surge Immunity Test according to EN61000-4-5. For this test, overvoltage protection for the voltage supply lines is necessary. The Dehn Blitzductor VT AD 24V Type no. 918402 or a comparable protection element is, for example, suitable. Manufacturer: DEHN+SÖHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt, Germany
Brands
All names which are labeled with the trademark symbol ® are registered trademarks of Siemens AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners.
SIMATIC NET PROFIBUS, Optical Link Module
iv Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
1
Preface ...................................................................................................................................................... 1
1.1 Preface...........................................................................................................................................1
2 Introduction................................................................................................................................................ 3
2.1 Introduction ....................................................................................................................................3
3 Network Topologies................................................................................................................................... 7
3.1 Linear (bus) Topology ....................................................................................................................8
3.1.1 Linear (bus) topology with fiber-optic link monitoring and segmentation.......................................9
3.1.2 Bus topology without fiber-optic link monitoring.............................................................................9
3.2 Star Topology...............................................................................................................................10
3.3 Ring Topology..............................................................................................................................12
3.3.1 Redundant Optical Ring with two OLMs ......................................................................................14
4 Product Characteristics............................................................................................................................ 17
4.1 Technical Specifications ..............................................................................................................17
4.2 Installation ....................................................................................................................................20
4.2.1 Safety related notices ..................................................................................................................20
4.2.2 General information on commissioning .......................................................................................21
4.2.3 Setting compatibility, mode and transmit power ..........................................................................22
5 Installation and Maintenance ................................................................................................................... 27
5.1 Installation ....................................................................................................................................27
5.1.1 Installation instructions.................................................................................................................27
5.1.2 Connecting optical cables ............................................................................................................30
5.2 Installation of the Modules ...........................................................................................................31
5.3 Connection of the Electrical RS-485 Bus Cables ........................................................................33
5.4 Connecting of the Operating Power Supply.................................................................................35
5.5 Connecting the Signaling Contact Wires .....................................................................................35
5.6 Receive Level of the Optical Channels........................................................................................36
5.7 LED Displays and Troubleshooting .............................................................................................37
5.7.1 LED displays ................................................................................................................................37
5.7.2 Troubleshooting ...........................................................................................................................39
5.8 Maintenance.................................................................................................................................41
5.9 Cleaning .......................................................................................................................................41
5.10 Configuration................................................................................................................................42
5.10.1 Configuring optical bus and star topologies.................................................................................42
5.10.2 Configuring redundant optical rings .............................................................................................42
6 Approvals and Marks............................................................................................................................... 45
6.1 CE Mark .......................................................................................................................................45
6.2 c-tick.............................................................................................................................................46
6.3 FM approval ................................................................................................................... ..............47
Contents
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
v
6.4 Ex approval ..................................................................................................................................47
6.5 UL approval (U.S. and Canada)...................................................................................................47
6.6 Shipbuilding approvals.................................................................................................................48
7 References .............................................................................................................................................. 49
7.1 References..................................................... ..............................................................................49
8 Drawings.................................................................................................................................................. 51
Tables
Table 2-1
Number of electrical and optical ports per module, .......................................................................4
Table 4-1 Overview of the product characteristics .......................................................................................19
Table 4-2 DIL-switches in compatibility mode..............................................................................................23
Table 5-1 Meaning of the LED displays and indication by the signaling contact.........................................39
Table 5-2 Constants for calculating the slot time for DP-standard (redundant optical ring) ........................43
Table 5-3 Constants for calculating the slot time for DP/FMS (”universal“) and DP with S5 95U (redundant
optical ring)...................................................................................................................................43
Figures
Figure 2-1
PROFIBUS OLM with position of all interfaces, displays and adjustment options ........................3
Figure 3-1 Network structure in a linear (bus) optical topology.......................................................................8
Figure 3-2 Network structure with an optical star topology ...........................................................................10
Figure 3-3 Network structure with a redundant optical ring topology............................................................12
Figure 4-1 View of the OLM module from the top .........................................................................................21
Figure 5-1 Measures to suppress..................................................................................................................27
Figure 5-2 Securing shielded cables with cable clamps and cable retainers...............................................28
Figure 5-3 View of the module from below....................................................................................................30
Figure 5-4 Installation of a module on a standard DIN rail............................................................................31
Figure 5-5 Installation of a module with a mounting plate.............................................................................32
Figure 5-6 Drilling measures for the mounting plate, all dimensions are millimeter......................................33
Figure 5-7 Electrical port, connector assignment D-sub jack.......................................................................33
Figure 5-8 Operating power supply, pin assignment 5-pin terminal block ..................................................35
Figure 5-9 Signaling contact relay with floating contacts; ............................................................................35
Figure 5-10 Signaling contact, pin assignment 5 pin terminal block.............................................................35
Figure 5-11 Position of the level recording connections ................................................................................36
Figure 5-12 Relationship between measured output voltage and signal quality.............................................36
SIMATIC NET PROFIBUS, Optical Link Module
vi Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
Figure 5-13 LED displays on the front panel...................................................................................................37
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
1
1 Preface
1
1.1 Preface
Purpose of the operating instructions
These operating instructions support you when commissioning PROFIBUS OLM devices (Optical Link Module)
Validity of these operating instructions
These operating instructions are valid for the following devices:
SIMATIC NET OLM/P11 V4.0 6GK1 503-2CA00
SIMATIC NET OLM/P12 V4.0 6GK1 503-3CA00
SIMATIC NET OLM/G11 V4.0 6GK1 503-2CB00
SIMATIC NET OLM/G12 V4.0 6GK1 503-3CB00
SIMATIC NET OLM/G12-EEC V4.0 6GK1 503-3CD00
SIMATIC NET OLM/G11-1300 V4.0 6GK1 503-2CC00
SIMATIC NET OLM/G12-1300 V4.0 6GK1 503-3CC00
Convention
G 1 -1300
G glass fiber P plastic fiber
OLM/ 2
Number of RS-485 interfaces
optional: wavelength
Number of optical interfaces
Preface
1.1 Preface
SIMATIC NET PROFIBUS, Optical Link Module
2 Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
Further documentation
You will find more information on other SIMATIC NET products that you can use with the OLM V4.0 devices in the SIMATIC NET PROFIBUS networks SIEMENS AG” manual.
Finding information
To help you find the information you require more quickly, the manual includes not only the table of contents but also the following sections in the Appendix:
Glossary
Index
Audience
These operating instructions are intended for persons involved in the commissioning of PROFIBUS networks with the link modules of the OLM V4.0 series.
Standards and approvals
The devices of the OLM V4.0 series meet the requirements for the CE mark. For detailed information, please refer to chapter 6 of these operating instructions.
The devices of the OLM V4.0 series also meet the requirements for the UL, C-Tick, FM and ATEX marks. For detailed information please refer to chapter 6 of these operating instructions.
The devices of the OLM V4.0 series also meet several requirements for shipbuilding. For the respectively valid approvals call our hotline +49-18050500222.
Furthermore you can gather information at:
http://support.automation.siemens.com
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
3
2 Introduction
2
2.1 Introduction
This section provides you with an overview of the functions of the PROFIBUS OLM4.0 product family.
What is possible?
PROFIBUS OLMs are designed for use in optical PROFIBUS fieldbus networks. They allow the conversion of electrical PROFIBUS interfaces (RS-485 level) into optical PROFIBUS interfaces and vice versa. The modules can be integrated in existing PROFIBUS fieldbus networks with the known advantages of optical transmission technology. A complete PROFIBUS fieldbus network can also be set up with modules in a linear (bus), star or ring topology as well as any combination of these topologies. To increase the reliability of the fieldbus network in case of failure, the redundant ring is supported.
Figure 2-1 PROFIBUS OLM with position of all interfaces, displays and adjustment options
LED displays
Channel 1 RS-485
DIL switch fo
r
modes
Operating voltage
Signaling contact
Sockets for measuring levels of the optical interfaces (see section 5.6).
Channel 2 Channel 3 Optical channels
Introduction
2.1 Introduction
SIMATIC NET PROFIBUS, Optical Link Module
4 Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
Every module has two (OLM P11, G11) or three (OLM P12, G12) independent channels (ports) that consist of transmitter and receiver pairs. The power supply voltage for operation is 24 V DC. To increase operational reliability, a redundant power supply is possible.
The electrical channel is designed as 9-pin D-sub socket. An RS-485 bus segment complying with PROFIBUS standard EN 50170 /2/ can be connected to this channel. The fiber-optic cables are connected via BFOC
1
/2.5 connectors.
Six multicolor LEDs indicate the current mode and any disruptions as well as the level ratios on the optical interfaces.
Table 2-1 shows the different connection options of the modules and the maximum possible optical range of the single channels.
OLM/ P11 P12 G11 G12
G12-EEC
G11-1300 G12-1300
Number of channels
-electrical
-optical
1
1
1
2
1
1
1
2
1
1
1
2
Fiber types that can be used
- plastic fiber-optic cables
980/1000 µm
- PCF fiber-optic cables
(HCS
®
)
200/230 µm
- silica glass fiber-optic cables
10/125 µm (9/125µm)
50/125 µm
62.5/125 µm
80 m
400 m
-
-
-
80 m
400 m
-
-
-
-
-
-
3 km
3 km
-
-
-
3 km
3 km
-
-
15 km
10 km
10 km
-
-
15 km
10 km
10 km
Table 2-1 Number of electrical and optical ports per module, usable fiber types, as well as maximum achievable fiber-optic cable distances between the modules.
See the Technical Data for precise conditions of use. PCF stands for Polymer Cladded Fiber and is similar to HCS
®
2.
There is a measurement output available for every channel, at which the optical input level can be measured with a standard voltmeter.
The various error and disruption messages of the OLM are available as a group signal via a signaling contact (relay with floating contacts) for further processing. The individual modes as well as error/fault messages are displayed by several multicolor LEDs on the front panel of the device (see section 5.7.1).
The mechanical design consists of a compact and stable metal housing which can be mounted either on a DIN rail or on a mounting plate.
The modules are configured using switches that are easily accessible from the outside.
1
BFOC stands for Bayonet Fiber Optic Connector.
This type of connector is functionally compatible with ST connectors. ST is a registered trademark of the company AT&T.
2
HCS
®
is a trademark of Ensign-Bickford Optics Company.
Introduction
2.1 Introduction
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
5
The PROFIBUS OLMs comply with the standard EN 50170 /2/ and with the technical guideline Optical transmission technology for PROFIBUS published by the PROFIBUS User Organization (PNO).
OLM/G12 and OLM/G12-EEC have the same functions. They only differ in the specification of the ambient climatic conditions: the OLM/G12 is suitable for use in the standard temperature range from 0 °C to 60 °C, whereas the OLM/G12-EEC (extended environmental conditions) can be used in the extended temperature range of -25 °C to +60 °C and up to 100% humidity (condensing).
Network Topologies
2.1 Introduction
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
7
3 Network Topologies
3
Which network topologies can be implemented?
The following network topologies can be implemented with the PROFIBUS OLM:
Point-to-point connection
Bus (linear) topology
Star topology
Redundant optical ring
Combinations of these basic types are also possible. To set up the fiber-optic links of these network topologies, cables with two optical fibers are used.
If a high degree of availability is required of the fieldbus network, this can be increased by using a redundant network configuration, for example to allow continued communication if a cable is broken.
Please note the following:
¾ Single DTEs or complete PROFIBUS segments with a maximum of 31 nodes
can be connected to the electrical interface of the PROFIBUS OLM.
¾ Use only fiber-optic cables in areas subject to heavy noise to avoid EMC
problems affecting the entire network.
¾ Only OLMs of the same wavelength may be connected to each other optically:
– OLM/P11 and OLM/P12 with each other
– OLM/G11 and OLM/G12 as well as OLM/G12 EEC with each other
– OLM/G11-1300 and OLM/G12-1300 with each other
¾ Optical channels connected via fiber-optic cables must be set to the same mode.
¾ Transitions between different OLM types are only possible via the RS-485
interface.
¾ In the network topologies described below, the OLM/G12-EEC can be used
everywhere where an OLM/G12 can be used.
Network Topologies
3.1 Linear (bus) Topology
SIMATIC NET PROFIBUS, Optical Link Module
8 Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
3.1 Linear (bus) Topology
Figure 3-1 Network structure in a linear (bus) optical topology
In a linear or bus structure, the single PROFIBUS OLMs are connected by two-fiber cables. At the beginning and at the end of a line, modules with one optical channel are adequate, in-between modules with two optical channels are necessary.
If single point-to-point connections are required, they can be implemented with modules with one optical channel each.
The bus topology can be implemented with and without fiber-optic link monitoring. Fiber-optic link monitoring is recommended in homogeneous OLM networks (factory default).
Please note that to ensure correct operation, the following conditions must be kept to when configuring the network:
¾ The parameter MIN TSDR, described in the PROFIBUS standard EN 50170 /2/,
must be set to a value 11 on all DTEs. This is usually the case but should be checked if permanent communication problems occur.
¾ Choose bus node addresses as low as possible when configuring your network,
to reduce master timeouts that may occur due to disruptions.
You will find information on changing the setting in the documentation supplied by the manufacturer of your DTE.
Ch 1
Ch 2
SE
OLM/P11
OLM/G11(-1300)
Ch 1
Ch 2
SE
OLM/P11
OLM/G11(-1300)
Ch 1
Ch 2 SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
Ch 1
Ch 2
SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
FOC
RS-485
Network Topologies
3.1 Linear (bus) Topology
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
9
3.1.1 Linear (bus) topology with fiber-optic link monitoring and segmentation
Use this mode especially when you want a disrupted fiber-optic cable segment to be separated from the rest of the network (see section 4.2.2.4). Only use this mode, if you only connect PROFIBUS OLM V4.0 or V3/V4.0 with each other.
Monitoring mechanisms:
Send echo: yes
Monitor echo: yes
Suppress echo: yes
Monitor: yes
Segmentation: yes
In this mode, the individual fiber-optic links are monitored by the two connected modules.
If a module fails or a fiber-optic cable breaks or disturbances are detected on the optical transmission line, the fiber-optic link between the two OLMs is interrupted (segmented). The PROFIBUS network is separated into two (sub)networks each remaining functional on its own. The problem is indicated by the channel LEDs changing to red and by the signaling contacts of the two OLMs connected to the disturbed fiber-optic link. The segmentation is canceled automatically as soon as both modules recognize that the segmented fieldbus (sub)network is no longer disrupted based on test frames that they send out automatically. Note that if a problem occurs in networks with several active bus nodes, two logical token rings are formed. As a result, temporary network disturbances may occur due to double tokens or frame collisions when the full network is restored.
Note:
If modules with two optical channels are used at the end of a line, the unused optical channel must be set to the mode bus without fiber-optic link monitoring, so that it does not cause a broken fiber-optic cable signal (see section 4.2.3.4). Remember that the optical channels that are not connected must be protected against external light and pollution by protective caps.
3.1.2 Bus topology without fiber-optic link monitoring
Use this mode when you connect a PROFIBUS OLM with a different fiber-optic component according to the PROFIBUS guideline (optical/electrical converter), which does not send a frame echo and does not expect or tolerate a frame echo.
Monitoring mechanisms:
Send echo: no
Monitor echo: no
Suppress echo: no
Monitor: no
Segmentation: no
In this mode, there is no monitoring of the individual fiber-optic links.
Network Topologies
3.2 Star Topology
SIMATIC NET PROFIBUS, Optical Link Module
10 Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
3.2 Star Topology
Figure 3-2 Network structure with an optical star topology
Several modules are grouped together to form an active PROFIBUS star coupler. Further modules are connected to this via two-core fiber-optic cables. The modules of the star coupler are interconnected via the electrical channel (electrical star segment). All OLM types for different fiber-optic cables (plastic, PCF, glass) can be combined via the electrical star segment.
Please note the following:
¾ CH1 must be set to “Monitor off (S0 = 1) on all OLMs connected to the
electrical star segment. This disables segmentation function of the RS-485 channel of this OLM to achieve high availability of the electrical star.
¾ Make sure that the electrical star segment is carefully wired. Keep its span as
small as possible to avoid interference in the electrical star segment that can spread to the whole network. You can achieve this by positioning the OLMs directly next to each other on a DIN rail.
¾ Switch on the terminating resistors (see section 5.3) in the bus connectors at the
two ends of the electrical star segments.
¾ If possible do not connect any bus nodes to the electrical star segment.
To set up an active PROFIBUS star coupler, modules with one or two optical channels can be used. To connect a DTE or an RS-485 bus segment to an active star coupler, modules with one optical channel are adequate.
FOC
RS-485
Ch 1
Ch 2
SE
OLM/P11
Ch 1
Ch 2SECh 3
SE
OLM/G12
Ch 1
Ch 2
SE
OLM/G11-1300
Ch 1
Ch 2
SE
OLM/P11
Ch 1
OLM/P11
Ch 2
S
E
Ch 1
OLM/G11
Ch 2
S
E
Ch 1
OLM/G11-1300
Ch 2
S
E
Ch 1
OLM/P11
Ch 2
S
E
Ch 1
OLM/G11
Ch 2
S
E
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
Electrical star segment
Network Topologies
3.2 Star Topology
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
11
When the monitoring on the optical channels is active, the fiber-optic links are monitored by the connected OLMs.
Note:
Unused optical channels you intend to use later to expand the network cause a broken fiber-optic cable signal if the monitoring is active. You can avoid this error message by setting unused channels to the mode bus without fiber-optic link monitoring”. Remember that the optical channels that are not connected must be protected against external light and pollution by protective caps.
Network Topologies
3.3 Ring Topology
SIMATIC NET PROFIBUS, Optical Link Module
12 Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
3.3 Ring Topology
Figure 3-3 Network structure with a redundant optical ring topology
This network topology is a special form of the bus topology. “Closing the optical bus achieves high operational reliability in the network. A redundant optical ring can only be implemented using modules with two optical channels.
Monitoring mechanisms:
Send echo: yes
Monitor echo: yes
Suppress echo: yes
Segmentation: yes
The interruption of one or both fiber-optic cables between the modules is detected by the OLM and the ring becomes an optical bus.
If one module fails, only the DTEs connected to this module or the RS-485 segment are disconnected from the ring. The rest of the network itself stays functional as a bus. The problem is indicated by the LEDs of the two OLMs connected to the disrupted fiber-optic link and by the signaling contacts of these OLMs. The segmentation is canceled automatically as soon as both modules recognize that the segmented fieldbus (sub)network is no longer disrupted based on test frames that they send out automatically. The bus then closes again to form a ring.
Ch 1
Ch 2
SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
Ch 1
Ch 2 SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
Ch 1
Ch 2
SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
DTE/
bus segment
FOC
RS-485
Ch 1
Ch 2
SE
Ch 3
SE
OLM/P12
OLM/G12(-1300)
Network Topologies
3.3 Ring Topology
SIMATIC NET PROFIBUS, Optical Link Module Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
13
Please note the following:
For correct operation, the following conditions must be met:
¾ Only use this mode, if you only connect PROFIBUS OLMs with at least version
V3 with each other. Both optical channels must be set to the redundant optical ring” mode on all PROFIBUS OLMs. All modules within a ring must be connected to each other over fiber-optic cables. There must be no RS-485 bus cable within the ring.
¾ The MIN TSDR parameter described in the PROFIBUS standard EN 50170 /2/
must be set to a value 11 on all DTEs. This is usually the case but should be checked if permanent communication problems occur.
¾ Choose bus node addresses as low as possible when configuring your network,
to reduce master timeouts that may occur due to disruptions.
¾ If there is a failover (for example due to a cable break), there is failover time
during which correct data transmission is not possible. To ensure bumpless bridging for the application, it is advisable to set the frame retry number on the PROFIBUS master to at least 3. To ensure a bumpless return from the optical bus to the optical ring once a problem has been eliminated, there must be no frame on the network at this time. This status occurs when the master sends a GAP query to an address lower than HSA. The master tries to address the device cyclically and waits for a reply at the longest until the configured slot time has elapsed (GAP query). The OLM recognizes this status and closes the optical bus to form an optical ring in the middle of this query sequence. This results in the following two important configuration requirements for the redundant optical ring:
The value of the parameter HSA (Highest Station Address) must be set on
all DTEs so that there is at least one address between bus address 0 and the value HSA that is not occupied by a bus node, in other words there is at least one address gap. You can create this address gap simply by setting the HSA value one higher than the highest existing bus node address.
Notice
If this requirement is not or no longer met, the optical bus will no longer close to form a redundant optical ring after segmentation. In this case the error message
(LED and signaling contact) of the two
affected OLMs will not be cleared after eliminating the problem.
The slot time must be set to about twice the value compared with a
redundant network. See section 5.10 for further information. You will find information on changing the setting in the documentation supplied with your DTE or with the configuration software.
Notice
No glass fiber-optic cable may be connected to an OLM that uses plastic fiber-optic cable and vice versa.
Loading...
+ 42 hidden pages